36C25018B0803-024.pdf
PDF 15 MB Posted
- Attached to
- Renovate Building 83-2 515-14-108 Federal contract opportunity
- Solicitation number
- 36C25018B0803
About this file
36C25018B0803 515-14-108 Battle Creek 83-2 Patient Privacy BID Drawings_Part3.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25018B0803-0005001.pdf | ||
| 36C25018B0803-0005000.docx | DOCX document | |
| 36C25018B0803-0003001.pdf | ||
| 36C25018B0803-0003000.docx | DOCX document | |
| 36C25018B0803-0002003.zip | ZIP file | |
| 36C25018B0803-027.pdf | ||
| 36C25018B0803-023.pdf | ||
| 36C25018B0803-025.pdf | ||
| 36C25018B0803-026.pdf | ||
| 36C25018B0803-022.docx | DOCX document | |
| 36C25018B0803-000.docx | DOCX document |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Veterans Affairs Palo Alto Health Care System
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
NORTH
SCALE:
SECOND FLOOR HVAC DEMOLITION PLAN
1/8" = 1'-0"
DEMOLITION KEYNOTES
EXISTING DUCTWORK THROUGH CHASE DOWN TO FIRST FLOOR
(EXISTING TO REMAIN)
FIN TUBE RADIANT HEATERS TO BE DEMOLISHED, PIPING DEMOLISH
BACK TO MAIN. CAPPED, INSULATED, AND SEALED AFTER DEMOITION
STEAM RADIANT HEATER TO REMAIN, COVER TO DEMOLISHED AND
REPLACED WITH NEW (SEE ARCHITECTURAL) (STEAM HEATER
CONTROLS PREVIOUSLY REPLACED
EXISTING DUCTWORK FROM ATTIC INTO SECOND FLOOR SPACE
(EXISTING TO REMAIN)
DEMOLITION NOTES
1. DEMOLISH ALL EXISTING CEILING AIR DEVICES, DUCTWORK, TERMINAL
UNITS, AND PIPING WITHIN SECOND FLOOR SCOPE AREA
2. CONTRACTOR TO MAINTAIN ALL EXISTING MECHANCIAL.
3. CONTRACTOR SHALL FOLLOW FACILITIES ICRA PLAN DURING
CONSTRUCTION PERIOD
3 3
Veterans Affairs Palo Alto Health Care System
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
NORTH
SCALE:
ATTIC HVAC DEMOLITION PLAN
1/8" = 1'-0"
DEMOLITION KEYNOTES
EXISTING DUCTWORK THROUGH CHASE DOWN TO FIRST FLOOR
(EXISTING TO REMAIN)
FIN TUBE RADIANT HEATERS TO BE DEMOLISHED, PIPING DEMOLISH
BACK TO MAIN. CAPPED, INSULATED, AND SEALED AFTER DEMOITION
STEAM RADIANT HEATER TO REMAIN, COVER TO DEMOLISHED AND
REPLACED WITH NEW (SEE ARCHITECTURAL) (STEAM HEATER
CONTROLS PREVIOUSLY REPLACED
EXISTING DUCTWORK FROM ATTIC INTO SECOND FLOOR SPACE
(EXISTING TO REMAIN)
DEMOLITION NOTES
1. DEMOLISH ALL EXISTING CEILING AIR DEVICES, DUCTWORK, TERMINAL
UNITS, AND PIPING WITHIN SECOND FLOOR SCOPE AREA
2. CONTRACTOR TO MAINTAIN ALL EXISTING MECHANCIAL.
3. CONTRACTOR SHALL FOLLOW FACILITIES ICRA PLAN DURING
CONSTRUCTION PERIOD
NORTH
DINING
BEDROOM-
BARIATRIC
CHARTING
EXIST.
STAIR
S2-2
BATH
256A
BATH
245A
EXIST.
STAIR
S3-2
BEDROOM
NE
PARLOR/DEN
BATH
221A
BEDROOM
BATH
214A
MEDS/MED
SELECT
BATH
210A
BATH
253A
SUITE
PASSAGE
C25
UNIT
COORDINATOR
LOCKER
ROOM
BATH
254A
CHARTING
BATH
243A
BEDROOM
CORRIDOR
C22
EXIST.
ELEVATOR
P2-1
CORRIDOR
C23
STAFF
LOUNGE
SUITE
PASSAGE
C31
EXIST.
STAIR
S1-2
NORTH KITCHEN
ELECTRICAL
BATH
227A
BEDROOM
BEDROOM
EXIST.
STAIR
S4-2
NW
PARLOR
BATH
208A
CLEAN UTL.
BEDROOM
SOILED UTL/
HOLDING
BEDROOM
CORRIDOR
C32
BEDROOM
BEDROOM
MULTI-PURPOSE
ROOM
OFFICE
EQUIPMENT
STORAGE
SHOWER RM
TOILET
OFFICE
STAFF
TOILET
234A
OFFICE
SUITE
PASSAGE
C35
BEDROOM-
BARIATRIC
BEDROOM
SE
PARLOR
ELECTRICAL
BEDROOM
MEDS/MED
SELECT
SW
PARLOR/DEN
CLOSET
BEDROOM
SOUTH KITCHEN
SOUTH
DINING
LIVING
ROOM
CHARTING
CLEAN
LINEN
HAC
CLOSET
CLEAN
LINEN
CHARTING
SUITE
PASSAGE
C27
LIVING
ROOM/DEN
SUITE
PASSAGE
C29
BEDROOM-
BARIATRIC
SUITE
PASSAGE
C38
CONFERENCE
ROOM
CORRIDOR
C33
CORRIDOR
C37
BATH
215A
LAUNDRY
HAC
BATH
252A
BATH
220A
ELEV.
LOBBY
CORRIDOR
C26
CORRIDOR
C28
CORRIDOR
C30
HAC
STOR.
CORRIDOR
C24
CORRIDOR
C36
SUITE
PASSAGE
C34
STORAGE
W
D
CLOSET
CLOSET
203A
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
BATH
257A
BATH
236A
CEN. MEDICAL
SUPPLY
8"ø
TU-1-1
E-1
150 CFM
D-1
75 CFM
D-4
350 CFM
TU-1-2
TU-1-4
TU-1-3
NEW 10"x10" EXHAUST
FROM ATTIC
R-1
275 CFM
EXISTING 18"x20"
RETURN FROM ATTIC
D-1
50 CFM
8"x6"
8"x6"
E-1
150 CFM
D-1
75 CFM
D-3
200 CFM
D-4
300 CFM
D-4
300 CFM
EXISTING 20"x18"
SUPPLY FROM ATTIC
D-3
150 CFM
D-4
350 CFM
D-2
100 CFM
D-3
200 CFM
10"ø
10"ø
8"ø
10"ø
8"ø
6"ø
6"ø x
10"ø ø
16"x12"
10"ø x x x x
10"x6"
6"ø
10"ø
10"ø
10"ø
10"ø x x
R-1
225 CFM
R-2
700 CFM
R-2
650 CFM
L-1
125 CFM
E-1
150 CFM
D-1
75 CFM
TU-1-6
TU-1-5
TU-1-9
TU-1-10
TU-1-11
TU-1-12
TU-1-13
TU-1-8
TU-1-7
D-3
225 CFM
D-3
225 CFM
R-2
450 CFM
D-3
250 CFM
D-3
250 CFM
D-2
200 CFM
D-4
300 CFM
D-4
300 CFM
10"ø
6"ø
10"ø ø
6"ø
8"ø
8"ø
8"ø
10"ø
8"ø
8"ø
8"ø
E-1
150 CFM
8"x6"
6"x6"
10"ø
8"ø
8"ø
8"ø
8"ø
6"ø
10"ø x
8"x6"
8"x6"
6"ø
8"x6" x x x
12"x10" x
10"x8"
EXISTING 26"x30"
SUPPLY FROM ATTIC
EXISTING 24"x20"
RETURN FROM ATTIC
NEW 10"x10" EXHAUST
FROM ATTIC
EXISTING 24"x20"
RETURN FROM ATTIC
12"x10"
18"x14" 1 x x
D-3
200 CFM
D-3
200 CFM
x
20"x20" x
D-3
200 CFM
D-3
200 CFM
R-1
275 CFM
R-1
75 CFM
D-2
150 CFM
18"x12"
D-2
150 CFM
R-2
600 CFM
D-3
200 CFM
R-1
175 CFM
8"x6" x
8"ø ø ø
10"ø
8"ø x
10"ø
8"ø
8"ø
8"ø
8"ø
10"x10"
R-1
225 CFM
R-1
225 CFM
TU-1-15
TU-1-16
TU-1-14
TU-1-18
TU-1-17
6"ø
6"ø
6"ø
6"ø
6"ø
10"ø
10"ø
8"ø
8"ø
8"ø
8"ø
8"ø x
8"x6"
8"x6"
NEW 10"x12" EXHAUST
FROM ATTIC
NEW 18"x12"
RETURN FROM
ATTIC
EXISTING 24"x20"
SUPPLY FROM ATTIC
x
6"x6" x
10"x10"
8"ø x
12"x12" x
10"ø x x
8"ø
D-4
300 CFM
D-4
300 CFM
D-2
150 CFM
D-2
125 CFM
D-1
75 CFM
D-1
75 CFM
E-1
150 CFM
E-1
150 CFM
D-2
100 CFM
D-2
150 CFM
D-2
150 CFM
E-1
200 CFM
R-1
225 CFM
R-2
400 CFM
R-1
225 CFM
R-2
75 CFM
10"ø
10"ø
NEW 10"x10" EXHAUST
FROM ATTIC
EXISTING 26"x20"
SUPPLY FROM ATTIC
NEW 20"x12" RETURN
FROM ATTIC
D-4
300 CFM
D-3
200 CFM
TU-2-7
TU-2-8
TU-2-10
TU-2-9
TU-2-11
10"ø
10"ø
8"ø
10"ø
10"ø
6"ø
6"ø ø
12"x10" x x
8"ø
D-3
200 CFM
R-1
125 CFM
R-1
125 CFM
R-1
225 CFM
R-1
225 CFM
R-1
225 CFM
x ø x x ø ø x
10"x8"
8"ø
10"ø
10"x6"
8"ø
8"ø
8"x6" x
10"x6"
12"ø
D-4
300 CFM
D-4
300 CFM
D-3
200 CFM
R-1
325 CFM
R-2
200 CFM
E-1
125 CFM
E-1
75 CFM
E-1
125 CFM
D-1
75 CFM
D-1
75 CFM
EXISTING 20"x20"
RETURN FROM ATTIC
EXISTING 18"x20"
SUPPLY FROM ATTIC
NEW 12"x12" EXHAUST
FROM ATTIC
EXISTING 18"x20"
RETURN FROM ATTIC
EXISTING 18"x20"
SUPPLY FROM ATTIC
TU-2-23
TU-2-21
TU-2-22
TU-2-20
TU-2-19
TU-2-18
L-1
125 CFM
E-1
150 CFM
D-1
75 CFM
D-1
75 CFM
D-42
300 CFM
E-1
150 CFM
x
10"ø ø ø ø
R-1
225 CFM
R-2
450 CFM
x
10"x10" x
8"ø
8"ø x
8"x6" x
E-2
150 CFM
8"x6"
8"x6" ø ø
8"x6" ø ø ø
8"x8"
12"ø
8"x8" x
8"ø ø
8"ø ø ø
10"ø x
6"x6" ø ø ø
10"x10"
EXISTING 20"x20"
RETURN FROM ATTIC
NEW 10"x10"
EXHAUST FROM
ATTIC
EXISTING 20"x20"
SUPPLY FROM ATTIC
TU-2-17
TU-2-15
TU-2-16
D-4
300 CFM
D-3
225 CFM
D-3
225 CFM
D-2
100 CFM
D-4
300 CFM
ø ø
10"ø ø
10"ø
EXISTING 16"x16"
SUPPLY FROM ATTIC
NEW 18"x16" RETURN
FROM ATTIC
x
14"x12"
14"x12"
10"x10"
10"ø 8"ø
8"ø
6"ø
D-3
250 CFM
D-3
250 CFM
ø x
12"x10" x
10"ø
8"ø
8"ø
12"x12"
TU-2-13
TU-2-14
TU-2-12
10"ø
8"ø10"ø
D-4
300 CFM
D-1
75 CFM
R-1
225 CFM
D-1
75 CFM
D-4
350 CFM
D-3
200 CFM
D-3
200 CFM
D-3
200 CFM
ø ø
10"x6" x ø
8"ø x x
8"x6"
10"ø
10"x8"
10"x8" x
6"ø
6"ø
R-1
275 CFM
R-2
525 CFM
E-1
150 CFM
D-1
75 CFM
E-1
150 CFM
E-1
150 CFM
EXISTING 24"x20"
RETURN FROM ATTIC
TU-2-3
TU-2-1
TU-2-4
TU-2-2
EXISTING 20"x26"
RETURN FROM ATTIC
NEW 10"x12" EXHAUST
FROM ATTIC
EXISTING 24"x20"
SUPPLY FROM ATTIC
D-3
200 CFM
D-4
350 CFM
D-3
250 CFM
D-2
150 CFM
D-2
150 CFM
8"x8"
TU-2-6
TU-2-5
x
8"x6"
8"ø
8"ø
8"ø
20"x14"
8"ø
8"ø
8"ø
6"ø
10"x8"
10"x6"
R-2
200 CFM
R-2
350 CFM
x
R-2
150 CFM
R-2
150 CFM
R-2
250 CFM
8"x6"
8"ø
8"ø ø
12"x10"
R-2
150 CFM
E-1
150 CFM
E-1
150 CFM
10"ø
8"ø x x x
10"x8"
D-1
75 CFM
D-3
250 CFM
10"ø
10"ø
10"ø
10"ø
6"ø
6"ø
D-3
200 CFM
D-3
250 CFM
D-3
250 CFM
D-3
250 CFM
D-1
75 CFM
D-1
350 CFM
D-1
75 CFM
D-4
300 CFM
D-3
200 CFM
D-3
200 CFM
R-1
125 CFM
D-1
75 CFM
R-1
225 CFM
D-1
75 CFM
E-1
150 CFM
D-1
75 CFM
D-2
175 CFM
D-2
100 CFM
D-2
150 CFM
R-2
475 CFM
R-2
500 CFM
E-1
150 CFM
D-1
75 CFM
D-1
75 CFM
R-2
400 CFM
R-1
200 CFM
R-2
225 CFM
R-2
600 CFM
R-2
500 CFM
R-1
100 CFM
R-2
100 CFM
R-1
275 CFM
E-1
150 CFM
FULLY SPRINKLERED
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
NORTH
SCALE:
SECOND FLOOR HVAC NEW WORK PLAN
1/8" = 1'-0"
4"ø
DRYER VENT LENGTH SHALL NOT
EXCEED MANUFACUTURER
RECOMMENDATIONS. SEE DETAILS
FOR INSTALLATION INSTRUCTIONS.
PROVIDE SIDEWALL CAP WITH
BACKDRAFT DAMPER
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FDFD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
NEW 8"x6" EXHAUST
FROM ATTIC
10"ø x x x
10"x6" x
8"ø
6"ø
8"ø
8"ø
8"ø
L-1
100 CFM
L-1
125 CFM
8"ø
8"ø
8"ø
8"ø
8"ø
8"ø
L-1
125 CFM
L-1
100 CFM
FULLY SPRINKLERED
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
Veterans Affairs Palo Alto Health Care System
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
NORTH
SCALE:
ATTIC HVAC NEW WORK PLAN
1/8" = 1'-0"
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF PLAN VIEW
SUPPLY REGISTER
TAKE-OFF PLAN VIEW
FLOW
FLOW
F L O
W
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN SUPPLY
DUCT
SEE FLOOR PLAN
FOR SPLIT DIMENSION
PROVIDE
VOLUME
DAMPER
PROVIDE
VOLUME
DAMPER
ADJUSTABLE
METAL ROD
OR LINKAGE
TOP REGISTER
MAIN
SUPPLY
DUCT
VOLUME EXTRACTOR; ADJUSTABLE
FROM FULLY CLOSED POSITION TO
CFM NOTED ON FLOOR PLANS
FLOW FLOW
1/4 W OR 4"
[100mm] MIN.
FLOW
MAIN SUPPLY
DUCT
F L O
W
W
SMACNA FIGURE 4-6
45° LEED IN RIGID DUCT
TO AIR TERMINAL UNIT.
MAIN SUPPLY
PLAN VIEW
FLOW
F L
O W
FLOW
STANDARD RADIUS OR
LONG RADIUS ELBOW
VANE
VANE
NOTE:
1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL
SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,
SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R
SHALL
EQUAL
OR BE
GREATER
THAN W.
R
SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
R
SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
STANDARD RADIUS OR
LONG RADIUS ELBOW
SHORT RADIUS ELBOW
WITH ONE VANE
SHORT RADIUS ELBOW
WITH TWO VANES
W
R
R
W
W
W W
W
W
1/6W
R
NOTE:
1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W
DIMENSION.
3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50MM] RADIUS, 1 1/2" [40MM] MAXIMUM SPACE BETWEEN
VANES AND A 3/4" [20MM] TRAILING EDGE.
4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500MM] VANES SHALL BE DOUBLE VANE TYPE.
W
W1
NOTE:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE DAMPERS & ROUND
DAMPERS.
INSULATION
SEE
SPECIFICATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
INSULATION STAND-OFF
1/2" [15mm]
ROUND ROD PIN
DUCT
STIFFEN
BLADE AS
REQUIRED
SIDE ELEVATION SECTION
NOTE:
1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET.
2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO
ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900MM].
3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE
EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS). FOR
LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT
STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64PA/M].
4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500MM]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.
5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR
CONNECTING DUCT SECTIONS.
AIR TERMINAL
UNIT (CV OR VAV)
REHEAT COIL
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
DIFFUSER (TYP.)
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT
(TYP.)
SEE NOTE 5
S E
E
N
O T
E
SEE NOTE 3
SEE NOTE 2
SEE NOTE 1
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED CONNECTION ON
FAN SIDE
WASHER
1-1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL WITH
MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS
ON 12" [300mm]
CENTERS
RIVET ON 4"
[100mm]
CENTERS
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEM
ALTERNATE POSITION OF BOLT
1 1/2" [40mm]
POCKET SLIP
DUCT
SHEET METAL AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX.
INSTALLED. 6" [150mm] NOMINAL
WITH MATERIAL TAUT
FLANGED
CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS SPECIFIED
1/2" 1/2" 1 1/2"
NOTE:
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND FAN ROOM FLOORS
SHALL BE PROVIDED WITH A 3" [75MM] HIGH CONCRETE CURB AROUND OPENING FOR DUCT.
SEAL HOLE WITH FIRESTOPPING
MATERIAL AFTER DUCT INSTALLATION
2"x2"x1/4" [50x50x6mm] ANGLE
INSTALL ON BOTH LONG
DIMENSION SIDES OF DUCT.
DUCT RISER - SEE FLOOR
PLANS FOR DETAILS
SEAL HOLE WITH FIRESTOPPING
MATERIAL AFTER DUCT INSTALLATION
FLOOR
EXTEND ANGLE 3"
[75mm] BEYOND DUCT
DUCT RISER - SEE FLOOR
PLANS FOR SIZES
SHEET METAL SCREWS 4"
[100mm] ON CENTER
1 1/2"x1 1/2"x1/8" [40x40x3mm] ANGLE INSTALL ON
BOTH LONG DIMENSION SIDES OF DUCT. FOR
DUCTS OVER 60" [1500mm] USE 2"x2"x1/8"
[50x50x3mm] ANGLE.
HOLE IN STRUCTURAL FLOOR
DUCT RISER
0.5 INCH WG [125Pa] TO 2 INCHES WG [500Pa] DUCT RISER SUPPORT
ARRANGE RISER SO REINFORCER
TRANSVERSE JOINT IS AT RISER
SUPPORT POINT
FLOOR
2 INCHES WG [500Pa] TO 4 INCHES WG [1000Pa] DUCT RISER SUPPORT
HOLE IN STRUCTURAL FLOOR
DUCT RISER
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
SCALE:
VOLUME DAMPER DETAIL
N.T.S
SCALE:
DUCTWORK SQUARE VANE ELBOWS
N.T.S
SCALE:
SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS
N.T.S
SCALE:
SUPPLY DUCTWORK TAKE-OFFS
N.T.S
SCALE:
DUCTWORK RADIUS ELBOWS
N.T.S
SCALE:
DUCT CONNECTIONS-AIR TERMINAL UNITS
N.T.S
SCALE:
DUCT RISER SUPPORTS
N.T.S
SCALE:
FLEXIBLE DUCT CONNECTIONS
N.T.S
NOTE:
UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.
M
A
X
M
A
X
E Q
U I P
M E
N T
AIR
FLOW
AIR
FLOW
TYPICAL DUCTWORK TRANSITION
PLAN OR SIDE VIEW
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
PLAN OR SIDE VIEW
M
A
X
M
A
X
M A
X
M
A
X
5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
1312 14
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 2418 14 16128
1064 532 2 1/2
1 1/2 1 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700] [5200][4100] [4900][3700][3000] [3400][2700]
[2100]
[4900]
[4100][3700] [4000]
[3000][2400][1800] [1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP
TO 1000 LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm] m m
M
A X
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE
CHANNEL OR 2"x2"x1/4"
[50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH
COMPRESSIVE STRENGTH
INSULATION (9 PSF MIN.
DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTES:
SEE SPECIFIER FOR DETAILED
HANGER REQUIREMENTS
2500 [1133]
1320 [598]
420 [190]ONE 1 [25] x 18 GA STRAP36 [900]
TWO 1/2 [13] RODS
TWO 3/8 [10] RODS
ONE 1 [25] x 16 GA STRAP
84 [2100]
60 [1500]
50 [1250] 700 [317]
ONE 1 [25] x 22 GA STRAP
QUANTITY/SIZE
MAX. DUCT Ø
26 [650]
HANGER STRAPS OR RODS
MAX. LOAD
LBS. [kg]
260 [119]
MAX.
144 [3600]
IN. [mm]
SPACING
IN. [mm]
IN. [mm]
144 [3600]
144 [3600]
144 [3600]
144 [3600]
NOTE:
TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING
AND INSULATION, BUT NO EXTERNAL LOAD.
BAND
OVER 50"
[1250mm]
HANGER RODS
BAND OF
SAME SIZE AS
HANGER STRAP
LOAD RATED
FASTENERS
50"
[1250mm]
& UNDER
FIN TUBE ELEMENT
H W
R
H W
S
SHUT OFF VALVE
CONTROL VALVE
BV
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION
CONNECTIONS
(TYP.)
WATER SUPPLY
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
BV
FIN TUBE ENCLOSURES
LOCATED IN FOURTH FLOOR
SPACE TO BE REMOVED AND
REPLACED WITH NEW
SCALE:
FIN TUBE ELEMENT - PIPING CONNECTIONS
N.T.S
SCALE:
TERMINAL UNIT WATER COIL PIPING CONNECTION (2-WAY)
N.T.S
SCALE:
PIPING HANGERS
N.T.S
SCALE:
ROUND DUCT HANGERS
N.T.S
SCALE:
DUCTWORK TRANSITIONS (WITH EQUIPMENT MOUNTED IN DUCT)
N.T.S
SCALE:
CLOTHES DRYER EXHAUST DETAIL
N.T.S
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
GENERAL NOTES:
1. IF COMPLIANCE WITH TWO OR MORE DIFFERING STANDARDS, REQUIREMENTS, DRAWING OR SPECIFICATIONS, OR ANY COMBINATION THEREOF, IS SPECIFIED AND THESE ESTABLISH
DIFFERENT OF CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY LEVELS, COMPLY WITH THE MOST STRINGENT REQUIREMENT. THE MOST STRINGENT REQUIREMENT WILL
BE THE BETTER QUALITY OR GREATER QUANTITY OF WORK, AND WILL TYPICALLY BE THE MORE EXPENSIVE OPTION. REFER UNCERTAINTIES AND REQUIREMENTS THAT ARE DIFFERENT, BUT
APPARENTLY EQUAL, TO ENGINEER FOR A DECISION BEFORE PROCEEDING.
2. THE QUANTITY OR QUALITY LEVEL SHOWN OR SPECIFIED SHALL BE THE MINIMUM PROVIDED OR PERFORMED. THE ACTUAL INSTALLATION MAY COMPLY EXACTLY WITH THE MINIMUM QUANTITY
OR QUALITY SPECIFIED, OR IT MAY EXCEED THE MINIMUM WITHIN REASONABLE LIMITS. TO COMPLY WITH THESE REQUIREMENTS, INDICATED NUMERIC VALUES ARE MINIMUM OR MAXIMUM, AS
APPROPRIATE FOR THE CONTEXT OF REQUIREMENTS. REFER UNCERTAINTIES TO ENGINEER FOR A DECISION BEFORE PROCEEDING.
3. DESIGN DOCUMENTS MUST BE REPRODUCED IN THEIR ENTIRETY, INCLUDING ALL PLANS, SPECIFICATIONS, AND FRONT END DOCUMENTS.
4. ONLY COMPLETE DOCUMENT SETS ARE TO BE DISTRIBUTED TO SUBCONTRACTORS AND SUPPLIERS OF THE CONTRACTOR DURING BIDDING OR CONSTRUCTION.
5. FAILURE TO REVIEW AND COMPLY WITH A FULL SET OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED AS A VALID REASON FOR FAILURE TO MEET THE REQUIREMENTS OF THE PLANS AND
SPECIFICATIONS.
6. ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH VA HVAC DESIGN MANUAL, LOCAL ORDINANCES, AND LAWS AND SHALL BE OF SIMILAR QUALITY, MATERIAL, AND
INSTALLATION METHODOLOGY AS SIMILAR WORK IN EXISTING FACILITY. FOR PURPOSES OF THIS DESIGN, THE CODES FOR THE STATE OF MI WERE USED AS THE BASIS.
7. ALL SYSTEMS AND COMPONENTS (MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, ETC.) SHALL BE COORDINATED SUCH THAT THE SYSTEMS ARE PROPERLY INTEGRATED IN THE
SPACE PROVIDED. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR TO COORDINATE PATHWAYS WITHIN THE SPACE PROVIDED.
8. COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT CONSTRUCTION, AND CONSTRUCTION
DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ARCHITECT/ENGINEER PRIOR TO PROCEEDING AND COMPLETION OF WORK.
9. CEILING CONTRACTOR SHALL FURNISH AND INSTALL HINGED STEEL ACCESS PANELS FOR ALL ABOVE CEILING DAMPERS, VAV BOXES, FILTERS, BALANCING VALVES, AND ISOLATION VALVES IN
GYPSUM CEILINGS. PANELS SHALL BE KEYED FOR ACCESS BY MAINTENANCE STAFF ONLY, AND FINISHED WITH WHITE BAKED-ON ENAMEL. MECHANICAL CONTRACTOR SHALL PROVIDE ALL
NECESSARY ACCESS PANELS AS A RESULT FROM PLAN DEVIATION/ALTERATION. COORDINATE QUANTITY AND LOCATION OF ADDITIONAL ACCESS PANELS WITH CEILING CONTRACTOR.
10. CONTRACTOR SHALL FURNISH AND INSTALL BEVELED OR TAPERED TAKEOFFS AT ALL CONNECTIONS OF DUCT RUNOUTS TO TRUNKS. ALL FITTINGS SHAL BE IN ACCORDANCE WITH SMACNA.
11. CONTRACTOR SHALL FURNISH AND INSTALL MANUAL BALANCING DAMPERS AT ALL SUPPLY, RETURN, AND EXHAUST TRUNK BRANCHES AND RUNOUTS.
12. CONTRACTOR SHALL FURNISH AND INSTALL ISOLATION AND BALANCING VALVES AT ALL VAV BOXES, AND BALANCING VALVES AT EACH FLOOR'S DISTRIBUTION LOOP. CONTRACTOR SHALL
LOCATE VALVES TO ALLOW FOR ACCESS WITHIN 3' AFTER CONSTRUCTION IS COMPLETE.
13. MECHANICAL CONTRACTOR SHALL COORDINATE EQUIPMENT INSTALLATION WITH ROOFING CONTRACTOR OR ROOFING MANUFACTURER TO AVOID DAMAGE TO ROOFING SYSTEM.
14. COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL, STRUCTURAL, CIVIL, INTERIORS, AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT
CONSTRUCTION AND CONSTRUCTION DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ENGINEER PRIOR TO PROCEEDING AND COMPLETION OF WORK.
15. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIRESTOPPING ALL NEW MECHANICAL PENETRATIONS THROUGH RATED ASSEMBLIES.
16. A 'TAB' IS REQUIRED FOR THE WORK. EQUIPMENT SHOP DRAWINGS WILL NOT BE REVIEWED PRIOR TO RECEIPT OF THE EXISTING SYSTEM 'TAB'.
17. MECHANICAL CONTRACTOR SHALL MEASURE SYSTEM FLOWS BEFORE SYSTEM ALTERATIONS AND ADJUST SYSTEM TO ACHIEVE PRE-CONSTRUCTION VALUES. VALUES BEFORE AND AFTER THE
WORK SHALL BE RECORDED AND SUPPLIED TO THE OWNERS REPRESENTATIVE.
18. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH MOTOR STARTERS COMPATIBLE WITH CONTROLS SYSTEM. COORDINATE WITH CONTROLS AND ELECTRICAL CONTRACTORS.
AIR DEVICE NOTES:
1. ALL DIFFUSERS. REGISTERS, AND GRILLES TO HAVE REMOVABLE CENTERS TO ALLOW ACCESS FOR CEILING.
2. PROVIDE ALL SPECIALTIES, FRAMES, AND BORDERS REQUIRED FOR INSTALLATION IN CEILING TYPE INDICATED IN ARCHITECTURAL DOCUMENTS.
3. PROVIDE DUCT-MOUNTED, ROUND OR RECTANGULAR, BALANCING DAMPER FOR EACH DUCTED SUPPLY, RETURN, OR EXHAUST AIR DEVICE.
4. DO NOT PROVIDE BALANCING DAMPER INTEGRAL WITH AIR DEVICE UNLESS SPECIFICALLY INDICATED WITH THE AIR DEVICE.
5. FOR AIR DEVICES WITH ROUND CONNECTIONS, PROVIDE WRAPPED CONICAL SPIN-IN FITTING WITH BALANCING DAMPER AT MAIN DUCT.
6. PROVIDE BLACK COLORED INSULATED PLENUMS FOR ALL AIR DIFFUSERS AND GRILLES.
7. PROVIDE PROPER SUPPORT FROM THE STRUCTURE.
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
HWS
HWR
V-2
ROOM THERMOSTAT/SENSOR
WALL MOUNTED 48" [1200mm] AFF.
ROOM THERMOSTAT/SENSOR
WALL MOUNTED 48" [1200mm] AFF.
NO SUPPLEMENTAL HEATING WITH SUPPLEMENTAL HEATING
A I R
F L
O W
C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
VAV BOX CONTROL SEQUENCE
(NO DEADBAND)
SP
TU
RHC
HWS
HWR
V-1
REHEAT
COIL
AIR TERMINAL UNIT
AIR
FLOW
TE
ATU
CONTROLLER
PC
TE
TU
RHC
HWS
HWR
V-1
REHEAT COIL
AIR TERMINAL
UNIT
AIR
FLOW
TE
ATU CONTROLLER
PC
TE
A I R
F L O
W
C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
SP
A I R
F L
O W
C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
SP
A I R
F L
O W
C
F M
ROOM TEMPERATURE (°F)
HEATING
MINIMUM
VAV BOX CONTROL SEQUENCE
(W/DEADBAND)
VAV BOX CONTROL SEQUENCE
(NO DEADBAND)
VAV BOX CONTROL
SEQUENCE
W/DEADBAND
SUPPLEMENTAL HEAT
SP
FE
100%
100%
100% 100%
R
E
H
E
A
T
F
L
O
W
V
V
I
R
O
W
V
O
W
V
O
W
V
O
W
R
E
H
E
O
W
R
E
H
E
O
W
S
U
P
O
W
R
E
H
E
O
W
S
U
O
W
A. UPON FALL IN SPACE TEMPERATURE THE VAV
DAMPER WILL MODULATE TO MINIMUM POSITION.
B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE
V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.
THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED
TO PREVENT VALVE HUNTING.
C. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE
TEMPERATURE.
A. SET POINTS SHALL BE SET AS FOLLOWS:
COOLING 75°F (ADJ)
HEATING 70°F (ADJ)
DEADBAND OF 5° F BETWEEN HEATING AND COOLING
SET POINTS WILL BE MAINTAINED.
B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER
WILL MODULATE TO MINIMUM POSITION.
C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE
V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.
THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED
TO PREVENT VALVE HUNTING.
D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE
TEMPERATURE
C. VALVE V-2 SHALL BE ENABLED WHEN OUTSIDE AIR FALLS
BELOW 40° F (ADJ) AND VALVE V-1 HAS BEEN MODULATED
OPEN ABOVE 30% (ADJ). VALVE V-2 MAINTAIN SET POINT BY
+/- 0.5° F. THE ADJUSTABLE TOLERANCE HAS BEEN
SELECTED TO PREVENT VALVE HUNTING.
D. THE REVERSE SHALL OCCUR ON A RISE IN SPACE
TEMPERATURE.
FE
A. UPON FALL IN SPACE TEMPERATURE THE VAV
DAMPER WILL MODULATE TO MINIMUM POSITION.
B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE
V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.
THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED
TO PREVENT VALVE HUNTING.
A. SET POINTS SHALL BE SET AS FOLLOWS:
COOLING 75°F (ADJ)
HEATING 70°F (ADJ)
DEADBAND OF 5° F BETWEEN HEATING AND COOLING
SET POINTS WILL BE MAINTAINED.
B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER
WILL MODULATE TO MINIMUM POSITION.
D. VALVE V-2 SHALL BE ENABLED WHEN OUTSIDE AIR FALLS
BELOW 40° F (ADJ) AND VALVE V-1 HAS BEEN MODULATED
OPEN ABOVE 30% (ADJ). VALVE V-2 MAINTAIN SET POINT BY
+/- 0.5° F. THE ADJUSTABLE TOLERANCE HAS BEEN
SELECTED TO PREVENT VALVE HUNTING.
E. THE REVERSE SHALL OCCUR ON A RISE IN SPACE
TEMPERATURE.
C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE
V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.
THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED
TO PREVENT VALVE HUNTING.
FAN
UNIT HEATER
HWS
HWR
V-1
HEATING COIL
T-1
ROOM THERMOSTAT WALL MTD OR
RETURN AIR MTD 48" [1200mm] AFF.
T
HS
HOT WATER UNIT HEATER SEQUENCE
1. UNIT HEATER SHALL OPERATE ON A SCHEDULE AS SET BY THE ECC. FAN
STATUS SHALL BE MONITORED AND AN ALARM MESSAGE GENERATED IN THE
EVENT THE UNIT FAILS TO RUN. THE ROOM TEMP SETPOINT WILL BE 65° (ADJ).
THE HOT WATER VALVE WILL BE ENABLED AS REQUIRED TO MAINTAIN SPACE
TEMP SETPOINT. HI/LO/OFF SWITCH WILL ALLOW LOCAL FAN SPEED
ADJUSTMENT.
PC
HI
LO
OFF
FAN
MOTOR
120V
EMCS
ENABLE
STT
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
SCALE:
HOT WATER UNIT HEATER CONTROLS
N.T.S
SCALE:
VAV AIR TERMINAL UNIT CONTROL DIAGRAM
N.T.S
NORTH
DINING
BEDROOM-
BARIATRIC
CHARTING
EXIST.
STAIR
S2-2
BATH
256A
BATH
245A
EXIST.
STAIR
S3-2
BEDROOM
NE
PARLOR/DEN
BATH
221A
BEDROOM
BATH
214A
MEDS/MED
SELECT
BATH
210A
BATH
253A
SUITE
PASSAGE
C25
UNIT
COORDINATOR
LOCKER
ROOM
BATH
254A
CHARTING
BATH
243A
BEDROOM
CORRIDOR
C22
EXIST.
ELEVATOR
P2-1
CORRIDOR
C23
STAFF
LOUNGE
SUITE
PASSAGE
C31
EXIST.
STAIR
S1-2
NORTH KITCHEN
ELECTRICAL
BATH
227A
BEDROOM
BEDROOM
EXIST.
STAIR
S4-2
NW
PARLOR
BATH
208A
CLEAN UTL.
BEDROOM
SOILED UTL/
HOLDING
BEDROOM
CORRIDOR
C32
BEDROOM
BEDROOM
MULTI-PURPOSE
ROOM
OFFICE
EQUIPMENT
STORAGE
SHOWER RM
TOILET
OFFICE
STAFF
TOILET
234A
OFFICE
SUITE
PASSAGE
C35
BEDROOM-
BARIATRIC
BEDROOM
SE
PARLOR
ELECTRICAL
BEDROOM
MEDS/MED
SELECT
SW
PARLOR/DEN
CLOSET
BEDROOM
SOUTH KITCHEN
SOUTH
DINING
LIVING
ROOM
CHARTING
CLEAN
LINEN
HAC
CLOSET
CLEAN
LINEN
CHARTING
SUITE
PASSAGE
C27
LIVING
ROOM/DEN
SUITE
PASSAGE
C29
BEDROOM-
BARIATRIC
SUITE
PASSAGE
C38
CONFERENCE
ROOM
CORRIDOR
C33
CORRIDOR
C37
BATH
215A
LAUNDRY
HAC
BATH
252A
BATH
220A
ELEV.
LOBBY
CORRIDOR
C26
CORRIDOR
C28
CORRIDOR
C30
HAC
STOR.
CORRIDOR
C24
CORRIDOR
C36
SUITE
PASSAGE
C34
STORAGE
W
D
CLOSET
CLOSET
203A
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
CLOSET
BATH
257A
BATH
236A
CEN. MEDICAL
SUPPLY
FULLY SPRINKLERED
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
FULLY SPRINKLERED
SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION
100% BID DOCUMENT SUBMISSION
COMPLETION ITEM NO.
95% CONSTRUCTION DOCUMENTS
DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION
SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION
95% CONSTRUCTION DOCUMENTS SUBMISSION
NOT FOR CONSTRUCTION
TU-1-13
TU-1-12
TU-1-11
TU-1-9
TU-1-10
TU-1-8
TU-1-7
TU-1-6
TU-1-5
TU-1-4
TU-1-3
TU-1-2
TU-1-1
TU-1-16
TU-1-14
TU-1-15
TU-1-18
TU-1-17
TU-2-6
TU-2-5
TU-2-2
TU-2-4
TU-2-3
TU-2-1
TU-2-7
TU-2-8
TU-2-10
TU-2-9
TU-2-11
TU-2-12
TU-2-14
TU-2-13
TU-2-15
TU-2-16
TU-2-17
TU-2-18
TU-2-19
TU-2-20
TU-2-21
TU-2-22
TU-2-23
3/4"
3/4"
3/4" HWS/R
1" HWS/R
1" HWS/R
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4" HWS/R
1" HWS/R
1" HWS/R 1-1/2" HWS/R
1-1/2" HWS/R
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1-1/2" HWS/R
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1" HWS/R
3/4" HWS/R
1" HWS/R
3/4" HWS/R
1" HWS/R
1-1/2" HWS/R
3/4" HWS/R
3/4"
3/4"
3/4"
1-1/2" HWS/R
PROVIDE ISOLATION
VALVES
PROVIDE ISOLATION
VALVE
PROVIDE ISOLATION
VALVES
PROVIDE ISOLATION
VALVES
NORTH
SCALE:
SECOND FLOOR PIPING NEW WORK PLAN
1/8" = 1'-0"
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
GENERAL ELECTRICAL NOTES
A.
THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF
SYSTEMS, BUT ARE NOT TO BE CONSIDERED FABRICATION DRAWINGS. THESE
DRAWINGS ARE SUPPLEMENTARY TO THE PROJECT SPECIFICATIONS. COORDINATE
WITH OTHER TRADES, AND PROVIDE EACH SYSTEM COMPLETE, INCLUDING ALL
NECESSARY COMPONENTS, FITTINGS, AND OFFSETS.
B.
INSTALL SYSTEMS SUCH THAT CODE REQUIRED WORKING CLEARANCE AND
DEDICATED EQUIPMENT SPACE ALONG WITH SERVICE ACCESS SPACE IS PROVIDED
AROUND ALL MECHANICAL AND ELECTRICAL EQUIPMENT, AND AROUND ANY
COMPONENTS WHICH REQUIRE SERVICE ACCESS.
C.
COORDINATE AND PROVIDE ACCESS DOORS WITHIN INACCESSIBLE CEILING, SHAFT,
AND CHASE AREAS FOR ALL COMPONENTS WHICH REQUIRE SERVICE ACCESS.
REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES AND PARTITION RATINGS.
ACCESS DOORS IN FIRE RATED SURFACES SHALL MAINTAIN THE FIRE RATING OF THE
PARTITION.
D. PROVIDE ALL MISCELLANEOUS STEEL AND HARDWARE TO SUPPORT ALL
DEVICES AND EQUIPMENT AS INDICATED IN THE SPECIFICATIONS.
E. REFER TO MECHANICAL/ELECTRICAL SCHEDULE DRAWING(S) FOR ELECTRICAL
REQUIREMENTS FOR MECHANICAL EQUIPMENT. PROVIDE ALL CONNECTIONS,
STARTERS, DISCONNECTS, EQUIPMENT, AND DEVICES AS INDICATED ON THE
SCHEDULES AND WHERE ELSEWHERE NOTED. PROVIDE THE CIRCUIT OF
HIGHER AMPACITY WHERE CIRCUIT SIZES ARE SHOWN ON THE ELECTRICAL
DRAWINGS THAT DIFFER FROM WHAT IS INDICATED ON THE MECHANICAL
SCHEDULES.
F. VERIFY REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH EQUIPMENT
SHOP DRAWINGS PRIOR TO ORDERING MATERIALS. NOTIFY THE ENGINEER OF
ANY DISCREPANCIES BETWEEN THE EQUIPMENT SHOP DRAWINGS AND
ELECTRICAL DRAWINGS. OBTAIN DIRECTION FROM THE ENGINEER PRIOR TO
ORDERING MATERIALS WHERE DISCREPANCIES EXIST.
G. PROVIDE NEW OVERCURRENT PROTECTIVE DEVICES TO MATCH EXISTING
EQUIPMENT WHERE NEW OVERCURRENT PROTECTIVE DEVICES ARE
REQUIRED TO SERVE NEW LOADS FROM EXISTING EQUIPMENT.
H.
TRANSFORMER CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH THE
NEC UNLESS NOTED OTHERWISE.
I.
MOTOR CIRCUIT PROTECTION SHALL BE SIZED IN ACCORDANCE WITH THE NEC
UNLESS NOTED OTHERWISE.
J.
TYPICAL 20A HOMERUN CIRCUIT IS 3/4"C., 2#12 & 1#12 GND (CU), UNLESS
OTHERWISE NOTED. SHARED NEUTRALS ARE PROHIBITED. REFER TO THE
FOLLOWING TABLE FOR MAXIMUM DISTANCE FOR BRANCH CIRCUIT WIRING:
AWG 120V, 20A CICUIT 277V, 20A CIRCUIT
#12 65FT 150FT
#10 105FT 245FT
#8 160FT 375FT
K. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS
(EXCEPT WALL PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK
BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE FOR ALL
SIMILAR DEVICES.
L. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME
MOUNTING HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES
SO THAT THERE IS ONE INCH BETWEEN ADJACENT VERTICAL EDGES OF
THE FACEPLATES, UNLESS OTHERWISE NOTED.
M. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE
LOCATED IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR
CENTERLINES.
N. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATED LOCATIONS OF
TYPICAL ELECTRICAL DEVICES. VERIFY MOUNTING HEIGHTS OF ALL OUTLETS.
O. TYPICAL MOUNTING HEIGHTS ARE INDICATED ON THE ARCHITECTURAL
DRAWINGS. COORDINATE THE MOUNTING HEIGHT OF DEVICES AND
EQUIPMENT INDICATED ON THESE DRAWINGS THAT ARE INDICATED AT
DIFFERENT MOUNTING HEIGHTS THAN THOSE INDICATED ON THE
ARCHITECTURAL DRAWINGS WITH THE ARCHITECT AND/OR ENGINEER PRIOR
TO INSTALLATION.
P.
WHERE THE NUMBER OF CURRENT-CARRYING CONDUCTORS IN A RACEWAY
EXCEEDS THREE, THE ALLOWABLE AMPACITY OF EACH CONDUCTOR SHALL
BE REDUCED AS SHOWN IN THE ADJUSTMENT FACTOR TABLE IN THE
NATIONAL ELECTRICAL CODE. LOAD DIVERSITY FACTORS SHALL NOT BE USED
IN SIZING BRANCH CIRCUIT CONDUCTORS.
Q. CONTRACTOR SHALL PROVIDE UPDATED, TYPED PANEL DIRECTORIES FOR ALL
PANELBOARDS MODIFIED DURING DEMOLITION AND/OR CONSTRUCTION. ANY
CIRCUITS MADE AVAILABLE DURING DEMOLITION AND NOT RE-USED DURING
CONSTRUCTION SHALL BE MARKED "SPARE".
R.
PROVIDE A DISCONNECTING MEANS FOR ALL LIGHTING FIXTURES PER NEC
SECTION 410.130.G.1.
S.
COORDINATE ANY SHUT DOWN OF EXISTING SERVICES AND EQUIPMENT THAT ARE
REMAINING IN USE WITH THE OWNER'S REPRESENTATIVE. WHERE EXISTING
BUILDING SERVICE IS REQUIRED TO BE SHUT DOWN, INCLUDE ALL ASSOCIATED
OVERTIME COST TO PERFORM THIS WORK DURING WEEKENDS AND EVENINGS,
INCLUDE ALL COSTS FOR PROVIDING TEMPORARY POWER WHERE SHUT DOWNS
MUST OCCUR FOR PERIODS LONGER THAN THESE HOURS. COORDINATE ELECTRICAL
SHUT DOWNS WITH THE OWNER 72 HOURS PRIOR TO SHUT DOWN.
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
SCALE:
1. REMOVE THE EXISTING PANEL AND ALL ASSOCIATED CONDUIT AND WIRING BACK TO THE
SOURCE.
2. EXISTING CONDUIT AND WIRING SHALL REMAIN. PROTECT IN PLACE DURING
CONSTRUCTION.
3. EXISTING CIRCUIT 20 FEEDING THE EXISTING DDC CONTROL PANEL LOCATED IN THE ATTIC
SHALL BE RE-FED FROM AN EXISTING SPARE 20A-1P CIRCUIT BREAKER IN EXISTING PANEL
SB3A LOCATED IN THE ATTIC. PROVIDE 2#12, 1#12GND IN 3/4" CONDUIT TO RE-FEED THE
EXISTING DDC CONTROL PANEL.
4. REMOVE ALL ITEMS ASSOCIATED WITH ELECTRICAL SYSTEMS SERVING THE SECOND FLOOR
UNLESS NOTED OTHERWISE. ANY EXISTING ITEMS ASSOCIATED WITH THE ELECTRICAL
SYSTEMS SERVING OTHER FLOORS SHALL REMAIN AND SHALL BE PROTECTED IN PLACE
DURING CONSTRUCTION.
5. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE EXISTING
ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND SHALL REMAIN
OPERATIONAL.
6. REMOVE THE EXISTING PANEL. THE EXISTING FEEDER CONDUIT AND WIRING FROM EXISTING
PANEL SBDP3A LOCATED IN THE ATTIC SHALL REMAIN AND SHALL BE REVISED TO CONNECT
TO THE NEW PANELS AS INDICATED ON DRAWINGS EP121 AND EP601.
7. REMOVE EXISTING PULL BOX MOUNTED IN FIRST FLOOR CEILING SPACE. REFER TO SHEET
ED601 FOR ADDITIONAL REQUIREMENTS.
DEMOLITION KEYNOTES
GENERAL DEMOLITION NOTES
A. VISIT THE SITE PRIOR TO SUBMISSION OF BID TO EXAMINE THE EXISTING CONDITIONS
AND THE EXTENT OF DEMOLITION WORK.
B.
EXAMINE THE DRAWINGS OF OTHER TRADES AND BE FAMILIAR WITH THE DEMOLITION
REQUIRED BY OTHER TRADES. PERFORM ALL INCIDENTAL ELECTRICAL DEMOLITION AND/OR
RELOCATION REQUIRED TO FACILITATE THE DEMOLITION WORK OF OTHER TRADES, WHETHER
OR NOT SPECIFICALLY INDICATED.
C. ITEMS NOTED SHALL BE DEMOLISHED AND ALL ASSOCIATED DEVICES, CONDUIT, AND
WIRING SHALL BE REMOVED BACK TO THE SOURCE UNLESS NOTED OTHERWISE.
D. ALL EXISTING EQUIPMENT MAY NOT BE INDICATED. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS PRIOR TO BIDDING. EXISTING ITEMS SHALL REMAIN IN
OPERATION UNLESS NOTED OTHERWISE. REVISE THE EXISTING CIRCUITRY TO
MAINTAIN OPERATION OF ITEMS TO REMAIN.
E.
PROVIDE PROPER SUPPORT FOR EXISTING TO REMAIN CONDUITS AND BOXES WHERE
EXISTING SUPPORT IS TO BE REMOVED. RE-ROUTE BRANCH CIRCUIT CONDUITS AND
RELOCATE JUNCTION BOXES TO FACILITATE INSTALLATION OF NEW EQUIPMENT AND SYSTEMS
IN CEILING SPACES.
F.
COORDINATE WITH NEW WORK PLANS AND ONE-LINE DIAGRAMS FOR EXTENT OF DEMOLITION
WORK.
G. CIRCUITING SHOWN IS BASED ON CASUAL FIELD OBSERVATIONS AND/OR AS-BUILT
DRAWINGS. CONTRACTOR SHALL FIELD VERIFY CIRCUITING.
H.
MAINTAIN ELECTRICAL SERVICE TO ALL LIGHTING FIXTURES, DEVICES AND EQUIPMENT THAT
ARE TO REMAIN. EXTEND CONDUIT AND WIRE AS REQUIRED WHERE DEMOLITION WORK
AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM LOADS THAT ARE TO REMAIN.
I.
DISPOSE OF ALL MATERIALS OFF SITE AND INCLUDE ALL COSTS FOR DISPOSAL IN BID. ALL
MATERIALS SHALL BE DISPOSED OF IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL
REGULATIONS, INCLUDING TCLP TESTING, PROPER DISPOSAL AND/OR RECYCLING OF
FLUORESCENT LAMPS.
J.
RING OUT AND TAG ALL CIRCUITS AFFECTED BY THIS ALTERATION AT BOTH ENDS. MARK ALL
UNUSED CIRCUIT BREAKERS “SPARE” AND TURN OFF.
K.
VERIFY ALL UNDERGROUND AND IN SLAB UTILITY LOCATIONS PRIOR TO SAW-CUTTING OR
PENETRATING ANY FLOOR SLAB.
L.
OFFER OWNERS REPRESENTATIVE FIRST RIGHT OF REFUSAL OF ALL EQUIPMENT REMOVED
FROM SPACE.
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
1. REMOVE THE EXISTING FLUSH MOUNTED PULL BOX
AND PATCH THE EXISTING WALL TO MATCH THE
ADJACENT FINISH.
DEMOLITION KEYNOTES
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
W
D a a b c c aa a a b a b b a a c b b a c b b b c a b b a b a a c b b c a b c a a c b b a b c a b b a b a b c b a c b a b b b a a a a b aa a a c ba ba b aa a a a a a a b a a b c a b c a a b c a
3a
3a 3a
3a
3a a
3a
3a 3a a a
3a a a a
Db
Db
D a
Db
D a
D b
D b
D b b a a c a a a a
D b b b b c b c
D b b
D a a b c a a
D b a a a b c
D b
D a b a
D b
D a b c b a a b c b
D a a ba aa
D a b c b b a a a a
3Da
3Da a
D a b c b a a a a b c b b c b a a
3Da b c bb a
Da
D a a
D a
D b b a b b b b
D D
D b
D a
Db3Da Db3Da
D b
D a
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1
LG1LG1 LG1
LG1
LG1
D
LG1LG1
LG1
LG1
LG1
LG1
LG1 LG1
LG1
LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2
LG2
LG1
LG1
LG1
LG2
LG2
LG1
LG1
LG1
LG1
LG1
LG1
LG1 LG1
D D
D
D
LG1
LG1
a b
LG1
LG2
LG2
LG2
LG2
D
LA1
LA1
LA1
LA1
LA1
LA1
LA1
LA1
LA1LA1
LA1LA1
LA1
LA1
LB1
LA1 LA1
LA1
LA1
LA1
LA1
LA1
LA1
LA1
LB1
LB1
LA1
LA1
LA1LA1
LA1LA1
LB1
LA1
LA1
LA1 LA1 LA1
LA1LA1
LA1
LA1 LA1
LA1
LA1
LA1
LA1
LA1
LA1 LA1
LA1 LA1
LA1
LA1
LA1
LB1
LA1
LA1LA1
LA1LA1
LB1
LA1
LA1
LA1LA1
LA1LA1
LA1LA1
LA1
LA1
LB1
LA1
LA1LA1
LA1 LA1 LA1
LA1LA1LA1
LA1 LA1 LA1LA1
LA1
LA1
LA1
LB1
LA1
LA1
LA1LA1
LA1
LA1
LG1
LG1
LB1
LA1LA1LA1
LA1
LA1
a
LG1
LG1
LA1
LB1
LA1
LA1 LA1
LA1
LA1LA1
LA1
LB1
LA1
LA1LA1
LA1 LA1
LA1 LA1
LA1
LA1LA1
LA1
LA1
LB1
LA1LA1
LA1LA1
LA1LA1
LA1
LA1
D
LA1 LA1
LA1
LB1
LG1
LG1
LA1LA1
LA1
LA1 LA1
LA1
LA1
LA1
LA1 LA1 LA1
LA1LA1 LA1
LA1
LB1
LA1
LA1 LA1 LA1
LA1
LA1 LA1 LA1
c
LB1
LG1 LG1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
LE1
D
T
T
LG2
LG2
LG2
LA1
O S a b c
LH1
LH1
D
LG1LG1
LG1 LG1
VS
O S
VS
VS
VS
VS
b a
LA1LA1
VS
VS
VS
VS
LG1
VS
VS
VS
O S
VS
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
NORTH
SCALE:
1. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE
EXISTING ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND
SHALL REMAIN OPERATIONAL.
2. PROVIDE 2#12, 1#12GND IN 3/4" CONDUIT TO CONNECT THE NEW LIGHT
FIXTURE TO THE EXISTING CIRCUIT AND CONTROLS SERVING ADJACENT
STAIR.
3. CONNECT CORRIDOR LIGHTING TO PANEL SB2B CIRCUIT NUMBER 6 VIA
LIGHTING CONTROL PANEL LCP2A.
4. PROVIDE A BODINE BLCD-20A GENERATOR TRANSFER DEVICE FOR EACH
SWITCHES CIRCUIT, FOR LOCAL CONTROL OF EMERGENCY FIXTURES.
LOCATE DEVICE IN CEILING SPACE.
5. CONNECT CORRIDOR LIGHTING TO PANEL SB2C CIRCUIT NUMBER 35 VIA
LIGHTING CONTROL PANEL LCP2A.
PLAN NOTES
LD1
LC1
LD1
LS2A-1
LC1
LD1
LC1
LD1
LS2A-1
LD1
LS2A-1
LC1
LD1
LC1
LC1
LC1
LC1
LC1
LC1
LC1
LD1
LS2A-1
LC1
LD1
LS2A-1
LC1
LD1
LS2A-1
LF1 LF1
GENERAL LIGHTING NOTES
A. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL
LIGHTING FIXTURES UNLESS NOTED OTHERWISE.
B. REFER TO THE LUMINAIRE SCHEDULE LOCATED ON DRAWING EP501.
C. ALL ELECTRICAL DEVICES INDICATED ON THIS PLAN SHALL BE NEW UNLESS NOTED
OTHERWISE.
D. LIGHT SWITCHES SHALL BE GROUPED UNDER ONE COMMON FACEPLATE WHERE MORE
THAN ONE LIGHT SWITCH IS INDICATED TO BE INSTALLED AT THE SAME LOCATION.
E. ALL LIGHTING BRANCH CIRCUIT WIRING ASSOCIATED WITH NEW LIGHTING SHALL BE
2#12, 1#12GND IN 3/4"C UNLESS NOTED OTHERWISE.
F. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED
SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION
TO SUCH EQUIPMENT/DEVICES AS REQUIRED.
G. ALL NIGHT LIGHTS AND EXIT SIGNS SHALL BE UNCONTROLLED AND CONNECTED
AHEAD OF THE LOCAL LIGHTING CONTROLS.
H. ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.
LC1
LC1
LC1
LD1
LC1
LC1
LS2A
SB2A
LS2B
SB2C
SB2B
LD1
LS2A-1
LCP2A
SB2B-8
SB2B-8
SB2B-8
SB2B-8
SB2B-6
SB2B-10
SB2B-10
SB2B-10
SB2B-10
SB2B-10
SB2B-10
SB2B-10
SB2B-16 SB2B-16
SB2B-12
SB2B-12
SB2B-12
SB2B-12
SB2B-14
SB2B-14
SB2B-14
SB2B-14
SB2B-8
SB2B-6
SB2B-6
SB2B-6
SB2B-6
(TYP.)
NL
NL
NL
NL
LS2A-1
LS2A-1
LD1
LS2A-1
LS2A-1
LS2A-1
LS2A-1
LS2A-1
LS2A-1
LS2A-1LS2A-1LS2A-1
SB2B-14
LD1
LS2A-1
LD1
LS2A-1
LD1
LS2A-1
LD1
LS2A-1
LD1
LS2A-1
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
(TYP.)
SB2B-18
SB2B-18
SB2B-18
SB2B-16
SB2B-16
SB2B-16
SB2B-16
SB2B-16
SB2B-16
SB2B-16
SB2B-16
(TYP.)
SB2B-16
LD1
LS2B-1
LD1
LS2B-1
LD1
LS2B-1
LD1
LS2B-1
LD1
LS2B-1
LD1
LS2B-1
LD1
LS2B-1
LD1
LS2B-1
LD1
LS2B-1
SB2B-37
SB2B-37
SB2B-35
LS2B-1
LS2B-1
LS2B-1
LS2B-1
LS2B-1
LS2B-1
LS2B-1
LS2B-1
LS2B-1
SB2B-37
SB2B-37
SB2B-35
SB2B-35
SB2B-39
SB2B-39
SB2B-37
SB2B-37
LD1
LS2B-1
LD1
LS2B-1SB2B-35
SB2B-39
SB2C-41
SB2C-41
SB2C-41
SB2C-41
SB2C-39
SB2C-41
SB2C-41
SB2C-39
LD1
LS2B-1
SB2B-37
SB2B-39
SB2B-39
SB2C-35
LD1
LS2B-1
NL
NL
SB2B-18
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
1. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE EXISTING
ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND SHALL REMAIN
OPERATIONAL.
PLAN NOTES
(E)SWBD0A
(E)SBATS0A
(E)SBDP0A
(E)ESWBD0A
(E)LSDP0A
(E)LSATS0A
(E)SBATS0B
SCALE:
GENERAL POWER NOTES
A. REFER TO ARCHITECTURAL FLOOR PLAN AND ELEVATIONS FOR EXACT LOCATION OF
DEVICES WHERE INDICATED.
E. ALL JUNCTION BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.
G. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED
SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION
TO SUCH EQUIPMENT/DEVICES.
H. ALL CONDUITS IN FINISHED SPACES SHALL BE ROUTED CONCEALED UNLESS NOTED
OTHERWISE.
L. PROVIDE A METAL RACEWAY SYSTEM THAT QUALIFIES AS AN EQUIPMENT GROUND
CONDUCTOR IN ACCORDANCE WITH SECTION 250.118 OF THE NEC IN PATIENT CARE
AREAS AS REQUIRED BY SECTION 517.13 OF THE NEC. AN INSULATED EQUIPMENT
GROUND CONDUCTOR SHALL BE PROVIDED IN ADDITION AS INDICATED IN SECTION
517.13 OF THE NEC.
PULLBOX
PULLBOX
UP TO
SECOND
FLOOR
http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com
W
D
SSOE, Inc.
Project #
Troy, MI 48084
Suite 260
T 248-643-6222
1050 Wilshire Drive
015-02007-00
100% BID DOCUMENT SUBMISSION
SCALE:
1. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE EXISTING
ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND SHALL REMAIN
OPERATIONAL.
2. PROVIDE A NEMA 14-30R TYPE RECEPTACLE. CONNECT RECEPTACLE TO CIRCUIT INDICATED
ON PLANS USING 3#10,1#10G IN 3/4" CONDUIT.
PLAN NOTES
LS2A
SB2A
LS2B
SB2C
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
GFI
44"
36"
36"
GFI
AFC
GFI
GFI
44"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
TV
66"
GFI
TV
66"
TV
66"
TV
66"
GENERAL POWER NOTES
A. REFER TO ARCHITECTURAL FLOOR PLAN AND ELEVATIONS FOR EXACT LOCATION OF
DEVICES WHERE INDICATED.
B. ALL RECEPTACLE OUTLETS SHALL BE HOSPITAL GRADE RATED 20A.
C. PROVIDE GFI PROTECTION WHERE REQUIRED BY THE NEC WHETHER INDICATED OR
NOT.
D. ALL JUNCTION BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.
E. ALL 20A BRANCH CIRCUIT WIRING SHALL BE 2#12, 1#12GND IN 3/4"C UNLESS NOTED
OTHERWISE.
F. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED
SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION
TO SUCH EQUIPMENT/DEVICES.
G. ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.
H. PROVIDE A METAL RACEWAY SYSTEM, METALLIC CABLE ARMOR, OR SHEATH
ASSEMBLY THAT QUALIFIES AS AN EQUIPMENT GROUND CONDUCTOR IN ACCORDANCE
WITH SECTION 250.118 OF THE NEC IN PATIENT CARE AREAS AS REQUIRED BY SECTION
517.13 OF THE NEC. AN INSULATED EQUIPMENT GROUND CONDUCTOR SHALL BE
PROVIDED IN ADDITION AS INDICATED IN SECTION 517.13 OF THE NEC.
48"
(1)
48"
GFI
44"
48" (25)
48"
48"
GFI
(21)
GFI
AFC
GFI
SB2B
LIFT
LIFT
LIFT
LIFT
LIFT
LIFT
LIFT
LIFT
LIFT
LIFT
LIFT
GFI
SECURITY CAMERA HEAD END
SB2C-43
NURSE CALL
HEAD END
FIRE ALARM
PANEL
GFI
GFI
44"
GFI
44"
GFI
44"
(20)
FIREPLACE
TV
66"
GFI
GFI
GFI
AFC
FIREPLACE
LCP2A
GFI
44"
GFI
AFC
GFI
GFI
(27)
GFI
AFC
GFI
GFI
AFC
GFI
AFC
GFI
AFC
GFI
AFC
LIFT
(24)
(24)
(24)(24)
(22)
(22)
(22)
SB2C
SB2C-29
(32)
(32)
(32)
(32)
(30)
(30)
(30)
(30)
(30)
SB2C
(29)
(29)
SB2C-29
AFC
SB2C-29
SB2C-29
SB2C-31
SB2C-31
SB2C-31
SB2C-31
SB2C-31
SB2C-31
SB2C-33
(30)
SB2C
FRIDGE
(28)
DISHWASHER
(34, 36, 38)
MICROWAVE
(30)
(30)
(10)
(10)
(10)
SB2C
(12)
(12)
(12)
(12)
(16)
(16)
(16)
(16)
(14) (14)
SB2C
SB2C
DRYER
(40,42)
GFI
(27)
SB2C-27
SB2C-27
SB2C-27
SB2C-27
(25)
AFC
GFI
(25)
SB2C
(20)
(20)
(20)
(18)
(18) (18)
SB2C
SB2C-19
(21)
(21)
(21)
SB2C
(23)
FRIDGE
U/C
(19)
(19)
(19)
(19)
SB2C
AFC
SB2C-19
(4)
(4)
(2)
(2)
(2)
(2)
SB2C
(2)
SB2C-17
SB2C-17
(8) (8)
(8)
(8)
(8)
(6)
(6)
SB2C
(7)
(7)
SB2B
(5)
SB2B-7
(7) (3)
(5)
(5)
(5)
(5)
(5)
(19)
(3)
SB2B
SB2B-3
SB2B-3
SB2B-3
GFI
AFC
GFI
AFC
(1)
(1)
(1)
(4)
SB2C
(4)
(4)
(4)
(4)
(2)
(2)
SB2B
SB2C-1
SB2C
SB2C
SB2C
SB2C
SB2C
(15)
(15)
(15)
(15)
(15)
SB2C-19
(13)
(13)
(13)
(13)
(13)
(11)
(11)
(11)
(11)
(11)
(9) (9)
(9) (3)
(3)
AFC
GFI
AFC
(3)
(3)
(3)
(5)
MICROWAVE
(7)
36"
FRIDGE
SB2B
SB2B-3
(1)
(28)
SB2A
(28)
(28)
(24)
(26)
(24)
U/C FRIDGE
GFI
AFC
(19)
(19)
(19)
(19)
(17)
(17)
SB2A
(13)
(13)
(13)
(15)
(15)
(15)
(15)
SB2A-6
SB2A-6
SB2A
(11)
(11)
(11)
(9)
(9)
SB2A-6
SB2A-6
SB2A-6
SB2A-6
SB2A-6
SB2A-8
SB2A-8
SB2A-8
SB2A-8
SB2A-10
SB2A-10
SB2A-10
SB2A-10
SB2A-11
(7)
(7)
(5)
(5)
(7)
(7)
(3)
(3)
(3)
(3)
(3)
(1)
(1)
SB2A
AFC
(34)
AFC
(32)
SB2A-4
(22) (20)
SB2A
(14)
MICROWAVE
(18)
(14)
DISHWASHER
(30, 32, 34)
SB2A-12
(14)
(14)
FRIDGE
(16)
GFI
AFC
GFI
AFC
GFI
AFC
GFI
AFC
SB2A-4
SB2A-4
SB2A-2
AFC
SB2A-2
SB2A-2
(25)
(25)
(27)
(25)
SB2A
(27)
(27)
(27)
SB2A-2
SB2A-2
SB2A-2
(23)
(23)
(23)
(23)
(23)
(21)
(21)
SB2A
48"
48"
(14)
SB2A-42
48"
48"
48"
(1)
48"
(1)
SB2C-1
SB2C-27
48" (25)
48" (25)
(25)
TU-1-1
SB2C-45
TU-1-13
SB2C-45
TU-1-2
SB2C-45
TU-1-4
SB2C-45
TU-1-5
SB2C-45
TU-1-6
SB2C-45
TU-1-7
SB2C-47
TU-1-8
SB2C-47
TU-1-10
SB2C-47
TU-1-9
SB2C-47
TU-1-12
SB2C-47
TU-1-13
SB2C-47
TU-1-11
SB2C-47
TU-1-14
SB2C-49
TU-1-15
SB2C-49
TU-1-16
SB2C-49
TU-1-17
SB2C-49
TU-1-18
SB2C-49
TU-2-6
SB2B-9
TU-2-5
SB2B-9
TU-2-3
SB2B-9
TU-2-1
SB2B-9
TU-2-2
SB2B-9
TU-2-4
SB2B-9
TU-2-7
SB2B-11
TU-2-8
SB2B-11
TU-2-9
SB2B-11
TU-2-10
SB2B-11
TU-2-12
SB2B-11
TU-2-13
SB2B-11
TU-2-11
SB2B-13
TU-2-18
SB2B-13
TU-2-17
SB2B-13
TU-2-16
SB2B-13
TU-2-14
SB2B-13
TU-2-15
SB2B-13
TU-2-19
SB2B-15
TU-2-20
SB2B-15
TU-2-21
SB2B-15
TU-2-23
SB2B-17
TU-2-22
SB2B-15
TU-2-25
SB2B-17
TU-2-24
SB2B-17
SB2C
SB2C
SB2C
SB2C
SB2C
SB2A
SB2A
SB2A
SB2A
SB2A
SB2A
SB2A
SB2C
DOWN TO
BASEMENT
SB2A
SB2A
ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg…