Sherlock 802 with Opitional Strobe.pdf

PDF 453 KB Posted

Attached to
Y1DZ--NRM - CON - 561A4-18-101 Replace Central Chillers -Construction Federal contract opportunity
Solicitation number
36C24223B0035
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This document provides product specifications for a refrigerant gas leak monitoring and alarming system. The Sherlock 802 system can monitor up to eight refrigerant gas sensors and activate alarms based on user-defined setpoints. It has a NEMA 1 compliant enclosure for indoor use, inputs for up to eight sensors, six SPDT relay outputs for alarms and auxiliary uses, and optional strobe and Modbus communications. The system is ASHRAE 15 and mechanical code compliant for refrigerant monitoring and has a two-year warranty.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs for construction services to replace central chillers at a Veterans Health Administration facility. The solicitation number and opportunity details were provided.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DZ--NRM - CON - 561A4-18-101 Replace Central Chillers -Construction, newest first.
File Type Posted
36C24223B0035 0004.docx DOCX document
36C24223B0035 0003.docx DOCX document
20-105 Refrigeration Machine Schedule (8-1-23).xlsx XLSX spreadsheet
36C24223B0035 0002.docx DOCX document
Roof Pictures.pdf PDF
CEI085065 - LYONS VA - POWER SYSTEM STUDY 6-1-09.pdf PDF
561A4-18-101 Replace Central Chillers RFI for Construction - with updates.pdf PDF
S04 - Site Visit Sign In.pdf PDF
36C24223B0035 0001.docx DOCX document
561A4-18-101 Replace Central Chillers RFI for Construction.pdf PDF
Contract Specifications.pdf PDF
S02 - Buy American Certificate.pdf PDF
36C24223B0035_2.docx DOCX document
S02 - Wage Determination 07-03.pdf PDF
Contract Drawings.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHERLOCK 802 WITH OPTIONAL STROBE

REFRIGERANT GAS LEAK MONITORING AND ALARMING SYSTEM

TYPICAL MACHINE ROOM INSTALLATION

The SHERLOCK 802 (SHER802-S) Monitoring System with the optional factory mounted strobe light was designed to monitor up to eight SHERLOCK Refrigerant Gas Sensors, activating up to two alarms based upon user defined alarm level setpoints. The SHERLOCK 802-S is compliant with ASHRAE 15-2019 and Mechanical Code requirements for refrigerant gas monitoring.

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment.

The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, ie. environmentally controlled offices, control rooms, or environmentally con-trolled machine rooms.

Power Input 120/208/240vac, 50/60 Hz, 2.5 Amp

Inputs Up to 8 Sherlock Sensors: Cmos, Ir or Up to Seven Sherlock Sensors and One Oxygen Deprivation Sensor

Outputs Six (6) SPDT, 250VAC / 30V DC,

5.0 amp relays, Two (2) relays each, Level 1, 2 & System.

Auxiliary 12V DC Output Optional: Auxilliary (Zone cutoff) relays (SHER802-S-R) Optional: Modbus RS485 RTU Communications (MB-S)

Setback 24 Hour Time Clock Two Dry Contact Digital Inputs

Alarms Two Alarm Levels, One Fault Level, Two SPDT Relay per Level, Fuse On Common Terminal. One relay on each alarm level can be silenceable when in alarm. Zone isolation alarm relays can activate at either level.

Operating Environment Temperature 32°F To 120°F (0°C To 50°C) Humidity 0 To 95% RH Non-condensing

Display 2 Line By 20 Characters Alphanumeric Backlighted LCD display

Keypad 5 Tactile Pushbuttons Scroll Up, Scroll Down, Alarm Silent/ Clear, Select/Edit/Change, Exit Function-Menu

Alarm Indicators Display Name And Current Reading Of Alarming Sensor Buzzer Built-in Piezo-electric, 90db @10ft, Silenceable Strobe 90-110 Flashes/Min, Blue, Red, Amber

Listings ETL, Conforms to UL Std. 61010-1 CAN/CSA C22.2 Std. No. 61010-1

Warranty 15 Month Limited

GENESIS INTERNATIONAL, INC.

Nema/IP Size Electrical Pollution Model # Rating Inches (mm) Category Protection SHER802-S 1 12x9.5x5 II 2 (305x241x127)

SHER802 P/N 60-0101-00, SHER802-R P/N 60-0101-ZN, SHER802-MB 60-0101-MB, SHER802-MB-R 60-0101-MZ

W/STB P/N 87-00-0085, -0102, -0103 09-12-19

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

POWER LIGHT

SENSOR MODULE

SH E R LOCK

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

INFRARED SENSORS OPTIONAL

EXIT

SELECT

CHANGE

PRESS TO

SILENCE

ACTIVE

ALARM

SENSOR

B

SENSOR

A

SENSOR

C

SENSOR

D

SENSOR

F

SENSOR

E

ALARM

SILENCED

WHEN LIT

SENSOR

H

SENSOR

G

ALARM ACTIVE WHEN LIT

REFRIGERANT GAS

MONITORING SYSTEM

SENSOR ALARM STATUS

POWER LIGHT

SENSOR MODULE

SH E R LOCK

POWER LIGHT

SENSOR MODULE

SH E R LOCK

POWER LIGHT

SENSOR MODULE

SH E R LOCK

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

SHERLOCK

INFRARED

TM

GENESIS INTERNATIONAL INC.

SENSOR for REFRIGERANT GAS

1040 Fox Chase Industrial Dr. Arnold, MO. 63010

SENSOR B

POWER LIGHT

SENSOR MODULE

SH E R LOCK

POWER LIGHT

SENSOR MODULE

SH E R LOCK

POWER LIGHT

SENSOR MODULE

SH E R LOCK

POWER LIGHT

SENSOR MODULE

SH E R LOCK

TYPICAL WIRING DIAGRAM (EXAMPLE)

Alarm Level Settings - The SHERLOCK 802-S allows you to set a unique Level 1 and Level 2 Alarm Setpoint for up to 8 sensors. When an Alarm Setpoint is exceeded, alarm relays activate. Each alarm setpoint has a programmable Delay of 0 to 120 minutes. Sensor readings are required to exceed an Alarm Setpoint for the programmed amount of time before the control activates the corresponding alarm relay contacts.

Alarm Indication - Alarms are logged to indicate which sensor went in and out of alarm and when. The alarm log stores the last 32 alarms. When a sensor is in alarm, an LED for this sensor on the front panel will light, the on-board beeper will sound and the display will show the activated alarm level.

Systems Sensor Open Monitoring - The SHERLOCK 802-S constantly monitors the wiring to the sensors. If any sensor loses communication for any reason, “OPEN” will appear on the display, the alams will activate and the condition logged.

Setback Alarm Settings - In some instances the control may be expected to function in two different environments. The SHERLOCK 802-S provides a feature called SETBACK to accommodate alternate alarm conditions. SETBACK provides a secondary Alarm Setpoint and Delay. The control changes to the setback parameters when a dry contact closes (i.e. air flow switch, sail switch or timer switch) or on a daily schedule.

Alarm Relay Contacts - The SHERLOCK 802-S provides two fused SPDT (Single Pole Double Throw) relay outputs for each for two alarm levels and a system alarm that switch positions in the event of an alarm condition. Level 1 alarm activates the K1A and K1B relays. Level 2 alarm activates the K2A and K2B relays. System alarm activates the 3A and 3B relays.

Level 2 for each individual sensor can be disabled. Relays K1B, K2B and 3B can be silenced (returned to non-alarm state) when the SILENT button on the front panel is pushed. The other alarm relays will remain active until the alarm condition is cleared. The control can be programmed so the alarm is cleared automatically when the sensor goes below the alarm setpoint (UNLATCHED) or stay on until the alarm is manually reset (LATCHED). The K1/K2 alarm level can be config-ured so the relays are "Energized to Alarm" or "De-Energized to Alarm", Common-Normally Open (C-NO) or Common- Normally Closed (C-NC).

Optional Auxiliary Relays (SHER802-R-S) - Zone isolation alarm relays (ZA - Sensor A Zone, ZB - Sensor B Zone, ZC - Sensor C Zone, ZD - Sensor D Zone, ZE - Sensor E Zone, ZF

- Sensor F Zone, ZG - Sensor G Zone, ZH - Sensor H Zone).

Each relay can be programmed to activate by level 1 or level 2.

Optional: Modbus RTU (SHER802-MB-S) - This option adds an RS485 output that can communicate with a BAS.

1040 Fox Chase Industrial Dr Arnold, MO 63010

Tel: 636-282-0011 Fax:636-282-2722

Email: mail@genesis-international.com Web:www.genesis-international.com

GENESIS INTERNATIONAL, INC.

DOC# 44-0484-00

����������
�������������
������
��������
������������
����"��������������
������#��
�������
����
����������������
�����
��������������
��������
������
����������
�����������
����#�����
����������������
�����
���������$�$
����!�
�������%��!