Specification -STRUCTURAL STEEL FRAMING.docx

DOCX document 33 KB Posted

Attached to
Z1DA--506-17-503 Chiller Plant Optimization Federal contract opportunity
Solicitation number
36C25020B0063
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document contains a specification for structural steel framing and a pre-solicitation announcement for a construction project. The specification outlines requirements for structural steel shapes, plates, bars, and pipe to be used in framing. It includes sections on related work, quality assurance, submittals, materials, fabrication, finishes, accessories, erection, and field quality control.

The pre-solicitation announcement indicates the Department of Veterans Affairs will issue an Invitation for Bid on June 10, 2020 for a construction project at the Ann Arbor VA Medical Center to improve performance of existing water-cooled centrifugal chillers in the central chiller plant. The project scope includes rerouting primary and secondary chilled water piping, tying cooling tower basins together and modifying controls, eliminating 3-way chilled water valves, and modifying control sequences. The contract will be a firm fixed price awarded within 120 days, with a performance period of 270 days.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--506-17-503 Chiller Plant Optimization, newest first.
File Type Posted
36C25020B0063 0003.docx DOCX document
36C25020B0063 0002.docx DOCX document
Covid Instructions.docx DOCX document
506-17-503 RFI.docx DOCX document
36C25020B0063 0001.docx DOCX document
506-17-503 Drawing -Building 32 - Pipping Plan.pdf PDF
Pre-Bid Attendance.pdf PDF
506-17-503 Drawing - Building 32 - Roof Level.pdf PDF
Ann Arbor Chiller Plant Optimization - Project RFI Questions r1.pdf PDF
36C25020B0063.docx DOCX document
WD MI20200100 rev 7-10-2020.txt TXT text file
506-17-503 Contractor EMR Certification Form 2020.docx DOCX document
506-17-503 - Specifications.pdf PDF
506-17-503 PM_Part808.405-6_Atch1_Limiting_Sources_Justification_MPT-SAT - Siemens (003)- CORRECTED.pdf PDF
S02 - RFI Form 506-17-503.docx DOCX document
506-17-503 Drawings.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHILLER PLANT OPTIMIZATION506-17-503
ANN ARBOR, MI11-01-18

SECTION 05 12 00

STRUCTURAL STEEL FRAMING

SPEC WRITER NOTE: Delete text between // ______ // not applicable to project. Edit remaining text to suit project.

GENERAL

SUMMARY

Section Includes:

Structural steel shapes, plates, and bars.

Structural pipe.

RELATED REQUIREMENTS

SPEC WRITER NOTE: Update and retain references only when specified elsewhere in this section.

Materials Testing and Inspection During Construction: Section 01 45 29, TESTING LABORATORY SERVICES.

Roof Decks Framing: Section 03 51 16, GYPSUM CONCRETE ROOF DECKS.

Floor Decks Framing: Section 03 55 11, GYPSUM CONCRETE FLOOR DECKS.

Steel Framing: // Section 08 44 13, GLAZED ALUMINUM CURTAIN WALLS // Section 13 34 19, METAL BUILDING SYSTEMS //.

Steel Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.

Painting: Section 09 91 00, PAINTING.

Steel Piles: Section 31 62 00, DRIVEN PILES.

SPEC WRITER NOTE: AISC has a certification program confirming that certified structural steel fabricating plant has procedures and commitment to produce fabricated steel of required quality for given category of structural steel framing. Consider deleting category certification if there is minimal amount of steel required. Category is STD: Standard for Building Structures.

APPLICABLE PUBLICATIONS

Comply with references to extent specified in this section.

American Institute of Steel Construction (AISC):

AISC Manual - Steel Construction Manual, 14th Ed.

30310 - Code of Structural Steel Buildings and Bridges.

36010: Specification for Structural Steel Buildings.

The American Society of Mechanical Engineers (ASME):

B18.22.109 - Washers: Helical SpringLock, Tooth Lock, and Plain Washers.

American Welding Society (AWS):

D1.1/D1.1M15 - Structural Welding Code - Steel.

ASTM International (ASTM):

A6/A6M14 - General Requirements for Rolled Structural Steel Bars, Plates, Shapes, and Sheet Piling.

A36/A36M14 - Carbon Structural Steel.

A53/A53M12 - Pipe, Steel, Black and HotDip, ZincCoated, Welded and Seamless.

A123/A123M15 - Zinc (HotDip Galvanized) Coatings on Iron and Steel Products.

A242/A242M13 - HighStrength LowAlloy Structural Steel.

A283/A283M13 - Low and Intermediate Tensile Strength Carbon Steel Plates.

A30714 - Carbon Steel Bolts, Studs, and Threaded Rod 60,000 PSI Tensile Strength.

A500/A500M13 - ColdFormed Welded and Seamless Carbon Steel Structural Tubing and Rounds and Shapes.

A501/A501M14 - HotFormed Welded and Seamless Carbon Steel Structural Tubing and Rounds and Shapes.

A572/A572M15 - HighStrength LowAlloy ColumbiumVanadium Structural Steel.

A992/A992M15 - Structural Shapes.

F2329/F2329M15 - Zinc Coating, HotDip, Requirements for Application to Carbon and Alloy steel Bolts, Screws, washers, Nuts, and Special Threaded Fasteners.

F3125/F3125M-15 - Standard Specification for High Strength Structural Bolts, Steel and Alloy Steel, Heat Treated, 120 ksi (830 MPa) and 150 ksi (1040 MPa) Minimum Tensile Strength, Inch and Metric Dimensions Master Painters Institute (MPI):

No. 18 - Primer, Zinc Rich, Organic.

Military Specifications (Mil. Spec.):

MILP21035 - Paint, High Zinc Dust Content, Galvanizing, Repair.

Occupational Safety and Health Administration (OSHA):

29 CFR 1926.752(e) - Guidelines For Establishing The Components Of A SiteSpecific Erection Plan.

29 CFR 19262001 - Safety Standards for Steel Erection.

Research Council on Structural Connections (RCSC) of The Engineering Foundation:

Specification for Structural Joints Using ASTM F3125 Bolts.

SUBMITTALS

Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Submittal Drawings:

Show size, configuration, and fabrication and installation details.

Sustainable Construction Submittals:

Test Reports: Certify products comply with specifications.

Welders' qualifying tests.

Certificates: Certify each product complies with specifications.

Structural steel.

Steel connections.

Welding materials.

Shop coat primer paint.

Qualifications: Substantiate qualifications comply with specifications.

Fabricator // with project experience list //.

Installer // with project experience list //.

Welders and welding procedures.

SPEC WRITER NOTE: Include cooling tower supports, only when required and not detailed on structural drawings.

// Cooling Tower Supports. //

QUALITY ASSURANCE

Fabricator Qualifications: AISC Quality Certification participant designated as AISC Certified Plant, Category STD.

Regularly fabricates specified products.

Fabricated specified products with satisfactory service on five similar installations for minimum five years.

// Project Experience List: Provide contact names and addresses for completed projects. // Installer Qualifications: AISC Quality Certification Program participant designated as AISCCertified Erector, Category ACSE.

Regularly installs specified products.

Installed specified products with satisfactory service on five similar installations for minimum five years.

// Project Experience List: Provide contact names and addresses for completed projects. // Before commencement of Work, ensure steel erector provides written notification required by OSHA 29 CFR 1926.752(e). Submit a copy of the notification to Contracting Officer's Representative.

Welders and Welding Procedures Qualifications: AWS D1.1/D1.1M.

WARRANTY

SPEC WRITER NOTE: Always retain construction warranty. FAR includes Contractor's one year labor and material warranty.

Construction Warranty: FAR clause 52.24621, "Warranty of Construction."

PRODUCTS

NOT USED

SPEC WRITER NOTE: Include cooling tower supports when required for project. Add other specific components requiring delegated design.

Design cooling tower supports meeting specified performance:

Coordinate design criteria with cooling tower specified in Section 23 65 00, COOLING TOWERS.

Design Loads: Support operating cooling tower maximum dead load and minimum dead load when combined with lateral loads. Resist wind, snow, // seismic // loads indicated on drawings and supplied by Cooling Tower manufacturer.

Configuration: Design framing member sizes, dimensions, and locations to suit cooling tower load, size, and configuration. Submit detailed drawings and design calculations, prepared by a registered Professional Engineer, for approval before members are fabricated.

MATERIALS

SPEC WRITER NOTE: For each structural steel shape, select reference standard. First two subparagraphs are typical; last subparagraph is considered specialty steel.

WShapes:

ASTM A992/A992M.

ASTM A572/A572M; Grade // 50 // 60 // 65 //.

ASTM A529; Grade // 50 // 55 //.

ASTM A572/A572M; Grade // 50 // 60 // 65 //.

ASTM A529; Grade // 50 // 55 //.

Channel and Angles:

ASTM A36/A36M.

ASTM A572/A572M; Grade // 50 // 60 // 65 //.

ASTM A529; Grade // 50 // 55 //.

Plates and Bars:

ASTM A36/A36M.

ASTM A572/A572M; Grade // 50 // 60 // 65 //.

ASTM A529; Grade // 50 // 55 //.

Welding Materials: AWS D1.1, type to suit application.

PRODUCTS - GENERAL

Sustainable Construction Requirements:

Steel Recycled Content: 30 percent total recycled content, minimum.

Low PollutantEmitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:

Paints and coatings.

FABRICATION

Fabricate structural steel according to Chapter M, AISC 360.

Shop and Field Connections:

Weld connections according to AWS D1.1/D1.1M. Welds shall be made only by welders and welding operators who have been previously qualified by tests as prescribed in AWS D1.1 to perform type of work required.

FINISHES

Shop Priming:

Prime paint structural steel according to AISC 303, Section 6.

Interstitial Space Structural Steel: Prime paint, unless indicated to receive sprayed on fireproofing.

Shop Finish Painting: Apply primer and finish paint as specified in Section 09 91 00, PAINTING.

Do not paint:

Surfaces within 50 mm (2 inches) of field welded joints.

Surfaces indicated to be encased in concrete.

Surfaces receiving sprayed on fireproofing.

Beam top flanges receiving shear connector studs applied.

ACCESSORIES

General: Shop paint steel according to AISC 303, Section 6.

Finish Paint System: Primer and finish as specified in Section 09 91 00, PAINTING, OR OTHERWISE EXTERIOR URETHANE ALKYD SEMI-GLOSS ENAML COLOR TO MATCH EXISTING FRAMING PAINT.

EXECUTION

ERECTION

Erect structural steel according to AISC 303 and AISC 360.

Set structural steel accurately at locations and elevations indicated on drawings.

Maintain erection tolerances of structural steel within AISC 303 requirements.

Pour Stop Elevation Tolerance: 6 mm (1/4 inch), maximum, before concrete placement.

Weld and bolt connections as specified for shop connections.

FIELD PAINTING

After welding, clean and prime weld areas to match adjacent finish.

Touchup primer damaged by construction operations.

Finish Painting: As specified in Section 09 91 00, PAINTING.

FIELD QUALITY CONTROL

- E N D - 05 12 00 - 1