Renovate Building 83-2 515-14-108 Federal contract opportunity
Solicitation number
36C25018B0803
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25018B0803 515-14-108 Battle Creek 83-2 Patient Privacy BID Drawings_Part1.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Building 83-2 515-14-108, newest first.
File Type Posted
36C25018B0803-0005000.docx DOCX document
36C25018B0803-0005001.pdf PDF
36C25018B0803-0003001.pdf PDF
36C25018B0803-0003000.docx DOCX document
36C25018B0803-0002003.zip ZIP file
36C25018B0803-027.pdf PDF
36C25018B0803-024.pdf PDF
36C25018B0803-026.pdf PDF
36C25018B0803-022.docx DOCX document
36C25018B0803-023.pdf PDF
36C25018B0803-000.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TYPICAL MOUNTING HEIGHTS

MISCELLANEOUS ACCESSORIES, TOILET ACCESSORIES, AND FIXTURES

NOTE 1: MOUNTING HEIGHTS AND CLEARANCES SHOWN ARE PROPOSED FOR ALL ACCESSORIES AND

FIXTURES REQUIRED UNLESS OTHERWISE NOTED OR DIMENSIONED ON DRAWINGS FOR SPECIFIC

CONDITIONS.

*48" A.F.F. MAX

*15" A.F.F. MIN.

SOAP

DISH

SOAP

DISPENSER

SANITARY

NAPKIN

RECEPTACLE

SANITARY

NAPKIN

DISPENSER

SEAT

COVER

DISPENSER

T

Y P

I C

A L

H E

I G

H T

TOWEL

DISPENSER

TOWEL

DISPENSER

AND WASTE

RECEPTACLE

(B.F. DENOTES BARRIER

FREE REQUIREMENTS)

M

I N

WASTE

RECEPTACLE

T

Y P

I C

A L

H

E I G

H T

T

Y P

I C

A L

H E

I G

H T

HOOKS SHELF (ABOVE)

MAIL SLOT (BELOW)

TOWEL BAR

AND SHELF

TOWEL BAR B.F. SHELF OR

PURSE SHELF

BARRIER FREE

HOOKS

*48" A.F.F. MAX.

*15" A.F.F. MIN.

*OPERABLE CONTROLS SHALL FALL WITHIN

FORWARD APPROACH REACH RANGES

REQUIRED BY CODE REGULATIONS

CUP

DISPENSER

FACIAL TISSUE

DISPENSER

HAND DRYER

M

A X

M

A X

C

L

C CONTROLS

L

C

L

CONTROLS

*15" A.F.F. MIN.

*48" A.F.F. MAX.

BOTTOM OF

OUTLET

LIGHT

SWITCH

FIRE ALARM PULL

BOX (Above)

DUPLEX OUTLET

(B.F./STANDARD

HEIGHT) (Below)

THERMOSTAT ELEVATOR

PUSH

BUTTONS

ELECTRIC DUPLEX,

TELEPHONE, OR T.V. OUTLET

WITH LIGHT SWITCH

B

F

M A

X

TOILET

PAPER

HOLDER

TOILET

TISSUE

DISPENSER

M

I N

M

A X

1'-6"

(MIN.)

1'-5" (MIN.)

ADA

1'-6" MAX

1'-6" MIN

3" (MAX.)

8" CLEAR (MIN.)

M

A X

M

I N

LINE OF WALL

LAVATORY

VANITY

2'-6"

(B.F. MIN.)

M

I N

B

F

M

X

1'-3"

LINE OF WALL

ELEC. OUTLET

(SEE NOTE BELOW)

NOTE: ANY ELECT. OUTLET

NEAR SINKS IN B.F.. TOILET

ROOMS TO BE MOUNTED

33" TO 36" A.F.F. TO C

L

LAVATORY

L

C

L

C

L

C

L

C

L

C

L

C

L

C

L

C

F

R A

M E

2'-0"

2'-0"

2'-6"

(MIN)

M

I N

2'-6"

(MIN)

M

I N

M

I N

30" X 48"

CLEAR

30" X 24"

CLEAR

M

I N

M

A X

M

I N

PHYSICAL

OBSTRUCTION

DEEPER THAN 24"

EQ EQ

B

F

M

I N

1'-8"

(B.F. MIN.)

B

F

M

I N

FULL LENGTH

MIRROR AND

BARRIER FREE

MIRRORS

MIRROR SIZE AS

SPECIFIED OR

NOTED.

FRAMED MIRROR

(MFR'S STANDARD

SIZE AS SHOWN ON

DWG)

FRAMED MIRROR

(MFR'S STANDARD

SIZE AS SHOWN ON

DWG)

SURFACE MOUNTED

LIQUID SOAP

DISPENSER

STAINLESS STEEL

UTILITY SHELF

(LENGTH AS SHOWN

ON DWGS)

M

I N

D A

B

F

M

I N

HIGHEST

OPERABLE PART

DOOR

HARDWARE

LOCKSET/

LATCHSET

LOCATION

C HARDWARE -

KNOB OR

LEVER (B.F.)

L

FIRE

EXTINGUISHER

CABINET

FIRE

VALVE

CABINET

FIRE HOSE

RACK OR

VALVE

FIRE EXTINGUISHER

AND WALL BRACKET

B F

H A

N D

L E

H E

I G

H T

UTILITY SHELF

3'-0"3'-0"

M

I N

MOP RACK COAT

ROD AND

HAT

SHELF

(Above)

BOOT

RACK

(Below)

M

A X

I M

U M

WIDTH VARIES

(REFER TO

PLAN

DWGS)

WALL LINE

WHERE

INDICATED

ELECTRIC

PANEL

S

T D

S

T D

M

A X

1'-3"

(MAX.)

M

I N

B

F

M A

X

FOLDED

POSITION

SHOWER C

L

5'-0" MIN. LENGTH

HOSE WITH HAND HELD

OR ADJUSTABLE SPRAY

UNIT ON BAR

WALL LINE

NOTE: B.F. CONTROLS

ARE MOUNTED WITH-IN

THIS AREA

T

Y P

I C

A L

C.O. COVER

LINE OF

WALL BASE

B.F. SHOWER

SEAT

SHOWER

HEAD AND

VALVES

BARRIER FREE HAND

HELD SHOWER HEAD

AND CONTROLS

WALL C.O.

L

C

M

A X

T O

S

H E

L F

N

C

B

I N

E T

BARRIER FREE

MEDICINE

CABINET

MEDICINE

CABINET

STAINLESS STEEL

SHOWER CURTAIN HOOK (BY VA)

SHOWER CURTAIN ROD

(LENGTH AS SHOWN ON

DWGS)

VINYL SHOWER CURTAIN

(BY VA)

SHOWER CURTAIN

TOWEL PIN

GRAB

BAR

SHOWER STALL AND ACCESSORIES

TOILET AND JANITOR ACCESSORIES

ELECTRICAL ACCESSORIES

SAFETY AND FIRE PROTECTION ACCESSORIESMISCELLANEOUS ACCESSORIES

LAVATORY

M

I N

8"

6"

B

F

M

A X

LINE OF OBSTRUCTION

MIRROR SIZE AS

SPECIFIED OR NOTED

BOTTOM OF

REFLECTING SURFACE

REQUIRED KNEE SPACE

CLEAR TO 8" DEPTH MIN

MISCELLANEOUS ACCESSORIES AND CABINETS

5'-0"

(MIN)

M

I N

M

I N

3'-10"

(CLEAR)

M

I N

FLUSH VALVE

CLEAR GRAB BAR

CLEAR BELOW

GRAB BAR

STAINLESS

STEEL GRAB BAR

1'-0" 3'-6" (MIN.)

G.B.

1 1/2" 1 1/2"

7"-9" (TYP.)

FROM LIP OF

W.C. TO T.P.H

LINE OF WALL

SANITARY NAPKIN

DISPOSAL

INSTALLED FORWARDS

OF W.C. LIP

BARRIER FREE WATER CLOSETS

39" - 41"

STAINLESS STEEL GRAB BAR

3'-0"

(MAX)

3'-0"

6"

HANDRAIL

1'-0" TYP

HANDRAIL

EXTENSION

1'-11" AT BOTTOM OF

STAIRS ONLY

LINE OF RISER

OR END OF

RAMP

RESIDENT ROOM WATER CLOSETS

3'-6"

(MIN)

1'-0"

LINE OF WALL

2'-0"

8" 1'-4" 1'-4"

CLEAR SPACE

AT TOILET

M

I N

5'-8"

(CLEAR)

2'-8"

1'-4" 1'-4" 1'-4"

CLEAR SPACE

AT BARIATRIC

TOILET

FOLD-UP

GRAB

BARS

2'-8"

1'-4" BARIATRIC

1'-4" 1'-4"

1'-10"

(MIN)

LINE OF WALL

M

I N

2'-8"

UP-SWINGING

GRAB BARS

TOILET PAPER

DISPENSER

6"

(MIN)

BARIATRIC

S

N

K

R

I M

C

L

5'-0"

(MIN)

SHOWER

HEAD

C

L

C

L

STAINLESS STEEL

GRAB BAR

STAINLESS

STEEL GRAB

BAR

FLOOR

DRAIN

ROLL-IN

SHOWER CHAIR

2'-2"±

(4) 3/8" Ø ANCHOR

BOLTS

1 1/4" DIA S.S. UP SWINGING

GRAB BAR SCH. 40

SIDE ELEVATION OF UP-SWINGING GRAB BAR

HINGE PIN

F

I N

F

L

FULLY SPRINKLERED

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

FLOOR RUNNER TRACK

BOTTOM OF STRUCTURE

SLIP LEG TRACK

METAL STUDS AT

16" ON CENTER

TOP OF FLOOR

GYPSUM BOARD - 3 5/8" METAL STUD

1-HOUR RATED PARTITION UL. # U465

3 5/8" METAL STUD (UNLESS NOTED

OTHERWISE)

TOP OF FLOOR

FLOOR RUNNER

TRACK

(1) LAYER 5/8"

TYPE "X" GYPSUM

BOARD (EACH SIDE)

CEILING LINE

SLIP LEG TRACK

CEILING LINE

FIRE RATED JOINT SYSTEM

"A2" = 4 7/8""A1" = 4 7/8"

"A4" = 6 3/4"

"A5"" = 9 1/4"

BOTTOM OF STRUCTURE

METAL STUDS AT

16" ON CENTER

CONTINUOUS

FIRESTOP SEALANT

EACH SIDE

3 1/2" SOUND ATTENUATION

INSULATION

A1

(1) LAYER 5/8"

TYPE "X" GYPSUM

BOARD (EACH SIDE)

3 1/2" SOUND ATTENUATION

INSULATION

CONTINUOUS FIRESTOP

SEALANT EACH SIDE

A2

FLOOR RUNNER TRACK

BOTTOM OF STRUCTURE

SLIP LEG TRACK

METAL STUDS AT

24" ON CENTER

TOP OF FLOOR

"A3" = 10" (UNLESS

NOTED OTHERWISE)

3 1/2" SOUND ATTENUATION

INSULATION

(1) LAYER 5/8"

TYPE "X" GYPSUM

BOARD (EACH SIDE)

CEILING LINE

ACOUSTICAL GYP. BD. - 3 5/8" METAL STUD

55 STC

A3

2-HOUR RATED PARTITION UL. # U411

3 5/8" METAL STUD

FLOOR RUNNER

TRACK

(2) LAYER 5/8"

TYPE "X" GYPSUM

BOARD (EACH SIDE)

CEILING LINE

SLIP LEG TRACK

FIRE RATED JOINT SYSTEM

"B1" = 6 1/8"

BOTTOM OF STRUCTURE

METAL STUDS AT

16" ON CENTER

3 1/2" SOUND ATTENUATION

INSULATION

CONTINUOUS FIRESTOP

SEALANT EACH SIDE

B1

FLOOR RUNNER TRACK

BOTTOM OF STRUCTURE

METAL STUDS AT

16" ON CENTER

TOP OF FLOOR

GYPSUM BOARD - 2 1/2" METAL STUD

CEILING LINE

"C2" = 5 1/4"

"C3" = 4 1/8"

"C4" = 7 1/8"

C3

(1) LAYER 5/8"

TYPE "X" GYPSUM

BOARD (EACH SIDE)

GYPSUM BOARD - 5 1/2" METAL STUDC4

EXISTING CONSTRUCTION

FLOOR RUNNER TRACK

BOTTOM OF STRUCTURE

SLIP LEG TRACK

METAL STUDS AT

16" ON CENTER

TOP OF FLOOR

GYPSUM BOARD - 3 5/8" METAL STUD

CEILING LINE

"S2" = 4 1/4"

S2

(1) LAYER 5/8"

TYPE "X" GYPSUM

BOARD

FLOOR RUNNER TRACK

BOTTOM OF STRUCTURE

METAL STUDS AT

16" ON CENTER

TOP OF FLOOR

GYPSUM BOARD - 7/8" METAL FURRING

CEILING LINE

"S1" = 1 1/2"

S1

(1) LAYER 5/8"

TYPE "X" GYPSUM

BOARD

EXISTING CONSTRUCTION

PARTITION TYPE LEGEND

FLOOR RUNNER TRACK

BOTTOM OF STRUCTURE

SLIP LEG TRACK

METAL STUDS AT

16" ON CENTER

TOP OF FLOOR

GYPSUM BOARD - 2 1/2" METAL STUD

CEILING LINE

"C5" = 3 1/8"

C5

(1) LAYER 5/8"

TYPE "X" GYPSUM

BOARD (EACH SIDE)

3 1/2" SOUND ATTENUATION

INSULATION

TOP OF FLOOR

CONTINUOUS

FIRESTOP SEALANT

EACH SIDE

GYPSUM BOARD - 5 1/2" METAL STUDA4

VAPOR BARRIER

1" AIR SPACE

GYPSUM BOARD - 3 5/8" METAL STUDC2

SOUND ATTENUATION

INSULATION

UP SWING GRAB BAR DETAILS

NOT TO SCALETYP

F1

ABBREVIATION LEGEND

ADA AMERICAN DISABILITY ASSOCIATION

A.F.F. ABOVE FINISHED FLOOR

BET BETWEEN

B.F. BARRIER FREE

CG CORNER GUARD

CL CENTER LINE

C.O. CLEAN OUT

DIA DIAMETER

D.W. DISHWASHER

DWG DRAWING

G.B GRAB BAR

GYP. GYPSUM

GYP. BD GYPSUM BOARD

EXIST EXISTING

EG END GUARD

EQ EQUAL

FEC FIRE EXTINGUISHER CABINET

FD FLOOR DRAIN

FIN. FL. FINISHED FLOOR

FRT FIRE RETARDANT TREATED

HM HOLLOW METAL

MAX. MAXIMUM

MET. METAL

MIN. MINIMUM

N.I.C. NOT IN CONTRACT

O.C. ON CENTER

OH OPPOSITE HAND

RE: REFER TO

REF REFRIGERATOR

REQ'D REQUIRED

R.O. ROUGH OPENING

M.O. MASONRY OPENING

SIM SIMILAR

S.S. STAINLESS STEEL

T.P.H. TOILET PAPER HOLDER

TV TELEVISION

TYP TYPICAL

U.N.O. UNLESS NOTED OTHERWISE

VA VETERANS AFFAIRS

W/ WITH

WD WOOD

W.W. WATER CLOSET

WALLBD WALL BOARD

GYPSUM BOARD - 8" METAL STUDA5 T-1 1-HR RATED TEMPORARY PARTITION #U465

EXCEPT OMIT SOUND ATTENUATION

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

W

D

FIREPLACEFIREPLACE

TV

BEVERAGE

STATION

BEVERAGE

STATION

E TO F PATH TO

EXIT ACCESS

NFPA 101 18.2.5.7.2.4

90'-4" (100'-0"

ALLOWED)

SLEEPING SUITE

NFPA101 18.2.5.7.2

4,878 SF

2 EXITS REQUIRED

2-HOUR BARRIER

G TO H PATH OF TRAVEL

TO SMOKE BARRIER

169'-0" (200'-0" ALLOWED)

1-HOUR RATED FIRE

BARRIER

2-HOUR FIRE BARRIER

EXISTING STAIR 2-HOUR

NFPA101 8.6.5

EXIT AT WALK-OUT

BASEMENT LEVEL

NON-SLEEPING SUITE

NFPA101 18.2.5.5.2

1,166 SF

1 EXIT ALLOWED

C TO D PATH TO EXIT ACCESS

NFPA 101 18.2.5.3

76'-0" (100'-0" ALLOWED)

EXISTING STAIR 2-HOUR

NFPA101 8.6.5

EXIT AT WALK-OUT

BASEMENT LEVEL

2-HOUR RATED FIRE BARRIER

1-HOUR RATED SMOKE

BARRIER

1-HOUR RATED SMOKE

BARRIER

EXISTING ELEVATOR SHAFT

2-HOUR RATED

NFPA101 TABLE 8.3.4.2

1-HOUR RATED FIRE BARRIER

A TO B PATH TO EXIT ACCESS

NFPA 101 18.2.5.7.2.4

92'-0'' (100'-0'' ALLOWED)

SLEEPING SUITE

NFPA101 18.2.5.7.2

5,048 SF

2 EXITS REQUIRED

EXISTING STAIR 2-HOUR

NFPA101 8.6.5

EXIT AT WALK-OUT BASEMENT LEVEL

2-HOUR FIRE

BARRIER

1-HOUR RATED FIRE

BARRIER

1-HOUR RATED FIRE

BARRIER

J TO H PATH OF TRAVEL TO SMOKE

BARRIER 187'-0'' (200'-0'' ALLOWED)

1-HOUR RATED FIRE

BARRIER

EXISTING STAIR 2-HOUR

NFPA101 8.6.5

EXIT AT WALK-OUT

BASEMENT LEVEL

2-HOUR FIRE BARRIER

EXISTING

2-HOUR RATED

SHAFT

EXISTING

2-HOUR RATED

SHAFT

EXISTING 2-HOUR

RATED SHAFT

EXISTING

2-HOUR RATED

SHAFT

EXISTING

2-HOUR RATED

SHAFT

EXISTING

2-HOUR RATED

SHAFT

EXISTING

2-HOUR RATED

SHAFT

EXISTING

2-HOUR RATED

SHAFT

EXISTING STANDPIPE

NORTH

DINING

BEDROOM-

BARIATRIC

CHARTING

EXIST.

STAIR

S2-2

BATH

256A

BATH

245A

EXIST.

STAIR

S2-3

BEDROOM

N E

P A

R L

O R

D

E N

BATH

221A

BEDROOM

BATH

214A

MEDS/MED

SELECT

B A

T H

A

BATH

253A

SUITE

PASSAGE

C25

UNIT

COORDINATOR

LOCKER

ROOM

BATH

254A

CHARTING

BATH

243A

BEDROOM

CORRIDOR

C22

EXIST.

ELEVATOR

P2-1

CORRIDOR

C23

STAFF

LOUNGE

SUITE

PASSAGE

C31

EXIST.

STAIR

S1-1

NORTH KITCHEN

ELECTRICAL

BATH

227A

BEDROOM

BEDROOM

EXIST.

STAIR

S2-4

NW

PARLOR

BATH

208A

CLEAN UTL.

BEDROOM

SOILED UTL/

HOLDING

BEDROOM

CORRIDOR

C32

BEDROOM

BEDROOM

MULTI-PURPOSE

ROOM

OFFICE

EQUIPMENT

STORAGE

SHOWER RM

TOILET

OFFICE

STAFF

TOILET

234A

OFFICE

SUITE

PASSAGE

C35

BEDROOM-

BARIATRIC

BEDROOM

SE

PARLOR

ELECTRICAL

BEDROOM

MEDS/MED

SELECT

SW

PARLOR/DEN

CLOSET

BEDROOM

SOUTH KITCHEN

SOUTH

DINING

LIVING

ROOM

CHARTING

CLEAN

LINEN

HAC

CLOSET

CLEAN

LINEN

CHARTING

SUITE

PASSAGE

C27

LIVING

ROOM/DEN

SUITE

PASSAGE

C29

BEDROOM-

BARIATRIC

SUITE

PASSAGE

C38

CONFERENCE

ROOM

CORRIDOR

C33

C O

R R

I D

O R

C

BATH

215A

LAUNDRY

HAC

B A

T H

A

BATH

220A

ELEV.

LOBBY

CORRIDOR

C26

C O

R R

I D

O R

C

C O

R R

I D

O R

C

HAC

STOR.

C O

R R

I D

O R

C

C O

R R

I D

O R

C

SUITE

PASSAGE

C34

STORAGE

CLOSET

CLOSET

203A

BATH

257A

BATH

236A

CEN. MEDICAL

SUPPLY

EXISTING STANDPIPE

EXISTING 2-HOUR

RATED SHAFT

EXISTING

STANDPIPE

EXISTING STANDPIPE

EXISTING 2-HOUR

RATED SHAFT

EXISTING 2-HOUR

RATED SHAFT

SMOKE PARTITION

SMOKE PARTITION

SMOKE PARTITION

1-HOUR RATED

FIRE BARRIER

W

D

NORTH

DINING

BEDROOM-

BARIATRIC

CHARTING

EXIST.

STAIR

S2-2

BATH

256A

BATH

245A

EXIST.

STAIR

S2-3

BEDROOM

N E

P A

R L O

R D

E N

BATH

221A

BEDROOM

BATH

214A

MEDS/MED

SELECT

B A

T H

A

BATH

253A

SUITE

PASSAGE

C25

UNIT

COORDINATOR

LOCKER

ROOM

BATH

254A

CHARTING

BATH

243A

BEDROOM

CORRIDOR

C22

EXIST.

ELEVATOR

P2-1

CORRIDOR

C23

STAFF

LOUNGE

SUITE

PASSAGE

C31

EXIST.

STAIR

S1-1

NORTH KITCHEN

ELECTRICAL

BATH

227A

BEDROOM

BEDROOM

EXIST.

STAIR

S2-4

NW

PARLOR

BATH

208A

CLEAN UTL.

BEDROOM

SOILED UTL/

HOLDING

BEDROOM

CORRIDOR

C32

BEDROOM

BEDROOM

MULTI-PURPOSE

ROOM

OFFICE

EQUIPMENT

STORAGE

SHOWER RM

TOILET

OFFICE

STAFF

TOILET

234A

OFFICE

SUITE

PASSAGE

C35

BEDROOM-

BARIATRIC

BEDROOM

SE

PARLOR

ELECTRICAL

BEDROOM

MEDS/MED

SELECT

SW

PARLOR/DEN

CLOSET

BEDROOM

SOUTH KITCHEN

SOUTH

DINING

LIVING

ROOM

CHARTING

CLEAN

LINEN

HAC

CLOSET

CLEAN

LINEN

CHARTING

SUITE

PASSAGE

C27

LIVING

ROOM/DEN

SUITE

PASSAGE

C29

BEDROOM-

BARIATRIC

SUITE

PASSAGE

C38

CONFERENCE

ROOM

CORRIDOR

C33

C O

R R

I D

O R

C

BATH

215A

LAUNDRY

HAC

B A

T H

A

BATH

220A

ELEV.

LOBBY

CORRIDOR

C26

C O

R R

I D

O R

C

C O

R R

I D

O R

C

HAC

STOR.

C O

R R

I D

O R

C

C O

R R

I D

O R

C

SUITE

PASSAGE

C34

STORAGE

CLOSET

CLOSET

203A

BATH

257A

BATH

236A

CEN. MEDICAL

SUPPLY

FULLY SPRINKLERED

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

CORRIDOR

SLEEPING SUITE

NFPA 101 18.2.5.5.1

NON-SLEEPING SUITE

NFPA101 18.2.5.5.2

ROOM NAME

128 SF

ROOM TAG

EXISTING WALL

NEW WALLS

2 HOUR FIRE BARRIER (EXISTING)

EXTEND WALL TO UNDERSIDE OF DECK ABOVE,

PROVIDE 90 MINUTE LABEL DOORS WITH CLOSURES.

PROVIDE FIRE/SMOKE DAMPERS AT DUCTWORK

PENETRATIONS AS REQUIRED BY CODE. PROVIDE

FIRESTOPPING ALL AROUND ALL PENETRATIONS

THROUGH WALLS. PROVIDE 2-HOUR FIRESTOPPING

AT GAP BETWEEN WALL AND DECK ABOVE.

1 HOUR FIRE BARRIER (NEW)

EXTEND WALL TO UNDERSIDE OF DECK ABOVE,

PROVIDE 45 MINUTE DOORS WITH CLOSERS.

PROVIDE DAMPERS AT DUCTWORK PENETRATIONS

AS REQUIRED BY CODE. PROVIDE FIRESTOPPING

AROUND ALL PENETRATIONS THROUGH WALLS.

PROVIDE 1-HOUR FIRESTOPPING AT GAP BETWEEN

THE WALL AND DECK ABOVE.

SMOKE BARRIER (NEW)

1-HOUR RATED WALL - EXTEND WALL TO

UNDERSIDE OF DECK ABOVE. PROVIDE 20 MINUTE

LABELED DOORS WITH CLOSER. CROSS

CORRIDOR DOORS SHALL SWING IN OPPOSITE

DIRECTIONS. VISION PANEL REQUIRED. LATCHING

IS NOT REQUIRED. PROVIDE FIRE DAMPERS AT

DUCTWORK PENETRATION AND FIRESTOPPING

AT ALL GAPS AROUND PENETRATIONS THROUGH

WALL. PROVIDE FIRE STOPPING IN GAPS

BETWEEN WALL AND DECK ABOVE.

LEGEND

NOTE: ALL BUILDING FLOORS SHALL HAVE 1-HOUR FIRE RESISTANCE RATING AND 2-HOUR FIRE RESISTANCE RATING

AT STRUCTURAL FRAMING SUPPORTING 2-HOUR RATED SHAFTS (ELEVATOR, STAIR, DUCT, PIPE, ETC.) PROVIDE

DAMPERS AT DUCTWORK PENETRATIONS. PROVIDE FIRESTOPPING AT ALL GAPS AROUND PENETRATIONS.

MEANS OF EGRESS

NORTH

SECOND FLOOR LIFE SAFETY PLAN

1/8" = 1'-0"GI101

F1

PATH OF TRAVEL

LIFE SAFETY INFORMATION

Code Review

Building 83

Occupancy: NFPA Healthcare - Nursing Home

IBC: Institutional Group I-2

No. of Stories:2 + Basement and Attic

Construction Class: NFPA 220 Type II (111) ( IBC Construction Type II-A)

Owner: US Department of Veterans Affairs

Life Safety Code: NFPA-101 2015 governs with ICC International Building code 2015 subordinate to it.

Section 1 Prevailing Codes

Life Safety Code: NFPA-101 2015 edition.

Building Code: ICC International Building Code - 2015 edition.

Mechanical Code: ICC International Mechanical Code - 2015 edition

Plumbing Code: ICC International Plumbing Code - 2015 edition

Electrical Code: National Electric Code - 2014 edition

Energy: ASHRAE 90.1 - 2007 edition

Accessibility: ABAAS

Section 2 Basic Building Information

Incidental Uses: Accessory Business and Storage Uses

Fire Protection: The existing building is fully sprinklered. Sprinkler system required to comply with NFPA 13.

Rehabilitation: NFPA 101: a major rehabilitation concerns the modification of more than 50% of the smoke compartment.

Element Supporting Fire Rating Used on Project UL Assembly

Bearing Walls Floor 1 N N/A

Roof 1 N N/A

Columns Floor 1 Existing Concrete

Roof 1 Existing Concrete

Slab/Beams Floor 1 Existing Concrete K917

Roof 1 Existing Concrete K917

Existing Floor/Ceiling Assemblies 1 N N/A

New Floor Assembly 1 Y P714

Roof/Ceiling Assemblies 1 N N/A

Non-Bearing Walls Exterior or Interior 0 Y None Required

Height and Area limitations:

NFPA 101-2015 Table 19.1.6.1 - 3 Stories

IBC Table 504.3 Allowable Height: 3 stories, 85 Feet

Allowable Area: 45,000 Square Feet

Actual height: 2 stories + Attic mechanical space

The highest occupied floor is 22 feet above grade. This building is not classified as high-rise construction.

Floor Area Existing New

First Floor: 18.252 sq. ft. ~

Second Floor: 18,252 sq. ft. ~

Total: 36,504 sq. ft. ~

Section 3 Occupant Load

Existing Area New Area Load Factor Occupant Total

Second Floor

Nursing Home Use 15,081 sf N/A 1:120 sf 126

Office Use 1,151 sf N/A 1:100 sf 12

Mechanical/Electrical/ 862 sf N/A 1:500 sf 2

Storage

Total Building Occupant Load 140 people

Note: Above occupant loads are calculated on gross floor area

Section 4 Exits

Exits required based on Occupant load:

For occupant loads less than 50: 1

For occupant loads between 50 and 500: 2

For occupant loads between 501 and 1000: 3

Exits Required Existing Exits New Exits Totals

Second Floor: 2 4 N/A 4

Floor Exit Stairs Grade Exits Total Floor OL OL / Exit

2 4 0 4 144 36

Exit Capacity:

Allowable exit capacity for egress components NFPA-101 Table 7.3.3.1

Doors: .2 inches per occupant

Corridors: .2 inches per occupant

Stairs: .3 inches per occupant

Stair Capacity and Apportioned Occupant Load

Stair 2nd Floor OL Load Factor Req'd Width

1 36 .3 10.8 in.

2 36 .3 10.8 in.

3 36 .3 10.8 in.

4 36 .3 10.8 in.

All stairs meet or exceed the 36 inch minimum required width

Re:NFPA-101 2015 7.2.2.2.1.2 (A)

Section 5 Exit Access and Travel Distance:

With Approved Automatic Sprinkler System

Travel Distance to Exits: 200 feet

Common Path of Travel: 100 feet

Maximum Dead End Corridor: 30 feet NFPA 19.2.5.2

Existing dead end corridors in excess of 20 feet shall be permitted to continue in use if it is impractical and infeasible to alter them.

Section 6 Miscellaneous Provisions

Corridor Width: 96 inches where serving as access to sleeping rooms.

NFPA 101, SECTION 4.6.7.5

48 inches where serving as a means of egress from sleeping rooms

44 inches where not intended for housing, treatment, or use of inpatients

*where corridors are 6 feet or more in width, 6 inches maximum projections above handrail height are permitted

Fire Rated Assemblies:

Exit Stairs: 2 hour enclosures.

Elevators: 2 hour enclosures.

Shafts: 2 hour enclosures.

Smoke Compartment: 30 patients maximum, 22,500 sf maximum NFPA 19.3.7.1.

Corridors: With automatic sprinkler system - Smoke partition only NFPA 19.3.6.2.2

Horizontal Exit: 2 hour enclosure

FIRE EXTINGUISHER

CABINET

SMOKE COMPARTMENT #2

6,832 SF

SMOKE COMPARTMENT #1

9,463 SF

SMOKE COMPARTMENT KEY PLAN

NOT TO SCALE

1-HR RATED SMOKE

BARRIER ASSEMBLY

1-HOUR RATED SMOKE BARRIER

SMOKE PARTITION EXTEND WALL TO UNDERSIDE

OF DECK ABOVE. PROVIDE 20 MIN. FIRE RATED

DOOR WITH CLOSER.

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

GI100 LIFE SAFETY INFORMATION AND ADA TYPICAL MOUNTING HEIGHTS
Sheets and Views
GI100 LIFE SAFETY INFORMATION AND ADA TYPICAL MOUNTING HEIGHTS
GI101 SECOND FLOOR LIFE SAFETY PLAN, CODE INFORMATION
Sheets and Views
GI101 SECOND FLOOR LIFE SAFETY PLAN, CODE INFORMATION
HA121 SECOND FLOOR ASBESTOS ABATEMENT PLAN
Sheets and Views
HA121 SECOND FLOOR ASBESTOS ABATEMENT PLAN
AD121 SECOND FLOOR DEMOLITION PLAN
AE121 OVERALL SECOND FLOOR PLAN
AE221 SECOND FLOOR REFLECTED CEILING PLAN
Sheets and Views
AE221 SECOND FLOOR REFLECTED CEILING PLAN
AE421 ENLARGED FLOOR PLANS AND INTERIOR ELEVATIONS
Sheets and Views
AE421 ENLARGED FLOOR PLANS AND INTERIOR ELEVATIONS
AE422 ENLARGED FLOOR PLANS AND INTERIOR ELEVATIONS
Sheets and Views
AE422 ENLARGED FLOOR PLANS AND INTERIOR ELEVATIONS
AE423 ENLARGED FLOOR PLANS AND INTERIOR ELEVATIONS
AE424 ENLARGED FLOOR PLANS AND INTERIOR ELEVATIONS
Sheets and Views
AE424 ENLARGED FLOOR PLANS AND INTERIOR ELEVATIONS

AE431 ENLARGED BUILT-UP BATHROOM FLOOR PLANS