36C25218Q1052-011.pdf
PDF 330 KB Posted
- Attached to
- Image Stream Upgrade OR EQUIPT IDIQ - RFQ
- Solicitation number
- 36C25218Q1052
About this file
36C25218Q1052 Attachment B - P01 - Fire Stopping Policy.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25218Q1052-0003000.docx | DOCX document | |
| 36C25218Q1052-0002000.docx | DOCX document | |
| 36C25218Q1052-00001000.docx | DOCX document | |
| 36C25218Q1052-015.docx | DOCX document | |
| 36C25218Q1052-013.docx | DOCX document | |
| 36C25218Q1052-010.doc | DOC document | |
| 36C25218Q1052-009.docx | DOCX document | |
| 36C25218Q1052-008.docx | DOCX document | |
| 36C25218Q1052-014.docx | DOCX document | |
| 36C25218Q1052-012.doc | DOC document | |
| 36C25218Q1052-016.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLEMENT J. ZABLOCKI MEDICAL CENTER DEPARTMENT OF VETERANS AFFAIRS
MILWAUKEE, WI
10-11
FIRESTOPPING 07 84 00 - 1
SECTION 07 84 00
FIRESTOPPING
PART 1 GENERAL
1.1 DESCRIPTION
A. Closures of openings in walls, floors, and roof decks against penetration of flame, heat, and smoke or gases in f ire resistant rated construction.
B. Closure of openings in walls against penetration of gases or smoke in smoke partitions.
C. Firestop Systems to be HILTI.
1.2 RELATED WORK
1.3 SUBMITTALS
A. Manufacturers literature, data, and installation instructions for types of firestopping and smoke stopping used.
B. List of FM, UL, or WH classification number of s ystems installed.
C. Certified laboratory test reports for ASTM E814 tests for systems not listed by FM, UL, or WH proposed for use.
1.4 DELIVERY AND STORAGE
A. Deliver materials in their original unopened con tainers with manufacturer’s name and product identification.
B. Store in a location providing protection from da mage and exposure to the elements.
1.5 WARRANTY
Firestopping work subject to the terms of the Arti cle “Warranty of
Construction”, FAR clause 52.246-21, except extend the warranty period to five years.
1.6 QUALITY ASSURANCE
FM, UL, or WH or other approved laboratory tested products will be acceptable.
1.7 APPLICABLE PUBLICATIONS
A. Publications listed below form a part of this sp ecification to the extent referenced. Publications are referenced in t he text by the basic designation only.
B. American Society for Testing and Materials (ASTM ):
FIRESTOPPING 07 84 00 - 2
E84-10..................Surface Burning Characteris tics of Building
Materials
E814-11.................Fire Tests of Through-Penet ration Fire Stops
C. Factory Mutual Engineering and Research Corporat ion (FM):
Annual Issue Approval Guide Building Materials
D. Underwriters Laboratories, Inc. (UL):
Annual Issue Building Materials Directory
Annual Issue Fire Resistance Directory
1479-10.................Fire Tests of Through-Penet ration Firestops
E. Warnock Hersey (WH):
Annual Issue Certification Listings
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. HILTI Firestop Systems, Inc.
2.2 FIRESTOP SYSTEMS
A. Use either factory built (Firestop Devices) or f ield erected (through-
Penetration Firestop Systems) to form a specific bu ilding system maintaining required integrity of the fire barrier and stop the passage of gases or smoke.
B. Through-penetration firestop systems and firesto p devices tested in accordance with ASTM E814 or UL 1479 using the "F" or "T" rating to maintain the same rating and integrity as the fire barrier being sealed. "T" ratings are not required for penetratio ns smaller than or equal to 100 mm (4 in) nominal pipe or 0.01 m 2 (16 sq. in.) in overall cross sectional area.
C. Products requiring heat activation to seal an op ening by its intumescence shall exhibit a demonstrated ability t o function as designed to maintain the fire barrier.
D. Firestop sealants used for firestopping or smoke sealing shall have following properties:
1. Contain no flammable or toxic solvents.
2. Have no dangerous or flammable out gassing durin g the drying or curing of products.
3. Water-resistant after drying or curing and unaff ected by high humidity, condensation or transient water exposure.
FIRESTOPPING 07 84 00 - 3
4. When used in exposed areas, shall be capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface.
E. Firestopping system or devices used for penetrat ions by glass pipe, plastic pipe or conduits, unenclosed cables, or oth er non-metallic materials shall have following properties:
1. Classified for use with the particular type of p enetrating material used.
2. Penetrations containing loose electrical cables, computer data cables, and communications cables protected using f irestopping systems that allow unrestricted cable changes witho ut damage to the seal.
3. Intumescent products which would expand to seal the opening and act as fire, smoke, toxic fumes, and, water sealant.
F. Maximum flame spread of 25 and smoke development of 50 when tested in accordance with ASTM E84.
G. FM, UL, or WH rated or tested by an approved lab oratory in accordance with ASTM E814.
H. Materials to be asbestos free.
FIRESTOPPING 07 84 00 - 4
I. Firestop Selection Charts:
FIRESTOPPING 07 84 00 - 5
FIRESTOPPING 07 84 00 - 6
FIRESTOPPING 07 84 00 - 7
FIRESTOPPING 07 84 00 - 8
FIRESTOPPING 07 84 00 - 9
J. Engineering Judgements - For situations where cu stom drawings for firestopping assemblies are required to accommodate particular conditions/applications not identified in the HILTI Firestop Systems
Installers Guide U.S. Volume 12, contractor to comp lete documentation on page 270 of the guide to request an engineering judgement from
HILTI. Completed form(s) to be faxed to 918-254-167 9.
2.3 SMOKE STOPPING IN SMOKE PARTITIONS
A. Use silicone sealant in smoke partitions as spec ified in Section 07 92
00, JOINT SEALANTS.
B. Use mineral fiber filler and bond breaker behind sealant.
C. Sealants shall have a maximum flame spread of 25 and smoke developed of
50 when tested in accordance with E84.
D. When used in exposed areas capable of being sand ed and finished with similar surface treatments as used on the surroundi ng wall or floor surface.
PART 3 - EXECUTION
3.1 EXAMINATION
Submit product data and installation instructions, as required by article, submittals, after an on site examination o f areas to receive firestopping.
FIRESTOPPING 07 84 00 - 10
3.2 PREPARATION
A. Remove dirt, grease, oil, loose materials, or ot her substances that prevent adherence and bonding or application of the firestopping or smoke stopping materials.
B. Remove insulation on insulated pipe for a distan ce of 150 mm (six inches) on either side of the fire rated assembly p rior to applying the firestopping materials unless the firestopping mate rials are tested and approved for use on insulated pipes.
3.3 INSTALLATION
A. Do not begin work until the specified material d ata and installation instructions of the proposed firestopping systems h ave been submitted and approved.
B. Install firestopping systems with smoke stopping in accordance with FM, UL, WH, or other approved system details and instal lation instructions.
C. Install smoke stopping seals in smoke partitions .
3.4 CLEAN-UP AND ACCEPTANCE OF WORK
A. As work on each floor is completed, remove mater ials, litter, and debris.
B. Do not move materials and equipment to the next- scheduled work area until completed work is inspected and accepted by t he Resident
Engineer.
C. Clean up spills of liquid type materials.
- - - E N D - - -