36C24918R0140-003.pdf

PDF 27 KB Posted

Attached to
IDIQ Small Construction Contracts NRM
Solicitation number
36C24918R0140
Issued by

About this file

36C24918R0140 P01-Drawing 1 - Existing Floor Plan.pdf

View the file

Other files

File Type Posted
36C24918D0149-000.docx DOCX document
36C24918R0140-000002000.docx DOCX document
36C24918R0140-000002001.pdf PDF
36C24918R0140-000001000.docx DOCX document
36C24918R0140-000001001.pdf PDF
36C24918R0140-009.xlsx XLSX spreadsheet
36C24918R0140-006.pdf PDF
36C24918R0140-001.docx DOCX document
36C24918R0140-008.pdf PDF
36C24918R0140-004.pdf PDF
36C24918R0140-007.pdf PDF
36C24918R0140-005.pdf PDF
36C24918R0140-002.pdf PDF
36C24918R0140-00001000.docx DOCX document
36C24918R0140-000.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VHAMEMFONGL

Typewritten Text

DEMOLITION NOTES:

ARCHITECTURAL

1. REMOVE DOOR AND HARDWARE, HM DOOR FRAME TO REMAIN

2. REMOVE METAL WALL AND BASE CABINETS

3. REMOVE GYPSUM BOARD SOFFIT

4. REMOVE ACOUSTICAL TILE CEILING AND GRID

5. REMOVE VINYL COMPOSITION TILE FLOORING

6. REMOVE COVE BASE

PLUMBING

1. DISCONNECT AND REMOVE BASE CABINET SINK, INCLUDING SUPPLY AND WASTE PIPING

2. DISCONNECT AND REMOVE SERVICE SINK AND ELEVATED PLATFORM, INCLUDING SUPPLY AND WASTE PIPING

3. REMOVE CW AND HW PIPE BACK TO EXISTING MOP SINK THAT IS TO REMAIN. SO AS NOT TO CREATE DEAD LEGS, DO NOT CAP PIPE IN PLACE, INSTEAD REMOVE AND INSTALL NEW PIPE AND FITTINGS ON SUPPLY PIPING TO RECONNECT MOP SINK.

4. REMOVE SW PIPE FROM SINK CABINET OVER TO MOP SINK THAT IS TO REMAIN. REMOVE BRANCH FITTINGS FOR CABINET SINK AND UTILITY SINK. INSTALL NEW PIPE AND FITTINGS TO RECONNECT MOP SINK VENT.

HVAC

1. REMOVE EGGCRATE EXHAUST GRILLE. SEE NEW PLAN FOR RELOCATION.

ELECTRICAL

1. REMOVE 2X4 LIGHT TROFFER

2. REMOVE TOGGLE SWITCH