1352 Airport Road Kalispell, MT 59901 Phone: (406) 257-3013
TEST AND BALANCE REPORT
DATE
Tuesday, August 17, 2021
PROJECT
Fort Harrison Satellite Storage Rooms Balance Report
3687 Veterans Dr.
Fort Harrison, Montana
Table of Contents
PROJECT:
LOCATION:
VA PRESSURE ROOMS 8-17-21
DATE:
CONTACT:
AUTHOR:
8/21/2021 Jeremy Kiehn Jeremy Kiehn
Table Of Contents 1 NEBB Certification.pdf 2 Instrument Calibration Report.pdf 3 Legend.pdf 4 ACH / Pressurization
4.1 ACH / 363 D
4.2 ACH / 127-154 Cath Lab
4.3 ACH / 223 Ante Room
4.4 ACH / 363 E
4.5 ACH / 363A
4.6 ACH / 83 Gold Clinic
4.7 ACH / 94 Gold Clinic
4.8 ACH / Dnetal Storage 102S
4.9 ACH / EMERGENCY A87
4.10 ACH / Endoscope Cleaning 206
4.11 ACH / Gross Decontamination 221
4.12 ACH / Sterilie Processing 222
Precision Air and Water Balance
DATE:
1352 Airport Road Kalispell, MT 59901 Phone: (406) 257-3013 Fax: (406) 890-2848
NEBB TAB COMPANY: Precision Air & Water Balance
TAB SUPERVISOR: Jeremy Kiehn
SIGNATURE: 8/17/2021
PROJECT: Fort Harrison Satellite Storage Rooms Balance Report
ADDRESS: 3687 Veterans Dr. Fort Harrison, Montana
THE DATA PRESENTED IN THIS REPORT IS A SUMMARY OF SYSTEM PERFORMANCE
AND WAS OBTAINED IN ACCORDANCE WITH NEBB STANDARDS AND PROCEDURES.
ANY VARIANCES FROM DESIGN THAT EXCEEDS NEBB TOLERANCES ARE NOTED.
DATE: 8/17/2021
MODEL SERIAL
ADM-870 C M12307
S-PVF-1 1300267
Evergreen Telemetry Air Data Multimeter 3/23/2021
INSTRUMENT CALIBRATION REPORT
MANUFACTURER Purpose Last Calibrated
Shortridge Air Data Multimeter 3/29/2021
PROJECT:
TEST DATE: 8/17/2021
# NUMBER
W WEST
WT WATTS
S.P. STATIC PRESSURE
T.S.P. TOTAL STATIC PRESSURE
SER.FCTR SERVICE FACTOR
SHV SHEAVE
S SOUTH
S.A. SUPPLY AIR
RM ROOM
RPM ROTATIONS PER MINUTE
O.A. OUTSIDE AIR
O.D. OUTSIDE DIAMETER
N/A NOT APPLICABLE
NMP. NAMEPLATE
MKE MAKE
N NORTH
MAU MAKE UP AIR UNIT
MECH. MECHANICAL
IN INCHES
INCH W.C. INCHES WATER COLUMN
FUR FURNACE
HP HORSE POWER
EF EXHAUST FAN
E.S.P. EXTERNAL STATIC PRESSURE
DIA DIAMETER
DIS DISTANCE
E EAST
C.S. CIRCUIT SETTER
D.D. DIRECT DRIVE
C CENTER
CFM CUBIC FEET PER MINUTE
AHU AIR HANDLER UNIT
ACT. ACTUAL
LEGEND
Fort Harrison Satellite Storage Rooms Balance Report
SYMBOL DEFINITION
ACH / Pressurization
PROJECT:
LOCATION:
VA PRESSURE ROOMS 8-17-21
DATE:
CONTACT:
AUTHOR:
8/21/2021 Jeremy Kiehn Jeremy Kiehn
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / 363 D
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 7.00 ft Room Width 7.00 ft Room Height 8.00 ft Room Size 392 Ft3
Air Data Actual ACH 8 /hr Supply Airflow 55 CFM Exhaust/Return Airflow 25 CFM
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / 127-154 Cath Lab
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 26.00 ft Room Width 26.50 ft Room Height 9.00 ft Room Size 6201 Ft3
Air Data Actual ACH 10 /hr Supply Airflow 993 CFM Exhaust/Return Airflow 985 CFM
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / 223 Ante Room
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 18.00 ft Room Width 5.00 ft Room Height 8.00 ft Room Size 720 Ft3
Air Data Actual ACH 0 /hr Supply Airflow 0 CFM Exhaust/Return Airflow 158 CFM
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / 363 E
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 21.00 ft Room Width 15.45 ft Room Height 8.00 ft Room Size 2596 Ft3
Air Data Actual ACH 14 /hr Supply Airflow 621 CFM Exhaust/Return Airflow 217 CFM
PROJECT:
LOCATION:
VA PRESSURE ROOMS 8-17-21
DATE:
CONTACT:
AUTHOR:
8/21/2021 Jeremy Kiehn Jeremy Kiehn
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / 363A
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 21.00 ft Room Width 16.35 ft Room Height 8.00 ft Room Size 2747 Ft3
Air Data Actual ACH 10 /hr Supply Airflow 441 CFM Exhaust/Return Airflow 355 CFM
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / 83 Gold Clinic
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 18.00 ft Room Width 11.00 ft Room Height 8.00 ft Room Size 1584 Ft3
Air Data Actual ACH 4 /hr Supply Airflow 110 CFM Exhaust/Return Airflow 100 CFM
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / 94 Gold Clinic
Unit Data Type of Area Storage Room Required Pressure Negative Room Length 14.00 ft Room Width 6.00 ft Room Height 8.00 ft Room Size 672 Ft3
Air Data Actual ACH 11 /hr Supply Airflow 81 CFM Exhaust/Return Airflow 128 CFM
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / Dnetal Storage 102S
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 13.00 ft Room Width 7.20 ft Room Height 8.00 ft Room Size 749 Ft3
Air Data Actual ACH 5 /hr Supply Airflow 61 CFM Exhaust/Return Airflow 32 CFM
PROJECT:
LOCATION:
VA PRESSURE ROOMS 8-17-21
DATE:
CONTACT:
AUTHOR:
8/21/2021 Jeremy Kiehn Jeremy Kiehn
Tested By: Jeremy Kiehn Date: 8/17/2021
SYSTEM/UNIT: ACH / EMERGENCY A87
Unit Data Type of Area Storage Room Required Pressure Negative Room Length 12.00 ft Room Width 7.00 ft Room Height 8.00 ft Room Size 672 Ft3
Air Data Actual ACH 6 /hr Supply Airflow 30 CFM Exhaust/Return Airflow 67 CFM
SYSTEM/UNIT: ACH / Endoscope Cleaning 206
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 10.00 ft Room Width 11.50 ft Room Height 8.00 ft Room Size 920 Ft3
Air Data Actual ACH 14 /hr Supply Airflow 207 CFM Exhaust/Return Airflow 45 CFM
SYSTEM/UNIT: ACH / Gross Decontamination 221
Unit Data Type of Area Storage Room Required Pressure Negative Room Length 20.00 ft Room Width 11.90 ft Room Height 8.00 ft Room Size 1904 Ft3
Air Data Actual ACH 10 /hr Supply Airflow 0 CFM Exhaust/Return Airflow 333 CFM
SYSTEM/UNIT: ACH / Sterilie Processing 222
Unit Data Type of Area Storage Room Required Pressure Positive Room Length 30.00 ft Room Width 33.40 ft Room Height 8.00 ft Room Size 8016 Ft3
Air Data Actual ACH 21 /hr Supply Airflow 2744 CFM Exhaust/Return Airflow 701 CFM
| Cover Page.pdf |
| Table of Contents |
| NEBB Certification.pdf |
| Instrument Calibration Report.pdf |
| Legend.pdf |
| ACH / Pressurization |
| ACH / 363 D |
| ACH / 127-154 Cath Lab |
| ACH / 223 Ante Room |
| ACH / 363 E |
| ACH / 363A |
| ACH / 83 Gold Clinic |
| ACH / 94 Gold Clinic |
| ACH / Dnetal Storage 102S |
| ACH / EMERGENCY A87 |
| ACH / Endoscope Cleaning 206 |
| ACH / Gross Decontamination 221 |
| ACH / Sterilie Processing 222 |
File details come from the government source that posted it. Updated .