S06 36C25724B0008 Amendment 0004 Additional RFI Questions.pdf

PDF 129 KB Posted

Attached to
ELP Panel Annunciators' Relocation - Amendment 0004 Federal contract opportunity
Solicitation number
36C25724B0008
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17

About this file

This document contains responses to additional questions for Request for Information number 36C25724B0008 regarding the relocation of medical gas panel annunciators at the El Paso VA Healthcare System facility. The scope of work includes relocating one existing medical gas master alarm panel and providing an optional bid alternate to upgrade to the current generation panel. The facility is categorized as Risk Category 1 under NFPA 99. A second existing medical gas master alarm panel is located in the Engineering Building maintenance shop. As required by the VA Design Manual, two master system alarms are needed in separate warning locations for continuous responsible monitoring of the medical gas and vacuum system. The primary alarm must be located in the boiler plant control office, engineering control center, or office of the individual responsible for maintenance. A secondary warning location is also required to ensure continuous surveillance during facility working hours, such as an intensive care unit, fire station, or security office.

View the file

Other files for this federal contract opportunity

Other files attached to ELP Panel Annunciators' Relocation - Amendment 0004, newest first.
File Type Posted
S06 36C25724B0008 Amendment 0004.pdf PDF
36C25724B0008 Amendment 0003.pdf PDF
36C25724B0008 Amendment 0002.pdf PDF
S02_36C25724B0008 Amendment 0001.pdf PDF
75622203 Panel Annunciators Relocation IFC Specifications_01.pdf PDF
75622203 Panel Annunicators Relocation Drawings_01.pdf PDF
S02_36C25724B0008 REVISED.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Additional RFI Questions- 36C25724B0008 ELP Panel Annunciators' Relocation

1. There is a total of two panels shown in drawings ET901 detail 5 and 7 (OHIO#1 and OHIO#2) to be installed on the electrical cabinet but we are called to relocate just one.

Response: Design Analysis Part 2 – Design Requirements and Provisions, Chapter 3 Electrical, Section 3.1 Interior Low Voltage Systems, Paragraph 3.1.1 Existing Conditions, Sub-paragraph Medical Gas System Master Panel: The base scope of work includes relocating a single panel. Provide Bid-Alternate to Upgrade to current generation Master Alarm Panel due to limited replacement part availability. (Replacement Panel: Ohio Medical Master Alarm HMI 30 Point with Dry Contacts, Ethernet (263748-CE))

2. Is the current Med Gas Master Alarm Panel sharing a common on the low voltage signals? If the answer is yes, we would need to have it replaced in order to upgrade the panel to meet code standards NFPA99 to send individual connections for each signal.

Response: It is believed that all sensors are routed and terminated at each Master Panel as independent signal circuits with +/- terminations.

3. Which is the type of category for EL PASO VA HEALTHCARE SYSTEM, category 1, 2, 3 or 4?

Response: NFPA 99 Chapter 4 Fundamentals, Paragraph 4.1 Risk Categories: The type category for this facility is Category 1.

4. Besides the Med Gas Master Alarm Panel that would be relocated, is there any other Med Gas Master Alarm Panel on the facility.

Response: Yes. RE: Design Analysis Part 2 – Design Requirements and Provisions, Chapter 2 Mechanial, Paragraph 2.1 Plumbing, Sub-paragraph 2.1.1 Existing Conditions: The second panel is located in the Engineering Building – Maintenance Shop. Field verify location.

The two panels comply with VA Design Manual Requirements as follows:

RE: Plumbing PG-18-10 Design Manual (PG 18-10 – PLUMBING DESIGN MANUAL January 1, 2023); Chapter 8, Section 8.2.4 Alarms:

(a) To ensure continuous responsible observation, two master system alarms, in separate warning locations, are required for each medical gas and vacuum system.

(b) The primary warning location shall be supervised by engineering personnel and shall be located at one of the following (in order of priority): boiler plant control office, engineering control center, or in the office or principal working area of the individual responsible for the maintenance of the medical gas system. The primary alarm point shall be an alarm point in the direct digital control system and a physical, labeled, visual alarm indicator inside the primary warning location.

(c) The secondary warning location shall be situated to ensure continuous surveillance during the working hours of the facility. Suitable secondary warning locations may include: intensive care nursing unit, fire station, telephone switchboard, security office, or other continuously-staffed location.