Attachment VIII - CVAMC and FT Thomas Arc Flash Study.pdf

PDF 16 MB Posted

Attached to
Z1DA--Project No. 539-22-203 - Electric Deficiencies
Solicitation number
36C25025B0015
Issued by

View the file

Other files

File Type Posted
36C25025B0015 0003.docx DOCX document
Attachment IX - Justification and Approval - Sole Source to Post.pdf PDF
36C25025B0015 0002.docx DOCX document
Attachment II - Drawings Revised 2.26.2025.pdf PDF
Attachment VII - Pre-Bid RFIs - GDI.docx DOCX document
Attachment VI - Addendum - Specifications.pdf PDF
Site Visit Sign In.pdf PDF
36C25025B0015 0001.docx DOCX document
36C25025B0015.pdf PDF
Attachment II - Drawings.pdf PDF
Attachment I - DBA WD.pdf PDF
36C25025B0015_1.docx DOCX document
Attachment V - RFI Form.pdf PDF
Attachment III - Specifications.pdf PDF
Attachment IV - VAAR 852.219-75.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2023-05233 CVAMC Arch Flash Study TOC i

SHORT-CIRCUIT AND ARC FLASH STUDY

FOR

Main Campus and Ft Thomas, KY Division

TABLE OF CONTENTS

SECTION PAGE

EXECUTIVE SUMMARY

BACKGROUND

OBJECTIVES

REFERENCES

WARRANTY

LIMITS OF LIABILITY

SHORT-CIRCUIT STUDY

A. THREE-PHASE FAULT REPORT

B. DEVICE EVALUATION REPORT

ARC FLASH STUDY

A. ARC FLASH STANDARD PERSONAL PROTECTIVE EQUIPMENT TABLE

B. ARC FLASH STUDY

C. EQUIPMENT LABELS

INPUT DATA

A. SKM MODEL INPUT

ONE LINE DIAGRAM

RECOMMENDATIONS

APPENDIX – A.1 - CVAMC – THREE-PHASE FAULT REPORT

APPENDIX – A.2 – FT THOMAS – THREE-PHASE FAULT REPORT

APPENDIX – B.1 - CVAMC – EQUIPMENT EVALUATION

APPENDIX – B.2 – FT THOMAS – EQUIPMENT EVALUATION

APPENDIX – C - ARC FLASH STANDARD PERSONAL PROTECTIVE TABLE

APPENDIX – D .1 – CVAMC – ARC FLASH STUDY

APPENDIX – D.2 – FT THOMAS – ARC FLASH STUDY

APPENDIX – E.1 - CVAMC – EQUIPMENT LABELS

APPENDIX – E.2 – FT THOMAS – EQUIPMENT LABELS

APPENDIX – F.1 - CVAMC – INPUT DATA

APPENDIX – F.2 – FT THOMAS - INPUT DATA

APPENDIX G.1 – CVAMC – ONE-LINE DIAGRAM

APPENDIX G.2 – FT THOMAS – ONE-LINE DIAGRAM

2023-05233 CVAMC Arch Flash Study PAGE 2

EXECUTIVE SUMMARY

Heapy has performed an Engineering Study of the electrical system for the existing Cincinnati Veteran’s Affair Medical Center Main Campus and Ft Thomas, KY Division.

The CVAMC overall system contains distribution from utility feeding a medium voltage distribution system feeding multiple medium voltage switchgear locations throughout the campus with redundant feeds. These pieces of medium voltage gear feed substations at each building, the substations transformer power down to 480V power which distributes throughout the building.

There are two generators feeding 480V power throughout the campus for emergency power, the emergency power feeds into distribution gear and then feeds multiple ATS’s for separation of emergency branches. Critical designated buildings have a separate generator(s) feeding the building independently of the main generators as well. These buildings are designated as critical through the VA’s Physical Security and Resilience Design Manual.

The Ft Thomas overall system contains distribution from utility feeding a pad mount transformer that transforms medium voltage into low voltage 208V distribution for the entire building. There is a generator that feeds multiple ATS’s for emergency power throughout the building as well.

This Study includes short circuit and arc flash studies for equipment starting at utility and certain equipment downstream. Information for this Study comes from existing records and contractor field verification of the existing equipment. Arc flash labels have been provided for the electrical equipment affected as part of this project and along the pathway of this equipment.

BACKGROUND

In an electrical distribution system, overcurrent protective devices, such as circuit breakers and fuses, must not only operate when the level of current exceeds a safe value, but must be able to interrupt the energy that results from the enormous amount of current that flows during a fault condition. If the overcurrent protective device does not safely open the circuit and interrupt the fault current, catastrophic failure of equipment and personal hazard can occur. Short circuit (fault current) analysis is used to evaluate a distribution systems ability to interrupt such occurrence.

Each year, more than 2,000 people are admitted to burn centers and hospitals with severe burns from arc flash. Arc flash is the result of a rapid release of energy due to an arcing fault between phase-phase, phase-neutral or phase-ground bus bars, typically limited to systems with a nominal voltage greater than 120 volts. Most arc faults are manually started with the cause of the short burning away, leaving air as the conductor. The fault is sustained by the resultant highly conductive plasma and emits enormous amounts of energy limited only by the impedance of the arc. This enormous energy discharge burns the bus bars and vaporizes the copper, creating an explosive volumetric increase (Holt 1). The copper expands at a ratio of approximately 40,000 to 1 creating a violent fiery explosion and molten shrapnel with speeds approaching 700 MPH devastating everything in its path. Arc flash temperatures can reach 35,000 deg. F; accompanied by sound pressure levels of 160 dB. Pressures associated with the blast can reach thousands of foot pounds, collapsing lungs, rupturing eardrums and knocking workers off their feet. The extreme temperature of the flash can cause direct burns to skin as well as ignite clothing, further damaging the individual. Arc flash can be a deadly hazard when unprotected.

Recognizing this safety problem, IEEE and NFPA developed exposure risk calculation methods and safety standards OSHA enforces for employee protection. Compliance with OSHA 1910 Arc Flash Safety procedures involve:

1.) Provide and demonstrate a safety program with defined responsibilities.

2.) Calculations for the degree of arc flash hazard.

3.) Correct personal protective equipment (PPE) for workers.

4.) Training for workers on the hazards of arc flash.

5.) Appropriate tools for safe working.

2023-05233 CVAMC Arch Flash Study PAGE 3

6.) Warning labels on equipment, including flash protection boundary, incident energy level, and required PPE level. (Holt 2)

Personal protective equipment (PPE) as defined in NFPA 70E 2024 is as follows:

Cal/cm2 Range Clothing Req’d + Gloves, Hard Hat and face shield 0 1.2 Shirt & pants or coverall, Nonmelting (ASTM F1506) or Untreated Fiber

1.2 12.0 Arc-rated shirt & pants + arc-rated coverall + arc-rated arc flash suit

12.0 40.0 Arc-rated shirt & pants + arc-rated coverall + arc-rated arc flash suit

40.0 >40.0 No approved PPE, do not work on live. (not in since 2014)

With higher levels of personal required protection, secondary dangers are introduced including bulky suits making some tasks more difficult, heat, fatigue and dark visors lowering visibility.

Overly conservative arc flash calculations can unnecessarily require high levels of protection and possibly increase the risk of a flash occurring, making accurate calculations critical.

Holt, Mike; Arc Flash article; 2003 Mike Holt Enterprises.

OBJECTIVES

The objectives of these studies are as follows:

1.) Calculate the available levels of fault current and shock hazard at the key points within the area being studied.

2.) Evaluate equipment to determine conformance with calculated ratings.

3.) Evaluate the arc flash hazards associated with each major piece of electrical distribution.

4.) Produce and provide arc flash and shock hazard labeling for evaluated equipment.

REFERENCES

Standards used for this Study includes: American National Standards Institute/Institute of Electrical and Electronic Engineers (ANSI/IEEE) Recommended Practices; IEEE Standard 1584 and Arc Flash Calculation method 2018, NFPA 70 (National Electrical Code, 2023), NFPA 70E – 2024 Standard for Electrical Safety in the Workplace and recommendations of Electrical Manufacturers.

WARRANTY

This Study is based on sound engineering judgment. If it is determined that the Study does not satisfy the scope of work as in agreement, Heapy will modify this Study to satisfy the requirements.

Heapy worked with a third-party contractor for on-site data collection. Heapy does not take responsibility for any equipment, feeder, on-site information, etc that was not verified correctly.

LIMITS OF LIABILITY

Other than fulfilling the requirements of the Warranty, Heapy does not assume the application of the Study and shall not be liable for any damages resulting from the failure of the system to operate in accordance to predictions of this Study.

2023-05233 CVAMC Arch Flash Study PAGE 4

SHORT-CIRCUIT STUDY

Heapy used PTW DAPPER Version 11.0 software from SKM Systems Analysis, Inc. to perform the short-circuit modeling and calculations. The electrical system as installed features distribution as identified in the one-line diagrams included in this report.

The unbalanced bolted three-phase short circuit fault current is calculated for all busses shown on the one-line diagram. Multiple scenarios were created for faults coming from utility, generators, or a combination to find the worst-case scenario. The biggest fault values were utilized in the report. The Short-Circuit Report includes Unbalanced Three-phase Fault Report and an Equipment Evaluation.

A. THREE-PHASE FAULT REPORT

The balanced three-phase fault report section lists information about each bus as if a three-phase bolted fault occurred at that individual bus. This table includes: bus name, bus voltage, RMS symmetrical fault current, among other items. Refer to APPENDIX A.1 and A.2.

B. DEVICE EVALUATION REPORT

The device evaluation section gives a brief listing of fault information about each overcurrent protective device. This information includes: connected bus, device name, bus voltage, frame voltage, frame/trip, status, calculated kA, device kA, and interrupt rating. The status column shows all devices that are/aren’t rated for the available fault current. Devices which are labeled FAIL should be replaced with new devices with appropriate ratings. Refer to APPENDIX B.1 and B.2.

The following table was developed to document the evaluation of protective devices in the short circuit study. The descriptions for the columns are as follows:

Column Heading Description

Connected Bus Bus that the overcurrent device is connected to.

Device Name Device identification used in DAPPER short circuit referenced with the single line.

Bus Voltage Nominal operating line-to-line voltage, volts.

Device Voltage Nominal operating line-to-line voltage, volts.

Frame/Trip Trip Amperage of the current device.

Status Device ratings are compared to calculated fault current availability to determine if ratings are exceeded.

“PASSED” if rating is greater than available. “FAILED” if rating is exceeded.

Calc Int kA The calculated available fault current.

Dev Int kA The fault current rating of the equipment.

ARC FLASH STUDY

Heapy used PTW A_FLASH Ver. 11.0 software from SKM Systems Analysis, Inc. to perform arc flash studies to evaluate arc flash hazards associated with the electrical distribution system. Arc

2023-05233 CVAMC Arch Flash Study PAGE 5 flash levels are calculated based upon NFPA 70E 2018 Annex D.4 - IEEE 1584 incident energy calculation methods. Arc flash incident energy recommended personal protective equipment (PPE) and flash protection boundaries are defined.

A. ARC FLASH STANDARD PERSONAL PROTECTIVE EQUIPMENT TABLE

The table indicates the Personal Protective Equipment (PPE) required to prevent an incurable burn at the working distance during an arc flash. This table reflects NFPA 70E, 2024 edition standards. Refer to APPENDIX C.1 and C.2.

B. ARC FLASH STUDY

This study evaluates arc flash hazards associated with the electrical distribution system using the protective devices at their listed settings.

Locations were analyzed to determine the level of arc flash incident energy to which a worker might be exposed during an arc flash event. The details of the calculation results are in APPENDIX D.1 and D.2.

Note: In the required protective FR clothing class, some equipment are marked with a (*N9). This indicates when maximum arcing durations were reached prior to the breaker tripping. The maximum duration was set to 2 seconds for the purposes of this report.

C. EQUIPMENT LABELS

Refer to APPENDIX E.1 and E.2. The equipment labels provide additional information about required PPE, such as limited approach boundary and restricted approach boundary from NFPA 70E-2024 130.4 and table 130.4(E)(a).

1.) Limited approach boundary is an approach distance from an exposed live part within which a shock hazard exists.

3.) Restricted approach boundary is an approach distance from an exposed live part within which there is an increased risk of shock, due to electrical arc over combined with inadvertent movement, for personnel working in close proximity to the live part.

INPUT DATA

Data listed in APPENDIX F.1 and F.2 is the basis for both short circuit and arc flash studies.

Components included in the study and brief attribute listings are as follows.

A. SKM MODEL INPUT

1. UTILITY AND GENERATOR SOURCES

The utility section contains information about each utility source that contributes fault current to the system. Fault contribution sources can include the utility, generators, and motors. Motor contribution from motors served by VFD’s and under 25HP do not have a significant influence on the fault value due to limits of re-generation power; these have been intentionally omitted. Information includes;

Utility name, rated voltage, MVA contribution, symmetrical fault current contribution 3PH and SLG, X/R 3PH, and X/R SLG. Correspondence with the local electrical utility is included to document the characteristics mentioned above.

2. CABLE

2023-05233 CVAMC Arch Flash Study PAGE 6

The cable section contains information about each cable/feeder including;

component name conductor material, insulation type, class, voltage, conductor description, size, length, ampacity, temperature, quantity of parallel sets, ground size, neutral size, and short circuit rating (kA).

3. 2-WINDING TRANSFORMER

The transformer section contains information about each transformer including:

component name, nominal self cooled KVA rating, primary and secondary line-to-line voltages, primary and secondary connection, primary and secondary tap percentages, secondary ampacity (FLA), and zero impedance (%Z).

4. LOW VOLTAGE BREAKER

The LV breaker section contains information about each breaker (including associated ground fault relays) including : component name, manufacturer, description, frame/sensor size, short circuit ratings (kA) and settings (LTPU long time pick up, LTD long time delay, STPU short time pick up, STD short time delay, INST instantaneous pick up, GFPU ground fault pick up, and GFD ground fault delay where applicable).

5. FUSE

The fuse section contains information about each fuse including: component name, manufacturer, description, cartridge/trip (A) and short circuit rating (kA).

ONE LINE DIAGRAM

PTW Version 11.0 software from SKM Systems Analysis, Inc. was used to create the one-line diagram. The one-line diagram represents the overall model of the existing electrical system as provided with existing drawings and from contractor field visits. Any information that was not gathered is noted in the recommendations. Components out of service will appear lighter than connected components. The one-line diagram depicts the building during normal operation with the utility source energized. Refer to Appendix G.1 and G.2 for one-line diagram.

RECOMMENDATIONS

One-Line Distribution Diagram

The existing building one-line diagram has been updated for this study and was utilized as the basis for the model. Field review and contractor information of numerous components of the system was undertaken to determine the installed condition for analysis.

Out of Scope, Assumptions, Issues

- N/A

Short-Circuit Evaluation

Data was gathered for the installed equipment for purposes of this report. The calculated faults thru the distribution was performed.

Issues

See above in one line diagram for assumption made on arc fault current throughout distribution. Changes to this value can provide a more accurate result of devices being correctly rated or not.

Ft Thomas

2023-05233 CVAMC Arch Flash Study PAGE 7 o ATS 2 Rating is out of compliance for kA rating. Calculated Isc Ka is

19.720kA and the rating of this device is 10kA. Rating is out of compliance for breaker upstream. Breaker from MEDP and MS feed this 150A ATS from a 400A breaker. ATS 2 needs to be replaced with a 400A ATS rated for 20kA rating minimum or breaker in MEDP and MS needs to be replaced with 150A trip.

Feeder from MS is #1/0 CU which is not rated high enough for the 400A breaker. Feeder to be replaced with 2 sets of #1/0 CU minimum.

Feeder from ATS 2 to EDP-L is #1/0 CU. This is to small for the 150A ATS and the 400A breakers upstream. Feeder to be replaced with 2 sets of #1/0 CU minimum.

o ATS 1 Both feeders off the load side of the ATS are fed from 1 set of 500

KCMIL which is too small for the 800A breaker settings upstream.

Feeder needs to be replaced with 2 sets of 500 for each feed downstream.

o MCC Feeder to “Main Panelboard” is 1 set of 2/0 CU which is to small for the 250A rated breaker. Feeder needs to be replaced with 250KCMIL CU minimum.

“Main” Panelboard is rated at 225A which is lower then the 250A breaker feeding this equipment. Panel needs to be replaced with 250A panel or breaker needs to be replaced with 225A breaker trip.

Feeder to MCCP is 1 set of #2/0 CU which is to small for the 250A rated upstream breaker. Feeder to be replaced with 250KCMIL CU minimum.

Panel MCCP is rated at 225A which is too small for the 250A breaker and feeder. Replace MCCP with a 250A minimum panel rating or replace upstream breakers with 225A minimum breaker trip.

o S.PBB Breaker to “NEW PANEL” Breaker is set at 100A rating while the feeder size is only 1 set of #4

CU which is not rated for 100A load. Feeder needs to be replaced with #1 CU minimum or breaker to be replaced with 70A breaker.

CVAMC

o B2 DP1 – N2A/B/C

Multiple feeders fed through upstream breaker to panels N2A, N2B, and N2C are sized at #3/0 CU rated at 200A and upstream breaker is set for 225A. Breaker to be replaced with 200A trip breaker or replace all feeders with #250 CU minimum.

o B13 ATS 13C Main transformer does not have OCPD protection on the secondary side. This feeder runs through the building and is only protected by the primary side OCPD.

o B13 SB13C – DB13C Feeder to distribution DB13C sized at 2 sets of #350 KCMIL rated at

620A while breaker set at 800A trip. Replace feeder with 3 sets of 250CU minimum or set trip at 600A feeding DB13C.

o B14 MDP – P2A

2023-05233 CVAMC Arch Flash Study PAGE 8

B14 P2A panel fed with 2AWG wire rated at 115A but the upstream breaker is 200A trip. Breaker needs to be replaced with 100A breaker or wire needs to be upsized to 3/0AWG minimum.

o B15 E1 – E2 Feeder to panel B15 15E2 sized at #5 CU rated at 55A and upstream breaker rating is set for 150A. Feeder needs to be replaced with #1/0 CU minimum.

o B15 LPB/LP2/LP3/LP4 Feeders for all panels fed from 225A breaker out of MDP is fed with

2/0AWG or 175A wire. This does not comply with 80% derating from breaker and should all be replaced with minimum 3/0 CU AWG wire or breaker should be replaced with 175A breaker.

o DPA – 24A Panel 2A4 is fed with 2/0AWH which is rated at 175A and the upstream breaker is 300A. Needs to be provided with OCPD main breaker protection or wire needs to change to at minimum 350kCMIL.

o DPLF – TRAY CONV Tray CONV is fed with 2AWG wire rated at 115A but the upstream breaker is 200A trip. Breaker needs to be replaced or wire needs to be upsized to 3/0AWH minimum.

o DS-1B – 1C2PA Feeder to panel IC2PA sized at #4 CU rated at 70A and upstream breaker rated at 100A. Feeder to be replaced with #1 CU minimum.

o ESWB C2BB Panel feeds transformer T-C2BB from a 30A QBHW breaker which is rated for 208V. Breaker needs to be replaced with a 30A 480V breaker.

o ESWB B40a Feeder to B40b has no OCPD device and panel is B40b is rated for

400A. 400A OCPD Device needs to be added or panel needs to be replaced with 600A rated panel.

o ESWB ATS-26 Feeder and equipment ATS-26 is rated at 400A and upstream breaker is rated at 600A. Breaker trip to be replaced with 400A trip breaker.

o ESWB T-3RD FLR UPS Transformer secondary feeder sized at 2 sets of #4/0 CU rated at

460A and transformer is 225kVA which has a possible 780A on secondary. Secondary OCPD at panel is 600A. Feeder to be replaced with 2 sets of #350kCMIL CU minimum.

o GDE LDPF – LSF2 Feeder to LSF2 is sized at #6 CU rated at 55A while upstream breaker rated at 100A trip. Feeder to be replaced with #1 CU minimum.

o US-1A – ATS 1E4

2023-05233 CVAMC Arch Flash Study PAGE 9

Feeder to ATS 1E4 is sized at #600 KCMIL rated for 420A while ATS 1E4 and upstream breaker is rated at 600A. Feeder to be replaced with 2 sets of #350 KCMIL minimum.

o US1P - MCCD Feeder to MCCD sized at #350kCMIL rated at 310A while upstream breaker is rated at 400A. Feeder to be replaced with 2 sets of #3/0 CU minimum.

o Panel and Equipment Ratings The following equipment listed has been noted to have a higher short circuit available than the equipment is rated for.

For Example Panel A is rated for 10kA but has 28kA available at the panel. This panel needs to be replaced with appropriately rated equipment.

All panel ratings are based on worst case calculation. The preferred utility feed for the CVAMC main campus is lower than the alternate feed which is considered worst case. Busses, ATS’s, over current protection devices, etc are noted below when rated at an acceptable tolerance to available fault current under the preferred feed and not the alternate.

Ft Thomas – Panels

ECB.1 – Rated at 10kA, 14.66kA Available Over Current Protective Devices

EDP-C – All feeder devices within EDP-C are rated at 22kA, 25kA is available at this panel.

CVAMC –

Panels

Typical panel ratings are based on lowest rated over current device within equipment. These can be fixed by replacing individual devices within equipment.

1B2 – Rated at 10kA, 11.43 Available 2C1 – Rated at 10kA, 11.64 kA Available 4E1 – Rated at 10kA, 10.21 kA Available 6D3 – Rated at 10kA, 10.34 kA Available B14 P2A, Rated at 10kA, 18.52kA Available o This panel does have available series rating of 22kA and therefor is shown as acceptable in our report.

B15 15EMB – Rated at 10kA, 10.63 kA Available B2 Elev 1 CP – Rated at 5kA, 9.91 Available B2 Elev 2 CP – Rated at 5kA, 13.19kA Available B2 Elev 3 CP – Rated at 5kA, 18.23kA Available B2 Elev 4 CP – Rated at 5kA, 7.64kA Available B2 Elev CP – Rated at 5kA, 9.13kA Available BA1 – Rated at 10kA, 15.49kA Available BC1L – Rated at 14kA, 16.25kA Available BD3 – Rated at 10kA, 17.12kA Available BE1 – Rated at 10kA, 14.48kA Available BE3 – Rated at 10kA, 13.41kA Available PP-1 AHU-30 – Rated at 10kA, 42.96kA Available

MCC

10TH FLR MCC-B – Rated at 10kA, 28.42kA Available

2023-05233 CVAMC Arch Flash Study PAGE 10

MCC East - Rated at 25kA, 25.01kA Available o Under preferred source this MCC is in compliance with 23.41kA available.

MCC-2 – Rated at 25kA, 44.26kA Available MCC-G – Rated at 25kA, 30.5kA Available

ATS

ATS ELEV P17 Load – Rated at 10kA, 13.11kA Available PG ATS EM2 – Rated at 10kA, 11.56kA Available ATS ESWB F-3 – Rated at 51.43kA, 51.43kA Available o Under preferred source this ATS is in compliance with 46kA available.

Non-Fused Disconnect B15 Chiller Disc – Rated at 10kA, 10.54kA Available B15 FP EM Disc – Rated at 10kA, 10.27kA Available

Over Current Protective Devices

4E1 MCB – Rated at 10kA, 10.21kA Available 6D3 MCB - Rated at 10kA, 10.34kA Available B15 EMB EM - Rated at 10kA, 10.63kA Available PP1 AHU30-1 - Rated at 10kA, 42.97kA Available PP1 AHU30-2 - Rated at 10kA, 42.97kA Available PP1 AHU30-3 - Rated at 10kA, 42.97kA Available PP1 LV AHU30 – Rated at 25kA, 40.91kA Available BC1L MCB – Rated at 14kA, 16.25kA Available C2B TC2BB - Rated at 22kA at 240V.

o This panel is 480V panel. Breaker needs to be replaced with 480V breaker.

2023-05233 CVAMC Arch Flash Study PAGE 11

APPENDIX – A.1 - CVAMC – THREE-PHASE FAULT REPORT

DAPPER Unbalanced Fault Report

Comprehensive Short Circuit Study Settings

Three Phase Fault

Single Line to Ground

Line to Line Fault

Line to Line to Ground

All BusesFaulted Bus

Yes

Yes

Yes

No

No

Motor Contribution

Transformer Tap

Xformer Phase Shift

Yes

Yes

Bus Voltages

Branch Currents

Phase or Sequence

Fault Current Calculation

Asym Fault Current at Time 0.50

First Bus From Fault

First Branch From Fault

Report phase quantities

Initial Symmetrical RMS (with 1/2 Cycle Asym)

Cycles

VAMC CINCINNATI

Project: VA CINCINNATI BLDG 1 BACKUP 5-7-2024

One Line Diagram

Heapy Project # 2023-2024 ARC FLASH STUDY Print Date: March 8, 2024

Fault Location

Bus Name

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom

Amps 3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

(E)C7D 208 4,786 0.92 3,0271.72 4,791 4,786 4,786 4,7860.36 0.77

10A1 208 7,058 1.33 4,6532.54 7,121 7,058 7,058 7,0580.56 1.11

10TH FLR MCC-B 480 26,289 2.49 21,83621.86 28,320 26,289 26,289 26,2896.05 1.86

1A1 208 13,152 1.83 9,2024.74 13,569 13,152 13,152 13,1521.11 1.49

1A1L 480 5,020 0.46 3,0464.17 5,020 5,020 5,020 5,0200.84 0.36

1A1P 208 3,107 0.57 1,8891.12 3,107 3,107 3,107 3,1070.23 0.48

1A2 208 12,892 1.82 9,0024.64 13,292 12,892 12,892 12,8921.08 1.48

1A3 208 12,172 1.78 8,4494.38 12,523 12,172 12,172 12,1721.01 1.46

1B1 208 11,560 1.83 8,0014.16 11,925 11,560 11,560 11,5600.96 1.50

1B1P 208 3,585 0.69 2,2081.29 3,585 3,585 3,585 3,5850.27 0.58

Fault Location

Bus Name

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

1B2 208 11,238 1.78 7,7484.05 11,559 11,238 11,238 11,2380.93 1.45

1C1 208 13,217 1.81 9,3854.76 13,624 13,217 13,217 13,2171.13 1.56

1C1L 480 10,980 0.70 7,0339.13 10,981 10,980 10,980 10,9801.95 0.52

1C1P 208 5,412 0.70 3,3611.95 5,413 5,412 5,412 5,4120.40 0.58

1C1PA 208 1,041 0.23 6110.38 1,041 1,041 1,041 1,0410.07 0.19

1C2 208 12,755 1.73 9,0604.60 13,091 12,755 12,755 12,7551.09 1.52

1C2L 480 5,279 0.47 3,2094.39 5,279 5,279 5,279 5,2790.89 0.37

1C2P 208 3,882 0.61 2,3761.40 3,882 3,882 3,882 3,8820.29 0.51

1C2PA 208 3,698 0.59 2,2561.33 3,698 3,698 3,698 3,6980.27 0.49

1C2PB 208 3,445 0.55 2,0921.24 3,445 3,445 3,445 3,4450.25 0.46

1C3L 480 3,400 0.40 2,0392.83 3,400 3,400 3,400 3,4000.57 0.32

1C3P 208 2,041 0.52 1,2300.74 2,041 2,041 2,041 2,0410.15 0.44

1C4P 208 5,715 0.66 3,5382.06 5,716 5,715 5,715 5,7150.42 0.54

1C5L 480 4,170 0.43 2,5143.47 4,170 4,170 4,170 4,1700.70 0.34

1C5P 208 6,151 1.05 3,9552.22 6,166 6,151 6,151 6,1510.47 0.87

1C6P 208 6,051 1.04 3,8882.18 6,066 6,051 6,051 6,0510.47 0.87

1CEC-4 208 566 1.90 5780.20 587 566 566 5660.07 1.95

1CEC2 480 2,848 0.54 1,7282.37 2,848 2,848 2,848 2,8480.48 0.45

1CEC3 208 1,296 1.91 1,3290.47 1,344 1,296 1,296 1,2960.16 1.91

1CEC3 FDS 480 4,491 0.69 2,7863.73 4,492 4,491 4,491 4,4910.77 0.56

1CEC3 NFDS 480 4,593 0.70 2,8563.82 4,594 4,593 4,593 4,5930.79 0.58

1CEC4 208 1,338 1.70 1,4050.48 1,371 1,338 1,338 1,3380.17 1.83

1D1 208 15,786 1.92 11,2665.69 16,378 15,786 15,786 15,7861.35 1.55

1D2 208 15,415 1.90 10,9685.55 15,975 15,415 15,415 15,4151.32 1.54

1E1 208 13,490 1.86 9,4494.86 13,943 13,490 13,490 13,4901.13 1.51

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

1E2 208 12,956 1.83 9,0364.67 13,369 12,956 12,956 12,9561.09 1.49

1E3 208 14,343 1.58 10,3235.17 14,611 14,343 14,343 14,3431.24 1.45

1E7 208 14,170 2.22 9,9435.10 14,983 14,170 14,170 14,1701.19 1.80

1EC1 480 4,212 0.68 2,6093.50 4,212 4,212 4,212 4,2120.72 0.56

1EC3 480 2,860 0.54 1,7362.38 2,860 2,860 2,860 2,8600.48 0.45

1F1 208 7,673 1.04 4,9692.76 7,691 7,673 7,673 7,6730.60 0.86

1F1 (K) 208 12,371 1.89 8,6354.46 12,807 12,371 12,371 12,3711.04 1.55

1F2 208 6,847 0.89 4,3592.47 6,853 6,847 6,847 6,8470.52 0.73

1F2 (K) 208 12,004 1.83 8,3424.32 12,385 12,004 12,004 12,0041.00 1.50

1KA 208 6,531 1.74 4,3802.35 6,704 6,531 6,531 6,5310.53 1.46

1KB 208 4,749 1.37 3,0991.71 4,796 4,749 4,749 4,7490.37 1.15

1KC 208 22,224 1.30 15,8678.01 22,399 22,224 22,224 22,2241.91 0.98

1KD 208 21,660 1.27 15,4737.80 21,816 21,660 21,660 21,6601.86 0.97

1KE 208 22,224 1.30 15,8678.01 22,399 22,224 22,224 22,2241.91 0.98

203 CB LINE 480 6,470 0.63 4,0345.38 6,470 6,470 6,470 6,4701.12 0.49

203 XRAY MACH 480 5,910 0.59 3,6604.91 5,910 5,910 5,910 5,9101.01 0.47

243 CB LINE 480 14,468 1.43 10,28112.03 14,645 14,468 14,468 14,4682.85 1.10

243 XRAY MACH 480 12,262 1.15 8,37810.19 12,314 12,262 12,262 12,2622.32 0.89

246 208 5,704 0.66 3,5322.05 5,704 5,704 5,704 5,7040.42 0.54

246 CB LINE 480 10,853 0.95 7,1959.02 10,867 10,853 10,853 10,8531.99 0.73

246 XRAY MACH 480 9,353 0.84 6,0717.78 9,358 9,353 9,353 9,3531.68 0.65

248 CB LINE 480 11,852 1.49 8,2859.85 12,023 11,852 11,852 11,8522.30 1.18

248 XRAY MACH 480 9,843 1.12 6,5988.18 9,880 9,843 9,843 9,8431.83 0.89

249 CB LINE 480 9,705 0.92 6,3678.07 9,715 9,705 9,705 9,7051.76 0.71

249 XRAY MACH 480 8,280 0.81 5,3236.88 8,283 8,280 8,280 8,2801.48 0.64

252 208 7,826 0.85 4,9842.82 7,831 7,826 7,826 7,8260.60 0.69

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

252 CB LINE 480 13,646 1.25 9,50011.35 13,735 13,646 13,646 13,6462.63 0.96

252 XRAY MACH 480 10,543 0.92 6,9558.77 10,554 10,543 10,543 10,5431.93 0.71

2A1 208 11,196 1.73 7,7124.03 11,490 11,196 11,196 11,1960.93 1.42

2A2 208 11,007 1.72 7,5713.97 11,291 11,007 11,007 11,0070.91 1.42

2A3 208 10,476 1.70 7,1753.77 10,732 10,476 10,476 10,4760.86 1.40

2A4 208 9,880 1.57 6,7043.56 10,059 9,880 9,880 9,8800.81 1.29

2B1 208 11,425 1.82 7,8994.12 11,781 11,425 11,425 11,4250.95 1.49

2B2 208 11,165 1.80 7,7034.02 11,503 11,165 11,165 11,1650.93 1.48

2B3 208 10,678 1.78 7,3383.85 10,984 10,678 10,678 10,6780.88 1.46

2C1 208 10,872 1.74 7,4773.92 11,163 10,872 10,872 10,8720.90 1.43

2C1L 480 3,633 0.41 2,1823.02 3,633 3,633 3,633 3,6330.60 0.33

2C2 208 10,584 1.70 7,2543.81 10,843 10,584 10,584 10,5840.87 1.40

2C5P 208 4,104 0.95 2,5931.48 4,110 4,104 4,104 4,1040.31 0.80

2C6P 208 4,071 0.95 2,5711.47 4,076 4,071 4,071 4,0710.31 0.80

2CA 208 4,796 0.56 3,5931.73 4,796 4,796 4,796 4,7960.43 0.60

2CEC1 208 1,292 1.33 1,4120.47 1,303 1,292 1,292 1,2920.17 1.53

2D1 208 14,505 1.86 10,2445.23 14,990 14,505 14,505 14,5051.23 1.51

2D2 208 13,507 1.81 9,4634.87 13,919 13,507 13,507 13,5071.14 1.47

2DX 208 13,795 1.93 9,7274.97 14,318 13,795 13,795 13,7951.17 1.57

2E1 208 13,174 1.59 9,0974.75 13,423 13,174 13,174 13,1741.09 1.28

2E2 208 12,543 1.53 8,6034.52 12,747 12,543 12,543 12,5431.03 1.24

2E3 208 12,153 1.49 8,3014.38 12,333 12,153 12,153 12,1531.00 1.21

2E4 208 11,786 1.46 8,0194.25 11,945 11,786 11,786 11,7860.96 1.18

2F1 208 3,848 0.90 2,4191.39 3,852 3,848 3,848 3,8480.29 0.76

2F1 (K) 208 10,864 1.66 7,4473.91 11,110 10,864 10,864 10,8640.89 1.36

2F2 208 3,799 0.90 2,3871.37 3,802 3,799 3,799 3,7990.29 0.76

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

2F2 (K) 208 4,840 1.08 3,1001.74 4,854 4,840 4,840 4,8400.37 0.90

2FH 208 10,504 1.62 7,1693.78 10,717 10,504 10,504 10,5040.86 1.33

2PF1 480 21,167 2.55 16,76317.60 22,905 21,167 21,167 21,1674.65 1.98

2PF2 480 20,751 2.53 16,36117.25 22,423 20,751 20,751 20,7514.53 1.97

3A1 208 13,183 1.80 9,2154.75 13,580 13,183 13,183 13,1831.11 1.47

3A2 208 13,514 1.85 9,4834.87 13,958 13,514 13,514 13,5141.14 1.50

3B1 208 10,074 1.74 6,8893.63 10,344 10,074 10,074 10,0740.83 1.44

3B2 208 9,748 1.68 6,6763.51 9,975 9,748 9,748 9,7480.80 1.41

3C1 208 10,035 1.70 6,8563.62 10,281 10,035 10,035 10,0350.82 1.40

3C2 208 9,669 1.64 6,5763.48 9,878 9,669 9,669 9,6690.79 1.36

3C5P 208 3,238 0.91 2,0311.17 3,241 3,238 3,238 3,2380.24 0.77

3C6P 208 3,203 0.91 2,0091.15 3,206 3,203 3,203 3,2030.24 0.77

3CEC1 208 2,263 0.95 2,6590.82 2,266 2,263 2,263 2,2630.32 1.14

3CEC2 208 2,240 0.95 2,6080.81 2,243 2,240 2,240 2,2400.31 1.12

3D1 208 13,233 1.80 9,2514.77 13,627 13,233 13,233 13,2331.11 1.46

3D2 208 12,885 1.78 8,9824.64 13,257 12,885 12,885 12,8851.08 1.45

3E1 208 8,285 1.61 5,5732.98 8,450 8,285 8,285 8,2850.67 1.34

3E2 208 8,012 1.60 5,3792.89 8,167 8,012 8,012 8,0120.65 1.33

3F1 208 1,626 2.38 1,6330.59 1,739 1,626 1,626 1,6260.20 2.32

3RD FL UPS LINE 480 13,867 1.05 9,48211.53 13,902 13,867 13,867 13,8672.63 0.80

3RD FL UPS2 208 6,146 1.39 5,4502.21 6,213 6,146 6,146 6,1460.65 1.19

3RD FL UPS2 CB L 208 8,688 1.84 9,3903.13 8,971 8,688 8,688 8,6881.13 1.92

3RD FL UPS3 208 5,671 1.33 4,8592.04 5,721 5,671 5,671 5,6710.58 1.12

4A1 208 10,420 1.70 7,1343.75 10,674 10,420 10,420 10,4200.86 1.40

4A2 208 10,256 1.69 7,0123.69 10,501 10,256 10,256 10,2560.84 1.39

4B1 208 9,351 1.70 6,3583.37 9,582 9,351 9,351 9,3510.76 1.41

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

4B2 208 8,565 1.64 5,7813.09 8,747 8,565 8,565 8,5650.69 1.36

4B3 208 8,803 1.68 5,9603.17 9,007 8,803 8,803 8,8030.72 1.39

4C1 208 9,372 1.52 6,6383.38 9,522 9,372 9,372 9,3720.80 1.46

4C2 208 9,601 1.55 6,8243.46 9,767 9,601 9,601 9,6010.82 1.50

4CCU 480 13,432 1.40 9,41211.17 13,583 13,432 13,432 13,4322.61 1.09

4D1 208 12,015 1.74 8,3184.33 12,335 12,015 12,015 12,0151.00 1.42

4E1 208 10,084 1.69 6,8773.63 10,326 10,084 10,084 10,0840.83 1.39

4E2 208 9,055 1.64 6,1273.26 9,250 9,055 9,055 9,0550.74 1.36

4E3 208 9,183 1.65 6,2193.31 9,383 9,183 9,183 9,1830.75 1.36

4TH FL UPS LINE S 208 6,172 1.67 4,0912.22 6,314 6,172 6,172 6,1720.49 1.40

4TH FL UPS PNL1 208 5,979 1.70 3,9942.15 6,127 5,979 5,979 5,9790.48 1.42

4TH FL UPS PNL2 208 5,926 1.70 3,9572.13 6,071 5,926 5,926 5,9260.48 1.42

4TH PUMP PNL 480 9,526 1.03 6,3187.92 9,547 9,526 9,526 9,5261.75 0.82

5A1 208 10,256 1.69 7,0123.69 10,501 10,256 10,256 10,2560.84 1.39

5A2 208 10,097 1.68 6,8953.64 10,335 10,097 10,097 10,0970.83 1.39

5B1 208 9,006 1.69 6,1073.24 9,220 9,006 9,006 9,0060.73 1.39

5B2 208 8,806 1.65 5,9563.17 9,001 8,806 8,806 8,8060.72 1.37

5C1 208 9,108 1.51 6,4543.28 9,247 9,108 9,108 9,1080.78 1.46

5C2 208 8,900 1.48 6,2873.21 9,027 8,900 8,900 8,9000.76 1.43

5C3 208 8,291 1.32 5,7822.99 8,361 8,291 8,291 8,2910.69 1.24

5CCU 480 11,713 1.20 7,9779.74 11,774 11,713 11,713 11,7132.21 0.93

5D1 208 11,063 1.70 7,6023.99 11,332 11,063 11,063 11,0630.91 1.39

5D2 208 10,763 1.66 7,3703.88 11,003 10,763 10,763 10,7630.89 1.36

5E1 208 14,431 1.91 10,1845.20 14,962 14,431 14,431 14,4311.22 1.55

5F1 208 4,322 0.60 2,6461.56 4,322 4,322 4,322 4,3220.32 0.50

5F2 208 4,169 0.59 2,5481.50 4,169 4,169 4,169 4,1690.31 0.49

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

6A1 208 8,559 1.60 5,7713.08 8,725 8,559 8,559 8,5590.69 1.33

6A2 208 8,700 1.62 5,8773.13 8,878 8,700 8,700 8,7000.71 1.34

6B1 208 8,496 1.66 5,7383.06 8,687 8,496 8,496 8,4960.69 1.38

6B2 208 8,609 1.67 5,8193.10 8,804 8,609 8,609 8,6090.70 1.38

6C1 208 8,541 1.63 5,7673.08 8,720 8,541 8,541 8,5410.69 1.35

6C2 208 8,287 1.62 5,5852.99 8,456 8,287 8,287 8,2870.67 1.34

6C3 208 8,075 1.58 5,4272.91 8,226 8,075 8,075 8,0750.65 1.32

6D1 208 10,699 1.68 7,3323.85 10,951 10,699 10,699 10,6990.88 1.38

6D2 208 10,469 1.67 7,1623.77 10,711 10,469 10,469 10,4690.86 1.38

6D3 208 10,200 1.63 6,9553.67 10,416 10,200 10,200 10,2000.84 1.35

6F1 208 3,051 0.53 1,8461.10 3,051 3,051 3,051 3,0510.22 0.44

6F2 208 2,973 0.52 1,7971.07 2,973 2,973 2,973 2,9730.22 0.43

7A1 208 8,662 1.62 5,8503.12 8,838 8,662 8,662 8,6620.70 1.34

7A2 208 8,430 1.58 5,6773.04 8,588 8,430 8,430 8,4300.68 1.31

7B1 208 7,923 1.60 5,3192.85 8,077 7,923 7,923 7,9230.64 1.33

7B2 208 8,107 1.64 5,4592.92 8,282 8,107 8,107 8,1070.66 1.36

7C1 208 8,114 1.61 5,4612.92 8,277 8,114 8,114 8,1140.66 1.34

7C2 208 7,951 1.58 5,3392.86 8,100 7,951 7,951 7,9510.64 1.32

7D1 208 8,988 1.21 5,9363.24 9,037 8,988 8,988 8,9880.71 0.99

7D2 208 8,253 1.16 5,4132.97 8,291 8,253 8,253 8,2530.65 0.96

8A1 208 8,020 1.59 5,3892.89 8,173 8,020 8,020 8,0200.65 1.32

8A2 208 7,882 1.56 5,2862.84 8,023 7,882 7,882 7,8820.63 1.30

8B1 208 6,886 1.19 4,4902.48 6,921 6,886 6,886 6,8860.54 0.99

8B2 208 6,733 1.18 4,3832.43 6,766 6,733 6,733 6,7330.53 0.98

8B4 208 3,561 0.73 2,2021.28 3,562 3,561 3,561 3,5610.26 0.62

8C1 208 6,809 1.55 4,5372.45 6,927 6,809 6,809 6,8090.54 1.30

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

8C2 208 6,692 1.53 4,4522.41 6,803 6,692 6,692 6,6920.53 1.28

8D1 208 8,853 1.60 5,9813.19 9,027 8,853 8,853 8,8530.72 1.33

8D2 208 8,975 1.61 6,0703.23 9,154 8,975 8,975 8,9750.73 1.33

9A1 208 7,409 1.57 4,9562.67 7,542 7,409 7,409 7,4090.60 1.31

9B1 208 6,688 1.57 4,4542.41 6,809 6,688 6,688 6,6880.53 1.31

9C1 208 6,490 1.54 4,3142.34 6,599 6,490 6,490 6,4900.52 1.29

9CCU 480 8,815 0.93 5,7487.33 8,826 8,815 8,815 8,8151.59 0.74

9D1 208 8,618 1.60 5,8123.10 8,784 8,618 8,618 8,6180.70 1.32

ATS 1E3 LOAD S 208 20,904 1.92 15,2497.53 21,681 20,904 20,904 20,9041.83 1.49

ATS 1E4 LOAD S 208 13,886 2.24 9,4215.00 14,700 13,886 13,886 13,8861.13 1.79

ATS 1E5 LOAD S 208 16,223 2.31 11,2615.84 17,261 16,223 16,223 16,2231.35 1.84

ATS 1E6 LOAD S 208 22,527 1.99 16,1678.12 23,464 22,527 22,527 22,5271.94 1.51

ATS 1E7 LOAD S 208 23,429 2.57 17,7008.44 25,388 23,429 23,429 23,4292.13 2.03

ATS 1E8 LOAD S 208 11,658 1.69 8,5524.20 11,935 11,658 11,658 11,6581.03 1.94

ATS ELEV P17 LO 480 12,781 0.81 8,25810.63 12,787 12,781 12,781 12,7812.29 0.58

ATS SURGE STE L 480 21,730 1.89 16,69118.07 22,496 21,730 21,730 21,7304.63 1.40

ATS-10 LOAD SI 480 12,247 2.09 8,78010.18 12,838 12,247 12,247 12,2472.43 1.68

ATS-11 LOAD SI 480 16,967 1.94 12,41314.11 17,619 16,967 16,967 16,9673.44 1.48

ATS-12 LOAD SI 480 9,867 1.47 6,4498.20 10,002 9,867 9,867 9,8671.79 1.13

ATS-14 LOAD SI 208 38,220 2.96 32,80913.77 42,562 38,220 38,220 38,2203.94 2.27

ATS-16 LOAD SI 208 33,880 2.40 27,75312.21 36,277 33,880 33,880 33,8803.33 1.81

ATS-17 FDS 208 5,369 0.88 3,3911.93 5,373 5,369 5,369 5,3690.41 0.73

ATS-17 LOAD SI 208 20,717 1.25 14,6087.46 20,854 20,717 20,717 20,7171.75 0.95

ATS-21 EDPEQ L 480 19,363 2.04 14,74216.10 20,238 19,363 19,363 19,3634.09 1.56

ATS-26 LOAD SI 480 13,414 2.12 9,46711.15 14,087 13,414 13,414 13,4142.62 1.66

ATS-9 LOAD SIDE 480 9,924 1.14 6,6338.25 9,964 9,924 9,924 9,9241.84 0.90

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

ATS-E1X LOAD S 480 27,594 2.54 23,05522.94 29,836 27,594 27,594 27,5946.39 1.88

ATS-ESWB F-3 LO 480 39,833 3.28 39,15933.12 45,324 39,834 39,833 39,83310.85 2.39

B1 208 3,353 0.55 2,0291.21 3,354 3,353 3,353 3,3530.24 0.46

B13 ATS 13B (MCC 480 12,556 4.20 11,58710.44 15,109 12,558 12,556 12,5563.21 4.14

B13 ATS 13B CB L 480 13,039 4.46 12,38910.84 15,907 13,042 13,039 13,0393.43 4.42

B13 ATS 13C LOA 480 33,125 5.76 34,99727.54 42,826 33,173 33,126 33,1259.70 5.83

B13 ATS EB13A L 480 14,444 4.75 14,41312.01 17,886 14,449 14,444 14,4443.99 4.37

B13 CH1 CB LINE 480 28,499 4.07 27,68723.69 34,053 28,502 28,499 28,4997.67 3.48

B13 CH2 CB LINE 480 29,063 4.23 28,52124.16 35,036 29,067 29,063 29,0637.90 3.68

B13 CH3 CB LINE 480 28,779 4.15 28,09923.93 34,537 28,782 28,779 28,7797.79 3.57

B13 CH4 VFD CB L 480 16,024 4.26 15,58213.32 19,349 16,026 16,024 16,0244.32 3.63

B13 CT1 CB LINE 480 8,801 1.50 6,7037.32 8,934 8,801 8,801 8,8011.86 1.09

B13 CT1 NFDS 480 5,407 0.93 3,5434.50 5,413 5,407 5,407 5,4070.98 0.66

B13 CT2 CB LINE 480 9,057 1.57 6,9877.53 9,221 9,057 9,057 9,0571.94 1.15

B13 CT2 NFDS 480 5,407 0.93 3,5434.50 5,413 5,407 5,407 5,4070.98 0.66

B13 CT3 CB LINE 480 9,207 1.62 7,1587.65 9,393 9,207 9,207 9,2071.98 1.18

B13 CT3 NFDS 480 7,617 1.25 5,4846.33 7,666 7,617 7,617 7,6171.52 0.89

B13 CT4 CB LINE 480 9,361 1.66 7,3367.78 9,572 9,361 9,361 9,3612.03 1.22

B13 CT4 NFDS 480 7,939 1.31 5,8036.60 8,005 7,939 7,939 7,9391.61 0.94

B13 CWP1 CB LIN 480 15,756 1.39 11,77613.10 15,925 15,756 15,756 15,7563.26 1.02

B13 CWP2 CB LIN 480 14,993 1.33 11,06012.47 15,127 14,993 14,993 14,9933.07 0.98

B13 CWP3 CB LIN 480 14,296 1.29 10,42411.89 14,404 14,296 14,296 14,2962.89 0.95

B13 CWP4 CB LIN 480 14,993 1.33 11,06012.47 15,127 14,993 14,993 14,9933.07 0.98

B13 DB13C 480 30,775 4.80 31,06625.59 38,197 30,787 30,776 30,7758.61 4.45

B13 DB13D 480 17,858 5.18 18,39414.85 22,552 17,870 17,858 17,8585.10 4.93

B13 EB13A 480 14,219 4.59 14,05211.82 17,462 14,223 14,219 14,2193.89 4.11

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

B13 LP2 208 2,881 2.62 2,9991.04 3,133 2,881 2,881 2,8810.36 2.70

B13 LP2A 208 2,210 1.37 1,9220.80 2,232 2,210 2,210 2,2100.23 1.04

B13 MCC 480 12,463 4.16 11,43110.36 14,967 12,464 12,463 12,4633.17 4.05

B13 PC1 CB LINE 480 11,898 0.69 7,7899.89 11,899 11,898 11,898 11,8982.16 0.47

B13 PC2 CB LINE 480 16,983 0.96 12,11114.12 17,007 16,983 16,983 16,9833.36 0.64

B13 PC3 CB LINE 480 16,983 0.96 12,11114.12 17,007 16,983 16,983 16,9833.36 0.64

B13 PC4 CB LINE 480 13,754 0.93 9,38411.43 13,770 13,754 13,754 13,7542.60 0.64

B13 PE-1 CB LINE 480 5,167 0.71 3,2864.30 5,168 5,167 5,167 5,1670.91 0.47

B13 PE-2 CB LINE 480 5,521 0.74 3,5524.59 5,522 5,521 5,521 5,5210.98 0.49

B13 PE3 CB LINE 480 7,925 1.16 5,7226.59 7,959 7,925 7,925 7,9251.59 0.81

B13 PE4 CB LINE 480 7,482 1.08 5,2946.22 7,504 7,482 7,482 7,4821.47 0.75

B13 SB13C 480 31,866 5.26 32,87726.49 40,373 31,891 31,866 31,8669.11 5.25

B14 14LRP1 480 16,639 1.51 13,33013.83 16,895 16,639 16,639 16,6393.69 1.02

B14 14MDP 480 25,610 6.47 27,14521.29 33,950 25,685 25,611 25,6107.52 6.25

B14 14OSDP1 208 10,646 3.89 11,3283.84 12,583 10,646 10,646 10,6461.36 3.78

B14 14OSPDP1 480 22,673 5.05 22,45318.85 28,471 22,686 22,673 22,6736.22 4.22

B14 1A 208 10,008 3.24 10,0293.61 11,359 10,008 10,008 10,0081.20 2.75

B14 1B 208 9,309 2.69 8,9173.35 10,166 9,309 9,309 9,3091.07 2.12

B14 2A 208 9,382 2.47 8,9603.38 10,089 9,382 9,382 9,3821.08 1.89

B14 2B 208 9,098 2.27 8,5093.28 9,652 9,098 9,098 9,0981.02 1.70

B14 2EM 208 1,598 2.17 1,6220.58 1,684 1,598 1,598 1,5980.19 2.23

B14 3A 208 8,293 2.15 7,4362.99 8,727 8,293 8,293 8,2930.89 1.61

B14 3B 208 8,111 2.07 7,1882.92 8,493 8,111 8,111 8,1110.86 1.55

B14 3C 208 8,022 2.04 7,0702.89 8,382 8,022 8,022 8,0220.85 1.52

B14 ATSEM LOA 480 8,914 0.51 5,6877.41 8,914 8,914 8,914 8,9141.58 0.33

B14 ATSLR LOAD 480 19,945 2.09 17,64416.58 20,904 19,945 19,945 19,9454.89 1.41

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

B14 ATSOS1 LOA 480 22,337 4.73 21,93318.57 27,633 22,345 22,337 22,3376.08 3.85

B14 ATSOS2 LOA 480 22,956 5.16 22,88219.09 28,968 22,972 22,957 22,9566.34 4.35

B14 BA 208 5,000 1.00 3,5941.80 5,010 5,000 5,000 5,0000.43 0.72

B14 BB 208 4,895 0.98 3,4991.76 4,904 4,895 4,895 4,8950.42 0.71

B14 E1A 208 8,625 2.11 7,9583.11 9,051 8,625 8,625 8,6250.96 1.56

B14 E1B 208 8,476 2.05 7,7433.05 8,862 8,476 8,476 8,4760.93 1.51

B14 E2A 208 8,098 1.54 7,0022.92 8,235 8,098 8,098 8,0980.84 1.07

B14 E2B 208 8,823 2.36 8,3113.18 9,420 8,823 8,823 8,8231.00 1.81

B14 E3A 208 8,103 2.04 7,2722.92 8,469 8,103 8,103 8,1030.87 1.52

B14 E3B 208 8,194 2.08 7,3982.95 8,583 8,194 8,194 8,1940.89 1.55

B14 EBA 208 3,793 0.67 2,5271.37 3,793 3,793 3,793 3,7930.30 0.47

B14 EBB 208 3,699 0.66 2,4551.33 3,700 3,699 3,699 3,6990.29 0.47

B14 EL-2 FDS 480 9,840 0.76 6,5018.18 9,842 9,840 9,840 9,8401.80 0.51

B14 ELEV2 CP 480 1,269 2.57 1,2031.05 1,374 1,269 1,269 1,2690.33 2.55

B14 EP3A 480 13,419 1.78 10,47611.16 13,807 13,419 13,419 13,4192.90 1.30

B14 EPBA 480 11,655 1.40 8,6239.69 11,787 11,655 11,655 11,6552.39 1.02

B14 EPBB 208 1,871 2.52 1,9050.67 2,020 1,871 1,871 1,8710.23 2.53

B14 HVP SW 12,470 5,274 7.09 5,089113.91 7,124 5,300 5,275 5,27436.64 7.25

B14 P2A 480 17,575 1.41 14,11214.61 17,777 17,575 17,575 17,5753.91 0.92

B14 P3A 480 6,813 0.58 4,3255.66 6,814 6,813 6,813 6,8131.20 0.41

B14 RF2 FDS 480 0 0.00 00.00 0 0 0 00.00 0.00

B14 RF2 VFD CB L 480 1,684 0.14 9901.40 1,684 1,684 1,684 1,6840.27 0.11

B14DP1 208 10,512 3.82 10,8713.79 12,378 10,513 10,512 10,5121.31 3.57

B14ESWB 480 30,859 5.64 26,06425.66 39,724 30,897 30,859 30,8597.22 4.18

B15 15ATS1 LOA 208 15,041 1.07 9,8785.42 15,084 15,041 15,041 15,0411.19 0.84

B15 15ATS2 CB L 208 11,188 1.88 9,1034.03 11,577 11,188 11,188 11,1881.09 1.57

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

B15 15ATS2 LOA 208 16,855 1.32 11,3146.07 17,001 16,855 16,855 16,8551.36 1.02

B15 15ATS3 CB L 208 13,305 2.99 11,6354.79 14,841 13,305 13,305 13,3051.40 2.92

B15 15ATS3 LOA 208 19,037 2.24 13,5606.86 20,151 19,037 19,037 19,0371.63 1.76

B15 15E1 208 11,408 1.20 7,4874.11 11,469 11,408 11,408 11,4080.90 0.97

B15 15E2 208 2,357 0.28 1,3890.85 2,357 2,357 2,357 2,3570.17 0.23

B15 15EMB 208 10,532 0.76 6,6103.79 10,535 10,532 10,532 10,5320.79 0.60

B15 15OS1 208 11,761 1.22 7,7384.24 11,829 11,761 11,761 11,7610.93 0.98

B15 15OS2 208 4,444 0.52 2,6841.60 4,444 4,444 4,444 4,4440.32 0.43

B15 15OSDP1 208 16,643 2.07 11,6666.00 17,422 16,643 16,643 16,6431.40 1.65

B15 16ATS1 CB L 208 13,305 2.99 11,6354.79 14,841 13,305 13,305 13,3051.40 2.92

B15 16ATS1 LOA 208 19,885 2.31 14,2037.16 21,151 19,885 19,885 19,8851.71 1.80

B15 1A 208 5,925 0.61 3,6222.13 5,925 5,925 5,925 5,9250.43 0.50

B15 1G 208 6,963 0.68 4,2972.51 6,964 6,963 6,963 6,9630.52 0.56

B15 2M 208 7,900 0.62 4,8532.85 7,901 7,900 7,900 7,9000.58 0.50

B15 2N 208 8,116 0.63 4,9942.92 8,117 8,116 8,116 8,1160.60 0.51

B15 2O 208 7,314 0.59 4,4732.63 7,314 7,314 7,314 7,3140.54 0.48

B15 3M 208 5,972 0.53 3,6192.15 5,972 5,972 5,972 5,9720.43 0.43

B15 3N 208 6,227 0.54 3,7802.24 6,227 6,227 6,227 6,2270.45 0.44

B15 3O 208 5,519 0.51 3,3351.99 5,519 5,519 5,519 5,5190.40 0.42

B15 4N 208 5,519 0.51 3,3351.99 5,519 5,519 5,519 5,5190.40 0.42

B15 CB ELEV 208 5,532 0.63 3,2951.99 5,532 5,532 5,532 5,5320.40 0.49

B15 CHILLER DIS 208 10,445 0.66 6,5503.76 10,446 10,445 10,445 10,4450.79 0.51

B15 ELEV CP 480 670 2.12 6620.56 704 670 670 6700.18 2.23

B15 EM 208 3,579 0.31 2,1171.29 3,579 3,579 3,579 3,5790.25 0.25

B15 FP ATS LOAD 208 9,199 0.78 5,6643.31 9,202 9,199 9,199 9,1990.68 0.61

B15 FP CB LINE 208 13,188 1.01 8,4664.75 13,215 13,188 13,188 13,1881.02 0.79

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

B15 FP EM NFDS 208 10,269 1.45 7,9953.70 10,401 10,269 10,269 10,2690.96 1.15

B15 LP1 208 5,216 0.52 3,1541.88 5,216 5,216 5,216 5,2160.38 0.43

B15 LP2 208 5,505 0.74 3,4061.98 5,507 5,505 5,505 5,5050.41 0.61

B15 LP3 208 5,872 0.76 3,6422.12 5,874 5,872 5,872 5,8720.44 0.63

B15 LP4 208 5,505 0.74 3,4061.98 5,507 5,505 5,505 5,5050.41 0.61

B15 LPB 208 7,332 0.83 4,5962.64 7,336 7,332 7,332 7,3320.55 0.68

B15 MDP 208 23,494 2.63 17,2618.46 25,552 23,494 23,494 23,4942.07 2.03

B15 MDP LINE SI 208 23,603 2.63 17,3588.50 25,680 23,603 23,603 23,6032.08 2.03

B15 PANEL M 208 5,158 0.99 3,3381.86 5,167 5,158 5,158 5,1580.40 0.86

B15 PANEL O 208 4,587 0.97 2,9491.65 4,594 4,587 4,587 4,5870.35 0.84

B15 PNL BA 208 18,333 1.86 12,8466.60 18,951 18,333 18,333 18,3331.54 1.46

B15 WH 208 7,868 0.75 4,9002.83 7,870 7,868 7,868 7,8680.59 0.61

B16 FDS 208 6,235 1.58 3,9752.25 6,352 6,235 6,235 6,2350.48 1.29

B16 16MDP 208 4,169 1.65 2,5911.50 4,260 4,169 4,169 4,1690.31 1.33

B16 A1 208 4,073 1.59 2,5271.47 4,150 4,073 4,073 4,0730.30 1.29

B16 A2 208 4,011 1.55 2,4851.44 4,080 4,011 4,011 4,0110.30 1.26

B16 B 208 3,392 1.25 2,0791.22 3,414 3,392 3,392 3,3920.25 1.04

B16 CU 3/4 FDS 208 3,160 1.11 1,8971.14 3,171 3,160 3,160 3,1600.23 0.90

B16 CU 3/4 FDS0 208 3,245 1.14 1,9541.17 3,258 3,245 3,245 3,2450.23 0.92

B16 ELEV FDS 208 3,353 1.16 2,0431.21 3,368 3,353 3,353 3,3530.25 0.96

B2 ATS EQ1 (20) L 480 17,678 4.48 17,31214.70 21,598 17,682 17,678 17,6784.80 4.00

B2 ATS LS1 LOAD 480 15,514 1.99 13,72212.90 16,166 15,514 15,514 15,5143.80 1.41

B2 ATS-EC1 LOA 480 16,169 3.15 15,11213.44 18,238 16,169 16,169 16,1694.19 2.48

B2 ATS-EC2 LOA 480 7,651 1.04 5,3536.36 7,670 7,651 7,651 7,6511.48 0.77

B2 DP1 208 8,869 3.87 9,5143.20 10,474 8,870 8,869 8,8691.14 3.78

B2 DP2 208 8,657 3.31 9,5863.12 9,867 8,657 8,657 8,6571.15 3.30

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

B2 EC1A 208 3,118 1.59 2,5801.12 3,178 3,118 3,118 3,1180.31 1.21

B2 EC1C 208 3,755 1.38 3,3181.35 3,795 3,755 3,755 3,7550.40 1.16

B2 EC2A 208 3,083 1.58 2,5391.11 3,140 3,083 3,083 3,0830.30 1.20

B2 EC2B 208 2,530 0.92 1,8540.91 2,533 2,530 2,530 2,5300.22 0.65

B2 EC2C 208 3,633 1.35 3,1611.31 3,667 3,633 3,633 3,6330.38 1.12

B2 EC3A 208 3,111 1.73 2,5971.12 3,193 3,111 3,111 3,1110.31 1.35

B2 EC3B 208 3,076 1.71 2,5551.11 3,153 3,076 3,076 3,0760.31 1.33

B2 ECBA 208 4,370 2.13 4,2331.57 4,594 4,370 4,370 4,3700.51 1.69

B2 ECBB 208 4,977 1.73 5,1391.79 5,108 4,977 4,977 4,9770.62 1.64

B2 ECDP1 208 4,712 3.21 4,8541.70 5,335 4,712 4,712 4,7120.58 3.16

B2 ECDP2 208 5,300 2.02 5,7261.91 5,532 5,300 5,300 5,3000.69 2.20

B2 ELEV 1 CP 480 9,689 1.24 6,9888.05 9,750 9,689 9,689 9,6891.94 0.87

B2 ELEV 2 CP 480 12,762 1.62 10,20310.61 13,022 12,762 12,762 12,7622.83 1.12

B2 ELEV 3 CP 480 15,196 2.97 13,65512.63 16,924 15,196 15,196 15,1963.78 2.27

B2 ELEV 4 CP 480 7,524 0.95 5,0406.26 7,534 7,524 7,524 7,5241.40 0.67

B2 ELEV1 CB LIN 480 10,409 1.32 7,6808.65 10,499 10,409 10,409 10,4092.13 0.92

B2 ELEV2 CB LIN 480 14,421 1.93 12,26111.99 14,968 14,421 14,421 14,4213.40 1.35

B2 ELEV3 CB LIN 480 15,530 3.19 14,13712.91 17,558 15,531 15,530 15,5303.92 2.48

B2 ELEV4 CB LIN 480 8,410 1.03 5,7806.99 8,428 8,410 8,410 8,4101.60 0.71

B2 EQBA 208 836 2.27 8390.30 887 836 836 8360.10 2.21

B2 EQDP1 480 17,009 4.14 16,28814.14 20,401 17,011 17,009 17,0094.51 3.54

B2 EQDP2 480 11,435 2.51 9,3799.51 12,337 11,435 11,435 11,4352.60 1.95

B2 EQHBA 480 13,531 1.72 11,18011.25 13,878 13,531 13,531 13,5313.10 1.22

B2 LS1A 208 1,447 0.90 1,0880.52 1,448 1,447 1,447 1,4470.13 0.63

B2 LS1B 208 1,107 0.68 7680.40 1,107 1,107 1,107 1,1070.09 0.47

B2 LS2A 208 1,390 0.86 1,0300.50 1,391 1,390 1,390 1,3900.12 0.60

Bus

Voltage

3-Phase

Amps

3P

X/R

SLG

Amps

SLG

MVA

SLG

X/R

Mom Amps

3 Cycles 5 Cycles 8 Cycles

3-Phase

MVA

---------3P Asym Amps--------

B2 LS2B 208 1,049 0.65 7180.38 1,049 1,049 1,049 1,0490.09 0.45

B2 LS3A 208 983 0.61 6640.35 983 983 983 9830.08 0.43

B2 LSDP1 208 2,407 2.67 2,4490.87 2,626 2,407 2,407 2,4070.29 2.65

B2 MDP 480 18,842 5.25 19,18115.67 23,864 18,857 18,842 18,8425.32 5.29

B2 N1A 208 4,861 1.56 3,8551.75 4,948 4,861 4,861 4,8610.46 1.17

B2 N1B 208 4,787 1.55 3,7771.72 4,869 4,787 4,787 4,7870.45 1.15

B2 N1C 208 4,715 1.53 3,7031.70 4,792 4,715 4,715 4,7150.44 1.14

B2 N1D 208 5,245 1.62 4,3781.89 5,353 5,245 5,245 5,2450.53 1.22

B2 N1E 208 5,169 1.60 4,3031.86 5,269 5,169 5,169 5,1690.52 1.21

B2 N1F 208 5,245 1.62 4,3781.89 5,353 5,245 5,245 5,2450.53 1.22

B2 N2A 208 4,392 1.30 3,3311.58 4,427 4,392 4,392 4,3920.40 0.96

B2 N2B 208 4,321 1.28 3,2611.56 4,353 4,321 4,321 4,3210.39 0.95

B2 N2C 208 4,252 1.27 3,1951.53 4,282 4,252 4,252 4,2520.38 0.94

B2 N2D 208 4,996 1.56 4,0931.80 5,084 4,996 4,996 4,9960.49 1.17

B2 N2E 208 5,076 1.58…