This document provides specifications for low-energy power-assisted automatic swing door operators for a renovation project at the VA Illiana Health Care System in Danville, Illinois. The project involves renovating the pathology laboratory under solicitation number 36C25222B0033. The specifications require door operators that comply with UL standards and building codes, with a maximum opening force of 15 pounds and proven durability through 300,000 cycle tests. Acceptable materials include aluminum sheet and extrusions meeting ASTM standards. Required features involve safety functions, self-contained power units, electromechanical operation, solid-state controls, and anodized or powder-coated aluminum finishes. Installation must follow manufacturer instructions and include adjusting operations for pedestrian traffic flows. The contractor must demonstrate proper operation and train staff over a 15-day period without issues upon completion.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Illiana Health Care System September 27, 2022

550-20-110 100% Bid Documents

Renovate Pathology Laboratory 08-01-16

Danville, IL

08 71 13.11 - 1

SECTION 08 71 13.11

LOW ENERGY POWER ASSIST DOOR OPERATORS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Low-energy, power-assisted automatic swing door operators.

1.2 RELATED REQUIREMENTS

A. Commissioning; Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.

B. Steel Doors; Section 08 11 13, HOLLOW METAL DOORS AND FRAMES.

C. Wood Doors; Section 08 14 00, INTERIOR WOOD DOORS.

D. Aluminum Frames Entrance Work; Section 08 41 13, ALUMINUM-FRAMED

ENTRANCES AND STOREFRONTS.

E. Door Hardware; Section 08 71 00, DOOR HARDWARE.

F. Finish Color, Section 09 06 00, SCHEDULE FOR FINISHES.

G. Electric General Wiring, Connections and Equipment Requirements;

Division 26, ELECTRICAL.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. ASTM International (ASTM):

1. B209-14 - Aluminum and Aluminum-Alloy Sheet and Plate.

2. B221-14 - Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes.

C. Builders Hardware Manufacturers Association, Inc. (BHMA):

1. 156.19-07 - Power Assist and Low Energy Power Operated Doors.

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Show size, configuration, and fabrication and installation details.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Maintenance manuals.

3. Installation instructions.

4. Warranty.

D. Samples:

Renovate Pathology Laboratory 08-01-16

Danville, IL

08 71 13.11 - 2

1. Door Operator: Full sized, complete assembly.

2. Approved samples may be incorporated into work.

E. Certificates: Certify products comply with specifications.

1. Show door operator is UL Listed for specified application.

F. Operation and Maintenance Data:

1. Care instructions for each exposed finish product.

2. Start-up, maintenance, troubleshooting, emergency, and shut-down instructions for each operational product.

1.5 QUALITY ASSURANCE

A. Manufacturer Qualifications:

1. Regularly manufactures specified products.

B. Installer Qualifications:

1. Regularly installs specified products.

1.6 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.7 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight conditioned facility.

B. Protect products from damage during handling and construction operations.

1.8 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

B. Manufacturer's Warranty: Warrant automatic door operators against material and manufacturing defects.

1. Warranty Period: 3 years.

PART 2 - PRODUCTS

2.1 SYSTEM DESCRIPTION

A. Power assisted automatic door equipment accommodating normal traffic as well as the weight of the doors; UL approved and comply with applicable codes.

Renovate Pathology Laboratory 08-01-16

Danville, IL

08 71 13.11 - 3

2.2 SYSTEM PERFORMANCE

A. Opening Force: Maximum 67 N (15 lbf.).

B. Cycle Tests: 300,000 cycles.

1. Use the widest and heaviest door specified as a test specimen.

Narrower or lighter doors of the same configurations will be considered to meet the cycle test requirements.

2.3 MATERIALS

A. Aluminum:

1. Sheet: ASTM B209.

2. Extrusions: ASTM B221.

2.4 PRODUCTS - GENERAL

A. Provide automatic door operators from one manufacturer.

2.5 LOW-ENERGY AUTOMATIC DOOR OPERATORS

A. Conform to BHMA A156.19.

B. Enclosure: Self-contained within an extruded aluminum housing (alloy

6063-T6) to conceal operator mechanism and mounting brackets and with removable access cover with an overall maximum size of 140 mm

(5-1/2 inches) wide by 150 mm (6 inches) deep.

C. Safety Features:

1. Adjustable time delay.

2. Adjustable speed for opening and closing operations.

3. Adjustable backcheck.

4. Decals indicating "In" or "Do Not Enter" installed on both faces of each door where shown conforming to the requirements of

ANSI/BHMA A156.19.

5. Re-activation sensor mounted on the push-side door face near the top detect any person standing in the door swing path and prevent the door from closing.

6. Motion sensor to detect any person standing in the door swing path and prevent the door from opening.

a. Adjustable door sensor system providing complete operation and safety zone coverage.

D. Power Units:

1. Self-contained electric circuits for automatic operators located on each floor of the building.

Renovate Pathology Laboratory 08-01-16

Danville, IL

08 71 13.11 - 4

2. Interruption or failure of power circuits for operators located on one floor of the building shall not interfere with continuous performance of automatic operated doors located on other floors.

3. Power units designed to not interfere with continuous performance of automatic operated doors located on other floors in the case of power interruption or failure.

4. Capacity and size of power circuits according to automatic operator manufacturer's specifications.

2.6 OPERATION

A. Traffic Operation:

1. Single Door: Two way.

B. Operator: Electromechanical; surface-mounted.

1. Operators to have checking mechanism providing cushioning action at last part of door travel, in both opening and closing cycle.

2. Operators to recycle doors instantaneously to fully open position from any point in closing cycle when control switch is reactivated.

3. Operators to allow manual door control in event of power failure.

C. Controls: Solid-state type.

D. Activation: Push-plate switch.

2.7 FINISHES

A. Aluminum Anodized Finish: NAAMM AMP 500.

1. Clear Anodized Finish: AA-C22A41; Class I Architectural, 0.018 mm

(0.7 mil) thick.

2. Color Anodized Finish: AA-C22A42 or AA-C22A44; Class I

Architectural, 0.018 mm (0.7 mil) thick.

3. Clear Anodized Finish: AA-C22A31; Class II Architectural, 0.01 mm

(0.4 mil) thick.

4. Color Anodized Finish: AA-C22A32 or AA-C22A34; Class II

Architectural, 0.01 mm (0.4 mil) thick.

B. Aluminum Paint finish:

1. Baked-Enamel or Powder-Coat: AAMA 2603; dry film thickness of

0.04 mm (1.5 mils).

2.8 ACCESSORIES

A. Signage: BHMA standard for operation and door type specified.

B. Fasteners: Corrosion-resistant, compatible with adjoining materials.

Renovate Pathology Laboratory 08-01-16

Danville, IL

08 71 13.11 - 5

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine conditions effecting work, including door and frame preparation and electrical rough-ins.

3.2 INSTALLATION - GENERAL

A. Install products according to manufacturer's instructions and approved submittal drawings.

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Coordinate installation of equipment with other related work.

C. Mount manual controls and power disconnect switches recessed or semi-flush in partitions.

D. Secure operator components to adjacent construction with suitable fastenings. Conceal conduits, piping, and electric equipment in finish work.

E. Install power units and controls in locations indicated.

1. Where units are to be mounted on walls, provide metal supports or shelves for the units.

3.3 ADJUSTING

A. All equipment, including time delay switches, to be accessible for maintenance and adjustment.

B. Adjust operators to function properly for the type o£ traffic

(pedestrians) expected to pass through doors.

C. Adjust each door leaf of pairs of doors to open and close in synchronization.

D. On pairs of doors, adjust operators allowing either door to be opened manually without the other door opening.

3.4 DEMONSTRATION AND TRAINING

A. Instruct VA personnel in proper door operator operation and maintenance.

1. Trainer: Manufacturer approved instructor.

B. Submit training plan and trainer qualifications. See Section 01 91 00 -

GENERAL COMMISSIONING REQUIREMENTS.

Renovate Pathology Laboratory 08-01-16

Danville, IL

08 71 13.11 - 6

C. Acceptance Condition: After completing work, operate door operators 15 consecutive calendar days without breakdown.

- - - E N D - - -

PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1.2 RELATED REQUIREMENTS
A. Commissioning; Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.
B. Steel Doors; Section 08 11 13, HOLLOW METAL DOORS AND FRAMES.
C. Wood Doors; Section 08 14 00, INTERIOR WOOD DOORS.
D. Aluminum Frames Entrance Work; Section 08 41 13, ALUMINUM�FRAMED ENTRANCES AND STOREFRONTS.
E. Door Hardware; Section 08 71 00, DOOR HARDWARE.
F. Finish Color, Section 09 06 00, SCHEDULE FOR FINISHES.
G. Electric General Wiring, Connections and Equipment Requirements; Division 26, ELECTRICAL.
1.3 APPLICABLE PUBLICATIONS
A. Comply with references to extent specified in this section.
B. ASTM International (ASTM):
C. Builders Hardware Manufacturers Association, Inc. (BHMA):
1.4 SUBMITTALS
A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B. Submittal Drawings:
C. Manufacturer's Literature and Data:
D. Samples:
E. Certificates: Certify products comply with specifications.
F. Operation and Maintenance Data:
1.5 QUALITY ASSURANCE
A. Manufacturer Qualifications:
B. Installer Qualifications:
1.6 DELIVERY
A. Deliver products in manufacturer's original sealed packaging.
B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.
C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.
1.7 STORAGE AND HANDLING
A. Store products indoors in dry, weathertight conditioned facility.
B. Protect products from damage during handling and construction operations.
1.8 WARRANTY
A. Construction Warranty: FAR clause 52.246�21, "Warranty of Construction."
B. Manufacturer's Warranty: Warrant automatic door operators against material and manufacturing defects.
PART 2 - PRODUCTS
2.1 SYSTEM DESCRIPTION
A. Power assisted automatic door equipment accommodating normal traffic as well as the weight of the doors; UL approved and comply with applicable codes.
2.2 SYSTEM PERFORMANCE
A. Opening Force: Maximum 67 N (15 lbf.).
B. Cycle Tests: 300,000 cycles.
2.3 MATERIALS
A. Aluminum:
2.4 PRODUCTS - GENERAL
A. Provide automatic door operators from one manufacturer.
2.5 LOW�ENERGY AUTOMATIC DOOR OPERATORS
A. Conform to BHMA A156.19.
B. Enclosure: Self�contained within an extruded aluminum housing (alloy 6063�T6) to conceal operator mechanism and mounting brackets and with removable access cover with an overall maximum size of 140 mm (5�1/2 inches) wide by 150 mm (6 inches) deep.
C. Safety Features:
D. Power Units:
2.6 OPERATION
A. Traffic Operation:
B. Operator: Electromechanical; surface�mounted.
C. Controls: Solid�state type.
D. Activation: Push�plate switch.
2.7 FINISHES
A. Aluminum Anodized Finish: NAAMM AMP 500.
B. Aluminum Paint finish:
2.8 ACCESSORIES
A. Signage: BHMA standard for operation and door type specified.
B. Fasteners: Corrosion�resistant, compatible with adjoining materials.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine conditions effecting work, including door and frame preparation and electrical rough�ins.
3.2 INSTALLATION - GENERAL
A. Install products according to manufacturer's instructions and approved submittal drawings.
B. Coordinate installation of equipment with other related work.
C. Mount manual controls and power disconnect switches recessed or semi�flush in partitions.
D. Secure operator components to adjacent construction with suitable fastenings. Conceal conduits, piping, and electric equipment in finish work.
E. Install power units and controls in locations indicated.
3.3 ADJUSTING
A. All equipment, including time delay switches, to be accessible for maintenance and adjustment.
B. Adjust operators to function properly for the type o£ traffic (pedestrians) expected to pass through doors.
C. Adjust each door leaf of pairs of doors to open and close in synchronization.
D. On pairs of doors, adjust operators allowing either door to be opened manually without the other door opening.
3.4 DEMONSTRATION AND TRAINING
A. Instruct VA personnel in proper door operator operation and maintenance.
B. Submit training plan and trainer qualifications. See Section 01 91 00 - GENERAL COMMISSIONING REQUIREMENTS.
C. Acceptance Condition: After completing work, operate door operators 15 consecutive calendar days without breakdown.