Richard L Roudebush VAMC - Fire Damper Testing Project # 583-18-501
Damper Identifier FD-8-044 Location Unknown, unable to locate Damper Type Fire Damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-18-2018 Passed or Failed DID NOT TEST Deficiencies / Notes An old label was found in corridor A-8136. Could not locate the damper though.
Damper Identifier FD-8-045 Location Room A-8026 Damper Type Fire Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinge door Condition of Access Panel
Good
Date Tested 4-30-2018 Passed or Failed Failed Deficiencies Damper did not close all the way.
Damper Identifier FD-8-046
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018 Passed or Failed DID NOT TEST Deficiencies / Notes Unable to locate
Damper Identifier FD-8-047
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8-048 Location Room A-8095 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found.
Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 4-17-2018 Passed or Failed Failed Deficiencies Door did not close all the way. Also use to be spring loaded but springs were cut.
Damper Identifier FD-8-049
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8-050 Location Room A-8024 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel
Good
Date Tested 5-7-2018 Passed or Failed Could not test Deficiencies Fire dampers are out of reach from access panel. Could not be tested. There also appears to be two dampers in this location.
Damper Identifier FD-8D-001
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8D-002
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8D-003
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8D-004
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8D-005 Location Corridor A-8096 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Guillotine Spring Loaded Label On wall below ceiling Picture Yes Access Panel Hinged Door Condition of Access Panel
Good
Date Tested 4-17-2018
Deficiencies Had to cut springs to reopen damper.
Damper Identifier FD-8D-006
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8D-006A
Damper Type Fire damper Manufacturer Unknown, unable to locate Style Unknown, unable to locate Label None Picture No Access Panel Unknown, unable to locate Condition of Access Panel
Unknown, unable to locate
Date Tested 4-19-2018
Damper Identifier FD-8D-007 Location Room A-8116 Damper Type Fire Damper Manufacturer Greenheck Style Single Flap Label On cabinet trim below ceiling Picture Yes Access Panel Hand screw latches Condition of Access Panel
Good
Date Tested 4-17-2018 Passed or Failed Passed Deficiencies None
Damper Identifier FD-8D-008
Damper Type Fire Damper Manufacturer Unknown, no label found Style Fins Label On cabinet trim below ceiling Picture Yes Access Panel Latch only door Condition of Access Panel
Good
Date Tested 4-23-2018
Deficiencies / Notes None
Damper Identifier FD-8D-008A
Damper Type Fire Damper Manufacturer Unknown, no label found Style Fins Label On cabinet trim below ceiling Picture Yes Access Panel Latch only Condition of Access Panel
Good
Date Tested 4-23-2018
Damper Identifier FD-8D-009 Location Room A-8118 Damper Type Fire Damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hand knob screws Condition of Access Panel
Good
Date Tested 4-18-2018
Damper Identifier FD-8D-010 Location Room A-8118 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hand knob screws Condition of Access Panel
Good
Date Tested 4-18-2018 Passed or Failed Pass
Damper Identifier FD-8D-011 Location Room A-8030 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found.
Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged Door Condition of Access Panel
Good
Date Tested 4-23-2018
Deficiencies Damper did not close.
Damper Identifier FD-9-001 Location Mechanical Room C-9062 Damper Type Fire Damper Manufacturer Ruskin MFG. CO.
Style Guillotine Label On access door Picture Yes Access Panel Held in place by latches only.
Condition of Access Panel
Good
Date Tested 4-17-2018 Passed or Failed Failed Deficiencies Could not remove fusible link due to rust and improper installation of link.
Damper Identifier FD-9-002
Damper Type Fire Damper Manufacturer Unknown Style Unknown Label On side of access panel visible from catwalk.
Picture NO Access Panel Latch only Condition of Access Panel
Good
Date Tested 4-17-2018 Passed or Failed NOT TESTED Deficiencies / Notes Unable to access safely to test.
Damper Identifier FD-9-003
Damper Type Fire Damper Manufacturer Ruskin MGF. CO.
Style Guillotine Label On access door Picture Yes Access Panel Held in place by latches only Condition of Access Panel
Good
Date Tested 4-17-2018
Deficiencies
Damper Identifier FD-9-004
Damper Type Fire Damper Manufacturer Ruskin MGF. CO.
Style Guillotine Label On access door Picture Yes Access Panel Held in place by latches only Condition of Access Panel
Good
Date Tested 4-17-2018
Damper Identifier FD-9-005 Location Room C-9027 on blueprint (actual room number is different) Damper Type Fire Damper Manufacturer Ruskin MGF. CO.
Style Guillotine Label On wall below ceiling Picture Yes Access Panel Held in place by latches alone.
Condition of Access Panel
Good
Date Tested 4-17-2018
Damper Identifier FD-9-006 Location Room C-9027 (according to the blueprint, actual Rm# is different) Damper Type Fire Damper Manufacturer Ruskin MGF. CO.
Style Guillotine Label On wall below ceiling Picture Yes Access Panel Held in place by latches alone.
Condition of Access Panel
Good
Date Tested 4-17-2018
Damper Identifier FD-9-007 Location Unknown / Not Found Damper Type Fire Damper Manufacturer Unknown Style Unknown Label None Picture No Access Panel Unknown Condition of Access Panel
Unknown
Date Tested 4-17-2018
Damper Identifier FD-9-008 Location Room C-9094 Damper Type Fire Damper Manufacturer Unknown Style Unknown Label On wall below ceiling Picture NO Access Panel Could not find access panel Condition of Access Panel
Could not find access panel
Date Tested 4-17-2018 Passed or Failed N/A Deficiencies Need to find access panel
Notes Hard ceiling has been cut open with drop ceiling underneath.
Damper Identifier FD-9-009 Location Room C-9093 Damper Type Fire Damper Manufacturer Unknown Not Labeled Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 4-17-2018 Passed or Failed Passed
Notes Hard ceiling has access cut into it with a drop ceiling underneath.
Damper Identifier FD-9-009N Location Unknown Damper Type Unknown Manufacturer Unknown Style Unknown Label None Picture NO Access Panel Unknown Condition of Access Panel
Unknown
Date Tested 4-17-2018
Deficiencies / Notes Unknown, unable to locate
Damper Identifier FD-B-001 Location Elevator Lobby A-B149 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-002 Location Mechanical Room A-B148 Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-003
Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-004
Damper Type Fire damper Manufacturer Ruskin Style Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-005
Damper Type Fire / Smoke damper Manufacturer Greenheck Style Opposable Blades Label On access panel Picture Yes Access Panel Latches Only Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes This is a fire/smoke damper associated with AHU 20 which the VA did not have the information for yet because it is a brand new unit.
Damper Identifier FD-B-006
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Latches Only Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes Damper is too far away from access panel, could not reach to test.
Damper Identifier FD-B-007 Location Corridor CB-6 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-008
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-009
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-010
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Unknown, could not access Label On wall below ceiling Picture No Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes No access to fire damper to test. Utilities blocking access.
Damper Identifier FD-B-011
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Unknown, could not access Label On wall below ceiling Picture No Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Deficiencies / Notes No access to fire damper to test. Utilities blocking access.
Damper Identifier FD-B-012
Damper Type Fire / Smoke damper Manufacturer Unknown, no manufacturer label found Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Deficiencies / Notes Not hooked to an AHU. Not sure how to test.
Damper Identifier FD-B-013 & FD-B-014 Location Unknown, could not find Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel
Unknown, could not find
Date Tested 5-23-2018 Passed or Failed Unknown, could not find Deficiencies / Notes Unknown, could not find
Damper Identifier FD-B-015
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches Only Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-016
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches Only Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-017
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches Only Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-018
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes Access door is small and located to the side. Bigger access door is needed and located on the bottom of duct and centered in duct to allow proper access to test.
Damper Identifier FD-B-019
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes Access door is small and located to the side. Bigger
Damper Identifier FD-B-020
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes Access door is small and located to the side. Bigger
Damper Identifier FD-B-021
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-022
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches only Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-023
Damper Type Fire damper Manufacturer Unknown, no access panel Style Unknown, no access panel Label On wall below ceiling Picture No Access Panel No access panel Condition of Access Panel
No access panel
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes No access panel. Utilities block duct to install access panel.
Damper Identifier FD-B-024
Damper Type Fire damper Manufacturer Unknown, no access panel Style Unknown, no access panel Label On wall below ceiling Picture No Access Panel No access panel Condition of Access Panel
No access panel
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes No access panel. Utilities block duct to install access panel.
Damper Identifier FD-B-025 Location Corridor CB-9 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-026
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-027
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-028 Location Corridor CB-10 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On wall below ceiling Picture Yes Access Panel Latches Only Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-B-029 Location Corridor CB-10 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Unknown, could not get access open Label On wall below ceiling Picture Yes Access Panel Latches Only Condition of Access Panel
Won’t open
Date Tested 5-23-2018
Deficiencies / Notes Access door will not open to allow for testing.
Damper Identifier FD-B-030
Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel
Unknown, could not find
Date Tested 5-23-2018
Damper Identifier FD-BD-001 Location Room D-B003 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On side of damper housing Picture Yes Access Panel None Condition of Access Panel
No access panel
Date Tested 5-22-2018
Deficiencies / Notes Did not close after fire link was removed.
Damper Identifier FD-BD-002 Location Room D-B003 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-22-2018 Passed or Failed Passed Deficiencies / Notes None. Better access by removing diffuser grill inside
Room D-B003
Damper Identifier FD-BD-003 Location Room D-B007 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-22-2018
Damper Identifier FD-BD-004 Location Mechanical Room D-B004 Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-22-2018
Deficiencies / Notes Damper did not close after removing fire link.
Damper Identifier FD-BD-005 Location Room D-B004 Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture No Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Deficiencies / Notes Damper did not close
Damper Identifier FD-BD-006 Location Mechanical Room D-B003 Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-22-2018
Damper Identifier FD-BD-007
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-22-2018
Damper Identifier FD-BD-007A
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-22-2018 Passed or Failed Passed Deficiencies / Notes None
FD-BD-007 is actually two dampers so second one has been identified as FD-BD-007A
Damper Identifier FD-BD-008
Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Unknown, could not access Label On wall below damper Picture Yes Access Panel Unknown, could not access Condition of Access Panel
Unknown could not access
Date Tested 5-23-2018
Deficiencies / Notes Could not access
Damper Identifier FD-BD-009
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-BD-010
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-BD-011
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-BD-011A
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes None
FD-BD-011 was found to be four separate dampers. This one is now identified as FD-BD-011A
Damper Identifier FD-BD-011B
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes None one is now identified as FD-BD-011B
Damper Identifier FD-BD-011C
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes None one is now identified as FD-BD-011C
Damper Identifier FD-BD-012
Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel
Unknown, could not find
Date Tested 5-23-2018
Damper Identifier FD-BD-013 Location Mechanical Room D-B011 Damper Type Fire damper Manufacturer Greenheck Style Opposable Blades Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-BD-014
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hand knob screws Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-BD-014A
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hand knob screws Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes None
FD-BD-014 was found to be four separate dampers. This one is now identified as FD-BD-014A
Damper Identifier FD-BD-014B
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hand knob screws Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes None one is now identified as FD-BD-014B
Damper Identifier FD-BD-014C
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hand knob screws Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Passed Deficiencies / Notes None one is now identified as FD-BD-014C
Damper Identifier FD-BD-015 Location Room D-B009 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-BD-016 Location Room D-B009 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label On access panel Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018
Damper Identifier FD-BD-017
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On Grill Picture Yes Access Panel Screwed on grill Condition of Access Panel
Good
Date Tested 5-22-2018
Damper Identifier FD-BD-018
Damper Type Fire damper Manufacturer Greenheck Style Spring Loaded Guillotine Label On Grill Picture Yes Access Panel Screwed on grill Condition of Access Panel
Good
Date Tested 5-22-2018
Damper Identifier FD-BD-019 Location Room C-B069 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Spring Loaded Guillotine Label No Identifier Picture Yes Access Panel No access panel Condition of Access Panel
No access panel, open to room
Date Tested 5-23-2018 Passed or Failed Passed
Not on list
Damper Identifier FD-BD-020
Damper Type Fire damper Manufacturer Unknown, could not find Style Unknown, could not find Label None Picture No Access Panel Unknown, could not find Condition of Access Panel
Unknown, could not find
Date Tested 5-23-2018
Damper Identifier FD-BD-021 Location Room D-B004 Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Unknown, could not access Label On access panel Picture No Access Panel Hinged door Condition of Access Panel
Good
Date Tested 5-23-2018 Passed or Failed Could not test Deficiencies / Notes Access panel is located too far away from dampers to test. Would have to stand on other duct work, not recommended for safety reasons, also might damage other duct.
Damper Identifier FD-P-001 Location 11th Floor Damper Type Fire Damper Manufacturer Nailor Industries Style Guillotine Label On Access Grill Picture Yes Access Panel Grill screwed in place Condition of Access Panel
Grill is in good condition
Date Tested 4-17-2018
Damper Identifier FD-P-002 Location 11th floor Damper Type Fire Damper Manufacturer Nailor Industries Style Guillotine Label On access door Picture Yes Access Panel Hinged door Condition of Access Panel
Good
Date Tested 4-17-2018
Damper Identifier FD-P-003 Location 11th floor Damper Type Fire Damper Manufacturer Runkin MGF. CO.
Style Guillotine Label On access door Picture Yes Access Panel Hinged Door Condition of Access Panel
Good
Date Tested 4-17-2018
Damper Identifier FD-P-004 Location 10th floor Damper Type Fire Damper Manufacturer Ruskin MGF. CO.
Style Guillotine Label On access door Picture Yes Access Panel Hinged Door Condition of Access Panel
Good
Date Tested 4-17-2018
Damper Identifier FD-P-005 Location 10th floor Damper Type Fire Damper Manufacturer Unknown Style Guillotine Label On access door Picture Yes Access Panel Hinged Door Condition of Access Panel
Good but is located over a hole in the floor. Hard to access safely.
Date Tested 4-17-2018 Passed or Failed Not tested Deficiencies Air Damper blocking access to fire damper. Unable to test.
Damper Identifier FD-P-006 Location 10th Floor Damper Type Fire Damper Manufacturer Ruskin MFG. CO.
Style Guillotine Label No Label Not on list Picture Yes Access Panel Hinge Door Condition of Access Panel
Good
Date Tested 4-17-2018 Passed or Failed Passed Deficiencies / Notes Found fire damper not on the identifier list. This damper is not labled.
Damper Identifier FD-PGLC1 Location Parking Garage Level C Damper Type Fire damper Manufacturer Unknown, no manufacturer label found Style Guillotine Label No label Picture Yes Access Panel Diffuser grill Condition of Access Panel
Good
Date Tested 5-23-2018
| FD-8-044 |
| FD-8-045 |
| FD-8-046 |
| FD-8-047 |
| FD-8-048 |
| FD-8-049 |
| FD-8-050 |
| FD-8D-001 |
| FD-8D-002 |
| FD-8D-003 |
| FD-8D-004 |
| FD-8D-005 |
| FD-8D-006 |
| FD-8D-006A |
| FD-8D-007 |
| FD-8D-008 |
| FD-8D-008A |
| FD-8D-009 |
| FD-8D-010 |
| FD-8D-011 |
| FD-9-001 |
| FD-9-002 |
| FD-9-003 |
| FD-9-004 |
| FD-9-005 |
| FD-9-006 |
| FD-9-007 |
| FD-9-008 |
| FD-9-009 |
| FD-9-009N |
| FD-B-001 |
| FD-B-002 |
| FD-B-003 |
| FD-B-004 |
| FD-B-005 |
| FD-B-006 |
| FD-B-007 |
| FD-B-008 |
| FD-B-009 |
| FD-B-010 |
| FD-B-011 |
| FD-B-012 |
| FD-B-013 & FD-B-014 |
| FD-B-015 |
| FD-B-016 |
| FD-B-017 |
| FD-B-018 |
| FD-B-019 |
| FD-B-020 |
| FD-B-021 |
| FD-B-022 |
| FD-B-023 |
| FD-B-024 |
| FD-B-025 |
| FD-B-026 |
| FD-B-027 |
| FD-B-028 |
| FD-B-029 |
| FD-B-030 |
| FD-BD-001 |
| FD-BD-002 |
| FD-BD-003 |
| FD-BD-004 |
| FD-BD-005 |
| FD-BD-006 |
| FD-BD-007 |
| FD-BD-007A |
| FD-BD-008 |
| FD-BD-009 |
| FD-BD-010 |
| FD-BD-011 |
| FD-BD-011A |
| FD-BD-011B |
| FD-BD-011C |
| FD-BD-012 |
| FD-BD-013 |
| FD-BD-014 |
| FD-BD-014A |
| FD-BD-014B |