DEPARTMENT OF VETERANS AFFAIRS
3687 VETERANS DRIVE
FORT HARRISON, MT 59636
HELENA
A-101
A-102
A-103
A-104
A-105
A-106
M-001
M-002
M-003
M-004
M-005
M-101
M-102
M-103
M-104
M-105
M-106
BASEMENT PLAN
FIRST FLOOR PLAN
SECOND FLOOR PLAN
THIRD FLOOR PLAN
FOURTH FLOOR PLAN
PENTHOUSE PLAN
MECHANICAL LEGEND, NOTES & SCHEDULES
MECHANICAL LEGEND, NOTES & SCHEDULES
MECHANICAL LEGEND, NOTES & SCHEDULES
MECHANICAL LEGEND, NOTES & SCHEDULES
MECHANICAL LEGEND, NOTES & SCHEDULES
BASEMENT HVAC PLAN
FIRST FLOOR HVAC PLAN
SECOND FLOOR HVAC PLAN
THIRD FLOOR HVAC PLAN
FOURTH FLOOR HVAC PLAN
PENTHOUSE HVAC PLAN
GI001 COVER SHEET
A-101
M-001
M-002
M-101
ARCHITECTURAL PLAN FOR FIRST, SECOND AND THIRD FLOOR
MECHANICAL LEGEND, NOTES & SCHEDULES
MECHANICAL LEGEND, NOTES & SCHEDULES
HVAC PLAN FOR FIRST, SECOND AND THIRD FLOOR
Airside Equipment
154 154 AHUX-1
154-AHU-08-BSNS
OFF
154 Roof
Air Handling
Unit
Estimate
Constant Volume
Supply fan with reheat zones.
Business Offices.
1st Flr:(located under 154A graphic). 4 Zones
Serves Business
Offices.
McQuay
RDS708B
B
38B00525
N/A
4620 - 4200
- x / N/A
N/A FLA = 14.8 No
15,000
MBH
N/A n/a n/a Yes JCI A G G G A
L, E
Built appx. 1995. Average condition. Old but well-maintained. Upgraded
DDC dampers, valves.
AH-2 (AC-2) and
RE-2
154-AHU-15-2ND
Penthouse 1
Air Handling
Unit
Estimate
DDC shows 100% outside air steam preheat, chilled water cooling, steam reheat, humidifier, constant volume AHU with coil bypass.
2nd Flr: Old PT and
Surgery. 1st Flr:
Dental
N/A N/A N/A N/A
6500 - x -
5060 / 6228
"N/A /
TSP =
2.52
N/A / ESP
= 1.372"
"SF: FLA =
20.2 / Amps
= 9.7
RF = 1.5
HP"
No N/A n/a n/a n/a Yes JCI P A G A A
M, R, E, C
"(2) BX-90 good. Coils clean. Dirty filters.M = steam traps have failed, dirty filters
R, E = OSA ducting is in need of repair, OSA damper is not working, condensate leaking onto floor.
C = OSA damper and supply air steam valves are still pnuematic"
154 AHU AC-1
"154-AHU-02-154
Room 146
Air Handling
Unit
Estimate
Constant Volume
AHU (supply and return fans) with
VAVs. 2 preheat valves (steam), cooling water coil, humidity control(disconnecte d), Economizer control. Controls updated in 2010.
1st Flr: Outpatient
Mental Health, North, South and
East, x-ray, offices.
2nd Flr: Offices and
SPD. 1st Flr East
(TEC-8,17, 25, 24,
23, 21, 19, 18, 17, 16, 15, 14, 13, 12, 11), Mental Health
(TEC-16, 27, 28,
29, 30), 1st Flr
South (TEC-4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15), Dental
(TEC-18, 19, 20,
21, 22), Pharm
(TEC- 24, 25, 26),
2nd Flr PT (TEC-9, 10, 11), 2nd Flr
LAB/Offices
(TEC-8, 12, 13, 14,
15, 16, 17, 18, 19, 20, 21, 33, 45, 65), 2nd Flr South
(TEC-9, 10, 11, 16,
17, 18, 8, 45, 33).
N/A
BCHC090
E1
(original, couldn't find any field information
N/A N/A
15870 - x -
3735 /
20000 - 335
- 2695
"SF: 'N/A
/ N/A
RF: 'N/A /
TSP =
0.84"""
"SF: 69.5
Amps / 63.9
Amps
RF: 3.4
Amps / N/A"
No N/A N/A Disconnected 65 Yes
JCI- Constant
Volume AHU
(supply and return fans) with
VAVs.
A A G G A
E, M "Older unit (estimate 1990) in fair condition. New DDC damper and valve actuators in 2010.
E = Lacks VFD on supply fan.
M = Insulation poor in places."
154 ACRE-1
154-RF-01-AHU-02
Room 146 Return Fan
Estimate
Constant Volume return fan.
154-AHU-02-154 N/A N/A N/A N/A
15870 - x -
3735 /
20000 - 335
- 2695
RF: 'N/A /
TSP =
0.84"""
"SF: 69.5
Amps / 63.9
Amps
RF: 3.4
Amps / N/A"
No n/a n/a n/a n/a Yes
JCI- Constant
Volume AHU
(supply and return fans) with
VAVs.
A A G G A
E, M "Older unit (estimate 1990) in fair condition. New DDC damper actuators in 2010.
E = Lacks VFD on fan.
M = Insulation poor in places."
154 RE-1 154-RF-02-AHU-02 Room 146 Return Fan
Estimate
Constant Volume return fan.
154-AHU-02-154 N/A N/A N/A N/A
15870 - x -
3735 /
20000 - 335
- 2695
RF: 'N/A /
TSP =
0.84"""
"SF: 69.5
Amps / 63.9
Amps
RF: 3.4
Amps / N/A"
No n/a n/a n/a n/a Yes
JCI- Constant
Volume AHU
(supply and return fans) with
VAVs.
A A G G A
E, M "Older unit (estimate 1990) in fair condition. New DDC damper actuators in 2010.
E = Lacks VFD on fan.
M = Insulation poor in places."
154 AHU S1 154-AHU-01-154
"SF: B100
Air Handling
Unit
Estimate
Constant Volume
AHU (supply and return fans) with
VAVs. 2 preheat valves (steam), cooling water coil, humidity control, Economizer control.
Controls redone in
2010.
1st Flr: North, Rec
Hall, Canteen. 2nd
Flr: Offices (old PT).
1st Flr North
(TEC-4, 5, 6, 7, 8),
2nd Flr PT (TEC-4, 5, 6, 7, 8, 65?, 22, 35, 24, 25, 26)
N/A
BCHC036
E1
(original, couldn't find any field information
N/A N/A
"SF: 20540 /
12455
RF: 6305 /
5330"
"SF: 'N/A
/ TSP =
2.89""
RF: N/A /
TSP =
0.81"""
"SF: 65.1
Amps / 29.9
Amps
RF: 5.1
Amps / N/A"
No N/A N/A Yes 16 Yes
JCI- Constant
Volume AHU
(supply and return fans) with
VAVs.
P A G G P
M, L, E "M = Insulation damaged.
L, E = Old (estimate built in
1990) and nearing or past expected life. Updated
DDC damper and valve actuators in 2010. Lacks
VFD."
154 RE-1 154-RF-01-AHU01
RF: 146"
Return Fan
Estimate
Constant Volume return fan.
154-AHU-01-154
N/A
BCHC036
E1
(original, couldn't find any field information
N/A N/A
"SF: 20540 /
12455
RF: 6305 /
5330"
"SF: 'N/A
/ TSP =
2.89""
RF: N/A /
TSP =
0.81"""
"SF: 65.1
Amps / 29.9
Amps
RF: 5.1
Amps / N/A"
No n/a n/a n/a n/a Yes
JCI- Constant
Volume AHU
(supply and return fans) with
VAVs.
P A G G P
M, L, E "M = Insulation damaged.
L, E = Old (estimate built in
1990) and nearing or past expected life. Updated
DDC damper actuators in
2010. Lacks VFD."
154 AHU S1A 154-AHU-12-4TH
Penthouse
#3
Air Handling
Unit
Estimate
100% outside air unit. AHU equipped with return and relief dampers but they are closed. Not sure if dampers broken or control changed to 100%
OA strategy. Steam heat, chilled water cooling, humidification, economizer dampers (not sure if used) heat recovery coil.
4th Flr. 4th West
(VAV 22-14, 62-14,
23-14, 11-14, 09-14, 10-14, 12-14, 16-14, 70-14, 33-14?, 32-14?, 24-14, 24-14, 30-13, 41-13) 4th North??
(VAV 58-14, 57-14,
56-14, 55-14, 54-14, 53-14, 52-14, 61-14, 60-14, 59-14) = 25
Total VAVs
Carrier 39EF18 0682 N/A N/A N/A N/A Yes N/A N/A Yes 25 Yes
JCI- EEI told equipment being redone as part of current project 436-110.
P A G G A
L, M, C EEI told equipment being redone as part of current project, 436-110.
"L = Old- nearing end of useful life.
M = Poor pipe and unit insulation.
C = Humidifier valve still pnuematic.
SYSTEM CONDITION ANALYSIS
154 AHU S1A 154-AHU-12-4TH
Penthouse
#3
Air Handling
Unit
Estimate
100% outside air unit. AHU equipped with return and relief dampers but they are closed. Not sure if dampers broken or control changed to 100%
OA strategy. Steam heat, chilled water cooling, humidification, economizer dampers (not sure if used) heat recovery coil.
4th Flr. 4th West
(VAV 22-14, 62-14,
23-14, 11-14, 09-14, 10-14, 12-14, 16-14, 70-14, 33-14?, 32-14?, 24-14, 24-14, 30-13, 41-13) 4th North??
(VAV 58-14, 57-14,
56-14, 55-14, 54-14, 53-14, 52-14, 61-14, 60-14, 59-14) = 25
Total VAVs
Carrier 39EF18 0682 N/A N/A N/A N/A Yes N/A N/A Yes 25 Yes
JCI- EEI told equipment being redone as part of current project 436-110.
P A G G A
L, M, C EEI told equipment being redone as part of current project, 436-110.
"L = Old- nearing end of useful life.
M = Poor pipe and unit insulation.
C = Humidifier valve still pnuematic.
154 AHU S2 154-AHU-14-3RD
Penthouse 1
Air Handling
Unit
Estimate
Supply/return fan with VFD and controlling to static pressure. Steam preheat, chilled water cooling, bypass dampers for coils, economizer dampers.
3rd Flr. Supply fan replaced in 2002.
3rd North (VAV-12, 14, 18, 19, 363) 3rd
Flr East(VAV
60-12, 61-12, 7-12, 6-12, 5-12, 46-11, 47-11, 44-11, 45-11, 48-11, 43-11, 42-11, 41-11, 50-11, 51-11, 49-11, 59-12, 10-12, 9-12, 8-12) 3rd Flr South
(VAV 30-11, 31-11,
32-11, 34-11, 34-11, 35-11, 35-11, 36-11, 37-11, 38-11, 57-11, 39-11), 3rd
Flr West (VAV
23-12, 53-12, 21-12, 20-12, 19-12, 52-12, 11-12, 62-11, 30-11, 39-11, 29-11, 28-11, 55-11, 27-11, 25-11, 26-11, 63-11, 24-12 = 55
Total VAVs, 64 shown on schedule).
N/A N/A N/A N/A 1800 / N/A N/A
SF: 7.5 HP
/ 'N/A
Yes N/A N/A No 55 Yes
JCI- Variable
Volume AHU
(supply and return fans) with
VAVs.
P P G G A
"L, M
EEI told equipment being redone as part of current project, 436-110."
" L = Old- nearing end of useful life.
M = Pipe insulation poor.(2)
BX-90 belt in good condition. New DDC valves, dampers, and VFD.
Insulation is poor. Could not access to determine filter and coil condition. "
RF-1 (AHU S2)
154-RF-01-AHU-14-
3RD
Penthouse 2
Return Fan
Estimate
Return fan with
VFD associated with AHU-14-3RD.
154-AHU-14-3RD N/A N/A N/A N/A N/A N/A
RF: 5 Hp
Yes N/A N/A n/a n/a Yes
JCI- Variable
Volume AHU
(supply and return fans) with
VAVs.
A G G G
Average condition. (2)
BX-53 in good condition.
Newer VFD.
154 AHU S2A 154-AHU-13-4TH
Penthouse
#3
Air Handling
Unit
Variable volume
VAV AHU, steam preheat, chilled water cooling, economizer dampers, humidification.
4th Flr. 4th East
(VAV 60-12, 61-12,
7-12, 6-12, 5-12, 46-11, 47-11, 44-11, 45-11, 48-11, 43-11, 42-11, 41-11?, 50-11, 51-11, 49-11, 59-12, 10-12, 9-12, 8-12)
4th South (VAV
6-14, 7-14, 8-14, 72-14, 4-14, 5-14, 96-14, 13-14, 14-14, 15-14) 4th
West (VAV 66-13, 67-13, 65-13, 64-13, 44-13, 43-13, 42-13, 68-13, 69-13, 45-13, 63-13) = 41
Total VAVs
Trane
CC0B170
E
U848401?8 N/A N/A N/A
"SF: 10 HP,
29 Amps
RF: 3 HP,
11 Amps"
Yes N/A N/A Yes 41 Yes
JCI- EEI told equipment being redone as part of current project 436-110.
P A G G A
"L, M, C
EEI told equipment being redone as part of current project, 436-110."
"L = Old- nearing end of useful life.
M = Poor pipe and unit insulation.
C = Humidifier valve still pnuematic.
154 AHU S5 154-AHU-01-ELEC
1st Floor
Electrical
Room
Air Handling
Unit
Estimate
Unit has supply fan and mixing dampers. Relief is via EF-2 in this room.
Bldg 154 1st Flr:
Electrical Sub
Station
Trane 10 U53140 N/A 4000 / 3090 N/A N/A No n/a n/a n/a n/a Yes JCI A A A
L, E "E = Lacks VFD.
L = Older unit (estimate
1990). Fair condition. (4)
BX-53 belt is good."
AHU-1 (Mental
Outpatient)
154-AHU-07-OPMH 115-30
Air Handling
Unit
Variable Volume
AHU (supply and return fan), VFD controls to duct static, hot water coil, DX coil with condensing unit, economizer control, night setback and morning warm-up, unoccupied controls. Controls upgrade in 2011.
Mental health
Outpatient 1st Flr
VAV-1, 2, 3, 4, 5, 6,
7, 8, 9, 10, 11.
Trane
CSAA012
UAB00
K10K98755 N/A
6815 - 6815
- x / N/A
"TSP =
3.115"" /
N/A
ESP =
1.5"" /
N/A"
7.5 HP Yes
156.61
MBH
210.6
MBH and
15 GPM
No 11 Yes JCI G G G G G
R, E "R, E = duct pressure sensor controlling unit speed isn't working properly.
Built in 2010. Good belts.
Clean filters."
AHU-1 (Dental)
"154-AHU-09-SADI
E
Penthouse
203-154
Air Handling
Unit
Variable Volume
AHU (supply and return fan), new
VFD's control to duct static, hot water coil, dx coil with condensing unit, economizer control. Controls upgrade in 2011 with some night setback control.
SADIE non operating 2nd flr and 1st flr VAV
(Dental and
Cardio). V-1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19, 20.
Dunham-B ush
"SF:
BH021AS
6630401
"SF:
66304-01A
96C
N/A
8975 - x -
6500 / 8320
- x - 5960
"N/A /
TSP =
2.6""
N/A / ESP
= 1.79""
"SF: 43.4
Amps / 30.1
Amps
EF: 7.5 HP,
21.3 Amps
/ N/A"
Yes
315 MBH
/ 68 GPM
718 MBH
/ 36 GPM
No 20 Yes JCI G G G G A
C
"C = Steam valve is pnuematic.
Average condition. Built
2002, but new CHW valves, ductwork, VFD. Steam valve is pnuematic. (2)
BX-50 in good condition.
Clean filters & coils."
EAF-1 (Dental)
154-EF-01-AHU09S
ADIE
Penthouse
203-154
Exhaust Fan 2002
Variable Volume return fan. Newer
VFD.
"154-AHU-09-SADI
E
" Dunham-B ush
EF:
DH017AS
6630403"
EF:
66304-03A
96C"
N/A
8975 - x -
6500 / 8320
- x - 5960
"N/A /
TSP =
2.6""
N/A / ESP
= 1.79""
"SF: 43.4
Amps / 30.1
Amps
EF: 7.5 HP,
21.3 Amps
/ N/A"
Yes n/a n/a n/a n/a Yes JCI G G G G A
Built 2002, with 2010 VFD.
Average condition.
AHU-1 / RTU-1
Pharmacy
154-AHU-06-PHAR
M
Pharmacy
Roof
Air Handling
Unit
Constant Volume
RTU with VFD used solely to set constant speed.
Pharmacy Clean
Room
Trane
TSCB003
U0E00000
000AC00A
225.2
K07M4771
0A
N/A 940 / 990
N/A / TSP
= 1.91"
2HP, 7.8
Amps / 5.1
Amps
Yes N/A N/A No n/a Yes JCI A A A G A
E, M
"E, M = HW coil and the
CHW coil were both observed to be significantly matted with fibers. Flow is restricted.
Built 2007. Average condition. DDC dampers, valves. (4) 4L420 belt in poor condition. "
AHU-1 / AH-1
Laboratory
154-AHU-11-LAB
Lab 1st Floor
Mech
Air Handling
Unit
Constant Volume
AHU (supply and exhaust fan), hot water coil, preheat coil, dx coil with condensing unit and
4 stages of cooling, humidity control, 100% OSA.
Lab (Electro Stand
Alone) VAV1, 2, 3, 4, 5, 6, 7, 8, 9, 10.
Trane
MCCB035
UA0C0UA
K09H27200 N/A
15000 - x -
1500 /
ESP =
1.38"
25 HP, 78.2
Amps
Yes
537400
BTUH
1016700
BTUH
Yes 10 Yes JCI G G G G G
Built in 2009. Good belts.
Clean filters.
154 AHU-2
"154-AHU-10-SADI
E
203-154
Air Handling
Unit
Variable Volume
AHU (supply and return fan), new
VFD's control to duct static, hot water coil, dx coil with condensing unit, economizer control. Controls upgrade in 2011 with some night setback control.
SADIE 2nd Flr-
Surgical
Dunham-B ush
"SF:
HCS12MF
6630402
"SF:
66304-02A
96C
N/A
3120 - x -
2790 / N/A
N/A / N/A
"SF: 5 HP /
N/A
RF: 2 HP
N/A"
Yes
113.5
MBH / 21
GPM
274 MBH
/ 17 GPM
No n/a Yes JCI A A A
C "
"C = HW & CHW valves are pnuematic.
BAS control. Variable volume. Average condition.
Built appx. 2002. Newer
VFD, DDC dampers, ductwork. "
154 LCEF-1
154-LCEF-01-AHU1
0SADIE
203-154 Exhaust Fan 2002
Variable Volume exhaust fan.
Controls upgrade in
2011.
"154-AHU-10-SADI
E
Dunham-B ush
EF:
HCS08MF
6630404
EF:
66304-04A
96D
N/A
3120 - x -
2790 / N/A
N/A / N/A
"SF: 5 HP /
N/A
RF: 2 HP
N/A"
Yes n/a n/a n/a n/a Yes JCI A A A
Average condition. Built appx. 2002. Newer VFD, DDC dampers, ductwork.
2011. N/A"
154 AHU-3
154-AHU-03-MORG
UE
154 Crawl
Air Handling
Unit
Estimate
Constant volume
AHU, steam heat with face and bypass dampers, chilled water cooling, economizer dampers.
2nd Flr Morgue
Trane 3 269925 N/A 1360 / 905
N/A / ESP
= 0.39
N/A No N/A N/A No n/a Yes JCI A A G G A
E "E = Lacks VFD.
Estimate 1999 construction.
Average condition. New
DDC damper and valve actuators in 2010. (4)
4L440 belt is good."
154 AHU-4
154-AHU-04-2NDS
OUTH
154 Crawl
Air Handling
Unit
Estimate
Constant volume
AHU, steam heat with face and bypass dampers, chilled water cooling, economizer dampers.
2nd Flr South. 2nd
South (TEC-4, 5, 6, Trane 3 269926 N/A 900 / 470
N/A / ESP
= 0.23
N/A / 11.5 No N/A N/A No n/a Yes JCI A A G G A
E, R "E = Lacks VFD.
R = Chilled water pipes lack insulation.
Estimate 1999 construction.
Fair condition. New DDC damper and valve actuators in 2010. (4) BX-38 belt is good."
CU-1 (AHU-1 /
AH-1)
154-CUAC-04-AHU1
Ground outside
AHU-1 / AH-1
Condensing
Unit
Serves
154-AHU-11-LAB
Serves
154-AHU-11-LAB
Trane
RAUCC50
EB2030
C09H0215
N/A n/a n/a
1356 LRA
total
No n/a n/a n/a n/a Yes
Unitary
G G G
Built in 2010. Clean coils.
Well-maintained.
CU-1 (Mental
Outpatient)
154-CUAC-02-AHU
Ground West
Wing
Condensing
Unit
Serves
154-AHU-07-OPMH
(Mental Outpatient)
Serves
154-AHU-07-OPMH
(Mental Outpatient)
Trane
TTA180E3
00AA
10425J0KT
A
N/A n/a n/a
328 LRA
total
No n/a n/a n/a n/a Yes
Unitary
G G G
Built in 2010. Clean coils.
Well-maintained.
CU- (MZ-2)
154-CUAC-01-AHU
Ground
South by
Boiler Plant
Condensing
Unit
Serves
154-AHU-05-PHAR
M (MZ-2)
Serves
154-AHU-05-PHAR
M (MZ-2)
Aaon
CCB0142
D2
201011-CH
CC02469
N/A n/a n/a
46 RLA
total
No n/a n/a n/a n/a Yes
Unitary
G G G
Built in 2011. Clean coils.
Well-maintained.
154 Data Aire AHU
154-ACUC-01-DAT
A
Basement
Air Handling
Unit
Estimate
Constant Volume
100% return air unit.
Basement
Communications
Room
Data Aire N/A N/A N/A
12000 - x -x / N/A
ESP =
0.75
10 HP No 30 Tons n/a n/a n/a Yes
Unitary
G G G G G
According to VA Staff, the
Data Aire system fails frequently, but was operating per design at time of inspection. Belts good. Filters clean.
Data Aire Dry
Cooler
154-CHLR-03-DAT
ARM
154 Roof
Dry Cooler
Estimate
Constant Volume system
Basement
Communications
Room
Data Aire N/A N/A N/A N/A N/A N/A No 52 Tons n/a n/a n/a Yes
Unitary
G G
According to VA Staff, the
Data Aire system fails frequently, but was operating per design at time of inspection.
154 EF-27 154-EFT-27
Penthouse 1
Exhaust Fan
Estimate
Constant Volume exhaust.
Bldg 154 Toilets Trane B131 256441
N/A N/A N/A
1.5 Hp
No n/a n/a n/a n/a Yes
Unitary
P A A
L,E
Estimate 25 yo.(2) BX-70 belts good condition.
Newer motor. Old unit-replace.
154 EF-30 154-EF-30
Penthouse 1
Exhaust Fan
Estimate
Constant Volume exhaust.
Bldg 154 penthouse
Trane B131 256442
N/A N/A N/A
1.5 Hp
No n/a n/a n/a n/a Yes
Unitary
P P P
L,E,R
Disabled, and appears to be abandoned in place.
154 EF-1 154-EF-01-1ST 154 Roof Exhaust Fan
Estimate
Constant Volume exhaust.
Original Bldg 154
1st Floor
Twin City
Fan and
Blower
N/A
04-190575-
1-1
N/A N/A N/A
10 Hp
No n/a n/a n/a n/a Yes
Unitary
A A A
Older Twin City unit in average condition. Estimate
10 years of service life remaining.
154 EF-2 154-EF-02-1ST 154 Roof Exhaust Fan
Estimate
Constant Volume exhaust.
Original Bldg 154
1st Floor
Twin City
Fan and
Blower
N/A
04-190575-
1-2
N/A N/A N/A
10 Hp
No n/a n/a n/a n/a Yes
Unitary
A A A
Older Twin City unit in average condition. Estimate
10 years of service life remaining.
ERU- Lab &
Laundry
154-ERU-01-LAB
Roof- West
Wing
Energy
Recovery Unit
Lab & Laundry Serves Lab &
Laundry areas in
West Wing
Addition.
Innovert ERU-0U-P
L-15000-2
2090011
N/A N/A N/A
15 Hp
No n/a n/a n/a n/a Yes JCI G G G G G
Newer. Good condition.
Belts good. Filters clean.
154 ILF-1 154-EF-02-SADIE
Penthouse
203-154
Exhaust Fan
Estimate
Constant Volume exhaust.
SADIE exhaust Carnes
VIBK12S1
C1NL20S
_G
540266 N/A N/A / N/A n/a
1.5 HP, 5.3
Amps
No n/a n/a n/a n/a Yes JCI A A A
L
BAS control. Average condition- old. Newer motor. 1.5 Hp. (2) 4L390
MZ-2 (Mark in field is AHU-1)
154-AHU-05-PHAR
M
011-150
Air Handling
Unit, Multi-Zone
Constant Volume mixed air unit with hot and cold decks.
Hot deck served by steam. Cold deck served by DX Unit.
Controls upgrade in
2010.
Pharmacy
Pace
"MZ:
A-20AE
"MZ:
80-39479-0
N/A
7430 / 6860
/ 200 --7980
/ 6940 / x
N/A / TSP
= 1.53"
FLA = 22 /
Amps =
10.5
No N/A N/A No n/a Yes JCI P G A A A
L, E L, E = Built in 1980. Newer
DDC valve and damper actuators in 2010, but overall condition is poor and past useful life. Lacks
VFDs.
EF-1 (RF-1)
154-RF-01-AHU05P
HARM
011-150
Relief/Exhaust
Fan
Serves
154-AHU-05-PHAR
M
Serves
154-AHU-05-PHAR
M
Pace EF: U-27F
EF:
80-40064-0
1"
N/A
7430 / 6860
/ 200 --7980
/ 6940 / x
N/A N/A No N/A N/A No n/a Yes JCI P A G A
L, E L, E = Built in 1980. Newer
DDC damper actuators in
2010, but overall condition is poor and past useful life.
Lacks VFDs. (2) 4L840
CU-1 (AHUX-1)
154-CUAC-03-AHU
154A Roof
Condensing
Unit
Estimate
Constant speed
2-stage DX.
Serves
154-AHU-08-BSNS
OFF cooling coil only.
McQuay ALP012D
Y42
58B850430
N/A N/A N/A
2 x 18.6
RLA
No N/A n/a No n/a Yes JCI A A
L, E
Built appx. 1995. Average condition. Old but well-maintained. Clean coil.
R-22.
Evap-1 Clean
Side
154-AHUO-01-CLE
AN
154 Roof Evaporative
Cooling Unit
Single zone evaporative cooling only. Outside Air
Damper.
Laundry - Clean
Side
Innovent CAHU-400
0-DV-208
2090011
N/A N/A N/A
3 Hp / 9 A
No N/A n/a No n/a Yes JCI G P G G A
M
Built 2014. Good condition.
Dirty filters. Evaporative cooling only. (4) BX-75
Evap-2 Dirty Side
154-AHUO-02-DIRT
Y
154 Roof Evaporative
Cooling Unit
Single zone evaporative cooling only. Outside Air
Damper.
Laundry - Dirty Side
Innovent CAHU-400
0-DV-208
2090011
N/A N/A N/A
3 Hp / 9 A
No N/A n/a No n/a Yes JCI G P G G A
M
Built 2014. Good condition.
Dirty filters. Evaporative cooling only. (4) BX-75
154 HEPA-EF-South 154-EFB-01
Upper Roof
154- South
Wing
Exhaust Fan
Constant Volume
HEPA exhaust.
Serves 3rd & 4th
Floors
Pace TNKM307
01-82821-0
N/A N/A N/A
7.5 Hp
No n/a n/a n/a n/a Yes JCI A A A A
HEPA exhaust with Energy
Recovery Coil attached.
Average condition. (2)
BX-64 belts and filters average. Labelled "AHU-1".
7.5 Hp.
154 EF-1-West
154-EF-02-4THWE
ST
Upper Roof
154- West
Wing
Exhaust Fan
Constant Volume
3-zone exhaust.
Serves Patient
Rooms
Aladdin 1HC-22LS 83905
N/A N/A N/A
5 Hp
No n/a n/a n/a n/a Yes JCI P A P P
L, E "Exhaust with Energy
Recovery Coil attached. 5
Hp
L,E = Past useful life. Built
1983- Poor condition. Fan bearings are grinding. (2)
BX-48 belts and filters average. "
HEPA-EF-13B-No rth
154-EFI-13B-ISON
ORTH
Upper Roof
154- North
Wing
Exhaust Fan
Constant Volume
HEPA exhaust.
Serves Isolation
Rooms
Flanders BG1-1H2
W-2GGF-
304-D3
98-377
N/A N/A N/A
5 Hp
No n/a n/a n/a n/a Yes JCI A A A A
HEPA exhaust fan for
Isolation Rooms. Built 1998.
Average condition. (4)
BX-35 belt and filters average. 5 Hp.
Building CHWS
(Basement
Chiller)
154-CHLR-01-154 B100
Centrifugal
Chiller
Constant volume system with 3 way valves
Bldg 154 Chilled
Water System
Trane
RTHB180
ALB00LW
0000UNN
3LF2MF00
QU
U94L04732 N/A N/A N/A 692 LRA No N/A n/a n/a n/a Yes
Unitary w/JCI
Integration
A A A
Average condition. Built
1994, but estimate 10 years of useful life remaining.
CT-1 Building
CWS
154-CT-01-CWS
Penthouse 1
Open Loop
Cooling Tower
Estimate
Variable flow.
Bldg 154
Condenser Water
System
Evapco
LSTB5212 7329418 N/A N/A N/A N/A No N/A n/a n/a n/a Yes
Unitary w/JCI
Integration
A A G A
L, M
L, M = Older CT with newer
VFD, DDC damper, and piping. Unit is inside
Penthouse. CT is showing signs of leakage due to age.
Chiller
(Pharmacy)
154-CHLR-04-AHU0
Pharmacy
Roof
Chiller 2007 Constant Volume
Serves
154-AHU-06-PHAR
M Pharmacy unit cooling coil only.
Arctic Chill N/A N/A N/A N/A N/A N/A No 4 ton n/a n/a n/a Yes JCI G G G
Built 2007. Good condition.
Condensing coil is clean.
Chiller (SADIE)
154-CHLR-02-SADI
E
154 Roof Chiller 1996 Constant Volume
Serves
154-AHU-10-SADIE
cooling coil unit only.
Trane
CGAEC4O
GABA1G
J96B80395 N/A N/A N/A
692 LRA x compressor s
No N/A n/a n/a n/a Yes
Unitary w/JCI
Integration
A A A
Built 1996. Average condition. Condensing coil is clean.
Condensate
Pump 1
"154-CP-01-STEAM
B100
Condensate
Pump
1994 Constant Volume
Serves Bldg 154
Steam System Bell and
Gossett
ABB-1510 974767 N/A N/A N/A .5 HP ea. No n/a n/a n/a n/a No
Unitary
P P P
L, E
L, E = Poor condition. Built in 1994. Leakage and rust present. At or beyond useful life.
Condensate
Pump 2
154-CP-02-STEAM"
B100
Condensate
Pump
1994 Constant Volume
Serves Bldg 154
Steam System Bell and
Gossett
ABB-1510 974768 N/A N/A N/A .5 HP ea. No n/a n/a n/a n/a No
Unitary
P P P
L, E
L, E = Poor condition. Built in 1994. Leakage and rust present. At or beyond useful life.
154 CWP-1
154-CHWP-03-CHL
R02
Penthouse
203-154
Chilled Water
Circulation
Pump
Constant volume 3 way valve system
154-AHU-10-SADIE
Cooling Water only.
Taco 161C3N4 7/96 N/A N/A N/A
3 Hp / 5.7
Amps
No n/a n/a n/a n/a No
Unitary
A A
L, E
Built 1996. Fair condition-old. 3 Hp motor. No gpm/head data.
HW Pumps
"154-HWP-01-AHU0
B100
Heating Water
Circulation
Pump
Water/Water HE.
Constant volume 3 way valve system
Original Main
Building 154
Heating Water
Bell &
Gossett
185011 1129568AZ N/A N/A N/A
10 HP, 30
Amps
No n/a n/a n/a n/a Yes JCI A A A
Average condition, built in
1994. "
HW Pumps
154-HWP-02-AHU0
1"
B100
Heating Water
Circulation
Pump
Water/Water HE.
Constant volume 3 way valve system
Original Main
Building 154
Heating Water
Bell &
Gossett
185011 1129569AZ N/A N/A N/A
10 HP, 30
Amps
No n/a n/a n/a n/a Yes JCI A A A
Average condition, built in
1994. "
154 HWP-1
"154-HWP-09-AHU1
Lab 2nd
Floor Mech
Heating Water
Circulation
Pump
Constant volume 3 way valve system
154-AHU-11-LAB Taco
KS30009A
E2JCA876
M
EC49972/1 N/A N/A N/A
5 HP, 15
Amps / 13.1
Amps
No n/a
158.3
GPM / 95
GPM
n/a n/a Yes JCI G G G
E
E = Pumps lack VFDs.
Good condition, built in
2009.
154 HWP-2
154-HWP-10-AHU1
1"
Lab 2nd
Floor Mech
Heating Water
Circulation
Pump
Constant volume 3 way valve system
154-AHU-11-LAB Taco
KS30009A
E2JCA876
M
EC49972/2 N/A N/A N/A
5 HP, 15
Amps / 13.1
Amps
No n/a
158.3
GPM / 95
GPM
n/a n/a Yes JCI G G G
E
E = Pumps lack VFDs.
Good condition, built in
2009.
HWP-1 (SADIE)
"154-HWP-03-SADI
E
Sadie Crawl
SP
Heating Water
Circulation
Pump
Constant volume 3 way valve system
"154-AHU-10-SADI
E
Taco 1-96
1641C3N4
7.5
N/A N/A N/A
3 HP, 9
Amps
No n/a
MBH and
100 GPM
n/a n/a Yes JCI A A A
E
E = Pumps lack VFDs.
Average condition, built in
1996.
HWP-2 (SADIE)
154-HWP-04-SADIE
Sadie Crawl
SP
Heating Water
Circulation
Pump
Constant volume 3 way valve system
"154-AHU-10-SADI
E
Taco 1-96
1641C3N4
7.5
N/A N/A N/A
3 HP, 9
Amps
No n/a
MBH and
100 GPM
n/a n/a Yes JCI A A A
E
E = Pumps lack VFDs.
Average condition, built in
1996.
154 HX Lab 154-HEX-08-LAB
Lab 2nd
Floor Mech
Heat
Exchanger
Steam/Water HE.
Constant volume 3 way valve system
154-AHU-11-LAB N/A N/A N/A N/A N/A N/A n/a No n/a
1467600
BTU/H;
158.3
GPM
n/a n/a Yes JCI G G G
Built 2009. Good condition.
154 HX-1 154-HEX-06-OPMH 115-30
Heat
Exchanger
Steam/Water HE.
Constant volume 3 way valve system
Serves
154-AHU-07-OPMH
Mental Health
Outpatient
Taco E06208-S N/A N/A N/A N/A n/a No n/a
31.8
GPM / 54
GPM
n/a n/a Yes JCI G G G
Built in 2011. Good condition. Serve AHU-1
Mental Outpatient HW Coil.
P-1 Pharmacy
"154-HWP-05-PHA
RM
011-150
Heating Water
Circulation
Pump
Constant volume 3 way valve system
Pharmacy Heating
Water System
Bell and
Gossett
80 size
1.5AA 4
C058630-0
2A80
N/A N/A N/A
.33 HP, 6.6
fla / N/A
No n/a
10 GPM
/ 10.5
GPM and
10.0
GPM
n/a n/a Yes JCI A G A
R
R = Pumps are in good condition, but both balancing valves are leaking.
P-2 Pharmacy
154-HWP-06-PHAR
M"
011-150
Heating Water
Circulation
Pump
Constant volume 3 way valve system
Pharmacy Heating
Water System
Bell and
Gossett
80 size
1.5AA 4
C058943-0
1A80
N/A N/A N/A
.33 HP, 6.6
fla / N/A
No n/a
10 GPM
/ 10.5
GPM and
10.0
GPM
n/a n/a Yes JCI A G A
R
R = Pumps are in good condition, but both balancing valves are leaking.
154 PFHX-1
154-HEX-05-PHAR
M
011-150
Heat
Exchanger
Water/Water HE.
Constant volume 3 way valve system.
Converted to Low
Pressure Steam in
2010.
Pharmacy Heating
Water System.
Tranter Inc
GCD-008-
M-5-HJ-14
N/A N/A N/A N/A n/a No n/a 200 MBH n/a n/a Yes JCI G G G
Built 2009. Good condition.
154 PFHX-5A
"154-HEX-03-SADI
E
Sadie Crawl
SP
Heat
Exchanger
Water/Water HE.
Constant volume 3 way valve system
SADIE heating water
Tranter Inc
GXD-042-
H-4-UJ-23
N/A N/A N/A N/A n/a No n/a
MBH and
100 GPM
n/a n/a Yes JCI G G G
Built 2010. Good condition.
154 PFHX-5B 154-HEX-04-SADIE
Sadie Crawl
SP
Heat
Exchanger
Water/Water HE.
Constant volume 3 way valve system
SADIE heating water
Tranter Inc
GXD-042-
H-4-UJ-23
N/A N/A N/A N/A n/a No n/a
MBH and
100 GPM
n/a n/a Yes JCI G G G
Built 2010. Good condition.
154 PFHX-6A
"154-HEX-01-AHU0
B100
Heat
Exchanger
Water/Water HE.
Constant volume 3 way valve system
Steam to Water HX.
Serves original
Building 154.
Tranter Inc
GXD-042-
H-4-UJ-55
N/A N/A N/A N/A n/a No n/a
MBH and
250 GPM
n/a n/a Yes JCI G G G
Built 2010. Good condition.
154 PFHX-6B
154-HEX-02-AHU01
B100
Heat
Exchanger
Water/Water HE.
Constant volume 3 way valve system
Steam to Water HX.
Serves original
Building 154.
Tranter Inc
GXD-042-
H-4-UJ-55
N/A N/A N/A N/A n/a No n/a
MBH and
250 GPM
n/a n/a Yes JCI G G G
Built 2010. Good condition.
Pump-1 (HX
Pump)
"154-HWP-07-OPM
H
115-30
Heating Water
Circulation
Pumps
Constant volume 3 way valve system.
Mental Health
Outpatient
Taco 1619C3E3 25/11 N/A N/A N/A
FLA = 7.6 /
Amps = 5.3
No n/a
31.8
GPM / 54
GPM
n/a n/a Yes JCI G G G
E
"E = Pumps lack VFDs.
Built in 2011. Good condition. Serve AHU-1
Mental Outpatient HX."
Pump-2 (HX
Pump)
154-HWP-08-OPMH
115-30
Heating Water
Circulation
Pumps
Constant volume 3 way valve system.
Mental Health
Outpatient
Taco 1619C3E3 25/12 N/A N/A N/A
FLA = 7.6 /
Amps = 5.3
No n/a
31.8
GPM / 54
GPM
n/a n/a Yes JCI G G G
E
"E = Pumps lack VFDs.
Built in 2011. Good condition. Serve AHU-1
Mental Outpatient HX."
CHW Pump-1
"154-CHWP-03-CH
LR05
Penthouse
#3
Chilled Water
Circulation
Pump
Estimate
Constant volume 3 way valve system.
Serves
154-AHU-12-4TH,
154-AHU-13-4TH
(3rd and 4th Flr original Bldg 154)
Taco BB2510 31147 N/A N/A N/A
7.5 HP, 25
Amps = 25
/ Amps =
23.6
No
148 GPM
/ 148
GPM
n/a n/a n/a Yes JCI P P P P
L, E, M
"L = Very old and poor condition.
E = Lacks VFDs
M = Leaking, poor insulation."
CHW Pump-2
154-CHWP-04-CHL
R05"
Penthouse
#3
Chilled Water
Circulation
Pump
Estimate
Constant volume 3 way valve system.
Serves
154-AHU-12-4TH,
154-AHU-13-4TH
(3rd and 4th Flr original Bldg 154)
Taco BB2510 31148 N/A N/A N/A
7.5 HP, 25
Amps = 25
/ Amps =
23.6
No
148 GPM
/ 148
GPM
n/a n/a n/a Yes JCI P P P P
L, E, M
"L = Very old and poor condition.
E = Lacks VFDs
M = Leaking, poor insulation."
Rooftop Chiller
154-CHLR-05-S1AS
2A
154 Tower
Roof
Chiller, Air-Cooled
Constant volume 3 way valve system.
Serves
154-AHU-12-4TH,
154-AHU-13-4TH
(3rd and 4th Flr original Bldg 154)
Trane
CGAM100
A2C02AX
D2A1A1A1
AXXA1C1
A4XXAXX
XA1A5A1
DXXXCXX
U10K19065 N/A N/A N/A 4 X 91 RLA No N/A n/a n/a n/a Yes JCI G G G
Good condition. Built 2010.
Clean coils.
154 CHWP-1
"154-CHWP-01-CH
LR01
B-100
Chilled Water
Circulation
Pumps
Constant volume 3 way valve system.
Serves Basement
Chilled Water
System
(154-CHLR-01-154)
B & G B&G18501
1129569AZ
N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P
L, E, R
"L, E = At or beyond useful life. Poor condition. Built in
1994. Leakage and rust present.
R = Insulation damaged. "
154 CHWP-2
154-CHWP-02-CHL
R01"
B-100
Chilled Water
Circulation
Pumps
Constant volume 3 way valve system.
Serves Basement
Chilled Water
System
(154-CHLR-01-154)
B & G B&G18501
1129570AZ
N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P
L, E, R
"L, E = At or beyond useful life. Poor condition. Built in
1994. Leakage and rust present.
R = Insulation damaged. "
154 CWP-1
"154-COWP-01-CT1
B-100
Condenser
Water
Circulation
Pump
Constant volume 3 way valve system.
Serves Basement
Condenser Water
System
(154-CT-01-CWS)
B & G B&G18501
1129571AZ
N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P
L, E, R
"L, E = At or beyond useful life.Poor condition. Built in
1994. Leakage and rust present.
R = Insulation damaged. "
154 CWP-2
154-COWP-02-CT1"
B-100
Condenser
Water
Circulation
Pump
Constant volume 3 way valve system.
Serves Basement
Condenser Water
System
(154-CT-01-CWS)
B & G B&G18501
1129572AZ
N/A N/A N/A 5 HP ea. No N/A n/a n/a n/a Yes JCI P P P
L, E, R
"L, E = At or beyond useful life.Poor condition. Built in
1994. Leakage and rust present.
R = Insulation damaged. "
Heat Recovery
Pump CPX-1
154-HRWP-09-EFB
01"
011-150
Heat Recovery
Water
Circulation
Pump
Constant volume 3 way valve system.
Serves 154-EFB-01
(HEPA Exhasut
Fan) only.
Taco VII507 N/A N/A N/A N/A .5 HP No n/a
4.8 GPM
/ 40
Ft.Hd.
n/a n/a Yes JCI A A A
C, R
"C = 3-Way Bypass Valve is pneumatic. Replace with
DDC.
R= Pump is in average condition, but some leakage. "
Waterside Equipment
| Coversheet_GI001-GI001 |
| 436.B150-A-101 |
| 436.B150-M-001 |
| 436.B150-M-002 |
| 436.B150-M-101 |
| 436.154-A-101 |
| 436.154-A-102 |
| 436.154-A-103 |
| 436.154-A-104 |
| 436.154-A-105 |
| 436.154-A-106 |
| 436.154-M-001 |
| 436.154-M-002 |
| 436.154-M-003 |
| 436.154-M-004 |
| 436.154-M-005 |
| 436.154-M-101 |
| 436.154-M-102 |
| 436.154-M-103 |
| 436.154-M-104 |
| 436.154-M-105 |
| 436.154-M-106 |