This combined synopsis/solicitation seeks electrical testing services for the Veterans Affairs Medical Center in Wilkes-Barre, Pennsylvania. The solicitation includes an attachment listing electrical equipment and systems requiring maintenance, inspection and testing. Interested parties must submit quotes by February 17, 2020. The requirement is set aside for small businesses with a NAICS code of 238210 and size standard of $15 million. The Department of Veterans Affairs is the contracting agency. The resulting contract will include Service Contract Act wage determinations and have a period of performance as defined in the statement of work.

36C24420Q0199 SOW Ref Attachment 1 - Inventory of Electrical Power Distribution System Equipment.pdf

View the file

Other files

File Type Posted
36C24420Q0199-014.docx DOCX document
36C24420Q0199-010.docx DOCX document
36C24420Q0199-012.docx DOCX document
36C24420Q0199-011.pdf PDF
36C24420Q0199-013.docx DOCX document
36C24420Q0199-002.docx DOCX document
36C24420Q0199-008.pdf PDF
36C24420Q0199-003.docx DOCX document
36C24420Q0199-009.pdf PDF
36C24420Q0199-007.pdf PDF
36C24420Q0199-004.xlsx XLSX spreadsheet
36C24420Q0199-006.pdf PDF
36C24420Q0199-001.docx DOCX document
36C24420Q0199-000.docx DOCX document
Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENT 1

Inventory

DEPARTMENT OF VETERANS AFFAIRS

WILKES-BARRE VA MEDICAL CENTER

Inventory of Electrical Power Distribution System Equipment For

Maintenance, Inspection, and Testing Of the Electrical Power Distribution System

I. Switchgear and Switchboard Assemblies:

(Including metering, instruments and control transformers).

1. Main Service Medium Voltage Switchgear-15KV-1200Ampere-3Phase-4Wire

2. Bldg 11/12 Switchboard CH-1- 3000Amp-480/277V-3Ph-4W

3. Bldg 27 Switchboard MDS- 1600Amp-480/277V-3Ph-4W-includes Ground Fault Protection

Control System.

4. Ambulatory Care Switchboard MDP- 3000Amp-480/277V-3Ph-4W

5. Bldg 1 Switchboard A- 4000 Amp-208/120V-3Ph-4W

6. Bldg 1 Switchboard B- 4000 Amp-208/120V-3Ph-4W

7. Bldg 1 Challenger Switchboard- 2500Amp-208/120V-3Ph-4W

8. Bldg 1 GE Switchboard- 2500Amp-208/120V-3Ph-4W

9. Amb. Care Addition Switchboard EDP-1600Amp-480/277V-3Ph-4W

10. Bldg 1 Switchboard E-1200Amp-208/120V-3Ph-4W

11. Bldg 27 Switchboard EMDP-1-1600Amp-480/277V-3Ph-4W

12. Switchboard MDS- 1200Amp-480/277V-3Ph-4W

13. Bldg 11/12 Switchboard EBPD-1200Amp-480/277V-3Ph-4W

14. Bldg 11 Boiler Plant Switchboard Eaton 2000 Amp – 208Y/120V- 3Ph-4W

II. Transformers, Dry Type, Air-Cooled, Low-voltage, Small:

1. 500 KVA-480V 3Ph. Primary (Pri)/208/120V 3Ph.-4W Secondary (Sec), (2 Each).

2. 300 KVA-480V 3Ph. Pri/208/120V- 3Ph.-4W Sec, (4 Each).

3. 225 KVA-480V 3Ph. Pri/208/120V- 3Ph.-4W Sec, (3 Each).

4. 150 KVA-480V 3Ph. Pri/208/120V 3Ph.-4W Sec, (5 Each).

5. 112.5 KVA-480V 3Ph. Pri/208/120V 3Ph.-4W Sec, (2 Each).

6. 75 KVA-480V 3Ph. Pri/208/120V 3Ph.-4W Sec, (6 Each).

7. 45 KVA-480V 3Ph. Pri/208/120V 3Ph.-4W Sec, (1 Each).

III. Transformers, Dry Type, Air-Cooled, Low-voltage, Large:

1. 2000 KVA-480V 3Ph. Pri/208/120V-3Ph.-4W Sec, (2 Each).

2. 1500 KVA- 12470 3Ph H.V – L.V. 208Y/120 3Ph (2 Each).

3. 750 KVA – 12470 3Ph H.V. - L.V. 480Y/277 3Ph (1 Each)

IV. Transformers, Liquid-Filled:

2. 750 KVA-12470 3Ph. Pri/208/120V-3Ph-4W Sec, (2 Each).

V. Metal Enclosed Busways:

1. Bldg 1: 140 Linear Feet Vertical Busway Riser thru Floors, Each Run.

A. East Riser: 600Amp-208/120V-3Ph-4W

B. Center Riser: 600Amp-208/120V-3Ph-4W

C. West Riser: 600Amp-208/120V-3Ph-4W

2. Bldg 1: 60 Linear Feet Vertical Busway Riser Thru Floors, Each Run.

A. North Riser: 600Amp-208/120V-3Ph-4W

3. Ambulatory Care South: 140 Linear Feet Vertical Busway Riser thru Floors, Each Run.

A. Emergency Critical Riser: 400Amp-480/277V-3Ph-4W

B. Emergency Life Safety Riser: 225Amp-480/277V-3Ph-4W

C. Normal Lighting Riser: 400Amp-480/277V-3Ph-4W

D. Normal Power Riser: 400 Amp-208/120V-3Ph-4W

4. Amb. Care North: 70 Linear Feet Vertical Busway Riser thru Floors, Each Run.

B. Emergency Life Safety Riser: 225Amp-480/277V-3Ph-4W

C. Normal Lighting Riser: 225 Amp-480/277V-3Ph-4W

D. Normal Power Riser: 600 Amp-208/120V-3Ph-4W

5. Amb. Care Addition East: 120 Linear Feet Vertical Busway Riser thru Floors, Each Run.

B. Emergency Life Safety Riser: 225 Amp-480/277V-3Ph-4W

VI. Switches, Air, Low-Voltage:

1. For Motor Control Center Fusible Switches refer to section XII.

2. Square D 2000Amp-480V-3Ph Bolted Pressure Switch (1 Each).

VII. Switches, Air, Medium-Voltage, Metal-Enclosed:

1. 15KV Class HVL single selection load break air switches (11 Each).

2. 15KV Class single selection non-load break air switches (2 Each).

VIII. Circuit Breakers, Air, Insulated-Case/Molded-Case:

1. For Motor Control Center Circuit Breakers refer to section XII.

2. Bldg 27 Westinghouse Type LC with Seltronic type trip rating plugs (15 Each).

3. GE Type TKH8S with RMS-9 MicroVersa Trip Units (2 Each).

4. GE Type TKH12S with RMS-9 MicroVersa Trip Units (1 Each).

5. GE Type TP2525SSZ with RMS-9 MicroVersa Trip Units (1 Each).

VIII. Circuit Breakers, Air, Insulated-Case/Molded-Case: (continued)

6. Challenger CSPGA 32500F Style 1242C74608, Rating Plug CSP 2500 (2 Each).

7. Westinghouse Series C NDB12T36W with Digitrip RMS 310 Units (2 Each).

8. Challenger Type CK-35, CK3400F with Digitrip RMS 310 Units (4 Each).

9. Square D Type LX Circuit Breakers with Micrologic Standard Series B Trips (18 Each), Type

KC (2 Each), Type SE Main Breaker 3000Amp (1 Each).

10. Square D Speed-D I-Line Circuit Breakers(3-Pole):

A. 15Amp to 125Amp (45 Each).

B. 400Amp (1 Each).

C. 175Amp (2 Each).

D. 600Amp (1 Each).

E. 200Amp (2 Each).

F. 225Amp (1 Each).

11. GE AV Line Circuit Breakers (3-Pole):

A. Type TJK-150Amp to 300Amp (11 Each).

B. Type TKMA-600Amp to 800 Amp (3 Each).

C. Type THED-150Amp (1 Each).

D. Type TB4-200 Amp (1 Each).

E. Type TEY-20 Amp (1 Each).

12. Square D Thermal Magnetic (3-Pole):

A. Type LC-400Amp (3 Each).

B. Type KC-225Amp (5 Each).

C. Type MH-600Amp (2 Each).

D. Type FC-100Amp (1 Each).

13. GE Type SS/SH 1600Amp 3-Pole Powerbreak II w/MVT Plus/PM (1Each).

14. GE Spectra Series, Type SGLA, 3-Pole, 300Amp to 600Amp (7 Each).

15. GE Spectra Series, Type SFLA, 3-Pole, 225Amp (1 Each).

16. GE Type LX/LXI, 3-Pole, 400Amp (1 Each).

17. GE Type SKHP 1200Amp 3-Pole w/MVT+PM (1 Each).

18. GE Spectra Series, Type SGLA, 3-Pole, 400Amp to 500Amp (4 Each).

19. Square D Power Pact Series, R Frame, 3-Pole, 1600Amp (1 Each).

20. Square D Power Pact Series, R Frame, 3-Pole, 1200Amp (1 Each).

21. GE Type TRL 2000Amp, 3 Pole, w/MVT Plus/PM (1 Each).

22. Eaton RGH 65K 2000Amp, 3 Pole w/RG310 + Trip Unit (1 Each).

23. Eaton FD35K 100Amp, 3 Pole (5 Each)

24. Eaton RGH 65K 125Amp 3 Pole (1 Each)

25. Eaton EDS 42K 125Amp 3 Pole (1 Each)

26. Eaton EDS 42K 150Amp 3 Pole (4 Each)

27. Eaton FD35K 150Amp 3 Pole (1 Each)

28. Eaton EDS 42K 175Amp 3 Pole (2 Each)

29. Eaton EDS 42K 200 Amp, 3 Pole (6 Each)

30 Eaton EDS 42K 225 Amp, 3 Pole (1Each)

IX. Circuit Breakers, Air, Low-Voltage Power:

1. GE Type AKRU with Epic MicroVersaTrip. 4000Amp Mains and Tie breakers (3 Each).

2. GE Type AKRU with MVT, one being RMS-9. Trip settings from 150Amp to 1200Amp (43

Each).

X. Circuit Breakers, Air & Vacuum, Medium-Voltage:

1. 15KV Class, Square D DSE-65 Solenarc Air Circuit Breakers (5 Each).

2. 15KV Class, Square D VR Vacuum Circuit Breakers (2 Each).

XI. Protective Relays, Mechanical, and Solid State:

1. General Electric Model # 12IFC53B1A (6 Each).

2. General Electric Model # 12IFC53B2A (2 Each).

3. ABB Model # Micro 51 Circuit Shield, Cat. # 446S1201 (6 Each).

4. ABB Model # Micro 51 Circuit Shield, Cat. # 446S1101 (2 Each).

5. General Electric Model # 12IAV69A1A (2 Each).

6. General Electric Model # 12NBV11A3A (2 Each).

XII. Motor Control, Motor Control Centers, Low-Voltage:

1. Amb. EMCC3-600A-480/277V-3PH-4W, No Main Circuit Breaker (MCB), Square D Model

6, F.O. 11220535-043, Square D Type F Frame adjustable and fixed molded case circuit breakers, sizes vary 15Amp thru 50 Amp (15 Each), Starter sizes vary-1 through 3 (13 Each).

2. Amb. Care EMCC5-600A-480/277V-3PH-4W, No MCB,Square D Model 6, F.O. 11220535-

0XX, Square D Type F frame adjustable and fixed molded case circuit breakers, sizes vary 15

Amp thru 60 Amp (15 Each), Starter sizes vary 1 through 3 (15 Each), and 1-100Amp,1-400

Amp circuit breakers.

3. Amb. Care MCC3-600A-480/277V-3PH-4W, 400Amp MCB, Square D Model 6, F.O.

11220535-040, Type F Frame adjustable and fixed molded case circuit breakers, sizes vary 15

Amp thru 100Amp (15 Each), Starter sizes vary-1 through 3(15 Each).

4. Amb. Care MCC5-600Amp-480/277V-3PH-4W,225Amp MCB, Square D Model 6, F.O. 11220535-0XX, Type F frame adjustable and fixed molded case circuit breakers, sizes vary 15 Amp thru 60 Amp (7 Each), Starter sizes vary 1 through 3(7 Each), and

1-150 Amp circuit breaker.

5. Bldg.27 MCC1-600A-480V-3PH-3W, Square D Model 4, F.O. 12-61061-1, Fusible Switches

(14 Each), Starter sizes vary-1 through 3 (14 Each).

6. Bldg.27 MCC2-600A-480V-3PH-3W, Square D Model 4, F.O. 12-61061-2, Fusible Switches

(20 Each), Starter sizes vary-1 through 3 (20 Each).

7. Chiller Bldg MCC-CH1-1200Amp-480/277V-3PH-4W, Square D Model 6 w/ Powerlogic

Metering, F.O. 11220535-AOX, Square D Type PXF 1200, Amp 3-Pole, Main CB, Feeder

Breakers-Square D Circuit Breakers (19 Each), Starter sizes 1 through 5(11 Each).

XIII. Emergency Systems, Engine Generator:

1. Generator #1-1000KW-480/277V-3Ph-4W Diesel Fueled

2. Generator #2-800KW-480/277V-3Ph-4W Diesel Fueled.

3. Generator #3-750KW-480/277V-3Ph-4W Diesel Fueled.

XIV. Transfer Switches:

1. Amb. Care ASCO 962 600A BOM 619552 480V/277V (2 Each), ASCO 962 400A BOM

613915 480V/277V (3 Each), ASCO 962 260A BOM 605870 480V/277V (4 Each), ASCO 962

150A BOM 625013 480V/277V (1 Each), Zenith ZTS BOM # ZB4SB04041-07G614X Volts

277/480 Hz 60 Amps 400 Ph 3 Volts 277/480 Hz 60 Amps 400 Ph 3 (1 Each)

2. Bldg. 27 ASCO 7000 SERIES 1200A BOM 866211 208V (1 Each), ASCO 7000 SERIES

400A BOM 854829 480V (1 Each), ASCO 7000 SERIES 400A BOM 854829 480V (1 Each), ASCO 7000 SERIES 600A BOM 716084 (1 Each), ASCO 7000 SERIES 400A BOM 854830

480V (1 Each), ASCO 7000 SERIES 400A BOM 854831 208V (1 Each), ASCO 7000 SERIES

400A BOM 900787 480V (1 Each), ASCO 7000 SERIES 1200A BOM 866209 208V (1 Each), Metron# ZTS10E5 10000A 480V (1 Each)

3. Bldg. 11 ASCO 386 2000a BOM 791243 208V (1 Each), ASCO 175 800A BOM 7898BB

480V (1 Each), ASCO 7000 SERIES 800A BOM 716114 480V (1 Each), ASCO 7000 SERIES

2000A BOM 709368 (1 Each), ASCO 7000 SERIES 800A BOM 866207 208V (1 Each)

XV. Grounding Systems:

1. All Switchgear & Switchboard Assemblies listed in paragraph I.

2. All Emergency Systems, Engine Generators listed in paragraph XIII.

XVI. Ground-fault Protection Systems:

1. All equipment listed in paragraph I, sub-paragraph 3.