36C25019B0057-0009001.pdf

PDF Posted

Attached to
Correct Fire Damper Deficiencies 583-19-502 Federal contract opportunity
Solicitation number
36C25019B0057
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25019B0057 0009 Smoke Dampers Reference Material - Part2.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Correct Fire Damper Deficiencies 583-19-502, newest first.
File Type Posted
36C25019C0300-000.docx DOCX document
36C25019B0057-0010000.docx DOCX document
36C25019B0057-0010000.docx DOCX document
36C25019B0057-0009000.docx DOCX document
36C25019B0057-0009001.pdf PDF
36C25019B0057-0009000.docx DOCX document
36C25019B0057-0008001.pdf PDF
36C25019B0057-0008000.docx DOCX document
36C25019B0057-0008000.docx DOCX document
36C25019B0057-0008001.pdf PDF
36C25019B0057-0007001.pdf PDF
36C25019B0057-0007000.docx DOCX document
36C25019B0057-0006000.docx DOCX document
36C25019B0057-0006001.pdf PDF
36C25019B0057-0006000.docx DOCX document
36C25019B0057-0006001.pdf PDF
36C25019B0057-0005001.pdf PDF
36C25019B0057-0005000.docx DOCX document
36C25019B0057-0005000.docx DOCX document
36C25019B0057-0004000.docx DOCX document
36C25019B0057-0004001.pdf PDF
36C25019B0057-0004001.pdf PDF
36C25019B0057-0004000.docx DOCX document
36C25019B0057-0003001.pdf PDF
36C25019B0057-0003000.docx DOCX document
36C25019B0057-0003001.pdf PDF
36C25019B0057-0003000.docx DOCX document
36C25019B0057-0002001.docx DOCX document
36C25019B0057-0002000.docx DOCX document
36C25019B0057-0002000.docx DOCX document
36C25019B0057-0002001.docx DOCX document
36C25019B0057-0002002.pdf PDF
36C25019B0057-0001000.docx DOCX document
36C25019B0057-0001001.docx DOCX document
36C25019B0057-0001000.docx DOCX document
36C25019B0057-0001001.docx DOCX document
36C25019B0057-004.docx DOCX document
36C25019B0057-005.doc DOC document
36C25019B0057-001.docx DOCX document
36C25019B0057-003.pdf PDF
36C25019B0057-006.pdf PDF
36C25019B0057-002.docx DOCX document
36C25019B0057-001.docx DOCX document
36C25019B0057-006.pdf PDF
36C25019B0057-002.docx DOCX document
36C25019B0057-003.pdf PDF
36C25019B0057-004.docx DOCX document
36C25019B0057-005.doc DOC document
36C25019B0057-000.docx DOCX document
36C25019B0057-000.docx DOCX document
Show all 50

Correct Fire Damper Deficiencies 583-19-502 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Richard L Roudebush VAMC - Fire Damper Testing Project # 583-18-501

Damper Identifier SD-8-033A Location Mechanical room A-8086 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Blades Label On access panel Picture Yes Access Panel Latch only Condition of Access Panel Good Date Tested 4-24-2018 Passed or Failed Failed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board.

Damper Identifier SD-8-034

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Blades Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 4-24-2018 Passed or Failed Failed Deficiencies / Notes Located in the floor of AHU 49

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-8-034A

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Blades Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 4-24-2018 Passed or Failed Failed Deficiencies / Notes Located in the floor of AHU 49

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-8-035

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Blades Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 4-24-2018 Passed or Failed Failed Deficiencies / Notes Easier to access from inside AHU 49

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-8-035A

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Blades Label On access panel Picture Yes Access Panel Hinged Door Condition of Access Panel Good Date Tested 4-24-2018 Passed or Failed Failed Deficiencies / Notes Easier to access from inside AHU 49

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-9-001 Location 9th floor roof Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 4-26-2018 Passed or Failed Failed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NO

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? No smoke detector relay present. Traced wiring and disconnected smoke detector circuit at terminal board location 39 & 40 Not on list

Damper Identifier SD-9-002

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 4-30-2018 Passed or Failed Failed Deficiencies / Notes Return air actuator is unwired. Not on list

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? No

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA.

Damper Identifier SD-9-003

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 4-30-2018 Passed or Failed Failed Deficiencies / Notes Outside air damper actuator is removed from linkage. Not on list

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? NO

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES another method? NA

Damper Identifier SD-9-004 Location Mechanical room C-9062 Damper Type Smoke damper Manufacturer Unknown, no access to damper Style Unknown, no access to damper Label On access panel Picture No Access Panel None Condition of Access Panel Did not have access panel Date Tested 4-30-2018 Passed or Failed Did not test Deficiencies / Notes Unknown where the control panel is to test damper.

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-10-001 Location 10th Floor Roof Damper Type Smoke damper Manufacturer Ruskin Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 4-26-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-10-002

Damper Type Smoke damper Manufacturer Ruskin Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 4-26-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through another method? NA.

Damper Identifier SD-10-003

Damper Type Smoke damper Manufacturer Ruskin Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 4-26-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-10-004

Damper Type Smoke damper Manufacturer Ruskin Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 4-26-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

4) If the test failed, was the test simulated by activating the smoke detector relay or through

Damper Identifier SD-B-001 thru SD-B-004 Location Unknown, could not find Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier FD-B-005 Location Mechanical Room A-B148 Damper Type Fire / Smoke damper Manufacturer Greenheck Style Opposable Blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel

Good

Date Tested 5-24-2018 Passed or Failed Could not test Deficiencies / Notes This damper is attached to AHU 20 which is brand new.

The VA did not have the information on this unit yet to know how to test.

Damper Identifier SD-B-006 thru SD-B-011

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-B-012 Location Corridor CB-6 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-013 Location Corridor CB-6 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-014

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-23-2018 Passed or Failed Failed Deficiencies / Notes Damper did not seal in closed position

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-015

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-016

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-017

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-018

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-23-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-019

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-23-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-020 thru SD-B-028

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-B-029

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-B-030

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Latches only Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-001 thru SD-BD-011

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-BD-012

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-24-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-BD-013 thru SD-BD-019

Damper Type Smoke damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel Unknown, could not find Date Tested 5-22-2018 Passed or Failed Unknown, could not find Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? NA

2) Did the isolation dampers and or smoke dampers move to the alarm position? NA

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? NA

Damper Identifier SD-BD-020 Location Mechanical Room D-B004 Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-021

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-022

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-023

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-024

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-025

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-025A

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-026

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Failed Deficiencies / Notes Damper did not close all the way.

1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-027

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Passed Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-028

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label No Label Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-BD-029

Damper Type Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel Good Date Tested 5-24-2018 Passed or Failed Pass Deficiencies / Notes 1) Did the supply fan, and return fan if equipped, shut down upon the alarm condition? YES

2) Did the isolation dampers and or smoke dampers move to the alarm position? YES

3) Did the Chiller Plant BMS receive a smoke detector alarm in the alarm summary? YES

Damper Identifier SD-P-001 Location 10th floor Damper Type Smoke Damper Manufacturer Unknown Style Fin Label On access panel Picture Yes Access Panel Screwed in place sheet metal Condition of Access Panel

Not good access. Have to remove screws from sheet metal exposing sharp edges.

Date Tested 4-17-2018 Passed or Failed NOT TESTED Deficiencies / Notes Access door should be replaced. Don’t know how to test.

Damper Identifier SD-P-002

Damper Type Smoke Damper Manufacturer Unknown Style Unknown Label On side of duct Picture Yes Access Panel Screwed in place sheet metal Condition of Access Panel

Should have accessible door.

Date Tested 4-17-2018 Passed or Failed NOT TESTED Deficiencies / Notes Should replace sheet metal with access door. Don’t know how to test.

Damper Identifier SD-P-003

Damper Type Smoke Damper Manufacturer Unknown Style Fins Label On access panel Picture Yes Access Panel Screwed in place sheet metal Condition of Access Panel

Should be replaced with accessible door.

Date Tested 4-17-2018 Passed or Failed NOT TESTED Deficiencies / Notes Sheet metal panel is unsafe and should be replaced with accessible door. Don’t know how to test.

SD-8-033A
SD-8-034
SD-8-034A
SD-8-035
SD-8-035A
SD-9-001
SD-9-002
SD-9-003
SD-9-004
SD-10-001
SD-10-002
SD-10-003
SD-10-004
SD-B-001 thru SD-B-004
SD-B-005
SD-B-006 thru SD-B-011
SD-B-012
SD-B-013
SD-B-014
SD-B-015
SD-B-016
SD-B-017
SD-B-018
SD-B-019
SD-B-020 thru SD-B-028
SD-B-029
SD-B-030
SD-BD-001 thru SD-BD-011
SD-BD-012
SD-BD-013 thru SD-BD-019
SD-BD-020
SD-BD-021
SD-BD-022
SD-BD-023
SD-BD-024
SD-BD-025
SD-BD-025A
SD-BD-026
SD-BD-027
SD-BD-028
SD-BD-029
SD-P-001
SD-P-002
SD-P-003

File details come from the government source that posted it. Updated .