Attachment II - Drawings Revised 2.26.2025.pdf

PDF 5 MB Posted

Attached to
Z1DA--Project No. 539-22-203 - Electric Deficiencies
Solicitation number
36C25025B0015
Issued by

About this file

This is a set of electrical construction drawings for VA Cincinnati Electric Deficiencies Project (539-22-203) at 3200 Vine Street, Cincinnati, OH. The drawings detail electrical system upgrades including demolition and replacement of multiple motor control centers (MCCs) with new distribution panels.

The drawings include demolition plans, new work plans, single line diagrams, symbols legend, and general notes for electrical work in Buildings 1 and 14. Key components include: replacement of MCC-North with new DP-B-C-A panel, MCC-East with DP-B-C-B panel, MCC-D with DP-B-A-A panel, and MCC-P2 with DP-10-A-A panel. The work involves intercepting and extending existing feeders, installing new variable frequency drives (VFDs), updating circuit breakers, and connecting fire alarm control modules. The drawings specify detailed sequencing of construction to minimize outages, with requirements for 4-week advance scheduling of shutdowns with the VA. All new distribution panels must be integrated with the existing Building Automation System (BAS) by Tridium FX Explorer.

View the file

Other files

File Type Posted
36C25025B0015 0003.docx DOCX document
Attachment IX - Justification and Approval - Sole Source to Post.pdf PDF
Attachment VIII - CVAMC and FT Thomas Arc Flash Study.pdf PDF
36C25025B0015 0002.docx DOCX document
Attachment VII - Pre-Bid RFIs - GDI.docx DOCX document
Attachment VI - Addendum - Specifications.pdf PDF
Site Visit Sign In.pdf PDF
36C25025B0015 0001.docx DOCX document
36C25025B0015.pdf PDF
Attachment II - Drawings.pdf PDF
Attachment I - DBA WD.pdf PDF
36C25025B0015_1.docx DOCX document
Attachment V - RFI Form.pdf PDF
Attachment III - Specifications.pdf PDF
Attachment IV - VAAR 852.219-75.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

85% CONSTRUCTION DOCUMENTS 11/13/2023

A u to d e s k D o c s /2

.8

.0

V A

C in c in n a ti E le c tr ic D e fi c ie n c ie s /2

.8

.0

E v

.r v t

/2

/2

:3

:5

P

M

GI000

COVER SHEET

GUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

VA Cincinnati Electrical Deficiencies

3200 Vine Street, Cincinnati, OH

539-22-203

1, 14

01/27/2025

539-22-203

VA Cincinnati Electrical Deficiencies

VA Cincinnati

3200 Vine Street, Cincinnati, OH

Construction Documents

BID DOCUMENTS

FULLY SPRINKLERED

AREA MAP VICINITY MAPN N

PROJECT LOCATION

Contact:

VAMC CINCINNATI

Justin Beaudoin

COR

3200 Vine St Cincinnati, OH 45220 p: 513-609-2338 e: justin.beaudoin@va.gov

OWNER

Contact:

Al Halabi

Senior Electrical Engineer

ELECTRICAL

1221 North Pennsylvania Street Suite 200 Indianapolis, IN 46202 p: 317.800.6388 e: ahalabi@guidon.com

GUIDON DESIGN INC.

SHEET INDEX

SHEET NUMBER SHEET NAME

GENERAL

GI000 COVER SHEET

ELECTRICAL

E-000 ELECTRICAL SYMBOLS LEGEND AND GENERAL NOTES

E-001 ELECTRICAL NOTES

EP101 BUILDING 01 ELECTRICAL BASEMENT PLAN

EP102 BUILDING 01 ELECTRICAL TENTH FLOOR PLAN

EP114 BUILDING 14 ELECTRICAL SECOND FLOOR PLAN

EP401 BUILDING 01 ELECTRICAL ENLARGED PLANS - DEMOLITION

EP402 BUILDING 01 ELECTRICAL ENLARGED PLAN - DEMOLITION

EP403 BUILDING 01 ELECTRICAL ENLARGED PLANS - NEW WORK

EP404 BUILDING 01 ELECTRICAL ENLARGED PLAN - NEW WORK

E-701 ELECTRICAL SINGLE LINE DIAGRAM - DEMOLITION

E-702 ELECTRICAL SINGLE LINE DIAGRAM - DEMOLITION

E-703 ELECTRICAL SINGLE LINE DIAGRAM - NEW WORK

E-704 ELECTRICAL SINGLE LINE DIAGRAM - NEW WORK

Revisions: Date:

02/24/2025

ABBREVIATION DESCRIPTION

+ MOUNTING HEIGHT

1P SINGLE POLE

1PH SINGLE-PHASE

2P TWO POLE

2/C TWO-CONDUCTOR

3P THREE POLE

3PH THREE-PHASE

3W THREE-WIRE

3/C THREE-CONDUCTOR

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

(D) DEMOLISH

(E) EXISTING

(ER) EXISTING TO BE RELOCATED

(ETR) EXISTING TO REMAIN

(N) NEW

(R) REMOVE (DEMOLISH)

(REL) RELOCATE EXISTING

(T) TEMPORARY

A or AMP AMPERE A/C or AC AIR CONDITIONING

A/E ARCHITECT/ENGINEER

A/V AUDIO VISUAL

AC ALTERNATING CURRENT or

ARMORED CABLE

ACP ACCESS PANEL

ACU AIR CONDITIONING UNIT

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME or AMP FUSE

AFC AVAILABLE FAULT CURRENT

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AM AMMETER

AMB AMBIENT

APPROX. APPROXIMATELY

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AVG AVERAGE

BBH BASEBOARD HEATER

BC BARE COPPER

BFF BELOW FINISH FLOOR

BHP BRAKE HORSEPOWER

BIL BASIC INSULATION LEVEL

BKR BREAKER

BL BUILDING LINE

BLDG BUILDING

BR BRANCH

BRKR BREAKER

BTM BOTTOM

BYP BYPASS

°C CELSIUS

C CONDUIT

C/C CENTER TO CENTER

CAB CABINET

CALC CALCULATE or CALCULATION

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CB or C/B CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

ABBREVIATIONS

ABBREVIATION DESCRIPTION

CD CONSTRUCTION DOCUMENTS

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CL CENTER LINE

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAXIAL CABLE

COF COFFEE MACHINE

COL COLUMN

COMM COMMUNICATION

COMP COMPRESSOR

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUE

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CR CRITICAL

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTRL CONTROL

CU COPPER

CU FT CUBIC FEET

DB DECIBEL or DIRECT BURIAL

DC DIRECT CURRENT

DEMO DEMOLITION

DEPT DEPARTMENT

DF DRINKING FOUNTAIN

DISC DISCONNECT

DIST DISTRIBUTION

DM DEMAND METER

DN DOWN

DO DRAWOUT or DOOR OPENER

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DW DISHWASHER

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ECB ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC or ELECTRICAL

ELEV ELEVATOR

ELV ELEVATION

EMER or EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EP ELECTRIC PNEUMATIC

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXP EXPLOSIONPROOF

EXH EXHAUST

EXT EXTERIOR

°F FAHRENHEIT

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FHC FIRE HOSE CABINET

FIXT FIXTURE

FL FLOOR

FLA FULL LOAD AMPS

FP FIRE PROTECTION

ABBREVIATION DESCRIPTION

FLEX-CONN FLEXIBLE CONNECTION

FLUOR FLUORESCENT

FMC FLEXIBLE METALLIC CONDUIT

FRZ FREEZER

FSS FUSED SAFETY SWITCH

FT FEET or FOOT

FTG FOOTING

FV FULL VOLTAGE

FVNR FULL VOLTAGE NON-REVERSING

G or GND GROUND

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEC GROUNDING ELECTRODE CONDUCTOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

GFP GROUND FAULT PROTECTION

GRS GALVANIZED RIGID STEEL

GTB GROUND TERMINAL BOX

HGT or HT HEIGHT

HH HANDHOLE

HID HIGH INTENSITY DISCHARGE

HO HAND OPERATED

HOA HAND-OFF-AUTOMATIC

HORZ HORIZONTAL

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HTR HEATER

HV HIGH VOLTAGE

HZ HERTZ

IC INTERCOMMUNICATION

ID INSIDE DIAMETER

IDS INTRUSION DETECTION SYSTEM

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

ISG ISOLATED GROUND SURGE GUARD

IWH INSTANTANEOUS WATER HEATER

JB JUNCTION BOX

JT JOINT

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LS LIFE SAFETY

LT LIGHT

LTG LIGHTING

LV LOW VOLTAGE

LVL LEVEL

MATV MASTER ANTENNA TELEVISION

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

INDICATOR LIGHT

[LIGHT COLOR]

A AMBER

B BLUE

G GREEN

R RED

NORMALLY OPEN CONTACT

GROUND

MOTOR ("HP" INDICATES HORSEPOWER)

TRANSFORMER

UTILITY CONNECTION

KIRK KEY INTERLOCK

UTILITY METER OR RELAY COIL

DRAWOUT PROTECTION DEVICE

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

FEEDER CALLOUT

REFER TO FEEDER SCHEDULE

NORMALLY CLOSED CONTACT

LINE/LOAD REACTOR (IMPEDANCE AS

INDICATED)

CIRCUIT BREAKER OR MOTOR CIRCUIT

PROTECTOR

FUSE

RECTIFIER OR INVERTER

BATTERY SUPPLY

BUS

MOTOR OVERLOAD

A xxx

RESISTIVE HEATING ELEMENT

VARIABLE FREQUENCY CONTROLLER W/

DISCONNECT SWITCH

VARIABLE FREQUENCY CONTROLLER

VFD

SINGLE LINE SYMBOLS

BUS WITH EXTENSION PROVISIONS

SWITCH

3%

NODE CONNECTION TO BUS

DIGITAL METERDM

M

K

SURGE PROTECTION DEVICESPD

MEDIA CONVERTERMC

CABLE BONDING OR TERMINATION CONNECTION

VFD

HP

ABBREVIATION DESCRIPTION

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MM MILLIMETERS

MMFO MULTI-MODE FIBER OPTIC

MOCP MAXIMUM OVERCURRENT PROTECTION

MTD MOUNTED

MTG HT MOUNTING HEIGHT

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

MWV MICROWAVE

MXFMR MEDIUM VOLTAGE TRANSFORMER

N NEUTRAL

NA or N/A NOT APPLICABLE

NAC NOTIFICATION APPLIANCE CIRCUIT

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OCPD OVERCURRENT PROTECTION DEVICE

OD OUTSIDE DIAMETER

OL OVERLOAD

OR OPERATING ROOM

P POLE

PA PUBLIC ADDRESS

PACS PHYSICAL ACCESS CONTROL SYSTEM

PB PULL BOX or PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PC PHOTOCELL

PCB POLYCHLORINATED BIPHENYL

PF POWER FACTOR

PH or Ø PHASE

PIV POST INDICATOR VALVE

PL PILOT LIGHT

PNL PANELBOARD

PREFAB PREFABRICATED

PT POTENTIAL TRANSFORMER or

POKE-THRU

PTS PNEUMATIC TUBE STATION

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RACU ROOM AIR CONDITIONING UNIT

RAD RADIATION

RCP REFLECTED CEILING PLAN

REC or RECPT RECEPTACLE

REF REFRIGERATOR

REQD REQUIRED

RGIP REMOTE GROUND INDICATING PANEL

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RPM REVOLUTIONS PER MINUTE

ABBREVIATION DESCRIPTION

SC SHORT CIRCUIT

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SE SERVICE ENTRANCE

SF SQUARE FOOT (FEET)

SI INTERNATIONAL SYSTEM OF UNITS

SMFO SINGLE MODE FIBER OPTIC

SN SOLID NEUTRAL

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SQ SQUARE

SS SAFETY SWITCH

SSSS SOLID STATE SOFT START

SSTV SECURITY SURVEILLANCE TELEVISION

STD STANDARD

STN STATION

STP SHIELDED TWISTED PAIR

SUSP SUSPENDED

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TBB TELECOM BACK BOARD

TC TIME CLOCK

TCC TEMPERATURE CONTROL CONTRACTOR

TELE TELEPHONE

TELECOM TELECOMMUNICATION

TEMP TEMPERATURE OR TEMPORARY

TGB TELECOM GROUND BAR

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UC or U/C UNDER COUNTER UG or U/G UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

UV UNIT VENTILATOR

V VOLT or VOLTAGE

VA VOLT AMPERE

VAC VACUUM

VAR VOLT AMPERE REACTIVE

VB VACUUM BREAKER

VC VACUUM CLEANING

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

VM VOLTMETER

VOL VOLUME

VP VAPORPROOF

VSD/VFC VARIABLE SPEED DRIVE/CONTROLLER

W WATT

W/ WITH

W/O WITHOUT

WAO WORK AREA OUTLET (TELECOM)

WAP WIRELESS ACCESS POINT

WH WATER HEATER

WP WEATHERPROOF

WT WIRE TROUGH

WTR WATER

XFER TRANSFER

XFMR TRANSFORMER

Z IMPEDANCE

AUTOMATIC TRANSFER SWITCH

MANUAL TRANSFER SWITCH

A

N E AUTOMATIC TRANSFER SWITCH

WITH BYPASS

MOTOR STARTER WITH MOTOR

CIRCUIT PROTECTOR

FUSIBLE DISCONNECT SWITCH

DISCONNECT SWITCH

PACKAGED VARIABLE FREQUENCY CONTROLLER

WITH DISCONNECT/OVERCURRENT PROTECTION,

LINE REACTOR, FRONT MOUNTED DISPLAY AND

CONTROLS WITHIN A SINGLE ENCLOSURE.

3%

VFD

3%

IL

3%

VFD

3%

IL

XXXA

3P

XP

XXXA

3P

XP

EQUIP TAG

AMPS

POLES

TYPE

SIZE

DISCONNECT / OVERCURRENT PROTECTION TYPE

IN-LINE FUSE (SIZE PER MANUFACTURER)

LINE REACTOR (IMPEDANCE AS INDICATED)

INTERNAL VARIABLE FREQUENCY CONTROLLER

DRIVE OUTPUT FILTERING (WHERE

INDICATED) TYPE:

LOAD SIDE REACTOR (IMPEDANCE AS

INDICATED (AS SHOWN)

DV/DT FILTER:

DV/DT

PACKAGED VARIABLE FREQUENCY CONTROLLER

WITH DISCONNECT/OVERCURRENT PROTECTION,

LINE REACTOR, FRONT MOUNTED DISPLAY AND

CONTROLS WITHIN A SINGLE ENCLOSURE.

DISCONNECT / OVERCURRENT PROTECTION TYPE

IN-LINE FUSE (SIZE PER MANUFACTURER)

LINE REACTOR (IMPEDANCE AS INDICATED)

INTERNAL VARIABLE FREQUENCY CONTROLLER

DRIVE OUTPUT FILTERING (WHERE

INDICATED) TYPE:

LOAD SIDE REACTOR (IMPEDANCE AS

INDICATED (AS SHOWN)

DV/DT FILTER:

DV/DT

BYPASS (AUTO/MANUAL AS DESCRIBED) WITH

INPUT/OUTPUT ISOLATION (WHERE SHOWN)

AND MOTOR STARTER (WHERE SHOWN)

EQUIP

NAME

CP

PANELBOARD OR UTILIZATION

EQUIPMENT

UTILIZATION EQUIPMENT WITH CONTROL

PANEL

PANELBOARD

DEVICE

TOGGLE SWITCH

TELEPHONE/DATA OUTLET

DISCONNECT SWITCH

MOTOR STARTER AND VFD

FIRE ALARM PULL STATION

FIRE ALARM HORN/STROBE

WALL PHONE

EXIT SIGN

CARD READER AND KEYPAD

CLOCK RECEPTACLE

WALL SPEAKER

RECEPTACLE

DIGITAL MONITOR OR SCREEN

RECEPTACLE (CLEAN ROOM)

6' - 6"

MOUNTING HEIGHT (AFF)

4' - 0"

1' - 6"

6' - 6" MAX.

6' - 6" MAX.

4' - 0"

6' - 8"

5' - 0"

NOTE 10, 11

4' - 0"

8' - 0"

8' - 0"

1' - 6"

5' - 0"

4' - 0"

TOP

TO:

TOP

CENTER

TOP

CENTER

TOP

BOTTOM

CENTER

NOTE 10, 11

TOP

CENTER

CENTER

CENTER

CENTER

TOP

TELE/DATA OUTLET (CLEAN ROOM) 4' - 0" TOP

1. ALL MOUNTING HEIGHTS SHALL BE AS LISTED ABOVE UNLESS OTHERWISE

INDICATED ON DRAWINGS.

2. ALL MOUNTING HEIGHTS SHALL BE IN ACCORDANCE WITH THE AMERICANS

WITH DISABILITIES ACT.

3. MOUNTING HEIGHTS AND LOCATIONS OF DEVICES SHOWN ON HORIZONTAL

AND VERTICAL CHASES SHALL BE COORDINATED WITH OTHER UTILITIES IN

THE CHASE. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR

CHASE LOCATIONS AND MOUNTING LOCATIONS.

4. MOUNTING HEIGHTS AND LOCATIONS OF SURFACE PLUGMOLD RACEWAY

SHALL BE COORDINATED WITH COUNTER TOPS AND BACK SPLASHES.

REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR COUNTER

LOCATIONS AND DIMENSIONS.

5. '+' SHOWN BESIDE A DEVICE INDICATES THAT IT SHALL BE INSTALLED ABOVE

COUNTER, AND BACK SPLASH WHERE APPLICABLE. INSTALL OUTLETS 6"

ABOVE COUNTER TOP. COORDINATE EXACT HEIGHT WITH ARCHITECTURAL

ELEVATIONS AND/OR CASEWORK DRAWINGS.

6. 'UC' SHOWN BESIDE A DEVICE INDICATES THAT IT SHALL BE INSTALLED 4"

BELOW COUNTER OR 18" ABOVE FINISHED FLOOR, WHICHEVER IS FEASIBLE.

7. '+P' SHOWN BESIDE A DEVICE INDICATES IT SHALL BE INSTALLED 18" ABOVE

PLATFORM.

8. REFER TO SECURITY VENDOR AND CONTRACTOR RECOMMENDATIONS AND

PRODUCT DATA FOR MOUNTING HEIGHTS OF SECURITY CAMERAS.

9. INSTALL WALL MOUNTED OCCUPANCY SENSORS 6" BELOW CEILING OR AT

HEIGHT NOT TO EXCEED PRODUCT MANUFACTURER RECOMMENDATIONS.

10. WALL MOUNTED EXIT SIGNS INSTALLED ABOVE DOORS SHALL BE INSTALLED

1'-0" ABOVE THE TOP OF THE DOOR FRAME TO THE BOTTOM OF THE EXIT

SIGN. WHERE CEILING HEIGHT DOES NOT ALLOW FOR MOUNTING AT THIS

LOCATION, INSTALL SIGN CENTERED BETWEEN DOOR FRAME AND CEILING.

11. PENDANT MOUNTED EXIT SIGNS SHALL BE INSTALLED AT 10'-0" AFF AS

MEASURED TO THE BOTTOM OF THE EXIT SIGN. ADJUST AS NECESSARY IN

UNFINISHED SPACES TO CLEAR WORK PERFORMED BY OTHER TRADES.

INSTALL EXIT SIGN SO LINE OF SIGHT IS MAINTAINED AND NOT HINDERED BY

WORK FROM OTHER TRADES.

TOP

4' - 0" MAX.GROUND BUS BAR

DOOR OPERATOR 4' - 0" TOP

AUDIO-VISUAL OUTLETS 1' - 6" CENTER

DOOR RELEASE BUTTON 4' - 0" TOP

RECEPTACLE (ABOVE COUNTER) 6", NOTE 5 BOTTOM

STANDARD MOUNTING HEIGHTS

TELE/DATA OUTLET (ADA) 4' - 0" TOP

QUADRUPLEX RECEPTACLE

ON STANDBY POWER - 125V,2P,3W*

DUPLEX RECEPTACLE

ON STANDBY POWER - 125V,2P,3W*

CEILING MOUNTED JUNCTION BOX

W/ HANGING RECEPTACLE CORD

QUADRUPLEX RECEPTACLE - 125V,2P,3W*

SIMPLEX RECEPTACLE - 125V,2P,3W*

DUPLEX RECEPTACLE - 125V,2P,3W*

NEMA 250 ENCLOSURE RATING SHALL BE

INDICATED ON PLANS, RECEPTACLE TYPE

DESIGNATION, OR TEXT SHEET OR GENERAL

NOTATION. NEMA 1 UNLESS NOTED OTHERWISE.

NEMA RECEPTACLE WD 1 CONFIGURATION SHALL

BE INDICATED ON PLANS.

L5-20R UNLESS OTHERWISE NOTED.

SIMPLEX RECEPTACLE

ON UPS OR STANDBY POWER - 125V,2P,3W*

[INDICATES NEMA WD 1 CONFIGURATION].

L5-20R UNLESS OTHERWISE NOTED.

[RECEPTACLE TYPE]

GFCI GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE

IG ISOLATED GROUND RECEPTACLE

SP SURGE SUPPRESSION RECEPTACLE

WP RECEPTACLE WITH WEATHERPROOF

COVER

TP TAMPER-PROOF RECEPTACLE

XP EXPLOSION-PROOF RECEPTACLE

USB RECEPTACLE WITH INTEGRAL USB PORT

SW SWITCHED OR CONTROLLED RECEPTACLE

WALL

MOUNT

FLOOR

MOUNT

5-30R

IG

CEILING

MOUNT

QUADRUPLEX RECEPTACLE

ON UPS POWER - 125V,2P,3W*

DUPLEX RECEPTACLE

ON UPS POWER - 125V,2P,3W*

SPECIAL PURPOSE RECEPTACLE*^

SPECIAL PURPOSE RECEPTACLE

ON STANDBY POWER*^

XP BL

PULL BOXPB

SPECIAL PURPOSE RECEPTACLE

ON UPS POWER*^

J

POWER DEVICE

SYMBOLS

NONFUSIBLE SAFETY DISCONNECT SWITCH

WALL OR SURFACE MOUNTED TOGGLE SWITCH

[SUBSCRIPT INDICATES TYPE OF SWITCH]

3 THREE POLE SWITCH

4 FOUR POLE SWITCH

P SWITCH WITH PILOT LIGHT

V VARIABLE SPEED CONTROL SWITCH

T FRACTIONAL HORSEPOWER MANUAL MOTOR

CONTROLLER WITH OVERLOADS

M MANUAL MOTOR CONTROLLER

CO SINGLE POLE, CENTER-OFF MOMENTARY

CONTACT SWITCH

R/L RAISE/LOWER SWITCH

T

POWER EQUIPMENT

SYMBOLS

R

[DISCONNECT TYPE]

R RECESSED OR FLUSH MOUNTED

C AUXILIARY CONTACT

NEMA ENCLOSURE TYPE SHALL BE

INDICATED ON PLANS.

NEMA 1 UNLESS OTHERWISE NOTED.

FUSIBLE SAFETY DISCONNECT SWITCH

MOTOR STARTER

COMBINATION MOTOR STARTER

W/ MOTOR CIRCUIT PROTECTOR

COMBINATION MOTOR STARTER

WITH FUSIBLE DISCONNECT SWITCH

208/120V DISTRIBUTION OR BRANCH PANELBOARD

480V OR 480/277V DISTRIBUTION OR BRANCH PANELBOARD

VARIABLE FREQUENCY DRIVE OR CONTROLLER,

CONTROL PANEL OR OTHER DISTRIBUTION EQUIPMENT

SPD WALL MOUNTED SURGE PROTECTION DEVICE

240/120V DISTRIBUTION OR BRANCH PANELBOARD

ENCLOSED CIRCUIT BREAKER

VARIABLE FREQUENCY CONTROLLER W/ DISCONNECT SWITCH

VARIABLE FREQUENCY CONTROLLER

VFD

VFD

WALL OR CEILING MOUNTED FIRE ALARM AUDIBLE

AND VISIBLE DEVICE

INTELLIGENT SYSTEM MONITOR & CONTROL DEVICES

FIRE ALARM MANUAL PULL STATION

CEILING MOUNTED FIRE ALARM VISIBLE DEVICE

WALL OR CEILING MOUNTED FIRE AUDIBLE DEVICE

C

AUTOMATIC SMOKE/HEAT DETECTOR

[DETECTOR CLASSIFICATION]

AS AIR SAMPLING SMOKE DETECTOR

BR BEAM TYPE SMOKE DETECTOR - RECEIVER

BT BEAM TYPE SMOKE DETECTOR - TRANSMITTER

D DUCT MOUNTED, PHOTOELECTRIC SMOKE

DETECTOR

F FIXED TEMPERATURE HEAT DETECTOR

FR COMBINATION RATE OF RISE PLUS

FIXED TEMPERATURE HEAT DETECTOR

I IONIZATION SMOKE DETECTOR

P PHOTOELECTRIC SMOKE DETECTOR

R RELAY BASE SMOKE DETECTOR

RR RATE OF RISE HEAT DETECTOR

SB SOUNDER BASE SMOKE DETECTOR

SS SINGLE STATION SMOKE DETECTOR

[RELAY FUNCTION]

C CONTROL

I ISOLATION

M MONITOR

WALL MOUNTED FIRE ALARM VISIBLE DEVICE

AUTOMATIC GAS DETECTOR

[DETECTOR CLASSIFICATION]

A AMMONIA DETECTOR

CH4 METHANE DETECTOR

CO CARBON MONOXIDE DETECTOR

CO2 CARBON DIOXIDE DETECTOR

HCL HYDROGEN CHLORIDE DETECTOR

N2 NITROGEN DETECTOR

O2 OXYGEN DETECTOR

FIRE ALARM CONTROL PANEL

[CONTROL PANEL FUNCTION]

FACP FIRE ALARM MAIN CONTROL PANEL

FAA FIRE ALARM ANNUNCIATOR PANEL

PRE PRE-ACTION SPRINKLER SYSTEM CONTROL PANEL

SAP SPRINKLER ALARM SYSTEM CONTROL PANEL

FATC FIRE ALARM TERMINAL CABINET

BATT FIRE ALARM BATTERY CABINET

NAC FIRE ALARM POWER BOOSTER PANEL

GACP GAS DETECTION & ALARM CONTROL PANEL

A

B

F

F

P

FIRE ALARM BELL

FIRE ALARM TROUBLE BELLT

F

F

F

FACP

MAGNETIC DOOR HOLDERDH

FIRE ALARM FLOW SWITCHFS

FIRE ALARM TAMPER SWITCHTS

FIRE ALARM & DETECTION

SYSTEM SYMBOLS

FSD FIRE SMOKE DAMPER

SMOKE DETECTOR AND/OR DAMPER REMOTE TEST

SWITCH AND STATUS INDICATORRTS

WIRELESS ACCESS POINT

WALL MOUNTED VOICE/DATA FEED TO PRE-WIRED

FURNITURE SYSTEM

PP DUAL CHANNEL POWER & TELE/DATA POLE (FROM CEILING)

FC

FIRE RATED POKE-THRU ASSEMBLY

PX

[POKE-THRU FUNCTION]

AV POWER, VOICE, DATA AND A/V

D DATA RECEPTACLE

FC VOICE/DATA FEED TO PRE-WIRED FURNITURE SYSTEM

PX POWER, VOICE AND DATA

V VOICE RECEPTACLE

VD VOICE/DATA RECEPTACLE

SINGLE GANG VOICE/DATA OUTLET,

TYPICAL (1) VOICE, (1) DATA TERMINATIONS

WALL

MOUNT

FLOOR

MOUNT

CEILING

MOUNT

SINGLE GANG VOICE OUTLET,

TYPICAL (1) VOICE TERMINATION

SINGLE GANG DATA OUTLET,

TYPICAL (2) DATA TERMINATIONS

[INDICATES NUMBER OF DATA

TERMINATIONS].

IF NOT INDICATED, PROVIDE 2.

DATA SURFACE RACEWAY

WAP

FC

FLOOR BOX VOICE/DATA FEED TO PRE-WIRED

FURNITURE SYSTEM

COMMUNICATIONS SYSTEM

SYMBOLS

C DIRECT CONNECTION TO TELECOMMUNICATION SYSTEM

(NO FACEPLATE OR WALL DEVICE)

FB COMBINATION POWER AND DATA FLOOR BOX

DAS DISTRIBUTIVE ANTENNA SYSTEM

WALL MOUNTED CLOCK HANGER RECEPTACLE

GROUND ROD IN TEST WELL

WALL MOUNTED GROUNDING BUS BAR

TW

GROUND ROD

GROUNDING DUPLEX RECEPTACLE

LIGHTNING PROTECTION AIR TERMINAL

EXOTHERMIC WELD CONNECTION TO GROUND CONDUCTOR

EXOTHERMIC WELD CONNECTION TO BUILDING STRUCTURE

G

GROUNDING EQUIPMENT

SYMBOLS

MECHANICAL GROUND CONNECTION

CIRCUIT NUMBER(S) OF PANELBOARD

RP-2/1,3,5

PANELBOARD NAME

CONDUIT AND WIRING

SYMBOLS

HOT CONDUCTOR

NEUTRAL CONDUCTOR

GROUND CONDUCTOR

DEFERRED PERMIT

SUBMITTALS

1. FIRE ALARM SYSTEM INCLUDING BUT NOT LIMITED TO: BATTERY

CALCULATIONS, VOLTAGE DROP CALCULATIONS, NOTIFICATION

AND INITIATION DEVICE LOCATIONS, AND MANUFACTURER

CUTSHEETS FOR EQUIPMENT INSTALLED. SYSTEM SHALL BE IN

COMPLIANCE WITH INTERNATIONAL BUILDING CODE AND NFPA 72

REQUIREMENTS. REFER TO MORE INFORMATION IN

SPECIFICATION SECTION 283100.

GENERAL NOTES

1. LEAD SHEET CONTENT IS GENERAL IN NATURE, NOT ALL SYMBOLOGY,

LEGENDS ELEMENTS, AND ABBREVIATIONS SHOWN ON THIS SHEET

ARE USED AND THEIR INCLUSION ON THIS SHEET IS NOT AN

INDICATOR OF RELEVANCE TO SPECIFIC PROJECT SCOPES.

2. CONTRACTOR IS RESPONSIBLE FOR SCHEDULING OF LIGHTING,

POWER, FIRE ALARM, ETC. SHUT-DOWNS WITH THE OWNER. SHUT

DOWNS SHALL BE SCHEDULED DURING OFF-HOURS OR WEEKENDS.

3. CONDUIT ROUTING SHOWN ON THE DRAWINGS IS SCHEMATIC.

CONTRACTOR TO COORDINATE INSTALLATION WITH EXISTING

LIGHTING AND MECHANICAL SYSTEMS, AND WITH PIPING, PLUMBING

AND MECHANICAL INSTALLATION ON THIS PROJECT.

4. PROVIDE A 4" 3000 PSI CONCRETE HOUSE KEEPING PAD FOR ALL

FLOOR MOUNTED ELECTRICAL EQUIPMENT.

5. PROVIDE A SEPARATE GROUNDED CONDUCTOR (NEUTRAL) WIRE WITH

EACH CIRCUIT, UNLESS NOTED OTHERWISE. USE OF MULTIWIRE

BRANCH CIRCUITS IS NOT ACCEPTABLE.

6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL REQUIRED

SUPPORTS FOR ALL DEVICES AND EQUIPMENT FURNISHED BY THE

ELECTRICAL CONTRACTOR AND SHALL NOT RELY ON SUPPORTS

PROVIDED BY OTHER TRADES. SUPPORT SUCH EQUIPMENT PER

APPROVED GOVERNING CODES OR PER APPROVAL OF THE ENGINEER.

UNACCEPTABLE WORKMANSHIP OR MATERIALS SHALL BE REPLACED

AT THE REQUEST OF THE ENGINEER AT THE CONTRACTOR'S

EXPENSE.

7. ALL ELECTRICAL PERMITS AND INSPECTION FEES SHALL BE SECURED

AND PAID BY THE ELECTRICAL CONTRACTOR.

8. THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL PLANS FOR

ALL FLOOR PLAN DIMENSIONS.

9. ALL TELEPHONE AND DATA WIRING WILL BE BY

TELECOMMUNICATIONS CONTRACTOR. ELECTRICAL CONTRACTOR

SHALL PROVIDE ALL CONDUIT, JUNCTION BOXES WITH PULL STRINGS

TO AN ACCESSIBLE LOCATION ABOVE CEILING FOR INSTALLATION OF

TELECOMMUNICATION WIRING. CONDUITS SHALL BE 1" DEDICATED

CONDUIT FROM EACH OUTLET INDICATED ON FLOOR PLANS UNLESS

SPECIFICALLY NOTED OTHERWISE. PROVIDE DEDICATED 1-1/2"

CONDUIT TO EACH SURFACE RACEWAY LOW VOLTAGE CABLING

JUNCTION BOX. DO NOT DAISY CHAIN LOW VOLTAGE CONDUITS

INSTALLED IN WALLS AND CEILINGS.

10. ALL CONDUIT, HANGERS, AND SUPPORTS SHALL BE INSTALLED SUCH

THAT THEY DO NOT INTERFERE WITH EQUIPMENT ACCESS OR

EQUIPMENT REMOVAL SPACE.

11. CONTRACTOR SHALL PROVIDE OVERCURRENT PROTECTION DEVICES

THAT ARE SELECTIVELY COORDINATED FOR ALL EMERGENCY AND

LEGALLY REQUIRED STANDBY DISTRIBUTION SYSTEMS IN

ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC) ARTICLES

700.32 AND 701.32.

SINGLE LINE TYPES

NEW WORK

EXISTING WORK TO REMAIN

DEMOLITION WORK

FUTURE WORK (NOT IN SCOPE)

EQUIPMENT BOUNDARY

EQUIPMENT COMMUNICATIONS

NEW EQUIPMENT BUS

EXISTING EQUIPMENT BUS

DEMOLISH EQUIPMENT BUS

FUTURE EQUIPMENT BUS (NOT IN SCOPE)

SCOPE BOX

LINE BREAK OR CONTINUATION

END OF DEMOLITION POINT

POINT OF CONNECTION TO

EXISTING ELECTRICAL SYSTEM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

85% CONSTRUCTION DOCUMENTS 11/13/2023

A u to d e s k D o c s /2

.8

.0

V A

C in c in n a ti E le c tr ic D e fi c ie n c ie s /2

.8

.0

E v

.r v t

/2

/2

:3

:3

P

M

E-000

ELECTRICAL SYMBOLS LEGEND

AND GENERAL NOTESGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

VA Cincinnati Electrical Deficiencies

3200 Vine Street, Cincinnati, OH

539-22-203

1, 14

01/27/2025 ARH MCP

BID DOCUMENTS

FULLY SPRINKLERED

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGEND AND ABBREVIATIONS.

B. EXISTING ELECTRICAL ITEMS TO REMAIN ARE INDICATED WITH A LIGHT SOLID

LINEWEIGHT AND/OR ARE NOTED AS “EXISTING TO REMAIN”.

C. ELECTRICAL ITEMS TO BE REMOVED ARE INDICATED WITH A BOLD DASHED

LINEWEIGHT AND/OR ARE NOTED TO BE REMOVE.

D. INFORMATION SHOWN ON THE LIGHTING, POWER, TECHNOLOGY, AND SYSTEMS

PLANS IS BASED ON GENERAL FIELD OBSERVATION AND EXISTING RECORD

DRAWINGS WHERE AVAILABLE. THE DEMOLITION DRAWINGS DO NOT PURPORT

TO SHOW ALL EXISTING EQUIPMENT, WIRING, CONDUITS OR FIELD CONDITIONS.

FIELD VERIFY EXISTING BUILDING AND SITE CONDITIONS TO DETERMINE THE

ACTUAL EXTENT OF DEMOLITION WORK REQUIRED. THE CONTRACTOR IS

RESPONSIBLE FOR ANY ADDITIONAL TRACING, REMOVING, RELOCATION AND

EXTENDING CIRCUITS AND DEVICES NECESSARY TO MAINTAIN CONTINUITY OF

EXISTING EQUIPMENT NOT IN THE AREA OF WORK.

E. SEQUENCE, COORDINATE, AND INTEGRATE DEMOLITION OF ELECTRICAL

MATERIALS AND EQUIPMENT FOR EFFICIENT FLOW OF THE WORK. COORDINATE

ELECTRICAL DISCONNECTION OF EQUIPMENT TO BE REMOVED BY THE OTHER

TRADES.

F. COORDINATE DEMOLITION OF ALL AFFECTED ELECTRICAL SYSTEMS AS

REQUIRED TO PREVENT OR MINIMIZE DISRUPTION TO THE OWNER AND

DOWNTIME.

G. CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE EXISTING

CONDITIONS. IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO REVIEW

THE EXISTING CONDITIONS AS THEY RELATE TO THE SCOPE OF WORK AS

DEFINED ON THE CONSTRUCTION DOCUMENTS. CONTRACTOR SHALL REVIEW

LOCATIONS AND QUANTITIES OF ALL EXISTING EQUIPMENT INCLUDING

SWITCHBOARDS, TRANSFORMERS, PANELBOARDS, LIGHTING FIXTURES,

OUTLETS, FIRE ALARM DEVICES, TELECOMMUNICATIONS OUTLETS, SECURITY

DEVICES AND ALL OTHER ELECTRICAL DEVICES, COMPONENTS, ETC. IN THE

EXISTING FACILITY. AT THE BEGINNING OF DEMOLITION, THE CONTRACTOR

ACCEPTS THE EXISTING CONDITIONS, AND HAS INCLUDED ALL NECESSARY

MODIFICATIONS, REMOVAL, DEMOLITION, AND RELOCATION OF THE EXISTING

COMPONENTS FOR THE EXECUTION OF THE SCOPE OF WORK.

H. FIELD VERIFY ALL EXISTING CIRCUITS TO BE REMOVED AND TO REMAIN PRIOR

TO COMMENCEMENT OF ANY DEMOLITION ACTIVITIES.

I. WHERE EXISTING EQUIPMENT (SUCH AS LIGHT FIXTURES, WIRING DEVICES,

CONDUITS, ETC.) IS SHOWN ON PLANS TO BE REMOVED, DISCONNECT AND

COMPLETELY REMOVE ALL ASSOCIATED WIRING AND CONDUIT BACK TO PANEL

SOURCE OR BACK TO EXISTING JUNCTION BOX SERVING OTHER DEVICES TO

REMAIN.

J. WHERE EXISTING CIRCUITS ARE TO BE REMOVED, DISCONNECT WIRING AT THE

OVERCURRENT PROTECTIVE DEVICE AND MARK DEVICE AS SPARE.

K. DISCONNECT ALL WIRING SERVING EQUIPMENT TO BE REMOVED AT THE

OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED

WIRING AND ASSOCIATED CONDUITS WHERE NOT INDICATED OR REQUIRED TO

BE REUSED.

L. PROVIDE TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING

SYSTEMS TO REMAIN IN SERVICE DURING CONSTRUCTION. WHERE EXISTING

CIRCUITS ARE INTERRUPTED BY ELECTRICAL DEMOLITION: MAINTAIN, RESTORE,

AND REFEED EXISTING CIRCUITS TO REMAIN INCLUDING ASSOCIATED WIRING

AND CONDUITS THAT PASSES THROUGH AREAS TO BE RENOVATED THAT SERVE

AREAS OUTSIDE OF PROJECT SCOPE.

M. PROTECT EXISTING ELECTRICAL EQUIPMENT AND INSTALLATIONS INDICATED

TO REMAIN. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK,

REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL

CAPACITY, QUALITY, AND FUNCTIONALITY.

N. FIELD VERIFY EXACT DEMOLITION REQUIREMENTS AND INCLUDE ASSOCIATED

COSTS. ASSOCIATED WIRING, CONDUITS, FITTING, BOXES, SUPPORTS, SHALL BE

REMOVED FROM THE DEVICES BACK TO THE RESPECTIVE SOURCE PANEL.

O. UPDATE EXISTING PANEL DIRECTORIES AS REQUIRED. ALL OVERCURRENT

PROTECTIVE DEVICES FOR REMOVED CIRCUITS THAT ARE NOT RE-USED SHALL

REMAIN AND BE MARKED AS “SPARE” ON THE UPDATED PANEL DIRECTORY.

P. REFER TO THE SPECIFICATIONS FOR ADDITIONAL ELECTRICAL DEMOLITION

REQUIREMENTS.

Q. DASHED WALLS INDICATE EXISTING WALLS BEING REMOVED. REFER TO

ARCHITECTURAL DEMOLITION AND PHASING PLANS FOR THE EXACT EXTENT OF

GENERAL CONSTRUCTION DEMOLITION REQUIRED.

R. CONTRACTOR SHALL SUPPORT AND PROTECT ELECTRICAL INFRASTRUCTURE

EXISTING TO REMAIN, INCLUDING BUT NOT LIMITED TO CONDUITS, WIRING,

DEVICES, AND LIGHTING FIXTURES AS REQUIRED.

S. COORDINATE REMOVAL AND REPLACEMENT OF ANY EXISTING ELECTRICAL

CEILING MOUNTED DEVICES (I.E. LIGHT FIXTURES, FIRE ALARM) OUTSIDE THE

MAIN PROJECT AREA OF WORK TO ACCOMMODATE THE NEW CONSTRUCTION.

ELECTRICAL DEMOLITION GENERAL NOTES GENERAL ELECTRICAL NOTES GENERAL ELECTRICAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOLS LEGEND AND

ABBREVIATIONS.

B. EXISTING ELECTRICAL ITEMS TO REMAIN ARE INDICATED WITH A LIGHT SOLID

LINEWEIGHT AND/OR ARE NOTED AS “EXISTING TO REMAIN”.

C. NEW ELECTRICAL ITEMS ARE INDICATED WITH A BOLD SOLID LINEWEIGHT.

D. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE INTENDED TO

CONVEY THE SCOPE OF WORK AND INDICATE GENERAL ARRANGEMENT OF

EQUIPMENT, CONDUITS, DEVICES, FIXTURES, ETC. THE ELECTRICAL DRAWINGS

SHALL NOT BE SCALED FOR PURPOSES OF EQUIPMENT INSTALLATION. ALL

MEASUREMENTS SHALL BE VERIFIED AS REQUIRED TO INSTALL ALL EQUIPMENT

IN A NEAT AND WORKMANLIKE MANNER. REFER TO THE ENTIRE CONSTRUCTION

DRAWING SET AND SPECIFICATIONS FOR GUIDANCE ON DIMENSIONS, CEILING

HEIGHTS, DOOR SWINGS, ROOM FINISHES, STRUCTURAL DETAILS, LOCATIONS

OF PIPING, DUCTWORK, STRUCTURAL MEMBERS, AND OTHER OBSTRUCTIONS.

E. THE ENGINEER RESERVES THE RIGHT TO MAKE CHANGES IN THE LOCATIONS

OF RECEPTACLES, APPARATUS AND EQUIPMENT UP TO THE TIME OF ROUGH-IN

OR SETTING WITHOUT ADDITIONAL COST TO THE PROJECT. THE CONTRACTOR

SHALL, WITHOUT EXTRA CHARGE, MAKE REASONABLE MODIFICATIONS TO THE

ELECTRICAL LAYOUT FOR THE FOLLOWING:

1. AS NEEDED TO PREVENT CONFLICT WITH THE WORK OF OTHER

TRADES OR FOR PROPER EXECUTION OF THE WORK.

2. AS DIRECTED BY THE ENGINEER AND/OR OWNER IN WRITING, PRIOR

TO COMPONENT INSTALLATION, FOR MINOR REVISIONS TO

ELECTRICAL INSTALLATION.

F. COOPERATE AND COORDINATE WORK WITH OTHER TRADES SO AS TO NOT

DELAY THE COMPLETION DATE OF THE PROJECT. STUDY AND BE FAMILIAR WITH

THE WORK OF OTHER TRADES AS REQUIRED FOR PROPER COORDINATION.

G. CERTAIN ELECTRICAL WORK IS INDICATED ON THE DRAWINGS AND

SPECIFICATIONS OF OTHER TRADES AND MAY NOT BE REPEATED ON THE

ELECTRICAL DRAWINGS AND SPECIFICATIONS. EXAMINE THE DOCUMENTS OF

OTHER TRADES AND INCLUDE ALL ELECTRICAL WORK IN THE BID AS REQUIRED

FOR A COMPLETE ELECTRICAL SYSTEM(S), UNLESS SPECIFICALLY NOTED AS

FURNISHED AND INSTALLED BY OTHERS.

H. COMPLETE ROUGH-IN REQUIREMENTS OF ALL EQUIPMENT TO BE WIRED OR

CONNECTED UNDER THIS PROJECT ARE NOT SHOWN ON THE DRAWINGS.

VERIFY ALL REQUIREMENTS WITH THE CONTRACTOR FURNISHING THE

EQUIPMENT OR WITH THE OWNER WHERE THE EQUIPMENT IS OWNER

FURNISHED, FOR THE EXACT INSTALLATION REQUIREMENTS.

I. EXAMINE THE ARCHITECTURAL DRAWINGS AND VERIFY SUFFICIENT WALL

THICKNESS FOR PROPER RECESSING DEPTH FOR ALL FLUSH-MOUNTED

EQUIPMENT. ALL INSTANCES OF INADEQUATE DEPTH SHALL BE BROUGHT TO

THE ATTENTION OF THE ENGINEER BEFORE THE BID DATE OR PROVIDED FOR

BY THE BID.

J. WORK SHOWN ON THE DRAWINGS AS “EXISTING” IS ASSUMED TO BE IN PLACE

AND SUITABLE FOR MODIFICATIONS AND ADDITIONS AS INDICATED ON THE

DRAWINGS. VERIFY THESE ITEMS AND MAKE NECESSARY FIELD

MEASUREMENTS PRIOR TO BID AND SHALL MAKE ALL NECESSARY PROVISIONS

REQUIRED FOR PROPER INSTALLATION AS REQUIRED BY THE DRAWINGS AND

SPECIFICATIONS. SUBMIT ANY QUESTIONS REQUIRING CLARIFICATION IN

WRITING TO THE ENGINEER NOT LESS THAN TEN DAYS PRIOR TO THE BID DATE.

K. SCHEDULE TIMES FOR ALL NECESSARY POWER OUTAGES FOR INSTALLATION

OF NEW ELECTRICAL DISTRIBUTION EQUIPMENT, MODIFICATIONS TO EXISTING

ELECTRICAL DISTRIBUTION EQUIPMENT, INSTALLATION OR MODIFICATION OF

FEEDER OR BRANCH CIRCUITS, TERMINATION OF CIRCUITS, AND CUTOVERS

SHALL WITH THE OWNER. ALL POWER OUTAGES SHALL BE AT TIMES APPROVED

BY THE OWNER AND SHALL BE OF THE SHORTEST POSSIBLE DURATION.

L. VERIFY AVAILABLE RECESSING DEPTHS FOR LUMINARIES (LIGHT FIXTURES)

AGAINST LUMINAIRE CATALOG REFERENCE MATERIAL PRIOR TO FURNISHING

SUBMITTALS FOR REVIEW TO THE ENGINEER.

M. REVIEW THE ARCHITECTURAL PLANS AND SHALL PROVIDE ALL NECESSARY

HARDWARE, PLASTER RINGS, DRYWALL FRAMING KITS, AND SURFACE

MOUNTING KITS AS REQUIRED BY CEILING CONSTRUCTION.

N. VERIFY ALL NECESSARY VERTICAL AND HORIZONTAL CLEARANCES FOR THE

INSTALLATION OF ELECTRICAL EQUIPMENT AND SHALL SHARE THIS

INFORMATION WITH ALL ASSOCIATED PARTIES AS NECESSARY FOR PROPER

COORDINATION.

O. PROVIDE A SUITABLE BRANCH CIRCUIT FOR EACH AND EVERY LIGHT FIXTURE,

RECEPTACLE, UTILIZATION EQUIPMENT, ETC. INSIDE OR OUTSIDE OF THE

BUILDING WHETHER OR NOT SPECIFICALLY NOTED ON THE ELECTRICAL

DRAWINGS AND SPECIFICATIONS, INCLUDING THE DRAWINGS AND

SPECIFICATIONS OF OTHER TRADES.

P. ALL SERVICE ENTRANCE, FEEDER, AND BRANCH CIRCUIT CONDUCTORS SHALL

BE COPPER, THE USE OF ALUMINUM IS NOT ACCEPTABLE.

Q. PROVIDE MINIMUM OF #12 AWG CONDUCTOR SIZE FOR ALL LIGHTING AND

POWER BRANCH CIRCUITS WHERE A WIRE SIZE IS NOT SPECIFICALLY

INDICATED ON THE DRAWINGS OR REQUIRED BY CODE. INCREASE CONDUCTOR

SIZE AS SHOWN ON THE DRAWINGS, REQUIRED BY LOAD, OR AS REQUIRED TO

LIMIT BRANCH CIRCUIT VOLTAGE DROP TO A MAXIMUM OF 3 PERCENT.

R. CONDUITS SHALL BE LIMITED TO A MAXIMUM OF NINE BRANCH CIRCUIT

CONDUCTORS OF WHICH A MAXIMUM OF FOUR PHASE CONDUCTORS SHALL BE

PERMITTED. GROUNDING CONDUCTORS SHALL NOT BE INCLUDED IN THE

COUNT.

S. PROVIDE A FULL SIZE NEUTRAL FOR EACH 120-VOLT AND 277-VOLT BRANCH

CIRCUIT.

T. PERMANENTLY AND EFFECTIVELY IDENTIFY AND TAPE TOGETHER EACH

NEUTRAL CONDUCTOR WITH ITS RESPECTIVE PHASE CONDUCTOR IN EACH

JUNCTION BOX, OUTLET BOX AND PANELBOARD WHERE TWO OR MORE

NEUTRALS ARE INSTALLED WITHIN THE SAME CONDUIT. PROVIDE MARKERS ON

THE NEUTRAL WIRE NUMBERED THE SAME AS THE RESPECTIVE BRANCH

CIRCUIT CONDUCTOR.

U. PROVIDE AN INSULATED GROUNDING CONDUCTOR IN EACH BRANCH CIRCUIT

CONDUIT AND EACH FEEDER CONDUIT.

V. WIRING FOR ALL SERVICE ENTRANCE, FEEDER CIRCUITS AND BRANCH CIRCUITS

SHALL BE INSTALLED IN CONDUITS IN ACCORDANCE WITH THE SPECIFICATIONS.

W. WIRING FOR ALL LOW-VOLTAGE COMMUNICATIONS AND SIGNALING SYSTEMS

SHALL BE INSTALLED IN CONDUITS IN ACCORDANCE WITH THE SPECIFICATIONS.

THIS REQUIREMENT SHALL APPLY, BUT NOT BE LIMITED TO THE FOLLOWING

SYSTEMS: FIRE ALARM SYSTEM, SOUND SYSTEMS, ACCESS CONTROL SYSTEMS,

INTRUSIONS DETECTION SYSTEM, NURSE CALL SYSTEM, AND OTHER SPECIAL

SYSTEMS.

X. WIRING FOR ALL TELECOMMUNICATIONS SYSTEMS SHALL BE INSTALLED IN

PATHWAYS IN ACCORDANCE WITH DIVISION 27 SPECIFICATION REQUIREMENTS.

Y. GENERAL CONDUIT INSTALLATION.

1. AREAS WITHOUT SUSPENDED CEILINGS: SUPPORT CONDUITS FROM

THE STRUCTURE AND INSTALL EXPOSED AS HIGH AS POSSIBLE TO

AVOID FUTURE CONFLICTS WHEN NEW CEILINGS ARE INSTALLED OR

WHEN ADDITIONAL WORK IN INSTALLED. ROUTE ALL CONDUITS

PARALLEL AND PERPENDICULAR WITH THE STRUCTURE.

2. AREAS WITH SUSPENDED CEILINGS: INSTALL CONDUITS CONCEALED

ABOVE SUSPENDED CEILINGS.

3. NEW WALLS: INSTALL CONDUITS CONCEALED IN NEW WALLS EXCEPT

WHERE SPECIFICALLY SHOWN AND NOTED AS EXPOSED ON THE

DRAWINGS.

4. EXISTING WALLS: INSTALL CONDUITS CONCEALED IN EXISTING WALLS

EXCEPT WHERE SPECIFICALLY SHOWN AND NOTED AS EXPOSED ON

THE DRAWINGS. PROVIDE ALL CUTTING, PATCHING, REPAIR AND

FINISHING OF EXISTING WALLS AS REQUIRED.

Z. COORDINATE, CHECK, AND VERIFY ROUGH-IN HEIGHTS AND LOCATIONS OF ALL

EQUIPMENT, DEVICES, RECEPTACLES, ETC. WITH THE DRAWINGS, EXISTING

CONDITIONS, AND THE WORK OF OTHER TRADES.

AA. PROVIDE ALL CUTTING AND PATCHING OF EXISTING CONSTRUCTION EXCEPT

WHERE SPECIFIED TO BE PROVIDED BY OTHERS ELSEWHERE IN THESE

SPECIFICATIONS. VERIFY EXACT LOCATIONS AND MATERIALS BEFORE

PERFORMING WORK. THE CUTTING OF STRUCTURAL MEMBERS AND BEARING

WALLS IS PROHIBITED EXCEPT WHERE SPECIFICALLY SHOWN AND NOTED ON

THE DRAWINGS AND/OR WHERE SPECIFICALLY PERMITTED BY THE ARCHITECT

AND STRUCTURAL ENGINEER.

BB. PATCH ALL HOLES IN EXISTING WALLS OR FLOORS WHERE EQUIPMENT OR

CONDUITS HAVE BEEN REMOVED WITH THE PROPER MATERIAL TO MATCH

EXISTING CONSTRUCTION. PATCH ALL HOLES IN FIRE RATED CONSTRUCTION

WITH APPROVED FIRE RESISTANT MATERIALS TO MATCH EXISTING RATINGS OF

CONSTRUCTION.

CC. COLOR FOR ALL WIRING DEVICES AND WALL MOUNTED LIGHTING CONTROLS TO

BE SELECTED BY THE ARCHITECT.

DD. DEVICE PLATE TYPE (NYLON OR STAINLESS STEEL) TO BE SELECTED BY THE

ARCHITECT. COLOR FOR NYLON DEVICE PLATES TO BE SELECTED BY THE

ARCHITECT.

EE. PROVIDE TAMPER-RESISTANT RECEPTACLES FOR ALL RECEPTACLES TO BE

PROVIDED IN WAITING ROOMS, LOUNGES, AND LOBBY AREAS.

FF. UPON COMPLETION OF WORK, DISCONNECT AND RECONNECT BRANCH

LIGHTING CIRCUITS AT PANELBOARDS TO OBTAIN AS NEAR LOAD BALANCE ON

CIRCUITS AS POSSIBLE. DEMONSTRATE ALL RESULTS TO THE OWNER’S

REPRESENTATIVE WITH DIGITAL AMMETER.

GG. PROVIDE A COMPLETED, PROTECTED, AND TYPEWRITTEN DIRECTORY CARD IN

EACH NEW AND EXISTING DISTRIBUTION BOARD WITHIN THE SCOPE OF THIS

PROJECT. THE DIRECTORY SHALL BE APPROXIMATELY 5” X 8” AND SHALL

INDICATE LOAD DESIGNATIONS WITH THE OWNER’S ASSOCIATED ROOM

NUMBERS FOR EACH CIRCUIT. UPDATE THE PANEL DIRECTORY CARD FOR

EACH EXISTING DISTRIBUTION PANEL IN WHICH CIRCUITS ARE MODIFIED,

ADDED, OR SUBTRACTED. VERIFY ALL EXISTING CIRCUITS TO REMAIN AND LIST

ON THE UPDATED DIRECTORY. DO NOT LIST EXISTING CIRCUITS AS "EXISTING

CIRCUIT" BUT RATHER THE ACTUAL LOAD DESIGNATION.

HH. UPDATE ALL ENGRAVED LABELS AS NEEDED WITH A SIMILAR ENGRAVED LABEL

SHOWING THE UPDATED EQUIPMENT NAME AND THE PREVIOUS EQUIPMENT

NAME. EXAMPLE: AT DISTRIBUTION PANEL DS-1A, THE BREAKER FEEDING MCC-

NORTH SHALL BE PROVIDED WITH A (2) SEPARATE NEW ENGRAVED LABELS:

ONE WITH THE WORDING DP-B-C-A AND ONE WITH THE WORDING PREVIOUSLY

MCC-NORTH. EXISTING DISTRIBUTION BOARD SHALL ALSO BE PROVIDED WITH

AN UPDATED TYPEWRITTEN DIRECTORY CARD (UPDATES WITH SIMILAR ORDING

AS LABEL).

II. ALL NEW DISTRIBUTION BOARDS SHALL BE PROVIDED WITH (2) SEPARATE

ENGRAVED LABELS: ONE WITH THE NAME OF THE PANEL AND ONE WITH THE

NAME OF THE MCC IT REPLACES. EXAMPLE,: AT DISTRIBUTION BOARD DP-B-C-A,

PROVIDE (2) SEAPARTE ENGRAVED LABELS: ONE WITH THE WORDING DP-B-C-A

AND ONE WITH THE WORDING PREVIOUSLY MCC-NORTH.

JJ. CONTRACTOR SHALL PROVIDE A SHORT CIRCUIT AND COORDINATION STUDY

BASED ON THE 2024 STUDY PERFORMED BY THE VA. PROVIDE ARC FLASH

WARNING LABELS ON ALL NEW EQUIPMENT INCLUDING VFD'S.

KK. THE CONTRACTOR SHALL INCLUDE ALL WORK AND COSTS RELATED TO

CONNECTIONS AND UPDATES OF THE EXISTING BAS. THE EXISTING BAS IS BY

TIRIDIUM FX EXPLORER; ALL WORK SHALL BE COORDINATE AND/OR COMPLETED

BY JCI. NEW VFD'S AND ELECTRICAL METERS AT DISTRIBUTION BOARDS SHALL

BE CONNECTED TO THE EXISTING BAS; PROVIDE ALL REQUIRED CABLING AND

CONDUITS AND MAKE FINAL CONNECTIONS. ALL ASSOCIATED PROGRAMMING

FOR ADDITIONAL REQUIREED POINTS IN THE BAS SHALL BE INCLUDED.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

85% CONSTRUCTION DOCUMENTS 11/13/2023

A u to d e s k D o c s /2

.8

.0

V A

C in c in n a ti E le c tr ic D e fi c ie n c ie s /2

.8

.0

E v

.r v t

/2

/2

:3

:3

P

M

E-001

ELECTRICAL NOTES

GUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

VA Cincinnati Electrical Deficiencies

3200 Vine Street, Cincinnati, OH

539-22-203

1, 14

01/27/2025 ARH MCP

BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

ADDENDUM #1 02/24/2025

DN

DN

Elec. Rm.

C008

Transformer Room

A023

EP401

EP403

EP401

EP403

GENERAL NOTES

1. REFER TO SHEET E000 FOR ABBREVIATIONS AND SYMBOLS.

2. REFER TO SHEET E001 FOR NOTES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

85% CONSTRUCTION DOCUMENTS 11/13/2023

A u to d e s k D o c s /2

.8

.0

V A

C in c in n a ti E le c tr ic D e fi c ie n c ie s /2

.8

.0

E v

.r v t

/2

/2

:3

:4

P

M

EP101

BUILDING 01 ELECTRICAL

BASEMENT PLANGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

VA Cincinnati Electrical Deficiencies

3200 Vine Street, Cincinnati, OH

539-22-203

1, 14

01/27/2025 ARH MCP

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 3/64" = 1'-0"EP101

1 BASEMENT OVERALL PLAN

N

MACHINE ROOM

2121M

MACHINE ROOM

2121L

STAIRS #6

EP404

EP402

BLDG 1 KEYPLAN N

SHADE INDICATES

AREA OUT OF

PROJECT SCOPE

PROJECT

LOCATION

GENERAL NOTES

1. REFER TO SHEET E000 FOR ABBREVIATIONS AND SYMBOLS.

2. REFER TO SHEET E001 FOR NOTES.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

85% CONSTRUCTION DOCUMENTS 11/13/2023

A u to d e s k D o c s /2

.8

.0

V A

C in c in n a ti E le c tr ic D e fi c ie n c ie s /2

.8

.0

E v

.r v t

/2

/2

:3

:4

P

M

EP102

BUILDING 01 ELECTRICAL TENTH

FLOOR PLANGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

VA Cincinnati Electrical Deficiencies

3200 Vine Street, Cincinnati, OH

539-22-203

1, 14

01/27/2025

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"EP102

1 BUILDING 1 - TENTH FLOOR - ELECTRICAL ROOM - NEW WORK PLAN

EP114

Main Electric

Main Electric

MVS UNIT SUB US1A 14MDP

14TDP1

14DP1

P2A 2B 2A 1B 1A

BDA FAAR

POWER PLAN NOTES

1. DISCONNECT AND REMOVE 400A/3P BREAKER FEEDING 14TDP1. BREAKER IS

INSTALLED WITHIN A GE SPECTRA SERIES SWITCHBOARD SECTION. PROVIDE

NEW BREAKER AT SAME LOCATION, BREAKER TYPE AND AIC RATING SHALL

MATCH EXISTING. PROVIDE ALL REQUIRED HARDWARE AND MAKE ALL FINAL

CONNECTIONS. INCLUDE IN BID THE COST TO ADJUST BREAKER TRIP

SETTINGS IN ACCORDANCE WITH LATEST ARC FLASH AND COORDINATION

STUDY.

POWER GENERAL NOTES

A. REFER TO SHEET E-000 FOR ABBREVIATIONS AND SYMBOLS.

B. REFER TO SHEET E-001 FOR NOTES.

C. ALL EQUIPMENT AND DEVICES SHOWN IN THIN/LIGHT LINEWEIGHT ARE

EXISTING TO REMAIN OR WORK BY OTHERS. ALL ITEMS SHOWN IN BOLD/DARK

LINEWEIGHT ARE NEW WORK.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

85% CONSTRUCTION DOCUMENTS 11/13/2023

A u to d e s k D o c s /2

.8

.0

V A

C in c in n a ti E le c tr ic D e fi c ie n c ie s /2

.8

.0

E v

.r v t

/2

/2

:3

:4

P

M

EP114

BUILDING 14 ELECTRICAL

SECOND FLOOR PLANGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

VA Cincinnati Electrical Deficiencies

3200 Vine Street, Cincinnati, OH

539-22-203

1, 14

01/27/2025 ARH MCP

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/8" = 1'-0"EP114

1 SECOND FLOOR POWER PLAN

SCALE: 1/4" = 1'-0"EP114

2 BUILDING 14 - SECOND FLOOR - ENLARGED 211 MAIN ELECTRICAL ROOM - NEW WORK PLAN

N

DEMOLITION NOTES

1. DEMOLISH EXISTING MCC-NORTH. INTERCEPT ALL EXISTING TO REMAIN

LOADS AND EXTEND FEEDERS TO NEW DP-B-C-A. EXISTING TO REMAIN

BOTTOM-FED CONDUITS SHALL BE INTERCEPTED IN JUNCTION BOXES AND

EXTENDED TO NEW DP-B-C-A. THE FOLLOWING CONDUITS AND WIRES ARE

APPROXIMATIONS AND SHALL BE FIELD-VERIFIED BY THE CONTRACTOR:

SECTION 1:

(10) #14 IN 1-1/2"C STUB-UP

(4)#10, (1)#10G AND (4)#14 IN 1-1/2"C STUB-UP

(4)#10, (1)#10G IN 1-1/2"C STUB-UP

(4)#8, (1)#10G IN 1-1/2"C STUB-UP

(4) 3/4"C AND WIRING TOP-FED

(1) MAIN FEEDERS AND CONDUIT (DEMOLISH)

SECTION 2:

(3)#10, (1)#10G IN 1"C STUB-UP

(3)#8, (1)#10G IN 1"C STUB-UP

(2) 3/4"C AND WIRING TOP-FED

SECTION 3:

(3)#6, (1)#8G IN 1-1/2"C STUBBED UP INTO SECTION 3

SECTION 4:

(1) 3/4"C AND WIRING TOP-FED (FIRE ALARM)

(4) 2"C AND WIRING SIDE-FED

(6) 3/4"C AND WIRING SIDE-FED (TO VFD'S ALONG SAME WALL AS MCC)

2. DEMOLISH EXISTING MCC-EAST. INTERCEPT ALL EXISTING TO REMAIN LOADS

AND EXTEND FEEDERS TO NEW DP-B-C-B. THE FOLLOWING CONDUITS AND

WIRES ARE APPROXIMATIONS AND SHALL BE VERIFIED BY THE CONTRACTOR:

SECTION 1:

(2) MAIN FEEDERS AND CONDUITS (DEMOLISH)

SECTION 4:

(7) 1"C AND WIRING TOP-FED

(4) 3/4"C AND WIRING TOP-FED

3. DISCONNECT AND RETAIN FIRE ALARM CONTROL MODULES. VERIFY

EQUIPMENT BEING SERVED/MONITORED BY MODULES. NUMERAL INDICATES

QUANTITY OF MODULES.

4. DISCONNECT AND REMOVE WALL-MOUNTED CAPACITOR/FILTER AND

ASSOCIATED CONDUIT AND WIRING BACK TO MCC-D.

5. DEMOLISH EXISTING MCC-D. INTERCEPT ALL EXISTING TO REMAIN LOADS AND

EXTEND FEEDERS TO NEW DP-B-A-A. THE FOLLOWING CONDUITS AND WIRES

ARE APPROXIMATIONS AND SHALL BE VERIFIED BY THE CONTRACTOR:

SECTION 1:

(1) MAIN FEEDERS AND CONDUIT (DEMOLISH)

(1) 3/4" AND WIRING TOP-FED (TO AHU-14)

(1) 3/4" AND WIRING SIDE-FED (TO VFD-CWP4)

(1) 3/4" AND WIRING SIDE-FED (TO FILTER/CAPACITOR) (DEMOLISH)

(1) 3/4" AND WIRING SIDE-FED (TO FIRE ALARM MODULES)

(2) 3/4" AND WIRING STUB-UP

SECTION 2:

(1) 1-1/2"C AND WIRING STUB-UP (DEMOLISH)

SECTION 4:

(7) 1"C AND WIRING TOP-FED

(4) 3/4"C AND WIRING TOP-FED

# POWER GENERAL NOTES

A. REFER TO SHEET E-000 FOR ABBREVIATIONS AND SYMBOLS.

B. REFER TO SHEET E-001 FOR NOTES.

C. REFER TO E-700 SERIES SHEETS FOR SINGLE LINE DIAGRAMS.

D. ALL EQUIPMENT AND DEVICES SHOWN IN THIN/LIGHT LINEWEIGHT ARE

EXISTING TO REMAIN OR WORK BY OTHERS. ALL ITEMS SHOWN IN BOLD/DARK

LINEWEIGHT WITH A DASHED LINE TYPE ARE TO BE DEMOLISHED. ALL ITEMS

SHOWN IN BOLD/DARK LINEWEIGHT WITH A SOLID LINE TYPE ARE NEW WORK.

E. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL EQUIPMENT AND

DEVICES WITH OTHER EQUIPMENT AND DEVICES PRIOR TO ROUGH-IN AND

INSTALLATION.

F. PRIOR TO DEMOLISHING MOTOR CONTROL CENTER(S), THE CONTRACTOR

SHALL FIELD VERIFY ALL LOADS INCLUDING SIZE OF WIRES, BREAKERS,

SWITCHES, FUSES AND MOTOR STARTERS.

G. MAINTAIN CIRCUITRY OF ALL EXISTING TO REMAIN DEVICES. WHERE A

DEMOLISHED OR RELOCATED ELECTRICAL DEVICE SERVES DOWNSTREAM

DEVICES, RECONNECT ALL CIRCUITRY TO MAINTAIN OPERATION. WHERE

REQUIRED CIRCUITRY TO BE MAINTAINED CONFLICTS WITH NEW

CONSTRUCTION WORK, RELOCATE AS NEEDED.

H. FOR ELECTRICAL DEVICES AND EQUIPMENT NOTED TO BE REMOVED OR

RELOCATED, REMOVE DEVICE AS DIRECTED AND ALL ACCESSORY

COMPONENTS. REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO

SOURCE OR NEAREST DEVICE TO REMAIN, UNO.

I. ALL UNUSED CONDUIT AND/OR WIRING SHALL BE REMOVED BACK TO SOURCE.

UPDATE PANEL SCHEDULES WITH NEW TYPE WRITTEN DIRECTORIES TO

REFLECT REMOVED CIRCUITS.

J. PRIOR TO REMOVAL OF A CIRCUIT FROM A PANEL, CONTRACTOR SHALL

VERIFY NO OTHER DEVICES EXIST ON THE CIRCUIT. ONCE A CIRCUIT HAS

BEEN REMOVED, THE REMAINING CIRCUIT BREAKER SHALL BE LABELED

SPARE, READY FOR USE UNDER NEW WORK.

K. NOT ALL ELECTRICAL DEVICES AND EQUIPMENT ARE SHOWN. LOCATIONS OF

EXISTING DEVICES AND EQUIPMENT SHOWN SHALL BE CONSIDERED

APPROXIMATE. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS PRIOR TO

COMMENCING WORK.

L. TO THE BEST OF THEIR ABILITY, THE ENGINEER HAS IDENTIFIED EXISTING

ITEMS OF EQUIPMENT AND CONSTRUCTION THAT ARE REQUIRED TO BE

REMOVED OR OTHERWISE DEMOLISHED SO AS TO ALLOW THE INSTALLATION

OF NEW WORK. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND

ASSESS EACH SPACE AND FULFILL THE INTENT OF THE WORK INDICATED BY

THE CONSTRUCTION DOCUMENTS IN A MANNER SO AS NOT TO INTERFERE

WITH THE NORMAL OPERATION OF THE BUILDING. THE INFORMATION

PROVIDED IN NO WAY INTENDS TO SUGGEST THAT DEMOLITION IS LIMITED

ONLY TO THOSE ITEMS SPECIFICALLY IDENTIFIED. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO EXECUTE THE DEMOLITION PLAN, WHETHER SHOWN OR

NOT, TO ACCOMMODATE NEW CONSTRUCTION. ANY EXISTING WORK TO

REMAIN, IF DAMAGED BY ANY TRADE OR NEW CONSTRUCTION, SHALL BE

PATCHED, REPAIRED, OR REPLACED TO MATCH EXISTING.

M. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL

DEMOLITION WORK WITH ALL OTHER TRADES AND FOR THE MEANS AND

METHODS NECESSARY TO COMPLETE THE WORK.

N. PERFORM CUTTING, PATCHING, AND FILLING HOLES RESULTING FROM

DEMOLITION OR INSTALLATION OF NEW WORK, OR ANY OTHER EXISTING

FLOOR OR WALL PENETRATIONS WITH A UL-APPROVED MATERIAL TO

MAINTAIN THE EXISTING FIRE-RATED ASSEMBLY WHERE INDICATED.

PATCHING AND REPAIRS TO MATCH EXISTING CONDITIONS.

O. CONDUITS LOCATED IN EXISTING WALLS AND/OR FLOORS TO REMAIN AND

SERVING ITEMS BEING REMOVED SHALL HAVE WIRING REMOVED. CONDUIT

SHALL BE CUT OFF FLUSH WITH WALL OR FLOOR. WALL OR FLOOR SHALL BE

PATCHED TO MATCH SURROUNDING CONSTRUCTION.

P. DISRUPTION OF EXISTING SYSTEMS AND OPERATIONS SHALL BE

COORDINATED WITH OWNER FOUR WEEKS PRIOR TO PLANNED OUTAGE.

Q. SUPPORT AND PROTECT EXISTING TO REMAIN ELECTRICAL

INFRASTRUCTURE, INCLUDING BUT NOT LIMITED TO CONDUITS, WIRING,

DEVICES, AND FIXTURES AS REQUIRED.

R. REFER TO SHEET EP403 FOR SEQUENCE OF CONSTRUCTION PRIOR TO START

OF DEMOLITION WORK.

BC1L BEC1 1CEC3

ET1

(D) MCC-NORTH

SF9A SF9B EF30A EF30B

A T

S -P

S W

IT

C

H B

O A

R D

(D) MCC EAST

ESW-B 10

ESWB-20

PULL BOX

CONTROLS

ALTRONIX

CONTROLS

PULL BOXESWB

ESWB

PULL BOX

PULL BOXPULL BOX

PULL BOXPULL BOX

C A

B

IN

E T

B C

P

SWITCHBOARD DS-1X

ATS-SURG

C

C(4)

(6)

SWBD DS-1P

SECTION

SECTION

SECTION

SECTION

SPD

Elec. Rm.

C008

PB

SWITCHBOARD DS-1A

SECTION

SECTION

SECTION

SECTION

BLDG 1 KEYPLAN N

SHADE INDICATES

AREA OUT OF

PROJECT SCOPE

PROJECT

LOCATION

MAIN LUGS SPACE SPACE SPACE

SECTION 1 SECTION 2 SECTION 3 SECTION 4

MCC-EAST ELEVATION

(DEMOLITION)

SPARE

SPARE

RETURN AIR

SPACE SPACE SPACE SPACE

AHU 5

RETURN FAN 1

AH2 RETURN

(AHU 28)

SPACE

AHU 5 SUPPLY 1

A

B

C

D

E

F

G

H

I

J

L

M

K

N

O

SUPPLY AIR

AHU 5

RETURN FAN 2

AH2 SUPPLY

(AHU 28)

AHU 5 SUPPLY 2

MAIN LUGS

SF21B

SUPPLY FAN

SF21A

SUPPLY FAN

AHU 26

RETURN FAN

EF4

EXHAUST FAN

(SPARE)

EF9

EXHAUST FAN

(SPARE)

SPACE

SPACE

RF21

RETURN FAN

SPACE SPACE SPACE SPACE

SPACE SPACE SPACE SPACE

SPACE SPACE DAC-1

AIR COMPRESSOR

DOORS

(SPARE)

SPACE

AC-1

AIR COMPRESSOR

(SPARE)

EF2

TOILET EXHAUST FAN

CP1 & CP2

DUPLEX COND.

PUMPS

P1

PUMP

AHU 4

RETURN FAN #2

AHU 4

RETURN FAN #1

AHU 4

SUPPLY FAN #2

AHU 4

SUPPLY FAN #1

AHU 26

SUPPLY FAN

SECTION 1 SECTION 2 SECTION 3 SECTION 4

MCC-NORTH ELEVATION

(DEMOLITION)

P2

PUMP

A

B

C

D

E

F

G

H

I

J

L

M

K

N

O

US1D

MV SWGR PS1

Transformer

Room

A023

C

(2)

SECTION

(D) MCC-D

SECTION

SECTION

SECTION

SECTION

SECTION

(E) VFD-CWP4

US-P1

MAIN LUGS SPACE SPACE

SECTION 1 SECTION 2 SECTION 3

SPACE SPACE SPACE

P1

EAST CHILLED WATER

SHAFT PUMP

[OFF]

P2

SOUTH CHILLED WATER

SHAFT PUMP

[OFF]

A

B

C

D

E

F

G

H

I

J

L

M

K

N

O

AHU-14A

[SUPPLY FAN]

AHU-14B

[RETURN FAN]

P4

[OFF]

SPACE

SECTION 6

SPACE

SPACE

SPACE

CWP4

SPACE

SECTION 4 SECTION 5

SPARE

SPACESPACE

SPACEHWP3

SPACESPACE

SPACE

P3

NORTH CHILLED WATER

SHAFT PUMP

[OFF]

MCC-D ELEVATION

(DEMOLITION)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

85% CONSTRUCTION DOCUMENTS 11/13/2023

A u to d e s k D o c s /2

.8

.0

V A

C in c in n a ti E le c tr ic D e fi c ie n c ie s /2

.8

.0

E v

.r v t

/2

/2

:3

:5

P

M

EP401

BUILDING 01 ELECTRICAL

ENLARGED PLANS - DEMOLITIONGUIDON DESIGN

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

VA Cincinnati Electrical Deficiencies

3200 Vine Street, Cincinnati, OH

539-22-203

1, 14

01/27/2025 ARH ARH

BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"EP401

1 BUILDING 1 - BASEMENT - ENLARGED C008 ELECTRICAL ROOM - DEMOLITION PLAN

SCALE: 1/4" = 1'-0"EP401

2 BUILDING 1 - BASEMENT - ENLARGED A023 TRANSFORMER ROOM - DEMOLITION PLAN

MACHINE ROOM

2121L

STAIRS #6

(D) MCC-P2

SECTION

SECTION

(E) VFD-RF-AHU-7

(E) VFD-SF-AHU-7

(E) VFD-RF-AHU-8

(E) VFD-SF-AHU-8

BLDG 1 KEYPLAN N

SHADE INDICATES

AREA OUT OF

PROJECT SCOPE

PROJECT

LOCATION

POWER GENERAL NOTES

A. REFER TO SHEET E-000 FOR ABBREVIATIONS AND SYMBOLS.

B. REFER TO SHEET E-001 FOR NOTES.

C. REFER TO E-700 SERIES SHEETS FOR SINGLE LINE DIAGRAMS.

D. ALL EQUIPMENT AND DEVICES SHOWN IN THIN/LIGHT LINEWEIGHT ARE

EXISTING TO REMAIN OR WORK BY OTHERS. ALL ITEMS SHOWN IN BOLD/DARK

LINEWEIGHT WITH A DASHED LINE TYPE ARE TO BE DEMOLISHED. ALL ITEMS

SHOWN IN BOLD/DARK LINEWEIGHT WITH A SOLID LINE TYPE ARE NEW WORK.

E. CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL EQUIPMENT AND

DEVICES WITH OTHER EQUIPMENT AND DEVICES PRIOR TO ROUGH-IN AND

INSTALLATION.

F. PRIOR TO DEMOLISHING MOTOR CONTROL CENTER(S), THE CONTRACTOR

SHALL FIELD VERIFY ALL LOADS INCLUDING SIZE OF WIRES, BREAKERS,

SWITCHES, FUSES AND MOTOR STARTERS.

G. MAINTAIN CIRCUITRY OF ALL EXISTING TO REMAIN DEVICES. WHERE A

DEMOLISHED OR RELOCATED ELECTRICAL DEVICE SERVES DOWNSTREAM

DEVICES, RECONNECT ALL CIRCUITRY TO MAINTAIN OPERATION. WHERE

REQUIRED CIRCUITRY TO BE MAINTAINED CONFLICTS WITH NEW

CONSTRUCTION WORK, RELOCATE AS NEEDED.

H. FOR ELECTRICAL DEVICES AND EQUIPMENT NOTED TO BE REMOVED OR

RELOCATED, REMOVE DEVICE AS DIRECTED AND ALL ACCESSORY

COMPONENTS. REMOVE ASSOCIATED CONDUIT AND WIRING BACK TO

SOURCE OR NEAREST DEVICE TO REMAIN, UNO.

I. ALL UNUSED CONDUIT AND/OR WIRING SHALL BE REMOVED BACK TO SOURCE.

UPDATE PANEL SCHEDULES WITH NEW TYPE WRITTEN DIRECTORIES TO

REFLECT REMOVED CIRCUITS.

J. PRIOR TO REMOVAL OF A CIRCUIT…

This is the start of the file's text. The full file is on GovTribe.