Correct Fire Damper Deficiencies 583-19-502 Federal contract opportunity
Solicitation number
36C25019B0057
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25019B0057 0008 Smoke Dampers Reference Material - Part1.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Correct Fire Damper Deficiencies 583-19-502, newest first.
File Type Posted
36C25019C0300-000.docx DOCX document
36C25019B0057-0010000.docx DOCX document
36C25019B0057-0010000.docx DOCX document
36C25019B0057-0009000.docx DOCX document
36C25019B0057-0009001.pdf PDF
36C25019B0057-0009000.docx DOCX document
36C25019B0057-0008000.docx DOCX document
36C25019B0057-0008000.docx DOCX document
36C25019B0057-0007001.pdf PDF
36C25019B0057-0007000.docx DOCX document
36C25019B0057-0007001.pdf PDF
36C25019B0057-0007000.docx DOCX document
36C25019B0057-0006000.docx DOCX document
36C25019B0057-0006001.pdf PDF
36C25019B0057-0006000.docx DOCX document
36C25019B0057-0006001.pdf PDF
36C25019B0057-0005000.docx DOCX document
36C25019B0057-0005001.pdf PDF
36C25019B0057-0005000.docx DOCX document
36C25019B0057-0005001.pdf PDF
36C25019B0057-0004000.docx DOCX document
36C25019B0057-0004001.pdf PDF
36C25019B0057-0004001.pdf PDF
36C25019B0057-0004000.docx DOCX document
36C25019B0057-0003001.pdf PDF
36C25019B0057-0003000.docx DOCX document
36C25019B0057-0003001.pdf PDF
36C25019B0057-0003000.docx DOCX document
36C25019B0057-0002001.docx DOCX document
36C25019B0057-0002000.docx DOCX document
36C25019B0057-0002002.pdf PDF
36C25019B0057-0002001.docx DOCX document
36C25019B0057-0002002.pdf PDF
36C25019B0057-0002000.docx DOCX document
36C25019B0057-0001001.docx DOCX document
36C25019B0057-0001000.docx DOCX document
36C25019B0057-0001000.docx DOCX document
36C25019B0057-0001001.docx DOCX document
36C25019B0057-005.doc DOC document
36C25019B0057-001.docx DOCX document
36C25019B0057-003.pdf PDF
36C25019B0057-006.pdf PDF
36C25019B0057-002.docx DOCX document
36C25019B0057-002.docx DOCX document
36C25019B0057-003.pdf PDF
36C25019B0057-004.docx DOCX document
36C25019B0057-005.doc DOC document
36C25019B0057-001.docx DOCX document
36C25019B0057-006.pdf PDF
36C25019B0057-000.docx DOCX document
Show all 50

Correct Fire Damper Deficiencies 583-19-502 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Richard L Roudebush VAMC - Fire Damper Testing Project # 583-18-501

Damper Identifier FSD-2-034 Location Waiting Area C-2061 Damper Type Smoke damper Manufacturer Greenheck Style Opposable Blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-22-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA

Damper Identifier SD-1D-020 thru SD-1D-027 Location Unknown, could not find Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-2-026 Location Mechanical Room A-2010 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-2-027

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-2-028

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-2-029

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-2-030

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-2-031 Location Mechanical Room C-2050 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On Damper Picture Yes Access Panel None Condition of Access Panel No access panel Date Tested 5-21-2018 Passed or Failed Could not test Deficiencies / Notes Don’t know how to test. There is a pneumatic actuator.

Damper Identifier SD-2-032

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-2-033 Location Mechanical Room C-2050 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On Damper Picture Yes Access Panel None Condition of Access Panel No access panel Date Tested 5-21-2018 Passed or Failed Could not test Deficiencies / Notes Don’t know how to test. There is a pneumatic actuator.

Damper Identifier SD-2D-018

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-2D-019 thru SD-2D-033

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-3-062 thru SD-3-074

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-3-075 Location Mechanical Room C-3050 Damper Type Smoke Damper Manufacturer Ruskin Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Not on list

Damper Identifier SD-3-076 Location Mechanical Room C-3050 Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-3-077 Location Mechanical Room A-3001 Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-078

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-079

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-080

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-081

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-082

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-083

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-084

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-085

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access door Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-086

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-087

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-088

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Failed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES another method? Pulled smoke alarm relay.

Damper Identifier SD-3-089

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-090

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-091

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-092

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-093

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-094

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-095

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3-096

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-3D-016

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-3D-017

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-3D-019

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-3D-019A

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-3D-020

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-4-001 Location Mechanical Room C-4038 Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-10-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-4-002 Location Mechanical Room C-4038 Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-10-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-4D-018 Location Unknown, not found Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Unknown, not found

Damper Identifier SD-4D-019

Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-4D-021

Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-4D-023

Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-4D-024

Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-5-001 thru SD-5-023 Location Unknown, unable to locate Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018 Passed or Failed Unknown, unable to locate Deficiencies / Notes Unknown, unable to locate

Damper Identifier SD-5-024 Location Mechanical room C-5103 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Failed Deficiencies / Notes Dampers did not change positions. Not on list

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board.

Damper Identifier SD-5-025

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Failed Deficiencies / Notes Dampers did not change positions. Not on list

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board.

Damper Identifier SD-5-026

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Failed Deficiencies / Notes Dampers did not change positions. Not on list

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board.

Damper Identifier SD-5-027 Location Mechanical Room A-5001 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-028

Damper Type Smoke damper Manufacturer Ruskin Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-029

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-030

Damper Type Smoke damper Manufacturer Ruskin Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-031 Location Mechanical Room A-5000 Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? Smoke Detector Relay

Damper Identifier SD-5-032

Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Failed Deficiencies / Notes Damper did not seal shut. Not on list

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-033

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018

Damper Identifier SD-5-034

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018

Damper Identifier SD-5-035

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-8-2018

Damper Identifier SD-5-036 thru SD-5-040

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-9-2018

Damper Identifier SD-5-041

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-9-2018

Damper Identifier SD-5-042

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-043

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-044

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-045

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-046

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-047

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On outside of damper Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes Existing access door is located in between duct work and is hard to access.

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA

Damper Identifier SD-5-048

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-049

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-5-050

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-5-051

Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA

Damper Identifier SD-5-052

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-5-053 thru SD-5-054

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-9-2018

Damper Identifier SD-5-055

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Single Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-5-056 thru SD-5-057

Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-9-2018

Damper Identifier SD-5-058 thru SD-5-059

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-5-060

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes

2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes

Damper Identifier SD-5-061

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-5-062 thru SD-5-064

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-9-2018

Damper Identifier SD-5-065

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-5-066 thru SD-5-068

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-9-2018

Damper Identifier SD-5-069

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-5D-014

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier SD-5D-015

Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel

Unknown, unable to locate

Date Tested 5-7-2018

Damper Identifier SD-5P-001 Location 5th Floor Penthouse Damper Type Smoke damper Manufacturer Ruskin Style Opposable blades Label On access panel Picture Yes Access Panel Latches Only Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-5P-002

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-5P-003

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-5P-004

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-6-001 thru SD-6-025

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel

Unknown, could not find

Date Tested 5-7-2018 Passed or Failed Unknown, could not find Deficiencies / Notes Unknown, could not find

Damper Identifier SD-6-026 Location Mechanical room C-6036 Damper Type Smoke damper Manufacturer Unknown, could not read label Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at DX1.BI4, terminal board location 38 & 39

Damper Identifier SD-6-027 Location Mechanical room A-6144 Damper Type Smoke Damper Manufacturer Ruskin Style Opposable blades Label On access door on bottom side of duct Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-1-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-6-028

Damper Type Smoke Damper Manufacturer Ruskin Style Opposable blades Label On access door on bottom side of duct Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-1-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-6-029

Damper Type Smoke Damper Manufacturer Ruskin Style Opposable blades Label On Access Door Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-1-2018 Passed or Failed Passed…