36C24418B0287-00001004.pdf
PDF 5 MB Posted
- Attached to
- Upgrade Patient Environment NHCU #642-16-107
- Solicitation number
- 36C24418B0287
About this file
36C24418B0287 00001 Drawings 85-97.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24418C0174-000.docx | DOCX document | |
| 36C24418B0287-00004000.docx | DOCX document | |
| 36C24418B0287-00003002.pdf | ||
| 36C24418B0287-00003003.pdf | ||
| 36C24418B0287-00003001.pdf | ||
| 36C24418B0287-00003000.docx | DOCX document | |
| 36C24418B0287-00003005.pdf | ||
| 36C24418B0287-00003004.pdf | ||
| 36C24418B0287-00003006.pdf | ||
| 36C24418B0287-00002001.pdf | ||
| 36C24418B0287-00002000.docx | DOCX document | |
| 36C24418B0287-00001003.pdf | ||
| 36C24418B0287-00001000.docx | DOCX document | |
| 36C24418B0287-00001002.pdf | ||
| 36C24418B0287-00001001.pdf | ||
| 36C24418B0287-002.pdf | ||
| 36C24418B0287-001.docx | DOCX document | |
| 36C24418B0287-003.pdf | ||
| 36C24418B0287-000.docx | DOCX document |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
30-TS1(P1)
TELECOM & SECURITY
LEGEND & ABBREVIATIONS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Project Director
12/20/17 JWW PCGRevisions: Date:
97OfDwg.
C
X
J
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE
COMMUNICATION SYMBOLS
OUTLET DATA ONLY: LETTER INDICATES AS FOLLOWS:
C = CEILING
SCHEDULE ON LEGEND
OUTLET, TELEVISION
BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX
WITH BLANK COVER, MTD 18" [457mm] AFF UNLESS
OTHERWISE NOTED
C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF
M = MONITOR (CCTV SYSTEM)
V
CABLE TRAY
WANDER ALARM STATION; MOUNTING HEIGHT 48" AFF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
NOTES:
FOR BOTH VOICE JACKS PROVIDE 4 PAIR, 24
AWG, UNSHIELDED TWISTED PAIR, CATEGORY
5e CABLES FOR VOICE OUTLETS. SPLIT THE 4
PAIRS BETWEEN THE TWO VOICE JACKS;
WHITE/BLUE AND WHITE/ ORANGE PAIRS
TERMINATE TO THE TOP JACK, WHITE/GREEN
AND WHITE/BROWN PAIRS TERMINATE TO THE
BOTTOM JACK. CABLING SHALL BE PROVIDED
WITH WHITE OUTER JACKET
SINGLE GANG PLASTER RING BY EC
CATEGORY 5e COMPLIMENT, EIGHT POSITION, RJ-45
NON-KEYED COMMUNICATIONS
OUTLETS (TYPICAL OF FOUR)
OUTLET
NAMEPLATE
LABEL (TYP)
SINGLE GANG PLASTIC
FACEPLATE (TELCO IVORY)
JACKS DESIGNATED
FOR VOICE SHALL BE
WHITE IN COLOR WITH
VOICE ICON
4"x4"x2-1/2"D OUTLET
BOX BY EC
THREE (3) CATEGORY 5e
CABLING BY EC
TO EACH DATA JACK PROVIDE 4 PAIR,
24 AWG, UNSHIELDED TWISTED PAIR,
CATEGORY 5e CABLES FOR DATA
OUTLETS. CABLING SHALL BE
PROVIDED WITH BLUE OUTER JACKET
8 POSITION, 8 CONDUCTOR,
NON-KEYED RJ-45 CATEGORY
5e JACK BY EC
(TYPICAL OF FOUR SHOWN)
1" CONDUIT BY EC, PROVIDE NEW
CABLING IN RACEWAY FOR ENTIRE
RUN TO TELECOM CLOSET
1. THIS DETAIL APPLIES TO THE SYMBOL SHOWN ON
THE FLOOR PLANS.
2. ALL DATA WIRING SHALL BE INSTALLED IN
ACCORDANCE WITH APPLICABLE CODES AND
STANDARDS.
3. ALL DATA WIRING SHALL BE INSTALLED BY A CERTIFIED
INSTALLER.
4. THIS DETAIL IS INTENDED TO ILLUSTRATE THE INTENT
OF THE DATA HORIZONTAL WIRING AND DATA OUTLET
CONFIGURATION ONLY, ACTUAL REQUIREMENTS AND
CONDITIONS MAY VARY. IT SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO
VERIFY SITE CONDITIONS & COORDINATE
INSTALLATION REQUIREMENTS WITH OWNER &
ARCHITECT.
5. COORDINATE EXACT INFORMATION OUTLET LOCATION
WITH PLANNED FURNITURE LAYOUT.
6. AT FACEPLATE VOICE JACKS, SPLIT CATEGORY 5e
CABLE SHALL TERMINATE AS FOLLOWS. ON TOP JACK,
WHITE/BLUE PAIR SHALL TERMINATE AT WHITE/BLUE
PINS AND WHITE/ORANGE SHALL TERMINATE AT
WHITE/GREEN PINS. AT BOTTOM JACK, WHITE/GREEN
PAIR SHALL TERMINATE AT WHITE/BLUE PINS AND
WHITE/BROWN PAIR SHALL TERMINATE AT
WHITE/GREEN PINS.
7. DATA AND VOICE CABLING SHALL BE TERMINATED AT
DATA JACKS FOLLOWING PIN PAIR ASSIGNMENTS OF
EIA/TIA STANDARD T568A AND 606.
8. CABLING SHALL BE PULLED TO DATA CLOSET, PROVIDE
20' SLACK CABLE AT CLOSET FOR TERMINATIONS BY
OTHER CONTRACTS.
9. JACKS DESIGNATED FOR DATA SHALL BE ORANGE IN
COLOR AND PODITIONED ON TOP LEFT (A) AND BOTTOM
LEFT (B) OF FACEPLATE WITH IDENTIFICATION ON THE
BOTTOM OF FACEPLATE.
10. JACKS DESIGNATED FOR VOICE SHALL BE TELCO IVORY
IN COLOR AND POSITIONED ON TOP RIGHT AND
BOTTOM RIGHT OF FACEPLATE WITH IDENTIFICATION
ON THE TOP OF FACEPLATE.
JACKS DESIGNATED
FOR DATA SHALL BE
ORANGE IN COLOR
WITH DATA ICON
8-POSITION
(1)-BLUE COLOR SHEATHING, CAT
5E - 4 PR CABLE (DATA CABLING)
4"x4"x2" D
OUTLET BOX
MOUNT AT 18"
AFF, UNO
3/4" CONDUIT STUBBED ABOVE REMOVABLE
ACOUSTICAL TILE FINISHED CEILING IN CORRIDOR
W/ INSULATED BUSHING
(1)-BLUE COLOR SHEATHING, CAT 5E - 4 PR CABLE (DATA
CABLING)
SINGLE
GANG
PLASTER
RING
ORANGE COLOR
CODED ICON, DATA
ICON
DUAL CAT 5E
JACK
BLANK
COVERPLATE.
OUTLET
NAMEPLATE
LABEL (TYP)
SINGLE GANG PLASTIC
FACEPLATE (TELCO IVORY)
ORANGE COLOR
CODED ICON, DATA
ICON
4"x4"x2" D OUTLET BOX
MOUNT AT 18" AFF,
UNO
(1) GREEN COLOR SHEATHING,
CAT 5E-4PR CABLE (WIRELESS
DATA)
ORANGE COLOR
CODED ICON, DATA
ICON
SINGLE GANG
PLASTIC FACEPLATE
(TELCO IVORY)
OUTLET NAMEPLATE
LABEL (TYP)
BLANK COVERPLATE
SINGLE CAT 5E JACK,
8-POSITION
BLANK COVERPLATE
SINGLE GANG
PLASTER RING
UNO, 3/4" CONDUIT STUBBED ABOVE REMOVABLE
ACOUSTICAL TILE FINISHED CEILING IN CORRIDOR
W/ INSULATED BUSHING
NOTES:
1. THIS DETAIL APPLIES TO THE SYMBOL SHOWN ON THE FLOOR PLANS.
2. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE
CODES AND STANDARDS.
3. ALL WIRING SHALL BE INSTALLED BY A CERTIFIED INSTALLER.
4. THIS DETAIL IS INTENDED TO ILLUSTRATE THE INTENT OF THE DATA
HORIZONTAL WIRING AND DATA OUTLET CONFIGURATION ONLY, ACTUAL
REQUIREMENTS AND CONDITIONS MAY VARY. IT SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY SITE
CONDITIONS & COORDINATE INSTALLATION REQUIREMENTS WITH OWNER &
ARCHITECT.
5. WIRELESS DATA WIRING SHALL BE IN A GREEN JACKET.
6. COORDINATE EXACT INFORMATION OUTLET LOCATION WITH PLANNED
FURNITURE LAYOUT.
7. DATA CABLING SHALL BE TERMINATED AT DATA JACKS FOLLOWING PIN
PAIR ASSIGNMENTS OF TIA/EIA STANDARD T568A.
8. ALL DATA JACKS SHALL BE MANUFACTURED BY HUBBELL OR APPROVED
EQUAL..
9. CABLING SHALL BE PULLED TO DATA CLOSET 8A107, PROVIDE 20' SLACK
CABLE AT CLOSET FOR TERMINATIONS BY OTHER CONTRACTS.
NOTES:
1. THIS DETAIL APPLIES TO THE SYMBOL SHOWN ON THE FLOOR
PLANS.
2. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH
APPLICABLE CODES AND STANDARDS.
3. ALL WIRING SHALL BE INSTALLED BY A CERTIFIED INSTALLER.
4. THIS DETAIL IS INTENDED TO ILLUSTRATE THE INTENT OF THE DATA
HORIZONTAL WIRING AND DATA OUTLET CONFIGURATION ONLY,
ACTUAL REQUIREMENTS AND CONDITIONS MAY VARY. IT SHALL BE
THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY
SITE CONDITIONS & COORDINATE INSTALLATION REQUIREMENTS
WITH OWNER & ARCHITECT.
5. DATA WIRING SHALL BE IN A BLUE JACKET.
6. COORDINATE EXACT INFORMATION OUTLET LOCATION WITH
PLANNED FURNITURE LAYOUT.
7. DATA CABLING SHALL BE TERMINATED AT DATA JACKS FOLLOWING
PIN PAIR ASSIGNMENTS OF TIA/EIA STANDARD T568A.
8. ALL DATA JACKS SHALL BE MANUFACTURED BY HUBBELL OR
APPROVED EQUAL..
9. CABLING SHALL BE PULLED TO DATA CLOSET 8A107, PROVIDE 20'
SLACK CABLE AT CLOSET FOR TERMINATIONS BY OTHER
CONTRACTS.
10. JACKS DESIGNATED FOR DATA SHAL BE ORANGE IN COLOR AND
POSITIONED ON TOP LEFT (A) AND BOTTOM LEFT (B) OF FACEPLATE
WITH IDENTIFICATION ON THE BOTTOM OF FACEPLATE.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
TB** TB**
3" NOM.
CABINET WITH UFS150/200 & CF SERIES TRAY
NOT TO SCALE
CABLE TRAY TRAPEZE HANGING DETAIL
NOT TO SCALE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Project Director
DECEMBER 20, 2017 MJA SJARevisions: Date:
ARCHITECTURE
PLANNING
ENGINEERING
OfDwg.
1. EXTEND THE EXISTING FIRE ALARM SYSTEM INTO THE NEW PATIENT
ENVIRONMENT NHCU ADDITION OF THE CORPORAL MICHAEL J. CRESCENZ
VAMC LOCATED IN PHILADELPHIA, PA, PROJECT NO. 642-16-107. THIS
PROJECT IS LOCATED IN BUILDING 30. THIS PROJECT IS PART OF A SERIES
OF RENOVATIONS AND IS DESIGNATED AS PHASE 1.
2. THIS EXISTING BUILDING IS PROTECTED BY AN ADDRESSABLE GAMEWELL
SERIES E3 DIGITAL VOICE. ALL NEW DEVICES ARE TO BE CONNECTED TO
AND BE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM. THE MAIN
FIRE ALARM PANEL IS LOCATED IN ROOM 1A115. BUILDING 30 IS ALSO
NETWORKED TO A CAMPUS-WIDE PANEL IN BUILDING 1.
3. PROVIDE ALL NECESSARY MATERIALS AND LABOR TO DESIGN AND
INSTALL A COMPLETE AND OPERATIONAL SYSTEM AS DESCRIBED IN THE
PROJECT SPECIFICATIONS AND CONTRACT DRAWINGS.
4. FIRE ALARM AND DETECTION SYSTEM AND ASSOCIATED COMPONENTS
SHALL BE IN ACCORDANCE WITH:
· NFPA 70, NATIONAL ELECTRICAL CODE, 2017 EDITION
· NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2016 EDITION
· NFPA 101®, LIFE SAFETY CODE®, 2015 EDITION
· VA FIRE PROTECTION DESIGN MANUAL (VAFPDM) 7TH EDITION,
DECEMBER 2015
· ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS
· THE MANUFACTURER'S REQUIREMENTS
5. ALL AREAS PROVIDED WITH AUTOMATIC DETECTION SHALL BE ASSUMED
TO BE PROVIDED WITH A MINIMUM AMBIENT TEMPERATURE OF 40
DEGREES AND BE FREE OF EXCESSIVE DUST PARTICLES OR HUMIDITY
LEVELS, UNLESS NOTED OTHERWISE.
6. SEE THE RISER DIAGRAM DETAIL ON THIS DRAWING FOR GENERAL
INFORMATION ON HOW THE SYSTEM IS WIRED TOGETHER.
7. ALL NEW FIRE ALARM SYSTEM WIRING MUST BE IN CONDUIT. SIZE OF
CONDUIT AND PERCENT FILL MUST BE DETERMINED BY THE CONTRACTOR
AND MUST BE IN ACCORDANCE WITH NFPA 70. ALL FIRE ALARM WIRING
SHALL BE INSTALLED IN RACEWAY SEPARATE FROM ALL OTHER SYSTEMS.
8. SYSTEM CIRCUITS MUST CONFORM TO THE FOLLOWING:
· SIGNALING LINE CIRCUITS (SLC): CLASS B
· NOTIFICATION APPLIANCE CIRCUITS (NAC): CLASS B
9. PROVIDE TWISTED-PAIR, SHIELDED WIRE FOR ALL NEW AUDIO CIRCUITS.
PROVIDE A MINIMUM OF 12-18 AWG WIRE.
10. ALL ADDRESSABLE CONTROL MODULES AND ADDRESSABLE MONITOR
MODULES MUST BE LOCATED WITHIN 3 FT OF THE ASSOCIATED
NON-INTELLIGENT DEVICE MONITORED OR CONTROLLED.
11. ALL DETECTION AND CONTROL CONDUIT AND JUNCTION BOXES MUST BE
INSTALLED AS HIGH AS POSSIBLE. IN NO CASE MUST ANY PORTION OF THE
SYSTEM WIRING BE INSTALLED BELOW THE BOTTOM HORIZONTAL PLANE
OF LIGHTING FIXTURES, WITH THE EXCEPTION OF DROPS TO INDIVIDUAL
DEVICES AND PANELS. IN AREAS WITH SUSPENDED CEILINGS, ALL
CONDUIT MUST BE CONCEALED. PROVIDE ACCESS PANELS FOR
CONCEALED DEVICES AND JUNCTION BOXES, WHERE REQUIRED.
12. ALL WALL MOUNTED AUDIBLE AND VISUAL NOTIFICATION DEVICES MUST
BE MOUNTED A MINIMUM OF 80 INCHES AND A MAXIMUM OF 96 INCHES
ABOVE THE FINISHED FLOOR, PER NFPA 72.
13. SEE THE OPERATIONAL MATRIX DETAIL ON THIS DRAWING FOR
INFORMATION ON HOW THE SYSTEM SHALL FUNCTION.
14. A FULL ACCEPTANCE TEST OF ALL NEW FIRE ALARM DETECTION AND
CONTROL SYSTEM COMPONENTS IS REQUIRED AS PART OF THIS
PROJECT. THIS MUST INCLUDE A FUNCTIONAL TEST OF 100% OF NEW
INITIATING DEVICES. IN ADDITION, ANY CIRCUIT THAT IS MODIFIED SHALL
HAVE 10 PERCENT OF THE EXISTING TO REMAIN DEVICES RE-TESED.
CONTRACTOR MUST PROVIDE ALL MATERIALS AND TECHNICAL SUPPORT
TO PERFORM ACCEPTANCE TEST IN ACCORDANCE WITH NFPA 72. THE
ACCEPTANCE TESTING PERFORMED BY THE CONTRACTOR MUST BE
WITNESSED BY THE DEPARTMENT OF VETERANS AFFAIRS OR THEIR
CHOSEN REPRESENTATIVE.
15. ALL EQUIPMENT MUST BE LISTED AND FM APPROVED FOR USE ON
COMMERCIAL FIRE ALARM SYSTEMS.
16. PRIOR TO START OF WORK, CONTRACTOR MUST PERFORM A FULL
FUNCTION TEST OF THE EXISTING FIRE ALARM SYSTEM, INCLUDING THE
NETWORKED CONNECTION TO BUILDING 1, PER CHAPTER 10 OF NFPA 72.
ANY DEFECTS FOUND IN THE EXISTING SYSTEM MUST BE DOCUMENTED
AND REPORTED TO THE CONTRACTING OFFICER FOR CORRECTION.
OTHERWISE, ANY DEFECTS FOUND AT THE FINAL INSPECTION FOR THE
MODIFIED SYSTEM INSPECTION WILL BE PRESUMED TO BE THE
RESPONSIBILITY OF THE CONTRACTOR.
17. ENSURE NEW DEVICES COMMUNICATE WITH THE EXISTING NETWORKED
PANEL IN BUILDING 1.
18. THE FIRE ALARM SYSTEM IS TO REMAIN ACTIVE DURING CONSTRUCTION,
INCLUDING WITHIN ANY AREA OF WORK. MINIMIZE OR AVOID DISRUPTIONS
TO THE EXISTING SYSTEMS. FIRE ALARM SYSTEM SHALL BE RETURNED TO
SERVICE EACH DAY AND WHEN NOT UNDERGOING MODIFICATION. THE
CONTRACTING OFFICER SHALL APPROVE ALL SHUTDOWNS.
FIRE ALARM NOTES,
SYMBOLS, AND ABBREVIATIONS
A ALHPA-NUMERIC
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ASC AGENT STORAGE
CONTAINER
ASFP AIR SAMPLING DETECTOR
PANEL
CA CLEAN AGENT
CO2 CARBON DIOXIDE
CONC CONCRETE
CRAC COMPUTER ROOM AIR
CONDITIONER
CRAH COMPUTER ROOM AIR
HANDLER
DCH DRY CHEMICAL
DL DELUGE
DMC DISCONNECTING MEANS
CONTROL
EOL END OF LINE DEVICE
EPO EMERGENCY POWER OFF
ETR EXISTING TO REMAIN
EWFD EARLY WARNING FIRE
DETECTION
FA FIRE ALARM
FAA FIRE ALARM ANNUNCIATOR
PANEL
FAC FIRE ALARM
COMMUNICATOR
FACP FIRE ALARM CONTROL
PANEL
FO FOAM
FP FIRE PUMP
FSA FIRE SYSTEM ANNUNCIATOR
FSCP FIRE SYSTEM CONTROL
PANEL
FTR FIRE ALARM TRANSMITTER
G GRAPHIC
HL HALON
HVAC HEATING, VENTILATION AND
AIR CONDITIONING
MAX MAXIMUM
MIN MINIMUM
MT METAL TILE
N.C. NORMALLY CLOSED
(CONTACT)
N.O. NORMALLY OPEN (CONTACT)
NAC NOTIFICATION APPLIANCE
CIRCUIT
NIC NOT IN CONTRACT
NTS NOT TO SCALE
PA PRE-ACTION SYSTEM
PF FIRE PUMP POWER FAIL
PH FIRE PUMP PHASE
REVERSAL
PL PLASTER
PMO FIRE PUMP CONTROLLER -
MANUAL OFF
POC POINT OF CONNECTION
PR FIRE PUMP RUN
PRV PRESSURE
REGULATING/RELIEF VALVE
RA RETURN AIR (HVAC)
RF RADIO FREQUENCY
RTU ROOF TOP UNIT
RX REMOVE EXISTING DEVICE
SA SUPPLY AIR (HVAC)
SLC SIGNALING LINE CIRCUIT
SPL HIDDEN SPLINE (CEILING)
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VEWFD VERY EARLY WARNING FIRE
DETECTION
WCH WET CHEMICAL
WM WATER MIST
WP WEATHER PROOF
EVAC
FATC
FACP
FAA
FTR
FAC
FSCP
FSA
ASFP
DMC
AIM
AOM
AA
NAC
EOL
MIC
EOL
ACU
FIRE ALARM RISER GENERAL NOTES:
BLDG 30 - 2ND FLOOR
BLDG 30 - 1ST FLOOR
EXISTING
GAMEWELL
SERIES E3
DIGITAL
VOICE
FACP
NEW
REMOTE
POWER
SUPPLY
#2E
120 V
(1A115 -
ELECTRICAL
ROOM)
120 V
CCC
1. RISER IS INTENDED TO SHOW GENERAL SYSTEM ARCHITECTURE
AS IT RELATES TO THIS PROJECT. DIAGRAM REPRESENT MULTIPLE
TYPICAL DEVICES, APPLIANCES, AND CIRCUITS.
2. CONTRACTOR IS RESPONSIBLE FOR VERIFYING QUANTITY AND
LOCATION OF ALL EXISTING PANELS AND DEVICES.
3. CONTRACTOR IS RESPONSIBLE FOR VERIFYING LOCATION OF ALL
NEW CONNECTIONS OF NEW DEVICES.
4. CONTRACTOR MUST CREATE NEW CIRCUITS FROM NEW POWER
SUPPLIES.
5. T-TAPING INTO EXISTING SLC IS PERMITTED.
EXISTING
FATC
#5
F F
AOM
(2B117 -
ELECTRICAL
ROOM)
NEW
AUDIO
PANEL
EXISTING
FATC
#4
(2B144 -
ELECTRICAL
CLOSET)
(2B127 -
ELECTRICAL
ROOM)
NEW
NAC
PANEL
EXISTING
REMOTE
POWER
SUPPLY
120 V
CCC
EXISTING
FATC
#3
F F
AOM
(1A115 -
ELECTRICAL
ROOM)
NEW
AUDIO
PANEL
(1B128 -
ELECTRICAL
ROOM)
NEW
NAC
PANEL
AutoCAD SHX Text
AutoCAD SHX Text
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER PHILADELPHIA, PA
AutoCAD SHX Text 642-16-107
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1436 410.803.0009 fax 410.836.6611
AutoCAD SHX Text BUILDING COST CONSULTANTS COST ESTIMATING 12917 - 30TH AVENUE PLATTSMOUTH, NEBRASKA 68048 402.298.8260 - FAX 402.298.8290
AutoCAD SHX Text KOFFEL ASSOCIATES FIRE PROTECTION ENGINEERS 8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MARYLAND 21045 410.750.2246 - FAX 410.750.2588
AutoCAD SHX Text WHITMAN REQUARDT & ASSOCIATES CIVIL ENGINEER 801 SOUTH CAROLINE STREET BALTIMORE, MARYLAND 21231 410.864.1058 - FAX 443.224.1820
AutoCAD SHX Text RICKERT ENGINEERING, INC. STRUCTURAL ENGINEERING 8813 WALTHAM WOODS ROAD, SUITE 301 BALTIMORE, MARYLAND 21234 410.663.5110 - FAX 410.663.5114
AutoCAD SHX Text
PHASE 1 - UPGRADE PATIENT ENVIRONMENT NHCU ADDITION
AutoCAD SHX Text BURDETTE KOEHLER MURPHY & ASSOCIATES, INC. MECHANICAL / ELECTRICAL ENGINEERS 1416 CLARKVIEW ROAD BALTIMORE, MARYLAND 21209 410.323.0600 - FAX 410.377.2543
AutoCAD SHX Text
FIRE ALARM PROJECT NOTES:
AutoCAD SHX Text
30-FA1
AutoCAD SHX Text
FIRE ALARM SYSTEM ABBREVIATIONS
AutoCAD SHX Text FIRE ALARM SYSTEM SYMBOLS FIRE ALARM CONTROL PANEL FIRE ALARM ANNUNCIATOR PANEL (SUBSCRIPT DENOTES TYPE) FIRE ALARM TRANSMITTER FIRE ALARM COMMUNICATOR FIRE SYSTEM CONTROL PANEL (SUBSCRIPT DENOTES SYSTEM TYPE) FIRE SYSTEM ANNUNCIATOR (SUBSCRIPT DENOTES SYSTEM TYPE) AIR SAMPLING DETECTOR PANEL DISCONNECTING MEANS CONTROL PANEL ADDRESSABLE INPUT MODULE (MONITOR MODULE) ADDRESSABLE OUTPUT MODULE (CONTROL MODULE) AUDIO AMPLIFIER PANEL NAC POWER EXTENDER PANEL END OF LINE DEVICE VOICE EVACUATION SYSTEM REMOTE MICROPHONE VOICE EVACUATION SYSTEM CONTROL PANEL END OF LINE DEVICE - RESISTOR AUTONOMOUS CONTROL UNIT
AutoCAD SHX Text ULTRAVIOLET/INFRARED FLAME DETECTOR SPEAKER NOTIFICATION APPLIANCE STROBE NOTIFICATION APPLIANCE (SUBSCRIPT DENOTES CANDELA RATING) COMBINATION SPEAKER/STROBE APPLIANCE (SUBSCRIPT DENOTES CANDELA RATING) ROTATING BEACON ALARM BELL WATER MOTOR GONG ELECTRO-MAGNETIC DOOR HOLDER FIRE DAMPER SMOKE DAMPER COMBINATION FIRE/SMOKE DAMPER NEW POINT OF CONNECTION INTO EXISTING CIRCUIT FIRE ALARM LINETYPES: TYPICAL NEW DEVICE TYPICAL EXISTING DEVICE TO REMAIN TYPICAL EXISTING DEVICE TO BE REMOVED
AutoCAD SHX Text RATE COMPENSATION HEAT DETECTOR COMBINATION FIXED TEMPERATURE AND RATE OF RISE HEAT DETECTOR COMBINATION SMOKE HEAT DETECTOR LINE-TYPE HEAT DETECTOR GAS DETECTOR SMOKE DETECTOR PHOTOELECTRIC SMOKE DETECTOR IONIZATION SMOKE DETECTOR BEAM SMOKE DETECTOR - TRANSMITTER BEAM SMOKE DETECTOR - RECEIVER AIR SAMPLING SMOKE DETECTOR SPOT TYPE VEWFD SMOKE DETECTOR UNDER FLOOR SMOKE DETECTOR ABOVE CEILING SMOKE DETECTOR CRAH/CRAC UNIT SMOKE DETECTOR DUCT SMOKE DETECTOR (SUPERSCRIPT DENOTES SUPPLY OR RETURN) FLAME DETECTOR ULTRAVIOLET FLAME DETECTOR INFRARED FLAME DETECTOR
AutoCAD SHX Text FIRE ALARM TERMINAL CABINET ADDRESSABLE MODULE FOR FLOW SWITCH PRESSURE SWITCH WATER PRESSURE SWITCH LOW AIR PRESSURE SWITCH HIGH AIR PRESSURE SWITCH COMBINATION HIGH/LOW AIR PRESSURE SWITCH TAMPER SWITCH ADDRESSABLE MODULE FOR VALVE WITH TAMPER SWITCH ALARM SYSTEM ACTIVATION (SUBSCRIPT DENOTES SYSTEM TYPE) ALARM SYSTEM ABORT SWITCH (SUBSCRIPT DENOTES SYSTEM TYPE) FIRE ALARM MANUAL PULL STATION FIRE SERVICE TELEPHONE FIRE SERVICE TELEPHONE JACK FIRE SERVICE TELEPHONE ACCESSIBLE FIRE SERVICE TELEPHONE HEADSET HEAT DETECTOR FIXED TEMPERATURE HEAT DETECTOR RATE OF RISE HEAT DETECTOR
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text P
AutoCAD SHX Text J
AutoCAD SHX Text
XX
AutoCAD SHX Text
LH
AutoCAD SHX Text
HA
AutoCAD SHX Text
LA
AutoCAD SHX Text
XX
AutoCAD SHX Text W
AutoCAD SHX Text
UV/IR
AutoCAD SHX Text
IR
AutoCAD SHX Text
UV
AutoCAD SHX Text
XX
AutoCAD SHX Text X
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text U
AutoCAD SHX Text V
AutoCAD SHX Text
ASD
AutoCAD SHX Text
BR
AutoCAD SHX Text
BT
AutoCAD SHX Text I
AutoCAD SHX Text P
AutoCAD SHX Text R/F
AutoCAD SHX Text R/C
AutoCAD SHX Text
XX
AutoCAD SHX Text C
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text H
AutoCAD SHX Text R
AutoCAD SHX Text
RE
AutoCAD SHX Text (P1)
AutoCAD SHX Text
FIRE ALARM RISER
NAC
AA
AOM
AOM
AOM
AOM
AOM
1B128
(e)2 Bed
Room
1B127
(e)2 Bed
Room
1B129
(e)2 Bed
Room
1B126
(e)2 Bed
Room
1B130
(e)2 Bed
Room
1B125
(e)2 Bed
Room
1B128a
(e)S.Tlt.
1B126a
(e)S.Tlt.
C1-13
(e)Corridor
New Stair #3
1ST3
Storage
1B127
Restroom
1B126
Staff Lounge
1B125
Restroom
1B125A
Elec.
1B128
Corridor
C1-15
Activity/Dining
1B124
2B128
(e)2 Bed
Room
2B127
(e)2 Bed
Room
2B129
(e)2 Bed
Room
2B126
(e)2 Bed
Room
2B130
(e)2 Bed
Room
2B125
(e)2 Bed
Room
2B128a
(e)S.Tlt.
2B126a
(e)S.Tlt.
C2-5
(e)Corridor
Elec.
2B127
Storage
2B126
Restroom
2B125
Staff Lounge
2B124
Restroom
2B124A
Corridor
C2-6
Activity /
Dining
2B123
Stair #3
2ST3
AOM
NAC
AA
AOM
1B128
(e)2 Bed
Room
1B127
(e)2 Bed
Room
1B125
Staff Lounge
1B125A
Restroom
1B124
Activity/Dining
C1-15
Corridor
1ST3
Stair #3
2B128
(e)2 Bed
Room
2B127
(e)2 Bed
Room
2B124
Staff Lounge
2B124A
Restroom
2B123
Activity/Dining
C2-6
Corridor
2ST3
Stair #3
AOM
AOM
" = 1'-0"
FIRE ALARM - 2ND FLOOR PLAN - NEW WORK
1. T-TAP INTO THE EXISTING SLC AS NECESSARY TO
ACCOMMODATE NEW INITIATING APPLIANCES. SEE SHEET
30-FA1(P1) FOR MORE DETAILS.
2. EXISTING DEVICES IN THE AREA OF WORK CANNOT BE RE-USED
AND MUST BE DEMOLISHED IN THEIR ENTIRETY, WHICH
INCLUDES ALL DEVICES IN PHASE 2A AND 2B THAT ARE
CURRENTLY ONLY MOUNTED ON WHIPS. RETURN ALL INITIATING
AND NOTIFICATION DEVICES TO GOVERNMENT FOR SPARE
PARTS.
3. PROVIDE ONE NEW NOTIFICATION CIRCUIT PER SMOKE ZONE.
4. DO NOT USE TERMINAL STRIPS OR CONNECTOR NUTS TO PIECE
WIRING BACK TOGETHER AFTER DEMOLISHED DEVICES ARE
REMOVED, UNLESS IS NECESSARY TO MAINTAIN AN EXISTING TO
REMAIN CIRCUIT OUTSIDE OF THE CURRENT PHASE OR OUTSIDE
OF THE PROJECT SPACE.
EXISTING DEVICES IN THIS CORRIDOR SHALL REMAIN AS-IS.
THERE ARE CURRENTLY NO FIRE ALARM DEVICES IN THIS PARTIALLY
CONSTRUCTED ADDITION.
ADDRESSABLE OUTPUT MODULE FOR RELEASE FOR DOORS ON
SECURITY LOCKS.
PROVIDE SMOKE DETECTORS IN SPACES OPEN TO THE CORRIDOR.
COORDINATE 120V POWER WITH ELECTRICAL.
SMOKE DETECTOR FOR PANEL PROTECTION.
PROVIDE SMOKE DETECTOR WITHIN 5 FEET OF SMOKE
BARRIER CROSS CORRIDOR DOOR.
RELEASE FOR SMOKE BARRIER DOORS ON HOLD-OPEN DEVICES.
POWER FROM FIRE ALARM SYSTEM.
ADDRESSABLE OUTPUT MODULE TO LIGHTING CONTROL SYSTEM TO
RESTORE ALL MEANS OF EGRESS ILLUMINATION ON ANY FIRE
ALARM. EXACT QUANTITY AND LOCATION SHALL BE DETERMINED IN
FIELD.
WIRE THIS SMOKE DETECTOR FROM UNIT C SLC.
THIS DOOR IS LOCKABLE BUT REQUIRES NO FIRE ALARM INTERFACE
AS IT UNLOCKS ON CARD ACCESS ONLY PER THE VA.
ADDRESSABLE OUTPUT MODULE FOR RELEASE FOR EXTERIOR
GATE ON SECURITY LOCK. REFER TO DRAWING 30-ES2(P1) FOR
LOCATION. INSTALL INSIDE EAST WING. T-TAP INTO NEAREST SLC
CIRCUIT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Project Director
DECEMBER 20, 2017 MJA SJARevisions: Date:
ARCHITECTURE
PLANNING
ENGINEERING
Unit B
Unit C
Unit A
Court
C o u r t
N
Plan North 1st Floor Building Key Plan
N
True North
(N.I.C.)
(N.I.C.)
(N.I.C.)
N
I C
A d d i t i o n
OfDwg.
" = 1'-0"
FIRE ALARM - 1ST FLOOR PLAN - NEW WORK
" = 1'-0"
FIRE ALARM - 2ND FLOOR PLAN - DEMOLITION
" = 1'-0"
FIRE ALARM - 1ST FLOOR PLAN - DEMOLITION
FIRE ALARM - FIRST AND SECOND
FLOOR PLANS
30-FA-2
30-FA-2
30-FA-2
30-FA-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
SEAL DOOR AS REQUIRED FOR ICRA BARRIER
AutoCAD SHX Text
REMOVE EXISTING ICRA BARRIER AND CONTACT MATS
AutoCAD SHX Text
SEAL DOOR AS REQUIRED FOR ICRA BARRIER
AutoCAD SHX Text
REMOVE EXISTING ICRA BARRIER AND CONTACT MATS
AutoCAD SHX Text
LINE OF WALLS TO BE FORMED INTO ICRA BARRIERS
AutoCAD SHX Text
LINE OF WALLS TO BE FORMED INTO ICRA BARRIERS
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text KEY NOTES: SMOKE DETECTOR FOR PANEL PROTECTION. ADDRESSABLE OUTPUT MODULE TO LIGHTING CONTROL SYSTEM TO
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER PHILADELPHIA, PA
AutoCAD SHX Text 642-16-107
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1436 410.803.0009 fax 410.836.6611
AutoCAD SHX Text BUILDING COST CONSULTANTS COST ESTIMATING 12917 - 30TH AVENUE PLATTSMOUTH, NEBRASKA 68048 402.298.8260 - FAX 402.298.8290
AutoCAD SHX Text KOFFEL ASSOCIATES FIRE PROTECTION ENGINEERS 8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MARYLAND 21045 410.750.2246 - FAX 410.750.2588
AutoCAD SHX Text WHITMAN REQUARDT & ASSOCIATES CIVIL ENGINEER 801 SOUTH CAROLINE STREET BALTIMORE, MARYLAND 21231 410.864.1058 - FAX 443.224.1820
AutoCAD SHX Text RICKERT ENGINEERING, INC. STRUCTURAL ENGINEERING 8813 WALTHAM WOODS ROAD, SUITE 301 BALTIMORE, MARYLAND 21234 410.663.5110 - FAX 410.663.5114
AutoCAD SHX Text
PHASE 1 - UPGRADE PATIENT ENVIRONMENT NHCU ADDITION
AutoCAD SHX Text BURDETTE KOEHLER MURPHY & ASSOCIATES, INC. MECHANICAL / ELECTRICAL ENGINEERS 1416 CLARKVIEW ROAD BALTIMORE, MARYLAND 21209 410.323.0600 - FAX 410.377.2543
AutoCAD SHX Text
30-FA2
AutoCAD SHX Text (P1)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Project Director
DECEMBER 20, 2017 MJA SJARevisions: Date:
ARCHITECTURE
PLANNING
ENGINEERING
OfDwg.
POC POINT OF CONNECTION
QR QUICK RESPONSE (SPRINKLER)
STL STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
FHV FIRE HOSE VALVE
GYP GYPSUM WALL BOARD (SHEETROCK)
HT HIGH TEMPERATURE (SPRINKLER)
ITC INSPECTORS TEST CONNECTION
MAX MAXIMUM
MIN MINIMUM
MT METAL TILE
NIC NOT IN CONTRACT
NS NON-SPRINKLERED
NTS NOT TO SCALE
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
BFP BACKFLOW PREVENTER
COL COLUMN
CONC CONCRETE
DN DOWN
EC EXTENDED COVERAGE (SPRINKLER)
ETR EXISTING TO REMAIN
EXP EXPOSED (NO CEILING)
FDC FIRE DEPARTMENT CONNECTION
NOYES
WILL THERE BE ANY STORAGE OR PRODUCTS
OVER 12 FT (3.5 M) IN HEIGHT?
WILL THERE BE ANY STORAGE OF PLASTIC,
RUBBER, OR SIMILAR PRODUCTS OVER 5 FT (1.3 M)
HIGH EXCEPT AS DESCRIBED ABOVE?
THIS FORM HAS BEEN COMPLETED BY KOFFEL
ASSOCIATES ON BEHALF OF THE OWNER BASED ON
INFORMATION PROVIDED BY THE OWNER AND HIS AGENTS.
I CERTIFY THAT I HAVE KNOWLEDGE OF THE INTENDED USE
OF THE PROPERTY AND THAT THE ABOVE INFORMATION IS
CORRECT.
SIGNATURE OF OWNER'S REPRESENTATIVE OR AGENT
DATE: SEPTEMBER 7, 2017
KOFFEL ASSOCIATES, INC.
NAME OF OWNER'S REPRESENTATIVE OR AGENT
COMPLETING CERTIFICATE
CONSULTING ENGINEER
RELATIONSHIP AND FIRM OF AGENT
NOYES
INDICATE WHETHER ANY OF THE FOLLOWING SPECIAL
MATERIALS ARE INTENDED TO BE PRESENT:
FLAMMABLE OR COMBUSTIBLE LIQUIDS
AEROSOL PRODUCTS
NITRATE FILM
PYROXYLIN PLASTIC
COMPRESSED OR LIQUEFIED GAS CYLINDERS
LIQUID OR SOLID OXIDIZERS
ORGANIC PEROXIDE FORMULATIONS
IDLE PALLETS
INDICATE WHETHER THE PROTECTION IS INTENDED FOR
ONE OF THE FOLLOWING SPECIALIZED OCCUPANCIES OR
AREAS:
SPRAY AREA OR MIXING ROOM
SOLVENT EXTRACTION
LABORATORY USING CHEMICALS
OXYGEN-FUEL GAS SYSTEM FOR WELDING OR
CUTTING
ACETYLENE CYLINDER CHARGING
PRODUCTION OR USE OF COMPRESSED OR
LIQUEFIED GASES
COMMERCIAL COOKING OPERATION
CLASS A HYPERBARIC CHAMBER
CLEANROOM
INCINERATOR WASTE HANDLING SYSTEM
LINEN HANDLING SYSTEM
WATER-COOLING TOWER
YES NO
NOYES
NAME OF OWNER:
U.S. DEPARTMENT OF VETERAN AFFAIRS (VA)
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER
BUILDING 30
UPGRADE PATIENT ENVIRONMENT NHCU ADDITION
PHASE 1
EXISTING OR PLANNED CONSTRUCTION IS:
FIRE RESISTIVE OR NONCOMBUSTIBLE
WOOD FRAME OR ORDINARY
(MASONRY WALLS WITH WOOD BEAMS)
UNKNOWN
IS THE SYSTEM INSTALLATION INTENDED FOR ONE OF THE
FOLLOWING SPECIAL OCCUPANCIES:
AIRCRAFT HANGAR
FIXED GUIDEWAY TRANSIT SYSTEM
RACE TRACK STABLE
MARINE TERMINAL, PIER, OR WHARF
AIRPORT TERMINAL
AIRCRAFT ENGINE TEST FACILITY
POWER PLANT
WATER-COOLING TOWER
NOYES
UPRIGHT SPRINKLER;
ON SPRIG
PENDENT SPRINKLER;
ON DROP NIPPLE
SPRINKLER GUARD;
SHOWN ON UPRIGHT SPRINKLER
HEIGHT INDICATOR
NON-SPRINKLERED AREA
FULLY SPRINKLERED AREA
PARTIALLY SPRINKLERED AREA
AREA NOT IN PROJECT SCOPE
AREA NOT IN CURRENT PHASE
SPRINKLER ZONE BOUNDARY
TEMPORARY SPRINKLER ZONE BOUNDARY
TEMPORARY 1-HOUR ICRA FIRE BARRIER
PRESSURE GAUGE
ALARM CHECK VALVE
DRY PIPE VALVE
FIRE HYDRANT
FIRE DEPARTMENT CONNECTION
UPRIGHT SPRINKLER
PENDENT SPRINKLER
WATER METER
FLUSHING CONNECTION OR CAP
CONTROL VALVE
CHECK VALVE
OS&Y GATE VALVE
BUTTERFLY VALVE
NON-INDICATING CONTROL VALVE
BACKFLOW PREVENTER;
DOUBLE CHECK TYPE
POST-INDICATING VALVE
ZONE CONTROL ASSEMBLY
WATER FLOW SWITCH
NEW SYSTEM PIPING
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE REMOVED
NEW POINT OF CONNECTION
PIPE HANGER
SYSTEM RISER
DRAIN RISER
HOSE VALVE
PIPE ELBOW DOWN
PIPE TEE DOWN
CHANGE IN PIPE SIZE
1. EXTEND THE WET-PIPE SPRINKLER SYSTEMS INTO THE NEW PATIENT
ENVIRONMENT NHCU ADDITION OF THE CORPORAL MICHAEL J. CRESCENZ
VAMC LOCATED IN PHILADELPHIA, PA, PROJECT NO. 642-16-107. ALSO
PROVIDE TWO NEW ZONE CONTROL ASSEMBLIES. THIS PROJECT IS
LOCATED IN BUILDING 30 OF VA PHILADELPHIA. THIS PROJECT IS PART OF A
SERIES OF RENOVATIONS AND IS DESIGNATED AS PHASE 1.
2. A NEW 4-INCH STANDPIPE/SPRINKLER RISER IS REQUIRED IN THE NEW STAIR
AS THE FLOOR LEVEL OF THE HIGHEST STORY IN THE ADDITION IS LOCATED
MORE THAN 30 FEET ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
VEHICLE ACCESS. A STANDPIPE CALCULATION IS NOT REQUIRED AS THE
EXISTING SYSTEM INFRASTRUCTURE CANNOT SUPPORT FULL COMPLIANCE
WITH THE CURRENT EDITION OF NFPA 14.
3. THIS PROJECT ALSO INCLUDES SPRINKLER MODIFICATIONS TO SUPPORT
TWO NEW IT ROOMS AND ONE NEW ELECTRICAL ROOM. SEE DETAIL 3/30-FS4
AND 4/30-FS4 FOR MORE INFORMATION.
4. PROVIDE ALL NECESSARY MATERIALS AND LABOR TO FURNISH AND INSTALL
THE SYSTEM AS DESCRIBED IN THE PROJECT CONTRACT DOCUMENTS.
5. ALL REFERENCE TO THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL
MEAN THE DEPARTMENT OF VETERAN AFFAIRS (VA) REGIONAL FIRE
PROTECTION ENGINEER. ALL REFERENCE TO THE ENGINEER SHALL MEAN
KOFFEL ASSOCIATES, INC. ALL REFERENCE TO THE OWNER SHALL MEAN
THE VA.
6. SPRINKLER SYSTEM AND ASSOCIATED COMPONENTS SHALL BE IN
ACCORDANCE WITH:
· NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS,
2016 EDITION
· NFPA 14, STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE
SYSTEMS, 2016 EDITION
· NFPA 101®, LIFE SAFETY CODE®, 2015 EDITION
· VA FIRE PROTECTION DESIGN MANUAL (VAFPDM) 7TH EDITION, DECEMBER
· THE MANUFACTURER'S REQUIREMENTS
· APPLICABLE LOCAL CODES AND REGULATIONS
7. THE FOLLOWING DESIGN CRITERIA APPLIES:
· UNLESS NOTED OTHERWISE - LIGHT HAZARD: 0.10 GPM/SQ FT OVER 1,500
SQ FT
· ELECTRICAL ROOMS - ORDINARY HAZARD GROUP I: 0.15 GPM/SQ FT OVER
1,500 SQ FT
· STORAGE ROOMS - ORDINARY HAZARD GROUP II: 0.2 GPM/SQ FT OVER
1,500 SQ FT
PER SECTION 11.2.3.2.3.1 OF NFPA 13, A REDUCTION IN THE DESIGN AREA UP
TO 40% IS PERMITTED WHERE LISTED QUICK-RESPONSE SPRINKLERS ARE
UTILIZED.
8. A MUNICIPAL WATER SUPPLY SERVES THE BUILDING 30 SPRINKLER SYSTEM.
THE FIRE SPRINKLER LINE ENTERS THE BUILDING IN A BASEMENT
MECHANICAL ROOM. RESULTS FROM THE MOST RECENT HYDRANT FLOW
TEST ARE:
STATIC: 83 PSI
RESIDUAL: 80 PSI @ 1,307 GPM
LOCATION: UNDERGROUND MAIN DOWNSTREAM OF METER VAULT
DATE OF TEST: 8-29-17
SOURCE: KEYSTONE FIRE PROTECTION CO.
CONTRACTOR MUST CONDUCT A FIRE HYDRANT FLOW TEST. THE FLOW
HYDRANT MUST BE THE ON-SITE HYDRANT TO THE NORTH OF BUILDING AND
THE PRESSURE HYDRANT THE HYDRANT TO THE SOUTH. PROVIDE FLOW
TEST DATA NO MORE THAN ONE YEAR OLD FOR ALL HYDRAULIC
CALCULATIONS.
9. ALL HYDRAULIC CALCULATIONS MUST YIELD AT LEAST A 10 PERCENT
SAFETY FACTOR FOR EACH SPRINKLER DESIGN AREA, INCLUDING REQUIRED
HOSE STREAMS, PER VAFPDM §6.1D.
10. REPLACE ALL EXISTING SPRINKLERS IN THE PROJECT AREAS WITH NEW
SPRINKLERS. SPRINKLER TYPES MUST BE AS DESCRIBED IN THE PROJECT
SPECIFICATIONS. ALL SPRINKLERS MUST BE LISTED AND FM-APPROVED.
SPRINKLERS MUST ALSO BE QUICK RESPONSE, UNLESS PROHIBITED BY
THEIR LISTING.
11. SPRINKLER PIPE AND FITTINGS MUST MEET THE FOLLOWING CRITERIA:
· PIPE SIZES 2 IN. AND SMALLER: SCHEDULE 40, BLACK STEEL, MEETING
ASTM A53 (TYPE E GRADE B) OR A795 (TYPE E GRADE A) SPECIFICATIONS,
CONNECTED WITH THREADED FITTINGS.
· PIPE SIZES 2-1/2 IN. AND LARGER: SCHEDULE 10, BLACK STEEL, MEETING
ASTM A135 OR A795 TYPE E GRADE A SPECIFICATIONS, CONNECTED WITH
LISTED GROOVED COUPLINGS.
12. PIPE FITTINGS MUST INCLUDE:
· THREADED FITTINGS FOR SCHEDULE 40 PIPE MUST CONFORM TO SECTION
6.4 OF NFPA 13.
· ROLL GROOVED FITTINGS FOR SCHEDULE 10 PIPE MUST BE UL LISTED.
COUPLINGS MUST COMPLY WITH ASTM A536, AND A183 SPECIFICATIONS
WITH GRADE E, TYPE A GASKETS. ALL COMPONENTS MUST BE FROM A
SINGLE MANUFACTURER.
13. ALL MATERIALS MUST BE LISTED FOR USE ON COMMERCIAL FIRE
PROTECTION SYSTEMS. SPRINKLERS MUST ALSO BE FACTORY MUTUAL (FM)
APPROVED, PER VAFPDM § 6.1K.
14. ALL NECESSARY CONNECTIONS TO THE FIRE ALARM SYSTEM MUST BE MADE
BY AND COORDINATED WITH THE FIRE ALARM CONTRACTOR. SYSTEM
ACCEPTANCE TESTS MUST BE CONDUCTED BY THE FIRE ALARM
CONTRACTOR AND WITNESSED BY THE VA.
15. ALL HANGERS MUST BE LISTED FOR USE WITH SPRINKLER SYSTEMS.
HANGER INSTALLATION AND SPACING MUST BE IN ACCORDANCE WITH NFPA
13.
16. ALL SPRINKLER SYSTEM PIPING AND HANGERS MUST BE CONCEALED
WHEREVER POSSIBLE. PROVIDE ACCESS PANELS FOR ALL VALVES, WHERE
REQUIRED.
17. PENETRATION OF FIRE-RATED ASSEMBLIES MUST BE SEALED WITH A
THROUGH-PENETRATION SYSTEM APPROPRIATE FOR THE RATING OF THE
WALL PENETRATED.
18. COORDINATE THE LOCATION OF SPRINKLER PIPING SHOWN WITH EXISTING
MECHANICAL, STRUCTURAL, AND CEILING SYSTEMS. COORDINATE FINAL
LOCATIONS OF ALL SPRINKLERS, PIPING, PIPE SIZES, HANGER LOCATIONS,
ETC.
19. CONTRACTOR MUST BE RESPONSIBLE FOR DEVELOPMENT OF SHOP
DRAWINGS, HYDRAULIC CALCULATIONS, PERMIT FEES, APPROVAL OF SHOP
DRAWINGS, AND ACCEPTANCE OF THE SYSTEM BY THE OWNER.
20. PRIOR TO SUBMITTING AN APPLICATION FOR SPRINKLER PERMIT TO THE
AHJ, PROVIDE TWO COPIES OF ALL SHOP DRAWINGS, HYDRAULIC
CALCULATIONS, AND PRODUCT DATA SHEETS TO THE OWNER OR ENGINEER
FOR REVIEW AND COMMENT. PERMIT APPLICATION MUST NOT BE MADE
UNTIL SUCH TIME THAT THE OWNER OR ENGINEER HAS COMPLETED A
REVIEW OF THE SHOP DRAWING PACKAGE.
21. CONDUCT HYDROSTATIC TESTS OF ENTIRE AREA OF WORK TO 200 PSI FOR
TWO HOURS. A SEPARATE HYDROSTATIC TEST IS ALSO REQUIRED FOR THE
WORK IN THE NEW ELECTRICAL ROOM INDICATED IN DETAIL 3/30-FS4.
22. ALL SPRINKLER SYSTEMS ARE TO REMAIN ACTIVE DURING CONSTRUCTION,
INCLUDING WITHIN THE AREA OF WORK. MINIMIZE OR AVOID DISRUPTIONS
TO THE EXISTING SYSTEMS. SPRINKLER SYSTEM SHALL BE RETURNED TO
SERVICE EACH DAY AND WHEN NOT UNDERGOING MODIFICATION. THE
CONTRACTING OFFICER SHALL APPROVE ALL SHUTDOWNS.
23. SPRINKLERS MUST BE LOCATED IN SUSPENDED CEILING TILES AS INDICATED
ON DETAIL 2/30-FS4(P1). ARMOVERS AND DROPS TO INDIVIDUAL SPRINKLERS
MUST BE FIELD CUT TO ENSURE PROPER SPRINKLER PLACEMENT.
24. PLAIN END FITTINGS WITH MECHANICAL COUPLINGS AND FITTINGS THAT USE
STEEL GRIPPING DEVICES OR SADDLE-LETS TO BIT INTO THE PIPE ARE
PROHIBITED. ALL EXISTING DEVICES SHALL BE REMOVED. GROOVED-TYPE
MECHANICAL TEES ARE ALLOWABLE.
FIRE SUPPRESSION NOTES,
SYMBOLS, AND ABBREVIATIONS
AutoCAD SHX Text
AutoCAD SHX Text
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER PHILADELPHIA, PA
AutoCAD SHX Text 642-16-107
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1436 410.803.0009 fax 410.836.6611
AutoCAD SHX Text BUILDING COST CONSULTANTS COST ESTIMATING 12917 - 30TH AVENUE PLATTSMOUTH, NEBRASKA 68048 402.298.8260 - FAX 402.298.8290
AutoCAD SHX Text KOFFEL ASSOCIATES FIRE PROTECTION ENGINEERS 8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MARYLAND 21045 410.750.2246 - FAX 410.750.2588
AutoCAD SHX Text WHITMAN REQUARDT & ASSOCIATES CIVIL ENGINEER 801 SOUTH CAROLINE STREET BALTIMORE, MARYLAND 21231 410.864.1058 - FAX 443.224.1820
AutoCAD SHX Text RICKERT ENGINEERING, INC. STRUCTURAL ENGINEERING 8813 WALTHAM WOODS ROAD, SUITE 301 BALTIMORE, MARYLAND 21234 410.663.5110 - FAX 410.663.5114
AutoCAD SHX Text
PHASE 1 - UPGRADE PATIENT ENVIRONMENT NHCU ADDITION
AutoCAD SHX Text BURDETTE KOEHLER MURPHY & ASSOCIATES, INC. MECHANICAL / ELECTRICAL ENGINEERS 1416 CLARKVIEW ROAD BALTIMORE, MARYLAND 21209 410.323.0600 - FAX 410.377.2543
AutoCAD SHX Text
FIRE SUPPRESSION PROJECT NOTES:
AutoCAD SHX Text
FIRE SUPPRESSION ABBREVIATIONS
AutoCAD SHX Text
OWNER'S INFORMATION CERTIFICATE
AutoCAD SHX Text
FIRE SUPPRESSION SYMBOLS
AutoCAD SHX Text 8'-0"
AutoCAD SHX Text
AS
AutoCAD SHX Text
AS
AutoCAD SHX Text
NS
AutoCAD SHX Text
ZCA
AutoCAD SHX Text
FS
AutoCAD SHX Text
30-FS1
AutoCAD SHX Text M
(P1)
FROM 12" CITY MAIN
8"
PRESSURE
HYDRANT
FLOW
HYDRANT
8"
8"
8"
6" TO METER PIT
AND BUILDING
M
4" UP TO FIRST FLOOR.
APPROXIMATELY 13 FT.
4" 6"6"
6" BACK FLOW
PREVENTER ASSEMBLY
(AMES MODEL 2000SS).
6"
REFER TO SITE SPRINKLER
INFRASTRUCTURE DETAIL ON THIS
SHEET FOR CONTINUATION.
ZCA
ZCA
ZCA
ZCA
ZCA
4" FROM
BASEMENT
4"
4"
4"4"
4"
3" UP TO
SECOND
FLOOR
" UP TO
SECOND FLOOR
APPROXIMATELY
13FT
" UP TO
SECOND FLOOR
2"
1ST UNIT B WEST WING
ZONE
1ST UNIT B SOUTH WING
ZONE
1ST UNIT B EAST WING
ZONE
1ST UNIT B CENTER
WING ZONE
1ST UNIT A SOUTH
ZONE
2"
3"
1B122
1B125 1B124
1B118
1B118A
1B119
1B120
1B108A
1B108
1B106
1B107
1B102
1B132
1B130
1B124A
1B123
1B131
1B130A
1B132A
1B122A
1B121
1B133B
1B133A
C1-10
C1-14
1B104 1B103
1B148
1B133
1B134
1B134A
1B135
1B135A
1B145A
1B147
1B146
1B150
1B144
1B145
B
B
1B101
1B153 1B151
2ND UNIT B
WEST WING ZONE
2ND UNIT B
SOUTH WING ZONE
2ND UNIT B
EAST WING ZONE
2ND UNIT B
CENTER WING ZONE
ZCA ZCA
ZCA
" FROM
FIRST
FLOOR
3" FROM FIRST
FLOOR
" FROM
FIRST FLOOR
ZCA
3" 2"
2"
2" 3"
3"
3"
2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Project Director
DECEMBER 20, 2017 MJA SJARevisions: Date:
ARCHITECTURE
PLANNING
ENGINEERING
OfDwg.
SPRINKLER INFRASTRUCTURE PLANS
1/16" = 1'-0"SCALE:
SITE SPRINKLER INFRASTRUCTURE DETAIL
1/8" = 1'-0"SCALE:
BASEMENT SPRINKLER INFRASTRUCTURE DETAIL
1/8" = 1'-0"SCALE:
FIRST FLOOR SPRINKLER INFRASTRUCTURE DETAIL
1/8" = 1'-0"SCALE:
SECOND FLOOR SPRINKLER INFRASTRUCTURE DETAIL
30-FS2
30-FS2
30-FS2
30-FS2
AutoCAD SHX Text
%%UCIVIC CENTER BLVD.
AutoCAD SHX Text
%%UNURSING HOME CARE UNIT
AutoCAD SHX Text
%%UBLDG NO. 30
AutoCAD SHX Text
MEDICAL EXAMINER
AutoCAD SHX Text
%%UUNIVERSITY AVENUE
AutoCAD SHX Text BA100a
AutoCAD SHX Text
BA100
AutoCAD SHX Text
MECHANICAL ROOM
AutoCAD SHX Text
STAIR 9
AutoCAD SHX Text
STAIR 7
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
CB-1
AutoCAD SHX Text
CHILLER ROOM
AutoCAD SHX Text
PUBLIC
AutoCAD SHX Text
STAFF
AutoCAD SHX Text
1 BED ROOM
AutoCAD SHX Text
ELEC. CL0
AutoCAD SHX Text
1 BED RM.
AutoCAD SHX Text
2 BED ROOM
AutoCAD SHX Text
EXAM/TREATMENT
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text
PR. TLT.
AutoCAD SHX Text
1 BED RM.
AutoCAD SHX Text
LOUNGE TV RM
AutoCAD SHX Text
RESIDENT'S
AutoCAD SHX Text
TLT.
AutoCAD SHX Text
WAITING
AutoCAD SHX Text 1A105
AutoCAD SHX Text
UP
AutoCAD SHX Text
TOILET
AutoCAD SHX Text 1B100
AutoCAD SHX Text
STAIR #1
AutoCAD SHX Text
LAUNDRY
AutoCAD SHX Text
RESIDENT
AutoCAD SHX Text Gallery Storage
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text
ELEC.
AutoCAD SHX Text
CLO.
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text
PR. TLT.
AutoCAD SHX Text
NURSE ROOM.
AutoCAD SHX Text
PR. TLT.
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
BATH TLT.
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
MEDICATION
AutoCAD SHX Text
STATION
AutoCAD SHX Text
NURSE'S
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
MED. ROOM
AutoCAD SHX Text
BATH
AutoCAD SHX Text
CONGREGATE
AutoCAD SHX Text
PR TLT.
AutoCAD SHX Text
PR TLT.
AutoCAD SHX Text
NOURISHMENT
AutoCAD SHX Text
KITCHEN
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
SOILED
AutoCAD SHX Text
ELEC. CLO.
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text
WARD
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
CLEAN
AutoCAD SHX Text
LINEN
AutoCAD SHX Text
SECRETARY
AutoCAD SHX Text
ELEV.
AutoCAD SHX Text
W/C BATH
AutoCAD SHX Text
ELEV.
AutoCAD SHX Text P/S-2
AutoCAD SHX Text P/S-1
AutoCAD SHX Text C1-16
AutoCAD SHX Text
ELEC.
AutoCAD SHX Text H.A.C.
AutoCAD SHX Text
CLO.
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 1B155
AutoCAD SHX Text
TEL. CLO.
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text C1-17
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
CLASSROOM
AutoCAD SHX Text 1A108
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text Staff Lounge
AutoCAD SHX Text 1A113
AutoCAD SHX Text Retail
AutoCAD SHX Text Store
AutoCAD SHX Text 1A102
AutoCAD SHX Text Brenda Reed
AutoCAD SHX Text Nurse Manager
AutoCAD SHX Text 1B105
AutoCAD SHX Text Brian Gainsley
AutoCAD SHX Text Nurse Manager
AutoCAD SHX Text 1B149
AutoCAD SHX Text 1B156
AutoCAD SHX Text Nurse Pract. Office
AutoCAD SHX Text Storage
AutoCAD SHX Text Safemasters
AutoCAD SHX Text A. Klezek
AutoCAD SHX Text Psych.
AutoCAD SHX Text Lisa Bostic
AutoCAD SHX Text David LeFevre
AutoCAD SHX Text Health Techs:
AutoCAD SHX Text CLC Staff-Restorative
AutoCAD SHX Text
BUILT-IN FISHTANK
AutoCAD SHX Text
CASHIER
AutoCAD SHX Text Police
AutoCAD SHX Text Corridor
AutoCAD SHX Text C1-6
AutoCAD SHX Text Electric
AutoCAD SHX Text Room
AutoCAD SHX Text 1A115
AutoCAD SHX Text Lobby
AutoCAD SHX Text C1-2
AutoCAD SHX Text Nutrition
AutoCAD SHX Text Office
AutoCAD SHX Text 1A109
AutoCAD SHX Text Nutrition
AutoCAD SHX Text Staff
AutoCAD SHX Text 1A110B
AutoCAD SHX Text General
AutoCAD SHX Text Supplies
AutoCAD SHX Text 1A106
AutoCAD SHX Text ADA Toilet
AutoCAD SHX Text Room
AutoCAD SHX Text 1A105
AutoCAD SHX Text ADA Toilet
AutoCAD SHX Text Room
AutoCAD SHX Text 1A104
AutoCAD SHX Text Elevator
AutoCAD SHX Text Lobby
AutoCAD SHX Text C1-4
AutoCAD SHX Text Corridor
AutoCAD SHX Text C1-3
AutoCAD SHX Text Office
AutoCAD SHX Text 1A103
AutoCAD SHX Text Fine
AutoCAD SHX Text Dining
AutoCAD SHX Text 1A100
AutoCAD SHX Text C1-5
AutoCAD SHX Text 2B150
AutoCAD SHX Text 2B151
AutoCAD SHX Text
LAUNDRY
AutoCAD SHX Text
RESIDENT
AutoCAD SHX Text 2B103
AutoCAD SHX Text
PR. TLT.
AutoCAD SHX Text
PR. TLT.
AutoCAD SHX Text 2B122a
AutoCAD SHX Text
2 BED ROOM
AutoCAD SHX Text 2B124
AutoCAD SHX Text
2 BED ROOM
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text 2B124a
AutoCAD SHX Text 2B130a
AutoCAD SHX Text 2B123
AutoCAD SHX Text
1 BED ROOM
AutoCAD SHX Text 2B122
AutoCAD SHX Text
CLO.
AutoCAD SHX Text 2B132a
AutoCAD SHX Text
ELEC.
AutoCAD SHX Text
1 BED RM.
AutoCAD SHX Text 2B118
AutoCAD SHX Text 2B117
AutoCAD SHX Text
ELEC. CL0
AutoCAD SHX Text 2B119
AutoCAD SHX Text
2 BED ROOM
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text 2B118a
AutoCAD SHX Text
PR. TLT.
AutoCAD SHX Text 2B108a
AutoCAD SHX Text 2B108
AutoCAD SHX Text
1 BED RM.
AutoCAD SHX Text 2B107
AutoCAD SHX Text
LOUNGE TV RM
AutoCAD SHX Text
RESIDENT'S
AutoCAD SHX Text 2B121
AutoCAD SHX Text
NURSE ROOM
AutoCAD SHX Text 2B120
AutoCAD SHX Text
EXAM/TREATMENT
AutoCAD SHX Text 2B133a
AutoCAD SHX Text
BATH TLT.
AutoCAD SHX Text
ROOM
AutoCAD SHX Text C2-2
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text 2B106
AutoCAD SHX Text
STAFF
AutoCAD SHX Text
TLT.
AutoCAD SHX Text 2B104
AutoCAD SHX Text
SOCIAL
AutoCAD SHX Text 2B105
AutoCAD SHX Text
WORKER
AutoCAD SHX Text
STATION
AutoCAD SHX Text C2-3
AutoCAD SHX Text
MEDICATION
AutoCAD SHX Text
NURSE'S
AutoCAD SHX Text
2 BED ROOM
AutoCAD SHX Text 2B131
AutoCAD SHX Text
2 BED ROOM
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text 2B132
AutoCAD SHX Text
1 BED ROOM
AutoCAD SHX Text 2B133b
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
2 BED RM.
AutoCAD SHX Text
CONGREGATE
AutoCAD SHX Text 2B134
AutoCAD SHX Text 2B133
AutoCAD SHX Text
BATH
AutoCAD SHX Text 2B148
AutoCAD SHX Text
MED ROOM
AutoCAD SHX Text
KITCHEN
AutoCAD SHX Text
NOURISHMENT
AutoCAD SHX Text 2B147
AutoCAD SHX Text 2B146
AutoCAD SHX Text
2 BED RM.
AutoCAD SHX Text
UTILITY
AutoCAD SHX Text
SOILED
AutoCAD SHX Text 2B135a
AutoCAD SHX Text 2B135
AutoCAD SHX Text
1 BED RM.
AutoCAD SHX Text
PR TLT.
AutoCAD SHX Text 2B134a
AutoCAD SHX Text
PR TLT.
AutoCAD SHX Text 2B144
AutoCAD SHX Text
S. TLT.
AutoCAD SHX Text
1 BED RM.
AutoCAD SHX Text 2B145
AutoCAD SHX Text 2B145a
AutoCAD SHX Text
ELEC. CLO.
AutoCAD SHX Text
CLO.
AutoCAD SHX Text 2B102
AutoCAD SHX Text #1
AutoCAD SHX Text
STAIR
AutoCAD SHX Text
DN.
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text 2B101A
AutoCAD SHX Text
QUIET RM.
AutoCAD SHX Text
RESIDENT'S
AutoCAD SHX Text B.M.S.
AutoCAD SHX Text 2B100
AutoCAD SHX Text 2B101
AutoCAD SHX Text 2B153
AutoCAD SHX Text H.A.C.
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text C2-1
AutoCAD SHX Text
MECHANICAL ROOM
AutoCAD SHX Text 2B155
AutoCAD SHX Text
TEL. CLO.
AutoCAD SHX Text 2B154
AutoCAD SHX Text C2-7
AutoCAD SHX Text
ELEC.
AutoCAD SHX Text
CORRIDOR
AutoCAD SHX Text
TOIL.
AutoCAD SHX Text 2B156
AutoCAD SHX Text
CLEAN
AutoCAD SHX Text
LINEN
AutoCAD SHX Text
WARD
AutoCAD SHX Text 2B152
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
PUBLIC
AutoCAD SHX Text Michele McBride
AutoCAD SHX Text Nurse Manager
AutoCAD SHX Text 2B149
AutoCAD SHX Text
ELEV.
AutoCAD SHX Text
ELEV.
AutoCAD SHX Text P/S-2
AutoCAD SHX Text P/S-1
AutoCAD SHX Text
AutoCAD SHX Text
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER PHILADELPHIA, PA
AutoCAD SHX Text 642-16-107
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1436 410.803.0009 fax 410.836.6611
AutoCAD SHX Text BUILDING COST CONSULTANTS COST ESTIMATING 12917 - 30TH AVENUE PLATTSMOUTH, NEBRASKA 68048 402.298.8260 - FAX 402.298.8290
AutoCAD SHX Text KOFFEL ASSOCIATES FIRE PROTECTION ENGINEERS 8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MARYLAND 21045 410.750.2246 - FAX 410.750.2588
AutoCAD SHX Text WHITMAN REQUARDT & ASSOCIATES CIVIL ENGINEER 801 SOUTH CAROLINE STREET BALTIMORE, MARYLAND 21231 410.864.1058 - FAX 443.224.1820
AutoCAD SHX Text RICKERT ENGINEERING, INC. STRUCTURAL ENGINEERING 8813 WALTHAM WOODS ROAD, SUITE 301 BALTIMORE, MARYLAND 21234 410.663.5110 - FAX 410.663.5114
AutoCAD SHX Text
PHASE 1 - UPGRADE PATIENT ENVIRONMENT NHCU ADDITION
AutoCAD SHX Text BURDETTE KOEHLER MURPHY & ASSOCIATES, INC. MECHANICAL / ELECTRICAL ENGINEERS 1416 CLARKVIEW ROAD BALTIMORE, MARYLAND 21209 410.323.0600 - FAX 410.377.2543
AutoCAD SHX Text
30-FS2
(P1)
1B128
(e)2 Bed
Room
1B127
(e)2 Bed
Room
1B129
(e)2 Bed
Room
1B126
(e)2 Bed
Room
1B130
(e)2 Bed
Room
1B125
(e)2 Bed
Room
1B128a
(e)S.Tlt.
1B126a
(e)S.Tlt.
1B124a
(e)S.Tlt.
1B130a
(e)S.Tlt.
C1-13
(e)Corridor
New Stair #3
1ST3
Storage
1B127
Restroom
1B126
Staff Lounge
1B125
Restroom
1B125A
Elec.
1B128
Corridor
C1-15
Activity/Dining
1B124
2B128
(e)2 Bed
Room
2B127
(e)2 Bed
Room
2B129
(e)2 Bed
Room
2B126
(e)2 Bed
Room
2B130
(e)2 Bed
Room
2B125
(e)2 Bed
Room
2B128a
(e)S.Tlt.
2B126a
(e)S.Tlt.
2B124a
(e)S.Tlt.
2B130a
(e)S.Tlt.
C2-5
(e)Corridor
Elec.
2B127
Storage
2B126
Restroom
2B125
Staff Lounge
2B124
Restroom
2B124A
Corridor
C2-6
Activity /
Dining
2B123
Stair #3
2ST3
1B128
(e)2 Bed
Room
1B127
(e)2 Bed
Room
1B125
Staff Lounge
1B125A
Restroom
1B124
Activity/Dining
C1-15
Corridor
1ST3
Stair #3
2B128
(e)2 Bed
Room
2B127
(e)2 Bed
Room
2B124
Staff Lounge
2B124A
Restroom
2B123
Activity/Dining
C2-6
Corridor
2ST3
Stair #3
" = 1'-0"
FIRE SUPPRESSION - 2ND FLOOR PLAN - NEW WORK
1. EXISTING SPRINKLERS MUST REMAIN ACTIVE UNTIL NEW SYSTEM
IS INSTALLED.
2. SEE SHEET 30-FS2 FOR SPRINKLER INFRASTRUCTURE DETAILS.
3. SEE ADDITIONAL WORK ON DETAIL 3/30-FS4 AND 4/30-FS4 TO
SUPPORT TWO NEW IT ROOMS AND ONE NEW ELECTRICAL
ROOM.
PROVIDE ONE AUTOMATIC AIR VENT IN EACH SYSTEM PER NFPA 13
SECTION 8.16.6. THE VENT MUST BE LOCATED NEAR THE ZONE'S
HIGH POINT. PIPE THE BLOW-OFF DRAIN TO THE NEAREST
BATHROOM OR JANITOR'S CLOSET.
THERE ARE CURRENTLY NO SPRINKLERS IN THIS PARTIALLY
CONSTRUCTED ADDITION.
PROVIDE NEW 4-INCH PIPING TO NEW ZONE CONTROL VALVE
ASSEMBLY.
PROVIDE NEW 2-1/2" HOSE VALVE CONNECTION.
PROVIDE NEW ZONE CONTROL VALVE ASSEMBLY. SEE DETAIL
1/30-FS4(P1)
PROVIDE NEW 4-INCH RISER UP TO SECOND FLOOR. COORDINATE
RISER WITH STAIR DOORS AND PIPE TO OPPOSITE SIDE UNDER
SECOND FLOOR PRIMARY LANDING. ALSO PROVIDE 2-INCH
EXPRESS DRAIN RISER AND PIPE TO EXTERIOR WITH CONCRETE
SPLASH BLOCK.
EXTEND NEW SPRINKLER SYSTEM INTO PROJECT SPACE.
PROVIDE NEW CONTROL VALVE FOR RISER CONTROL.
CUT AND CAP EXISTING BRANCHLINES AT THIS LOCATION.
DEMOLISH ALL SPRINKLERS AND PIPING IN THIS AREA TO RE-ZONE
SPRINKLER SYSTEM.
PIPE NEW 4-INCH TEE INTO CORRIDOR C1-13. PROVIDE
TEMPORARY CONNECTION INTO 2-INCH PIPE FOR SOUTH WING
ZONE. THIS 4-INCH CONNECTION WILL BE COMPLETED IN PHASE 3.
CALCULATION CAN ASSUME 4-INCH PIPE.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
Project Director
DECEMBER 20, 2017 MJA SJARevisions: Date:
ARCHITECTURE
PLANNING
ENGINEERING
Unit B
Unit C
Unit A
Court
C o u r t
N
Plan North 1st Floor Building Key Plan
N
True North
(N.I.C.)
(N.I.C.)
(N.I.C.)
N
I C
A d d i t i o n
OfDwg.
" = 1'-0"
FIRE SUPPRESSION - 1ST FLOOR PLAN - NEW WORK
" = 1'-0"
FIRE SUPPRESSION - 2ND FLOOR PLAN - DEMOLITION
" = 1'-0"
FIRE SUPPRESSION - 1ST FLOOR PLAN - DEMOLITION
FIRE SUPPRESSION - FIRST AND
SECOND FLOOR PLANS
30-FS3
30-FS3
30-FS3
30-FS3
AutoCAD SHX Text
ZCA
AutoCAD SHX Text
ZCA
AutoCAD SHX Text 2"
AutoCAD SHX Text
1ST UNIT B ADDITION
AutoCAD SHX Text
1ST UNIT B SOUTH WING
AutoCAD SHX Text
2ND UNIT B ADDITION
AutoCAD SHX Text 2"
AutoCAD SHX Text 4"
AutoCAD SHX Text 4"
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
2ND UNIT B SOUTH WING
AutoCAD SHX Text
SEAL DOOR AS REQUIRED FOR ICRA BARRIER
AutoCAD SHX Text
REMOVE EXISTING ICRA BARRIER AND CONTACT MATS
AutoCAD SHX Text
SEAL DOOR AS REQUIRED FOR ICRA BARRIER
AutoCAD SHX Text
REMOVE EXISTING ICRA BARRIER AND CONTACT MATS
AutoCAD SHX Text
LINE OF WALLS TO BE FORMED INTO ICRA BARRIERS
AutoCAD SHX Text
LINE OF WALLS TO BE FORMED INTO ICRA BARRIERS
AutoCAD SHX Text
1ST UNIT B SOUTH WING
AutoCAD SHX Text
2ND UNIT B SOUTH WING
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
KEY NOTES:
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CORPORAL MICHAEL J. CRESCENZ VA MEDICAL CENTER PHILADELPHIA, PA
AutoCAD SHX Text 642-16-107
AutoCAD SHX Text 2215 Conowingo Rd, Suite 100 Bel Air, Maryland 21015-1436 410.803.0009 fax 410.836.6611
AutoCAD SHX Text BUILDING COST CONSULTANTS COST ESTIMATING 12917 - 30TH AVENUE PLATTSMOUTH, NEBRASKA 68048 402.298.8260 - FAX 402.298.8290
AutoCAD SHX Text KOFFEL ASSOCIATES FIRE PROTECTION ENGINEERS 8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MARYLAND 21045 410.750.2246 - FAX 410.750.2588
AutoCAD SHX Text WHITMAN REQUARDT & ASSOCIATES CIVIL ENGINEER 801 SOUTH CAROLINE STREET BALTIMORE, MARYLAND 21231 410.864.1058 - FAX 443.224.1820
AutoCAD SHX Text RICKERT ENGINEERING, INC. STRUCTURAL ENGINEERING 8813 WALTHAM WOODS ROAD, SUITE 301 BALTIMORE, MARYLAND 21234 410.663.5110 - FAX 410.663.5114
AutoCAD SHX Text
PHASE 1 - UPGRADE PATIENT ENVIRONMENT NHCU ADDITION
AutoCAD SHX Text BURDETTE KOEHLER MURPHY & ASSOCIATES, INC. MECHANICAL / ELECTRICAL ENGINEERS 1416 CLARKVIEW ROAD BALTIMORE, MARYLAND 21209 410.323.0600 - FAX 410.377.2543