36C25920Q0333-004.pdf
PDF Posted
- Attached to
- H268--Water System Chemical Treatment Services
- Solicitation number
- 36C25920Q0333
About this file
This document is a water treatment services report for the Salt Lake City Veterans Affairs Medical Center. It provides test results for various water systems at the facility, including softeners, deaerator, boilers, and condensate lines. Water quality parameters such as hardness, alkalinity, pH, conductivity, orthophosphate, sulfite, iron, and chloride levels are reported and compared against specification limits. The boiler treatment results are within specification limits except for slightly elevated neutralized conductance and iron in the condensate lines. Recommendations include maintaining the functioning water softeners, investigating the cause of low condensate return and elevated iron in the condensate, and confirming whether hospital condensate is being improperly discharged. The attached federal contract opportunity is for water system chemical treatment services under solicitation number 36C25920Q0333 from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19.
36C25920Q0333 Sample Test Report - VAMC Boilers and CHP.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25920Q0333-000.docx | DOCX document | |
| 36C25920Q0333-003.docx | DOCX document | |
| 36C25920Q0333-002.xlsx | XLSX spreadsheet | |
| 36C25920Q0333-001.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Company Location Date
Test Units Total Hardness ppm as CaCO3
Calcium Hardness ppm as CaCO3
P Alkalinity ppm as CaCO3
M Alkalinity ppm as CaCO3
OH Alkalinity ppm as CaCO3 pH pH
Conductance μS/cm
Orthophosphate ppm as PO4
Sulfite ppm as SO3
Iron ppm as Fe
Chloride ppm as Cl-
Conductivity Cycles % Condensate Return %
Neutralized Conductance μS/cm
Status
Softener 1
Softener 2
Deaerator
Boiler 1
Boiler 2
Boiler 3
CHP
Main Condensate
Laundry Condensate
Water and Energy Systems Technology, Inc.
P.O. Box 166 - Kaysville, Utah 84037 - Telephone (801) 546-4031
VAMC Attn: Allen Thacker Salt Lake City, UT Copy: Staff 3/9/2020 Copy:
Sample Point Softener 1 Softener 2 Deaerator Boiler 1 Boiler 2 Deaerator Boilers Condensate
Boiler 3 CHP Main Condensate
Laundry Condensate
Softener
LSLLSL USL LSL USL
1.00 0.00 Test Results Specification Limits
0.00 0.00 0.50
425 70 75 168 168 52 655 130 185 1 1 24 540 100 130
35 31417 424 397 4454 617 814
8.34 8.328.34 8.34 9.28
37.8 9.5 12.0 62 16 19
0.18 0.000.18
11.22 1.55 2.05 5.2%
3149 438 585
The boiler treatment is very good. The neutralized conductance is just slightly high - I have checked the boiler conductivity and made a slight correction to bring this in range.
The boiler is in standby.
The boiler is in standby.
Off.
The condensate pH is on target, bu the iron is elevated and it measured 1 ppm of hardness.
The condensate treatment is perfect with perfect corrosion protection.
Recommendations The water softener is perfect!
The water softener is perfect!
The DA hardness is in range, but the iron levels are elevated and the % condensate return is VERY low. Have you lost condensate? The boiler operators indicated that the hospital condensate was hard - is this being dumped?
On Off Off Off
USL
0.00 0.50
LSL USL
0.00 0.50 0.00 0.50
300 1000 300 800
8.50 10.50 8.00 9.00 1 750
20 60 3500 5000
25 75
0.00 0.100.00 0.10
30.00 60.00 60% 100%
2000 3000
Shading Legend White - No Specification Limit
Green -No Action, Data is Within Specification
Yellow: Action Required, Out of Specification
Red: Critical Out of Speciffication & System Damage Potential
Blue: Non-Critical Out of Specification