Attachment II - Drawings Revised 2.26.2025.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25025B0015
About this file
This is a set of electrical construction drawings for VA Cincinnati Electric Deficiencies Project (539-22-203) at 3200 Vine Street, Cincinnati, OH. The drawings detail electrical system upgrades including demolition and replacement of multiple motor control centers (MCCs) with new distribution panels.
The drawings include demolition plans, new work plans, single line diagrams, symbols legend, and general notes for electrical work in Buildings 1 and 14. Key components include: replacement of MCC-North with new DP-B-C-A panel, MCC-East with DP-B-C-B panel, MCC-D with DP-B-A-A panel, and MCC-P2 with DP-10-A-A panel. The work involves intercepting and extending existing feeders, installing new variable frequency drives (VFDs), updating circuit breakers, and connecting fire alarm control modules. The drawings specify detailed sequencing of construction to minimize outages, with requirements for 4-week advance scheduling of shutdowns with the VA. All new distribution panels must be integrated with the existing Building Automation System (BAS) by Tridium FX Explorer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25025B0015 0003.docx | DOCX document | |
| Attachment IX - Justification and Approval - Sole Source to Post.pdf | ||
| Attachment VIII - CVAMC and FT Thomas Arc Flash Study.pdf | ||
| 36C25025B0015 0002.docx | DOCX document | |
| Attachment VII - Pre-Bid RFIs - GDI.docx | DOCX document | |
| Attachment VI - Addendum - Specifications.pdf | ||
| Site Visit Sign In.pdf | ||
| 36C25025B0015 0001.docx | DOCX document | |
| 36C25025B0015.pdf | ||
| Attachment II - Drawings.pdf | ||
| Attachment I - DBA WD.pdf | ||
| 36C25025B0015_1.docx | DOCX document | |
| Attachment V - RFI Form.pdf | ||
| Attachment III - Specifications.pdf | ||
| Attachment IV - VAAR 852.219-75.pdf |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
85% CONSTRUCTION DOCUMENTS 11/13/2023
A u to d e s k D o c s /2
.8
.0
V A
C in c in n a ti E le c tr ic D e fi c ie n c ie s /2
.8
.0
E v
.r v t
/2
/2
:3
:5
P
M
GI000
COVER SHEET
GUIDON DESIGN
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
VA Cincinnati Electrical Deficiencies
3200 Vine Street, Cincinnati, OH
539-22-203
1, 14
01/27/2025
539-22-203
VA Cincinnati Electrical Deficiencies
VA Cincinnati
3200 Vine Street, Cincinnati, OH
Construction Documents
BID DOCUMENTS
FULLY SPRINKLERED
AREA MAP VICINITY MAPN N
PROJECT LOCATION
Contact:
VAMC CINCINNATI
Justin Beaudoin
COR
3200 Vine St Cincinnati, OH 45220 p: 513-609-2338 e: justin.beaudoin@va.gov
OWNER
Contact:
Al Halabi
Senior Electrical Engineer
ELECTRICAL
1221 North Pennsylvania Street Suite 200 Indianapolis, IN 46202 p: 317.800.6388 e: ahalabi@guidon.com
GUIDON DESIGN INC.
SHEET INDEX
SHEET NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
ELECTRICAL
E-000 ELECTRICAL SYMBOLS LEGEND AND GENERAL NOTES
E-001 ELECTRICAL NOTES
EP101 BUILDING 01 ELECTRICAL BASEMENT PLAN
EP102 BUILDING 01 ELECTRICAL TENTH FLOOR PLAN
EP114 BUILDING 14 ELECTRICAL SECOND FLOOR PLAN
EP401 BUILDING 01 ELECTRICAL ENLARGED PLANS - DEMOLITION
EP402 BUILDING 01 ELECTRICAL ENLARGED PLAN - DEMOLITION
EP403 BUILDING 01 ELECTRICAL ENLARGED PLANS - NEW WORK
EP404 BUILDING 01 ELECTRICAL ENLARGED PLAN - NEW WORK
E-701 ELECTRICAL SINGLE LINE DIAGRAM - DEMOLITION
E-702 ELECTRICAL SINGLE LINE DIAGRAM - DEMOLITION
E-703 ELECTRICAL SINGLE LINE DIAGRAM - NEW WORK
E-704 ELECTRICAL SINGLE LINE DIAGRAM - NEW WORK
Revisions: Date:
02/24/2025
ABBREVIATION DESCRIPTION
+ MOUNTING HEIGHT
1P SINGLE POLE
1PH SINGLE-PHASE
2P TWO POLE
2/C TWO-CONDUCTOR
3P THREE POLE
3PH THREE-PHASE
3W THREE-WIRE
3/C THREE-CONDUCTOR
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
(D) DEMOLISH
(E) EXISTING
(ER) EXISTING TO BE RELOCATED
(ETR) EXISTING TO REMAIN
(N) NEW
(R) REMOVE (DEMOLISH)
(REL) RELOCATE EXISTING
(T) TEMPORARY
A or AMP AMPERE A/C or AC AIR CONDITIONING
A/E ARCHITECT/ENGINEER
A/V AUDIO VISUAL
AC ALTERNATING CURRENT or
ARMORED CABLE
ACP ACCESS PANEL
ACU AIR CONDITIONING UNIT
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME or AMP FUSE
AFC AVAILABLE FAULT CURRENT
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AM AMMETER
AMB AMBIENT
APPROX. APPROXIMATELY
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AVG AVERAGE
BBH BASEBOARD HEATER
BC BARE COPPER
BFF BELOW FINISH FLOOR
BHP BRAKE HORSEPOWER
BIL BASIC INSULATION LEVEL
BKR BREAKER
BL BUILDING LINE
BLDG BUILDING
BR BRANCH
BRKR BREAKER
BTM BOTTOM
BYP BYPASS
°C CELSIUS
C CONDUIT
C/C CENTER TO CENTER
CAB CABINET
CALC CALCULATE or CALCULATION
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CB or C/B CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
ABBREVIATIONS
ABBREVIATION DESCRIPTION
CD CONSTRUCTION DOCUMENTS
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CL CENTER LINE
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAXIAL CABLE
COF COFFEE MACHINE
COL COLUMN
COMM COMMUNICATION
COMP COMPRESSOR
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUE
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CR CRITICAL
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTRL CONTROL
CU COPPER
CU FT CUBIC FEET
DB DECIBEL or DIRECT BURIAL
DC DIRECT CURRENT
DEMO DEMOLITION
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DISC DISCONNECT
DIST DISTRIBUTION
DM DEMAND METER
DN DOWN
DO DRAWOUT or DOOR OPENER
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DW DISHWASHER
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC or ELECTRICAL
ELEV ELEVATOR
ELV ELEVATION
EMER or EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EP ELECTRIC PNEUMATIC
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXP EXPLOSIONPROOF
EXH EXHAUST
EXT EXTERIOR
°F FAHRENHEIT
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FHC FIRE HOSE CABINET
FIXT FIXTURE
FL FLOOR
FLA FULL LOAD AMPS
FP FIRE PROTECTION
ABBREVIATION DESCRIPTION
FLEX-CONN FLEXIBLE CONNECTION
FLUOR FLUORESCENT
FMC FLEXIBLE METALLIC CONDUIT
FRZ FREEZER
FSS FUSED SAFETY SWITCH
FT FEET or FOOT
FTG FOOTING
FV FULL VOLTAGE
FVNR FULL VOLTAGE NON-REVERSING
G or GND GROUND
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GRS GALVANIZED RIGID STEEL
GTB GROUND TERMINAL BOX
HGT or HT HEIGHT
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HO HAND OPERATED
HOA HAND-OFF-AUTOMATIC
HORZ HORIZONTAL
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HTR HEATER
HV HIGH VOLTAGE
HZ HERTZ
IC INTERCOMMUNICATION
ID INSIDE DIAMETER
IDS INTRUSION DETECTION SYSTEM
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
ISG ISOLATED GROUND SURGE GUARD
IWH INSTANTANEOUS WATER HEATER
JB JUNCTION BOX
JT JOINT
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LS LIFE SAFETY
LT LIGHT
LTG LIGHTING
LV LOW VOLTAGE
LVL LEVEL
MATV MASTER ANTENNA TELEVISION
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
INDICATOR LIGHT
[LIGHT COLOR]
A AMBER
B BLUE
G GREEN
R RED
NORMALLY OPEN CONTACT
GROUND
MOTOR ("HP" INDICATES HORSEPOWER)
TRANSFORMER
UTILITY CONNECTION
KIRK KEY INTERLOCK
UTILITY METER OR RELAY COIL
DRAWOUT PROTECTION DEVICE
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
FEEDER CALLOUT
REFER TO FEEDER SCHEDULE
NORMALLY CLOSED CONTACT
LINE/LOAD REACTOR (IMPEDANCE AS
INDICATED)
CIRCUIT BREAKER OR MOTOR CIRCUIT
PROTECTOR
FUSE
RECTIFIER OR INVERTER
BATTERY SUPPLY
BUS
MOTOR OVERLOAD
A xxx
RESISTIVE HEATING ELEMENT
VARIABLE FREQUENCY CONTROLLER W/
DISCONNECT SWITCH
VARIABLE FREQUENCY CONTROLLER
VFD
SINGLE LINE SYMBOLS
BUS WITH EXTENSION PROVISIONS
SWITCH
3%
NODE CONNECTION TO BUS
DIGITAL METERDM
M
K
SURGE PROTECTION DEVICESPD
MEDIA CONVERTERMC
CABLE BONDING OR TERMINATION CONNECTION
VFD
HP
ABBREVIATION DESCRIPTION
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MM MILLIMETERS
MMFO MULTI-MODE FIBER OPTIC
MOCP MAXIMUM OVERCURRENT PROTECTION
MTD MOUNTED
MTG HT MOUNTING HEIGHT
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
MWV MICROWAVE
MXFMR MEDIUM VOLTAGE TRANSFORMER
N NEUTRAL
NA or N/A NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CIRCUIT
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OCPD OVERCURRENT PROTECTION DEVICE
OD OUTSIDE DIAMETER
OL OVERLOAD
OR OPERATING ROOM
P POLE
PA PUBLIC ADDRESS
PACS PHYSICAL ACCESS CONTROL SYSTEM
PB PULL BOX or PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PC PHOTOCELL
PCB POLYCHLORINATED BIPHENYL
PF POWER FACTOR
PH or Ø PHASE
PIV POST INDICATOR VALVE
PL PILOT LIGHT
PNL PANELBOARD
PREFAB PREFABRICATED
PT POTENTIAL TRANSFORMER or
POKE-THRU
PTS PNEUMATIC TUBE STATION
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RACU ROOM AIR CONDITIONING UNIT
RAD RADIATION
RCP REFLECTED CEILING PLAN
REC or RECPT RECEPTACLE
REF REFRIGERATOR
REQD REQUIRED
RGIP REMOTE GROUND INDICATING PANEL
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RPM REVOLUTIONS PER MINUTE
ABBREVIATION DESCRIPTION
SC SHORT CIRCUIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SE SERVICE ENTRANCE
SF SQUARE FOOT (FEET)
SI INTERNATIONAL SYSTEM OF UNITS
SMFO SINGLE MODE FIBER OPTIC
SN SOLID NEUTRAL
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SQ SQUARE
SS SAFETY SWITCH
SSSS SOLID STATE SOFT START
SSTV SECURITY SURVEILLANCE TELEVISION
STD STANDARD
STN STATION
STP SHIELDED TWISTED PAIR
SUSP SUSPENDED
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TBB TELECOM BACK BOARD
TC TIME CLOCK
TCC TEMPERATURE CONTROL CONTRACTOR
TELE TELEPHONE
TELECOM TELECOMMUNICATION
TEMP TEMPERATURE OR TEMPORARY
TGB TELECOM GROUND BAR
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UC or U/C UNDER COUNTER UG or U/G UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
UV UNIT VENTILATOR
V VOLT or VOLTAGE
VA VOLT AMPERE
VAC VACUUM
VAR VOLT AMPERE REACTIVE
VB VACUUM BREAKER
VC VACUUM CLEANING
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VM VOLTMETER
VOL VOLUME
VP VAPORPROOF
VSD/VFC VARIABLE SPEED DRIVE/CONTROLLER
W WATT
W/ WITH
W/O WITHOUT
WAO WORK AREA OUTLET (TELECOM)
WAP WIRELESS ACCESS POINT
WH WATER HEATER
WP WEATHERPROOF
WT WIRE TROUGH
WTR WATER
XFER TRANSFER
XFMR TRANSFORMER
Z IMPEDANCE
AUTOMATIC TRANSFER SWITCH
MANUAL TRANSFER SWITCH
A
N E AUTOMATIC TRANSFER SWITCH
WITH BYPASS
MOTOR STARTER WITH MOTOR
CIRCUIT PROTECTOR
FUSIBLE DISCONNECT SWITCH
DISCONNECT SWITCH
PACKAGED VARIABLE FREQUENCY CONTROLLER
WITH DISCONNECT/OVERCURRENT PROTECTION,
LINE REACTOR, FRONT MOUNTED DISPLAY AND
CONTROLS WITHIN A SINGLE ENCLOSURE.
3%
VFD
3%
IL
3%
VFD
3%
IL
XXXA
3P
XP
XXXA
3P
XP
EQUIP TAG
AMPS
POLES
TYPE
SIZE
DISCONNECT / OVERCURRENT PROTECTION TYPE
IN-LINE FUSE (SIZE PER MANUFACTURER)
LINE REACTOR (IMPEDANCE AS INDICATED)
INTERNAL VARIABLE FREQUENCY CONTROLLER
DRIVE OUTPUT FILTERING (WHERE
INDICATED) TYPE:
LOAD SIDE REACTOR (IMPEDANCE AS
INDICATED (AS SHOWN)
DV/DT FILTER:
DV/DT
PACKAGED VARIABLE FREQUENCY CONTROLLER
WITH DISCONNECT/OVERCURRENT PROTECTION,
LINE REACTOR, FRONT MOUNTED DISPLAY AND
CONTROLS WITHIN A SINGLE ENCLOSURE.
DISCONNECT / OVERCURRENT PROTECTION TYPE
IN-LINE FUSE (SIZE PER MANUFACTURER)
LINE REACTOR (IMPEDANCE AS INDICATED)
INTERNAL VARIABLE FREQUENCY CONTROLLER
DRIVE OUTPUT FILTERING (WHERE
INDICATED) TYPE:
LOAD SIDE REACTOR (IMPEDANCE AS
INDICATED (AS SHOWN)
DV/DT FILTER:
DV/DT
BYPASS (AUTO/MANUAL AS DESCRIBED) WITH
INPUT/OUTPUT ISOLATION (WHERE SHOWN)
AND MOTOR STARTER (WHERE SHOWN)
EQUIP
NAME
CP
PANELBOARD OR UTILIZATION
EQUIPMENT
UTILIZATION EQUIPMENT WITH CONTROL
PANEL
PANELBOARD
DEVICE
TOGGLE SWITCH
TELEPHONE/DATA OUTLET
DISCONNECT SWITCH
MOTOR STARTER AND VFD
FIRE ALARM PULL STATION
FIRE ALARM HORN/STROBE
WALL PHONE
EXIT SIGN
CARD READER AND KEYPAD
CLOCK RECEPTACLE
WALL SPEAKER
RECEPTACLE
DIGITAL MONITOR OR SCREEN
RECEPTACLE (CLEAN ROOM)
6' - 6"
MOUNTING HEIGHT (AFF)
4' - 0"
1' - 6"
6' - 6" MAX.
6' - 6" MAX.
4' - 0"
6' - 8"
5' - 0"
NOTE 10, 11
4' - 0"
8' - 0"
8' - 0"
1' - 6"
5' - 0"
4' - 0"
TOP
TO:
TOP
CENTER
TOP
CENTER
TOP
BOTTOM
CENTER
NOTE 10, 11
TOP
CENTER
CENTER
CENTER
CENTER
TOP
TELE/DATA OUTLET (CLEAN ROOM) 4' - 0" TOP
1. ALL MOUNTING HEIGHTS SHALL BE AS LISTED ABOVE UNLESS OTHERWISE
INDICATED ON DRAWINGS.
2. ALL MOUNTING HEIGHTS SHALL BE IN ACCORDANCE WITH THE AMERICANS
WITH DISABILITIES ACT.
3. MOUNTING HEIGHTS AND LOCATIONS OF DEVICES SHOWN ON HORIZONTAL
AND VERTICAL CHASES SHALL BE COORDINATED WITH OTHER UTILITIES IN
THE CHASE. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR
CHASE LOCATIONS AND MOUNTING LOCATIONS.
4. MOUNTING HEIGHTS AND LOCATIONS OF SURFACE PLUGMOLD RACEWAY
SHALL BE COORDINATED WITH COUNTER TOPS AND BACK SPLASHES.
REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR COUNTER
LOCATIONS AND DIMENSIONS.
5. '+' SHOWN BESIDE A DEVICE INDICATES THAT IT SHALL BE INSTALLED ABOVE
COUNTER, AND BACK SPLASH WHERE APPLICABLE. INSTALL OUTLETS 6"
ABOVE COUNTER TOP. COORDINATE EXACT HEIGHT WITH ARCHITECTURAL
ELEVATIONS AND/OR CASEWORK DRAWINGS.
6. 'UC' SHOWN BESIDE A DEVICE INDICATES THAT IT SHALL BE INSTALLED 4"
BELOW COUNTER OR 18" ABOVE FINISHED FLOOR, WHICHEVER IS FEASIBLE.
7. '+P' SHOWN BESIDE A DEVICE INDICATES IT SHALL BE INSTALLED 18" ABOVE
PLATFORM.
8. REFER TO SECURITY VENDOR AND CONTRACTOR RECOMMENDATIONS AND
PRODUCT DATA FOR MOUNTING HEIGHTS OF SECURITY CAMERAS.
9. INSTALL WALL MOUNTED OCCUPANCY SENSORS 6" BELOW CEILING OR AT
HEIGHT NOT TO EXCEED PRODUCT MANUFACTURER RECOMMENDATIONS.
10. WALL MOUNTED EXIT SIGNS INSTALLED ABOVE DOORS SHALL BE INSTALLED
1'-0" ABOVE THE TOP OF THE DOOR FRAME TO THE BOTTOM OF THE EXIT
SIGN. WHERE CEILING HEIGHT DOES NOT ALLOW FOR MOUNTING AT THIS
LOCATION, INSTALL SIGN CENTERED BETWEEN DOOR FRAME AND CEILING.
11. PENDANT MOUNTED EXIT SIGNS SHALL BE INSTALLED AT 10'-0" AFF AS
MEASURED TO THE BOTTOM OF THE EXIT SIGN. ADJUST AS NECESSARY IN
UNFINISHED SPACES TO CLEAR WORK PERFORMED BY OTHER TRADES.
INSTALL EXIT SIGN SO LINE OF SIGHT IS MAINTAINED AND NOT HINDERED BY
WORK FROM OTHER TRADES.
TOP
4' - 0" MAX.GROUND BUS BAR
DOOR OPERATOR 4' - 0" TOP
AUDIO-VISUAL OUTLETS 1' - 6" CENTER
DOOR RELEASE BUTTON 4' - 0" TOP
RECEPTACLE (ABOVE COUNTER) 6", NOTE 5 BOTTOM
STANDARD MOUNTING HEIGHTS
TELE/DATA OUTLET (ADA) 4' - 0" TOP
QUADRUPLEX RECEPTACLE
ON STANDBY POWER - 125V,2P,3W*
DUPLEX RECEPTACLE
ON STANDBY POWER - 125V,2P,3W*
CEILING MOUNTED JUNCTION BOX
W/ HANGING RECEPTACLE CORD
QUADRUPLEX RECEPTACLE - 125V,2P,3W*
SIMPLEX RECEPTACLE - 125V,2P,3W*
DUPLEX RECEPTACLE - 125V,2P,3W*
NEMA 250 ENCLOSURE RATING SHALL BE
INDICATED ON PLANS, RECEPTACLE TYPE
DESIGNATION, OR TEXT SHEET OR GENERAL
NOTATION. NEMA 1 UNLESS NOTED OTHERWISE.
NEMA RECEPTACLE WD 1 CONFIGURATION SHALL
BE INDICATED ON PLANS.
L5-20R UNLESS OTHERWISE NOTED.
SIMPLEX RECEPTACLE
ON UPS OR STANDBY POWER - 125V,2P,3W*
[INDICATES NEMA WD 1 CONFIGURATION].
L5-20R UNLESS OTHERWISE NOTED.
[RECEPTACLE TYPE]
GFCI GROUND FAULT CIRCUIT INTERRUPTER
RECEPTACLE
IG ISOLATED GROUND RECEPTACLE
SP SURGE SUPPRESSION RECEPTACLE
WP RECEPTACLE WITH WEATHERPROOF
COVER
TP TAMPER-PROOF RECEPTACLE
XP EXPLOSION-PROOF RECEPTACLE
USB RECEPTACLE WITH INTEGRAL USB PORT
SW SWITCHED OR CONTROLLED RECEPTACLE
WALL
MOUNT
FLOOR
MOUNT
5-30R
IG
CEILING
MOUNT
QUADRUPLEX RECEPTACLE
ON UPS POWER - 125V,2P,3W*
DUPLEX RECEPTACLE
ON UPS POWER - 125V,2P,3W*
SPECIAL PURPOSE RECEPTACLE*^
SPECIAL PURPOSE RECEPTACLE
ON STANDBY POWER*^
XP BL
PULL BOXPB
SPECIAL PURPOSE RECEPTACLE
ON UPS POWER*^
J
POWER DEVICE
SYMBOLS
NONFUSIBLE SAFETY DISCONNECT SWITCH
WALL OR SURFACE MOUNTED TOGGLE SWITCH
[SUBSCRIPT INDICATES TYPE OF SWITCH]
3 THREE POLE SWITCH
4 FOUR POLE SWITCH
P SWITCH WITH PILOT LIGHT
V VARIABLE SPEED CONTROL SWITCH
T FRACTIONAL HORSEPOWER MANUAL MOTOR
CONTROLLER WITH OVERLOADS
M MANUAL MOTOR CONTROLLER
CO SINGLE POLE, CENTER-OFF MOMENTARY
CONTACT SWITCH
R/L RAISE/LOWER SWITCH
T
POWER EQUIPMENT
SYMBOLS
R
[DISCONNECT TYPE]
R RECESSED OR FLUSH MOUNTED
C AUXILIARY CONTACT
NEMA ENCLOSURE TYPE SHALL BE
INDICATED ON PLANS.
NEMA 1 UNLESS OTHERWISE NOTED.
FUSIBLE SAFETY DISCONNECT SWITCH
MOTOR STARTER
COMBINATION MOTOR STARTER
W/ MOTOR CIRCUIT PROTECTOR
COMBINATION MOTOR STARTER
WITH FUSIBLE DISCONNECT SWITCH
208/120V DISTRIBUTION OR BRANCH PANELBOARD
480V OR 480/277V DISTRIBUTION OR BRANCH PANELBOARD
VARIABLE FREQUENCY DRIVE OR CONTROLLER,
CONTROL PANEL OR OTHER DISTRIBUTION EQUIPMENT
SPD WALL MOUNTED SURGE PROTECTION DEVICE
240/120V DISTRIBUTION OR BRANCH PANELBOARD
ENCLOSED CIRCUIT BREAKER
VARIABLE FREQUENCY CONTROLLER W/ DISCONNECT SWITCH
VARIABLE FREQUENCY CONTROLLER
VFD
VFD
WALL OR CEILING MOUNTED FIRE ALARM AUDIBLE
AND VISIBLE DEVICE
INTELLIGENT SYSTEM MONITOR & CONTROL DEVICES
FIRE ALARM MANUAL PULL STATION
CEILING MOUNTED FIRE ALARM VISIBLE DEVICE
WALL OR CEILING MOUNTED FIRE AUDIBLE DEVICE
C
AUTOMATIC SMOKE/HEAT DETECTOR
[DETECTOR CLASSIFICATION]
AS AIR SAMPLING SMOKE DETECTOR
BR BEAM TYPE SMOKE DETECTOR - RECEIVER
BT BEAM TYPE SMOKE DETECTOR - TRANSMITTER
D DUCT MOUNTED, PHOTOELECTRIC SMOKE
DETECTOR
F FIXED TEMPERATURE HEAT DETECTOR
FR COMBINATION RATE OF RISE PLUS
FIXED TEMPERATURE HEAT DETECTOR
I IONIZATION SMOKE DETECTOR
P PHOTOELECTRIC SMOKE DETECTOR
R RELAY BASE SMOKE DETECTOR
RR RATE OF RISE HEAT DETECTOR
SB SOUNDER BASE SMOKE DETECTOR
SS SINGLE STATION SMOKE DETECTOR
[RELAY FUNCTION]
C CONTROL
I ISOLATION
M MONITOR
WALL MOUNTED FIRE ALARM VISIBLE DEVICE
AUTOMATIC GAS DETECTOR
[DETECTOR CLASSIFICATION]
A AMMONIA DETECTOR
CH4 METHANE DETECTOR
CO CARBON MONOXIDE DETECTOR
CO2 CARBON DIOXIDE DETECTOR
HCL HYDROGEN CHLORIDE DETECTOR
N2 NITROGEN DETECTOR
O2 OXYGEN DETECTOR
FIRE ALARM CONTROL PANEL
[CONTROL PANEL FUNCTION]
FACP FIRE ALARM MAIN CONTROL PANEL
FAA FIRE ALARM ANNUNCIATOR PANEL
PRE PRE-ACTION SPRINKLER SYSTEM CONTROL PANEL
SAP SPRINKLER ALARM SYSTEM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
BATT FIRE ALARM BATTERY CABINET
NAC FIRE ALARM POWER BOOSTER PANEL
GACP GAS DETECTION & ALARM CONTROL PANEL
A
B
F
F
P
FIRE ALARM BELL
FIRE ALARM TROUBLE BELLT
F
F
F
FACP
MAGNETIC DOOR HOLDERDH
FIRE ALARM FLOW SWITCHFS
FIRE ALARM TAMPER SWITCHTS
FIRE ALARM & DETECTION
SYSTEM SYMBOLS
FSD FIRE SMOKE DAMPER
SMOKE DETECTOR AND/OR DAMPER REMOTE TEST
SWITCH AND STATUS INDICATORRTS
WIRELESS ACCESS POINT
WALL MOUNTED VOICE/DATA FEED TO PRE-WIRED
FURNITURE SYSTEM
PP DUAL CHANNEL POWER & TELE/DATA POLE (FROM CEILING)
FC
FIRE RATED POKE-THRU ASSEMBLY
PX
[POKE-THRU FUNCTION]
AV POWER, VOICE, DATA AND A/V
D DATA RECEPTACLE
FC VOICE/DATA FEED TO PRE-WIRED FURNITURE SYSTEM
PX POWER, VOICE AND DATA
V VOICE RECEPTACLE
VD VOICE/DATA RECEPTACLE
SINGLE GANG VOICE/DATA OUTLET,
TYPICAL (1) VOICE, (1) DATA TERMINATIONS
WALL
MOUNT
FLOOR
MOUNT
CEILING
MOUNT
SINGLE GANG VOICE OUTLET,
TYPICAL (1) VOICE TERMINATION
SINGLE GANG DATA OUTLET,
TYPICAL (2) DATA TERMINATIONS
[INDICATES NUMBER OF DATA
TERMINATIONS].
IF NOT INDICATED, PROVIDE 2.
DATA SURFACE RACEWAY
WAP
FC
FLOOR BOX VOICE/DATA FEED TO PRE-WIRED
FURNITURE SYSTEM
COMMUNICATIONS SYSTEM
SYMBOLS
C DIRECT CONNECTION TO TELECOMMUNICATION SYSTEM
(NO FACEPLATE OR WALL DEVICE)
FB COMBINATION POWER AND DATA FLOOR BOX
DAS DISTRIBUTIVE ANTENNA SYSTEM
WALL MOUNTED CLOCK HANGER RECEPTACLE
GROUND ROD IN TEST WELL
WALL MOUNTED GROUNDING BUS BAR
TW
GROUND ROD
GROUNDING DUPLEX RECEPTACLE
LIGHTNING PROTECTION AIR TERMINAL
EXOTHERMIC WELD CONNECTION TO GROUND CONDUCTOR
EXOTHERMIC WELD CONNECTION TO BUILDING STRUCTURE
G
GROUNDING EQUIPMENT
SYMBOLS
MECHANICAL GROUND CONNECTION
CIRCUIT NUMBER(S) OF PANELBOARD
RP-2/1,3,5
PANELBOARD NAME
CONDUIT AND WIRING
SYMBOLS
HOT CONDUCTOR
NEUTRAL CONDUCTOR
GROUND CONDUCTOR
DEFERRED PERMIT
SUBMITTALS
1. FIRE ALARM SYSTEM INCLUDING BUT NOT LIMITED TO: BATTERY
CALCULATIONS, VOLTAGE DROP CALCULATIONS, NOTIFICATION
AND INITIATION DEVICE LOCATIONS, AND MANUFACTURER
CUTSHEETS FOR EQUIPMENT INSTALLED. SYSTEM SHALL BE IN
COMPLIANCE WITH INTERNATIONAL BUILDING CODE AND NFPA 72
REQUIREMENTS. REFER TO MORE INFORMATION IN
SPECIFICATION SECTION 283100.
GENERAL NOTES
1. LEAD SHEET CONTENT IS GENERAL IN NATURE, NOT ALL SYMBOLOGY,
LEGENDS ELEMENTS, AND ABBREVIATIONS SHOWN ON THIS SHEET
ARE USED AND THEIR INCLUSION ON THIS SHEET IS NOT AN
INDICATOR OF RELEVANCE TO SPECIFIC PROJECT SCOPES.
2. CONTRACTOR IS RESPONSIBLE FOR SCHEDULING OF LIGHTING,
POWER, FIRE ALARM, ETC. SHUT-DOWNS WITH THE OWNER. SHUT
DOWNS SHALL BE SCHEDULED DURING OFF-HOURS OR WEEKENDS.
3. CONDUIT ROUTING SHOWN ON THE DRAWINGS IS SCHEMATIC.
CONTRACTOR TO COORDINATE INSTALLATION WITH EXISTING
LIGHTING AND MECHANICAL SYSTEMS, AND WITH PIPING, PLUMBING
AND MECHANICAL INSTALLATION ON THIS PROJECT.
4. PROVIDE A 4" 3000 PSI CONCRETE HOUSE KEEPING PAD FOR ALL
FLOOR MOUNTED ELECTRICAL EQUIPMENT.
5. PROVIDE A SEPARATE GROUNDED CONDUCTOR (NEUTRAL) WIRE WITH
EACH CIRCUIT, UNLESS NOTED OTHERWISE. USE OF MULTIWIRE
BRANCH CIRCUITS IS NOT ACCEPTABLE.
6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED
SUPPORTS FOR ALL DEVICES AND EQUIPMENT FURNISHED BY THE
ELECTRICAL CONTRACTOR AND SHALL NOT RELY ON SUPPORTS
PROVIDED BY OTHER TRADES. SUPPORT SUCH EQUIPMENT PER
APPROVED GOVERNING CODES OR PER APPROVAL OF THE ENGINEER.
UNACCEPTABLE WORKMANSHIP OR MATERIALS SHALL BE REPLACED
AT THE REQUEST OF THE ENGINEER AT THE CONTRACTOR'S
EXPENSE.
7. ALL ELECTRICAL PERMITS AND INSPECTION FEES SHALL BE SECURED
AND PAID BY THE ELECTRICAL CONTRACTOR.
8. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR
ALL FLOOR PLAN DIMENSIONS.
9. ALL TELEPHONE AND DATA WIRING WILL BE BY
TELECOMMUNICATIONS CONTRACTOR. ELECTRICAL CONTRACTOR
SHALL PROVIDE ALL CONDUIT, JUNCTION BOXES WITH PULL STRINGS
TO AN ACCESSIBLE LOCATION ABOVE CEILING FOR INSTALLATION OF
TELECOMMUNICATION WIRING. CONDUITS SHALL BE 1" DEDICATED
CONDUIT FROM EACH OUTLET INDICATED ON FLOOR PLANS UNLESS
SPECIFICALLY NOTED OTHERWISE. PROVIDE DEDICATED 1-1/2"
CONDUIT TO EACH SURFACE RACEWAY LOW VOLTAGE CABLING
JUNCTION BOX. DO NOT DAISY CHAIN LOW VOLTAGE CONDUITS
INSTALLED IN WALLS AND CEILINGS.
10. ALL CONDUIT, HANGERS, AND SUPPORTS SHALL BE INSTALLED SUCH
THAT THEY DO NOT INTERFERE WITH EQUIPMENT ACCESS OR
EQUIPMENT REMOVAL SPACE.
11. CONTRACTOR SHALL PROVIDE OVERCURRENT PROTECTION DEVICES
THAT ARE SELECTIVELY COORDINATED FOR ALL EMERGENCY AND
LEGALLY REQUIRED STANDBY DISTRIBUTION SYSTEMS IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) ARTICLES
700.32 AND 701.32.
SINGLE LINE TYPES
NEW WORK
EXISTING WORK TO REMAIN
DEMOLITION WORK
FUTURE WORK (NOT IN SCOPE)
EQUIPMENT BOUNDARY
EQUIPMENT COMMUNICATIONS
NEW EQUIPMENT BUS
EXISTING EQUIPMENT BUS
DEMOLISH EQUIPMENT BUS
FUTURE EQUIPMENT BUS (NOT IN SCOPE)
SCOPE BOX
LINE BREAK OR CONTINUATION
END OF DEMOLITION POINT
POINT OF CONNECTION TO
EXISTING ELECTRICAL SYSTEM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
85% CONSTRUCTION DOCUMENTS 11/13/2023
A u to d e s k D o c s /2
.8
.0
V A
C in c in n a ti E le c tr ic D e fi c ie n c ie s /2
.8
.0
E v
.r v t
/2
/2
:3
:3
P
M
E-000
ELECTRICAL SYMBOLS LEGEND
AND GENERAL NOTESGUIDON DESIGN
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
VA Cincinnati Electrical Deficiencies
3200 Vine Street, Cincinnati, OH
539-22-203
1, 14
01/27/2025 ARH MCP
BID DOCUMENTS
FULLY SPRINKLERED
A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGEND AND ABBREVIATIONS.
B. EXISTING ELECTRICAL ITEMS TO REMAIN ARE INDICATED WITH A LIGHT SOLID
LINEWEIGHT AND/OR ARE NOTED AS “EXISTING TO REMAIN”.
C. ELECTRICAL ITEMS TO BE REMOVED ARE INDICATED WITH A BOLD DASHED
LINEWEIGHT AND/OR ARE NOTED TO BE REMOVE.
D. INFORMATION SHOWN ON THE LIGHTING, POWER, TECHNOLOGY, AND SYSTEMS
PLANS IS BASED ON GENERAL FIELD OBSERVATION AND EXISTING RECORD
DRAWINGS WHERE AVAILABLE. THE DEMOLITION DRAWINGS DO NOT PURPORT
TO SHOW ALL EXISTING EQUIPMENT, WIRING, CONDUITS OR FIELD CONDITIONS.
FIELD VERIFY EXISTING BUILDING AND SITE CONDITIONS TO DETERMINE THE
ACTUAL EXTENT OF DEMOLITION WORK REQUIRED. THE CONTRACTOR IS
RESPONSIBLE FOR ANY ADDITIONAL TRACING, REMOVING, RELOCATION AND
EXTENDING CIRCUITS AND DEVICES NECESSARY TO MAINTAIN CONTINUITY OF
EXISTING EQUIPMENT NOT IN THE AREA OF WORK.
E. SEQUENCE, COORDINATE, AND INTEGRATE DEMOLITION OF ELECTRICAL
MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. COORDINATE
ELECTRICAL DISCONNECTION OF EQUIPMENT TO BE REMOVED BY THE OTHER
TRADES.
F. COORDINATE DEMOLITION OF ALL AFFECTED ELECTRICAL SYSTEMS AS
REQUIRED TO PREVENT OR MINIMIZE DISRUPTION TO THE OWNER AND
DOWNTIME.
G. CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE EXISTING
CONDITIONS. IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO REVIEW
THE EXISTING CONDITIONS AS THEY RELATE TO THE SCOPE OF WORK AS
DEFINED ON THE CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL REVIEW
LOCATIONS AND QUANTITIES OF ALL EXISTING EQUIPMENT INCLUDING
SWITCHBOARDS, TRANSFORMERS, PANELBOARDS, LIGHTING FIXTURES,
OUTLETS, FIRE ALARM DEVICES, TELECOMMUNICATIONS OUTLETS, SECURITY
DEVICES AND ALL OTHER ELECTRICAL DEVICES, COMPONENTS, ETC. IN THE
EXISTING FACILITY. AT THE BEGINNING OF DEMOLITION, THE CONTRACTOR
ACCEPTS THE EXISTING CONDITIONS, AND HAS INCLUDED ALL NECESSARY
MODIFICATIONS, REMOVAL, DEMOLITION, AND RELOCATION OF THE EXISTING
COMPONENTS FOR THE EXECUTION OF THE SCOPE OF WORK.
H. FIELD VERIFY ALL EXISTING CIRCUITS TO BE REMOVED AND TO REMAIN PRIOR
TO COMMENCEMENT OF ANY DEMOLITION ACTIVITIES.
I. WHERE EXISTING EQUIPMENT (SUCH AS LIGHT FIXTURES, WIRING DEVICES,
CONDUITS, ETC.) IS SHOWN ON PLANS TO BE REMOVED, DISCONNECT AND
COMPLETELY REMOVE ALL ASSOCIATED WIRING AND CONDUIT BACK TO PANEL
SOURCE OR BACK TO EXISTING JUNCTION BOX SERVING OTHER DEVICES TO
REMAIN.
J. WHERE EXISTING CIRCUITS ARE TO BE REMOVED, DISCONNECT WIRING AT THE
OVERCURRENT PROTECTIVE DEVICE AND MARK DEVICE AS SPARE.
K. DISCONNECT ALL WIRING SERVING EQUIPMENT TO BE REMOVED AT THE
OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED
WIRING AND ASSOCIATED CONDUITS WHERE NOT INDICATED OR REQUIRED TO
BE REUSED.
L. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING
SYSTEMS TO REMAIN IN SERVICE DURING CONSTRUCTION. WHERE EXISTING
CIRCUITS ARE INTERRUPTED BY ELECTRICAL DEMOLITION: MAINTAIN, RESTORE,
AND REFEED EXISTING CIRCUITS TO REMAIN INCLUDING ASSOCIATED WIRING
AND CONDUITS THAT PASSES THROUGH AREAS TO BE RENOVATED THAT SERVE
AREAS OUTSIDE OF PROJECT SCOPE.
M. PROTECT EXISTING ELECTRICAL EQUIPMENT AND INSTALLATIONS INDICATED
TO REMAIN. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK,
REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL
CAPACITY, QUALITY, AND FUNCTIONALITY.
N. FIELD VERIFY EXACT DEMOLITION REQUIREMENTS AND INCLUDE ASSOCIATED
COSTS. ASSOCIATED WIRING, CONDUITS, FITTING, BOXES, SUPPORTS, SHALL BE
REMOVED FROM THE DEVICES BACK TO THE RESPECTIVE SOURCE PANEL.
O. UPDATE EXISTING PANEL DIRECTORIES AS REQUIRED. ALL OVERCURRENT
PROTECTIVE DEVICES FOR REMOVED CIRCUITS THAT ARE NOT RE-USED SHALL
REMAIN AND BE MARKED AS “SPARE” ON THE UPDATED PANEL DIRECTORY.
P. REFER TO THE SPECIFICATIONS FOR ADDITIONAL ELECTRICAL DEMOLITION
REQUIREMENTS.
Q. DASHED WALLS INDICATE EXISTING WALLS BEING REMOVED. REFER TO
ARCHITECTURAL DEMOLITION AND PHASING PLANS FOR THE EXACT EXTENT OF
GENERAL CONSTRUCTION DEMOLITION REQUIRED.
R. CONTRACTOR SHALL SUPPORT AND PROTECT ELECTRICAL INFRASTRUCTURE
EXISTING TO REMAIN, INCLUDING BUT NOT LIMITED TO CONDUITS, WIRING,
DEVICES, AND LIGHTING FIXTURES AS REQUIRED.
S. COORDINATE REMOVAL AND REPLACEMENT OF ANY EXISTING ELECTRICAL
CEILING MOUNTED DEVICES (I.E. LIGHT FIXTURES, FIRE ALARM) OUTSIDE THE
MAIN PROJECT AREA OF WORK TO ACCOMMODATE THE NEW CONSTRUCTION.
ELECTRICAL DEMOLITION GENERAL NOTES GENERAL ELECTRICAL NOTES GENERAL ELECTRICAL NOTES
A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOLS LEGEND AND
ABBREVIATIONS.
B. EXISTING ELECTRICAL ITEMS TO REMAIN ARE INDICATED WITH A LIGHT SOLID
LINEWEIGHT AND/OR ARE NOTED AS “EXISTING TO REMAIN”.
C. NEW ELECTRICAL ITEMS ARE INDICATED WITH A BOLD SOLID LINEWEIGHT.
D. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE INTENDED TO
CONVEY THE SCOPE OF WORK AND INDICATE GENERAL ARRANGEMENT OF
EQUIPMENT, CONDUITS, DEVICES, FIXTURES, ETC. THE ELECTRICAL DRAWINGS
SHALL NOT BE SCALED FOR PURPOSES OF EQUIPMENT INSTALLATION. ALL
MEASUREMENTS SHALL BE VERIFIED AS REQUIRED TO INSTALL ALL EQUIPMENT
IN A NEAT AND WORKMANLIKE MANNER. REFER TO THE ENTIRE CONSTRUCTION
DRAWING SET AND SPECIFICATIONS FOR GUIDANCE ON DIMENSIONS, CEILING
HEIGHTS, DOOR SWINGS, ROOM FINISHES, STRUCTURAL DETAILS, LOCATIONS
OF PIPING, DUCTWORK, STRUCTURAL MEMBERS, AND OTHER OBSTRUCTIONS.
E. THE ENGINEER RESERVES THE RIGHT TO MAKE CHANGES IN THE LOCATIONS
OF RECEPTACLES, APPARATUS AND EQUIPMENT UP TO THE TIME OF ROUGH-IN
OR SETTING WITHOUT ADDITIONAL COST TO THE PROJECT. THE CONTRACTOR
SHALL, WITHOUT EXTRA CHARGE, MAKE REASONABLE MODIFICATIONS TO THE
ELECTRICAL LAYOUT FOR THE FOLLOWING:
1. AS NEEDED TO PREVENT CONFLICT WITH THE WORK OF OTHER
TRADES OR FOR PROPER EXECUTION OF THE WORK.
2. AS DIRECTED BY THE ENGINEER AND/OR OWNER IN WRITING, PRIOR
TO COMPONENT INSTALLATION, FOR MINOR REVISIONS TO
ELECTRICAL INSTALLATION.
F. COOPERATE AND COORDINATE WORK WITH OTHER TRADES SO AS TO NOT
DELAY THE COMPLETION DATE OF THE PROJECT. STUDY AND BE FAMILIAR WITH
THE WORK OF OTHER TRADES AS REQUIRED FOR PROPER COORDINATION.
G. CERTAIN ELECTRICAL WORK IS INDICATED ON THE DRAWINGS AND
SPECIFICATIONS OF OTHER TRADES AND MAY NOT BE REPEATED ON THE
ELECTRICAL DRAWINGS AND SPECIFICATIONS. EXAMINE THE DOCUMENTS OF
OTHER TRADES AND INCLUDE ALL ELECTRICAL WORK IN THE BID AS REQUIRED
FOR A COMPLETE ELECTRICAL SYSTEM(S), UNLESS SPECIFICALLY NOTED AS
FURNISHED AND INSTALLED BY OTHERS.
H. COMPLETE ROUGH-IN REQUIREMENTS OF ALL EQUIPMENT TO BE WIRED OR
CONNECTED UNDER THIS PROJECT ARE NOT SHOWN ON THE DRAWINGS.
VERIFY ALL REQUIREMENTS WITH THE CONTRACTOR FURNISHING THE
EQUIPMENT OR WITH THE OWNER WHERE THE EQUIPMENT IS OWNER
FURNISHED, FOR THE EXACT INSTALLATION REQUIREMENTS.
I. EXAMINE THE ARCHITECTURAL DRAWINGS AND VERIFY SUFFICIENT WALL
THICKNESS FOR PROPER RECESSING DEPTH FOR ALL FLUSH-MOUNTED
EQUIPMENT. ALL INSTANCES OF INADEQUATE DEPTH SHALL BE BROUGHT TO
THE ATTENTION OF THE ENGINEER BEFORE THE BID DATE OR PROVIDED FOR
BY THE BID.
J. WORK SHOWN ON THE DRAWINGS AS “EXISTING” IS ASSUMED TO BE IN PLACE
AND SUITABLE FOR MODIFICATIONS AND ADDITIONS AS INDICATED ON THE
DRAWINGS. VERIFY THESE ITEMS AND MAKE NECESSARY FIELD
MEASUREMENTS PRIOR TO BID AND SHALL MAKE ALL NECESSARY PROVISIONS
REQUIRED FOR PROPER INSTALLATION AS REQUIRED BY THE DRAWINGS AND
SPECIFICATIONS. SUBMIT ANY QUESTIONS REQUIRING CLARIFICATION IN
WRITING TO THE ENGINEER NOT LESS THAN TEN DAYS PRIOR TO THE BID DATE.
K. SCHEDULE TIMES FOR ALL NECESSARY POWER OUTAGES FOR INSTALLATION
OF NEW ELECTRICAL DISTRIBUTION EQUIPMENT, MODIFICATIONS TO EXISTING
ELECTRICAL DISTRIBUTION EQUIPMENT, INSTALLATION OR MODIFICATION OF
FEEDER OR BRANCH CIRCUITS, TERMINATION OF CIRCUITS, AND CUTOVERS
SHALL WITH THE OWNER. ALL POWER OUTAGES SHALL BE AT TIMES APPROVED
BY THE OWNER AND SHALL BE OF THE SHORTEST POSSIBLE DURATION.
L. VERIFY AVAILABLE RECESSING DEPTHS FOR LUMINARIES (LIGHT FIXTURES)
AGAINST LUMINAIRE CATALOG REFERENCE MATERIAL PRIOR TO FURNISHING
SUBMITTALS FOR REVIEW TO THE ENGINEER.
M. REVIEW THE ARCHITECTURAL PLANS AND SHALL PROVIDE ALL NECESSARY
HARDWARE, PLASTER RINGS, DRYWALL FRAMING KITS, AND SURFACE
MOUNTING KITS AS REQUIRED BY CEILING CONSTRUCTION.
N. VERIFY ALL NECESSARY VERTICAL AND HORIZONTAL CLEARANCES FOR THE
INSTALLATION OF ELECTRICAL EQUIPMENT AND SHALL SHARE THIS
INFORMATION WITH ALL ASSOCIATED PARTIES AS NECESSARY FOR PROPER
COORDINATION.
O. PROVIDE A SUITABLE BRANCH CIRCUIT FOR EACH AND EVERY LIGHT FIXTURE,
RECEPTACLE, UTILIZATION EQUIPMENT, ETC. INSIDE OR OUTSIDE OF THE
BUILDING WHETHER OR NOT SPECIFICALLY NOTED ON THE ELECTRICAL
DRAWINGS AND SPECIFICATIONS, INCLUDING THE DRAWINGS AND
SPECIFICATIONS OF OTHER TRADES.
P. ALL SERVICE ENTRANCE, FEEDER, AND BRANCH CIRCUIT CONDUCTORS SHALL
BE COPPER, THE USE OF ALUMINUM IS NOT ACCEPTABLE.
Q. PROVIDE MINIMUM OF #12 AWG CONDUCTOR SIZE FOR ALL LIGHTING AND
POWER BRANCH CIRCUITS WHERE A WIRE SIZE IS NOT SPECIFICALLY
INDICATED ON THE DRAWINGS OR REQUIRED BY CODE. INCREASE CONDUCTOR
SIZE AS SHOWN ON THE DRAWINGS, REQUIRED BY LOAD, OR AS REQUIRED TO
LIMIT BRANCH CIRCUIT VOLTAGE DROP TO A MAXIMUM OF 3 PERCENT.
R. CONDUITS SHALL BE LIMITED TO A MAXIMUM OF NINE BRANCH CIRCUIT
CONDUCTORS OF WHICH A MAXIMUM OF FOUR PHASE CONDUCTORS SHALL BE
PERMITTED. GROUNDING CONDUCTORS SHALL NOT BE INCLUDED IN THE
COUNT.
S. PROVIDE A FULL SIZE NEUTRAL FOR EACH 120-VOLT AND 277-VOLT BRANCH
CIRCUIT.
T. PERMANENTLY AND EFFECTIVELY IDENTIFY AND TAPE TOGETHER EACH
NEUTRAL CONDUCTOR WITH ITS RESPECTIVE PHASE CONDUCTOR IN EACH
JUNCTION BOX, OUTLET BOX AND PANELBOARD WHERE TWO OR MORE
NEUTRALS ARE INSTALLED WITHIN THE SAME CONDUIT. PROVIDE MARKERS ON
THE NEUTRAL WIRE NUMBERED THE SAME AS THE RESPECTIVE BRANCH
CIRCUIT CONDUCTOR.
U. PROVIDE AN INSULATED GROUNDING CONDUCTOR IN EACH BRANCH CIRCUIT
CONDUIT AND EACH FEEDER CONDUIT.
V. WIRING FOR ALL SERVICE ENTRANCE, FEEDER CIRCUITS AND BRANCH CIRCUITS
SHALL BE INSTALLED IN CONDUITS IN ACCORDANCE WITH THE SPECIFICATIONS.
W. WIRING FOR ALL LOW-VOLTAGE COMMUNICATIONS AND SIGNALING SYSTEMS
SHALL BE INSTALLED IN CONDUITS IN ACCORDANCE WITH THE SPECIFICATIONS.
THIS REQUIREMENT SHALL APPLY, BUT NOT BE LIMITED TO THE FOLLOWING
SYSTEMS: FIRE ALARM SYSTEM, SOUND SYSTEMS, ACCESS CONTROL SYSTEMS,
INTRUSIONS DETECTION SYSTEM, NURSE CALL SYSTEM, AND OTHER SPECIAL
SYSTEMS.
X. WIRING FOR ALL TELECOMMUNICATIONS SYSTEMS SHALL BE INSTALLED IN
PATHWAYS IN ACCORDANCE WITH DIVISION 27 SPECIFICATION REQUIREMENTS.
Y. GENERAL CONDUIT INSTALLATION.
1. AREAS WITHOUT SUSPENDED CEILINGS: SUPPORT CONDUITS FROM
THE STRUCTURE AND INSTALL EXPOSED AS HIGH AS POSSIBLE TO
AVOID FUTURE CONFLICTS WHEN NEW CEILINGS ARE INSTALLED OR
WHEN ADDITIONAL WORK IN INSTALLED. ROUTE ALL CONDUITS
PARALLEL AND PERPENDICULAR WITH THE STRUCTURE.
2. AREAS WITH SUSPENDED CEILINGS: INSTALL CONDUITS CONCEALED
ABOVE SUSPENDED CEILINGS.
3. NEW WALLS: INSTALL CONDUITS CONCEALED IN NEW WALLS EXCEPT
WHERE SPECIFICALLY SHOWN AND NOTED AS EXPOSED ON THE
DRAWINGS.
4. EXISTING WALLS: INSTALL CONDUITS CONCEALED IN EXISTING WALLS
EXCEPT WHERE SPECIFICALLY SHOWN AND NOTED AS EXPOSED ON
THE DRAWINGS. PROVIDE ALL CUTTING, PATCHING, REPAIR AND
FINISHING OF EXISTING WALLS AS REQUIRED.
Z. COORDINATE, CHECK, AND VERIFY ROUGH-IN HEIGHTS AND LOCATIONS OF ALL
EQUIPMENT, DEVICES, RECEPTACLES, ETC. WITH THE DRAWINGS, EXISTING
CONDITIONS, AND THE WORK OF OTHER TRADES.
AA. PROVIDE ALL CUTTING AND PATCHING OF EXISTING CONSTRUCTION EXCEPT
WHERE SPECIFIED TO BE PROVIDED BY OTHERS ELSEWHERE IN THESE
SPECIFICATIONS. VERIFY EXACT LOCATIONS AND MATERIALS BEFORE
PERFORMING WORK. THE CUTTING OF STRUCTURAL MEMBERS AND BEARING
WALLS IS PROHIBITED EXCEPT WHERE SPECIFICALLY SHOWN AND NOTED ON
THE DRAWINGS AND/OR WHERE SPECIFICALLY PERMITTED BY THE ARCHITECT
AND STRUCTURAL ENGINEER.
BB. PATCH ALL HOLES IN EXISTING WALLS OR FLOORS WHERE EQUIPMENT OR
CONDUITS HAVE BEEN REMOVED WITH THE PROPER MATERIAL TO MATCH
EXISTING CONSTRUCTION. PATCH ALL HOLES IN FIRE RATED CONSTRUCTION
WITH APPROVED FIRE RESISTANT MATERIALS TO MATCH EXISTING RATINGS OF
CONSTRUCTION.
CC. COLOR FOR ALL WIRING DEVICES AND WALL MOUNTED LIGHTING CONTROLS TO
BE SELECTED BY THE ARCHITECT.
DD. DEVICE PLATE TYPE (NYLON OR STAINLESS STEEL) TO BE SELECTED BY THE
ARCHITECT. COLOR FOR NYLON DEVICE PLATES TO BE SELECTED BY THE
ARCHITECT.
EE. PROVIDE TAMPER-RESISTANT RECEPTACLES FOR ALL RECEPTACLES TO BE
PROVIDED IN WAITING ROOMS, LOUNGES, AND LOBBY AREAS.
FF. UPON COMPLETION OF WORK, DISCONNECT AND RECONNECT BRANCH
LIGHTING CIRCUITS AT PANELBOARDS TO OBTAIN AS NEAR LOAD BALANCE ON
CIRCUITS AS POSSIBLE. DEMONSTRATE ALL RESULTS TO THE OWNER’S
REPRESENTATIVE WITH DIGITAL AMMETER.
GG. PROVIDE A COMPLETED, PROTECTED, AND TYPEWRITTEN DIRECTORY CARD IN
EACH NEW AND EXISTING DISTRIBUTION BOARD WITHIN THE SCOPE OF THIS
PROJECT. THE DIRECTORY SHALL BE APPROXIMATELY 5” X 8” AND SHALL
INDICATE LOAD DESIGNATIONS WITH THE OWNER’S ASSOCIATED ROOM
NUMBERS FOR EACH CIRCUIT. UPDATE THE PANEL DIRECTORY CARD FOR
EACH EXISTING DISTRIBUTION PANEL IN WHICH CIRCUITS ARE MODIFIED,
ADDED, OR SUBTRACTED. VERIFY ALL EXISTING CIRCUITS TO REMAIN AND LIST
ON THE UPDATED DIRECTORY. DO NOT LIST EXISTING CIRCUITS AS "EXISTING
CIRCUIT" BUT RATHER THE ACTUAL LOAD DESIGNATION.
HH. UPDATE ALL ENGRAVED LABELS AS NEEDED WITH A SIMILAR ENGRAVED LABEL
SHOWING THE UPDATED EQUIPMENT NAME AND THE PREVIOUS EQUIPMENT
NAME. EXAMPLE: AT DISTRIBUTION PANEL DS-1A, THE BREAKER FEEDING MCC-
NORTH SHALL BE PROVIDED WITH A (2) SEPARATE NEW ENGRAVED LABELS:
ONE WITH THE WORDING DP-B-C-A AND ONE WITH THE WORDING PREVIOUSLY
MCC-NORTH. EXISTING DISTRIBUTION BOARD SHALL ALSO BE PROVIDED WITH
AN UPDATED TYPEWRITTEN DIRECTORY CARD (UPDATES WITH SIMILAR ORDING
AS LABEL).
II. ALL NEW DISTRIBUTION BOARDS SHALL BE PROVIDED WITH (2) SEPARATE
ENGRAVED LABELS: ONE WITH THE NAME OF THE PANEL AND ONE WITH THE
NAME OF THE MCC IT REPLACES. EXAMPLE,: AT DISTRIBUTION BOARD DP-B-C-A,
PROVIDE (2) SEAPARTE ENGRAVED LABELS: ONE WITH THE WORDING DP-B-C-A
AND ONE WITH THE WORDING PREVIOUSLY MCC-NORTH.
JJ. CONTRACTOR SHALL PROVIDE A SHORT CIRCUIT AND COORDINATION STUDY
BASED ON THE 2024 STUDY PERFORMED BY THE VA. PROVIDE ARC FLASH
WARNING LABELS ON ALL NEW EQUIPMENT INCLUDING VFD'S.
KK. THE CONTRACTOR SHALL INCLUDE ALL WORK AND COSTS RELATED TO
CONNECTIONS AND UPDATES OF THE EXISTING BAS. THE EXISTING BAS IS BY
TIRIDIUM FX EXPLORER; ALL WORK SHALL BE COORDINATE AND/OR COMPLETED
BY JCI. NEW VFD'S AND ELECTRICAL METERS AT DISTRIBUTION BOARDS SHALL
BE CONNECTED TO THE EXISTING BAS; PROVIDE ALL REQUIRED CABLING AND
CONDUITS AND MAKE FINAL CONNECTIONS. ALL ASSOCIATED PROGRAMMING
FOR ADDITIONAL REQUIREED POINTS IN THE BAS SHALL BE INCLUDED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
85% CONSTRUCTION DOCUMENTS 11/13/2023
A u to d e s k D o c s /2
.8
.0
V A
C in c in n a ti E le c tr ic D e fi c ie n c ie s /2
.8
.0
E v
.r v t
/2
/2
:3
:3
P
M
E-001
ELECTRICAL NOTES
GUIDON DESIGN
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
VA Cincinnati Electrical Deficiencies
3200 Vine Street, Cincinnati, OH
539-22-203
1, 14
01/27/2025 ARH MCP
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
ADDENDUM #1 02/24/2025
DN
DN
Elec. Rm.
C008
Transformer Room
A023
EP401
EP403
EP401
EP403
GENERAL NOTES
1. REFER TO SHEET E000 FOR ABBREVIATIONS AND SYMBOLS.
2. REFER TO SHEET E001 FOR NOTES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
85% CONSTRUCTION DOCUMENTS 11/13/2023
A u to d e s k D o c s /2
.8
.0
V A
C in c in n a ti E le c tr ic D e fi c ie n c ie s /2
.8
.0
E v
.r v t
/2
/2
:3
:4
P
M
EP101
BUILDING 01 ELECTRICAL
BASEMENT PLANGUIDON DESIGN
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
VA Cincinnati Electrical Deficiencies
3200 Vine Street, Cincinnati, OH
539-22-203
1, 14
01/27/2025 ARH MCP
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 3/64" = 1'-0"EP101
1 BASEMENT OVERALL PLAN
N
MACHINE ROOM
2121M
MACHINE ROOM
2121L
STAIRS #6
EP404
EP402
BLDG 1 KEYPLAN N
SHADE INDICATES
AREA OUT OF
PROJECT SCOPE
PROJECT
LOCATION
GENERAL NOTES
1. REFER TO SHEET E000 FOR ABBREVIATIONS AND SYMBOLS.
2. REFER TO SHEET E001 FOR NOTES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
85% CONSTRUCTION DOCUMENTS 11/13/2023
A u to d e s k D o c s /2
.8
.0
V A
C in c in n a ti E le c tr ic D e fi c ie n c ie s /2
.8
.0
E v
.r v t
/2
/2
:3
:4
P
M
EP102
BUILDING 01 ELECTRICAL TENTH
FLOOR PLANGUIDON DESIGN
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
VA Cincinnati Electrical Deficiencies
3200 Vine Street, Cincinnati, OH
539-22-203
1, 14
01/27/2025
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"EP102
1 BUILDING 1 - TENTH FLOOR - ELECTRICAL ROOM - NEW WORK PLAN
EP114
Main Electric
Main Electric
MVS UNIT SUB US1A 14MDP
14TDP1
14DP1
P2A 2B 2A 1B 1A
BDA FAAR
POWER PLAN NOTES
1. DISCONNECT AND REMOVE 400A/3P BREAKER FEEDING 14TDP1. BREAKER IS
INSTALLED WITHIN A GE SPECTRA SERIES SWITCHBOARD SECTION. PROVIDE
NEW BREAKER AT SAME LOCATION, BREAKER TYPE AND AIC RATING SHALL
MATCH EXISTING. PROVIDE ALL REQUIRED HARDWARE AND MAKE ALL FINAL
CONNECTIONS. INCLUDE IN BID THE COST TO ADJUST BREAKER TRIP
SETTINGS IN ACCORDANCE WITH LATEST ARC FLASH AND COORDINATION
STUDY.
POWER GENERAL NOTES
A. REFER TO SHEET E-000 FOR ABBREVIATIONS AND SYMBOLS.
B. REFER TO SHEET E-001 FOR NOTES.
C. ALL EQUIPMENT AND DEVICES SHOWN IN THIN/LIGHT LINEWEIGHT ARE
EXISTING TO REMAIN OR WORK BY OTHERS. ALL ITEMS SHOWN IN BOLD/DARK
LINEWEIGHT ARE NEW WORK.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
85% CONSTRUCTION DOCUMENTS 11/13/2023
A u to d e s k D o c s /2
.8
.0
V A
C in c in n a ti E le c tr ic D e fi c ie n c ie s /2
.8
.0
E v
.r v t
/2
/2
:3
:4
P
M
EP114
BUILDING 14 ELECTRICAL
SECOND FLOOR PLANGUIDON DESIGN
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
VA Cincinnati Electrical Deficiencies
3200 Vine Street, Cincinnati, OH
539-22-203
1, 14
01/27/2025 ARH MCP
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/8" = 1'-0"EP114
1 SECOND FLOOR POWER PLAN
SCALE: 1/4" = 1'-0"EP114
2 BUILDING 14 - SECOND FLOOR - ENLARGED 211 MAIN ELECTRICAL ROOM - NEW WORK PLAN
N
DEMOLITION NOTES
1. DEMOLISH EXISTING MCC-NORTH. INTERCEPT ALL EXISTING TO REMAIN
LOADS AND EXTEND FEEDERS TO NEW DP-B-C-A. EXISTING TO REMAIN
BOTTOM-FED CONDUITS SHALL BE INTERCEPTED IN JUNCTION BOXES AND
EXTENDED TO NEW DP-B-C-A. THE FOLLOWING CONDUITS AND WIRES ARE
APPROXIMATIONS AND SHALL BE FIELD-VERIFIED BY THE CONTRACTOR:
SECTION 1:
(10) #14 IN 1-1/2"C STUB-UP
(4)#10, (1)#10G AND (4)#14 IN 1-1/2"C STUB-UP
(4)#10, (1)#10G IN 1-1/2"C STUB-UP
(4)#8, (1)#10G IN 1-1/2"C STUB-UP
(4) 3/4"C AND WIRING TOP-FED
(1) MAIN FEEDERS AND CONDUIT (DEMOLISH)
SECTION 2:
(3)#10, (1)#10G IN 1"C STUB-UP
(3)#8, (1)#10G IN 1"C STUB-UP
(2) 3/4"C AND WIRING TOP-FED
SECTION 3:
(3)#6, (1)#8G IN 1-1/2"C STUBBED UP INTO SECTION 3
SECTION 4:
(1) 3/4"C AND WIRING TOP-FED (FIRE ALARM)
(4) 2"C AND WIRING SIDE-FED
(6) 3/4"C AND WIRING SIDE-FED (TO VFD'S ALONG SAME WALL AS MCC)
2. DEMOLISH EXISTING MCC-EAST. INTERCEPT ALL EXISTING TO REMAIN LOADS
AND EXTEND FEEDERS TO NEW DP-B-C-B. THE FOLLOWING CONDUITS AND
WIRES ARE APPROXIMATIONS AND SHALL BE VERIFIED BY THE CONTRACTOR:
SECTION 1:
(2) MAIN FEEDERS AND CONDUITS (DEMOLISH)
SECTION 4:
(7) 1"C AND WIRING TOP-FED
(4) 3/4"C AND WIRING TOP-FED
3. DISCONNECT AND RETAIN FIRE ALARM CONTROL MODULES. VERIFY
EQUIPMENT BEING SERVED/MONITORED BY MODULES. NUMERAL INDICATES
QUANTITY OF MODULES.
4. DISCONNECT AND REMOVE WALL-MOUNTED CAPACITOR/FILTER AND
ASSOCIATED CONDUIT AND WIRING BACK TO MCC-D.
5. DEMOLISH EXISTING MCC-D. INTERCEPT ALL EXISTING TO REMAIN LOADS AND
EXTEND FEEDERS TO NEW DP-B-A-A. THE FOLLOWING CONDUITS AND WIRES
ARE APPROXIMATIONS AND SHALL BE VERIFIED BY THE CONTRACTOR:
SECTION 1:
(1) MAIN FEEDERS AND CONDUIT (DEMOLISH)
(1) 3/4" AND WIRING TOP-FED (TO AHU-14)
(1) 3/4" AND WIRING SIDE-FED (TO VFD-CWP4)
(1) 3/4" AND WIRING SIDE-FED (TO FILTER/CAPACITOR) (DEMOLISH)
(1) 3/4" AND WIRING SIDE-FED (TO FIRE ALARM MODULES)
(2) 3/4" AND WIRING STUB-UP
SECTION 2:
(1) 1-1/2"C AND WIRING STUB-UP (DEMOLISH)
SECTION 4:
(7) 1"C AND WIRING TOP-FED
(4) 3/4"C AND WIRING TOP-FED
# POWER GENERAL NOTES
A. REFER TO SHEET E-000 FOR ABBREVIATIONS AND SYMBOLS.
B. REFER TO SHEET E-001 FOR NOTES.
C. REFER TO E-700 SERIES SHEETS FOR SINGLE LINE DIAGRAMS.
D. ALL EQUIPMENT AND DEVICES SHOWN IN THIN/LIGHT LINEWEIGHT ARE
EXISTING TO REMAIN OR WORK BY OTHERS. ALL ITEMS SHOWN IN BOLD/DARK
LINEWEIGHT WITH A DASHED LINE TYPE ARE TO BE DEMOLISHED. ALL ITEMS
SHOWN IN BOLD/DARK LINEWEIGHT WITH A SOLID LINE TYPE ARE NEW WORK.
E. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL EQUIPMENT AND
DEVICES WITH OTHER EQUIPMENT AND DEVICES PRIOR TO ROUGH-IN AND
INSTALLATION.
F. PRIOR TO DEMOLISHING MOTOR CONTROL CENTER(S), THE CONTRACTOR
SHALL FIELD VERIFY ALL LOADS INCLUDING SIZE OF WIRES, BREAKERS,
SWITCHES, FUSES AND MOTOR STARTERS.
G. MAINTAIN CIRCUITRY OF ALL EXISTING TO REMAIN DEVICES. WHERE A
DEMOLISHED OR RELOCATED ELECTRICAL DEVICE SERVES DOWNSTREAM
DEVICES, RECONNECT ALL CIRCUITRY TO MAINTAIN OPERATION. WHERE
REQUIRED CIRCUITRY TO BE MAINTAINED CONFLICTS WITH NEW
CONSTRUCTION WORK, RELOCATE AS NEEDED.
H. FOR ELECTRICAL DEVICES AND EQUIPMENT NOTED TO BE REMOVED OR
RELOCATED, REMOVE DEVICE AS DIRECTED AND ALL ACCESSORY
COMPONENTS. REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO
SOURCE OR NEAREST DEVICE TO REMAIN, UNO.
I. ALL UNUSED CONDUIT AND/OR WIRING SHALL BE REMOVED BACK TO SOURCE.
UPDATE PANEL SCHEDULES WITH NEW TYPE WRITTEN DIRECTORIES TO
REFLECT REMOVED CIRCUITS.
J. PRIOR TO REMOVAL OF A CIRCUIT FROM A PANEL, CONTRACTOR SHALL
VERIFY NO OTHER DEVICES EXIST ON THE CIRCUIT. ONCE A CIRCUIT HAS
BEEN REMOVED, THE REMAINING CIRCUIT BREAKER SHALL BE LABELED
SPARE, READY FOR USE UNDER NEW WORK.
K. NOT ALL ELECTRICAL DEVICES AND EQUIPMENT ARE SHOWN. LOCATIONS OF
EXISTING DEVICES AND EQUIPMENT SHOWN SHALL BE CONSIDERED
APPROXIMATE. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO
COMMENCING WORK.
L. TO THE BEST OF THEIR ABILITY, THE ENGINEER HAS IDENTIFIED EXISTING
ITEMS OF EQUIPMENT AND CONSTRUCTION THAT ARE REQUIRED TO BE
REMOVED OR OTHERWISE DEMOLISHED SO AS TO ALLOW THE INSTALLATION
OF NEW WORK. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND
ASSESS EACH SPACE AND FULFILL THE INTENT OF THE WORK INDICATED BY
THE CONSTRUCTION DOCUMENTS IN A MANNER SO AS NOT TO INTERFERE
WITH THE NORMAL OPERATION OF THE BUILDING. THE INFORMATION
PROVIDED IN NO WAY INTENDS TO SUGGEST THAT DEMOLITION IS LIMITED
ONLY TO THOSE ITEMS SPECIFICALLY IDENTIFIED. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO EXECUTE THE DEMOLITION PLAN, WHETHER SHOWN OR
NOT, TO ACCOMMODATE NEW CONSTRUCTION. ANY EXISTING WORK TO
REMAIN, IF DAMAGED BY ANY TRADE OR NEW CONSTRUCTION, SHALL BE
PATCHED, REPAIRED, OR REPLACED TO MATCH EXISTING.
M. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL
DEMOLITION WORK WITH ALL OTHER TRADES AND FOR THE MEANS AND
METHODS NECESSARY TO COMPLETE THE WORK.
N. PERFORM CUTTING, PATCHING, AND FILLING HOLES RESULTING FROM
DEMOLITION OR INSTALLATION OF NEW WORK, OR ANY OTHER EXISTING
FLOOR OR WALL PENETRATIONS WITH A UL-APPROVED MATERIAL TO
MAINTAIN THE EXISTING FIRE-RATED ASSEMBLY WHERE INDICATED.
PATCHING AND REPAIRS TO MATCH EXISTING CONDITIONS.
O. CONDUITS LOCATED IN EXISTING WALLS AND/OR FLOORS TO REMAIN AND
SERVING ITEMS BEING REMOVED SHALL HAVE WIRING REMOVED. CONDUIT
SHALL BE CUT OFF FLUSH WITH WALL OR FLOOR. WALL OR FLOOR SHALL BE
PATCHED TO MATCH SURROUNDING CONSTRUCTION.
P. DISRUPTION OF EXISTING SYSTEMS AND OPERATIONS SHALL BE
COORDINATED WITH OWNER FOUR WEEKS PRIOR TO PLANNED OUTAGE.
Q. SUPPORT AND PROTECT EXISTING TO REMAIN ELECTRICAL
INFRASTRUCTURE, INCLUDING BUT NOT LIMITED TO CONDUITS, WIRING,
DEVICES, AND FIXTURES AS REQUIRED.
R. REFER TO SHEET EP403 FOR SEQUENCE OF CONSTRUCTION PRIOR TO START
OF DEMOLITION WORK.
BC1L BEC1 1CEC3
ET1
(D) MCC-NORTH
SF9A SF9B EF30A EF30B
A T
S -P
S W
IT
C
H B
O A
R D
(D) MCC EAST
ESW-B 10
ESWB-20
PULL BOX
CONTROLS
ALTRONIX
CONTROLS
PULL BOXESWB
ESWB
PULL BOX
PULL BOXPULL BOX
PULL BOXPULL BOX
C A
B
IN
E T
B C
P
SWITCHBOARD DS-1X
ATS-SURG
C
C(4)
(6)
SWBD DS-1P
SECTION
SECTION
SECTION
SECTION
SPD
Elec. Rm.
C008
PB
SWITCHBOARD DS-1A
SECTION
SECTION
SECTION
SECTION
BLDG 1 KEYPLAN N
SHADE INDICATES
AREA OUT OF
PROJECT SCOPE
PROJECT
LOCATION
MAIN LUGS SPACE SPACE SPACE
SECTION 1 SECTION 2 SECTION 3 SECTION 4
MCC-EAST ELEVATION
(DEMOLITION)
SPARE
SPARE
RETURN AIR
SPACE SPACE SPACE SPACE
AHU 5
RETURN FAN 1
AH2 RETURN
(AHU 28)
SPACE
AHU 5 SUPPLY 1
A
B
C
D
E
F
G
H
I
J
L
M
K
N
O
SUPPLY AIR
AHU 5
RETURN FAN 2
AH2 SUPPLY
(AHU 28)
AHU 5 SUPPLY 2
MAIN LUGS
SF21B
SUPPLY FAN
SF21A
SUPPLY FAN
AHU 26
RETURN FAN
EF4
EXHAUST FAN
(SPARE)
EF9
EXHAUST FAN
(SPARE)
SPACE
SPACE
RF21
RETURN FAN
SPACE SPACE SPACE SPACE
SPACE SPACE SPACE SPACE
SPACE SPACE DAC-1
AIR COMPRESSOR
DOORS
(SPARE)
SPACE
AC-1
AIR COMPRESSOR
(SPARE)
EF2
TOILET EXHAUST FAN
CP1 & CP2
DUPLEX COND.
PUMPS
P1
PUMP
AHU 4
RETURN FAN #2
AHU 4
RETURN FAN #1
AHU 4
SUPPLY FAN #2
AHU 4
SUPPLY FAN #1
AHU 26
SUPPLY FAN
SECTION 1 SECTION 2 SECTION 3 SECTION 4
MCC-NORTH ELEVATION
(DEMOLITION)
P2
PUMP
A
B
C
D
E
F
G
H
I
J
L
M
K
N
O
US1D
MV SWGR PS1
Transformer
Room
A023
C
(2)
SECTION
(D) MCC-D
SECTION
SECTION
SECTION
SECTION
SECTION
(E) VFD-CWP4
US-P1
MAIN LUGS SPACE SPACE
SECTION 1 SECTION 2 SECTION 3
SPACE SPACE SPACE
P1
EAST CHILLED WATER
SHAFT PUMP
[OFF]
P2
SOUTH CHILLED WATER
SHAFT PUMP
[OFF]
A
B
C
D
E
F
G
H
I
J
L
M
K
N
O
AHU-14A
[SUPPLY FAN]
AHU-14B
[RETURN FAN]
P4
[OFF]
SPACE
SECTION 6
SPACE
SPACE
SPACE
CWP4
SPACE
SECTION 4 SECTION 5
SPARE
SPACESPACE
SPACEHWP3
SPACESPACE
SPACE
P3
NORTH CHILLED WATER
SHAFT PUMP
[OFF]
MCC-D ELEVATION
(DEMOLITION)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
85% CONSTRUCTION DOCUMENTS 11/13/2023
A u to d e s k D o c s /2
.8
.0
V A
C in c in n a ti E le c tr ic D e fi c ie n c ie s /2
.8
.0
E v
.r v t
/2
/2
:3
:5
P
M
EP401
BUILDING 01 ELECTRICAL
ENLARGED PLANS - DEMOLITIONGUIDON DESIGN
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
VA Cincinnati Electrical Deficiencies
3200 Vine Street, Cincinnati, OH
539-22-203
1, 14
01/27/2025 ARH ARH
BID DOCUMENTS
FULLY SPRINKLERED
SCALE: 1/4" = 1'-0"EP401
1 BUILDING 1 - BASEMENT - ENLARGED C008 ELECTRICAL ROOM - DEMOLITION PLAN
SCALE: 1/4" = 1'-0"EP401
2 BUILDING 1 - BASEMENT - ENLARGED A023 TRANSFORMER ROOM - DEMOLITION PLAN
MACHINE ROOM
2121L
STAIRS #6
(D) MCC-P2
SECTION
SECTION
(E) VFD-RF-AHU-7
(E) VFD-SF-AHU-7
(E) VFD-RF-AHU-8
(E) VFD-SF-AHU-8
BLDG 1 KEYPLAN N
SHADE INDICATES
AREA OUT OF
PROJECT SCOPE
PROJECT
LOCATION
POWER GENERAL NOTES
A. REFER TO SHEET E-000 FOR ABBREVIATIONS AND SYMBOLS.
B. REFER TO SHEET E-001 FOR NOTES.
C. REFER TO E-700 SERIES SHEETS FOR SINGLE LINE DIAGRAMS.
D. ALL EQUIPMENT AND DEVICES SHOWN IN THIN/LIGHT LINEWEIGHT ARE
EXISTING TO REMAIN OR WORK BY OTHERS. ALL ITEMS SHOWN IN BOLD/DARK
LINEWEIGHT WITH A DASHED LINE TYPE ARE TO BE DEMOLISHED. ALL ITEMS
SHOWN IN BOLD/DARK LINEWEIGHT WITH A SOLID LINE TYPE ARE NEW WORK.
E. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL EQUIPMENT AND
DEVICES WITH OTHER EQUIPMENT AND DEVICES PRIOR TO ROUGH-IN AND
INSTALLATION.
F. PRIOR TO DEMOLISHING MOTOR CONTROL CENTER(S), THE CONTRACTOR
SHALL FIELD VERIFY ALL LOADS INCLUDING SIZE OF WIRES, BREAKERS,
SWITCHES, FUSES AND MOTOR STARTERS.
G. MAINTAIN CIRCUITRY OF ALL EXISTING TO REMAIN DEVICES. WHERE A
DEMOLISHED OR RELOCATED ELECTRICAL DEVICE SERVES DOWNSTREAM
DEVICES, RECONNECT ALL CIRCUITRY TO MAINTAIN OPERATION. WHERE
REQUIRED CIRCUITRY TO BE MAINTAINED CONFLICTS WITH NEW
CONSTRUCTION WORK, RELOCATE AS NEEDED.
H. FOR ELECTRICAL DEVICES AND EQUIPMENT NOTED TO BE REMOVED OR
RELOCATED, REMOVE DEVICE AS DIRECTED AND ALL ACCESSORY
COMPONENTS. REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO
SOURCE OR NEAREST DEVICE TO REMAIN, UNO.
I. ALL UNUSED CONDUIT AND/OR WIRING SHALL BE REMOVED BACK TO SOURCE.
UPDATE PANEL SCHEDULES WITH NEW TYPE WRITTEN DIRECTORIES TO
REFLECT REMOVED CIRCUITS.
J. PRIOR TO REMOVAL OF A CIRCUIT…