20-105 Refrigeration Machine Schedule (8-1-23).xlsx
XLSX spreadsheet 13 KB Posted
- Attached to
- Y1DZ--NRM - CON - 561A4-18-101 Replace Central Chillers -Construction Federal contract opportunity
- Solicitation number
- 36C24223B0035
About this file
This document contains a refrigeration machine schedule and details for a federal contract opportunity to replace central chillers. The refrigeration machine schedule lists two water-cooled centrifugal chillers to be installed at a medical center, providing 700 and 1000 ton capacities. It specifies efficiency requirements and includes notes on controls integration, power connection, variable frequency drives, piping configurations, and marine waterboxes. The related federal contract opportunity is solicited by the Department of Veterans Affairs for project 561A4-18-101 to replace central chillers at a Veterans Health Administration facility. The solicitation number and opportunity type are provided.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sherlock 802 with Opitional Strobe.pdf | ||
| 36C24223B0035 0004.docx | DOCX document | |
| 36C24223B0035 0003.docx | DOCX document | |
| CEI085065 - LYONS VA - POWER SYSTEM STUDY 6-1-09.pdf | ||
| 561A4-18-101 Replace Central Chillers RFI for Construction - with updates.pdf | ||
| Roof Pictures.pdf | ||
| 36C24223B0035 0002.docx | DOCX document | |
| 561A4-18-101 Replace Central Chillers RFI for Construction.pdf | ||
| S04 - Site Visit Sign In.pdf | ||
| 36C24223B0035 0001.docx | DOCX document | |
| S02 - Wage Determination 07-03.pdf | ||
| Contract Drawings.pdf | ||
| Contract Specifications.pdf | ||
| S02 - Buy American Certificate.pdf | ||
| 36C24223B0035_2.docx | DOCX document |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHILLER
| REFRIGERATION MACHINE SCHEDULE | |||||||||||||||||||||||||||||
| MARK | LOCATION | SYSTEM AND/OR SERVICE | TYPE | CAPACITY | MIN. FULL LOAD EFFICIENCY (FL) | MIN. INTEGRATED PART LOAD EFFICIENCY (IPLV) | MIN. PART LOAD EFFICIENCIES | EVAPORATOR | CONDESNER | COMPRESSOR | REFRIG. TYPE | UNIT OPERATING WEIGHT | REMARKS | ||||||||||||||||
| 100% | 75% | 50% | 25% | WATER QUANTITY | NO. OF PASSES | WATER ENT. | WATER LV. | PRESS. DROP | FOULING FACTOR | WATER QUANTITY | NO. OF PASSES | WATER ENT. | WATER LV. | PRESS. DROP | FOULING FACTOR | NO. OF COMP. | VOLTAGE | MCA | MOCP | ||||||||||
| TONS | KW/TON | KW/TON | KW/TON | GPM | °F | °F | FT | GPM | °F | °F | FT | LBS | |||||||||||||||||
| WC-2 | BUILDING 136 | MEDICAL CENTER | WATER COOLED CENTRIFUGAL | 700 | 0.5675 | 0.3214 | 0.5675 | 0.4061 | 0.2728 | 0.2925 | 1,675 | 2 | 54 | 44 | 11.9 | 0.000100 | 1,969 | 2 | 85 | 95 | 12.7 | 0.000250 | 1 | 460/3/60 | 626 | 1,000 | R-513A | 31,426 | SEE NOTES |
| WC-3 | BUILDING 136 | MEDICAL CENTER | WATER COOLED CENTRIFUGAL | 1,000 | 0.5927 | 0.3193 | 0.5927 | 0.4096 | 0.2712 | 0.2786 | 2,392 | 2 | 54 | 44 | 17.4 | 0.000100 | 2,830 | 2 | 85 | 95 | 16.2 | 0.000250 | 1 | 460/3/60 | 933 | 1,600 | R-513A | 39,908 | SEE NOTES |
| NOTES |
| 1. PROVIDE WITH LONWORKS OPEN PROTOCOL COMMUNITCATION. COORDINATE WITH CONTROLS INSTALLER ON ALL REQUIREMENTS. |
| 2. PROVIDE WITH SINGLE POINT POWER CONNECTION. |
| 3. PROVIDE WITH UNIT MOUNTED INTEGRAL VFD STARTER(S). |
| 4. PROVIDE WITH FLANGED RIGHT HAND PIPING CONNECTIONS. |
| 5. PROVIDE MARINE WATERBOXES ON BOTH THE EVAPORATOR AND CONDENSER. REAR INLET/TOP OUTLET ON THE EVAPORATOR AND FRONT INLET/TOP OUTLET ON THE CONDESNER. |
| 6. PROVIDE WITH HINGED DOORS ON BOTH ENDS. |