36C25018B0803-026.pdf
PDF 8 MB Posted
- Attached to
- Renovate Building 83-2 515-14-108 Federal contract opportunity
- Solicitation number
- 36C25018B0803
About this file
36C25018B0803 515-14-108 Battle Creek 83-2 Patient Privacy BID Drawings_Part4.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25018B0803-0005000.docx | DOCX document | |
| 36C25018B0803-0005001.pdf | ||
| 36C25018B0803-0003001.pdf | ||
| 36C25018B0803-0003000.docx | DOCX document | |
| 36C25018B0803-0002003.zip | ZIP file | |
| 36C25018B0803-027.pdf | ||
| 36C25018B0803-025.pdf | ||
| 36C25018B0803-024.pdf | ||
| 36C25018B0803-022.docx | DOCX document | |
| 36C25018B0803-023.pdf | ||
| 36C25018B0803-000.docx | DOCX document |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
SCALE:
GENERAL POWER NOTES
A. REFER TO ARCHITECTURAL FLOOR PLAN AND ELEVATIONS FOR EXACT LOCATION OF
DEVICES WHERE INDICATED.
B. ALL JUNCTION BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.
C. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED
SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION
TO SUCH EQUIPMENT/DEVICES AS REQUIRED.
D. ALL CONDUITS IN FINISHED SPACES SHALL BE ROUTED CONCEALED UNLESS NOTED
OTHERWISE.
E. PROVIDE A METAL RACEWAY SYSTEM THAT QUALIFIES AS AN EQUIPMENT GROUND
CONDUCTOR IN ACCORDANCE WITH SECTION 250.118 OF THE NEC IN PATIENT CARE
AREAS AS REQUIRED BY SECTION 517.13 OF THE NEC. AN INSULATED EQUIPMENT
GROUND CONDUCTOR SHALL BE PROVIDED IN ADDITION AS INDICATED IN SECTION
517.13 OF THE NEC.
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
GENERAL SCHEDULE NOTES
A. PROVIDE CIRCUIT DIRECTORIES IN ALL ELECTRICAL PANELS AND NAMEPLATES ON
SWITCHBOARDS PER THE SPECIFICATIONS.
B. PROVIDE ARC FLASH CALCULATIONS AND LABELS FOR ALL SWITCHBOARDS,
PANELBOARDS, MOTOR CONTROLLERS, AND CONTROL PANELS PER SECTION 110.16
OF THE NEC AND NFPA 70E. REFER TO THE SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
NOTES:
LIGHTING CONTROL PANEL TO BE PROVIDED WITH RELAYS AND CONTROL INPUTS INDICATED ON THE
CONTROL SCHEDULE. PROVIDE LOCAL KEYPAD PROGRAMMING,, ASTRONOMIC, TIME OF DAY, DAY OF WEEK
AND HOLIDAY SCHEDULING. LIGHTING CONTROL PANEL CHALL BE LEVITON GREENAMX 16 RELAY PANEL OR
EQUAL BY LC&D OR HUBBELL. LIGHTING CONTROL PANEL TO PROGRAMMED AS 'REMOTE' CONTROL.
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
GENERAL ONE-LINE NOTES
A.
ALL JUNCTION AND PULL BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.
B.
PROVIDE\UPDATE CIRCUIT DIRECTORIES IN ALL ELECTRICAL PANELS AND
NAMEPLATES ON SWITCHBOARDS PER THE SPECIFICATIONS.
C. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED
SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION
TO SUCH EQUIPMENT/DEVICES AS REQUIRED.
D.
ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.
E.
PROVIDE ARC FLASH CALCULATIONS AND LABELS FOR ALL SWITCHBOARDS,
PANELBOARDS, MOTOR CONTROLLERS, AND CONTROL PANELS PER SECTION 110.16
OF THE NEC AND NFPA 70E. REFER TO THE SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
1. PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL. CIRCUIT BREAKER TO MATCH
EXISTING EQUIPMENT. SIZE AS INDICATED.
PLAN NOTES
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
| 515.14.108.EP131 |
| Sheets and Views |
| 515.14.108.EP131-ELECTRICAL POWER PLAN - ATTIC LEVEL |
| 515.14.108.EP501 |
| Sheets and Views |
| 515.14.108.EP501-Layout1 |
| 515.14.108.EP502 |
| Sheets and Views |
| 515.14.108.EP502-ELECTRICAL DETAILS |
| 515.14.108.EP601 |
| Sheets and Views |
| 515.14.108.EP601-ELECTRICAL ONE-LINE DIAGRAM |
| 515.14.108.ET001 |
| 515.14.108.TD121 |
| 515.14.108.ET121 |
| 515.14.108.ET131 |
| 515.14.108.EY121 |
| 515.14.108.EY500 |
| 515.14.108.EY501 |
| 515.14.108.EY502 |