36C25018B0803-026.pdf

PDF 8 MB Posted

Attached to
Renovate Building 83-2 515-14-108 Federal contract opportunity
Solicitation number
36C25018B0803
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25018B0803 515-14-108 Battle Creek 83-2 Patient Privacy BID Drawings_Part4.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Building 83-2 515-14-108, newest first.
File Type Posted
36C25018B0803-0005000.docx DOCX document
36C25018B0803-0005001.pdf PDF
36C25018B0803-0003001.pdf PDF
36C25018B0803-0003000.docx DOCX document
36C25018B0803-0002003.zip ZIP file
36C25018B0803-027.pdf PDF
36C25018B0803-025.pdf PDF
36C25018B0803-024.pdf PDF
36C25018B0803-022.docx DOCX document
36C25018B0803-023.pdf PDF
36C25018B0803-000.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

SCALE:

GENERAL POWER NOTES

A. REFER TO ARCHITECTURAL FLOOR PLAN AND ELEVATIONS FOR EXACT LOCATION OF

DEVICES WHERE INDICATED.

B. ALL JUNCTION BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.

C. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED

SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION

TO SUCH EQUIPMENT/DEVICES AS REQUIRED.

D. ALL CONDUITS IN FINISHED SPACES SHALL BE ROUTED CONCEALED UNLESS NOTED

OTHERWISE.

E. PROVIDE A METAL RACEWAY SYSTEM THAT QUALIFIES AS AN EQUIPMENT GROUND

CONDUCTOR IN ACCORDANCE WITH SECTION 250.118 OF THE NEC IN PATIENT CARE

AREAS AS REQUIRED BY SECTION 517.13 OF THE NEC. AN INSULATED EQUIPMENT

GROUND CONDUCTOR SHALL BE PROVIDED IN ADDITION AS INDICATED IN SECTION

517.13 OF THE NEC.

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

GENERAL SCHEDULE NOTES

A. PROVIDE CIRCUIT DIRECTORIES IN ALL ELECTRICAL PANELS AND NAMEPLATES ON

SWITCHBOARDS PER THE SPECIFICATIONS.

B. PROVIDE ARC FLASH CALCULATIONS AND LABELS FOR ALL SWITCHBOARDS,

PANELBOARDS, MOTOR CONTROLLERS, AND CONTROL PANELS PER SECTION 110.16

OF THE NEC AND NFPA 70E. REFER TO THE SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

NOTES:

LIGHTING CONTROL PANEL TO BE PROVIDED WITH RELAYS AND CONTROL INPUTS INDICATED ON THE

CONTROL SCHEDULE. PROVIDE LOCAL KEYPAD PROGRAMMING,, ASTRONOMIC, TIME OF DAY, DAY OF WEEK

AND HOLIDAY SCHEDULING. LIGHTING CONTROL PANEL CHALL BE LEVITON GREENAMX 16 RELAY PANEL OR

EQUAL BY LC&D OR HUBBELL. LIGHTING CONTROL PANEL TO PROGRAMMED AS 'REMOTE' CONTROL.

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

GENERAL ONE-LINE NOTES

A.

ALL JUNCTION AND PULL BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.

B.

PROVIDE\UPDATE CIRCUIT DIRECTORIES IN ALL ELECTRICAL PANELS AND

NAMEPLATES ON SWITCHBOARDS PER THE SPECIFICATIONS.

C. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED

SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION

TO SUCH EQUIPMENT/DEVICES AS REQUIRED.

D.

ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.

E.

PROVIDE ARC FLASH CALCULATIONS AND LABELS FOR ALL SWITCHBOARDS,

PANELBOARDS, MOTOR CONTROLLERS, AND CONTROL PANELS PER SECTION 110.16

OF THE NEC AND NFPA 70E. REFER TO THE SPECIFICATIONS FOR ADDITIONAL

REQUIREMENTS.

1. PROVIDE NEW CIRCUIT BREAKER IN EXISTING PANEL. CIRCUIT BREAKER TO MATCH

EXISTING EQUIPMENT. SIZE AS INDICATED.

PLAN NOTES

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

515.14.108.EP131
Sheets and Views
515.14.108.EP131-ELECTRICAL POWER PLAN - ATTIC LEVEL
515.14.108.EP501
Sheets and Views
515.14.108.EP501-Layout1
515.14.108.EP502
Sheets and Views
515.14.108.EP502-ELECTRICAL DETAILS
515.14.108.EP601
Sheets and Views
515.14.108.EP601-ELECTRICAL ONE-LINE DIAGRAM
515.14.108.ET001
515.14.108.TD121
515.14.108.ET121
515.14.108.ET131
515.14.108.EY121
515.14.108.EY500
515.14.108.EY501
515.14.108.EY502