Correct Fire Damper Deficiencies 583-19-502 Federal contract opportunity
Solicitation number
36C25019B0057
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25019B0057 0005 Fire Dampers Reference Material - Part3.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Correct Fire Damper Deficiencies 583-19-502, newest first.
File Type Posted
36C25019C0300-000.docx DOCX document
36C25019B0057-0010000.docx DOCX document
36C25019B0057-0010000.docx DOCX document
36C25019B0057-0009001.pdf PDF
36C25019B0057-0009000.docx DOCX document
36C25019B0057-0009001.pdf PDF
36C25019B0057-0009000.docx DOCX document
36C25019B0057-0008001.pdf PDF
36C25019B0057-0008000.docx DOCX document
36C25019B0057-0008000.docx DOCX document
36C25019B0057-0008001.pdf PDF
36C25019B0057-0007001.pdf PDF
36C25019B0057-0007000.docx DOCX document
36C25019B0057-0006000.docx DOCX document
36C25019B0057-0006001.pdf PDF
36C25019B0057-0006000.docx DOCX document
36C25019B0057-0006001.pdf PDF
36C25019B0057-0005001.pdf PDF
36C25019B0057-0005000.docx DOCX document
36C25019B0057-0005000.docx DOCX document
36C25019B0057-0004000.docx DOCX document
36C25019B0057-0004001.pdf PDF
36C25019B0057-0004001.pdf PDF
36C25019B0057-0004000.docx DOCX document
36C25019B0057-0003001.pdf PDF
36C25019B0057-0003000.docx DOCX document
36C25019B0057-0003001.pdf PDF
36C25019B0057-0003000.docx DOCX document
36C25019B0057-0002001.docx DOCX document
36C25019B0057-0002000.docx DOCX document
36C25019B0057-0002000.docx DOCX document
36C25019B0057-0002001.docx DOCX document
36C25019B0057-0002002.pdf PDF
36C25019B0057-0001000.docx DOCX document
36C25019B0057-0001001.docx DOCX document
36C25019B0057-0001000.docx DOCX document
36C25019B0057-0001001.docx DOCX document
36C25019B0057-004.docx DOCX document
36C25019B0057-005.doc DOC document
36C25019B0057-001.docx DOCX document
36C25019B0057-003.pdf PDF
36C25019B0057-006.pdf PDF
36C25019B0057-001.docx DOCX document
36C25019B0057-006.pdf PDF
36C25019B0057-002.docx DOCX document
36C25019B0057-003.pdf PDF
36C25019B0057-004.docx DOCX document
36C25019B0057-005.doc DOC document
36C25019B0057-000.docx DOCX document
36C25019B0057-000.docx DOCX document
Show all 50

Correct Fire Damper Deficiencies 583-19-502 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Richard L Roudebush VAMC - Fire Damper Testing Project # 583-18-501

Damper Identifier FD-5-063 Location Interspatial Space A-5005 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes None

Damper Identifier FD-5-064

Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-9-2018 Passed or Failed Failed Deficiencies / Notes Damper did not close all the way.

Damper Identifier FD-5-065

Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-9-2018

Damper Identifier FD-5-066 Location Unknown, unable to locate Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018 Passed or Failed Unknown, unable to locate Deficiencies / Notes Unknown, unable to locate

Damper Identifier FD-5-067

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018

Damper Identifier FD-5-068 Location Interstitial Space A-5005 Damper Type Fire damper Manufacturer Unknown, could not access Style Unknown, could not access Label On access door Picture No Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-8-2018 Passed or Failed Could not test Deficiencies / Notes Fire damper is inaccessible.

Damper Identifier FD-5-069

Damper Type Fire damper Manufacturer Unknown, could not access Style Unknown, could not access Label On access panel Picture No Access Panel Hinged Door Condition of Access Panel

Good

Date Tested 5-9-2018

Deficiencies / Notes Inaccessible, could not test.

Damper Identifier FD-5-070A Location Mechanical room A-5000 Damper Type Fire damper Manufacturer Unknown, could not read manufacturer label Style Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-8-2018

Deficiencies / Notes Fire damper is too far away from access door to test.

Damper Identifier FD-5-071 Location Mechanical room A-5000 Damper Type Fire damper Manufacturer Unknown, could not read manufacturer label Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-8-2018

Deficiencies / Notes Fire damper is too far away from access door to test.

Damper Identifier FD-5-072A Location Mechanical Room a-5000 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-8-2018

Damper Identifier FD-5-073 Location Mechanical Room a-5000 Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-8-2018

Damper Identifier FD-5-074

Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Hand Knob Screws Condition of Access Panel

Good

Date Tested 5-9-2018

Damper Identifier FD-5-075

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-9-2018

Damper Identifier FD-5-076

Damper Type Fire damper Manufacturer Unknown, could not access Style Unknown, could not access Label On access door Picture No Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-8-2018

Damper Identifier FD-5-077

Damper Type Fire damper Manufacturer Unknown, could not access Style Unknown, could not access Label On access door Picture No Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-8-2018

Damper Identifier FD-5-078

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018

Damper Identifier FD-5-079

Damper Type Fire damper Manufacturer Unknown, could not access damper Style Unknown, could not access damper Label On access door Picture No Access Panel Latches Only Condition of Access Panel

Good

Date Tested 5-9-2018

Deficiencies / Notes Inaccessible, could not test

Damper Identifier FD-5-079A

Damper Type Fire damper Manufacturer Unknown, could not access damper Style Unknown, could not access damper Label On access door Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-9-2018

Deficiencies / Notes Inaccessible, could not test.

Damper Identifier FD-5-080

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018

Damper Identifier FD-5D-001 Location Room D-5033 Damper Type Fire damper Manufacturer Greenheck Style Opposable Blades Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-7-2018

Deficiencies / Notes Access is in inside of chase.

Damper Identifier FD-5D-002 Location Room D-5033 Damper Type Fire damper Manufacturer Greenheck Style Opposable Blades Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access

Damper Identifier FD-5D-003

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier FD-5D-004

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier FD-5D-005 Location Room D-5018 Damper Type Fire damper Manufacturer No manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door, and Latches only Condition of Access

Deficiencies / Notes Has two access panels.

Damper Identifier FD-5D-006 Location Chase accessed off corridor C5-18 Damper Type Fire damper Manufacturer No manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access

Deficiencies / Notes Access panel into chase off of corridor C5-18 is spring loaded hinged door. Chase access door cannot be opened from inside the chase. Safety release has been painted over and will not move.

Damper Identifier FD-5D-007 Location Room D-5004 Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door in hard ceiling Picture Yes Access Panel Hinged door Condition of Access

Deficiencies / Notes Above hard ceiling.

Damper Identifier FD-5D-008 Location Room D-5004 Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door in hard ceiling Picture Yes Access Panel Hinged door Condition of Access

Deficiencies / Notes Above hard ceiling.

Damper Identifier FD-5D-009 Location Room D-5007 Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access

Damper Identifier FD-5D-010 Location Room D-5010 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access

Damper Identifier FD-5D-011 Location Room D-5010 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access

Damper Identifier FD-5D-012 Location Men’s Restroom D-5022 Damper Type Fire damper Manufacturer No manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access

Passed or Failed Did not test Deficiencies / Notes Due to very small access the fire link could not be removed to test.

Damper Identifier FD-5D-013 Location Women’s Restroom D-5023 Damper Type Fire damper Manufacturer No manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access

Deficiencies / Notes Access is very limited, should be bigger.

Damper Identifier FD-5D-014 Location Unknown Damper Type Fire damper Manufacturer Unknown Style Unknown Label None Picture No Access Panel Unknown Condition of Access Panel

Unknown

Date Tested 5-7-2018 Passed or Failed Not found Deficiencies / Notes Was not found.

Damper Identifier FD-5D-015 Location Women’s restroom C-5111 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On access door in hard ceiling Picture Yes Access Panel Hinged door Condition of Access

Deficiencies / Notes Damper could not be reached from access panel.

Damper Identifier FD-5D-016

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier FD-5D-017

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier FD-5D-018 Location Restroom C-5052 Damper Type Unknown, could not access damper Manufacturer Unknown, could not access damper Style Unknown, could not access damper Label On access door in hard ceiling Picture No Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-8-2018 Passed or Failed Could not test Deficiencies / Notes Could not access fire damper it is too far away from access in hard ceiling

Damper Identifier FD-5D-019 Location Restroom C-5052 Damper Type Unknown, could not access damper Manufacturer Unknown, could not access damper Style Unknown, could not access damper Label On access door in hard ceiling Picture No Access Panel None Condition of Access Panel

No access panel

Date Tested 5-8-2018 Passed or Failed Could not test Deficiencies / Notes Could not access fire damper it is too far away from access in hard ceiling

Damper Identifier FD-5D-020 thru FD-5D-069

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier FD-5D-070 Location Women’s Restroom C-5111 Damper Type Fire damper Manufacturer Removed Style Removed Label None Picture No Access Panel None Condition of Access Panel

Removed

Date Tested 5-7-2018 Passed or Failed Removed Deficiencies / Notes This fire damper was removed and capped off.

Identifying label has now be removed from access panel in hard ceiling.

Damper Identifier FD-5D-071 Location Mechanical Room C-5103 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access

Deficiencies / Notes Damper could not be reached from access panel. There are also pipes below access door making access very limited, cannot set up a ladder to reach properly.

Damper Identifier FD-5D-072

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier FD-5P-001 Location 5th Floor Penthouse Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Not on list

Damper Identifier FD-5P-002

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-003

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-004

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-005

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-006

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-007

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-008

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-009

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-010

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-5P-011

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-15-2018 Passed or Failed Passed

Not on List

Damper Identifier FD-5P-012

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-15-2018 Passed or Failed Passed

Damper Identifier FD-5P-013

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Screwed on cap Condition of Access Panel

Good

Date Tested 5-15-2018 Passed or Failed Passed Deficiencies / Notes None

This duct has been capped off and is no longer in use.

Damper Identifier FD-5P-014

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-14-2018 Passed or Failed Passed

Damper Identifier FD-6-001 Location Unknown, could not find Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-3-2018 Passed or Failed Unknown, could not find Deficiencies / Notes Unknown, could not find

Damper Identifier FD-6-002 Location Room C-6116 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-8-2018

Deficiencies / Notes Linkage should be addressed it is not 100% correct.

Damper Identifier FD-6-003 Location Mechanical room C-6036 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Damper Identifier FD-6-004

Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Damper Identifier FD-6-005 Location Room C-6089 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-8-2018

Damper Identifier FD-6-006 Location Room C-6089 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On wall below ceiling Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-8-2018

Deficiencies / Notes Need to find air source to shut down the air flow.

Damper Identifier FD-6-007 Location Unknown, could not locate Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-2-2018

Damper Identifier FD-6-008

Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-3-2018

Damper Identifier FD-6-009

Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-3-2018

Damper Identifier FD-6-010 Location Room A-6155 Damper Type Fire damper Manufacturer Lloyd Industries Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Latches alone Condition of Access Panel

Good

Date Tested 5-2-2018

Damper Identifier FD-6-011 Location Repertory therapy hallway Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018 Passed or Failed Passed Deficiencies / Notes Damper rises up from the bottom. Not sure that is the correct way to install damper.

Damper Identifier FD-6-012 Location Room A-6163 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-2-2018 Passed or Failed Could not test Deficiencies / Notes The straps that hold the fire link in place are under the lap of the duct work and could not be undone. Very difficult to access. Damper rises up from the bottom. Not sure that is the correct way to install damper.

Damper Identifier FD-6-013 Location Corridor C6-12 Damper Type Fire damper Manufacturer Unknown Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged Door / hand knob screws Condition of Access Panel

Broken hinge. Has second access on other side of the wall.

Date Tested 5-1-2018

Deficiencies / Notes None.

Damper Identifier FD-6-014

Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On wall below ceiling Picture No Access Panel Hinged Door Condition of Access Panel

Too Small

Date Tested 5-1-2018 Passed or Failed Failed Deficiencies / Notes Access door to damper is too small. Cannot reach damper to test.

Damper Identifier FD-6-015 Location Room A-6062 Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access panel in drywall wall.

Picture Yes Access Panel Latches only Condition of Access Panel

One broken latch out of four.

Date Tested 5-1-2018

Deficiencies / Notes Access panel is too small to reach fire damper for testing.

Damper Identifier FD-6-016

Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-3-2018

Damper Identifier FD-6-017 Location Room A-6036 Damper Type Fire damper Manufacturer Unknown, in patient room not allowed access Style Unknown, in patient room not allowed access Label None Picture No Access Panel Unknown, in patient room not allowed access Condition of Access Panel

Unknown, in patient room not allowed access

Date Tested 5-1-2018

Deficiencies / Notes Unknown, in patient room not allowed access

Damper Identifier FD-6-018 Location Room A-6036 Damper Type Fire damper Manufacturer Unknown, in patient room not allowed access Style Unknown, in patient room not allowed access Label None Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018

Deficiencies / Notes Unknown, in patient room not allowed access

Damper Identifier FD-6-019 Location Room A-6050 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found.

Style Spring Loaded Guillotine Label On access door in drywall, wall Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-020 Location Room A-6051 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found.

Style Spring Loaded Guillotine Label On access door in drywall, wall Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Deficiencies / Notes Wrong fire link was installed to hold open temporarily.

Damper Identifier FD-6-021 Location Mechanical room A-6144 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On Access Door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-022

Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On Access Door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-023

Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On Access Door Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-024

Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On Access Door Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Deficiencies / Notes Damper only closed 90% of the way.

Damper Identifier FD-6-025

Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On Access Door Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-026

Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On Access Door Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-027

Damper Type Fire Damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Deficiencies / Notes Access is too small to reach dampers to test.

Damper Identifier FD-6-028

Damper Type Fire Damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Deficiencies / Notes Access door is too small to reach dampers to test.

Damper Identifier FD-6-029

Damper Type Fire Damper Manufacturer Ruskin Style Guillotine Label On wall below damper Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-030

Damper Type Fire Damper Manufacturer Ruskin Style Guillotine Label On Access Door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-031

Damper Type Fire Damper Manufacturer Ruskin Style Guillotine Label On Access Door Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-032

Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-1-2018

Damper Identifier FD-6-033

Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-034 thru FD-6-037 Location Unknown, could not find Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-1-2018

Damper Identifier FD-6-038 Location Room A-6062 Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-2-2018

Damper Identifier FD-6-039 Location Room A-6047A Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found.

Style Spring Loaded Guillotine Label On access door in drywall, wall Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Deficiencies / Notes Access panel should be bigger.

Damper Identifier FD-6-040 Location Room A-6020 Damper Type Fire Damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door in drywall, wall Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-041 Location Room A-6020 Damper Type Fire Damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door in drywall, wall Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-042 Location Corridor C6-10 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access door in drywall, wall Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018 Passed or Failed Failed Deficiencies / Notes The access for this damper is too small. Cannot reach dampers for testing.

Damper Identifier FD-6-043 Location Corridor C6-10 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access door in drywall, wall Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018 Passed or Failed Failed Deficiencies / Notes The access for this damper is too small. Cannot reach dampers for testing.

Damper Identifier FD-6-044 Location Room A-6019 Damper Type Fire Damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On access door in drywall, wall Picture Yes Access Panel Hinged door Condition of Access Panel

Good

Date Tested 5-1-2018

Damper Identifier FD-6-045 Location Mechanical Room A-6144 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-1-2018

Deficiencies / Notes Damper did not close all the way. Fire link is rusty.

Damper Identifier FD-6-046 thru FD-6-063

Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-1-2018

Damper Identifier FD-6-064 Location Corridor C6-7 Damper Type Fire / Smoke Damper Manufacturer Unknown, no access door to see label.

Style Opposable blades Label On wall below ceiling Picture No Access Panel None Condition of Access Panel

No access panel

Date Tested 5-2-2018 Passed or Failed Failed Deficiencies / Notes There is no access panel to see if the damper closed.

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Unknown

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? Smoke relay and removing wire.

Damper Identifier FD-6-065 Location Corridor C6-7 Damper Type Fire / Smoke Damper Manufacturer Greenheck Style Opposable blades Label On wall below ceiling Picture Yes Access Panel Hand knob screws Condition of Access Panel

Good

Date Tested 5-2-2018 Passed or Failed Failed Deficiencies / Notes Did not close when wire was lifted from fire alarm control box.

Damper Identifier FD-6-066

Damper Type Fire smoke combination damper Manufacturer Greenheck Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Failed Deficiencies / Notes Did not close upon fire alarm control panel disconnect.

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? Smoke Detector Relay

Damper Identifier FD-6D-001 Location Electrical room D-6022 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling in lobby area Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-2-2018 Passed or Failed Failed Deficiencies / Notes Damper found partially closed. Tab to hold fire link is missing. 2X4 placed in to hold damper open.

Damper Identifier FD-6D-002 Location Electrical room D-6022 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall diffuser Picture Yes Access Panel Remove wall diffuser Condition of Access Panel

Good

Date Tested 5-2-2018 Passed or Failed Failed Deficiencies / Notes Damper found partially closed. Tab to hold fire link is missing. 2X4 placed in to hold damper open.

Damper Identifier FD-6D-003 Location Lobby C6-32 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018 Passed or Failed Failed Deficiencies / Notes Due to lack of access this damper was not tested. There is a better access panel in the plumbing chase but no way to set up a ladder to reach it.

Damper Identifier FD-6D-004 Location Room D-6025 Damper Type Fire damper Manufacturer Ruskin Style Spring Loaded Guillotine Label On wall below ceiling Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Damper Identifier FD-6D-005

Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-3-2018

Damper Identifier FD-6D-006 Location Room D-6001 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Two access panels, one hinged and one latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Damper Identifier FD-6D-007 Location Room D-6039 Damper Type Fire damper Manufacturer Greenheck Style Opposable blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Damper Identifier FD-6D-008 Location Room D-6039 Damper Type Fire damper Manufacturer Greenheck Style Guillotine Label On wall below ceiling Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Deficiencies / Notes Unmovable desk in the way to test.

Damper Identifier FD-6D-009 Location Room D-6004 Damper Type Fire damper Manufacturer Greenheck Style Opposable blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018 Passed or Failed Failed Deficiencies / Notes Damper is installed the wrong direction to test. If fire link is removed the reset button will be inaccessible inside the chase. Did not test because would not be able to reopen if closed.

Damper Identifier FD-6D-010 Location Room D-6004-1 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel

Broken hinge

Date Tested 5-3-2018

Damper Identifier FD-6D-011 Location Room D-6004-2 Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018 Passed or Failed Failed Deficiencies / Notes Unmovable desk in the way to access damper. Damper could not be tested.

Damper Identifier FD-6D-012 Location Room D-6004-4 Damper Type Fire damper Manufacturer Unknown, could not access damper Style Unknown, could not access damper Label On wall below ceiling Picture No Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018 Passed or Failed Failed Deficiencies / Notes Unmovable desk in the way to access damper. Damper could not be tested.

Damper Identifier FD-6D-013 Location Room D-6007 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018 Passed or Failed Failed Deficiencies / Notes Unmovable desk is in the way of accessing damper to test.

Damper Identifier FD-6D-014 Location Room D-6007 Damper Type Fire damper Manufacturer Greenheck Style Opposable blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-3-2018

Damper Identifier FD-6D-015 Location Men’s restroom D-6027 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged Door Condition of Access Panel

Good

Date Tested 5-3-2018 Passed or Failed Failed Deficiencies / Notes Damper was found partially closed. Tab to hold fire link is missing so a 2X4 was placed in to hold damper open.

Damper Identifier FD-6D-016 Location Women’s restroom D-6028 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged Door Condition of Access Panel

Good

Date Tested 5-2-2018

Deficiencies / Notes Very small access.

Damper Identifier FD-6D-017 Location Room D-6004 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On wall below ceiling Picture Yes Access Panel Screwed in place cap.

Condition of Access Panel

No access panel. Duct was capped off.

Date Tested 5-3-2018 Passed or Failed Passed Deficiencies / Notes Damper was found behind capped off duct. Damper was tested and then closed as the duct is capped off and is no longer in use.

FD-5-063
FD-5-064
FD-5-065
FD-5-066
FD-5-067
FD-5-068
FD-5-069
FD-5-070A
FD-5-071
FD-5-072A
FD-5-073
FD-5-074
FD-5-075
FD-5-076
FD-5-077
FD-5-078
FD-5-079
FD-5-079A
FD-5-080
FD-5D-001
FD-5D-002
FD-5D-003
FD-5D-004
FD-5D-005
FD-5D-006
FD-5D-007
FD-5D-008
FD-5D-009
FD-5D-010
FD-5D-011
FD-5D-012
FD-5D-013
FD-5D-014
FD-5D-015
FD-5D-016
FD-5D-017
FD-5D-018
FD-5D-019
FD-5D-020 - 069
FD-5D-070
FD-5D-071
FD-5D-072
FD-5P-001
FD-5P-002
FD-5P-003
FD-5P-004
FD-5P-005
FD-5P-006
FD-5P-007
FD-5P-008
FD-5P-009
FD-5P-010
FD-5P-011
FD-5P-012
FD-5P-013
FD-5P-014
FD-6-001
FD-6-002
FD-6-003
FD-6-004
FD-6-005
FD-6-006
FD-6-007
FD-6-008
FD-6-009
FD-6-010
FD-6-011
FD-6-012
FD-6-013
FD-6-014
FD-6-015
FD-6-016
FD-6-017
FD-6-018
FD-6-019
FD-6-020
FD-6-021
FD-6-022
FD-6-023
FD-6-024