36C24918R0163-013.pdf
PDF 6 MB Posted
- Attached to
- Construct Parking Garage on West Lot - Project 614-320 Federal contract opportunity
- Solicitation number
- 36C24918R0163
About this file
36C24918R0163 Structural.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24918R0163-00004000.docx | DOCX document | |
| 36C24918R0163-00003008.pdf | ||
| 36C24918R0163-00003006.docx | DOCX document | |
| 36C24918R0163-00003007.pdf | ||
| 36C24918R0163-00002000.docx | DOCX document | |
| 36C24918R0163-00001000.docx | DOCX document | |
| 36C24918R0163-011.pdf | ||
| 36C24918R0163-014.docx | DOCX document | |
| 36C24918R0163-006.pdf | ||
| 36C24918R0163-010.pdf | ||
| 36C24918R0163-003.xlsx | XLSX spreadsheet | |
| 36C24918R0163-007.pdf | ||
| 36C24918R0163-004.pdf | ||
| 36C24918R0163-005.pdf | ||
| 36C24918R0163-002.docx | DOCX document | |
| 36C24918R0163-009.pdf | ||
| 36C24918R0163-012.pdf | ||
| 36C24918R0163-016.pdf | ||
| 36C24918R0163-008.pdf | ||
| 36C24918R0163-015.xlsx | XLSX spreadsheet | |
| 36C24918R0163-001.docx | DOCX document | |
| 36C24918R0163-000.docx | DOCX document |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MISCELLANEOUS SYMBOLS
NORTH ARROW
GRIDLINES
EARTH
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
F ## COLUMN FOOTING NOTATION
GB ## GRADE BEAM NOTATION
P ## PIER NOTATION
B ## CONCRETE BEAM NOTATION
PC ## PILE CAP NOTATION
WF ## WALL FOOTING NOTATION
SHEAR WALL NOTATIONSW ##
BW ## BEARING WALL NOTATION
GRAVEL
Name
Elevation
TF ## TRENCH FOOTING NOTATION
FLOOR DRAIN
FD
N
20 GA. 3" ROOF DECK
DIRECTION OF SPAN
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
MEMPHIS, TN
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
614-319
MEMPHIS VAMC
1030 JEFFERSON AVE, MEMPHIS, TN 38104
ARCHITECT/ENGINEERS:
MEP Engineer
APOGEE CONSULTING
GROUP
1151 Kildaire Farm Rd.
Suite 120 Cary, NC 27511
Tele: 919-858-7420
Functional Design
CARL WALKER INC.
3211 Internet Blvd., Suite 220 Frisco, TX 75034
Tele: 469-777-5143
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
C U s e rs
\b th o m a s \D o c u m e n ts
\1 .1
-S
-M e m p h is
V A
-G a ra g e W
J T h o m a s .r v t
BID SET
SI001
WJTMAV
ABBREVIATIONS AND SYMBOLS
11/14/2016
15.1067CONSTRUCT PARKING GARAGE
ON WEST LOT
JST JOIST
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABORATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
P PIER
PC PIER CAP OR PRECAST
PCC PRECAST CONCRETE
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PREL PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST-TENSIONED
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
SCH SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SL SLOPE
SL-DN SLOPE DOWN
SL-UP SLOPE UP
SOG SLAB-ON-GRADE
SP SHEET PILING
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TEMP TEMPERATURE
TF TRENCH FOOTING
THRU THROUGH
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WF WALL FOOTING
WP WORK POINT
WWF WELDED WIRE FABRIC
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ACP AUGER CAST PILE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BD BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOTT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
CW CONCRETE WALL
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DRILLED PIER OR DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FAB FROM ADJACENT BEAM
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FOOTING STEP
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GRND GROUND
GT GIRDER TRUSS
HAS, HS HEADED ANCHOR STUD
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HS HOLLOW STRUCTURAL SECTION
HT HIP TRUSS
HVAC HEATING, VENTILATION, AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J/BRG JOIST BEARING
STRUCTURAL DRAWINGS ABBREVIATIONS
STRUCTURAL SHEET LIST
SHEET NUMBER SHEET NAME
SI001 ABBREVIATIONS AND SYMBOLS
SI002 LOAD MAPS
SI003 STRUCTURAL GENERAL NOTES
SB101 FOUNDATION PLAN
SB401 ENLARGED FOUNDATION PLANS
SB501 TYPICAL FOUNDATION SECTIONS AND DETAILS
SB502 FOUNDATION SECTIONS AND DETAILS
SB601 FOUNDATION SCHEDULES, SECTIONS AND DETAILS
SF101 SLAB-ON-GRADE PLAN
SF102 LEVEL 2 FRAMING PLAN
SF103 LEVEL 3 FRAMING PLAN
SF201 BUILDING ELEVATIONS
SF202 SHEARWALL ELEVATIONS AND SCHEDULES
SF203 PRECAST ELEVATIONS
SF401 ENLARGED FRAMING PLANS - STAIR #1 AND #2
SF501 TYPICAL FRAMING DETAILS
SF502 FRAMING SECTIONS AND DETAILS
SF901 ISOMETRIC VIEWS
1 2
A
B
3 4
C
5 6 7 8 9
A
B
D
B B
45 PSF
10 PSF
45 PSF
10 PSF
9.
9.
6,000 LBS ON AN AREA OF 1 SQUARE FOOT
6,000 LBS ON AN AREA OF 1 SQUARE FOOT
1'
9"
2'
PRECAST PANEL, COLUMN, WALL, OR
BARRIER CABLE
NOTES:
1. THE APPLIED HORIZONTAL LOAD CAN ACT IN ANY DIRECTION.
2. THE TWO CONDITIONS DO NOT ACT CONCURRENTLY. DESIGN FOR WORSE CASE CONDITION.
3. LOADS SHOWN ARE UNFACTORED LIVE LOADS.
FLOOR LOAD SCHEDULE
A
B
TYP FLOOR 5 NOTE 1
STAIRS 5
- 40 (NR) 0
100 (NR)
C ROOF 5 20
MARK
DEAD LOAD
(PSF)
DESCRIPTION
SDL
OCCUPANCY/USE
POINT LOAD
(LBS)
DESCRIPTION LIVE LOAD
(PSF)
SNOW LOAD (PSF)
SDL LL SL
NOTE 1
NOTE 1
NOTES:
1. SDL INDICATES SUPERIMPOSED DEAD LOAD AND IS DL IN ADDITION TO THE SELF WEIGHT OF THE PRIMARY STRUCTURAL SYSTEM.
2. (NR) INDICATES NON-REDUCIBLE LIVE LOAD.
D UPPER FLOOR 5 40 (NR)NOTE 1 -- --
10 MINIMUM BALANCED OR
SEE LOAD MAP (DRIFT +
BALANCED)
1 2
A
B
3 4
C
5 6 7 8 9
D
45 PSF
80 PSF
60 PSF
10 PSF
35 PSF
10 PSF
35 PSF
10 PSF
45 PSF
10 PSF
45 PSF
10 PSF
6.73'
35 PSF
10 PSF
10 PSF
45 PSF
60 PSF
10 PSF
60 PSF
10 PSF
15.61'
6.
45 PSF
10 PSF
9.
6.
15.61'
9.
6.
15.61'
9.
9.
.3 4'
1 2
A
B
3 4
C
5 6 7 8 9
C
C
26 PSF
10 PSF
4'
C
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
MEMPHIS, TN
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
614-319
MEMPHIS VAMC
1030 JEFFERSON AVE, MEMPHIS, TN 38104
ARCHITECT/ENGINEERS:
MEP Engineer
APOGEE CONSULTING
GROUP
1151 Kildaire Farm Rd.
Suite 120 Cary, NC 27511
Tele: 919-858-7420
Functional Design
CARL WALKER INC.
3211 Internet Blvd., Suite 220 Frisco, TX 75034
Tele: 469-777-5143
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
C U s e rs
\b th o m a s \D o c u m e n ts
\1 .1
-S
-M e m p h is
V A
-G a ra g e W
J T h o m a s .r v t
BID SET
SI002
WJTMAV
LOAD MAPS
11/14/2016
15.1067CONSTRUCT PARKING GARAGE
ON WEST LOT
SCALE: 3/64" = 1'-0"SI002
1 LEVEL 2 LOAD MAP
SCALE: 1/2" = 1'-0"SI002
3 TYPICAL PRECAST PANEL VEHICLE BARRIER LOADING DIAGRAM
DESIGN DATA
THE BUILDING STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE
2015 INTERNATIONAL BUILDING CODE.
SEE LOAD MAPS FOR FLOOR LOADING CRITERIA.
SNOW LOAD DESIGN DATA
1. GROUND SNOW LOAD (PG) = 10 PSF
2. LOW-SLOPE ROOF SNOW LOAD (PF) = 10 PSF
3. SNOW EXPOSURE FACTOR (CE) = 0.9
4. THERMAL FACTOR (CT) = 1.0
5. SNOW LOAD IMPORTANCE FACTOR (IS) = 1.0
WIND LOAD DESIGN DATA
1. BASIC WIND SPEED (3-SECOND GUST) = 115 MPH
2. WIND EXPOSURE = B
3. WIND DESIGN PRESSURE (P) = VARIES WITH HEIGHT AND LOCATION
EARTHQUAKE DESIGN DATA
1. SHORT PERIOD SPECTRAL RESPONSE (SS) = 1.289
2. 1-SECOND SPECTRAL RESPONSE (S1) = 0.354
3. SEISMIC IMPORTANCE FACTOR (IE) = 1.0
4. OCCUPANCY CATEGORY = II
5. SEISMIC DESIGN CATEGORY = D
6. SITE CLASSIFICATION = D
7. SHORT PERIOD SPECTRAL RESPONSE COEFFICIENT (SDS) = 0.859
8. 1-SECOND SPECTRAL RESPONSE COEFFICIENT (SD1) = 0.399
9. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: INTERMEDIATE PRECAST SHEAR WALLS
10. ANALYSIS PROCEDURE UTILIZED = EQUIVALENT LATERAL FORCE PROCEDURE
11. RESPONSE MODIFICATION COEFFICIENT (R) = 4.0
12. SEISMIC RESPONSE COEFFICIENT (AFTER VERTICAL EXPANSION): EAST-WEST NORTH-SOUTH
(CS) = 0.182 (CS) = 0.215
SCALE: 3/64" = 1'-0"SI002
2 LEVEL 3 LOAD MAP
SCALE: 3/64" = 1'-0"SI002
5 ROOF LOAD MAP
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
MEMPHIS, TN
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
614-319
MEMPHIS VAMC
1030 JEFFERSON AVE, MEMPHIS, TN 38104
ARCHITECT/ENGINEERS:
MEP Engineer
APOGEE CONSULTING
GROUP
1151 Kildaire Farm Rd.
Suite 120 Cary, NC 27511
Tele: 919-858-7420
Functional Design
CARL WALKER INC.
3211 Internet Blvd., Suite 220 Frisco, TX 75034
Tele: 469-777-5143
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
C U s e rs
\b th o m a s \D o c u m e n ts
\1 .1
-S
-M e m p h is
V A
-G a ra g e W
J T h o m a s .r v t
BID SET
SI003
WJTMAV
STRUCTURAL GENERAL NOTES
11/14/2016
15.1067CONSTRUCT PARKING GARAGE
ON WEST LOT
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF
NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES
AND THE FULL SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE
ANY CONCRETE OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION, AND NAME AND LOCATION
OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN ACCORDANCE WITH "STANDARD
DEVIATION" DETERMINATION OUTLINED IN ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP
DRAWINGS WILL BE
REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL
DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF SHOP DRAWINGS. FOR HARD COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF SHOP DRAWINGS TO THE STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED
BY THE
STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT SHOP DRAWINGS IN ADOBE PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. CONCRETE MASONRY REINFORCEMENT
3. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE
STATE WHERE THE PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT SPECIFICALLY DETAILED ON THE
DRAWINGS)
4. PRECAST CONCRETE COMPONENTS (PRECAST LINTELS, ARCHITECTURAL PRECAST)
5. METAL MESH SYSTEM (INCLUDING DESIGN CALCULATIONS AND CONNECTION DETAILS SEALED BY A PROFESSIONAL
ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT IS CONSTRUCTED)
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL
SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF PRODUCT DATA. FOR HARD COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF PRODUCT DATA TO THE STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED BY THE STRUCTURAL ENGINEER). FOR
ELECTRONIC OPTION, SUBMIT PRODUCT DATA IN ADOBE PDF FORMAT.
1. FIBER REINFORCEMENT FOR CONCRETE
2. DIAMOND PLATE DOWELS FOR SLABS ON GRADE
3. CONCRETE CURING COMPOUND
4. CONCRETE JOINT SEALANT
5. WATER STOPS
6. MASONRY JOINT REINFORCEMENT
7. EXPANSION ANCHORS
8. ADHESIVE ANCHORS
9. NON-SHRINK GROUT
FOUNDATIONS
FOUNDATION EXCAVATIONS AND SOIL RELATED WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE GEOTECHNICAL REPORT
NUMBER A8165003 PREPARED BY TERRACON DATED APRIL 25, 2016.
FOUNDATIONS HAVE BEEN DESIGNED BASED ON ASSUMED ALLOWABLE CAPACITIES INDICATED BELOW. CONTRACTOR SHALL ENGAGE A LICENSED GEOTECHNICAL ENGINEER TO REVIEW THE SOIL CONDITIONS AT THE SITE AS NECESSARY TO CONFIRM THE ALLOWABLE CAPACITIES PRIOR TO PLACEMENT OF THE FOUNDATIONS. CONFIRMATION OF THE ACCEPTABILITY OF THE SOILS SHALL BE
REPORTED IN WRITING TO THE STRUCTURAL ENGINEER.
IF ACTUAL ALLOWABLE CAPACITIES ARE FOUND TO BE LESS THAN THE ASSUMED VALUES, THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL NOT PROCEED WITH FOUNDATION CONSTRUCTION WITHOUT REVIEW BY THE
STRUCTURAL ENGINEER.
FOOTING DESIGN NET ALLOWABLE BEARING PRESSURE:
FOOTINGS: NET TOTAL LOAD - 4,000 PSF
FOUNDATIONS AND SOILS RELATED WORK SHALL BE INSPECTED BY A LICENSED GEOTECHNICAL ENGINEER. WRITTEN FIELD REPORTS SHALL BE FORWARDED TO THE STRUCTURAL ENGINEER AS SOON AS THEY BECOME AVAILABLE.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER
CONSTRUCTION IS ATTEMPTED.
EXCAVATIONS FOR SPREAD FOOTINGS, COMBINED FOOTINGS, CONTINUOUS FOOTINGS AND MAT FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED TO UNIFORM SURFACE AND SHALL BE PROTECTED AND MAINTAINED UNIFORM UNTIL CONCRETE IS PLACED.
THE CONTRACTOR SHALL REFERENCE THE SPECIFICATION SECTION 316613 - RAMMED AGGREGATE PIERS FOR IMPLEMENTATION
OF GROUND IMPROVEMENT PROGRAM.
BELOW-GRADE WALLS
DO NOT BACKFILL AGAINST BELOW-GRADE CONCRETE (OR MASONRY) WALLS UNTIL THE CONCRETE (OR MASONRY
ASSEMBLAGE) HAS REACHED ITS 28-DAY COMPRESSIVE STRENGTH.
WHERE BACKFILL IS REQUIRED ON BOTH SIDES OF BELOW-GRADE WALLS, BACKFILL EVENLY ON EACH SIDE OF EACH WALL
TO PREVENT UNBALANCED SOIL LOADS AGAINST THE WALL.
UNLESS NOTED OTHERWISE, DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL THE BASEMENT AND GROUND FLOOR SLABS HAVE BEEN COMPLETELY INSTALLED AND REACHED THEIR 28-DAY COMPRESSIVE STRENGTH AND ALL FLOOR FRAMING AND SLAB CONNECTIONS TO THE BASEMENT WALLS HAVE BEEN COMPLETELY INSTALLED.
WHERE BASEMENT WALLS OCCUR, BACKFILL EVENLY ON ALL SIDES OF THE BUILDING TO PREVENT UNBALANCED SOIL
LOADS AGAINST THE BASEMENT STRUCTURE, UNLESS NOTED OTHERWISE.
SHORING/RE-SHORING
THE SHORING AND/OR RE-SHORING DESIGN FOR CONCRETE FRAME SYSTEMS IS THE RESPONSIBILITY OF THE CONTRACTOR. TEMPORARY SHORING FOR SLABS, BEAMS, AND GIRDERS SHALL BE ADEQUATE TO CARRY THE TOTAL WEIGHT OF THE SLAB-BEAM-GIRDER SYSTEM AND ANY TEMPORARY CONSTRUCTION LOADS TO BE IMPOSED ON THE STRUCTURAL SYSTEM. SHORING FOR A LEVEL SHALL NOT BE REMOVED UNTIL THE CONCRETE AT THAT LEVEL HAS ATTAINED THE SPECIFIED COMPRESSIVE STRENGTH (F'C). REMOVAL OF SHORING AND/OR RESHORING SHALL NOT CAUSE OVERSTRESSING OF ANY STRUCTURAL
ELEMENTS.
CONCRETE SLABS ON GRADE
SLABS ON GRADE SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST EDITION OF THE GUIDE FOR CONCRETE FLOOR AND SLAB
CONSTRUCTION (ACI 302.1R).
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX. DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO ASTM C309, UNLESS NOTED OTHERWISE. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE RECOATED DAILY. OTHER CURING METHODS MAY BE USED
WITH APPROVAL BY THE STRUCTURAL ENGINEER.
UNLESS SHOWN OR NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION JOINTS IN SLABS-ON-GRADE AT A MAXIMUM SPACING OF 36 TIMES THE SLAB THICKNESS. PROVIDE JOINTS AT ALL COLUMN LOCATIONS. LOCATE JOINTS TO ELIMINATE RE-ENTRANT CORNERS AND TO CREATE SQUARE OR RECTANGULAR
SECTIONS WITH MAXIMUM LONG SIDE TO SHORT SIDE RATIO OF 1.5 TO 1.
CONTROL JOINTS IN SLABS ON GRADE SHALL NOT RECEIVE JOINT FILLER MATERIAL UNLESS NOTED OTHERWISE.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND SHALL HAVE A MINIMUM YIELD
STRENGTH OF 60,000 PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING
STANDARDS: ACI 301, ACI 315, ACI 318 AND ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE THE FOLLOWING MINIMUM CONCRETE
COVER OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT UNLESS INDICATED ON THE CONTRACT
DOCUMENTS OR APPROVED BY THE
STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE STANDARD HOOKS, UNLESS NOTED
OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT CORNERS OF ALL WALLS AND GRADE BEAMS.
LAP SPLICE CORNER BARS WITH
STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE) AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND
CORNERS.
FIBER REINFORCEMENT
FIBER REINFORCEMENT SHALL BE 3/4" LONG, VIRGIN (NON-RECYCLED) NYLON OR POLYPROPYLENE FIBERS, INTRODUCED INTO THE CONCRETE MIX AT THE BATCH PLANT, IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. DOSAGE SHALL BE 1.5
POUNDS PER CUBIC YARD OF CONCRETE.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS.
EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING UNLESS DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS SHALL BE
PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED.
THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL CURING BOXES ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER, READY-MIX SUPPLIER AND CONTRACTOR
WITHIN 24 HOURS AFTER TESTING.
MASONRY
CONCRETE MASONRY HAS BEEN DESIGNED IN ACCORDANCE WITH THE LATEST EDITION OF THE BUILDING CODE
REQUIREMENTS FOR CONCRETE MASONRY STRUCTURES (ACI 530).
CONCRETE MASONRY SHALL CONSIST OF HOLLOW UNITS CONFORMING TO THE REQUIREMENTS OF ASTM C90, WITH A MINIMUM NET AREA COMPRESSIVE STRENGTH OF 1900 PSI. CONCRETE MASONRY ASSEMBLAGES SHALL HAVE A MINIMUM
COMPRESSIVE STRENGTH (F'M) OF 1,500 PSI AT 28 DAYS.
MORTAR SHALL BE TYPE S PROPORTIONED IN ACCORDANCE WITH ASTM C270.
GROUT FOR REINFORCED MASONRY SHALL BE PROPORTIONED IN ACCORDANCE WITH ASTM C476. COARSE AND FINE AGGREGATES SHALL CONFORM TO ASTM C404. USE COARSE GROUT FOR ALL GROUTING EXCEPT HIGH-LIFT POURS DEFINED
BY ACI 530 TABLE 1.16.1, WHERE FINE GROUT SHALL BE USED.
PROVIDE 9-GAUGE GALVANIZED STEEL WIRE JOINT REINFORCEMENT IN ALL MASONRY CONSTRUCTION. REINFORCEMENT SHALL BE CONTINUOUS AND BE LAPPED EIGHT INCHES AT SPLICES. CUT REINFORCEMENT AT ALL CONTROL AND EXPANSION JOINTS. SPACE REINFORCEMENT AT 8" ON CENTER FOR PARAPETS AND BELOW GROUND FLOOR ELEVATION. ELSEWHERE
SPACE REINFORCEMENT AT 16 INCHES ON CENTER.
BEAMS AND LINTELS SHALL BEAR A MINIMUM OF 8 INCHES ONTO SUPPORTING MASONRY, UNLESS NOTED OTHERWISE.
BEARING FOR ALL BEAMS, LINTELS, JOISTS, ETC. SHALL BE GROUTED SOLID A MINIMUM OF ONE COURSE (8 INCHES) BELOW
BEARING ELEVATION, UNLESS NOTED OTHERWISE.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE CARBON STEEL ANCHORS AS MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER AND SHALL BE INSTALLED IN CONFORMANCE WITH
THE MANUFACTURER'S RECOMMENDATIONS.
EXPANSION ANCHORS SHALL NOT BE INSTALLED IN CONCRETE UNTIL IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY
COMPRESSIVE STRENGTH.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI "HIT HY200" FOR SOLID SUBSTRATE AND HILTI "HIT HY70" FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS BY INSTALLERS TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS. GROUT SHALL
HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF 5,000 PSI IN 28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE VOLCLAY WATERSTOP-RX 101 UNLESS NOTED OTHERWISE.
INSTALL IN ACCORDANCE WITH MANUFACTURER'S WRITTEN NSTRUCTIONS.
PVC WATERSTOPS
PROVIDE FACTORY MADE WATERSTOP FABRICATIONS FOR ALL CHANGES OF DIRECTION, INTERSECTIONS, AND
TRANSITIONS LEAVING ONLY STRAIGHT BUTT JOINT SPLICES FOR THE FIELD.
PROVIDE HOG RINGS OR GROMMETS SPACED AT 12 INCHES ON CENTER ALONG LENGTH OF WATERSTOP.
PROVIDE TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRONS FOR FIELD BUTT SPLICES.
FIELD BUTT SPLICES SHALL BE HEAT FUSED WELDED USING A TEFLON COATED THERMOSTATICALLY CONTROLLED WATERSTOP SPLICING IRON AT APPROXIMATELY 380 DEGREES F. FOLLOW APPROVED MANUFACTURER
RECOMMENDATIONS.
LAPPING OF WATERSTOP, USE OF ADHESIVES, OR SOLVENTS SHALL NOT BE ALLOWED.
CENTER WATERSTOP IN JOINT AND SECURE WATERSTOP IN CORRECT POSITION USING HOG RINGS OR GROMMETS SPACED AT 12 INCHES ON CENTER ALONG THE LENGTH OF THE WATERSTOP AND WIRE TIE TO ADJACENT REINFORCING
STEEL.
MASTIC COATING
MASTIC COATING FOR PROTECTION OF INDICATED ITEMS SHALL BE BITUMASTIC 50 COAL TAR MASTIC BY CARBOLINE OR EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER. INSTALL AT LOCATIONS INDICATED ON DRAWINGS.
UNLESS NOTED OTHERWISE, APPLY MASTIC TO A COATING THICKNESS OF 18 MILS. PROVIDE FULL COVERAGE OVER ITEMS
INDICATED TO RECEIVE COATING.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, 50 KSI.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES SHALL CONFORM TO ASTM A36, UNLESS
NOTED OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE.
STEEL STUDS SHALL CONFORM TO ASTM A108.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL BETIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN
BRACE ELEMENTS ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY'S STRUCTURAL WELDING
CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.
UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD
E70XX ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY THE
ARCHITECT. COORDINATE FINISH PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL THAT IS NOT EXPOSED IN THE FINISHED CONSTRUCTION AND DOES NOT RECEIVE FINISH PAINT SHALL NOT BE
SHOP-PRIMED, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE. FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED STEEL, USE
A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION AND MANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A 10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
PROVIDE L4X4X1/4 FRAMED OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR LARGER ALONG ANY SIDE, UNLESS LARGER FRAMING IS INDICATED. REFER TO MECHANICAL AND PLUMBING DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED OPENING
SIZES AND LOCATIONS WITH THE MECHANICAL AND PLUMBING CONTRACTORS.
GALVANIZE ALL EXPOSED STEEL.
ARCHITECTURAL PRECAST PANELS
SUPPLIER OF ARCHITECTURAL PRECAST PANELS IS RESPONSIBLE FOR THE DESIGN AND DETAILING OF THE PANELS AND
CONNECTIONS.
STEEL REQUIRED TO TRANSMIT THE GRAVITY AND/OR LATERAL LOADS TO THE STRUCTURE NOT DETAILED ON THE STRUCTURAL
DRAWINGS IS THE RESPONSIBILITY OF THE PRECAST SUPPLIER TO DESIGN AND DETAIL.
PRECAST PANELS TO BE DESIGNED FOR VEHICULAR IMPACT LOADING PER ASCE7.
GRAVITY CONNECTIONS SHALL NOT BE MADE TO BEAMS, JOISTS, OR JOIST GIRDERS WITHOUT PERMISSION OF THE STRUCTURAL
ENGINEER, UNLESS SPECIFICALLY SHOWN ON THE DRAWINGS.
CONNECTIONS TO TRANSMIT LATERAL LOADS TO THE STRUCTURE SHALL BE MADE ONLY TO A COLUMN OR THE TOP FLANGE OF A STEEL BEAM, OR THE TOP CHORD OF A STEEL JOIST OR JOIST GIRDER AT A TOP CHORD PANEL POINT. CONNECTIONS TO TRANSMIT LATERAL LOADS TO THE STRUCTURE SHALL NOT BE MADE TO THE BOTTOM FLANGES OF BEAMS, BOTTOM CHORDS OF JOIST GIRDERS OR BOTTOM CHORDS OF JOISTS WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER.
PRECAST CONCRETE CONNECTIONS SHOWN ON DRAWINGS SHALL BE PROVIDED AS SHOWN, BY THE STEEL FABRICATOR. IF DETAILS NEED TO BE ADJUSTED BASED ON AN INDIVIDUAL PRECAST MANUFACTURER'S DETAILS, THE MANUFACTURER MUST INFORM THE STEEL FABRICATOR PRIOR TO FABRICATION OF THE STEEL. CHANGES REQUIRED AFTER THE STEEL IS FABRICATED SHALL BE THE SOLE RESPONSIBILITY OF THE PRECAST MANUFACTURER (INCLUDING ENGINEERING, MATERIAL AND
INSTALLATION).
PRECAST CONCRETE SPANDREL PANELS SHALL NOT BE ERECTED AT ANY LEVEL PRIOR TO PLACEMENT OF FLOOR OR ROOF DECK
ON THAT LEVEL.
ELEVATORS
CONTRACTOR SHALL COORDINATE ELEVATOR PITS, SHAFTS, SLAB OPENINGS, FRAMING LOCATIONS, GUIDE RAIL SUPPORTS, DIVIDER BEAMS, HOIST BEAMS AND SUMP PITS WITH ELEVATOR SUPPLIER PRIOR TO CONSTRUCTION AS REQUIRED FOR
PROPER INSTALLATION AND OPERATION.
COORDINATE ANY REQUIRED STRUCTURAL MODIFICATIONS WITH THE STRUCTURAL ENGINEER PRIOR TO FABRICATION
AND/OR INSTALLATION OF ANY STRUCTURAL ELEMENTS.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318) AND
COMMENTARY (ACI 318R) AND ACI GUIDE 362.1R.
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301). READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN CASE OF A DISCREPANCY, THE PLANS AND SPECIFICATIONS
SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
REINFORCEMENT ANCHORAGE SHALL BE LENTON TERMINATOR BY PENTAIR OR APPROVED EQUIVALENT.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT
(BY WEIGHT) OF FLY ASH TO TOTAL CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT
EXCEED 25 PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE WITH OTHER
ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON THE DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER
FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL HAVE THE PROPERTIES AS SHOWN BELOW:
STRUCTURAL PRECAST CONCRETE (GENERAL)
SUPPLIER OF STRUCTURAL PRECAST CONCRETE IS RESPONSIBLE FOR THE DESIGN, DETAILING, AND INSTALLATION OF THE PRECAST MEMBERS AND CONNECTIONS. DESIGN AND INSTALL PANELS IN ACCORDANCE WITH ACI 318 AND THE PCI DESIGN HANDBOOK, CURRENT EDITIONS. MANUFACTURE IN ACCORDANCE WITH MANUAL FOR QUALITY CONTROL FOR PLANTS AND PRODUCTION OF STRUCTURAL PRECAST CONCRETE PRODUCTS (PCI MNL 116).
THE PRECAST SUPPLIER SHALL ENGAGE A PROFESSIONAL ENGINEER LICENSED IN THE STATE WHERE THE PROJECT IS CONSTRUCTED TO PERFORM THE
DESIGN.
PRECAST SUPPLIER IS RESPONSIBLE FOR TEMPORARY BRACING, GUYS, TIEDOWNS, DEADMEN, ETC. AS REQUIRED TO SUPPORT STRUCTURAL PRECAST UNTIL THE STRUCTURAL FRAMING SYSTEM AND DECKING INSTALLATION ARE COMPLETE AND FINAL STABILITY IS ACHIEVED.
CONTRACTOR SHALL DESIGN ALL PRECAST MEMBERS AND ERECTION ASSEMBLIES FOR DESIGN AND TEMPORARY ERECTION FORCES, ERECTION SEQUENCING, GUY STAYING AND SHORING. CONTRACTOR SHALL CONFIRM ALL APPROPRIATE CONNECTIONS ARE COMPLETED AND REQUIRED GROUTING HAS OCCURRED TO ENSURE STABILITY DURING CONSTRUCTION BEFORE ERECTING STRUCTURE VERTICALLY.
EMBEDS AND OTHER STEEL ITEMS TO BE EMBEDDED IN THE PRECAST ARE TO BE PROVIDED AND INSTALLED BY THE PRECASTER, UNLESS NOTED
OTHERWISE.
STRUCTURAL STEEL ITEMS TO BE FIELD WELDED TO EMBEDDED ITEMS IN THE PRECAST ARE TO BE PROVIDED AND INSTALLED BY THE STEEL ERECTOR, UNLESS NOTED OTHERWISE.
EMBEDS AND OTHER ITEMS TO BE EMBEDDED IN CAST-IN-PLACE CONCRETE SHALL BE SUPPLIED BY THE PRECASTER AND INSTALLED BY THE CONCRETE
CONTRACTOR, UNLESS NOTED OTHERWISE.
IF THE DETAILS INDICATED ON THESE DRAWINGS NEED TO BE MODIFIED TO ACCOMMODATE THE PRECAST SUPPLIER'S FABRICATION OR INSTALLATION STANDARDS, THE PRECASTER MUST INFORM THE STRUCTURAL ENGINEER AND ALL AFFECTED FABRICATORS AND CONTRACTORS PRIOR TO FABRICATION OF AFFECTED MATERIALS. MODIFICATIONS REQUESTED BY THE PRECASTER AFTER THE AFFECTED ITEMS ARE FABRICATED SHALL BE SOLELY THE RESPONSIBILITY OF THE PRECASTER (INCLUDING ENGINEERING, MATERIAL AND INSTALLATION) AND SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE
PROJECT.
COORDINATE ALL OPENINGS, REVEALS, DRIP EDGES, BLOCKOUTS, INSERTS, ETC. TO BE CAST INTO PRECAST MEMBERS WITH STRUCTURAL, ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS. AS PART OF THE SUBMITTAL PROCESS COORDINATION OF EXACT SIZES IS REQUIRED AND
SHALL BE PERFORMED BY THE CONTRACTOR.
ALL LIFTING POCKETS TO BE FILLED WITH GROUT. GROUT COLOR TO MATCH PRECAST.
ALL PRECAST CONCRETE TO HAVE CAST-IN-PLACE CONCRETE WASH PLACED ON IT TO HAVE A RAKED FINISH.
LOAD BEARING PRECAST CONCRETE WALL PANELS
LOAD BEARING PRECAST WALL PANELS ARE USED TO SUPPORT GRAVITY AND LATERAL LOADS. PRECAST PANELS ARE TO BE DESIGNED FOR THE REACTIONS AND LOAD INFORMATION INDICATED ON THE DRAWINGS AND IN ACCORDANCE WITH THE
GOVERNING BUILDING CODE.
DESCRIPTION
F'C
PSI,
MIX
MAXIMUM
CHLORIDE
ION
CONTENT
MAX
W/C
RATIO
AVERAGE
ENTRAINED
AIR
MINIMUM
CEMENTITIOUS
MATERIALS
CONTENT,
LB/CYD
MAXIMUM
SLUMP
MAXIMUM SLUMP FOR
CONCRETE CONTAINING
HIGH-RANGE WATER-
REDUCING
ADMIXTURE
MAXIMUM
COARSE
AGGREGATE
SIZE
FOUNDATIONS & PILE
CAPS
4000 STD 0.30% 0.48 N/A 470 4" 8" AAC 1.5"
FOUNDATION WALLS &
GRADE BEAMS
4000 STD 0.30% 0.48 N/A 470 4" 8" AAC 1"
RETAINING WALLS &
CURBS/SIDEWALKS/SLABS
EXPOSED TO DE-ICERS
4000 CNA 0.15% 0.45 6% +/- 1% 517 4" 8" AAC 1"
SLABS-ON-GRADE
CNA/SF
0.15% 0.48 6% +/- 1% 470 4" 8" AAC 1"
NOTES:
1. "STD" INDICATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION WHICH DOES NOT REQUIRE A SILICA FUME, GGBS/FLY ASH OR
CALCIUM NITRITE ADMIXTURE.
2. "CNA" INDICATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION WHICH CONTAINS 3 GAL/CYD OF CALCIUM NITRITE CORROSION-
INHIBITOR ADMIXTURE.
3. "SF" INDICATES A CONCRETE MIX DESIGN WITH 1.5 LBS STRUCTURAL FIBERS PER CYD OF CONCRETE.
4. "AAC" MEANS SLUMP IS AFTER ADMIXTURE IS ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP.
DESCRIPTION F'C PSI, MIX
MAX
W/C
RATIO
AVERAGE
ENTRAINED AIR
MAXIMUM
SLUMP
MAXIMUM COARSE
AGGREGATE SIZE
COLUMNS, LIGHT WALLS & WALLS 6000 STD 0.38 5.5% +/- 1% N/A .75"
BEAMS, DOUBLE TEES (PRETOPPED),
STAIRS & SPANDRELS 6000 CNA 0.38 5.5% +/- 1% N/A .75"
CAST-IN-PLACE TOPPING, WASHES &
POUR STRIPS
4000 CNA 0.40 5.5% +/- 1% N/A .75"
NOTES:
1. "STD" INDICATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION WHICH DOES NOT REQUIRE A SILICA FUME, GGBS/FLY ASH OR CALCIUM NITRITE ADMIXTURE.
2. "CNA" INDICATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION WHICH CONTAINS 3 GAL/CYD OF CALCIUM NITRITE
CORROSION-INHIBITOR ADMIXTURE.
3. MAXIMUM WATER SOLUBLE CHLORIDE ION CONTENT FROM ALL CONCRETE CONSTITUENTS SHALL NOT EXCEED 0.06% OF WEIGHT OF CEMENT FOR ALL PRESTRESSED CONCRETE ELEMENTS, 0.15% OF WEIGHT OF CONCRETE FOR CAST-IN-PLACE TOPPINGS, WASHES &
POUR STRIPS AND 0.30% FOR ALL OTHER CONCRETE ELEMENTS.
B
3 4
46' - 0" 36' - 0" 36' - 0" 36' - 0" 36' - 0" 36' - 0" 36' - 0" 46' - 0"
9.
.0 0'
.0
0'
C
5 6 7 8 9
4 \ SF201
1 \ SF201
308' - 0"
4'
"2
SF
SB401
SB401
SB401
SF
CW10
WF3.75 WF3.75
CW10
WF3.75
CW10
WF5
CW14
WF5
CW14
F11.0F11.0F11.0F12.0F13.0
CW12
PCSW05PCSW04PCSW03PCSW02PCSW01 PCSW06 PCSW07 PCSW08 PCSW09 PCSW10 PCSW11 PCSW12
C1 C1 C1
C1 C1 C1 C1
C2
C3 C1 C1 C1
F14.0AF14.0AF15.0
C1
F14.0A F14.0A
C1 C1
F14.0A F15.0
C1
F11.0
C3
P C
S W
P C
S W
C2
F11.0A F12.0
CW10
WF3.75
F14.0 F14.0
P C
S W
SB502
SB502
SB502
SB502
SB502
SB501
SB501
T/FTG = 98' - 0" T/FTG = 97' - 6" T/FTG = 97' - 0" T/FTG = 96' - 10" T/FTG = 96' - 6" T/FTG = 96' - 2" T/FTG = 95' - 10"
T/FTG = 96' - 1"
T/FTG = 95' - 9"
T/FTG = 95' - 9"
T/FTG = 96' - 4" T/FTG = 96' - 4" T/FTG = 96' - 4"
T/FTG = 96' - 4" T/FTG = 96' - 4"
T/FTG = 96' - 11"
FS
3'
5'
6'
SB501
CW8 CW8 CW8 CW8 CW8 CW8 CW8 CW8
6"
2'
1'
2'
0"
FS
SB502
T/FTG = 95' - 9"
WF10
T/FTG = 92' - 6"
T/FTG = 96' - 7"
T/FTG = 96' - 7"
.7
3'
SEE NOTE 13, TYP
ALONG GRIDLINE A
SEE NOTE 13
SB501
F2
24.20' 7.80'
9'
4'
6' - 3" 16' - 0"
F1
NOTES:
1. REFERENCE (FIN FLR) = 100’-0”. ELEVATION 100’-0” = USGS 247.40 FEET.
2. SEE SI001 FOR ABBREVIATIONS, SYMBOLS & LEGENDS
3. SEE SI002 FOR STRUCTURAL DESIGN LOAD INFORMATION
4. SEE SI003 FOR GENERAL STRUCTURAL NOTES
5. REFERENCE ARCHITECTURAL DRAWINGS FOR LOCATIONS AND SIZES OF DOOR OPENINGS, STAIRS, DOWNSPOUTS RECESSES, ETC.
6. SEE PLUMBING DRAWINGS FOR LOCATION OF DOWNSPOUTS.
7. PROVIDE A 1” GAP BETWEEN ALL CAST-IN-PLACE FOUNDATION WALLS AND PRECAST COLUMNS, UNLESS NOTED OTHERWISE.
8. SEE AW SHEETS FOR WATERPROOFING AND JOINT DETAILS.
9. SEE SB601 FOR COLUMN FOOTING, WALL FOOTING, CMU WALL AND CONCRETE WALL SCHEDULES.
10. ALL FOOTINGS TO HAVE 3" CLEAR COVER FOR REINFORCEMENT IN ALL DIRECTIONS.
11. EXTEND REBAR TO 3" CLEAR OPPOSITE SIDE OF SPREAD FOOTING WHERE WALL FOOTINGS TIE INTO SPREAD FOOTINGS.
12. PROVIDE RAMMED AGGREGATE PIERS UNDER ALL FOUNDATIONS. THE CONTRACTOR SHALL REFERENCE THE SPECIFICATION SECTION
31663 - RAMMED AGGREGATE PIERS- FOR IMPLEMENTAION OF GROUND IMPROVEMENT PROGRAM.
13. PROVIDE TEMPORARY BRACING FOR THE WALLS UNTIL THE RAMP IS PLACED.
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
MEMPHIS, TN
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
614-319
MEMPHIS VAMC
1030 JEFFERSON AVE, MEMPHIS, TN 38104
ARCHITECT/ENGINEERS:
MEP Engineer
APOGEE CONSULTING
GROUP
1151 Kildaire Farm Rd.
Suite 120 Cary, NC 27511
Tele: 919-858-7420
Functional Design
CARL WALKER INC.
3211 Internet Blvd., Suite 220 Frisco, TX 75034
Tele: 469-777-5143
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
C U s e rs
\b th o m a s \D o c u m e n ts
\1 .1
-S
-M e m p h is
V A
-G a ra g e W
J T h o m a s .r v t
BID SET
SB101
WJTMAV
FOUNDATION PLAN
11/14/2016
15.1067CONSTRUCT PARKING GARAGE
ON WEST LOT
SCALE: 3/32" = 1'-0"SB101
1 FOUNDATION PLAN
N
COLUMN SCHEDULE
Type Mark SIZE REMARKS
C1 24" X 33"
C2 24" X 24"
C3 33" X 33"
32' - 0"
/2
8"
5' - 2 1/2" 19' - 0" 3' - 4" 4' - 5 1/2"
C W
CW8
C W
C W
8" 2'
3'
T/WALL = 96' - 7"
T/WALL = 98' - 4"
SF
SF
3 \ SF203
4 \ SF203
5 \ SF203
6 \ SF203
9'
/2
8" P
R E
C A
S T
W A
LL
8" PRECAST WALL
8" P
R E
C A
S T
W A
LL
4' - 0"
CW12
C W
CW12
2' X 2' SUMP PIT
T/WALL = 98' - 4"
T/WALL = 98' - 4"
C W
T/WALL = 98' - 4"
1' - 0"
2'
9'
/2
9'
8'
8'
1'
4"
CW12
T/FTG = 96' - 7"
T/FTG = 92' - 6"
F2
FS
T/WALL = 98' - 4"
4 \ SF202
SB502
A
4"
8'
5' - 9" 10' - 6" 6' - 0"
6" 10' - 0"
SF
8 \ SF203
9 \ SF203
22' - 3"
P C
S W
8" PRECAST WALL
8" P
R E
C A
S T
W A
LL
T/FTG = 98' - 0"
9'
F1
8" PRECAST WALL
A
B
17' - 8"
1' - 0" 16' - 8"
1/
2"
/2
5"
C W
C W
CW10
WF3.75
W F
W F
MW8
MW8
MW8
WF2
WF2
WF2
T/FTG = 95' - 9"
T/FTG = 95' - 9"
T/FTG = 95' - 9"
T/FTG = 95' - 9"
T/FTG = 95' - 9"
T/WALL = 101' - 8"
3/ 8"
1/ 8"
PCSW11
10" PRECAST WALL 10" PRECAST WALL
F11.0A
T/FTG = 96' - 4"
SB501
C1
SB502
1'
3'
3/ 8"
3'
7'
3'
6'
1/
8"
SB502
SB502
TYP @
D
OOR
SB502
TYP
A
B
17' - 8"
1' - 0" 16' - 8"
1/
2"
/2
5"
T/SLAB = 97' - 8"
T/SLAB = 98' - 0"
T/SLAB = 97' - 11"
T/SLAB = 98' - 4"
MW8
MW8
MW8
T/WALL = 109' - 10"
CW10
M W
1'
3'
3/ 8"
3'
7'
3'
6'
1/
8"
M W
M
W
M W
C1
PCSW11
10" PRECAST WALL10" PRECAST WALL
T/WALL = 106' - 6"
T/WALL = 107' - 3 1/2"
SB502
SB502
SB502
TYP @
D
OOR
SB502
TYP
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
MEMPHIS, TN
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
614-319
MEMPHIS VAMC
1030 JEFFERSON AVE, MEMPHIS, TN 38104
ARCHITECT/ENGINEERS:
MEP Engineer
APOGEE CONSULTING
GROUP
1151 Kildaire Farm Rd.
Suite 120 Cary, NC 27511
Tele: 919-858-7420
Functional Design
CARL WALKER INC.
3211 Internet Blvd., Suite 220 Frisco, TX 75034
Tele: 469-777-5143
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
C U s e rs
\b th o m a s \D o c u m e n ts
\1 .1
-S
-M e m p h is
V A
-G a ra g e W
J T h o m a s .r v t
BID SET
SB401
WJTMAV
ENLARGED FOUNDATION PLANS
11/14/2016
15.1067CONSTRUCT PARKING GARAGE
ON WEST LOT
SCALE: 3/16" = 1'-0"SB401
1 STAIR #1 - FOUNDATION PLAN
SCALE: 3/16" = 1'-0"SB401
2 STAIR #2 - FOUNDATION PLAN
SCALE: 3/16" = 1'-0"SB401
3 STORAGE AREA - FOUNDATION PLAN
SCALE: 3/16" = 1'-0"SB401
4 STORAGE AREA - SLAB-ON-GRADE PLAN
DOWEL SIZE AND SPACING
DOWEL DIAMETER
IN
SLAB DEPTH
(T)
TOTAL DOWEL
LENGTH (L)
DOWEL SPACING CENTER
TO CENTER
IN IN IN
3/44 16 24
3/45-6 16 12
1 18 12
1 1/4 18 12
7-8
9-11
T/SLAB
SEE PLAN
SLAB SEE PLAN
TOOLED JOINT SEE AW
SERIES SHEETS
CONC SLAB ON GRADE
PAINT DOWEL WITH
BOND BRAKING COMPONENT
T/SLAB
SEE PLAN
SMOOTH SQUARE DOWEL W/ SLEEVE
TO ALLOW LATERAL MOVEMENT
CONSTRUCTION JOINT
CONTROL JOINT
TOOLED JOINT SEE AW
SERIES SHEETS
L/2 L/2
6" (MIN) COMPACTED
CRUSHED STONE BASE
#4 @ 12" OC
(MAX), TYP
#4 @ 12" OC (MAX)
EACH WAY AT MID-DEPTH
#4 @ 12" OC (MAX)
EACH WAY AT MID-DEPTH
1" CHAMFER TYP
AT CORNERS
NOTES:
1. CONCRETE 28-DAY COMPRESSIVE STRENGTH = 4000 PSI, MINIMUM.
AIR ENTRAINMENT = 6% +/- 1%
MAX W/C RATIO = 0.45
BROOM FINISH SURFACE
2. PROVIDE SAW-CUT CONTROL JOINTS SPACED NOT MORE THAN 24 TIMES THE SLAB THICKNESS
CENTER-TO-CENTER, UNO. SEAL JOINTS WITH WEATHER-RESISTANT SEALANT.
3. SEE PLANS FOR OVERALL PAD DIMENSION.
4. COORDINATE EXACT LOCATION WITH CIVIL AND MECHANICAL DRAWINGS, AND EQUIPMENT SUPPLIER.
TURN-DOWN ALL 4 SIDES
8" T
Y P
3" C
LR
TYP
8" MIN
TYP
8" MIN
3' -6
M
IN
BELOW GRADE DETAIL
PRECAST COLUMN
CIP WALLSEE TO AW-SERIES SHEETS
ABOVE GRADE DETAIL
PRECAST COLUMN
CIP WALL
SEE AW-SERIES SHEETS
SLAB/BEAM EDGE
SEE AW-SERIES SHEETS
NOTE:
1) T/SOG ELEVATIONS ON PLANS DO NOT INCLUDE WASH CONCRETE.
3/4" CHAMFER
ELEVATION PER PLAN
SLAB SEE PLAN
3"
SEAL JOINT SEE AW
SERIES DWGS
1 1/2" RADIUS
INTENTIONALLY ROUGHEN
SURFACE TO 1/4" AMPLITUDE
CONTROL JOINTS TO MATCH
SLAB ON GRADE SEE 1/SB501
WASH LINE
FLOOR DRAIN
2 - #4x4'-0"
EA SIDE, TYP
SEE AW-SERIES
SHEETS
2'-0"x2'-0" SQUARE
FLOOR DRAIN SYSTEM,
REFER TO PLUMBING DWGS
2 - #4, SEE DETAIL
7/SB501
CONC SOG
T/SLAB
SEE PLAN
SEE AW-SERIES
SHEETS
CONCRETE COLUMN
CONSTRUCTION JOINT, REFER
TO 1/SB501
SEE AW-SERIES SHEETS
CONSTR OR CONTROL JOINT,
REFER TO AW-SERIES SHEETS
PLACE FILL AREA A MINIMUM OF
56 DAYS AFTER PLACEMENT OF
SUPPORTED LEVELS ABOVE, TYPICAL
CONCRETE COLUMN
CONSTRUCTION JOINT,
REFER TO 1/SB501
SEE AW-SERIES SHEETS
WALL
WALL FTG
4' - 0"
DOWELS TO MATCH ADJOINING
FOUNDATION REINF.
2x6 KEYS, TYP.
CONTROL JOINT CONSTRUCTION JOINT
SEALANT
CUT EVERY OTHER
HORIZ BAR @ JOINT
UNLESS NOTED
INSIDE FACE
OF WALL
SOIL SIDE
OF WALL
WATERPROOFING
MEMBRANE
2x4 KEYWAY
"V" GROOVE, REFER TO NOTE
1/8" EARTH DAM
NOTE: FOR 8" WALL, PROVIDE 1" "V" GROOVE EACH SIDE OF
WALL. FOR 10" OR LARGER WALL, PROVIDE 1" "V"
GROOVE AT INSIDE FACE OF WALL AND 1 1/2" "V"
GROOVE AT SOIL SIDE OF WALL
NOTE:
PROVIDE CORNER BARS AT ALL
INTERSECTIONS, SAME SIZE AND
SPACING AS HORIZ REINF
JAMB SHOWN
AT HEAD PROVIDE (2) #5
AND EXTEND 2'-0" EITHER
SIDE OF OPENING
INTERSECTION JAMB & HEAD CORNER
LA
P
S P
LI
C
E C
LA
S
S B
ALT DIR
OF BEND
(2) #5 JAMB BARS
EXTEND FULL HEIGHT
OF WALL OPENING
CORNER BARS TO MATCH TYPICAL HORIZONTAL
WALL REINFORCEMENT SIZE AND SPACING
LA
P
S P
LI
C
E
C
LA
S S
B
TYP WALL REINFTYP WALL REINF
NOTE:
PROVIDE CORNER BARS AT ALL
INTERSECTIONS, SAME SIZE AND
SPACING AS HORIZ REINF
JAMB SHOWN
AT HEAD PROVIDE (2) #5
AND EXTEND 2'-0" EITHER
SIDE OF OPENING
INTERSECTION JAMB & HEAD CORNER
(2) #5 JAMB BARS
EXTEND FULL HEIGHT
OF WALL OPENING
LAP SPLICE
CLASS B
U-SHAPED BARLAP SPLICE
CLASS B
SLAB SEE PLAN
T/SLAB
SEE PLAN
T/SLAB
SEE PLAN
MIN
6"
1 (MAX.)
ALTER EXCAVATION LIMITS
t
1' - 6"
CLASS B TENSION LAP PER
SCHEDULE
t
T/FTG
EQ. EQ.
BARS TO MATCH FOOTING REINF.
SIZE AND SPACING
F S
INDICATES
FOOTING STEP
F S
F S
4'-0" MIN.
1' - 7"
CLASS B TENSION LAP
PER SCHEDULE
T Y
P
3" C
LR
T/FTG
S E
E P
LA
N
A
PRECAST COLUMN
BY PC MFR
CAST IN PLACE
WALL SEE PLAN
AND SCHED
PROVIDE 1" GAP, TYP
1'
/2
A
1'
/2
PRECAST COLUMN
BY PC MFR
CAST IN PLACE
WALL SEE PLAN
AND SCHED
CAST IN PLACE
WALL SEE PLAN
AND SCHED
PROVIDE 1" GAP, TYP
A
PRECAST COLUMN
BY PC MFR
CAST IN PLACE
WALL SEE PLAN
AND SCHED
CAST IN PLACE
WALL SEE PLAN
AND SCHED
PROVIDE 1" GAP, TYP
1'
/2
1' - 0"
T/SLAB
SEE PLAN
SLAB SEE PLAN
SEE CIVIL
1'
C
T/SLAB
SEE PLAN
SLAB SEE PLAN
GRADE SEE CIVIL
CONCRETE WASH
8" CONCRETE
KNEEWALL
2'
8 1/2"
1' - 4 1/2"
T/SLAB
SEE PLAN
1'
(3) #5 CONT
8" 2'-0"
(4) #5 CONT
#5 @ 12" OC
LENTON TERMINATOR OR
APPROVED EQUAL
CONCRETE FOOTING SEE
PLAN AND SCHEDULES FOR
REINFORCING
T Y
P 3"
C
LR
C
PRECAST COLUMN
BY PC MFR
CAST IN PLACE
WALL SEE PLAN
AND SCHED
PROVIDE 1" GAP, TYP
1/
2"
OPENING PER ARCH
WALL - SEE PLAN
TYPICAL SLAB REINFORCING @ ALL
OVERHEAD DOORS, MANDOORS AND
WALL OPENINGS (WHERE APPLICABLE)
#4 BAR x OPENING + 3'-0" @ SLAB
MID DEPTH
1 - #4 BAR x 2'-6" @ SLAB MID DEPTH
1/
2" C
LR
Drawing Title
Approved for Design Concept:
Project Title
Date
Location
Checked By:
Building Number
Project Number
Drawing Number
Drawn By:
Revisions: Date
MEMPHIS, TN
o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
B
A
C
D
E
F
1 2 3 4 5 6 7 9
F
E
D
C
B
A
97 8654321
OFFICE OF
FACILITIES
MANAGEMENT
VA Project Number
FACILITY MANAGEMENT
DIVISION MANAGER
614-319
MEMPHIS VAMC
1030 JEFFERSON AVE, MEMPHIS, TN 38104
ARCHITECT/ENGINEERS:
MEP Engineer
APOGEE CONSULTING
GROUP
1151 Kildaire Farm Rd.
Suite 120 Cary, NC 27511
Tele: 919-858-7420
Functional Design
CARL WALKER INC.
3211 Internet Blvd., Suite 220 Frisco, TX 75034
Tele: 469-777-5143
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN. 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
C U s e rs
\b th o m a s \D o c u m e n ts
\1 .1
-S
-M e m p h is
V A
-G a ra g e W
J T h o m a s .r v t
BID SET
SB501
WJTMAV
TYPICAL FOUNDATION SECTIONS AND DETAILS
11/14/2016
15.1067CONSTRUCT PARKING GARAGE
ON WEST LOT
SCALE: 3/4" = 1'-0"SB501
1 TYPICAL SLAB ON GRADE JOINTS
SCALE: 3/4" = 1'-0"SB501
2 EXTERIOR EQUIPMENT PAD DETAIL
SCALE: 3/4" = 1'-0"SB501
4 COLUMN / WALL JOINT DETAIL
SCALE: 1 1/2" = 1'-0"SB501
5 TYPICAL (SOG) WASH DETAIL
SCALE: 1 1/2" = 1'-0"SB501
6 TYPICAL ISLAND DETAIL
SCALE: 3/4" = 1'-0"SB501
7 FLOOR DRAIN DETAIL
SCALE: 3/4" = 1'-0"SB501
8 FLOOR DRAIN DETAIL
SCALE: 3/4" = 1'-0"SB501
9 COLUMN ISOLATION DETAIL
SCALE: 3/4" = 1'-0"SB501
10 COLUMN ISOLATION DETAIL
SCALE: 3/8" = 1'-0"SB501
11 TYPICAL FOUNDATION INTERSECTION
SCALE: 3/4" = 1'-0"SB501
12 CONCRETE WALL DETAIL
SCALE: 3/4" = 1'-0"SB501
13 CORNER BAR DETAILS
SCALE: 3/4" = 1'-0"SB501
14 CORNER BAR DETAILS
SCALE: 3/4" = 1'-0"SB501
15 TYPICAL SLAB ELEVATION CHANGE
SCALE: 3/4" = 1'-0"SB501
3 TYPICAL STEPPED FOOTING
SCALE: 3/4" = 1'-0"SB501
18 DETAIL
SCALE: 3/4" = 1'-0"SB501
19 DETAIL
SCALE: 3/4" = 1'-0"SB501
20 DETAIL
SCALE: 3/4" = 1'-0"SB501
16 TYPICAL TURN DOWN SLAB SECTION
SCALE: 3/4" = 1'-0"SB501
22 SECTION
NOT TO SCALESB501
23 REBAR…