DEPARTMENT OF VETERANS AFFAIRS

3687 VETERANS DRIVE

FORT HARRISON, MT 59636

HELENA

A-101

A-102

A-103

A-104

A-105

A-106

M-001

M-002

M-003

M-004

M-005

M-101

M-102

M-103

M-104

M-105

M-106

BASEMENT PLAN

FIRST FLOOR PLAN

SECOND FLOOR PLAN

THIRD FLOOR PLAN

FOURTH FLOOR PLAN

PENTHOUSE PLAN

MECHANICAL LEGEND, NOTES & SCHEDULES

MECHANICAL LEGEND, NOTES & SCHEDULES

MECHANICAL LEGEND, NOTES & SCHEDULES

MECHANICAL LEGEND, NOTES & SCHEDULES

MECHANICAL LEGEND, NOTES & SCHEDULES

BASEMENT HVAC PLAN

FIRST FLOOR HVAC PLAN

SECOND FLOOR HVAC PLAN

THIRD FLOOR HVAC PLAN

FOURTH FLOOR HVAC PLAN

PENTHOUSE HVAC PLAN

GI001 COVER SHEET

A-101

M-001

M-002

M-101

ARCHITECTURAL PLAN FOR FIRST, SECOND AND THIRD FLOOR

MECHANICAL LEGEND, NOTES & SCHEDULES

MECHANICAL LEGEND, NOTES & SCHEDULES

HVAC PLAN FOR FIRST, SECOND AND THIRD FLOOR

Airside Equipment

154 154 AHUX-1

154-AHU-08-BSNS

OFF

154 Roof

Air Handling

Unit

Estimate

Constant Volume

Supply fan with reheat zones.

Business Offices.

1st Flr:(located under 154A graphic). 4 Zones

Serves Business

Offices.

McQuay

RDS708B

B

38B00525

N/A

4620 - 4200

- x / N/A

N/A FLA = 14.8 No

15,000

MBH

N/A n/a n/a Yes JCI A G G G A

L, E

Built appx. 1995. Average condition. Old but well-maintained. Upgraded

DDC dampers, valves.

AH-2 (AC-2) and

RE-2

154-AHU-15-2ND

Penthouse 1

Air Handling

Unit

Estimate

DDC shows 100% outside air steam preheat, chilled water cooling, steam reheat, humidifier, constant volume AHU with coil bypass.

2nd Flr: Old PT and

Surgery. 1st Flr:

Dental

N/A N/A N/A N/A

6500 - x -

5060 / 6228

"N/A /

TSP =

2.52

N/A / ESP

= 1.372"

"SF: FLA =

20.2 / Amps

= 9.7

RF = 1.5

HP"

No N/A n/a n/a n/a Yes JCI P A G A A

M, R, E, C

"(2) BX-90 good. Coils clean. Dirty filters.M = steam traps have failed, dirty filters

R, E = OSA ducting is in need of repair, OSA damper is not working, condensate leaking onto floor.

C = OSA damper and supply air steam valves are still pnuematic"

154 AHU AC-1

"154-AHU-02-154

Room 146

Air Handling

Unit

Estimate

Constant Volume

AHU (supply and return fans) with

VAVs. 2 preheat valves (steam), cooling water coil, humidity control(disconnecte d), Economizer control. Controls updated in 2010.

1st Flr: Outpatient

Mental Health, North, South and

East, x-ray, offices.

2nd Flr: Offices and

SPD. 1st Flr East

(TEC-8,17, 25, 24,

23, 21, 19, 18, 17, 16, 15, 14, 13, 12, 11), Mental Health

(TEC-16, 27, 28,

29, 30), 1st Flr

South (TEC-4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15), Dental

(TEC-18, 19, 20,

21, 22), Pharm

(TEC- 24, 25, 26),

2nd Flr PT (TEC-9, 10, 11), 2nd Flr

LAB/Offices

(TEC-8, 12, 13, 14,

15, 16, 17, 18, 19, 20, 21, 33, 45, 65), 2nd Flr South

(TEC-9, 10, 11, 16,

17, 18, 8, 45, 33).

N/A

BCHC090

E1

(original, couldn't find any field information

N/A N/A

15870 - x -

3735 /

20000 - 335

- 2695

"SF: 'N/A

/ N/A

RF: 'N/A /

TSP =

0.84"""

"SF: 69.5

Amps / 63.9

Amps

RF: 3.4

Amps / N/A"

No N/A N/A Disconnected 65 Yes

JCI- Constant

Volume AHU

(supply and return fans) with

VAVs.

A A G G A

E, M "Older unit (estimate 1990) in fair condition. New DDC damper and valve actuators in 2010.

E = Lacks VFD on supply fan.

M = Insulation poor in places."

154 ACRE-1

154-RF-01-AHU-02

Room 146 Return Fan

Estimate

Constant Volume return fan.

154-AHU-02-154 N/A N/A N/A N/A

15870 - x -

3735 /

20000 - 335

- 2695

RF: 'N/A /

TSP =

0.84"""

"SF: 69.5

Amps / 63.9

Amps

RF: 3.4

Amps / N/A"

No n/a n/a n/a n/a Yes

JCI- Constant

Volume AHU

(supply and return fans) with

VAVs.

A A G G A

E, M "Older unit (estimate 1990) in fair condition. New DDC damper actuators in 2010.

E = Lacks VFD on fan.

M = Insulation poor in places."

154 RE-1 154-RF-02-AHU-02 Room 146 Return Fan

Estimate

Constant Volume return fan.

154-AHU-02-154 N/A N/A N/A N/A

15870 - x -

3735 /

20000 - 335

- 2695

RF: 'N/A /

TSP =

0.84"""

"SF: 69.5

Amps / 63.9

Amps

RF: 3.4

Amps / N/A"

No n/a n/a n/a n/a Yes

JCI- Constant

Volume AHU

(supply and return fans) with

VAVs.

A A G G A

E, M "Older unit (estimate 1990) in fair condition. New DDC damper actuators in 2010.

E = Lacks VFD on fan.

M = Insulation poor in places."

154 AHU S1 154-AHU-01-154

"SF: B100

Air Handling

Unit

Estimate

Constant Volume

AHU (supply and return fans) with

VAVs. 2 preheat valves (steam), cooling water coil, humidity control, Economizer control.

Controls redone in

2010.

1st Flr: North, Rec

Hall, Canteen. 2nd

Flr: Offices (old PT).

1st Flr North

(TEC-4, 5, 6, 7, 8),

2nd Flr PT (TEC-4, 5, 6, 7, 8, 65?, 22, 35, 24, 25, 26)

N/A

BCHC036

E1

(original, couldn't find any field information

N/A N/A

"SF: 20540 /

12455

RF: 6305 /

5330"

"SF: 'N/A

/ TSP =

2.89""

RF: N/A /

TSP =

0.81"""

"SF: 65.1

Amps / 29.9

Amps

RF: 5.1

Amps / N/A"

No N/A N/A Yes 16 Yes

JCI- Constant

Volume AHU

(supply and return fans) with

VAVs.

P A G G P

M, L, E "M = Insulation damaged.

L, E = Old (estimate built in

1990) and nearing or past expected life. Updated

DDC damper and valve actuators in 2010. Lacks

VFD."

154 RE-1 154-RF-01-AHU01

RF: 146"

Return Fan

Estimate

Constant Volume return fan.

154-AHU-01-154

N/A

BCHC036

E1

(original, couldn't find any field information

N/A N/A

"SF: 20540 /

12455

RF: 6305 /

5330"

"SF: 'N/A

/ TSP =

2.89""

RF: N/A /

TSP =

0.81"""

"SF: 65.1

Amps / 29.9

Amps

RF: 5.1

Amps / N/A"

No n/a n/a n/a n/a Yes

JCI- Constant

Volume AHU

(supply and return fans) with

VAVs.

P A G G P

M, L, E "M = Insulation damaged.

L, E = Old (estimate built in

1990) and nearing or past expected life. Updated

DDC damper actuators in

2010. Lacks VFD."

154 AHU S1A 154-AHU-12-4TH

Penthouse

#3

Air Handling

Unit

Estimate

100% outside air unit. AHU equipped with return and relief dampers but they are closed. Not sure if dampers broken or control changed to 100%

OA strategy. Steam heat, chilled water cooling, humidification, economizer dampers (not sure if used) heat recovery coil.

4th Flr. 4th West

(VAV 22-14, 62-14,

23-14, 11-14, 09-14, 10-14, 12-14, 16-14, 70-14, 33-14?, 32-14?, 24-14, 24-14, 30-13, 41-13) 4th North??

(VAV 58-14, 57-14,

56-14, 55-14, 54-14, 53-14, 52-14, 61-14, 60-14, 59-14) = 25

Total VAVs

Carrier 39EF18 0682 N/A N/A N/A N/A Yes N/A N/A Yes 25 Yes

JCI- EEI told equipment being redone as part of current project 436-110.

P A G G A

L, M, C EEI told equipment being redone as part of current project, 436-110.

"L = Old- nearing end of useful life.

M = Poor pipe and unit insulation.

C = Humidifier valve still pnuematic.

SYSTEM CONDITION ANALYSIS

154 AHU S1A 154-AHU-12-4TH

Penthouse

#3

Air Handling

Unit

Estimate

100% outside air unit. AHU equipped with return and relief dampers but they are closed. Not sure if dampers broken or control changed to 100%

OA strategy. Steam heat, chilled water cooling, humidification, economizer dampers (not sure if used) heat recovery coil.

4th Flr. 4th West

(VAV 22-14, 62-14,

23-14, 11-14, 09-14, 10-14, 12-14, 16-14, 70-14, 33-14?, 32-14?, 24-14, 24-14, 30-13, 41-13) 4th North??

(VAV 58-14, 57-14,

56-14, 55-14, 54-14, 53-14, 52-14, 61-14, 60-14, 59-14) = 25

Total VAVs

Carrier 39EF18 0682 N/A N/A N/A N/A Yes N/A N/A Yes 25 Yes

JCI- EEI told equipment being redone as part of current project 436-110.

P A G G A

L, M, C EEI told equipment being redone as part of current project, 436-110.

"L = Old- nearing end of useful life.

M = Poor pipe and unit insulation.

C = Humidifier valve still pnuematic.

154 AHU S2 154-AHU-14-3RD

Penthouse 1

Air Handling

Unit

Estimate

Supply/return fan with VFD and controlling to static pressure. Steam preheat, chilled water cooling, bypass dampers for coils, economizer dampers.

3rd Flr. Supply fan replaced in 2002.

3rd North (VAV-12, 14, 18, 19, 363) 3rd

Flr East(VAV

60-12, 61-12, 7-12, 6-12, 5-12, 46-11, 47-11, 44-11, 45-11, 48-11, 43-11, 42-11, 41-11, 50-11, 51-11, 49-11, 59-12, 10-12, 9-12, 8-12) 3rd Flr South

(VAV 30-11, 31-11,

32-11, 34-11, 34-11, 35-11, 35-11, 36-11, 37-11, 38-11, 57-11, 39-11), 3rd

Flr West (VAV

23-12, 53-12, 21-12, 20-12, 19-12, 52-12, 11-12, 62-11, 30-11, 39-11, 29-11, 28-11, 55-11, 27-11, 25-11, 26-11, 63-11, 24-12 = 55

Total VAVs, 64 shown on schedule).

N/A N/A N/A N/A 1800 / N/A N/A

SF: 7.5 HP

/ 'N/A

Yes N/A N/A No 55 Yes

JCI- Variable

Volume AHU

(supply and return fans) with

VAVs.

P P G G A

"L, M

EEI told equipment being redone as part of current project, 436-110."

" L = Old- nearing end of useful life.

M = Pipe insulation poor.(2)

BX-90 belt in good condition. New DDC valves, dampers, and VFD.

Insulation is poor. Could not access to determine filter and coil condition. "

RF-1 (AHU S2)

154-RF-01-AHU-14-

3RD

Penthouse 2

Return Fan

Estimate

Return fan with

VFD associated with AHU-14-3RD.

154-AHU-14-3RD N/A N/A N/A N/A N/A N/A

RF: 5 Hp

Yes N/A N/A n/a n/a Yes

JCI- Variable

Volume AHU

(supply and return fans) with

VAVs.

A G G G

Average condition. (2)

BX-53 in good condition.

Newer VFD.

154 AHU S2A 154-AHU-13-4TH

Penthouse

#3

Air Handling

Unit

Variable volume

VAV AHU, steam preheat, chilled water cooling, economizer dampers, humidification.

4th Flr. 4th East

(VAV 60-12, 61-12,

7-12, 6-12, 5-12, 46-11, 47-11, 44-11, 45-11, 48-11, 43-11, 42-11, 41-11?, 50-11, 51-11, 49-11, 59-12, 10-12, 9-12, 8-12)

4th South (VAV

6-14, 7-14, 8-14, 72-14, 4-14, 5-14, 96-14, 13-14, 14-14, 15-14) 4th

West (VAV 66-13, 67-13, 65-13, 64-13, 44-13, 43-13, 42-13, 68-13, 69-13, 45-13, 63-13) = 41

Total VAVs

Trane

CC0B170

E

U848401?8 N/A N/A N/A

"SF: 10 HP,

29 Amps

RF: 3 HP,

11 Amps"

Yes N/A N/A Yes 41 Yes

JCI- EEI told equipment being redone as part of current project 436-110.

P A G G A

"L, M, C

EEI told equipment being redone as part of current project, 436-110."

"L = Old- nearing end of useful life.

M = Poor pipe and unit insulation.

C = Humidifier valve still pnuematic.

154 AHU S5 154-AHU-01-ELEC

1st Floor

Electrical

Room

Air Handling

Unit

Estimate

Unit has supply fan and mixing dampers. Relief is via EF-2 in this room.

Bldg 154 1st Flr:

Electrical Sub

Station

Trane 10 U53140 N/A 4000 / 3090 N/A N/A No n/a n/a n/a n/a Yes JCI A A A

L, E "E = Lacks VFD.

L = Older unit (estimate

1990). Fair condition. (4)

BX-53 belt is good."

AHU-1 (Mental

Outpatient)

154-AHU-07-OPMH 115-30

Air Handling

Unit

Variable Volume

AHU (supply and return fan), VFD controls to duct static, hot water coil, DX coil with condensing unit, economizer control, night setback and morning warm-up, unoccupied controls. Controls upgrade in 2011.

Mental health

Outpatient 1st Flr

VAV-1, 2, 3, 4, 5, 6,

7, 8, 9, 10, 11.

Trane

CSAA012

UAB00

K10K98755 N/A

6815 - 6815

- x / N/A

"TSP =

3.115"" /

N/A

ESP =

1.5"" /

N/A"

7.5 HP Yes

156.61

MBH

210.6

MBH and

15 GPM

No 11 Yes JCI G G G G G

R, E "R, E = duct pressure sensor controlling unit speed isn't working properly.

Built in 2010. Good belts.

Clean filters."

AHU-1 (Dental)

"154-AHU-09-SADI

E

Penthouse

203-154

Air Handling

Unit

Variable Volume

AHU (supply and return fan), new

VFD's control to duct static, hot water coil, dx coil with condensing unit, economizer control. Controls upgrade in 2011 with some night setback control.

SADIE non operating 2nd flr and 1st flr VAV

(Dental and

Cardio). V-1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20.

Dunham-B ush

"SF:

BH021AS

6630401

"SF:

66304-01A

96C

N/A

8975 - x -

6500 / 8320

- x - 5960

"N/A /

TSP =

2.6""

N/A / ESP

= 1.79""

"SF: 43.4

Amps / 30.1

Amps

EF: 7.5 HP,

21.3 Amps

/ N/A"

Yes

315 MBH

/ 68 GPM

718 MBH

/ 36 GPM

No 20 Yes JCI G G G G A

C

"C = Steam valve is pnuematic.

Average condition. Built

2002, but new CHW valves, ductwork, VFD. Steam valve is pnuematic. (2)

BX-50 in good condition.

Clean filters & coils."

EAF-1 (Dental)

154-EF-01-AHU09S

ADIE

Penthouse

203-154

Exhaust Fan 2002

Variable Volume return fan. Newer

VFD.

"154-AHU-09-SADI

E

" Dunham-B ush

EF:

DH017AS

6630403"

EF:

66304-03A

96C"

N/A

8975 - x -

6500 / 8320

- x - 5960

"N/A /

TSP =

2.6""

N/A / ESP

= 1.79""

"SF: 43.4

Amps / 30.1

Amps

EF: 7.5 HP,

21.3 Amps

/ N/A"

Yes n/a n/a n/a n/a Yes JCI G G G G A

Built 2002, with 2010 VFD.

Average condition.

AHU-1 / RTU-1

Pharmacy

154-AHU-06-PHAR

M

Pharmacy

Roof

Air Handling

Unit

Constant Volume

RTU with VFD used solely to set constant speed.

Pharmacy Clean

Room

Trane

TSCB003

U0E00000

000AC00A

225.2

K07M4771

0A

N/A 940 / 990

N/A / TSP

= 1.91"

2HP, 7.8

Amps / 5.1

Amps

Yes N/A N/A No n/a Yes JCI A A A G A

E, M

"E, M = HW coil and the

CHW coil were both observed to be significantly matted with fibers. Flow is restricted.

Built 2007. Average condition. DDC dampers, valves. (4) 4L420 belt in poor condition. "

AHU-1 / AH-1

Laboratory

154-AHU-11-LAB

Lab 1st Floor

Mech

Air Handling

Unit

Constant Volume

AHU (supply and exhaust fan), hot water coil, preheat coil, dx coil with condensing unit and

4 stages of cooling, humidity control, 100% OSA.

Lab (Electro Stand

Alone) VAV1, 2, 3, 4, 5, 6, 7, 8, 9, 10.

Trane

MCCB035

UA0C0UA

K09H27200 N/A

15000 - x -

1500 /

ESP =

1.38"

25 HP, 78.2

Amps

Yes

537400

BTUH

1016700

BTUH

Yes 10 Yes JCI G G G G G

Built in 2009. Good belts.

Clean filters.

154 AHU-2

"154-AHU-10-SADI

E

203-154

Air Handling

Unit

Variable Volume

AHU (supply and return fan), new

VFD's control to duct static, hot water coil, dx coil with condensing unit, economizer control. Controls upgrade in 2011 with some night setback control.

SADIE 2nd Flr-

Surgical

Dunham-B ush

"SF:

HCS12MF

6630402

"SF:

66304-02A

96C

N/A

3120 - x -

2790 / N/A

N/A / N/A

"SF: 5 HP /

N/A

RF: 2 HP

N/A"

Yes

113.5

MBH / 21

GPM

274 MBH

/ 17 GPM

No n/a Yes JCI A A A

C "

"C = HW & CHW valves are pnuematic.

BAS control. Variable volume. Average condition.

Built appx. 2002. Newer

VFD, DDC dampers, ductwork. "

154 LCEF-1

154-LCEF-01-AHU1

0SADIE

203-154 Exhaust Fan 2002

Variable Volume exhaust fan.

Controls upgrade in

2011.

"154-AHU-10-SADI

E

Dunham-B ush

EF:

HCS08MF

6630404

EF:

66304-04A

96D

N/A

3120 - x -

2790 / N/A

N/A / N/A

"SF: 5 HP /

N/A

RF: 2 HP

N/A"

Yes n/a n/a n/a n/a Yes JCI A A A

Average condition. Built appx. 2002. Newer VFD, DDC dampers, ductwork.

2011. N/A"

154 AHU-3

154-AHU-03-MORG

UE

154 Crawl

Air Handling

Unit

Estimate

Constant volume

AHU, steam heat with face and bypass dampers, chilled water cooling, economizer dampers.

2nd Flr Morgue

Trane 3 269925 N/A 1360 / 905

N/A / ESP

= 0.39

N/A No N/A N/A No n/a Yes JCI A A G G A

E "E = Lacks VFD.

Estimate 1999 construction.

Average condition. New

DDC damper and valve actuators in 2010. (4)

4L440 belt is good."

154 AHU-4

154-AHU-04-2NDS

OUTH

154 Crawl

Air Handling

Unit

Estimate

Constant volume

AHU, steam heat with face and bypass dampers, chilled water cooling, economizer dampers.

2nd Flr South. 2nd

South (TEC-4, 5, 6, Trane 3 269926 N/A 900 / 470

N/A / ESP

= 0.23

N/A / 11.5 No N/A N/A No n/a Yes JCI A A G G A

E, R "E = Lacks VFD.

R = Chilled water pipes lack insulation.

Estimate 1999 construction.

Fair condition. New DDC damper and valve actuators in 2010. (4) BX-38 belt is good."

CU-1 (AHU-1 /

AH-1)

154-CUAC-04-AHU1

Ground outside

AHU-1 / AH-1

Condensing

Unit

Serves

154-AHU-11-LAB

Serves

154-AHU-11-LAB

Trane

RAUCC50

EB2030

C09H0215

N/A n/a n/a

1356 LRA

total

No n/a n/a n/a n/a Yes

Unitary

G G G

Built in 2010. Clean coils.

Well-maintained.

CU-1 (Mental

Outpatient)

154-CUAC-02-AHU

Ground West

Wing

Condensing

Unit

Serves

154-AHU-07-OPMH

(Mental Outpatient)

Serves

154-AHU-07-OPMH

(Mental Outpatient)

Trane

TTA180E3

00AA

10425J0KT

A

N/A n/a n/a

328 LRA

total

No n/a n/a n/a n/a Yes

Unitary

G G G

Built in 2010. Clean coils.

Well-maintained.

CU- (MZ-2)

154-CUAC-01-AHU

Ground

South by

Boiler Plant

Condensing

Unit

Serves

154-AHU-05-PHAR

M (MZ-2)

Serves

154-AHU-05-PHAR

M (MZ-2)

Aaon

CCB0142

D2

201011-CH

CC02469

N/A n/a n/a

46 RLA

total

No n/a n/a n/a n/a Yes

Unitary

G G G

Built in 2011. Clean coils.

Well-maintained.

154 Data Aire AHU

154-ACUC-01-DAT

A

Basement

Air Handling

Unit

Estimate

Constant Volume

100% return air unit.

Basement

Communications

Room

Data Aire N/A N/A N/A

12000 - x -x / N/A

ESP =

0.75

10 HP No 30 Tons n/a n/a n/a Yes

Unitary

G G G G G

According to VA Staff, the

Data Aire system fails frequently, but was operating per design at time of inspection. Belts good. Filters clean.

Data Aire Dry

Cooler

154-CHLR-03-DAT

ARM

154 Roof

Dry Cooler

Estimate

Constant Volume system

Basement

Communications

Room

Data Aire N/A N/A N/A N/A N/A N/A No 52 Tons n/a n/a n/a Yes

Unitary

G G

According to VA Staff, the

Data Aire system fails frequently, but was operating per design at time of inspection.

154 EF-27 154-EFT-27

Penthouse 1

Exhaust Fan

Estimate

Constant Volume exhaust.

Bldg 154 Toilets Trane B131 256441

N/A N/A N/A

1.5 Hp

No n/a n/a n/a n/a Yes

Unitary

P A A

L,E

Estimate 25 yo.(2) BX-70 belts good condition.

Newer motor. Old unit-replace.

154 EF-30 154-EF-30

Penthouse 1

Exhaust Fan

Estimate

Constant Volume exhaust.

Bldg 154 penthouse

Trane B131 256442

N/A N/A N/A

1.5 Hp

No n/a n/a n/a n/a Yes

Unitary

P P P

L,E,R

Disabled, and appears to be abandoned in place.

154 EF-1 154-EF-01-1ST 154 Roof Exhaust Fan

Estimate

Constant Volume exhaust.

Original Bldg 154

1st Floor

Twin City

Fan and

Blower

N/A

04-190575-

1-1

N/A N/A N/A

10 Hp

No n/a n/a n/a n/a Yes

Unitary

A A A

Older Twin City unit in average condition. Estimate

10 years of service life remaining.

154 EF-2 154-EF-02-1ST 154 Roof Exhaust Fan

Estimate

Constant Volume exhaust.

Original Bldg 154

1st Floor

Twin City

Fan and

Blower

N/A

04-190575-

1-2

N/A N/A N/A

10 Hp

No n/a n/a n/a n/a Yes

Unitary

A A A

Older Twin City unit in average condition. Estimate

10 years of service life remaining.

ERU- Lab &

Laundry

154-ERU-01-LAB

Roof- West

Wing

Energy

Recovery Unit

Lab & Laundry Serves Lab &

Laundry areas in

West Wing

Addition.

Innovert ERU-0U-P

L-15000-2

2090011

N/A N/A N/A

15 Hp

No n/a n/a n/a n/a Yes JCI G G G G G

Newer. Good condition.

Belts good. Filters clean.

154 ILF-1 154-EF-02-SADIE

Penthouse

203-154

Exhaust Fan

Estimate

Constant Volume exhaust.

SADIE exhaust Carnes

VIBK12S1

C1NL20S

_G

540266 N/A N/A / N/A n/a

1.5 HP, 5.3

Amps

No n/a n/a n/a n/a Yes JCI A A A

L

BAS control. Average condition- old. Newer motor. 1.5 Hp. (2) 4L390

MZ-2 (Mark in field is AHU-1)

154-AHU-05-PHAR

M

011-150

Air Handling

Unit, Multi-Zone

Constant Volume mixed air unit with hot and cold decks.

Hot deck served by steam. Cold deck served by DX Unit.

Controls upgrade in

2010.

Pharmacy

Pace

"MZ:

A-20AE

"MZ:

80-39479-0

N/A

7430 / 6860

/ 200 --7980

/ 6940 / x

N/A / TSP

= 1.53"

FLA = 22 /

Amps =

10.5

No N/A N/A No n/a Yes JCI P G A A A

L, E L, E = Built in 1980. Newer

DDC valve and damper actuators in 2010, but overall condition is poor and past useful life. Lacks

VFDs.

EF-1 (RF-1)

154-RF-01-AHU05P

HARM

011-150

Relief/Exhaust

Fan

Serves

154-AHU-05-PHAR

M

Serves

154-AHU-05-PHAR

M

Pace EF: U-27F

EF:

80-40064-0

1"

N/A

7430 / 6860

/ 200 --7980

/ 6940 / x

N/A N/A No N/A N/A No n/a Yes JCI P A G A

L, E L, E = Built in 1980. Newer

DDC damper actuators in

2010, but overall condition is poor and past useful life.

Lacks VFDs. (2) 4L840

CU-1 (AHUX-1)

154-CUAC-03-AHU

154A Roof

Condensing

Unit

Estimate

Constant speed

2-stage DX.

Serves

154-AHU-08-BSNS

OFF cooling coil only.

McQuay ALP012D

Y42

58B850430

N/A N/A N/A

2 x 18.6

RLA

No N/A n/a No n/a Yes JCI A A

L, E

Built appx. 1995. Average condition. Old but well-maintained. Clean coil.

R-22.

Evap-1 Clean

Side

154-AHUO-01-CLE

AN

154 Roof Evaporative

Cooling Unit

Single zone evaporative cooling only. Outside Air

Damper.

Laundry - Clean

Side

Innovent CAHU-400

0-DV-208

2090011

N/A N/A N/A

3 Hp / 9 A

No N/A n/a No n/a Yes JCI G P G G A

M

Built 2014. Good condition.

Dirty filters. Evaporative cooling only. (4) BX-75

Evap-2 Dirty Side

154-AHUO-02-DIRT

Y

154 Roof Evaporative

Cooling Unit

Single zone evaporative cooling only. Outside Air

Damper.

Laundry - Dirty Side

Innovent CAHU-400

0-DV-208

2090011

N/A N/A N/A

3 Hp / 9 A

No N/A n/a No n/a Yes JCI G P G G A

M

Built 2014. Good condition.

Dirty filters. Evaporative cooling only. (4) BX-75

154 HEPA-EF-South 154-EFB-01

Upper Roof

154- South

Wing

Exhaust Fan

Constant Volume

HEPA exhaust.

Serves 3rd & 4th

Floors

Pace TNKM307

01-82821-0

N/A N/A N/A

7.5 Hp

No n/a n/a n/a n/a Yes JCI A A A A

HEPA exhaust with Energy

Recovery Coil attached.

Average condition. (2)

BX-64 belts and filters average. Labelled "AHU-1".

7.5 Hp.

154 EF-1-West

154-EF-02-4THWE

ST

Upper Roof

154- West

Wing

Exhaust Fan

Constant Volume

3-zone exhaust.

Serves Patient

Rooms

Aladdin 1HC-22LS 83905

N/A N/A N/A

5 Hp

No n/a n/a n/a n/a Yes JCI P A P P

L, E "Exhaust with Energy

Recovery Coil attached. 5

Hp

L,E = Past useful life. Built

1983- Poor condition. Fan bearings are grinding. (2)

BX-48 belts and filters average. "

HEPA-EF-13B-No rth

154-EFI-13B-ISON

ORTH

Upper Roof

154- North

Wing

Exhaust Fan

Constant Volume

HEPA exhaust.

Serves Isolation

Rooms

Flanders BG1-1H2

W-2GGF-

304-D3

98-377

N/A N/A N/A

5 Hp

No n/a n/a n/a n/a Yes JCI A A A A

HEPA exhaust fan for

Isolation Rooms. Built 1998.

Average condition. (4)

BX-35 belt and filters average. 5 Hp.

Building CHWS

(Basement

Chiller)

154-CHLR-01-154 B100

Centrifugal

Chiller

Constant volume system with 3 way valves

Bldg 154 Chilled

Water System

Trane

RTHB180

ALB00LW

0000UNN

3LF2MF00

QU

U94L04732 N/A N/A N/A 692 LRA No N/A n/a n/a n/a Yes

Unitary w/JCI

Integration

A A A

Average condition. Built

1994, but estimate 10 years of useful life remaining.

CT-1 Building

CWS

154-CT-01-CWS

Penthouse 1

Open Loop

Cooling Tower

Estimate

Variable flow.

Bldg 154

Condenser Water

System

Evapco

LSTB5212 7329418 N/A N/A N/A N/A No N/A n/a n/a n/a Yes

Unitary w/JCI

Integration

A A G A

L, M

L, M = Older CT with newer

VFD, DDC damper, and piping. Unit is inside

Penthouse. CT is showing signs of leakage due to age.

Chiller

(Pharmacy)

154-CHLR-04-AHU0

Pharmacy

Roof

Chiller 2007 Constant Volume

Serves

154-AHU-06-PHAR

M Pharmacy unit cooling coil only.

Arctic Chill N/A N/A N/A N/A N/A N/A No 4 ton n/a n/a n/a Yes JCI G G G

Built 2007. Good condition.

Condensing coil is clean.

Chiller (SADIE)

154-CHLR-02-SADI

E

154 Roof Chiller 1996 Constant Volume

Serves

154-AHU-10-SADIE

cooling coil unit only.

Trane

CGAEC4O

GABA1G

J96B80395 N/A N/A N/A

692 LRA x compressor s

No N/A n/a n/a n/a Yes

Unitary w/JCI

Integration

A A A

Built 1996. Average condition. Condensing coil is clean.

Condensate

Pump 1

"154-CP-01-STEAM

B100

Condensate

Pump

1994 Constant Volume

Serves Bldg 154

Steam System Bell and

Gossett

ABB-1510 974767 N/A N/A N/A .5 HP ea. No n/a n/a n/a n/a No

Unitary

P P P

L, E

L, E = Poor condition. Built in 1994. Leakage and rust present. At or beyond useful life.

Condensate

Pump 2

154-CP-02-STEAM"

B100

Condensate

Pump

1994 Constant Volume

Serves Bldg 154

Steam System Bell and

Gossett

ABB-1510 974768 N/A N/A N/A .5 HP ea. No n/a n/a n/a n/a No

Unitary

P P P

L, E

L, E = Poor condition. Built in 1994. Leakage and rust present. At or beyond useful life.

154 CWP-1

154-CHWP-03-CHL

R02

Penthouse

203-154

Chilled Water

Circulation

Pump

Constant volume 3 way valve system

154-AHU-10-SADIE

Cooling Water only.

Taco 161C3N4 7/96 N/A N/A N/A

3 Hp / 5.7

Amps

No n/a n/a n/a n/a No

Unitary

A A

L, E

Built 1996. Fair condition-old. 3 Hp motor. No gpm/head data.

HW Pumps

"154-HWP-01-AHU0

B100

Heating Water

Circulation

Pump

Water/Water HE.

Constant volume 3 way valve system

Original Main

Building 154

Heating Water

Bell &

Gossett

185011 1129568AZ N/A N/A N/A

10 HP, 30

Amps

No n/a n/a n/a n/a Yes JCI A A A

Average condition, built in

1994. "

HW Pumps

154-HWP-02-AHU0

1"

B100

Heating Water

Circulation

Pump

Water/Water HE.

Constant volume 3 way valve system

Original Main

Building 154

Heating Water

Bell &

Gossett

185011 1129569AZ N/A N/A N/A

10 HP, 30

Amps

No n/a n/a n/a n/a Yes JCI A A A

Average condition, built in

1994. "

154 HWP-1

"154-HWP-09-AHU1

Lab 2nd

Floor Mech

Heating Water

Circulation

Pump

Constant volume 3 way valve system

154-AHU-11-LAB Taco

KS30009A

E2JCA876

M

EC49972/1 N/A N/A N/A

5 HP, 15

Amps / 13.1

Amps

No n/a

158.3

GPM / 95

GPM

n/a n/a Yes JCI G G G

E

E = Pumps lack VFDs.

Good condition, built in

2009.

154 HWP-2

154-HWP-10-AHU1

1"

Lab 2nd

Floor Mech

Heating Water

Circulation

Pump

Constant volume 3 way valve system

154-AHU-11-LAB Taco

KS30009A

E2JCA876

M

EC49972/2 N/A N/A N/A

5 HP, 15

Amps / 13.1

Amps

No n/a

158.3

GPM / 95

GPM

n/a n/a Yes JCI G G G

E

E = Pumps lack VFDs.

Good condition, built in

2009.

HWP-1 (SADIE)

"154-HWP-03-SADI

E

Sadie Crawl

SP

Heating Water

Circulation

Pump

Constant volume 3 way valve system

"154-AHU-10-SADI

E

Taco 1-96

1641C3N4

7.5

N/A N/A N/A

3 HP, 9

Amps

No n/a

MBH and

100 GPM

n/a n/a Yes JCI A A A

E

E = Pumps lack VFDs.

Average condition, built in

1996.

HWP-2 (SADIE)

154-HWP-04-SADIE

Sadie Crawl

SP

Heating Water

Circulation

Pump

Constant volume 3 way valve system

"154-AHU-10-SADI

E

Taco 1-96

1641C3N4

7.5

N/A N/A N/A

3 HP, 9

Amps

No n/a

MBH and

100 GPM

n/a n/a Yes JCI A A A

E

E = Pumps lack VFDs.

Average condition, built in

1996.

154 HX Lab 154-HEX-08-LAB

Lab 2nd

Floor Mech

Heat

Exchanger

Steam/Water HE.

Constant volume 3 way valve system

154-AHU-11-LAB N/A N/A N/A N/A N/A N/A n/a No n/a

1467600

BTU/H;

158.3

GPM

n/a n/a Yes JCI G G G

Built 2009. Good condition.

154 HX-1 154-HEX-06-OPMH 115-30

Heat

Exchanger

Steam/Water HE.

Constant volume 3 way valve system

Serves

154-AHU-07-OPMH

Mental Health

Outpatient

Taco E06208-S N/A N/A N/A N/A n/a No n/a

31.8

GPM / 54

GPM

n/a n/a Yes JCI G G G

Built in 2011. Good condition. Serve AHU-1

Mental Outpatient HW Coil.

P-1 Pharmacy

"154-HWP-05-PHA

RM

011-150

Heating Water

Circulation

Pump

Constant volume 3 way valve system

Pharmacy Heating

Water System

Bell and

Gossett

80 size

1.5AA 4

C058630-0

2A80

N/A N/A N/A

.33 HP, 6.6

fla / N/A

No n/a

10 GPM

/ 10.5

GPM and

10.0

GPM

n/a n/a Yes JCI A G A

R

R = Pumps are in good condition, but both balancing valves are leaking.

P-2 Pharmacy

154-HWP-06-PHAR

M"

011-150

Heating Water

Circulation

Pump

Constant volume 3 way valve system

Pharmacy Heating

Water System

Bell and

Gossett

80 size

1.5AA 4

C058943-0

1A80

N/A N/A N/A

.33 HP, 6.6

fla / N/A

No n/a

10 GPM

/ 10.5

GPM and

10.0

GPM

n/a n/a Yes JCI A G A

R

R = Pumps are in good condition, but both balancing valves are leaking.

154 PFHX-1

154-HEX-05-PHAR

M

011-150

Heat

Exchanger

Water/Water HE.

Constant volume 3 way valve system.

Converted to Low

Pressure Steam in

2010.

Pharmacy Heating

Water System.

Tranter Inc

GCD-008-

M-5-HJ-14

N/A N/A N/A N/A n/a No n/a 200 MBH n/a n/a Yes JCI G G G

Built 2009. Good condition.

154 PFHX-5A

"154-HEX-03-SADI

E

Sadie Crawl

SP

Heat

Exchanger

Water/Water HE.

Constant volume 3 way valve system

SADIE heating water

Tranter Inc

GXD-042-

H-4-UJ-23

N/A N/A N/A N/A n/a No n/a

MBH and

100 GPM

n/a n/a Yes JCI G G G

Built 2010. Good condition.

154 PFHX-5B 154-HEX-04-SADIE

Sadie Crawl

SP

Heat

Exchanger

Water/Water HE.

Constant volume 3 way valve system

SADIE heating water

Tranter Inc

GXD-042-

H-4-UJ-23

N/A N/A N/A N/A n/a No n/a

MBH and

100 GPM

n/a n/a Yes JCI G G G

Built 2010. Good condition.

154 PFHX-6A

"154-HEX-01-AHU0

B100

Heat

Exchanger

Water/Water HE.

Constant volume 3 way valve system

Steam to Water HX.

Serves original

Building 154.

Tranter Inc

GXD-042-

H-4-UJ-55

N/A N/A N/A N/A n/a No n/a

MBH and

250 GPM

n/a n/a Yes JCI G G G

Built 2010. Good condition.

154 PFHX-6B

154-HEX-02-AHU01

B100

Heat

Exchanger

Water/Water HE.

Constant volume 3 way valve system

Steam to Water HX.

Serves original

Building 154.

Tranter Inc

GXD-042-

H-4-UJ-55

N/A N/A N/A N/A n/a No n/a

MBH and

250 GPM

n/a n/a Yes JCI G G G

Built 2010. Good condition.

Pump-1 (HX

Pump)

"154-HWP-07-OPM

H

115-30

Heating Water

Circulation

Pumps

Constant volume 3 way valve system.

Mental Health

Outpatient

Taco 1619C3E3 25/11 N/A N/A N/A

FLA = 7.6 /

Amps = 5.3

No n/a

31.8

GPM / 54

GPM

n/a n/a Yes JCI G G G

E

"E = Pumps lack VFDs.

Built in 2011. Good condition. Serve AHU-1

Mental Outpatient HX."

Pump-2 (HX

Pump)

154-HWP-08-OPMH

115-30

Heating Water

Circulation

Pumps

Constant volume 3 way valve system.

Mental Health

Outpatient

Taco 1619C3E3 25/12 N/A N/A N/A

FLA = 7.6 /

Amps = 5.3

No n/a

31.8

GPM / 54

GPM

n/a n/a Yes JCI G G G

E

"E = Pumps lack VFDs.

Built in 2011. Good condition. Serve AHU-1

Mental Outpatient HX."

CHW Pump-1

"154-CHWP-03-CH

LR05

Penthouse

#3

Chilled Water

Circulation

Pump

Estimate

Constant volume 3 way valve system.

Serves

154-AHU-12-4TH,

154-AHU-13-4TH

(3rd and 4th Flr original Bldg 154)

Taco BB2510 31147 N/A N/A N/A

7.5 HP, 25

Amps = 25

/ Amps =

23.6

No

148 GPM

/ 148

GPM

n/a n/a n/a Yes JCI P P P P

L, E, M

"L = Very old and poor condition.

E = Lacks VFDs

M = Leaking, poor insulation."

CHW Pump-2

154-CHWP-04-CHL

R05"

Penthouse

#3

Chilled Water

Circulation

Pump

Estimate

Constant volume 3 way valve system.

Serves

154-AHU-12-4TH,

154-AHU-13-4TH

(3rd and 4th Flr original Bldg 154)

Taco BB2510 31148 N/A N/A N/A

7.5 HP, 25

Amps = 25

/ Amps =

23.6

No

148 GPM

/ 148

GPM

n/a n/a n/a Yes JCI P P P P

L, E, M

"L = Very old and poor condition.

E = Lacks VFDs

M = Leaking, poor insulation."

Rooftop Chiller

154-CHLR-05-S1AS

2A

154 Tower

Roof

Chiller, Air-Cooled

Constant volume 3 way valve system.

Serves

154-AHU-12-4TH,

154-AHU-13-4TH

(3rd and 4th Flr original Bldg 154)

Trane

CGAM100

A2C02AX

D2A1A1A1

AXXA1C1

A4XXAXX

XA1A5A1

DXXXCXX

U10K19065 N/A N/A N/A 4 X 91 RLA No N/A n/a n/a n/a Yes JCI G G G

Good condition. Built 2010.

Clean coils.

154 CHWP-1

"154-CHWP-01-CH

LR01

B-100

Chilled Water

Circulation

Pumps

Constant volume 3 way valve system.

Serves Basement

Chilled Water

System

(154-CHLR-01-154)

B & G B&G18501

1129569AZ

N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P

L, E, R

"L, E = At or beyond useful life. Poor condition. Built in

1994. Leakage and rust present.

R = Insulation damaged. "

154 CHWP-2

154-CHWP-02-CHL

R01"

B-100

Chilled Water

Circulation

Pumps

Constant volume 3 way valve system.

Serves Basement

Chilled Water

System

(154-CHLR-01-154)

B & G B&G18501

1129570AZ

N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P

L, E, R

"L, E = At or beyond useful life. Poor condition. Built in

1994. Leakage and rust present.

R = Insulation damaged. "

154 CWP-1

"154-COWP-01-CT1

B-100

Condenser

Water

Circulation

Pump

Constant volume 3 way valve system.

Serves Basement

Condenser Water

System

(154-CT-01-CWS)

B & G B&G18501

1129571AZ

N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P

L, E, R

"L, E = At or beyond useful life.Poor condition. Built in

1994. Leakage and rust present.

R = Insulation damaged. "

154 CWP-2

154-COWP-02-CT1"

B-100

Condenser

Water

Circulation

Pump

Constant volume 3 way valve system.

Serves Basement

Condenser Water

System

(154-CT-01-CWS)

B & G B&G18501

1129572AZ

N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P

L, E, R

"L, E = At or beyond useful life.Poor condition. Built in

1994. Leakage and rust present.

R = Insulation damaged. "

Heat Recovery

Pump CPX-1

154-HRWP-09-EFB

01"

011-150

Heat Recovery

Water

Circulation

Pump

Constant volume 3 way valve system.

Serves 154-EFB-01

(HEPA Exhasut

Fan) only.

Taco VII507 N/A N/A N/A N/A .5 HP No n/a

4.8 GPM

/ 40

Ft.Hd.

n/a n/a Yes JCI A A A

C, R

"C = 3-Way Bypass Valve is pneumatic. Replace with

DDC.

R= Pump is in average condition, but some leakage. "

Waterside Equipment

Coversheet_GI001-GI001
436.B150-A-101
436.B150-M-001
436.B150-M-002
436.B150-M-101
436.154-A-101
436.154-A-102
436.154-A-103
436.154-A-104
436.154-A-105
436.154-A-106
436.154-M-001
436.154-M-002
436.154-M-003
436.154-M-004
436.154-M-005
436.154-M-101
436.154-M-102
436.154-M-103
436.154-M-104
436.154-M-105
436.154-M-106