This pre-solicitation announcement seeks bids for construction project number 515-19-101 to upgrade HVAC systems in various buildings at the Battle Creek VA Medical Center in Battle Creek, Michigan. The Department of Veterans Affairs will issue an invitation for bid on August 11, 2020 through the Contract Opportunities website seeking a qualified contractor to furnish all labor, materials, equipment and supervision to upgrade HVAC systems at the medical center over a 545 calendar day performance period. The project value is between $2 million and $5 million and the contract type will be firm fixed price. The solicitation is a 100% set aside for Service-Disabled Veteran Owned Small Businesses. Interested parties should register on Contract Opportunities and monitor the site for solicitation documents and any amendments with bids due as specified. The North American Industry Classification code is 238220 and the size standard is $16.5 million.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Limited Asbestos, Lead-Based Paint, and Lead Dust Sampling
Prepared for:
The Reese Group
April 22, 2019
VA Medical Center – Battle Creek 5500 Armstrong Road Battle Creek, Michigan
188BS19195
VA Medical Center – Battle Creek
April 22, 2019 ATC ii
Document Information
Prepared for The Reese Group
Project Name VA Medical Center – Battle Creek
Job Reference 188BS19195
Date April 22, 2019
Contact Information
ATC Group Services LLC
2650 Horizon Drive SE, Suite 110
Grand Rapids, Michigan 49546
Telephone: 616-698-3131
Facsimile: 616-698-1922 www.atcgs.com
Document Control
Version Date Author Author Initials
Reviewer Reviewer Initials
V1 4/22/2019 Robert N. VanDyke, P.E. RV Robert Smith RS
Robert N. VanDyke, P.E Robert C. Smith Project Manager Building Sciences Department Manager for ATC for ATC Direct Line +1 616-265-3002 Direct Line +1 248-669-5140 Email: robert.vandyke@atcgs.com Email:robert.smith@atcgs.com
April 22, 2019 ATC iii
Executive Summary
ATC has completed the pre-renovation limited asbestos, lead based paint (LBP), and lead dust sampling of various buildings at the VA Medical Center property located at 5500 Armstrong Road, Battle Creek, Michigan. ATC understands these structures will be renovated in connection with a HVAC upgrade.
Asbestos Survey
An ATC licensed asbestos inspector performed an asbestos containing materials (ACM) survey of the subject buildings in accordance with Part 602, the Michigan Occupational Safety and Health Administration (MIOSHA)
Asbestos Standard for Construction, and NESHAP (Title 40, Part 61, Subpart M) requirements. ATC was provided specific rooms and areas of each of the buildings to inspect. The survey identified ACM and presumed asbestos containing materials (PACM).
One hundred twenty (120) samples, taken from forty (40) homogenous areas, were collected and submitted for laboratory analysis by polarized-light microscopy. Based on the laboratory results, two of the materials sampled were found to be ACM.
Section 61.145(c) of the Asbestos NESHAP requires that each owner or operator of a demolition or renovation activity involving regulated asbestos containing materials (RACM), remove all such material from a facility being demolished or renovated before any activity begins that would break up, dislodge, or similarly disturb the material or preclude access to the material for subsequent removal.
Michigan Public Act 135, P.A. 1986, as amended requires a Licensed Asbestos Abatement Contractor to perform abatement of ACM and PACM in accordance with Part 602 (MIOSHA Asbestos Standard for Construction) and
NESHAP (Title 40, Part 61, Subpart M) requirements.
The National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 CFR Part 61, Subpart M requires licensed asbestos abatement contractor to submit notification of abatement ten (10) working days prior to renovation or demolition activity for asbestos materials when quantities of Regulated Asbestos-Containing
Materials (RACM) are greater than two hundred and sixty (260) linear feet or one hundred and sixty (160) square feet.
The Department of Licensing and Regulatory Affairs (Michigan OSHA) through P.A 135 of 1986 requires a licensed asbestos abatement contractor to submit notification for asbestos abatement ten (10) calendar days prior to the start of renovation or demolition activity that will disturb greater than ten (10) linear or fifteen (15) square feet.
Lead Containing Paint
Paint chip samples were collected and analyzed for total lead content. A total of nineteen (19) paint samples were submitted for analysis by USEPA Method SW846-7420 for lead. The results of laboratory testing during the limited lead-based paint sampling conducted at the property indicate that eight (8) of the samples contained levels of lead greater than the method detection limit of 0.01%.
ATC recommends that the project specifications include a section on worker protection according to the OSHA regulations at 29 CFR 1926.62 and that a contractor knowledgeable (does not require licensing) in lead paint removal and worker protection be specified for this portion of the project.
ATC shall not be responsible for identifying all lead-containing materials located behind walls and /or columns, beneath flooring, above solid ceilings, underground or any other inaccessible areas. If material is found during the course of demolition that is not listed in the report the material should be assumed to be lead containing until it can be sampled and analyzed at a laboratory.
Lead Dust Wipes
Dust wipe sampling was conducted using “Lead Wipes” to sample representative surface areas measuring twelve inches by twelve inches within the ductwork in various locations throughout the buildings. A total of seven (7) paint samples were submitted for analysis. The results of laboratory testing during the lead wipe sampling conducted at the property indicate that lead levels in the sampled locations ranged from 80.8 to 253.3 µg/ft2.
April 22, 2019 ATC iv
Table of Contents
Executive Summary iii
1 Introduction 5
1.1 Purpose 5
1.2 Pre-Renovation Asbestos Survey 5
2 General Site Conditions 6
2.1 General Property and Building Information 6
2.2 Exterior Finish Descriptions 6
2.3 Interior Building Descriptions 6
3 Limited Pre-Renovation Asbestos Survey 7
3.1 Homogeneous Areas 7
3.2 Hazard Assessment Factors 7
3.3 Laboratory Analytical Methodology 7
3.4 Sampling Results 8
4 Limited Lead-Based Paint Sampling 10
5 Limited Lead Wipe Sampling 11
6 Conclusions and Recommendations 12
6.1 Asbestos-Containing Materials 12
6.2 Lead-Based Paint 12
7 Assumptions and Limitations 13
Tables
Table 2-1 General Property and Building Information 6
Table 3-1 ACM and PACM Summary Table 8
Table 4-1 LBP Sampling Results 10
Table 5-1 Lead Wipe Sampling Results 11
Appendices
Appendix A ASBESTOS LABORATORY REPORT
Appendix B LEAD-BASED PAINT LABORATORY REPORT
Appendix C LEAD WIPE LABORATORY REPORT
Appendix D SAMPLING DIAGRAMS
Appendix E QUALIFICATIONS
April 22, 2019 ATC 5
1 Introduction
1.1 Purpose
The purpose of this project was to conduct limited asbestos, lead-based paint, and lead dust sampling at various buildings at the VA Medical Center property located at 5500 Armstrong Road, Battle Creek, Michigan.
1.2 Pre-Renovation Asbestos Survey
The scope of the asbestos survey included the following:
> Reviewing existing asbestos reports for the subject property, if available;
> Identification of accessible suspect asbestos-containing materials (ACMs);
> Collection of bulk samples for PLM analysis of suspect friable and non-friable materials; and
> Describing types, locations and estimated quantities of identified ACM and PACM.
1.3 Limited Lead-Based Paint Sampling
The scope of the limited lead-based paint (LBP) sampling included the following:
> Survey to identify paint coatings that were deemed representative of the predominant paint coatings within the property building(s); and
> Collection and analysis of paint chip samples from selected interior and exterior surfaces
1.4 Limited Lead Wipe Sampling
The scope of the limited lead-based paint (LBP) sampling included the following:
> Survey to identify access points within the HVAC system); and
> Collection and analysis of paint wipe samples from representative surface areas measuring twelve inches by twelve inches
April 22, 2019 ATC 6
2 General Site Conditions
2.1 General Property and Building Information
General property and building information is presented in the following table:
Table 2-1 General Property and Building Information
Date of Inspection: April 1, 2019 to April 11, 2019
Inspector Robert N. VanDyke, P.E.
Inspector Number A19528
Property Address: 5500 Armstrong Road, Battle Creek, Michigan
Property Owner Battle Creek VA Medical Center
Property Owner Address 5500 Armstrong Road, Battle Creek, Michigan
Property Owner Telephone No. NA
Building Construction Date: NA
Date(s) of Significant Renovations: NA
Building Description: Multiple story medical facility
Building Square Footage (Approximate): N/A.
2.2 Exterior Finish Descriptions
The structures targeted for renovation are occupied medical facility buildings. The property buildings are constructed of concrete block and brick with a basement (where present) and built up roofing (where present).
Exterior finish materials noted during the property inspection include brick, cement blocks, concrete, glass, metal, and steel.
2.3 Interior Building Descriptions
The interior of the buildings consists of treatment, exam, and recovery rooms, restrooms, storage rooms, mechanical rooms, break rooms, and office areas. Interior finish materials noted during the property inspection include resilient floor tiles (RFTs) and associated mastic; ceramic floor tile and associated grout and mortar, acoustical ceiling tiles (ACTs), drywall with associated joint compound, base cove and associated mastic, plaster, paint, concrete, metal, steel, glass, plastic, and carpet.
April 22, 2019 ATC 7
3 Limited Pre-Renovation Asbestos Survey
ATC representative, Mr. Robert N. VanDyke, P.E., conducted the pre-renovation asbestos inspection of the areas identified at the property buildings from April 1 through April 11, 2019. Mr. VanDyke is a State of Michigan Certified
Asbestos Inspector’s (Certification No. A19528). Site sketches identifying sampling locations and general building details are included as Appendix D. The property buildings were visually inspected for the presence of building materials that are suspected to contain asbestos. Bulk samples of suspect ACMs were collected and placed into individual containers for transport to a National Voluntary Lab Accreditation Program (NVLAP)-accredited laboratory for analysis. Materials typically known as non-asbestos items (i.e. fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos inspection consisted of the following three basic procedures:
> Conducting a visual inspection of the structures;
> Identifying homogeneous areas (HAs) of suspect surfacing, thermal system insulation, and miscellaneous materials; and
> Sampling accessible, friable and non-friable suspect materials.
3.1 Homogeneous Areas
Prior to collecting any samples, homogenous areas (HAs) were identified. A homogeneous sampling area can be described as one or more areas of material that are similar in appearance and texture and that have the same apparent installation date, appearance and function. Actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and professional opinion of the inspector.
3.2 Hazard Assessment Factors
From the list of suspect homogeneous areas, a physical assessment was performed for each material on the list.
A physical assessment includes evaluating the condition, assessing the potential for disturbance, and determining the friability of each material. By definition, "friable" materials are those that can be crumbled or reduced to powder by hand pressure when dry. Each material identified was further classified into one of three categories: surfacing materials, thermal systems insulation (TSI) and miscellaneous materials. Each of the three categories have specific sampling requirements, outlined below.
> Surfacing Materials: Refers to spray-applied or troweled surfaces such as plaster ceilings and walls, fireproofing, textured paints, textured plasters, and spray-applied acoustical surfaces.
> Thermal System Insulation: Refers to insulation used to inhibit heat gain or loss on pipes, boilers, tanks, ducts, and various other building components.
> Miscellaneous Materials: Refers to friable and non-friable products and materials that do not fit in any of the above two categories such as resilient floor covering, baseboards, mastics, adhesives, roofing material, caulking, glazing, and siding. This category also contains wallboard and ceiling tile.
All materials were assessed related to their condition in one of the three categories: good (intact), fair (damaged) or poor (significantly damaged) per Title 40 Code of Federal Regulations Part 763. Material with localized, significant damage was also assessed as poor.
3.3 Laboratory Analytical Methodology
Bulk samples were analyzed by APEX Research Inc, 11054 Hi Tech Drive, Whitmore Lake, Michigan, using polarized-light microscopy (PLM) and dispersion staining (Method Reference: 40 CFR Part 763, Volume 47, No.
103, May 27, 1982 pg. 23376). This laboratory participates in the National Voluntary Laboratory Accreditation
Program (NVLAP #102118-0), a quality assurance program for PLM analysis, and is accredited by the National
Institute of Standards and Technology (NIST) as well as accreditation requirements under 15 CFR Part 25.
Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in Appendix A.
Positive sample results are reported in percent asbestos by volume of the sample and the type of asbestos material
April 22, 2019 ATC 8 within the sample. Other common non-asbestos components may also be noted on the analytical reports.
Inspector and laboratory accreditations are provided in Appendix E.
3.4 Sampling Results
Bulk samples were collected from the site building and analyzed by polarized light microscopy (PLM), EPA Method
600/R-93/116. Two (2) of the materials sampled were found to contain concentrations of asbestos greater than
1%.
The following table provides a summary of accessible suspect and confirmed ACMs from the Site buildings:
Table 3-1 ACM and PACM Summary Table
Sample ID Sample Description Sample
Location/Quantity if Positive
Friable
Yes/No Asbestos Content
01-CT-012-A,B,C
Ceiling Tile - white with pinholes & gouges Bldg 12 Yes ND
02-WBS-012-A,B,C Wall Board System Bldg 12 Yes ND
03-CN-012-A,B,C Concrete Bldg 12 No ND
04-PL-012-A,B,C Plaster Bldg 12 Yes ND
05-PF-012-A,B,C Mudded fitting on steam Bldg 12 Yes ND
06-PF-012-A,B,C
Mudded fittings on DWR
(Drip Water Return) Bldg 12 (2 Fittings) Yes 10% Chrysotile
01-WBS-002-A,B,C Wall board system Bldg 2 Yes ND
02-CT-002-A,B,C
Ceiling Tile - white with pinholes & gouges Bldg 2 Yes ND
01-PL-005-A,B,C Plaster Bldg 5 Yes ND
02-CN-005-A,B,C Concrete Bldg 5 No ND
03-MT-A,B,C Mortar Bldg 5 No ND
01-WBS-014-A,B,C Wall board system Bldg 14 Yes ND
02-CN-014-A,B,C Concrete Bldg 14 No ND
03-MT-014-A,B,C Mortar Bldg 14 No ND
01-WBS-082-A,B,C Wall board system Bldg 82 Yes ND
02-CT-082-A,B,C
Ceiling Tile - white with pinholes & gouges Bldg 82 Yes ND
03-CC-082-A,B,C Concrete Bldg 82 No ND
04-PF-082-A,B,C
Mudded fitting on fiberglass Bldg 82 Yes ND
01-CC-136-A,B,C Concrete Bldg 136 No ND
02-BM-136-A,B,C Brick mortar Bldg 136 No ND
April 22, 2019 ATC 9
Sample ID Sample Description Sample
Location/Quantity if Positive
Friable
Yes/No Asbestos Content
03-VM-136-A,B,C Vibration dampener Bldg 136 No ND
04-CT-136-A,B,C
Ceiling tile - white with pinholes & gouges Bldg 136 Yes ND
05-WBS-136-A,B,C Wall board system Bldg 136 Yes ND
01-WBS-039-A,B,C Wall board system Bldg 39 Yes ND
02-CC-039-A,B,C Concrete Bldg 39 No ND
03-PL-039-A,B,C Plaster Bldg 39 Yes ND
04-BM-039-A,B,C Brick mortar Bldg 39 No ND
05-CT-039-A,B,C
Ceiling Tile - white with pinholes & gouges Bldg 39 Yes ND
01-WBS-083-A,B,C Wall board system Bldg 83 Yes ND
02-CT-083-A,B,C
Ceiling Tile - white with pinholes & gouges Bldg 83 Yes ND
03-CC-083-A,B,C Concrete Bldg 83 No ND
04-BM-083-A,B,C Brick mortar Bldg 83 No ND
05-PI-083-A,B,C Pipe Insulation-4” lines Bldg 83 (240LF, 3 pipes -
80LF each) Yes 50% Chrysotile
01-WBS-200-A,B,C Wall board system Bldg 200 Yes ND
02-CC-200-A,B,C Concrete Bldg 200 No ND
01-WBS-022-A,B,C Wall board System Bldg 22 Yes ND
02-CC-022-A,B,C Concrete Bldg 22 No ND
03-CT-022-A,B,C
Ceiling Tile - white with pinholes & gouges Bldg 22 Yes ND
01-CT-084-A,B,C
Ceiling Tile - white with pinholes & gouges Bldg 84 Yes ND
02-CC-084-A,B,C Concrete Bldg 84 No ND
NAD: No Asbestos Detected SF/LF: square feet/linear feet VFT: Vinyl Floor Tile
NA: Not Applicable M: Miscellaneous S: Surfacing
TSI: Thermal System Insulation PACM: Presumed ACM UNQ: Not Quantified
NESHAP
RACM: Regulated ACM Cat. I: Category I Non-Friable ACM Cat. II: Category II Non-Friable ACM
In the event additional suspect material is discovered during demolition activities, this material should be treated as presumed asbestos-containing material (PACM) in accordance with regulations 29 CFR 1926.1101 and
1910.1001 and other applicable state and local regulations and either sampled to confirm or nullify asbestos content or be treated as ACM and handled accordingly.
April 22, 2019 ATC 10
4 Limited Lead-Based Paint Sampling
A Limited Lead-Based Paint (LBP) survey was conducted of readily accessible interior building areas by ATC representative Mr. Robert N. VanDyke, P.E. The LBP survey was completed from April 1 through April 11, 2019 and included physical sampling of paint coatings that were deemed representative of the predominant paint coatings observed within the building. LBP, as defined by the EPA is paint with a lead concentration of greater than or equal to 0.5% lead by weight.
Paint chip samples were collected from homogeneous interior/exterior areas and submitted to APEX Research
Inc, 11054 Hi Tech Drive, Whitmore Lake, Michigan for lead analysis. Bulk samples were analysed using the
Environmental Protection Agency's Test Method SW 846 -3050B and 7420 using Flame AAS to determine lead concentration in percent (%) by weight.
The following table provides a summary of the sampled paint from the Site buildings:
Table 4-1 LBP Sampling Results
Sample ID Color Sample Location Lead Content (%)
01-PT-014-A White Bldg 14 <0.01
01-PT-005-A Green Bldg 5 0.12
01-PT-002-A Tan Bldg 2 <0.03
02-PT-002-A Blue Bldg 2 <0.03
03-PT-002-A White Bldg 2 <0.04
04-PT-002-A Beige Bldg 2 <0.03
01-PT-136-A Gray Bldg 136 0.06
02-PT-136-B Yellow Bldg 136 0.04
01-PT-022-A Yellow Bldg 22 <0.02
01-PT-200-A White Bldg 200 <0.01
02-PT-200-A Beige Bldg 200 <0.02
01-PT-084-A Brown Bldg 84 0.13
02-PT-084-A White Bldg 84 0.23
03-PT-084-A Beige Bldg 84 <0.04
01-PT-083-A White Bldg 83 <0.07
02-PT-083-A Green Bldg 83 0.04
01-PT-039-A Green Bldg 39 0.30
02-PT-039-A White Bldg 39 0.24
03-PT-039-A Yellow Bldg 39 <0.03
Lead was detected in eight (8) of the samples; however, the results reported were below the EPA guideline of
0.5% lead by weight. Laboratory results of the paint chip sampling are included in Appendix B.
April 22, 2019 ATC 11
5 Limited Lead Wipe Sampling
Dust wipe sampling was conducted using “Lead Wipes” to sample representative surface areas measuring twelve inches by twelve inches within the ductwork in various locations throughout the buildings. A total of seven (7) dust samples were submitted for analysis to APEX Research Inc, 11054 Hi Tech Drive, Whitmore Lake, Michigan for lead analysis.
The following table provides a summary of the wipe samples from the Site buildings:
Table 5-1 Lead Wipe Sampling Results
Sample ID Area (ft2) Sample Location Lead Content (µg/ft2)
01-LW-002-A 1.0 Bldg 2 - Attic 168.0
02-LW-002-A 1.0 Bldg 2 - Basement 153.3
03-LW-012-A 1.0 Bldg 12 - 1st Floor 253.3
04-LW-012-A 1.0 Bldg 12 - 2nd Floor 159.0
05-LW-012-A 1.0 Bldg 12 - Attic 226.0
06-LW-136-A 1.0 Bldg 136 - Penthouse 216.0
07-LW-136-A 1.0 Bldg 136 - Ground Floor 80.8
The results of the lead sampling in dust indicate levels of lead were detected above the detection limit. OSHA does not have a standard for levels of lead in dust, however, the OSHA Lead in Construction standard requires workers who may disturb lead surfaces to be trained in accordance with the standard. In addition, workers should be notified of the potential lead in dust or paint hazards, and to ensure work that will disturb the materials that contain lead are done so with appropriate work practices, PPE, and personal hygiene requirements as stated in the standard.
Laboratory results of the wipe sampling are included in Appendix C.
April 22, 2019 ATC 12
6 Conclusions and Recommendations
6.1 Asbestos-Containing Materials
The results of laboratory testing during the pre-renovation asbestos survey conducted at the property indicate that two (2) of the materials sampled were found to contain asbestos.
Non-friable ACM’s shall not be subjected to abrasion, grinding, sanding or any other processes during demolition activities which will render these non-friable materials friable.
Based on the NESHAP (National Emission Standards for Hazardous Air Pollutants) non-friable Category I ACM and Category I non-friable PACM roofing materials that are asphalt/tar based can be demolished with a building so long as it is in good condition and will not be cut, pounded, sanded, or grinded during demolition, and that measures are taken to ensure that it does not become friable, at which point will be considered RACM. This material can also be disposed off-site in a Class III, construction and demolition (C&D) debris, landfill within the framework of local/state regulations. In addition all roofing materials shall not be recycled if they contain Category
I ACM.
6.2 Lead-Based Paint
The results of laboratory testing during the limited lead-based paint sampling conducted at the property indicate that lead was not detected above the EPA established threshold of 0.5%.
The results of the lead in dust sampling in the ductwork indicate that lead is present in the dust above the detection limit.
The presence of LBP and lead dust requires, under OSHA 1926.62 requirements, that the contractor performing demolition, surface preparation, and other activities that impact or potentially impact on the LBP coating systems and dust, evaluate potential worker exposures to airborne lead. This evaluation can be based, for the specific activities denoted in 1926.62, on objective data obtained by the contractor on other, similar, worksites within the prior calendar year or, the Contractor should conduct a negative exposure assessment during work activities to ensure they are below the applicable Action Level for airborne lead. . In addition, LBP and LBP coated waste and construction debris must be evaluated and, on a case-by-case basis depending on this evaluation, quantitative analysis be performed on these waste steams to ensure compliance with EPA waste disposal regulations.
The presence of LBP does not, in itself, trigger regulatory compliance actions. However, when these materials are disturbed, the requirements of OSHA (1926.1101) and EPA may become operative. Appropriate actions in terms of removal methods, emissions control, worker protection, and waste disposal should be considered by the general contractor and applicable subcontractors while completing demolition activities.
April 22, 2019 ATC 13
7 Assumptions and Limitations
The results, findings, conclusions, and recommendations expressed in the report are based only on conditions that were noted during the NESHAP inspection conducted on March 11, 2019 performed by ATC. Selection of sample locations and frequency of sampling were based on EPA Guidance documents, ATC observations, and the assumption that building vintage and renovation history information presented to ATC allowed the proper designation of homogenous materials for each building.
This document does not contain the elements necessary for an abatement work plan and this document does not contain, nor should it take the place of, technical specifications for asbestos abatement.
Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering.
This statement is in lieu of other statements either expressed or implied. This report does not warrant against changes to material from future operations or conditions, nor does it warrant against operations or conditions against present
ACM material in locations not investigated.
The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users, and use or re-use of this document or the findings, conclusions, or recommendations is at the risk of said user.
April 22, 2019
APPENDIX A
ASBESTOS LABORATORY REPORT
Certificate of Laboratory Analysis Test Method, Polarized Light Microscopy (PLM)
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 01 Asbestos Present: NO Cellulose - 40%
Cust. #: 01-CT-012-A No Asbestos Observed Mineral Wool - 30% Material: Ceiling Tile, White w/ Pinholes/Gouges Other - 30% Location: Building 12 Appearance: beige,fibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 02 Asbestos Present: NO Cellulose - 40% Cust. #: 01-CT-012-B No Asbestos Observed Mineral Wool - 30% Material: Ceiling Tile, White w/ Pinholes/Gouges Other - 30% Location: Building 12 Appearance: beige,fibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 03 Asbestos Present: NO Cellulose - 40% Cust. #: 01-CT-012-C No Asbestos Observed Mineral Wool - 30% Material: Ceiling Tile, White w/ Pinholes/Gouges Other - 30% Location: Building 12 Appearance: beige,fibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Project # :188BS19195
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
Project : BCVA
NVLAP Lab Code 102118-0
APEX Research Inc., 11054 Hi Tech Drive, Whitmore Lake, MI 48189
(734) 449-9990, Fax (734) 449-9991 Page 1 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 04 Asbestos Present: NO Cellulose - 5%
Cust. #: 02-WBS-012-A No Asbestos Observed Fiberglass - 2% Material: Wallboard/Drywall Other - 93% Location: Building 12 Appearance: white,fibrous,nonhomogenous Layer: 1 of 2
Lab ID #: 83417 - 04a Asbestos Present: NO Other - 100% Cust. #: 02-WBS-012-A No Asbestos Observed Material: Joint Compound Location: Building 12 Appearance: white,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 83417 - 05 Asbestos Present: NO Cellulose - 5% Cust. #: 02-WBS-012-B No Asbestos Observed Fiberglass - 2% Material: Wallboard/Drywall Other - 93% Location: Building 12 Appearance: white,fibrous,nonhomogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 2 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 05a Asbestos Present: NO Other - 100%
Cust. #: 02-WBS-012-B No Asbestos Observed Material: Joint Compound Location: Building 12 Appearance: white,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 83417 - 06 Asbestos Present: NO Cellulose - 5% Cust. #: 02-WBS-012-C No Asbestos Observed Fiberglass - 1% Material: Wallboard/Drywall Other - 94% Location: Building 12 Appearance: white,fibrous,nonhomogenous Layer: 1 of 2
Lab ID #: 83417 - 06a Asbestos Present: NO Other - 100% Cust. #: 02-WBS-012-C No Asbestos Observed Material: Joint Compound Location: Building 12 Appearance: white,nonfibrous,homogenous Layer: 2 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 3 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 07 Asbestos Present: NO Other - 100%
Cust. #: 03-CN-012-A No Asbestos Observed Material: Concrete Location: Building 12 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 08 Asbestos Present: NO Other - 100% Cust. #: 03-CN-012-B No Asbestos Observed Material: Concrete Location: Building 12 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 09 Asbestos Present: NO Other - 100% Cust. #: 03-CN-012-C No Asbestos Observed Material: Concrete Location: Building 12 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 4 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 10 Asbestos Present: NO Other - 100%
Cust. #: 04-PL-012-A No Asbestos Observed Material: Plaster Finish Coat Location: Building 12 Appearance: white,nonfibrous,homogenous Layer: 1 of 2
Lab ID #: 83417 - 10a Asbestos Present: NO Cellulose - 1% Cust. #: 04-PL-012-A No Asbestos Observed Other - 99% Material: Plaster Base Coat Location: Building 12 Appearance: grey,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 83417 - 11 Asbestos Present: NO Other - 100% Cust. #: 04-PL-012-B No Asbestos Observed Material: Plaster Finish Coat Location: Building 12 Appearance: white,nonfibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 5 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 12 Asbestos Present: NO Other - 100%
Cust. #: 04-PL-012-C No Asbestos Observed Material: Plaster Finish Coat Location: Building 12 Appearance: white,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 13 Asbestos Present: NO Cellulose - 10% Cust. #: 05-PF-012-A No Asbestos Observed Mineral Wool - 20% Material: Mudded Fitting on Steam Other - 70% Location: Building 12 Appearance: grey,fibrous,nonhomogenous Layer: 1 of 1
Lab ID #: 83417 - 14 Asbestos Present: NO Cellulose - 10% Cust. #: 05-PF-012-B No Asbestos Observed Mineral Wool - 20% Material: Mudded Fitting on Steam Other - 70% Location: Building 12 Appearance: grey,fibrous,nonhomogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 6 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 15 Asbestos Present: NO Cellulose - 10%
Cust. #: 05-PF-012-C No Asbestos Observed Mineral Wool - 20% Material: Mudded Fitting on Steam Other - 70% Location: Building 12 Appearance: grey,fibrous,nonhomogenous Layer: 1 of 1
Lab ID #: 83417 - 16 Asbestos Present: YES Cellulose - 10% Cust. #: 06-PF-012-A Chrysotile - 10% Mineral Wool - 10% Material: Mudded Fittings on DWR Other - 70% Location: Building 12 Appearance: white,fibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 17 Asbestos Present:
Cust. #: 06-PF-012-B Material: Mudded Fittings on DWR Location: Building 12 NOT ANALYZED Appearance:
Layer: of
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 7 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 18 Asbestos Present:
Cust. #: 06-PF-012-C Material: Mudded Fittings on DWR Location: Building 12 NOT ANALYZED Appearance:
Layer: of
Lab ID #: 83417 - 19 Asbestos Present: NO Cellulose - 5% Cust. #: 01-WBS-002-A No Asbestos Observed Fiberglass - 5% Material: Wallboard/Drywall Other - 90% Location: Building 2 Appearance: white,fibrous,nonhomogenous Layer: 1 of 2
Lab ID #: 83417 - 19a Asbestos Present: NO Other - 100% Cust. #: 01-WBS-002-A No Asbestos Observed Material: Joint Compound Location: Building 2 Appearance: white,nonfibrous,homogenous Layer: 2 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 8 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 20 Asbestos Present: NO Cellulose - 5%
Cust. #: 01-WBS-002-B No Asbestos Observed Fiberglass - 2% Material: Wallboard/Drywall Other - 93% Location: Building 2 Appearance: white,fibrous,nonhomogenous Layer: 1 of 2
Lab ID #: 83417 - 20a Asbestos Present: NO Other - 100% Cust. #: 01-WBS-002-B No Asbestos Observed Material: Joint Compound Location: Building 2 Appearance: white,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 83417 - 21 Asbestos Present: NO Cellulose - 5% Cust. #: 01-WBS-002-C No Asbestos Observed Fiberglass - 2% Material: Wallboard/Drywall Other - 93% Location: Building 2 Appearance: white,fibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 9 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 21a Asbestos Present: NO Other - 100%
Cust. #: 01-WBS-002-C No Asbestos Observed Material: Joint Compound Location: Building 2 Appearance: white,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 83417 - 22 Asbestos Present: NO Cellulose - 40% Cust. #: 02-CT-002-A No Asbestos Observed Mineral Wool - 40% Material: Ceiling Tile, White w/ Pinholes/Gouges Other - 20% Location: Building 2 Appearance: beige,fibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 23 Asbestos Present: NO Cellulose - 40% Cust. #: 02-CT-002-B No Asbestos Observed Mineral Wool - 40% Material: Ceiling Tile, White w/ Pinholes/Gouges Other - 20% Location: Building 2 Appearance: beige,fibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification,approval, or endorsement by NVLAP, NIST, or any agency of the US Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 10 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 24 Asbestos Present: NO Cellulose - 40%
Cust. #: 02-CT-002-C No Asbestos Observed Mineral Wool - 40% Material: Ceiling Tile, White w/ Pinholes/Gouges Other - 20% Location: Building 2 Appearance: beige,fibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 25 Asbestos Present: NO Other - 100% Cust. #: 01-PL-005-A No Asbestos Observed Material: Plaster Finish Coat Location: Building 5 Appearance: white,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 26 Asbestos Present: NO Other - 100% Cust. #: 01-PL-005-B No Asbestos Observed Material: Plaster Finish Coat Location: Building 5 Appearance: white,nonfibrous,homogenous Layer: 1 of 2
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification,approval, or endorsement by NVLAP, NIST, or any agency of the US Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 11 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 26a Asbestos Present: NO Other - 100%
Cust. #: 01-PL-005-B No Asbestos Observed Material: Plaster Base Coat Location: Building 5 Appearance: brown,nonfibrous,homogenous Layer: 2 of 2
Lab ID #: 83417 - 27 Asbestos Present: NO Other - 100% Cust. #: 01-PL-005-C No Asbestos Observed Material: Plaster Finish Coat Location: Building 5 Appearance: white,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 28 Asbestos Present: NO Other - 100% Cust. #: 02-CN-005-A No Asbestos Observed Material: Concrete Location: Building 5 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification,approval, or endorsement by NVLAP, NIST, or any agency of the US Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 12 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 29 Asbestos Present: NO Other - 100%
Cust. #: 02-CN-005-B No Asbestos Observed Material: Concrete Location: Building 5 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 30 Asbestos Present: NO Other - 100% Cust. #: 02-CN-005-C No Asbestos Observed Material: Concrete Location: Building 5 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 31 Asbestos Present: NO Other - 100% Cust. #: 03-MT-A No Asbestos Observed Material: Mortar Location: Building 5 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification,approval, or endorsement by NVLAP, NIST, or any agency of the US Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 13 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 32 Asbestos Present: NO Other - 100%
Cust. #: 03-MT-B No Asbestos Observed Material: Mortar Location: Building 5 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 33 Asbestos Present: NO Other - 100% Cust. #: 03-MT-C No Asbestos Observed Material: Mortar Location: Building 5 Appearance: grey,nonfibrous,homogenous Layer: 1 of 1
Lab ID #: 83417 - 34 Asbestos Present: NO Cellulose - 5% Cust. #: 01-WBS-014-A No Asbestos Observed Fiberglass - 2% Material: Wallboard/Drywall Other - 93% Location: Building 14 Appearance: white,fibrous,nonhomogenous Layer: 1 of 1
For Layered Samples, each component will be analyzed and reported separately.
Robert T. Letarte Jr., Laboratory Director
Test Method EPA 600/R-93/116 was used to analyze the above samples. Matrix interference and/or resolution limits may yield false/negative results in certain circumstances. Suspect floor tiles containing <1% should be tested with SEM or TEM. This certificate of analysis relates only to the samples tested and to insure the integrity of the results, may only be reproduced in full. This certificate must not be used by the customer to claim product certification,approval, or endorsement by NVLAP, NIST, or any agency of the US Government. APEX Research Inc. is not responsible for the accuracy of the results for layered samples or samples comprising multiple materials. Liability limited to cost of analysis.
(734) 449-9990, Fax (734) 449-9991 Page 14 of 47
Report To: ARI Report # 19-83417 Mr. Robert Van Dyke Date Collected:
ATC Group Services, LLC Date Received: 04/12/19 2650 Horizon Dr., Suite 110 Date Analyzed: 04/16/19 Grand Rapids, MI 49546 Date Reported: 04/17/19
Project # :188BS19195 Project : BCVA
Sample Information Asbestos Type/Percent Non-Asbestos Material
Lab ID #: 83417 - 35 Asbestos Present: NO Cellulose - 5%
Cust. #: 01-WBS-014-B No Asbestos Observed…