36C25018B0803-024.pdf

PDF 15 MB Posted

Attached to
Renovate Building 83-2 515-14-108 Federal contract opportunity
Solicitation number
36C25018B0803
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25018B0803 515-14-108 Battle Creek 83-2 Patient Privacy BID Drawings_Part3.pdf

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Building 83-2 515-14-108, newest first.
File Type Posted
36C25018B0803-0005001.pdf PDF
36C25018B0803-0005000.docx DOCX document
36C25018B0803-0003001.pdf PDF
36C25018B0803-0003000.docx DOCX document
36C25018B0803-0002003.zip ZIP file
36C25018B0803-027.pdf PDF
36C25018B0803-023.pdf PDF
36C25018B0803-025.pdf PDF
36C25018B0803-026.pdf PDF
36C25018B0803-022.docx DOCX document
36C25018B0803-000.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Veterans Affairs Palo Alto Health Care System

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

NORTH

SCALE:

SECOND FLOOR HVAC DEMOLITION PLAN

1/8" = 1'-0"

DEMOLITION KEYNOTES

EXISTING DUCTWORK THROUGH CHASE DOWN TO FIRST FLOOR

(EXISTING TO REMAIN)

FIN TUBE RADIANT HEATERS TO BE DEMOLISHED, PIPING DEMOLISH

BACK TO MAIN. CAPPED, INSULATED, AND SEALED AFTER DEMOITION

STEAM RADIANT HEATER TO REMAIN, COVER TO DEMOLISHED AND

REPLACED WITH NEW (SEE ARCHITECTURAL) (STEAM HEATER

CONTROLS PREVIOUSLY REPLACED

EXISTING DUCTWORK FROM ATTIC INTO SECOND FLOOR SPACE

(EXISTING TO REMAIN)

DEMOLITION NOTES

1. DEMOLISH ALL EXISTING CEILING AIR DEVICES, DUCTWORK, TERMINAL

UNITS, AND PIPING WITHIN SECOND FLOOR SCOPE AREA

2. CONTRACTOR TO MAINTAIN ALL EXISTING MECHANCIAL.

3. CONTRACTOR SHALL FOLLOW FACILITIES ICRA PLAN DURING

CONSTRUCTION PERIOD

3 3

Veterans Affairs Palo Alto Health Care System

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

NORTH

SCALE:

ATTIC HVAC DEMOLITION PLAN

1/8" = 1'-0"

DEMOLITION KEYNOTES

EXISTING DUCTWORK THROUGH CHASE DOWN TO FIRST FLOOR

(EXISTING TO REMAIN)

FIN TUBE RADIANT HEATERS TO BE DEMOLISHED, PIPING DEMOLISH

BACK TO MAIN. CAPPED, INSULATED, AND SEALED AFTER DEMOITION

STEAM RADIANT HEATER TO REMAIN, COVER TO DEMOLISHED AND

REPLACED WITH NEW (SEE ARCHITECTURAL) (STEAM HEATER

CONTROLS PREVIOUSLY REPLACED

EXISTING DUCTWORK FROM ATTIC INTO SECOND FLOOR SPACE

(EXISTING TO REMAIN)

DEMOLITION NOTES

1. DEMOLISH ALL EXISTING CEILING AIR DEVICES, DUCTWORK, TERMINAL

UNITS, AND PIPING WITHIN SECOND FLOOR SCOPE AREA

2. CONTRACTOR TO MAINTAIN ALL EXISTING MECHANCIAL.

3. CONTRACTOR SHALL FOLLOW FACILITIES ICRA PLAN DURING

CONSTRUCTION PERIOD

NORTH

DINING

BEDROOM-

BARIATRIC

CHARTING

EXIST.

STAIR

S2-2

BATH

256A

BATH

245A

EXIST.

STAIR

S3-2

BEDROOM

NE

PARLOR/DEN

BATH

221A

BEDROOM

BATH

214A

MEDS/MED

SELECT

BATH

210A

BATH

253A

SUITE

PASSAGE

C25

UNIT

COORDINATOR

LOCKER

ROOM

BATH

254A

CHARTING

BATH

243A

BEDROOM

CORRIDOR

C22

EXIST.

ELEVATOR

P2-1

CORRIDOR

C23

STAFF

LOUNGE

SUITE

PASSAGE

C31

EXIST.

STAIR

S1-2

NORTH KITCHEN

ELECTRICAL

BATH

227A

BEDROOM

BEDROOM

EXIST.

STAIR

S4-2

NW

PARLOR

BATH

208A

CLEAN UTL.

BEDROOM

SOILED UTL/

HOLDING

BEDROOM

CORRIDOR

C32

BEDROOM

BEDROOM

MULTI-PURPOSE

ROOM

OFFICE

EQUIPMENT

STORAGE

SHOWER RM

TOILET

OFFICE

STAFF

TOILET

234A

OFFICE

SUITE

PASSAGE

C35

BEDROOM-

BARIATRIC

BEDROOM

SE

PARLOR

ELECTRICAL

BEDROOM

MEDS/MED

SELECT

SW

PARLOR/DEN

CLOSET

BEDROOM

SOUTH KITCHEN

SOUTH

DINING

LIVING

ROOM

CHARTING

CLEAN

LINEN

HAC

CLOSET

CLEAN

LINEN

CHARTING

SUITE

PASSAGE

C27

LIVING

ROOM/DEN

SUITE

PASSAGE

C29

BEDROOM-

BARIATRIC

SUITE

PASSAGE

C38

CONFERENCE

ROOM

CORRIDOR

C33

CORRIDOR

C37

BATH

215A

LAUNDRY

HAC

BATH

252A

BATH

220A

ELEV.

LOBBY

CORRIDOR

C26

CORRIDOR

C28

CORRIDOR

C30

HAC

STOR.

CORRIDOR

C24

CORRIDOR

C36

SUITE

PASSAGE

C34

STORAGE

W

D

CLOSET

CLOSET

203A

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

BATH

257A

BATH

236A

CEN. MEDICAL

SUPPLY

8"ø

TU-1-1

E-1

150 CFM

D-1

75 CFM

D-4

350 CFM

TU-1-2

TU-1-4

TU-1-3

NEW 10"x10" EXHAUST

FROM ATTIC

R-1

275 CFM

EXISTING 18"x20"

RETURN FROM ATTIC

D-1

50 CFM

8"x6"

8"x6"

E-1

150 CFM

D-1

75 CFM

D-3

200 CFM

D-4

300 CFM

D-4

300 CFM

EXISTING 20"x18"

SUPPLY FROM ATTIC

D-3

150 CFM

D-4

350 CFM

D-2

100 CFM

D-3

200 CFM

10"ø

10"ø

8"ø

10"ø

8"ø

6"ø

6"ø x

10"ø ø

16"x12"

10"ø x x x x

10"x6"

6"ø

10"ø

10"ø

10"ø

10"ø x x

R-1

225 CFM

R-2

700 CFM

R-2

650 CFM

L-1

125 CFM

E-1

150 CFM

D-1

75 CFM

TU-1-6

TU-1-5

TU-1-9

TU-1-10

TU-1-11

TU-1-12

TU-1-13

TU-1-8

TU-1-7

D-3

225 CFM

D-3

225 CFM

R-2

450 CFM

D-3

250 CFM

D-3

250 CFM

D-2

200 CFM

D-4

300 CFM

D-4

300 CFM

10"ø

6"ø

10"ø ø

6"ø

8"ø

8"ø

8"ø

10"ø

8"ø

8"ø

8"ø

E-1

150 CFM

8"x6"

6"x6"

10"ø

8"ø

8"ø

8"ø

8"ø

6"ø

10"ø x

8"x6"

8"x6"

6"ø

8"x6" x x x

12"x10" x

10"x8"

EXISTING 26"x30"

SUPPLY FROM ATTIC

EXISTING 24"x20"

RETURN FROM ATTIC

NEW 10"x10" EXHAUST

FROM ATTIC

EXISTING 24"x20"

RETURN FROM ATTIC

12"x10"

18"x14" 1 x x

D-3

200 CFM

D-3

200 CFM

x

20"x20" x

D-3

200 CFM

D-3

200 CFM

R-1

275 CFM

R-1

75 CFM

D-2

150 CFM

18"x12"

D-2

150 CFM

R-2

600 CFM

D-3

200 CFM

R-1

175 CFM

8"x6" x

8"ø ø ø

10"ø

8"ø x

10"ø

8"ø

8"ø

8"ø

8"ø

10"x10"

R-1

225 CFM

R-1

225 CFM

TU-1-15

TU-1-16

TU-1-14

TU-1-18

TU-1-17

6"ø

6"ø

6"ø

6"ø

6"ø

10"ø

10"ø

8"ø

8"ø

8"ø

8"ø

8"ø x

8"x6"

8"x6"

NEW 10"x12" EXHAUST

FROM ATTIC

NEW 18"x12"

RETURN FROM

ATTIC

EXISTING 24"x20"

SUPPLY FROM ATTIC

x

6"x6" x

10"x10"

8"ø x

12"x12" x

10"ø x x

8"ø

D-4

300 CFM

D-4

300 CFM

D-2

150 CFM

D-2

125 CFM

D-1

75 CFM

D-1

75 CFM

E-1

150 CFM

E-1

150 CFM

D-2

100 CFM

D-2

150 CFM

D-2

150 CFM

E-1

200 CFM

R-1

225 CFM

R-2

400 CFM

R-1

225 CFM

R-2

75 CFM

10"ø

10"ø

NEW 10"x10" EXHAUST

FROM ATTIC

EXISTING 26"x20"

SUPPLY FROM ATTIC

NEW 20"x12" RETURN

FROM ATTIC

D-4

300 CFM

D-3

200 CFM

TU-2-7

TU-2-8

TU-2-10

TU-2-9

TU-2-11

10"ø

10"ø

8"ø

10"ø

10"ø

6"ø

6"ø ø

12"x10" x x

8"ø

D-3

200 CFM

R-1

125 CFM

R-1

125 CFM

R-1

225 CFM

R-1

225 CFM

R-1

225 CFM

x ø x x ø ø x

10"x8"

8"ø

10"ø

10"x6"

8"ø

8"ø

8"x6" x

10"x6"

12"ø

D-4

300 CFM

D-4

300 CFM

D-3

200 CFM

R-1

325 CFM

R-2

200 CFM

E-1

125 CFM

E-1

75 CFM

E-1

125 CFM

D-1

75 CFM

D-1

75 CFM

EXISTING 20"x20"

RETURN FROM ATTIC

EXISTING 18"x20"

SUPPLY FROM ATTIC

NEW 12"x12" EXHAUST

FROM ATTIC

EXISTING 18"x20"

RETURN FROM ATTIC

EXISTING 18"x20"

SUPPLY FROM ATTIC

TU-2-23

TU-2-21

TU-2-22

TU-2-20

TU-2-19

TU-2-18

L-1

125 CFM

E-1

150 CFM

D-1

75 CFM

D-1

75 CFM

D-42

300 CFM

E-1

150 CFM

x

10"ø ø ø ø

R-1

225 CFM

R-2

450 CFM

x

10"x10" x

8"ø

8"ø x

8"x6" x

E-2

150 CFM

8"x6"

8"x6" ø ø

8"x6" ø ø ø

8"x8"

12"ø

8"x8" x

8"ø ø

8"ø ø ø

10"ø x

6"x6" ø ø ø

10"x10"

EXISTING 20"x20"

RETURN FROM ATTIC

NEW 10"x10"

EXHAUST FROM

ATTIC

EXISTING 20"x20"

SUPPLY FROM ATTIC

TU-2-17

TU-2-15

TU-2-16

D-4

300 CFM

D-3

225 CFM

D-3

225 CFM

D-2

100 CFM

D-4

300 CFM

ø ø

10"ø ø

10"ø

EXISTING 16"x16"

SUPPLY FROM ATTIC

NEW 18"x16" RETURN

FROM ATTIC

x

14"x12"

14"x12"

10"x10"

10"ø 8"ø

8"ø

6"ø

D-3

250 CFM

D-3

250 CFM

ø x

12"x10" x

10"ø

8"ø

8"ø

12"x12"

TU-2-13

TU-2-14

TU-2-12

10"ø

8"ø10"ø

D-4

300 CFM

D-1

75 CFM

R-1

225 CFM

D-1

75 CFM

D-4

350 CFM

D-3

200 CFM

D-3

200 CFM

D-3

200 CFM

ø ø

10"x6" x ø

8"ø x x

8"x6"

10"ø

10"x8"

10"x8" x

6"ø

6"ø

R-1

275 CFM

R-2

525 CFM

E-1

150 CFM

D-1

75 CFM

E-1

150 CFM

E-1

150 CFM

EXISTING 24"x20"

RETURN FROM ATTIC

TU-2-3

TU-2-1

TU-2-4

TU-2-2

EXISTING 20"x26"

RETURN FROM ATTIC

NEW 10"x12" EXHAUST

FROM ATTIC

EXISTING 24"x20"

SUPPLY FROM ATTIC

D-3

200 CFM

D-4

350 CFM

D-3

250 CFM

D-2

150 CFM

D-2

150 CFM

8"x8"

TU-2-6

TU-2-5

x

8"x6"

8"ø

8"ø

8"ø

20"x14"

8"ø

8"ø

8"ø

6"ø

10"x8"

10"x6"

R-2

200 CFM

R-2

350 CFM

x

R-2

150 CFM

R-2

150 CFM

R-2

250 CFM

8"x6"

8"ø

8"ø ø

12"x10"

R-2

150 CFM

E-1

150 CFM

E-1

150 CFM

10"ø

8"ø x x x

10"x8"

D-1

75 CFM

D-3

250 CFM

10"ø

10"ø

10"ø

10"ø

6"ø

6"ø

D-3

200 CFM

D-3

250 CFM

D-3

250 CFM

D-3

250 CFM

D-1

75 CFM

D-1

350 CFM

D-1

75 CFM

D-4

300 CFM

D-3

200 CFM

D-3

200 CFM

R-1

125 CFM

D-1

75 CFM

R-1

225 CFM

D-1

75 CFM

E-1

150 CFM

D-1

75 CFM

D-2

175 CFM

D-2

100 CFM

D-2

150 CFM

R-2

475 CFM

R-2

500 CFM

E-1

150 CFM

D-1

75 CFM

D-1

75 CFM

R-2

400 CFM

R-1

200 CFM

R-2

225 CFM

R-2

600 CFM

R-2

500 CFM

R-1

100 CFM

R-2

100 CFM

R-1

275 CFM

E-1

150 CFM

FULLY SPRINKLERED

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

NORTH

SCALE:

SECOND FLOOR HVAC NEW WORK PLAN

1/8" = 1'-0"

4"ø

DRYER VENT LENGTH SHALL NOT

EXCEED MANUFACUTURER

RECOMMENDATIONS. SEE DETAILS

FOR INSTALLATION INSTRUCTIONS.

PROVIDE SIDEWALL CAP WITH

BACKDRAFT DAMPER

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FDFD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

FD

NEW 8"x6" EXHAUST

FROM ATTIC

10"ø x x x

10"x6" x

8"ø

6"ø

8"ø

8"ø

8"ø

L-1

100 CFM

L-1

125 CFM

8"ø

8"ø

8"ø

8"ø

8"ø

8"ø

L-1

125 CFM

L-1

100 CFM

FULLY SPRINKLERED

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

Veterans Affairs Palo Alto Health Care System

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

NORTH

SCALE:

ATTIC HVAC NEW WORK PLAN

1/8" = 1'-0"

AIR SPLIT DUCT TAKE-OFF

PLAN VIEW

BRANCH DUCT TAKE-OFF PLAN VIEW

SUPPLY REGISTER

TAKE-OFF PLAN VIEW

FLOW

FLOW

F L O

W

SUPPLY REGISTER

OR BRANCH DUCT

TURNING VANES

MAIN SUPPLY

DUCT

SEE FLOOR PLAN

FOR SPLIT DIMENSION

PROVIDE

VOLUME

DAMPER

PROVIDE

VOLUME

DAMPER

ADJUSTABLE

METAL ROD

OR LINKAGE

TOP REGISTER

MAIN

SUPPLY

DUCT

VOLUME EXTRACTOR; ADJUSTABLE

FROM FULLY CLOSED POSITION TO

CFM NOTED ON FLOOR PLANS

FLOW FLOW

1/4 W OR 4"

[100mm] MIN.

FLOW

MAIN SUPPLY

DUCT

F L O

W

W

SMACNA FIGURE 4-6

45° LEED IN RIGID DUCT

TO AIR TERMINAL UNIT.

MAIN SUPPLY

PLAN VIEW

FLOW

F L

O W

FLOW

STANDARD RADIUS OR

LONG RADIUS ELBOW

VANE

VANE

NOTE:

1. THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

2. ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS. ALL

SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R

SHALL

EQUAL

OR BE

GREATER

THAN W.

R

SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

R

SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS ELBOW

WITH ONE VANE

SHORT RADIUS ELBOW

WITH TWO VANES

W

R

R

W

W

W W

W

W

1/6W

R

NOTE:

1. ALL VANE ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE THICKNESS VANE TYPE REGARDLESS OF W

DIMENSION.

3. ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50MM] RADIUS, 1 1/2" [40MM] MAXIMUM SPACE BETWEEN

VANES AND A 3/4" [20MM] TRAILING EDGE.

4. WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500MM] VANES SHALL BE DOUBLE VANE TYPE.

W

W1

NOTE:

1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR MULTI-BLADE DAMPERS & ROUND

DAMPERS.

INSULATION

SEE

SPECIFICATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION STAND-OFF

1/2" [15mm]

ROUND ROD PIN

DUCT

STIFFEN

BLADE AS

REQUIRED

SIDE ELEVATION SECTION

NOTE:

1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET.

2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO

ACCOMMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0" [900MM].

3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE

EQUIVALENT LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET (3 METERS). FOR

LONGER LENGTHS, INCREASE THE DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT

STATIC PRESSURE DROP AT OR BELOW 0.2"/100' [1.64PA/M].

4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0" [1500MM]. USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.

5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR

CONNECTING DUCT SECTIONS.

AIR TERMINAL

UNIT (CV OR VAV)

REHEAT COIL

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL

DIFFUSER (TYP.)

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT

(TYP.)

SEE NOTE 5

S E

E

N

O T

E

SEE NOTE 3

SEE NOTE 2

SEE NOTE 1

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED CONNECTION ON

FAN SIDE

WASHER

1-1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS

ON 12" [300mm]

CENTERS

RIVET ON 4"

[100mm]

CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEM

ALTERNATE POSITION OF BOLT

1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

[15mm] [15mm] [40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL

WITH MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

1/2" 1/2" 1 1/2"

NOTE:

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND FAN ROOM FLOORS

SHALL BE PROVIDED WITH A 3" [75MM] HIGH CONCRETE CURB AROUND OPENING FOR DUCT.

SEAL HOLE WITH FIRESTOPPING

MATERIAL AFTER DUCT INSTALLATION

2"x2"x1/4" [50x50x6mm] ANGLE

INSTALL ON BOTH LONG

DIMENSION SIDES OF DUCT.

DUCT RISER - SEE FLOOR

PLANS FOR DETAILS

SEAL HOLE WITH FIRESTOPPING

MATERIAL AFTER DUCT INSTALLATION

FLOOR

EXTEND ANGLE 3"

[75mm] BEYOND DUCT

DUCT RISER - SEE FLOOR

PLANS FOR SIZES

SHEET METAL SCREWS 4"

[100mm] ON CENTER

1 1/2"x1 1/2"x1/8" [40x40x3mm] ANGLE INSTALL ON

BOTH LONG DIMENSION SIDES OF DUCT. FOR

DUCTS OVER 60" [1500mm] USE 2"x2"x1/8"

[50x50x3mm] ANGLE.

HOLE IN STRUCTURAL FLOOR

DUCT RISER

0.5 INCH WG [125Pa] TO 2 INCHES WG [500Pa] DUCT RISER SUPPORT

ARRANGE RISER SO REINFORCER

TRANSVERSE JOINT IS AT RISER

SUPPORT POINT

FLOOR

2 INCHES WG [500Pa] TO 4 INCHES WG [1000Pa] DUCT RISER SUPPORT

HOLE IN STRUCTURAL FLOOR

DUCT RISER

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

SCALE:

VOLUME DAMPER DETAIL

N.T.S

SCALE:

DUCTWORK SQUARE VANE ELBOWS

N.T.S

SCALE:

SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS

N.T.S

SCALE:

SUPPLY DUCTWORK TAKE-OFFS

N.T.S

SCALE:

DUCTWORK RADIUS ELBOWS

N.T.S

SCALE:

DUCT CONNECTIONS-AIR TERMINAL UNITS

N.T.S

SCALE:

DUCT RISER SUPPORTS

N.T.S

SCALE:

FLEXIBLE DUCT CONNECTIONS

N.T.S

NOTE:

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

M

A

X

M

A

X

E Q

U I P

M E

N T

AIR

FLOW

AIR

FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEW

TYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

M

A

X

M

A

X

M A

X

M

A

X

5 FT

THRU [20]

6 8 10

[32][25] [40]

[65]

[50]

[75]

1312 14

[125][100]

[150]

[250]

[200]

[300]

[400]

[350]

[450]

[600]

[500]

20 2418 14 16128

1064 532 2 1/2

1 1/2 1 1 1/4

[9100] [9600][8500][7600] [8200][7000][5800] [6700] [5200][4100] [4900][3700][3000] [3400][2700]

[2100]

[4900]

[4100][3700] [4000]

[3000][2400][1800] [1500]

THRU 3/4

[2100] [2100]

[2100]

[2700]

[2400]

SIDE VIEW TRAPEZE HANGER FOR UP

TO 1000 LB. [453KG] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER

TYPE 43 - SEE SPECIFICATIONS

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

[mm]

FT.

[mm]

FT.

[mm] m m

M

A X

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" [200mm] MIN.)

BAND

1-5/8" [43mm] 12 GAUGE

CHANNEL OR 2"x2"x1/4"

[50x50x6.4mm] ANGLE

1/2" [15mm] DIA.

HANGER RODS WITH

36" [900mm] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH

COMPRESSIVE STRENGTH

INSULATION (9 PSF MIN.

DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NOTES:

SEE SPECIFIER FOR DETAILED

HANGER REQUIREMENTS

2500 [1133]

1320 [598]

420 [190]ONE 1 [25] x 18 GA STRAP36 [900]

TWO 1/2 [13] RODS

TWO 3/8 [10] RODS

ONE 1 [25] x 16 GA STRAP

84 [2100]

60 [1500]

50 [1250] 700 [317]

ONE 1 [25] x 22 GA STRAP

QUANTITY/SIZE

MAX. DUCT Ø

26 [650]

HANGER STRAPS OR RODS

MAX. LOAD

LBS. [kg]

260 [119]

MAX.

144 [3600]

IN. [mm]

SPACING

IN. [mm]

IN. [mm]

144 [3600]

144 [3600]

144 [3600]

144 [3600]

NOTE:

TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING

AND INSULATION, BUT NO EXTERNAL LOAD.

BAND

OVER 50"

[1250mm]

HANGER RODS

BAND OF

SAME SIZE AS

HANGER STRAP

LOAD RATED

FASTENERS

50"

[1250mm]

& UNDER

FIN TUBE ELEMENT

H W

R

H W

S

SHUT OFF VALVE

CONTROL VALVE

BV

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

WATER RETURN

MANUAL AIR VENT

UNION

CONNECTIONS

(TYP.)

WATER SUPPLY

SHUT OFF VALVE

DRAIN WITH HOSE

CONNECTION

MV

MODULATION CONTROL VALVE

BV

FIN TUBE ENCLOSURES

LOCATED IN FOURTH FLOOR

SPACE TO BE REMOVED AND

REPLACED WITH NEW

SCALE:

FIN TUBE ELEMENT - PIPING CONNECTIONS

N.T.S

SCALE:

TERMINAL UNIT WATER COIL PIPING CONNECTION (2-WAY)

N.T.S

SCALE:

PIPING HANGERS

N.T.S

SCALE:

ROUND DUCT HANGERS

N.T.S

SCALE:

DUCTWORK TRANSITIONS (WITH EQUIPMENT MOUNTED IN DUCT)

N.T.S

SCALE:

CLOTHES DRYER EXHAUST DETAIL

N.T.S

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

GENERAL NOTES:

1. IF COMPLIANCE WITH TWO OR MORE DIFFERING STANDARDS, REQUIREMENTS, DRAWING OR SPECIFICATIONS, OR ANY COMBINATION THEREOF, IS SPECIFIED AND THESE ESTABLISH

DIFFERENT OF CONFLICTING REQUIREMENTS FOR MINIMUM QUANTITIES OR QUALITY LEVELS, COMPLY WITH THE MOST STRINGENT REQUIREMENT. THE MOST STRINGENT REQUIREMENT WILL

BE THE BETTER QUALITY OR GREATER QUANTITY OF WORK, AND WILL TYPICALLY BE THE MORE EXPENSIVE OPTION. REFER UNCERTAINTIES AND REQUIREMENTS THAT ARE DIFFERENT, BUT

APPARENTLY EQUAL, TO ENGINEER FOR A DECISION BEFORE PROCEEDING.

2. THE QUANTITY OR QUALITY LEVEL SHOWN OR SPECIFIED SHALL BE THE MINIMUM PROVIDED OR PERFORMED. THE ACTUAL INSTALLATION MAY COMPLY EXACTLY WITH THE MINIMUM QUANTITY

OR QUALITY SPECIFIED, OR IT MAY EXCEED THE MINIMUM WITHIN REASONABLE LIMITS. TO COMPLY WITH THESE REQUIREMENTS, INDICATED NUMERIC VALUES ARE MINIMUM OR MAXIMUM, AS

APPROPRIATE FOR THE CONTEXT OF REQUIREMENTS. REFER UNCERTAINTIES TO ENGINEER FOR A DECISION BEFORE PROCEEDING.

3. DESIGN DOCUMENTS MUST BE REPRODUCED IN THEIR ENTIRETY, INCLUDING ALL PLANS, SPECIFICATIONS, AND FRONT END DOCUMENTS.

4. ONLY COMPLETE DOCUMENT SETS ARE TO BE DISTRIBUTED TO SUBCONTRACTORS AND SUPPLIERS OF THE CONTRACTOR DURING BIDDING OR CONSTRUCTION.

5. FAILURE TO REVIEW AND COMPLY WITH A FULL SET OF CONTRACT DOCUMENTS WILL NOT BE ACCEPTED AS A VALID REASON FOR FAILURE TO MEET THE REQUIREMENTS OF THE PLANS AND

SPECIFICATIONS.

6. ALL MECHANICAL WORK SHALL BE INSTALLED IN ACCORDANCE WITH VA HVAC DESIGN MANUAL, LOCAL ORDINANCES, AND LAWS AND SHALL BE OF SIMILAR QUALITY, MATERIAL, AND

INSTALLATION METHODOLOGY AS SIMILAR WORK IN EXISTING FACILITY. FOR PURPOSES OF THIS DESIGN, THE CODES FOR THE STATE OF MI WERE USED AS THE BASIS.

7. ALL SYSTEMS AND COMPONENTS (MECHANICAL, ELECTRICAL, PLUMBING, FIRE PROTECTION, ETC.) SHALL BE COORDINATED SUCH THAT THE SYSTEMS ARE PROPERLY INTEGRATED IN THE

SPACE PROVIDED. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR TO COORDINATE PATHWAYS WITHIN THE SPACE PROVIDED.

8. COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT CONSTRUCTION, AND CONSTRUCTION

DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ARCHITECT/ENGINEER PRIOR TO PROCEEDING AND COMPLETION OF WORK.

9. CEILING CONTRACTOR SHALL FURNISH AND INSTALL HINGED STEEL ACCESS PANELS FOR ALL ABOVE CEILING DAMPERS, VAV BOXES, FILTERS, BALANCING VALVES, AND ISOLATION VALVES IN

GYPSUM CEILINGS. PANELS SHALL BE KEYED FOR ACCESS BY MAINTENANCE STAFF ONLY, AND FINISHED WITH WHITE BAKED-ON ENAMEL. MECHANICAL CONTRACTOR SHALL PROVIDE ALL

NECESSARY ACCESS PANELS AS A RESULT FROM PLAN DEVIATION/ALTERATION. COORDINATE QUANTITY AND LOCATION OF ADDITIONAL ACCESS PANELS WITH CEILING CONTRACTOR.

10. CONTRACTOR SHALL FURNISH AND INSTALL BEVELED OR TAPERED TAKEOFFS AT ALL CONNECTIONS OF DUCT RUNOUTS TO TRUNKS. ALL FITTINGS SHAL BE IN ACCORDANCE WITH SMACNA.

11. CONTRACTOR SHALL FURNISH AND INSTALL MANUAL BALANCING DAMPERS AT ALL SUPPLY, RETURN, AND EXHAUST TRUNK BRANCHES AND RUNOUTS.

12. CONTRACTOR SHALL FURNISH AND INSTALL ISOLATION AND BALANCING VALVES AT ALL VAV BOXES, AND BALANCING VALVES AT EACH FLOOR'S DISTRIBUTION LOOP. CONTRACTOR SHALL

LOCATE VALVES TO ALLOW FOR ACCESS WITHIN 3' AFTER CONSTRUCTION IS COMPLETE.

13. MECHANICAL CONTRACTOR SHALL COORDINATE EQUIPMENT INSTALLATION WITH ROOFING CONTRACTOR OR ROOFING MANUFACTURER TO AVOID DAMAGE TO ROOFING SYSTEM.

14. COORDINATE LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL, STRUCTURAL, CIVIL, INTERIORS, AND ELECTRICAL PRIOR TO ROUGH-IN. ALL CONFLICTS WITH FINISHES, ADJACENT

CONSTRUCTION AND CONSTRUCTION DOCUMENTS ARE TO GENERATE AN RFI FROM THE MECHANICAL CONTRACTOR TO THE ENGINEER PRIOR TO PROCEEDING AND COMPLETION OF WORK.

15. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIRESTOPPING ALL NEW MECHANICAL PENETRATIONS THROUGH RATED ASSEMBLIES.

16. A 'TAB' IS REQUIRED FOR THE WORK. EQUIPMENT SHOP DRAWINGS WILL NOT BE REVIEWED PRIOR TO RECEIPT OF THE EXISTING SYSTEM 'TAB'.

17. MECHANICAL CONTRACTOR SHALL MEASURE SYSTEM FLOWS BEFORE SYSTEM ALTERATIONS AND ADJUST SYSTEM TO ACHIEVE PRE-CONSTRUCTION VALUES. VALUES BEFORE AND AFTER THE

WORK SHALL BE RECORDED AND SUPPLIED TO THE OWNERS REPRESENTATIVE.

18. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH MOTOR STARTERS COMPATIBLE WITH CONTROLS SYSTEM. COORDINATE WITH CONTROLS AND ELECTRICAL CONTRACTORS.

AIR DEVICE NOTES:

1. ALL DIFFUSERS. REGISTERS, AND GRILLES TO HAVE REMOVABLE CENTERS TO ALLOW ACCESS FOR CEILING.

2. PROVIDE ALL SPECIALTIES, FRAMES, AND BORDERS REQUIRED FOR INSTALLATION IN CEILING TYPE INDICATED IN ARCHITECTURAL DOCUMENTS.

3. PROVIDE DUCT-MOUNTED, ROUND OR RECTANGULAR, BALANCING DAMPER FOR EACH DUCTED SUPPLY, RETURN, OR EXHAUST AIR DEVICE.

4. DO NOT PROVIDE BALANCING DAMPER INTEGRAL WITH AIR DEVICE UNLESS SPECIFICALLY INDICATED WITH THE AIR DEVICE.

5. FOR AIR DEVICES WITH ROUND CONNECTIONS, PROVIDE WRAPPED CONICAL SPIN-IN FITTING WITH BALANCING DAMPER AT MAIN DUCT.

6. PROVIDE BLACK COLORED INSULATED PLENUMS FOR ALL AIR DIFFUSERS AND GRILLES.

7. PROVIDE PROPER SUPPORT FROM THE STRUCTURE.

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

HWS

HWR

V-2

ROOM THERMOSTAT/SENSOR

WALL MOUNTED 48" [1200mm] AFF.

ROOM THERMOSTAT/SENSOR

WALL MOUNTED 48" [1200mm] AFF.

NO SUPPLEMENTAL HEATING WITH SUPPLEMENTAL HEATING

A I R

F L

O W

C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

VAV BOX CONTROL SEQUENCE

(NO DEADBAND)

SP

TU

RHC

HWS

HWR

V-1

REHEAT

COIL

AIR TERMINAL UNIT

AIR

FLOW

TE

ATU

CONTROLLER

PC

TE

TU

RHC

HWS

HWR

V-1

REHEAT COIL

AIR TERMINAL

UNIT

AIR

FLOW

TE

ATU CONTROLLER

PC

TE

A I R

F L O

W

C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

SP

A I R

F L

O W

C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

SP

A I R

F L

O W

C

F M

ROOM TEMPERATURE (°F)

HEATING

MINIMUM

VAV BOX CONTROL SEQUENCE

(W/DEADBAND)

VAV BOX CONTROL SEQUENCE

(NO DEADBAND)

VAV BOX CONTROL

SEQUENCE

W/DEADBAND

SUPPLEMENTAL HEAT

SP

FE

100%

100%

100% 100%

R

E

H

E

A

T

F

L

O

W

V

V

I

R

O

W

V

O

W

V

O

W

V

O

W

R

E

H

E

O

W

R

E

H

E

O

W

S

U

P

O

W

R

E

H

E

O

W

S

U

O

W

A. UPON FALL IN SPACE TEMPERATURE THE VAV

DAMPER WILL MODULATE TO MINIMUM POSITION.

B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE

V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.

THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED

TO PREVENT VALVE HUNTING.

C. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE

TEMPERATURE.

A. SET POINTS SHALL BE SET AS FOLLOWS:

COOLING 75°F (ADJ)

HEATING 70°F (ADJ)

DEADBAND OF 5° F BETWEEN HEATING AND COOLING

SET POINTS WILL BE MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER

WILL MODULATE TO MINIMUM POSITION.

C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE

V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.

THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED

TO PREVENT VALVE HUNTING.

D. THE REVERSE SHALL OCCUR ON THE RISE IN SPACE

TEMPERATURE

C. VALVE V-2 SHALL BE ENABLED WHEN OUTSIDE AIR FALLS

BELOW 40° F (ADJ) AND VALVE V-1 HAS BEEN MODULATED

OPEN ABOVE 30% (ADJ). VALVE V-2 MAINTAIN SET POINT BY

+/- 0.5° F. THE ADJUSTABLE TOLERANCE HAS BEEN

SELECTED TO PREVENT VALVE HUNTING.

D. THE REVERSE SHALL OCCUR ON A RISE IN SPACE

TEMPERATURE.

FE

A. UPON FALL IN SPACE TEMPERATURE THE VAV

DAMPER WILL MODULATE TO MINIMUM POSITION.

B. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE

V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.

THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED

TO PREVENT VALVE HUNTING.

A. SET POINTS SHALL BE SET AS FOLLOWS:

COOLING 75°F (ADJ)

HEATING 70°F (ADJ)

DEADBAND OF 5° F BETWEEN HEATING AND COOLING

SET POINTS WILL BE MAINTAINED.

B. UPON FALL IN SPACE TEMPERATURE THE VAV DAMPER

WILL MODULATE TO MINIMUM POSITION.

D. VALVE V-2 SHALL BE ENABLED WHEN OUTSIDE AIR FALLS

BELOW 40° F (ADJ) AND VALVE V-1 HAS BEEN MODULATED

OPEN ABOVE 30% (ADJ). VALVE V-2 MAINTAIN SET POINT BY

+/- 0.5° F. THE ADJUSTABLE TOLERANCE HAS BEEN

SELECTED TO PREVENT VALVE HUNTING.

E. THE REVERSE SHALL OCCUR ON A RISE IN SPACE

TEMPERATURE.

C. UPON FURTHER DROP IN SPACE TEMPERATURE VALVE

V-1 WILL MODULATE TO MAINTAIN SET POINT BY +/- 0.5° F.

THE ADJUSTABLE TOLERANCE HAS BEEN SELECTED

TO PREVENT VALVE HUNTING.

FAN

UNIT HEATER

HWS

HWR

V-1

HEATING COIL

T-1

ROOM THERMOSTAT WALL MTD OR

RETURN AIR MTD 48" [1200mm] AFF.

T

HS

HOT WATER UNIT HEATER SEQUENCE

1. UNIT HEATER SHALL OPERATE ON A SCHEDULE AS SET BY THE ECC. FAN

STATUS SHALL BE MONITORED AND AN ALARM MESSAGE GENERATED IN THE

EVENT THE UNIT FAILS TO RUN. THE ROOM TEMP SETPOINT WILL BE 65° (ADJ).

THE HOT WATER VALVE WILL BE ENABLED AS REQUIRED TO MAINTAIN SPACE

TEMP SETPOINT. HI/LO/OFF SWITCH WILL ALLOW LOCAL FAN SPEED

ADJUSTMENT.

PC

HI

LO

OFF

FAN

MOTOR

120V

EMCS

ENABLE

STT

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

SCALE:

HOT WATER UNIT HEATER CONTROLS

N.T.S

SCALE:

VAV AIR TERMINAL UNIT CONTROL DIAGRAM

N.T.S

NORTH

DINING

BEDROOM-

BARIATRIC

CHARTING

EXIST.

STAIR

S2-2

BATH

256A

BATH

245A

EXIST.

STAIR

S3-2

BEDROOM

NE

PARLOR/DEN

BATH

221A

BEDROOM

BATH

214A

MEDS/MED

SELECT

BATH

210A

BATH

253A

SUITE

PASSAGE

C25

UNIT

COORDINATOR

LOCKER

ROOM

BATH

254A

CHARTING

BATH

243A

BEDROOM

CORRIDOR

C22

EXIST.

ELEVATOR

P2-1

CORRIDOR

C23

STAFF

LOUNGE

SUITE

PASSAGE

C31

EXIST.

STAIR

S1-2

NORTH KITCHEN

ELECTRICAL

BATH

227A

BEDROOM

BEDROOM

EXIST.

STAIR

S4-2

NW

PARLOR

BATH

208A

CLEAN UTL.

BEDROOM

SOILED UTL/

HOLDING

BEDROOM

CORRIDOR

C32

BEDROOM

BEDROOM

MULTI-PURPOSE

ROOM

OFFICE

EQUIPMENT

STORAGE

SHOWER RM

TOILET

OFFICE

STAFF

TOILET

234A

OFFICE

SUITE

PASSAGE

C35

BEDROOM-

BARIATRIC

BEDROOM

SE

PARLOR

ELECTRICAL

BEDROOM

MEDS/MED

SELECT

SW

PARLOR/DEN

CLOSET

BEDROOM

SOUTH KITCHEN

SOUTH

DINING

LIVING

ROOM

CHARTING

CLEAN

LINEN

HAC

CLOSET

CLEAN

LINEN

CHARTING

SUITE

PASSAGE

C27

LIVING

ROOM/DEN

SUITE

PASSAGE

C29

BEDROOM-

BARIATRIC

SUITE

PASSAGE

C38

CONFERENCE

ROOM

CORRIDOR

C33

CORRIDOR

C37

BATH

215A

LAUNDRY

HAC

BATH

252A

BATH

220A

ELEV.

LOBBY

CORRIDOR

C26

CORRIDOR

C28

CORRIDOR

C30

HAC

STOR.

CORRIDOR

C24

CORRIDOR

C36

SUITE

PASSAGE

C34

STORAGE

W

D

CLOSET

CLOSET

203A

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

CLOSET

BATH

257A

BATH

236A

CEN. MEDICAL

SUPPLY

FULLY SPRINKLERED

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

FULLY SPRINKLERED

SCHEMATIC SUBMISSION - NOT FOR CONSTRUCTION

100% BID DOCUMENT SUBMISSION

COMPLETION ITEM NO.

95% CONSTRUCTION DOCUMENTS

DESIGN DEVELOPMENT - NOT FOR CONSTRUCTION

SCHEMATIC DESIGN_REV, MOD P00001 SUBMISSION

95% CONSTRUCTION DOCUMENTS SUBMISSION

NOT FOR CONSTRUCTION

TU-1-13

TU-1-12

TU-1-11

TU-1-9

TU-1-10

TU-1-8

TU-1-7

TU-1-6

TU-1-5

TU-1-4

TU-1-3

TU-1-2

TU-1-1

TU-1-16

TU-1-14

TU-1-15

TU-1-18

TU-1-17

TU-2-6

TU-2-5

TU-2-2

TU-2-4

TU-2-3

TU-2-1

TU-2-7

TU-2-8

TU-2-10

TU-2-9

TU-2-11

TU-2-12

TU-2-14

TU-2-13

TU-2-15

TU-2-16

TU-2-17

TU-2-18

TU-2-19

TU-2-20

TU-2-21

TU-2-22

TU-2-23

3/4"

3/4"

3/4" HWS/R

1" HWS/R

1" HWS/R

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4" HWS/R

1" HWS/R

1" HWS/R 1-1/2" HWS/R

1-1/2" HWS/R

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

1-1/2" HWS/R

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

1" HWS/R

3/4" HWS/R

1" HWS/R

3/4" HWS/R

1" HWS/R

1-1/2" HWS/R

3/4" HWS/R

3/4"

3/4"

3/4"

1-1/2" HWS/R

PROVIDE ISOLATION

VALVES

PROVIDE ISOLATION

VALVE

PROVIDE ISOLATION

VALVES

PROVIDE ISOLATION

VALVES

NORTH

SCALE:

SECOND FLOOR PIPING NEW WORK PLAN

1/8" = 1'-0"

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

GENERAL ELECTRICAL NOTES

A.

THESE DRAWINGS REPRESENT THE GENERAL EXTENT AND ARRANGEMENT OF

SYSTEMS, BUT ARE NOT TO BE CONSIDERED FABRICATION DRAWINGS. THESE

DRAWINGS ARE SUPPLEMENTARY TO THE PROJECT SPECIFICATIONS. COORDINATE

WITH OTHER TRADES, AND PROVIDE EACH SYSTEM COMPLETE, INCLUDING ALL

NECESSARY COMPONENTS, FITTINGS, AND OFFSETS.

B.

INSTALL SYSTEMS SUCH THAT CODE REQUIRED WORKING CLEARANCE AND

DEDICATED EQUIPMENT SPACE ALONG WITH SERVICE ACCESS SPACE IS PROVIDED

AROUND ALL MECHANICAL AND ELECTRICAL EQUIPMENT, AND AROUND ANY

COMPONENTS WHICH REQUIRE SERVICE ACCESS.

C.

COORDINATE AND PROVIDE ACCESS DOORS WITHIN INACCESSIBLE CEILING, SHAFT,

AND CHASE AREAS FOR ALL COMPONENTS WHICH REQUIRE SERVICE ACCESS.

REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES AND PARTITION RATINGS.

ACCESS DOORS IN FIRE RATED SURFACES SHALL MAINTAIN THE FIRE RATING OF THE

PARTITION.

D. PROVIDE ALL MISCELLANEOUS STEEL AND HARDWARE TO SUPPORT ALL

DEVICES AND EQUIPMENT AS INDICATED IN THE SPECIFICATIONS.

E. REFER TO MECHANICAL/ELECTRICAL SCHEDULE DRAWING(S) FOR ELECTRICAL

REQUIREMENTS FOR MECHANICAL EQUIPMENT. PROVIDE ALL CONNECTIONS,

STARTERS, DISCONNECTS, EQUIPMENT, AND DEVICES AS INDICATED ON THE

SCHEDULES AND WHERE ELSEWHERE NOTED. PROVIDE THE CIRCUIT OF

HIGHER AMPACITY WHERE CIRCUIT SIZES ARE SHOWN ON THE ELECTRICAL

DRAWINGS THAT DIFFER FROM WHAT IS INDICATED ON THE MECHANICAL

SCHEDULES.

F. VERIFY REQUIREMENTS OF ALL MECHANICAL EQUIPMENT WITH EQUIPMENT

SHOP DRAWINGS PRIOR TO ORDERING MATERIALS. NOTIFY THE ENGINEER OF

ANY DISCREPANCIES BETWEEN THE EQUIPMENT SHOP DRAWINGS AND

ELECTRICAL DRAWINGS. OBTAIN DIRECTION FROM THE ENGINEER PRIOR TO

ORDERING MATERIALS WHERE DISCREPANCIES EXIST.

G. PROVIDE NEW OVERCURRENT PROTECTIVE DEVICES TO MATCH EXISTING

EQUIPMENT WHERE NEW OVERCURRENT PROTECTIVE DEVICES ARE

REQUIRED TO SERVE NEW LOADS FROM EXISTING EQUIPMENT.

H.

TRANSFORMER CONDUCTORS SHALL BE SIZED IN ACCORDANCE WITH THE

NEC UNLESS NOTED OTHERWISE.

I.

MOTOR CIRCUIT PROTECTION SHALL BE SIZED IN ACCORDANCE WITH THE NEC

UNLESS NOTED OTHERWISE.

J.

TYPICAL 20A HOMERUN CIRCUIT IS 3/4"C., 2#12 & 1#12 GND (CU), UNLESS

OTHERWISE NOTED. SHARED NEUTRALS ARE PROHIBITED. REFER TO THE

FOLLOWING TABLE FOR MAXIMUM DISTANCE FOR BRANCH CIRCUIT WIRING:

AWG 120V, 20A CICUIT 277V, 20A CIRCUIT

#12 65FT 150FT

#10 105FT 245FT

#8 160FT 375FT

K. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS

(EXCEPT WALL PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK

BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE FOR ALL

SIMILAR DEVICES.

L. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME

MOUNTING HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES

SO THAT THERE IS ONE INCH BETWEEN ADJACENT VERTICAL EDGES OF

THE FACEPLATES, UNLESS OTHERWISE NOTED.

M. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE

LOCATED IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR

CENTERLINES.

N. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATED LOCATIONS OF

TYPICAL ELECTRICAL DEVICES. VERIFY MOUNTING HEIGHTS OF ALL OUTLETS.

O. TYPICAL MOUNTING HEIGHTS ARE INDICATED ON THE ARCHITECTURAL

DRAWINGS. COORDINATE THE MOUNTING HEIGHT OF DEVICES AND

EQUIPMENT INDICATED ON THESE DRAWINGS THAT ARE INDICATED AT

DIFFERENT MOUNTING HEIGHTS THAN THOSE INDICATED ON THE

ARCHITECTURAL DRAWINGS WITH THE ARCHITECT AND/OR ENGINEER PRIOR

TO INSTALLATION.

P.

WHERE THE NUMBER OF CURRENT-CARRYING CONDUCTORS IN A RACEWAY

EXCEEDS THREE, THE ALLOWABLE AMPACITY OF EACH CONDUCTOR SHALL

BE REDUCED AS SHOWN IN THE ADJUSTMENT FACTOR TABLE IN THE

NATIONAL ELECTRICAL CODE. LOAD DIVERSITY FACTORS SHALL NOT BE USED

IN SIZING BRANCH CIRCUIT CONDUCTORS.

Q. CONTRACTOR SHALL PROVIDE UPDATED, TYPED PANEL DIRECTORIES FOR ALL

PANELBOARDS MODIFIED DURING DEMOLITION AND/OR CONSTRUCTION. ANY

CIRCUITS MADE AVAILABLE DURING DEMOLITION AND NOT RE-USED DURING

CONSTRUCTION SHALL BE MARKED "SPARE".

R.

PROVIDE A DISCONNECTING MEANS FOR ALL LIGHTING FIXTURES PER NEC

SECTION 410.130.G.1.

S.

COORDINATE ANY SHUT DOWN OF EXISTING SERVICES AND EQUIPMENT THAT ARE

REMAINING IN USE WITH THE OWNER'S REPRESENTATIVE. WHERE EXISTING

BUILDING SERVICE IS REQUIRED TO BE SHUT DOWN, INCLUDE ALL ASSOCIATED

OVERTIME COST TO PERFORM THIS WORK DURING WEEKENDS AND EVENINGS,

INCLUDE ALL COSTS FOR PROVIDING TEMPORARY POWER WHERE SHUT DOWNS

MUST OCCUR FOR PERIODS LONGER THAN THESE HOURS. COORDINATE ELECTRICAL

SHUT DOWNS WITH THE OWNER 72 HOURS PRIOR TO SHUT DOWN.

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

SCALE:

1. REMOVE THE EXISTING PANEL AND ALL ASSOCIATED CONDUIT AND WIRING BACK TO THE

SOURCE.

2. EXISTING CONDUIT AND WIRING SHALL REMAIN. PROTECT IN PLACE DURING

CONSTRUCTION.

3. EXISTING CIRCUIT 20 FEEDING THE EXISTING DDC CONTROL PANEL LOCATED IN THE ATTIC

SHALL BE RE-FED FROM AN EXISTING SPARE 20A-1P CIRCUIT BREAKER IN EXISTING PANEL

SB3A LOCATED IN THE ATTIC. PROVIDE 2#12, 1#12GND IN 3/4" CONDUIT TO RE-FEED THE

EXISTING DDC CONTROL PANEL.

4. REMOVE ALL ITEMS ASSOCIATED WITH ELECTRICAL SYSTEMS SERVING THE SECOND FLOOR

UNLESS NOTED OTHERWISE. ANY EXISTING ITEMS ASSOCIATED WITH THE ELECTRICAL

SYSTEMS SERVING OTHER FLOORS SHALL REMAIN AND SHALL BE PROTECTED IN PLACE

DURING CONSTRUCTION.

5. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE EXISTING

ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND SHALL REMAIN

OPERATIONAL.

6. REMOVE THE EXISTING PANEL. THE EXISTING FEEDER CONDUIT AND WIRING FROM EXISTING

PANEL SBDP3A LOCATED IN THE ATTIC SHALL REMAIN AND SHALL BE REVISED TO CONNECT

TO THE NEW PANELS AS INDICATED ON DRAWINGS EP121 AND EP601.

7. REMOVE EXISTING PULL BOX MOUNTED IN FIRST FLOOR CEILING SPACE. REFER TO SHEET

ED601 FOR ADDITIONAL REQUIREMENTS.

DEMOLITION KEYNOTES

GENERAL DEMOLITION NOTES

A. VISIT THE SITE PRIOR TO SUBMISSION OF BID TO EXAMINE THE EXISTING CONDITIONS

AND THE EXTENT OF DEMOLITION WORK.

B.

EXAMINE THE DRAWINGS OF OTHER TRADES AND BE FAMILIAR WITH THE DEMOLITION

REQUIRED BY OTHER TRADES. PERFORM ALL INCIDENTAL ELECTRICAL DEMOLITION AND/OR

RELOCATION REQUIRED TO FACILITATE THE DEMOLITION WORK OF OTHER TRADES, WHETHER

OR NOT SPECIFICALLY INDICATED.

C. ITEMS NOTED SHALL BE DEMOLISHED AND ALL ASSOCIATED DEVICES, CONDUIT, AND

WIRING SHALL BE REMOVED BACK TO THE SOURCE UNLESS NOTED OTHERWISE.

D. ALL EXISTING EQUIPMENT MAY NOT BE INDICATED. CONTRACTOR SHALL FIELD VERIFY

EXISTING CONDITIONS PRIOR TO BIDDING. EXISTING ITEMS SHALL REMAIN IN

OPERATION UNLESS NOTED OTHERWISE. REVISE THE EXISTING CIRCUITRY TO

MAINTAIN OPERATION OF ITEMS TO REMAIN.

E.

PROVIDE PROPER SUPPORT FOR EXISTING TO REMAIN CONDUITS AND BOXES WHERE

EXISTING SUPPORT IS TO BE REMOVED. RE-ROUTE BRANCH CIRCUIT CONDUITS AND

RELOCATE JUNCTION BOXES TO FACILITATE INSTALLATION OF NEW EQUIPMENT AND SYSTEMS

IN CEILING SPACES.

F.

COORDINATE WITH NEW WORK PLANS AND ONE-LINE DIAGRAMS FOR EXTENT OF DEMOLITION

WORK.

G. CIRCUITING SHOWN IS BASED ON CASUAL FIELD OBSERVATIONS AND/OR AS-BUILT

DRAWINGS. CONTRACTOR SHALL FIELD VERIFY CIRCUITING.

H.

MAINTAIN ELECTRICAL SERVICE TO ALL LIGHTING FIXTURES, DEVICES AND EQUIPMENT THAT

ARE TO REMAIN. EXTEND CONDUIT AND WIRE AS REQUIRED WHERE DEMOLITION WORK

AFFECTS ELECTRICAL SERVICE TO DOWNSTREAM LOADS THAT ARE TO REMAIN.

I.

DISPOSE OF ALL MATERIALS OFF SITE AND INCLUDE ALL COSTS FOR DISPOSAL IN BID. ALL

MATERIALS SHALL BE DISPOSED OF IN ACCORDANCE WITH ALL FEDERAL, STATE, AND LOCAL

REGULATIONS, INCLUDING TCLP TESTING, PROPER DISPOSAL AND/OR RECYCLING OF

FLUORESCENT LAMPS.

J.

RING OUT AND TAG ALL CIRCUITS AFFECTED BY THIS ALTERATION AT BOTH ENDS. MARK ALL

UNUSED CIRCUIT BREAKERS “SPARE” AND TURN OFF.

K.

VERIFY ALL UNDERGROUND AND IN SLAB UTILITY LOCATIONS PRIOR TO SAW-CUTTING OR

PENETRATING ANY FLOOR SLAB.

L.

OFFER OWNERS REPRESENTATIVE FIRST RIGHT OF REFUSAL OF ALL EQUIPMENT REMOVED

FROM SPACE.

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

1. REMOVE THE EXISTING FLUSH MOUNTED PULL BOX

AND PATCH THE EXISTING WALL TO MATCH THE

ADJACENT FINISH.

DEMOLITION KEYNOTES

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

W

D a a b c c aa a a b a b b a a c b b a c b b b c a b b a b a a c b b c a b c a a c b b a b c a b b a b a b c b a c b a b b b a a a a b aa a a c ba ba b aa a a a a a a b a a b c a b c a a b c a

3a

3a 3a

3a

3a a

3a

3a 3a a a

3a a a a

Db

Db

D a

Db

D a

D b

D b

D b b a a c a a a a

D b b b b c b c

D b b

D a a b c a a

D b a a a b c

D b

D a b a

D b

D a b c b a a b c b

D a a ba aa

D a b c b b a a a a

3Da

3Da a

D a b c b a a a a b c b b c b a a

3Da b c bb a

Da

D a a

D a

D b b a b b b b

D D

D b

D a

Db3Da Db3Da

D b

D a

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1

LG1LG1 LG1

LG1

LG1

D

LG1LG1

LG1

LG1

LG1

LG1

LG1 LG1

LG1

LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2LG2

LG2

LG1

LG1

LG1

LG2

LG2

LG1

LG1

LG1

LG1

LG1

LG1

LG1 LG1

D D

D

D

LG1

LG1

a b

LG1

LG2

LG2

LG2

LG2

D

LA1

LA1

LA1

LA1

LA1

LA1

LA1

LA1

LA1LA1

LA1LA1

LA1

LA1

LB1

LA1 LA1

LA1

LA1

LA1

LA1

LA1

LA1

LA1

LB1

LB1

LA1

LA1

LA1LA1

LA1LA1

LB1

LA1

LA1

LA1 LA1 LA1

LA1LA1

LA1

LA1 LA1

LA1

LA1

LA1

LA1

LA1

LA1 LA1

LA1 LA1

LA1

LA1

LA1

LB1

LA1

LA1LA1

LA1LA1

LB1

LA1

LA1

LA1LA1

LA1LA1

LA1LA1

LA1

LA1

LB1

LA1

LA1LA1

LA1 LA1 LA1

LA1LA1LA1

LA1 LA1 LA1LA1

LA1

LA1

LA1

LB1

LA1

LA1

LA1LA1

LA1

LA1

LG1

LG1

LB1

LA1LA1LA1

LA1

LA1

a

LG1

LG1

LA1

LB1

LA1

LA1 LA1

LA1

LA1LA1

LA1

LB1

LA1

LA1LA1

LA1 LA1

LA1 LA1

LA1

LA1LA1

LA1

LA1

LB1

LA1LA1

LA1LA1

LA1LA1

LA1

LA1

D

LA1 LA1

LA1

LB1

LG1

LG1

LA1LA1

LA1

LA1 LA1

LA1

LA1

LA1

LA1 LA1 LA1

LA1LA1 LA1

LA1

LB1

LA1

LA1 LA1 LA1

LA1

LA1 LA1 LA1

c

LB1

LG1 LG1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

LE1

D

T

T

LG2

LG2

LG2

LA1

O S a b c

LH1

LH1

D

LG1LG1

LG1 LG1

VS

O S

VS

VS

VS

VS

b a

LA1LA1

VS

VS

VS

VS

LG1

VS

VS

VS

O S

VS

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

NORTH

SCALE:

1. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE

EXISTING ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND

SHALL REMAIN OPERATIONAL.

2. PROVIDE 2#12, 1#12GND IN 3/4" CONDUIT TO CONNECT THE NEW LIGHT

FIXTURE TO THE EXISTING CIRCUIT AND CONTROLS SERVING ADJACENT

STAIR.

3. CONNECT CORRIDOR LIGHTING TO PANEL SB2B CIRCUIT NUMBER 6 VIA

LIGHTING CONTROL PANEL LCP2A.

4. PROVIDE A BODINE BLCD-20A GENERATOR TRANSFER DEVICE FOR EACH

SWITCHES CIRCUIT, FOR LOCAL CONTROL OF EMERGENCY FIXTURES.

LOCATE DEVICE IN CEILING SPACE.

5. CONNECT CORRIDOR LIGHTING TO PANEL SB2C CIRCUIT NUMBER 35 VIA

LIGHTING CONTROL PANEL LCP2A.

PLAN NOTES

LD1

LC1

LD1

LS2A-1

LC1

LD1

LC1

LD1

LS2A-1

LD1

LS2A-1

LC1

LD1

LC1

LC1

LC1

LC1

LC1

LC1

LC1

LD1

LS2A-1

LC1

LD1

LS2A-1

LC1

LD1

LS2A-1

LF1 LF1

GENERAL LIGHTING NOTES

A. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL

LIGHTING FIXTURES UNLESS NOTED OTHERWISE.

B. REFER TO THE LUMINAIRE SCHEDULE LOCATED ON DRAWING EP501.

C. ALL ELECTRICAL DEVICES INDICATED ON THIS PLAN SHALL BE NEW UNLESS NOTED

OTHERWISE.

D. LIGHT SWITCHES SHALL BE GROUPED UNDER ONE COMMON FACEPLATE WHERE MORE

THAN ONE LIGHT SWITCH IS INDICATED TO BE INSTALLED AT THE SAME LOCATION.

E. ALL LIGHTING BRANCH CIRCUIT WIRING ASSOCIATED WITH NEW LIGHTING SHALL BE

2#12, 1#12GND IN 3/4"C UNLESS NOTED OTHERWISE.

F. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED

SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION

TO SUCH EQUIPMENT/DEVICES AS REQUIRED.

G. ALL NIGHT LIGHTS AND EXIT SIGNS SHALL BE UNCONTROLLED AND CONNECTED

AHEAD OF THE LOCAL LIGHTING CONTROLS.

H. ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.

LC1

LC1

LC1

LD1

LC1

LC1

LS2A

SB2A

LS2B

SB2C

SB2B

LD1

LS2A-1

LCP2A

SB2B-8

SB2B-8

SB2B-8

SB2B-8

SB2B-6

SB2B-10

SB2B-10

SB2B-10

SB2B-10

SB2B-10

SB2B-10

SB2B-10

SB2B-16 SB2B-16

SB2B-12

SB2B-12

SB2B-12

SB2B-12

SB2B-14

SB2B-14

SB2B-14

SB2B-14

SB2B-8

SB2B-6

SB2B-6

SB2B-6

SB2B-6

(TYP.)

NL

NL

NL

NL

LS2A-1

LS2A-1

LD1

LS2A-1

LS2A-1

LS2A-1

LS2A-1

LS2A-1

LS2A-1

LS2A-1LS2A-1LS2A-1

SB2B-14

LD1

LS2A-1

LD1

LS2A-1

LD1

LS2A-1

LD1

LS2A-1

LD1

LS2A-1

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

SB2B-18

SB2B-18

SB2B-18

SB2B-16

SB2B-16

SB2B-16

SB2B-16

SB2B-16

SB2B-16

SB2B-16

SB2B-16

(TYP.)

SB2B-16

LD1

LS2B-1

LD1

LS2B-1

LD1

LS2B-1

LD1

LS2B-1

LD1

LS2B-1

LD1

LS2B-1

LD1

LS2B-1

LD1

LS2B-1

LD1

LS2B-1

SB2B-37

SB2B-37

SB2B-35

LS2B-1

LS2B-1

LS2B-1

LS2B-1

LS2B-1

LS2B-1

LS2B-1

LS2B-1

LS2B-1

SB2B-37

SB2B-37

SB2B-35

SB2B-35

SB2B-39

SB2B-39

SB2B-37

SB2B-37

LD1

LS2B-1

LD1

LS2B-1SB2B-35

SB2B-39

SB2C-41

SB2C-41

SB2C-41

SB2C-41

SB2C-39

SB2C-41

SB2C-41

SB2C-39

LD1

LS2B-1

SB2B-37

SB2B-39

SB2B-39

SB2C-35

LD1

LS2B-1

NL

NL

SB2B-18

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

1. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE EXISTING

ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND SHALL REMAIN

OPERATIONAL.

PLAN NOTES

(E)SWBD0A

(E)SBATS0A

(E)SBDP0A

(E)ESWBD0A

(E)LSDP0A

(E)LSATS0A

(E)SBATS0B

SCALE:

GENERAL POWER NOTES

A. REFER TO ARCHITECTURAL FLOOR PLAN AND ELEVATIONS FOR EXACT LOCATION OF

DEVICES WHERE INDICATED.

E. ALL JUNCTION BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.

G. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED

SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION

TO SUCH EQUIPMENT/DEVICES.

H. ALL CONDUITS IN FINISHED SPACES SHALL BE ROUTED CONCEALED UNLESS NOTED

OTHERWISE.

L. PROVIDE A METAL RACEWAY SYSTEM THAT QUALIFIES AS AN EQUIPMENT GROUND

CONDUCTOR IN ACCORDANCE WITH SECTION 250.118 OF THE NEC IN PATIENT CARE

AREAS AS REQUIRED BY SECTION 517.13 OF THE NEC. AN INSULATED EQUIPMENT

GROUND CONDUCTOR SHALL BE PROVIDED IN ADDITION AS INDICATED IN SECTION

517.13 OF THE NEC.

PULLBOX

PULLBOX

UP TO

SECOND

FLOOR

http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com http://www.ssoe.com

W

D

SSOE, Inc.

Project #

Troy, MI 48084

Suite 260

T 248-643-6222

1050 Wilshire Drive

015-02007-00

100% BID DOCUMENT SUBMISSION

SCALE:

1. THE EXISTING ELEVATOR SHALL REMAIN. ALL ITEMS ASSOCIATED WITH THE EXISTING

ELEVATOR SHALL BE PROTECTED DURING CONSTRUCTION AND SHALL REMAIN

OPERATIONAL.

2. PROVIDE A NEMA 14-30R TYPE RECEPTACLE. CONNECT RECEPTACLE TO CIRCUIT INDICATED

ON PLANS USING 3#10,1#10G IN 3/4" CONDUIT.

PLAN NOTES

LS2A

SB2A

LS2B

SB2C

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

GFI

44"

36"

36"

GFI

AFC

GFI

GFI

44"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

TV

66"

GFI

TV

66"

TV

66"

TV

66"

GENERAL POWER NOTES

A. REFER TO ARCHITECTURAL FLOOR PLAN AND ELEVATIONS FOR EXACT LOCATION OF

DEVICES WHERE INDICATED.

B. ALL RECEPTACLE OUTLETS SHALL BE HOSPITAL GRADE RATED 20A.

C. PROVIDE GFI PROTECTION WHERE REQUIRED BY THE NEC WHETHER INDICATED OR

NOT.

D. ALL JUNCTION BOXES SHALL BE LABELED WITH THE CIRCUITS ENCLOSED.

E. ALL 20A BRANCH CIRCUIT WIRING SHALL BE 2#12, 1#12GND IN 3/4"C UNLESS NOTED

OTHERWISE.

F. ALL EXISTING EQUIPMENT/DEVICES NOT SPECIFICALLY INDICATED TO BE DEMOLISHED

SHALL REMAIN OPERATIONAL. REVISE EXISTING CIRCUITING TO MAINTAIN OPERATION

TO SUCH EQUIPMENT/DEVICES.

G. ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.

H. PROVIDE A METAL RACEWAY SYSTEM, METALLIC CABLE ARMOR, OR SHEATH

ASSEMBLY THAT QUALIFIES AS AN EQUIPMENT GROUND CONDUCTOR IN ACCORDANCE

WITH SECTION 250.118 OF THE NEC IN PATIENT CARE AREAS AS REQUIRED BY SECTION

517.13 OF THE NEC. AN INSULATED EQUIPMENT GROUND CONDUCTOR SHALL BE

PROVIDED IN ADDITION AS INDICATED IN SECTION 517.13 OF THE NEC.

48"

(1)

48"

GFI

44"

48" (25)

48"

48"

GFI

(21)

GFI

AFC

GFI

SB2B

LIFT

LIFT

LIFT

LIFT

LIFT

LIFT

LIFT

LIFT

LIFT

LIFT

LIFT

GFI

SECURITY CAMERA HEAD END

SB2C-43

NURSE CALL

HEAD END

FIRE ALARM

PANEL

GFI

GFI

44"

GFI

44"

GFI

44"

(20)

FIREPLACE

TV

66"

GFI

GFI

GFI

AFC

FIREPLACE

LCP2A

GFI

44"

GFI

AFC

GFI

GFI

(27)

GFI

AFC

GFI

GFI

AFC

GFI

AFC

GFI

AFC

GFI

AFC

LIFT

(24)

(24)

(24)(24)

(22)

(22)

(22)

SB2C

SB2C-29

(32)

(32)

(32)

(32)

(30)

(30)

(30)

(30)

(30)

SB2C

(29)

(29)

SB2C-29

AFC

SB2C-29

SB2C-29

SB2C-31

SB2C-31

SB2C-31

SB2C-31

SB2C-31

SB2C-31

SB2C-33

(30)

SB2C

FRIDGE

(28)

DISHWASHER

(34, 36, 38)

MICROWAVE

(30)

(30)

(10)

(10)

(10)

SB2C

(12)

(12)

(12)

(12)

(16)

(16)

(16)

(16)

(14) (14)

SB2C

SB2C

DRYER

(40,42)

GFI

(27)

SB2C-27

SB2C-27

SB2C-27

SB2C-27

(25)

AFC

GFI

(25)

SB2C

(20)

(20)

(20)

(18)

(18) (18)

SB2C

SB2C-19

(21)

(21)

(21)

SB2C

(23)

FRIDGE

U/C

(19)

(19)

(19)

(19)

SB2C

AFC

SB2C-19

(4)

(4)

(2)

(2)

(2)

(2)

SB2C

(2)

SB2C-17

SB2C-17

(8) (8)

(8)

(8)

(8)

(6)

(6)

SB2C

(7)

(7)

SB2B

(5)

SB2B-7

(7) (3)

(5)

(5)

(5)

(5)

(5)

(19)

(3)

SB2B

SB2B-3

SB2B-3

SB2B-3

GFI

AFC

GFI

AFC

(1)

(1)

(1)

(4)

SB2C

(4)

(4)

(4)

(4)

(2)

(2)

SB2B

SB2C-1

SB2C

SB2C

SB2C

SB2C

SB2C

(15)

(15)

(15)

(15)

(15)

SB2C-19

(13)

(13)

(13)

(13)

(13)

(11)

(11)

(11)

(11)

(11)

(9) (9)

(9) (3)

(3)

AFC

GFI

AFC

(3)

(3)

(3)

(5)

MICROWAVE

(7)

36"

FRIDGE

SB2B

SB2B-3

(1)

(28)

SB2A

(28)

(28)

(24)

(26)

(24)

U/C FRIDGE

GFI

AFC

(19)

(19)

(19)

(19)

(17)

(17)

SB2A

(13)

(13)

(13)

(15)

(15)

(15)

(15)

SB2A-6

SB2A-6

SB2A

(11)

(11)

(11)

(9)

(9)

SB2A-6

SB2A-6

SB2A-6

SB2A-6

SB2A-6

SB2A-8

SB2A-8

SB2A-8

SB2A-8

SB2A-10

SB2A-10

SB2A-10

SB2A-10

SB2A-11

(7)

(7)

(5)

(5)

(7)

(7)

(3)

(3)

(3)

(3)

(3)

(1)

(1)

SB2A

AFC

(34)

AFC

(32)

SB2A-4

(22) (20)

SB2A

(14)

MICROWAVE

(18)

(14)

DISHWASHER

(30, 32, 34)

SB2A-12

(14)

(14)

FRIDGE

(16)

GFI

AFC

GFI

AFC

GFI

AFC

GFI

AFC

SB2A-4

SB2A-4

SB2A-2

AFC

SB2A-2

SB2A-2

(25)

(25)

(27)

(25)

SB2A

(27)

(27)

(27)

SB2A-2

SB2A-2

SB2A-2

(23)

(23)

(23)

(23)

(23)

(21)

(21)

SB2A

48"

48"

(14)

SB2A-42

48"

48"

48"

(1)

48"

(1)

SB2C-1

SB2C-27

48" (25)

48" (25)

(25)

TU-1-1

SB2C-45

TU-1-13

SB2C-45

TU-1-2

SB2C-45

TU-1-4

SB2C-45

TU-1-5

SB2C-45

TU-1-6

SB2C-45

TU-1-7

SB2C-47

TU-1-8

SB2C-47

TU-1-10

SB2C-47

TU-1-9

SB2C-47

TU-1-12

SB2C-47

TU-1-13

SB2C-47

TU-1-11

SB2C-47

TU-1-14

SB2C-49

TU-1-15

SB2C-49

TU-1-16

SB2C-49

TU-1-17

SB2C-49

TU-1-18

SB2C-49

TU-2-6

SB2B-9

TU-2-5

SB2B-9

TU-2-3

SB2B-9

TU-2-1

SB2B-9

TU-2-2

SB2B-9

TU-2-4

SB2B-9

TU-2-7

SB2B-11

TU-2-8

SB2B-11

TU-2-9

SB2B-11

TU-2-10

SB2B-11

TU-2-12

SB2B-11

TU-2-13

SB2B-11

TU-2-11

SB2B-13

TU-2-18

SB2B-13

TU-2-17

SB2B-13

TU-2-16

SB2B-13

TU-2-14

SB2B-13

TU-2-15

SB2B-13

TU-2-19

SB2B-15

TU-2-20

SB2B-15

TU-2-21

SB2B-15

TU-2-23

SB2B-17

TU-2-22

SB2B-15

TU-2-25

SB2B-17

TU-2-24

SB2B-17

SB2C

SB2C

SB2C

SB2C

SB2C

SB2A

SB2A

SB2A

SB2A

SB2A

SB2A

SB2A

SB2C

DOWN TO

BASEMENT

SB2A

SB2A

ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg ftp://image.autodesk.com/drawing/WHEEL_CHAIR_WITH_MAN_PV.dwg…