Richard L Roudebush VAMC - Fire Damper Testing Project # 583-18-501
Damper Identifier FSD-2-034 Location Waiting Area C-2061 Damper Type Smoke damper Manufacturer Greenheck Style Opposable Blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-22-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA
Damper Identifier SD-1D-020 thru SD-1D-027 Location Unknown, could not find Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-2-026 Location Mechanical Room A-2010 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-2-027
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-2-028
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-2-029
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-2-030
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-2-031 Location Mechanical Room C-2050 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On Damper Picture Yes Access Panel None Condition of Access Panel No access panel Date Tested 5-21-2018 Passed or Failed Could not test Deficiencies / Notes Don’t know how to test. There is a pneumatic actuator.
Damper Identifier SD-2-032
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-2-033 Location Mechanical Room C-2050 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On Damper Picture Yes Access Panel None Condition of Access Panel No access panel Date Tested 5-21-2018 Passed or Failed Could not test Deficiencies / Notes Don’t know how to test. There is a pneumatic actuator.
Damper Identifier SD-2D-018
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-2D-019 thru SD-2D-033
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-3-062 thru SD-3-074
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-3-075 Location Mechanical Room C-3050 Damper Type Smoke Damper Manufacturer Ruskin Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Not on list
Damper Identifier SD-3-076 Location Mechanical Room C-3050 Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-3-077 Location Mechanical Room A-3001 Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-078
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-079
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-080
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-081
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-082
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-083
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-084
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-085
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access door Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-086
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-087
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-088
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Failed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? NO
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES another method? Pulled smoke alarm relay.
Damper Identifier SD-3-089
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-090
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-091
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-092
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-093
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-094
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-095
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3-096
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-21-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-3D-016
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-3D-017
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-3D-019
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-3D-019A
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-3D-020
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-21-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-4-001 Location Mechanical Room C-4038 Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-10-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-4-002 Location Mechanical Room C-4038 Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-10-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-4D-018 Location Unknown, not found Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Unknown, not found
Damper Identifier SD-4D-019
Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-4D-021
Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-4D-023
Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-4D-024
Damper Type Smoke damper Manufacturer Unknown, not found Style Unknown, not found Label None Picture No Access Panel Unknown, not found Condition of Access Panel Unknown, not found Date Tested 5-14-2018 Passed or Failed Unknown, not found Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-5-001 thru SD-5-023 Location Unknown, unable to locate Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-8-2018 Passed or Failed Unknown, unable to locate Deficiencies / Notes Unknown, unable to locate
Damper Identifier SD-5-024 Location Mechanical room C-5103 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Failed Deficiencies / Notes Dampers did not change positions. Not on list
1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? NO
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board.
Damper Identifier SD-5-025
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Failed Deficiencies / Notes Dampers did not change positions. Not on list
1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? NO
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board.
Damper Identifier SD-5-026
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Failed Deficiencies / Notes Dampers did not change positions. Not on list
1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? NO
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board.
Damper Identifier SD-5-027 Location Mechanical Room A-5001 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-028
Damper Type Smoke damper Manufacturer Ruskin Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-029
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-030
Damper Type Smoke damper Manufacturer Ruskin Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-031 Location Mechanical Room A-5000 Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? Smoke Detector Relay
Damper Identifier SD-5-032
Damper Type Smoke damper Manufacturer Unknown no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Failed Deficiencies / Notes Damper did not seal shut. Not on list
1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-033
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-8-2018
Damper Identifier SD-5-034
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-8-2018
Damper Identifier SD-5-035
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-8-2018
Damper Identifier SD-5-036 thru SD-5-040
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-9-2018
Damper Identifier SD-5-041
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-9-2018
Damper Identifier SD-5-042
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-043
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-044
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-045
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-046
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-047
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On outside of damper Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes Existing access door is located in between duct work and is hard to access.
1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA
Damper Identifier SD-5-048
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-049
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-5-050
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-5-051
Damper Type Smoke Damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-9-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA
Damper Identifier SD-5-052
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-5-053 thru SD-5-054
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-9-2018
Damper Identifier SD-5-055
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Single Blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-5-056 thru SD-5-057
Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-9-2018
Damper Identifier SD-5-058 thru SD-5-059
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-5-060
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? Yes
2) Did the isolation dampers and or smoke dampers move to the alarm position? Yes
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? Yes
Damper Identifier SD-5-061
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-5-062 thru SD-5-064
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-9-2018
Damper Identifier SD-5-065
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-5-066 thru SD-5-068
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-9-2018
Damper Identifier SD-5-069
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA
2) Did the isolation dampers and or smoke dampers move to the alarm position? NA
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA
Damper Identifier SD-5D-014
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-7-2018
Damper Identifier SD-5D-015
Damper Type Smoke Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 5-7-2018
Damper Identifier SD-5P-001 Location 5th Floor Penthouse Damper Type Smoke damper Manufacturer Ruskin Style Opposable blades Label On access panel Picture Yes Access Panel Latches Only Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-5P-002
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-5P-003
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-5P-004
Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blade Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-14-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through
Damper Identifier SD-6-001 thru SD-6-025
Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel
Unknown, could not find
Date Tested 5-7-2018 Passed or Failed Unknown, could not find Deficiencies / Notes Unknown, could not find
Damper Identifier SD-6-026 Location Mechanical room C-6036 Damper Type Smoke damper Manufacturer Unknown, could not read label Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-8-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at DX1.BI4, terminal board location 38 & 39
Damper Identifier SD-6-027 Location Mechanical room A-6144 Damper Type Smoke Damper Manufacturer Ruskin Style Opposable blades Label On access door on bottom side of duct Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-1-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-6-028
Damper Type Smoke Damper Manufacturer Ruskin Style Opposable blades Label On access door on bottom side of duct Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-1-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES
2) Did the isolation dampers and or smoke dampers move to the alarm position? YES
3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES
Damper Identifier SD-6-029
Damper Type Smoke Damper Manufacturer Ruskin Style Opposable blades Label On Access Door Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-1-2018 Passed or Failed Passed…