This notice is for a federal solicitation seeking proposals for an electrical upgrade project at a Department of Veterans Affairs facility in East Orange, New Jersey. Key details include:

  • Scope of work involves replacing the campus switchyard building and associated electrical equipment including controls, site work, and replacing normal and emergency power switchgear in two vaults. Additional work includes replacing substations and electrical panels in various campus buildings.

  • Estimated cost is between $5-10 million. Proposals are due by the date specified in the solicitation to be released on or about April 20, 2020.

  • The project has a NAICS code of 236220 and is set aside for Service-Disabled Veteran Owned Small Businesses. The response submittal address, date and time will be in the solicitation.

  • Work includes civil site work like retaining wall relocation, structural elements like installing concrete pads and a canopy structure, and architectural elements such as metal wall panels and a standing seam roof for the canopy.

  • Construction is to be completed within 730 calendar days of award. The contractor must submit a preliminary schedule and contingency plan for electrical outages.

36C24220B0035 0001 S02 Drawings 04-Electrical.pdf

View the file

Other files

File Type Posted
36C24220B0035-0002000.docx DOCX document
36C24220B0035-0001001.pdf PDF
36C24220B0035-0001003.pdf PDF
36C24220B0035-0001004.pdf PDF
36C24220B0035-0001000.docx DOCX document
36C24220B0035-0001002.pdf PDF
36C24220B0035-020.pdf PDF
36C24220B0035-015.docx DOCX document
36C24220B0035-021.pdf PDF
36C24220B0035-019.pdf PDF
36C24220B0035-017.pdf PDF
36C24220B0035-016.pdf PDF
36C24220B0035-018.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Δ DELTA

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY

CONTROL, OR AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB AMBIENT

AMP OR A AMPERE

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BFG BELOW FINISH GRADE

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CATV COMMUNITY ANTENNA TELEVISION

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CLG CEILING

CM CENTRAL MONITOR/METERING ASSEMBLY

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EX, EXIST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FLA FULL LOAD AMPS

FMC FLEXIBLE METALLIC CONDUIT

FP FIRE PROTECTION

FT FEET OR FOOT

FS FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GRS GALVANIZED RIGID STEEL

GTB GROUND TERMINAL BOX

ELECTRICAL ABBREVIATIONS

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

J-BOX JUNCTION BOX

kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT OR MICROWAVE

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEUT OR N NEUTRAL

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR PUSHBUTTON

PCB POLYCHLORINATED BIPHENYL

PC PHOTOELECTRIC CELL

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

POS POSITION

PRI, PRIM PRIMARY

PVC POLYVINYL CHLORIDE (PLASTIC)

R RELOCATED

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

REQD REQUIRED

SCC SHORT CIRCUIT CAPACITY

SEC SECONDARY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL

BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS,

THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE

LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, THE

LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, AND THE VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT

AND FEEDERS WHERE THE BUILDING CONSTRUCTION IS NOT SUITABLE

FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR

SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS,

FLOORS, CEILINGS AND ROOFS IN ACCORDANCE WITH THE

REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTINGS

REQUIREMENT AND THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES,

TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO SUIT THE

PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES

DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO

INSTALLATION SO AS TO AVOID CONFLICT DURING CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR

DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE

NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.

PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE

ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL,

BREAKER OR PARTICULAR EQUIPMENT MANUFACTURER'S

SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES

SHALL BE TERMINATED ON THE DEVICE'S SCREW TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET,

FIXTURE, OR EQUIPMENT UNLESS NOTED OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS

OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC

CONDUIT MAY BE USED ON VIBRATING EQUIPMENT.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT

SHALL BE LABEL LISTED BY AN APPROVED THIRD PARTY TESTING

AGENCY.

17. DIMENSIONS, QUANTITIES AND LOCATIONS OF EXISTING CONDUIT AND

EQUIPMENT AS SHOWN ON THESE DRAWINGS ARE BASED ON RECORD

DRAWINGS AND CASUAL OBSERVATION AND ARE NOT NECESSARILY

COMPLETELY ACCURATE. CONTRACTOR SHALL BE RESPONSIBLE FOR

VERIFYING ANY AND ALL EXISTING EQUIPMENT AND CONDITIONS THAT

MIGHT AFFECT THE WORK.

GENERAL NOTES

J

J

S

E

JUNCTION BOX, PURPOSE AS NOTED

JUNCTION BOX IN WALL, PURPOSE AS NOTED:

18" AFF STANDARD UNO

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SWITCH: 44" AFF STANDARD UNO

SWITCH MODIFIERS:

M - MOTOR RATED

3 - THREE-WAY

T - DIGITAL TIMER SWITCH

PANELBOARD

EQUIPMENT ELECTRICAL CONNECTION

HOMERUN - 120V OR 277V

HOMERUN - 208V OR 480V

120V DUPLEX RECEPTACLE: 18" AFF STANDARD, UNO

RECEPTACLE MODIFIERS:

GFCI - GROUND FAULT CIRCUIT INTERRUPTER

WP - WEATHERPROOF

DED - DEDICATED

KK

KIRK-KEY MANUAL INTERLOCK

UNDERGROUND ELECTRICALUGE

CONTACTOR OR MOTOR STARTER

5"

UNDERGROUND DUCT, (2) 5" CONDUIT

PANELBOARD

SYMBOL LEGEND

INDICATOR LIGHT (G=GREEN, R=RED,

A=AMBER, W-WHITE)

MOTOR WITH HORSEPOWER

BOND TO GROUNDING ELECTRODE SYSTEM

CONTACT (NORMALLY CLOSED)

THERMAL OVERLOAD RELAY

CONTACT (NORMALLY OPEN)

REMOVABLE ELEMENT

FUSE

HOMERUN CONDUIT

THERMOSTAT

METER

CURRENT TRANSFORMER

SINGLE POLE SWITCH

M

CT

S

T

2 AWG BARE TINNED CU UNO

UNDERGROUND CONDUIT

G

G G

DEMOLITION (ITEM TO BE REMOVED) WHEN NOTED

KK

KIRK-KEY MANUAL INTERLOCK

CIRCUIT BREAKER

DRIVEN GROUND ROD

GROUND BOND BY EXOTHERMIC WELD

PM

POWER METER/MONITOR

FIRE ALARM PULL STATION

F

F

FIRE ALARM SPEAKER

FIRE ALARM STROBE

FIRE ALARM PULL SPEAKER AND STROBE

48"

90"

90"

90"

F

S

F

S

FIRE ALARM SMOKE DETECTOR

W WALL PHONE

SWITCH - MOUNTED 48" AFF

B PUSHBUTTON

LINEAR INDUSTRIAL (LED) CHAIN HUNG

WALL MOUNTED EXIT SIGN (AC)

WALL MOUNTED EMERGENCY LIGHT (WALL PACK)

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

E-001

ELECTRICAL NOTES, LEGENDS, AND

ABBREVIATIONS

NEW WORK:

A. PROVIDE ARC FLASH CALCULATIONS AND

RESPECTIVE LABELING AT ALL RESPECTIVE

ELECTRICAL EQUIPMENT REVISED OR MODIFIED

BY THIS RENOVATION. SEE SPECIFICATIONS

260573.

B. SEE SPECIFICATIONS 013526 SAFETY

REQUIREMENTS FOR LOCK OUT TAG OUT

PROCEDURES, AND ELECTRICAL SAFETY

REQUIREMENTS. ELECTRICAL SHUTDOWNS NEED

TO BE SCHEDULED WITH COR WITH AT LEAST

TWO WEEKS MINIMUM NOTICE. SEE

SPECIFICATIONS 260511 1.9C.

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

DocuSign Envelope ID: CA86D127-DB02-414A-9C7B-04E0EE29525A

2/4/2020

X X

X X

XXX

XXXX

XXXX

XXXX

X

X

X X

X X

X X

X X X X X X X X X X X

X X

X X

X X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

(EX)

BUILDING #24

CONCRETE

ASPHALT DRIVEWAY

(EX)

DECONTAMINATION

CENTER

(EX) ELECTRICAL YARD

(EX) ELECTRICAL YARD

(EX)

PAD MOUNTED

TRANSFORMER

X

(EX)

26,400V

VA PRIMARY

SWITCH

(EX)

26,400V

VA PRIMARY

SWITCH

(EX)26,400V

UTILITY

SWITCH /

CONNECTIONS

(EX)26,400V

UTILITY

SWITCH /

CONNECTIONS

(EX)

EMERGENCY

GENERATOR SET

X X X X X X X X X X X

(EX) RETAINING WALL (TYP)

(EX) RETAINING WALL (TYP)

(EX) MV MANHOLE

(EX) ATS/

SWITCHGEAR

U

G

E

U G

E

(EX) MV DUCT BANK (VIF)

(EX) MV DUCT BANK (VIF)

NEW MH OVER (EX)

DUCT BANK

U

G

E

UGE

U G

E

UGE UGE

U

G

E

U G

E

U

G

E

U

G

E

U

G

E

UGE

"A"

"A"

PNL SG

(4)3 AWG

(1)8 AWG EG

1-1/2"C

(EX)

PNL SWGR

(EX)26,400V ELECTRICAL

DISTRIBUTION EQUIPMENT

AND SERVICES ARE OWNED,

OPERATED AND MAINTAINED

BY THE UTILITY PROVIDER

(NIC)

52-1

52-4

52-5

52-3TIE

52-6

52-9 (SP)

52-10

52-11

52-12

52-13

52-14

SPACE

52-7

52-8 (SP)

52-2

52-15

52-16

X X X X X X X X X X X

J

J

J

J

(2)

(4)

(1)

(3)

(EX)PNL AC

S

(7)

(5)

S

(5)

(7)

"A" S

(8)

(6)

"A"

S

(6)

(8)

S S

(9)

(11)

(9)

(11)

"A"

S

(12)

(10)

S

(10)

(12)

(EX)PNL DC

J J

ADD (1) 100A 3P

DEVICE AT EXISTING

PANEL SWGR

GENERAL NOTES:

1.

2.

3.

4.

CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS,

OR AS SPECIFIED.

PROVIDE #4 REINFORCING RODS ON TOP AND

BOTTOM OF DUCTS WHEN CROSSING OR

PLACED IN ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE SHALL

BE 610mm (24").

GENERAL NOTES:

1.

2.

3.

4.

CONCRETE SHALL BE 2000 P.S.I. @ 28

DAYS, OR AS SPECIFIED.

PROVIDE #4 REINFORCING RODS ON TOP

AND BOTTOM OF DUCTS WHEN CROSSING

OR PLACED IN ROADWAYS.

MINIMUM COVER TO TOP OF ENVELOPE

SHALL BE 610mm (24").

5" PVC 40 RACEWAY FOR ELECTRICAL

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

1. PG&E 26,400V SERVICE ENTRANCE FEEDER

(1) (N300), (2) (1-61). OPERATION AND

MAINTENANCE OF THE DEVICES IS

RESPONSIBILITY OF THE UTILITY PROVIDER.

2. OVERCURRENT PROTECTION 1200A (VACUUM

SWITCH), OWNED AND MAINTAINED BY EAST

ORANGE VAMC. EXISTING DEVICES TO

REMAIN, FIELD VERIFY EXISTING

CONDITIONS.

SEE SHEET E-601.

3. SERVICE ENTRANCE TRANFORMERS, 5000

KVA 26,400-4160Y/2400V 3PH.

TRANSFORMERS SHALL BE REPLACED.

5000/6250 KVA OA/FA OIL FILLED

TRANSFORMER 55 DEG C RISE.

4. 1200 AMP 4160V 3PH, 3W FEEDER BELOW

GRADE. REMOVE FROM SECONDARY OF

TRANSFORMER TO EXISTING PRIMARY

SWITCHGEAR. SEE SHEET E-601 AND

COORDINATE WITH INSTALLATION OF NEW

5KV SWITCHGEAR. FEEDER SHALL BE

REMOVED UPON ACTIVATION OF NEW

SWITCHGEAR.

5. 5 KV SWITCHGEAR WITH DISTRIBUTION

CIRCUIT BREAKERS SERVICING 5KV

DISTRIBUTION TO EAST ORANGE VAMC

CAMPUS. SEE SHEET E-601. MV CABLE

TERMINATIONS ARE ACCESSIBLE FROM THE

EAST SIDE EXTERIOR DOOR PANELS TO

BUILDING 24. SWITCHGEAR TO BE DE

ACTIVATED AND REMOVED WITH EXCEPTION

OF REAR TERMINAL/SPLICE CABINET UPON

ACTIVATION OF NEW SWITCHGEAR.

6. NEW (1200A) 5KV (4160V) FEEDER BELOW

GRADE. PROVIDE NEW RACEWAYS, MV

CABLES, AND TERMINATIONS.

7. NEW 5KV DISTRIBUTION SWITCHGEAR (NEMA

3R, WALK IN ENCLOSURE) WITH EXTERIOR

ACCESS DOORS TO 5KV CONNECTIONS.

MANUFACTURED ASSEMBLY PROVIDED BY

ELECTRICAL EQUIPMENT PROVIDER. 15KV

METAL CLAD SWITCHGEAR WITH VACU

BREAK SWITCH ASSEMBLIES.

8. OVERHEAD 5KV DISTRIBUTION CIRCUITS IN

CABLE TRAY (HOT DIPPED GALVANIZED

STEEL , WITH COVER) TO RE FEED 5KV

DISTRIBUTION CIRCUITS. CABLE TRAY TO BE

SIZED FOR RESPECTIVE 5KV DISTRIBUTION

CABLES, PROVIDE SHOP DRAWING FOR

APPROVAL. SEE SHEET E-601.

9. SEE CIVIL/SITE DOCUMENTS. A PORTION OF

THE EXISTING RETAINING WALL AND OR

FENCING TO BE REMOVED.

10. (TYPICAL) AREA LUMINAIRE MOUNTED TO

EXISTING STRUCTURE TO BE REPLACED

WITH LED AREA LIGHT (WITH PHOTOCELL).

RETAIN AND REUSE EXISTING BRANCH

CIRCUITS, REPLACE EXISTING SWITCH AND

RECEPTACLE AT EACH LOCATION (3R)

ENCLOSURE/GASKET.

11. DISCONNECT EXISTING 24.6KV CABLES AT

TRANSFORMER AND RETAIN FOR REUSE.

PROVIDE FOR TESTING AND EVALUATION

PRIOR TO RECONNECTION. PROVIDE NEW

TERMINATIONS AND RECONNECT PRIMARY

26.4KV TO NEW TRANSFORMERS.

COORDINATE WITH 5KV DISTRIBUTION

SWITCHGEAR REPLACEMENT.

12. NEW DUCT BANK EXTENDED FROM NEW 5KV

SWITCHGEAR TO EXISTING 5KV DISTRIBUTION

DUCT BANK LOCATIONS. PROVIDE MANHOLE

AT THIS LOCATION FOR FUTURE ROUTING OF

5KV DISTRIBUTION CABLES TO THE EXISTING

5KV CAMPUS DISTRIBUTION LOOP

RACEWAYS. UNDER A FUTURE PROJECT,

CAMPUS 5KV DISTRIBUTION CABLES WILL BE

REPLACED. AT THAT TIME THE 5KV

DISTRIBUTION WILL BE ROUTED DIRECTLY

FROM THE NEW SWITCHGEAR.

13. UTILITY CONTROL CABINET, COORDINATE

WIRING WITH UTILITY PROVIDER. PROVIDE

2"C BACK TO EXISTING CONTROL/METERING

CABINET AT BLDG 24.

14. EXISTING PANELBOARD AT ELECTRICAL

YARD. PROVIDE NEW FEEDER FROM

LRP-SWGR (4 #8,#10G, 1-1/2"C) 60A-3P .

RETAIN AND REUSE EXISTING PANELBOARD.

15. EXISTING (DC) CONTROL CABINET/PANEL TO

REMAIN. RETAIN EXISTING SERVICES.

EXTEND REQUIRED CONTROLS TO NEW

SWITCHGEAR BUILDING.

16. 1-1/2"C (FA,PA,PHONE) SEE SHEET E-502.

17. COORDINATE WITH MANUFACTURES SHOP

DRAWINGS. EXTEND/EXPAND TRANSFORMER

PAD AS REQUIRED FOR NEW TRANSFORMER.

PARTIAL PLAN SITE ELECTRICAL

1" = 16'

ES-101

PARTIAL SITE PLAN ELECTRICAL

0 8' 16' 32'

DUCTBANK LAYOUT (DISTRIBUTION FEEDERS)

NO SCALE

DUCTBANK LAYOUT (SERVICE FEEDERS)

NO SCALE

EXISTING SITE :

A. VERIFY IN FIELD THE LOCATIONS OF EXISTING

MEDIUM VOLTAGE UNDERGROUND DUCT BANKS

AND MEDIUM VOLTAGE DISTRIBUTION SYSTEM.

PROTECT DURING CONSTRUCTION AS

REQUIRED.

B. WHERE NEW CONSTRUCTION ( FOOTINGS AND

OR FOUNDATIONS ) CROSS THE EXISTING DUCT

BANKS COORDINATE WITH STRUCTURAL DETAILS

TO ENSURE NEW WORK BRIDGES OVER THE

EXISTING DUCT BANKS WHICH WILL REMAIN AT

THIS TIME.

C. SEE SHEET E-001 FOR LIGHT FIXTURE

SCHEDULE.

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

3000A

208Y-120V

3PH,4W

1000KVA

4160/208Y-120V

NEW

SUBSTATION AE

NEW ROTARY DOCKING

STATION 3000AMP

AT GRADE LEVEL (ABOVE)

3000NG

3000NG

AREA WELL OPENING (ABOVE) TO BE

COVERED AND MADE WEATHER PROOF.

SEE ARCHITECTURAL/STRUCTURAL

DETAILS

NEW WALL

GND BUS

EXISTING (TO REMAIN)

800KW/1000KVA

DIESEL GEN SET

GENERATOR FEEDER (BUS DUCT)

TO SWITCHBOARD AE

(REVISED/RELOCATED)

(CT)

F

R

SS

SS

F

F

PNL AE-21

(EX)

TXF (A1)

(EX)

TXF (A)

(EX)

SS

G G

G

G

G

G

G

G

F F

TXF (X RAY)

A-241

(EX)

PNL VAE/

VAEA

400/3

GENERATOR

CONTROLS

(EX)

GENERATOR

CONTROLS

(EX)

R

EM

R

R

R R

R

R

R

R

R

R

R

(CT)

(CT)

NEW (RATED DOOR)

CHGR

R

R

(CT)

JUNCTION BOXJUNCTION BOX

(CT)

(CT)

750KVA

4160/208Y-120V

3000A

208Y-120V 3PH,4W

NEW

SUBSTATION AN

4" CONCRETE

PAD UNDER SWITCHGEAR

ASSEMBLY(PAINTED YELLOW)

(CT)

R

R

R

R

(EX) SUMP/ELEC TO

REMAIN.

AE-7

200NG

(VAE-3)

(VAE-1)

REVISE/MODFIY EXISTING

PAD UNDER SWITCHGEAR ASSENBLY

TERMINAL BOX AT TOP

OF TRANSFORMER

TANK - BUSHINGS

5KV VACUM FAULT

INTERUPTER AT

TRANSFORMER

5KV VACUM FAULT

INTERUPTER AT

TRANSFORMER

B

M

2P

M

2P

VAEA-5,7

VAEA-5,7

REVISE/MODFIY EXISTING

15KV DISTRIBUTION TO

SUBSTATIONS

EM/NL

VAE-3

EM/NL

VAE-3

EM/NL

VAE-3

EM/NL

EM

EM

EM

VAE-*

VAE-1

VAE-1

X1

X1

X1

VAE-1

D001

EXISTING (TO REMAIN)

800KW/1000KVA

DIESEL GEN SET

SUBSTATION AN

(TO BE REMOVED)

5KV LOAD

BREAK SW

200e (AF)

750KVA

4160/208Y-120V

3000A

208Y-120V 3PH,4W

SUBSTATION AE

(TO BE REMOVED)

3000A

208Y-120V 3PH,4W

5KV LOAD

BREAK SW

200e (AF)

1000KVA

4160/208Y-120V

EXPAND EXISTING WALL

OPENING, AND REMOVE

SLIDING DOOR ASSEMBLY

GENERATOR FEEDER (BUS DUCT)

TO SWITCHBOARD AE

(REVISED/RELOCATED)

T-MDP (ER)

SUBSTATION TIE SWITCH

TO BE REMOVED

TXF (A1)

(EX)

TXF (A)

(EX)

GROUND BUS/CABINET

TO BE REMOVED. SEE

NEW WORK PLANS

TXF (X RAY)

A-241

(EX)

GENERATOR

CONTROLS

(EX)

PNL VAE

PNL AE-21

(EX)

(TO REMAIN)

(CT)

(CT)

(CT)

(CT)

(BD)

(BD)

(CT)

(CT)

F

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

SS

(VAE-3)

G G

G

G

G

G

G

400/3

G

SS

SS

CHGR CHGR

R

R

F

F

R

F F

R

GENERATOR

CONTROLS

(EX)

R

R

(EX) SUMP/ELEC TO

REMAIN.

MODIFY EXISTING WALL TO

CREATE OPENING FOR NEW

RATED DOOR ASSEMBLY,

SEE NEW WORK PLAN.

(VAE-1)

REMOVE AND RELOCATE

TO VAULT B

G R

E G

G

D

R I V

E

O

R

E

S

K

O

S

T

R

E

E

TL

G

S

O

U

H

C

E

N

T

R

R

E

E

T

DN

(E X

F

IR

S

T F

L R

A R

E A

W E

L L

E

N T

R Y

E

X I

P

A T

H W

A Y

QTY.

(2)

D001

NO.

MISCELLANEOUS

THICK.

FRAME INFORMATION

HEIGHTWIDTH MAT'LTYPE MAT'LTYPE RATING

3 HR

REMARKS

1 3/4"7'-0"3'-0" A METAL HMTYPE I

7'-0"

2"

2" 6'-0" 2"

HRDWR.

SET 1

DEPTH

5 3/4"

DOOR INFORMATION

HINGES

FLUSH BOLTS

DUST PROOF STRIKE

PASSAGE SET

COORDINATOR

ASTRAGAL

DOOR CLOSER

KICK PLATES

GASKETING

TA2714

ML2010

2600 SERIES

BY DOOR MANUF.

DC6210xA11

K1050F

S888 x HEAD & JAMBS

HARDWARE SET 1

32D

32D

26D

32D

32D

MK

RO

RO

CO

RO

CO

RO

PE

MANUFACTURERS:

CORBIN RUSSWIN

McKINNEY

PEMKO

ROCKWOOD

CO

MK

PE

RO

NOTE:

HARDWARE MANUFACTURER'S LISTED AS BASIS OF DESIGN.

ALTERNATE MANUFACTURERS ACCEPTABLE, SUBJECT TO

REVIEW BY ARCHITECT AND C.O.R .FOR EQUAL QUALITY

COMPLIANCE.

DOOR SET IN CONCRETE P.I.P. WALL

* DOOR AND FRAME TO BE GALVANIZED.

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

A-VAULT POWER DEMOLITION PLAN ENLARGEMENT

1/4" = 1'-0"

E-101

A-VAULT POWER PLAN ENLARGEMENT

1/4" = 1'-0"

A VAULT ELECTRICAL PLANS

BUILDING 1, A (LEVEL)

A-VAULT POWER PLAN ENLARGEMENT

1" = 50'-0"

DEMOLITION:

A. DEMOLITION WORK SHALL INCLUDE BUT NOT BE

LIMITED TO THE ELECTRICAL SYSTEMS, DEVICES

AND EQUIPMENT SHOWN ON THE DEMOLITION

PLAN. FIELD VERIFY EXISTING CONDITIONS.

COORDINATE THE DE-ENERGIZING OF FEEDERS

WITH COR AND VA FACILITIES.

B. FEEDERS ARE TO BE REMOVED TO A POINT

WHERE THEY EXIT THE SUBSTATION VAULT.

PROVIDE NEW JUNCTION BOX TO

REROUTE/EXTEND FEEDERS TO NEW

SWITCHGEAR LOCATION. ALL EXISTING AND NEW

JUNCTION BOXES AND CABLE TRAYS ARE TO BE

ACCESSIBLE AT ALL TIMES.

NEW WORK:

A. PROVIDE NEW RACEWAYS OR CABLE TRAY FOR

REROUTING OF FEEDERS. CABLE TRAY TO

MATCH EXISTING (24"W LADDER TYPE). SEE

SHEET E-600 THROUGH E-604 FOR RISER

DIAGRAMS. CONTRACTOR TO PROVIDE

CONDUCTOR FILL CALCULATIONS FOR NEW

CABLE TRAY ASSEMBLIES.

B. SEE SHEET E-001 FOR LIGHT FIXTURE

SCHEDULE.

1. EMERGENCY POWER FEEDER TO SUBSTATION

AE. SEE SHEET E-603

2. OVERHEAD TIE CONNECTION BETWEEN AN/AE

SUBSTATIONS.

3. EMERGENCY GENERATOR FEEDER TO DOCKING

STATION. SEE SHEET E-603.

4. GENERATOR DOCKING STATION FOR REMOTE

(TEMPORARY GENERATOR). TRYSTAR 303PCM

OR EQUAL. 3000 AMP 208/120V 3PG,4W RATED IN

NEMA 3R ENCLOSURE, PAD MOUNTED, CAM

LOCK CONNECTIONS .PROVIDE CONCRETE

BOLLARDS AS SHOWN, SEE CIVIL/SITE DETAILS.

5. UTILIZE EXISTING (3000A) BUS DUCT. PROVIDE

TAP/JUNCTION BOXES AT BOTH ENDS TO ALLOW

FOR CABLE TERMINATIONS/CONNECTIONS AS

SHOWN.

6. RELOCATED (GENERATOR CONTROLS)

BATTERIES AND CHARGER. PROVIDE FOR

TEMPORARY RELOCATION DURING

CONSTRUCTION UNTIL EXISTING SWITCHGEAR

BATTERIES ARE REMOVED. RETAIN AND REUSE

EXISTING CIRCUIT.

7. 1"C BETWEEN EXISTING GENERATOR CONTROL

CABINET AND NEW SUBSTATION AE BREAKER

CONTROLS AND MONITORING. EQUIPMENT

MANUFACTURER TO PROVIDE FOR

INTERCONNECTION AND AUTO START

CONTROLS/WIRING.

AE SWITCHGEAR CONTROLS:

SHALL PROVIDE FOR THE INTERCONNECTION OF

THE EXISTING GENERATOR CONTROLS WITH THE

SWITCHGEAR AUTO TRANSFER.

SWITCHGEAR SHALL AUTOMATICALLY DETECT LOSS

OF SOURCE,START THE GENERATOR AND RELATED

BREAKER CONTROLS.

SWITCHGEAR SHALL AUTOMATICALLY DETECT

RETURN OF SOURCE,RELATED BREAKER CONTROLS

TO RETURN TO NORMAL SOURCE, AND INITIATE COOL

DOWN CYCLE/GENREATOR SHUT DOWN.

8. NEW CABLE TRAY (24"W LADDER TYPE) TO

MATCH EXISTING. CONTRACTOR TO

COORDINATE MOUNTING/SUPPORT WITH

EXISTING CONDITIONS AND AVOID CONFLICT

WITH EXISTING RACEWAYS/CABLE TRAY NOT

BEING REMOVED. COORDINATE WITH CABLE

TRAY AND OTHER SERVICES FOR FEEDERS THAT

CAN NOT BE REMOVED OR RELOCATED UNTIL

AFTER THE ORIGINAL SUBSTATIONS ARE

REMOVED.

9. NEW JUNCTION BOXES (HIGH ON WALL) TO

TRANSITION BETWEEN REVISED/REROUTED

FEEDERS AT THE SUBSTATION AND EXISTING

FEEDERS OUTSIDE THE SUBSTATION AND

EXISTING FEEDERS OUTSIDE THE SUBSTATION

VAULT. COORDINATE WITH EXISTING

CONDITIONS, PROVIDE JUNCTION BOXES

SUITABLE FOR RELATED CABLING AND

SPECIFIED SPLICES/CABLE TERMINATIONS. SEE

SHEETS E600 THOUGH E-604.

10. NEW GROUND BUS TO REPLACE EXISTING

GROUNDING CABINET. SEE DETAIL SHEET E-501.

RETAIN AND/OR REPLACE EXISTING GROUNDING

CONNECTIONS AT THIS LOCATION EXISTING

GROUND BUS AT SUBSTATION VAULT TO REMAIN.

11. RELOCATED AREA LIGHT. REINSTALL AT REVISED

LOCATION, EXTEND/RETAIN EXISTING CIRCUIT.

12. NEW FIRE RATED DOOR ASSEMBLY. NEW

6'-0"X7'-0" PAIR RATED DOOR(WITH 2"FRAME ON

BOTH SIDES AND 4"HEAD)-SEE DOOR SCHEDULE

IN SPECIFICATION 087100.

13. PROVIDE NEW REMOTE STOP SWITCH FOR

GENERATOR. TIE TO EXISTING GENERATOR

CONTROLS. E STOP PUSHBUTTON, TAMPER

PROOF FLIP COVER. CALIBRATION

TECHNOLOGIES IN SB-ES1 OR EQUAL.

14. SEE DETAIL 8/E-501.

0 2' 4' 8'

0 2' 4' 8'

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

DOOR SCHEDULE

NTS

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

EXISTING (TO REMAIN)

800KW/1000KVA

DIESEL GEN SET

SUBSTATION BN

(TO BE REMOVED)

5KV LOAD

BREAK SW

200e (AF)

750KVA

4160/208Y-120V

3000A

208Y-120V 3PH,4W

SUBSTATION BE

(TO BE REMOVED)

3000A

208Y-120V 3PH,4W

5KV LOAD

BREAK SW

200e (AF)

1000KVA

4160/208Y-120V

(EX) SUMP/ELEC TO BE

REMAIN.

WP,GFI

SUB BN TO SUB BE

TIE SWITCH

TO BE REMOVED

PNL

VBE

F

(EX)

MDP-B

1200 /3 DISC

LDP-A

PNL VBN

GROUND BUS/CABINET

TO BE REMOVED. SEE

NEW WORK PLANS

GENERATOR

CONTROLS

(EX)

(BD)

(BD)

R

R

R

R

R

G

SS

CHGR

C H

G R

R

F F

R

R

(BD)

SS

R

R

R

(EX)

G GG

G

G

G

G

GG

R R

R R R

F

S

R

R

(EX)

GENERATOR

CONTROLS

EXPAND EXISTING WALL

OPENING, AND REMOVE

SLIDING DOOR ASSEMBLY

AT EXISTING AREAWAY, REMOVE

FENCING AT TOP OF RETAINING

WALL FOR THE PORTION OF

THE AREAWAY BEING MODIFIED.

SEE NEW WORK PLAN AND

DETAILS.

MODIFY EXISTING WALL TO

CREATE OPENING FOR NEW

RATED DOOR ASSEMBLY,

SEE NEW WORK PLAN.

EXISTING (TO REMAIN)

800KW/1000KVA

DIESEL GEN SET

NEW

SUBSTATION BN

NEW

SUBSTATION BE

NEW ROTARY DOCKING

STATION 3000AMP

AT GRADE LEVEL (ABOVE)

PROVIDE UNISTRUT

FRAMING/SUPPORT

3000NG

(EX)

MDP-B

3000A

208Y-120V

3PH,4W

1000KVA

4160/208Y-120V

GND BUS

5KV VACUM FAULT

INTERUPTER AT

TRANSFORMER

750KVA

4160/208Y-120V

3000A

208Y-120V 3PH,4W

AREA WELL OPENING (ABOVE) TO BE

COVERED AND MADE WEATHER PROOF.

SEE ARCHITECTURAL/STRUCTURAL

DETAILS

GENERATOR

CONTROLS

(EX)

SS

F

SS

PNL VBN

(EX)

GG

F

S

GG

G

G

G

G

PNL VBE/VBEA

R

R

F

R

G

R

EM

R

R

R

R

R

R

R

R

R

R

(BD)

R

(EX) SUMP/ELEC TO BE

REMAIN.

WP,GFI

J U

N C

T I O

N

B

O X

REVISE/MODFIY EXISTING

PAD UNDER SWITCHGEAR ASSENBLY

3000NG

CHGR

R

(EX)

(CT)

(CT)

(CT)

(CT)

(CT)

(CT)

(CT)

(CT)

(EX)

GENERATOR

CONTROLS

3000NG

3000NG

14 14

TERMINAL BOX AT TOP

OF TRANSFORMER

TANK - BUSHINGS

5KV VACUM FAULT

INTERUPTER AT

TRANSFORMER

B

M

2P

VBEA-5,7

REVISE/MODFIY EXISTING

15KV DISTRIBUTION TO

SUBSTATIONS

4" CONCRETE

PAD UNDER SWITCHGEAR

ASSEMBLY(PAINTED YELLOW)

EM

EM

EM

EM/NL

VBE-2

(VBE-2)

EM/NL

VBE-2

EM/NL

VBE-2

EM/NL

VBE-2

(VBE-2)

VBE-2

X

VBE-2

VBE-2

X1

X1

VBE-2

X1

NEW (RATED DOOR)

D001

O R

E S

R

E E

T

O

R

E

S

R

E

E

T

(E X

F

IR

S

T F

L R

A R

E A

W E

L L

(E N

T R

Y /E

X

IT

P A

T H

W A

Y

QTY.

(2)

D001

NO.

MISCELLANEOUS

THICK.

FRAME INFORMATION

HEIGHTWIDTH MAT'LTYPE MAT'LTYPE RATING

3 HR

REMARKS

1 3/4"7'-0"3'-0" A METAL HMTYPE I

7'-0"

2"

2" 6'-0" 2"

HRDWR.

SET 1

DEPTH

5 3/4"

DOOR INFORMATION

HINGES

FLUSH BOLTS

DUST PROOF STRIKE

PASSAGE SET

COORDINATOR

ASTRAGAL

DOOR CLOSER

KICK PLATES

GASKETING

TA2714

ML2010

2600 SERIES

BY DOOR MANUF.

DC6210xA11

K1050F

S888 x HEAD & JAMBS

HARDWARE SET 1

32D

32D

26D

32D

32D

MK

RO

RO

CO

RO

CO

RO

PE

MANUFACTURERS:

CORBIN RUSSWIN

McKINNEY

PEMKO

ROCKWOOD

CO

MK

PE

RO

NOTE:

HARDWARE MANUFACTURER'S LISTED AS BASIS OF DESIGN.

ALTERNATE MANUFACTURERS ACCEPTABLE, SUBJECT TO

REVIEW BY ARCHITECT AND C.O.R .FOR EQUAL QUALITY

COMPLIANCE.

DOOR SET IN CONCRETE P.I.P. WALL

* DOOR AND FRAME TO BE GALVANIZED.

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

B-VAULT POWER DEMOLITION PLAN ENLARGEMENT

1/4" = 1'-0"

E-102

B-VAULT POWER PLAN ENLARGEMENT

1/4" = 1'-0"

B VAULT ELECTRICAL PLANS

BUILDING 1, C (LEVEL)

0 2' 4' 8'

B-VAULT POWER PLAN ENLARGEMENT

1" = 50'-0"

1. EMERGENCY POWER FEEDER TO SUBSTATION

BE. SEE SHEET E-604

2. OVERHEAD TIE CONNECTION BETWEEN BN/BE

SUBSTATIONS.

3. EMERGENCY GENERATOR FEEDER TO DOCKING

STATION. SEE SHEET E-603.

4. GENERATOR DOCKING STATION FOR REMOTE

(TEMPORARY GENERATOR). TRYSTAR 303PCM

OR EQUAL. 3000 AMP 208/120V 3PG,4W RATED IN

NEMA 3R ENCLOSURE, PAD MOUNTED, CAM

LOCK CONNECTIONS .PROVIDE CONCRETE

BOLLARDS AS SHOWN, SEE CIVIL/SITE DETAILS.

5. UTILIZE EXISTING (3000A) BUS DUCT. PROVIDE

TAP/JUNCTION BOXES AT BOTH ENDS TO ALLOW

FOR CABLE TERMINATIONS/CONNECTIONS AS

SHOWN.

6. RELOCATED (GENERATOR CONTROLS)

BATTERIES AND CHARGER.

7. 1"C BETWEEN EXISTING GENERATOR CONTROL

CABINET AND NEW SUBSTATION AE BREAKER

CONTROLS AND MONITORING. EQUIPMENT

MANUFACTURER TO PROVIDE FOR

INTERCONNECTION AND AUTO START

CONTROLS/WIRING.

BE SWITCHGEAR CONTROLS:

SHALL PROVIDE FOR THE INTERCONNECTION OF

THE EXISTING GENERATOR CONTROLS WITH THE

SWITCHGEAR AUTO TRANSFER.

SWITCHGEAR SHALL AUTOMATICALLY DETECT LOSS

OF SOURCE,START THE GENERATOR AND RELATED

BREAKER CONTROLS.

8. SWITCHGEAR SHALL AUTOMATICALLY DETECT

RETURN OF SOURCE,RELATED BREAKER

CONTROLS TO RETURN TO NORMAL SOURCE,

AND INITIATE COOL DOWN CYCLE/GENREATOR

SHUT DOWN.

9. NEW CABLE TRAY (24"W LADDER TYPE) TO

MATCH EXISTING. CONTRACTOR TO

COORDINATE MOUNTING/SUPPORT WITH

EXISTING CONDITIONS AND AVOID CONFLICT

WITH EXISTING RACEWAYS/CABLE TRAY NOT

BEING REMOVED. COORDINATE WITH CABLE

TRAY AND OTHER SERVICES FOR FEEDERS THAT

CAN NOT BE REMOVED OR RELOCATED UNTIL

AFTER THE ORIGINAL SUBSTATIONS ARE

REMOVED.

10. NEW JUNCTION BOXES (HIGH ON WALL) TO

TRANSITION BETWEEN REVISED/REROUTED

FEEDERS AT THE SUBSTATION AND EXISTING

FEEDERS OUTSIDE THE SUBSTATION AND

EXISTING FEEDERS OUTSIDE THE SUBSTATION

VAULT. COORDINATE WITH EXISTING

CONDITIONS, PROVIDE JUNCTION BOXES

SUITABLE FOR RELATED CABLING AND

SPECIFIED SPLICES/CABLE TERMINATIONS. SEE

SHEETS E600 THOUGH E-604.

11. NEW GROUND BUS TO REPLACE EXISTING

GROUNDING CABINET. SEE DETAIL SHEET E-501.

RETAIN AND/OR REPLACE EXISTING GROUNDING

CONNECTIONS AT THIS LOCATION EXISTING

GROUND BUS AT SUBSTATION VAULT TO REMAIN.

12. RELOCATED AREA LIGHT. REINSTALL AT REVISED

LOCATION FIXTURE THAT WAS REMOVED FORM B

VAULT AREAWAY. EXTEND/RETAIN EXISTING

CIRCUIT.

13. NEW FIRE RATED DOOR ASSEMBLY. NEW

6'-0"X7'-0" PAIR RATED DOOR(WITH 2"FRAME ON

BOTH SIDES AND 4"HEAD)-SEE DOOR SCHEDULE

IN SPECIFICATION 087100.

14. FOR REVISION/EXTENSION OF FEEDER TO MDP-B

PROVIDE WIREWAY (6X6) EXTENSION AT SIDE OF

PANEL (TUB) FOR ROUTING CABLES. FIELD

COORDINATE INSTALLATION WITH EXISTING

CONDITIONS.

15. EXISTING JUNCTION BOXES FOR FEEDERS

EXITING THE SUBSTATION VAULT. RETAIN AND

REUSE JUNCTION BOXES. PROVIDE

SPLICE/CABLE TERMINATIONS AT THESE

LOCATIONS.

16. PROVIDE NEW REMOTE STOP SWITCH FOR

GENERATOR. TIE TO EXISTING GENERATOR

CONTROLS. E STOP PUSHBUTTON, TAMPER

PROOF FLIP COVER. CALIBRATION

TECHNOLOGIES IN SB-ES1 OR EQUAL.

17. SEE DETAIL 8/E-501.

0 2' 4' 8'

DEMOLITION:

A. DEMOLITION WORK SHALL INCLUDE BUT NOT BE

LIMITED TO THE ELECTRICAL SYSTEMS, DEVICES

AND EQUIPMENT SHOWN ON THE DEMOLITION

PLAN. FIELD VERIFY EXISTING CONDITIONS.

COORDINATE THE DE-ENERGIZING OF FEEDERS

WITH COR AND VA FACILITIES.

B. FEEDERS ARE TO BE REMOVED TO A POINT

WHERE THEY EXIT THE SUBSTATION VAULT.

PROVIDE NEW JUNCTION BOX TO

REROUTE/EXTEND FEEDERS TO NEW

SWITCHGEAR LOCATION. ALL EXISTING AND NEW

JUNCTION BOXES AND CABLE TRAYS ARE TO BE

ACCESSIBLE AT ALL TIMES.

NEW WORK:

A. PROVIDE NEW RACEWAYS OR CABLE TRAY FOR

REROUTING OF FEEDERS. CABLE TRAY TO

MATCH EXISTING (24"W LADDER TYPE). SEE

SHEET E-600 THROUGH E-604 FOR RISER

DIAGRAMS. CONTRACTOR TO PROVIDE

CONDUCTOR FILL CALCULATIONS FOR NEW

CABLE TRAY ASSEMBLIES.

B. SEE SHEET E-001 FOR LIGHT FIXTURE

SCHEDULE.

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

DOOR SCHEDULE

NTS

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

(EX)

PANEL

'LPC-9'

(EX)

PANEL

'PP-7-1'

(EX)

PANEL

'PP-8-1'

(EX)

PANEL

'PP-7-2'

(EX)

PANEL

'PP-8-2'

(EX)

GROUND

BUS

(EX)

PANEL 'SWB-D'

(EX)

SUBSTATION

'CN-2'

(EX)

PANEL 'VCE'

(EX)

GROUND

BUS

(EX)

SUBSTATION

'CE'

(EX)

CABLE TAP

BOX 119" AFF

(EX) (3) 3-1/2"C

GENERATOR

121" AFF

(EX) AREA

WELL

(UP) TO LEVEL 1

(SEE PARTIAL PLAN THIS

SHEET)

(EX)

ACCESS LADDER

(3) 3-1/2" C

(3) 3-1/2" C

JA

C

O B

C

IR

C

LE

G R

E G

G

D

R I V

E

O R

E S

R

E E

T

CN-2

3A

TO C-VAULT

F

IR

S T

F L R

A R

E A

W E

L L

M A

N H

O L E

T

Y P

E

X

V

D

S

T B

V

I F

(E X

) 5 K

V D

IS

T

B , (V

IF

E

X

S

T

B

V

I F

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

C-VAULT POWER PLAN ENLARGEMENT

1/4" = 1'-0"

E-103

C-VAULT POWER PLAN ENLARGEMENT

1" = 50'-0"

C VAULT ELECTRICAL PLANS

1. ADD EXTENSION (BOX) TO EXISTING PULL BOX

FOR REROUTING/EXTENSION OF FEEDERS.

COORDINATE WITH FIELD CONDITIONS.

2. EXISTING GENERATOR FEEDER TO SUBSTATION

CE IS TO BE REVISED AND REROUTED TO

REMOTE TEMPORARY GENERATOR DOCKING

STATION. VERIFY IN FIELD (3) 3-1/2"C 4-600 MCM

EACH.

3. NEW EMERGENCY FEEDER TO SUBSTATION CE

ROUTED WITH EXISTING RACEWAYS.

TERMINATIONS/SPLICES TO BE MADE AT

EXISTING/MODIFIED TOP BOX. SEE SHEET E-605.

4. EMERGENCY FEEDER TO SUBSTATION CE FROM

REMOTE DOCKING STATION. SEE SHEET E-605.

5. EMERGENCY FEEDER RACEWAYS ROUTED UP

AREA WAY TO LEVEL A AND LOCATION OF NEW

TEMPORARY GENERATOR DOCKING STATION.

6. GENERATOR DOCKING STATION FOR REMOTE

TEMPORARY GENERATOR. TRYSTAR 303 PCM OR

EQUAL, 1200 AMP 208/120V 3PH 4W RATED WITH

NEMA 3R ENCLOSURE. PAD MOUNTED WITH

CAMLOCK CONNECTIONS. PROVIDE REQUIRED

UNISTRUT SUPPORT AND/OR ACCESSORIES FOR

INSTALLATION.

0 2' 4' 8'

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

PANEL

PP9

PANEL

EMP-CB

RM C112

RM C-E-108

FED FROM

SUBSTATION BE

BKR 14

FED FROM

LCP-E6 BKR 5

PNL

EMP-BC

RM B-E-107

ELECTRICAL

CLOSET

FED FROM

LCP-E6

BKR 2

PNL EMP-AD

A-E-102

ELECTRICAL

CLOSET

FED FROM

LCP-E3-2

(B-E-103)

PNL

EMP-AC

AE-238

ELECTRICAL

CLOSET

FED FROM

LCP-E3-1

(B-E-103)

AREA OF WORK

KEY PLAN - BUILDING 1

N

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

BUILDING 1 - C-LEVEL RM C-E-108 & C-112 PARTIAL ELECTRICAL PLANS

3/8" = 1'-0"

E-111

BUILDING 1 PARTIAL PLANS

ELECTRICAL

00 2' 4' 8'0

BUILDING - 1 A-LEVEL RM A-E-102 PARTIAL ELECTRICAL PLAN

3/8" = 1'-0"

BUILDING 1 - B-LEVEL RM B-E-107 PARTIAL ELECTRICAL PLAN

3/8" = 1'-0"

BUILDING 1 - A-LEVEL RM AE-238 PARTIAL ELECTRICAL PLAN

3/8" = 1'-0"

A. LIGHTER LINE WEIGHT INDICATES EXISTING TO

REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT

INDICATES NEW WORK.

B. FIELD VERIFY FEEDERS TO PANELS DESIGNATED

FOR REPLACEMENT. COORDINATE OUTAGES

WITH COR.

1. REMOVE AND REPLACE PANEL PP9 AT EXISTING

LOCATION. SEE PANEL SCHEDULE SHEET E-401.

2. REMOVE AND REPLACE PANEL EMP-CB. PROVIDE

NEW INTERIOR AND BREAKERS IN EXISTING TUB.

SEE PANEL SCHEDULE SHEET E-401.

3. REMOVE AND REPLACE PANEL EMP-BC AT

EXISTING LOCATION. SEE PANEL SCHEDULE

SHEET E-401.

4. REMOVE AND REPLACE PANEL EMP-AD AT

EXISTING LOCATION. SEE PANEL SCHEDULE

SHEET E-401.

5. REMOVE AND REPLACE PANEL EMP-AC AT

EXISTING LOCATION. SEE PANEL SCHEDULE

SHEET E-401.

LEVEL C

RM C-E-108

LEVEL C

RM C-112

LEVEL B

RM B-E-107

LEVEL A

RM A-E-102

LEVEL A

RM AE-238

00 2' 4' 8'000 2' 4' 8'0

00 2' 4' 8'0

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

2-231

2-230

OFFICE

2-230A 2-230A

PANEL

2A

TO

PANEL

MDP

VERIFY EXISTING

FEEDER.

AREA OF WORK

KEY PLAN - BUILDING 2

N

(EX)

(3) #6 IN 2"C

(EX)

(4) #4 IN 1.25"C

(EX)

(3) #3 IN 1.25"C

(EX)

(4) #3/0 IN 3"C

(EX)

(4) #3/0 IN 2"C

(EX) (3) #1/0 IN 2"C

(EX) (3) #4

IN 2.5"C

B-104

B-104

B-104

RM 1-200

RM 2-200

PANEL

1A

PANEL

PP1

PANEL

PP-2

PANEL

MDP

PANEL

A

PANEL

PP3

PANEL

AC-1

PANEL

AC-2

PANEL

2A

(EX)

PANEL

3A

(EX)

ELEV.

175A

B-104

NO

MCB

EB

EB3

EXISTING FEEDER

TO EXISTING ELEC. WATER

HEATER

(EX) 2 SETS OF: (4)#500KCM IN (2)

4"C TO BUILDING #1 SUBSTATION

AN, BREAKER #14

GROUND FLOOR (BASEMENT)

1ST FLOOR

2ND FLOOR

3RD FLOOR

MECHANICAL PENTHOUSE

ROOF

2ND

FLOOR HALL

EXISTING FEEDER

(EX) (EX)

(EX)(EX)

(EX) (EX) (EX) (EX) (EX)

(EX)

PANEL

1A

TO

PANEL

MDP

VERIFY EXISTING

FEEDER.

PANEL

3A

(EX)

FEEDER/RISER

FROM PANEL 2A

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

BUILDING 2 - FLOOR 2 PARTIAL ELECTRICAL PLAN

1/4" = 1'-0"

E-121

BUILDING 2 PARTIAL PLANS

ELECTRICAL

BUILDING 2 - RISER DIAGRAM

N.T.S.

BUILDING 2 - FLOOR 1 PARTIAL ELECTRICAL PLAN

1/4" = 1'-0"

BUILDING 2 - FLOOR 1 PARTIAL ELECTRICAL PLAN

1/4" = 1'-0"

REPLACE EXISTING PANEL 1A WITH NEW PANEL

INTERIOR AND BREAKERS. SEE PANEL

SCHEDULE SHEET E-401. RETAIN AND REUSE

EXISTING PANEL TUB AND COVER. COORDINATE

SHUTDOWN AND REPLACEMENT WITH COR.

REPLACE EXISTING PANEL 2A WITH NEW PANEL

INTERIOR AND BREAKERS. SEE PANEL

SCHEDULE SHEET E-401. RETAIN AND REUSE

EXISTING PANEL TUB. FEEDER/RISER SERVICES

PANELS 2A/3A. COORDINATE SHUTDOWN AND

REPLACEMENT WITH COR.

REPLACE EXISTING PANEL 3A WITH NEW PANEL

INTERIOR AND BREAKERS. SEE PANEL

SCHEDULE SHEET E-401. RETAIN AND REUSE

EXISTING PANEL TUB. PANEL IS FED FROM

RISER AT PANEL 2A. COORDINATE SHUTDOWN

AND REPLACEMENT WITH COR.

1.

2.

3.

0 2' 4' 8'

0 2' 4' 8'0 2' 4' 8'

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

AREA OF WORK

KEY PLAN - BUILDING 5

N

BASEMENT

SECOND FLOOR

5-2-108

OFFICE

CONFERENCE

ROOM

CHIEF

SUPPLY

5-2-106A

STAIRWAY

5-2-106B

CLOSET

5-2-105C

ELEV.1

FISCAL

CONFERENCE

ROOM

TELEPHONE

CLOSET

5-2-101

STAIRWAY

OFFICE

5-2-100

CORRIDOR

ELEVATOR

LOBBY

MENS

TOILET

OFFICE

5-2-105A

SUPPLY SERVICE

5-2-107 5-2-106

5-2-105

5-2-105B

5-2-102A

5-2-102

5-2-103

5-2-104

5-2-103A

EX

72"

EX

72"

EX

40"

EX

72"

EX

72"

EX

72"

EX

72"

EX

72"

EX

72"

72"72"

EX

72"

NEW PANEL 5A2

FED FROM PP5

SEE RISER

SHEET E-152

72"

72"72"

5A2-13

5A2-15

(3) 3 AWG

(1) 3 AWG N

(1) 8 AWG EG

1-1/4" C

(ROUTED ABOVE

EXISTING CEILING)

5A2-115A2-9

5A2-75A2-55A2-35A2-1

5A2-145A2-125A2-105A2-85A2-65A2-45A2-2

S

SSS

S S

S

S

S

S

S

SS

5-1-114

OFFICE

5-1-113

OFFICE

5-1-111

OFFICE

WOMENS

TOILET

OFFICE

A

C L O S E T

5-1-106A

HALLWAY

MENS

TOILET

ROOM

OFFICE

5-1-109

FISCAL

VBRI

OFFICE

5-1-107

CLOSET

ELEVATOR

LOBBY

5-1-100B

ELEV 1

ROOM

5-1-100C

STAIRWAY

5-1-100

HALLWAY

5-1-115

SUPERVISOR

5-1-109B

HALLWAY

5-1-109C

STAIRWAY

5-1-110A

STAIRWELL

5-1-106

5-1-105

5-1-100A

COPY

5-1-112

5-1-112A

MECHANICAL

5-1-108

TRAVEL

5-1-102

5-1-101A

VBRI

OFFICE

5-1-101B

VBRI

OFFICE

5-1-101C

VBRI

OFFICE

5-1-101D

EX

72"

5A2-21

S

EX

72"

5A2-19

S

EX

72"

S

EX

72"

S

EX

72"

5A2-24

S

EX

60"

5A2-18

S

EX

5A2-17

EX

72"

5A2-28

S

EX

72"

S

5A2-30

EX

72"

S

5A2-31

EX

72"

5A2-27

S

EX

72"

S

EX

72"

S

5A2-23 5A2-25

EX

72"

5A2-29

S

EX

72"

S

5A2-16

5A2-20

5A2-22

EX

72"

S

5A2-26

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

E-151

BUILDING 5 PARTIAL PLANS

BUILDING 5 - FLOOR 2 PARTIAL PLAN

1/4" = 1'-0"

1. EXISTING SERVICE ENTRANCE WIREWAY AND

DISCONNECTS TO REMAIN.

2. AT EXISTING PANEL 5, PROVIDE NEW 60A-3ɸ

BREAKER TO EXISTING SPACE. (SQUARE D NQOD)

3. ROUTE NEW RACEWAY (UP) AT EXTERIOR OF THE

BUILDING TO SECOND FLOOR.

4. FEEDER TO NEW PANEL (5A2) UP AND ACROSS

THE SECOND FLOOR ACCESSIBLE CEILING.

5. PROVIDE NEW WALL TO CONTAIN PANEL (5A2).

WALL TO BE THE SAME LENGTH AS EXISTING

CLOSET WALL. CONSTRUCT WALL OF 6" 24 GAUGE

STEEL STUDS AND 5/8" GYPSUM BOARD

EXTENDING 6" ABOVE THE CEILING. PANEL FACE

TO BE FLUSH WITH WALL SURFACE. PAINT WALL

WALL AND PANEL COVER TO MATCH EXISTING

ADJACENT WALL SURFACES. PROVIDE NEW BASE

MATCHING EXISTING, AND MODIFY CEILING GRID

AND TILES AS REQUIRED TO CLOSE WITH NEW

WALL SURFACE.

A. ALL EXTERIOR WALL PENETRATIONS TO BE

SEALED WITH (VA EAST ORANGE FACILITIES)

APPROVED WEATHER PROTECTIVE MATERIALS.

B. LIGHTER LINE WEIGHT INDICATES EXISTING TO

REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT

INDICATES NEW WORK.

0 2' 4' 8'

BUILDING 5 - FLOOR 1 PARTIAL PLAN

1/4" = 1'-0"

0 2' 4' 8'

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

MECHANICAL

ROOM

IRM

CLOSET

5-B-100

CORRIDOR

5-B-103

5-B-103A

FILE

STORAGE

5-B-102

TO

TUNNEL

EX

PP5

EX

LP1

EX

PP4

EX

LP2

1-1/4"C

(3) 3 AWG

(1) 3 AWG N

(1) 8 AWG EG

AREA OF WORK

KEY PLAN - BUILDING 5

N

BASEMENT

SECOND FLOOR

M

EX

JB

EXISTING

PAD MOUNTED

TRANSFORMER

B-103 B-103

B-103 B-103

B-103

EX

PNL 4

FL1&2

EX

PANEL

EX

PANEL

EX

PNL 5

FL1

EX

ECB

175A

100A

B-103

B-103

EX

E-MON

D-MON

KWH

B-103

EX

NSS

TO 5KV

SWITCH

EXISTING

EXISTING

NEW

PNL 5A2

A/C

FL2

RM 5-2-102

(3) 3 AWG

(1) 3 AWG N

(1) 8 AWG EG

1-1/4" C

AT PNL 5, ADD (1)

100A -3P BREAKER TO

FEED PNL 5A2. MATCH

EXISTING (SQ D NQOD)

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

BUILDING 5 - BASEMENT PARTIAL PLAN

1/4" = 1'-0"

E-152

BUILDING 5 PARTIAL PLANS

ELECTRICAL AND DIAGRAMS

BUILDING 5 - RISER DIAGRAM

N.T.S.

TO TRANSFORMER

1. EXISTING SERVICE ENTRANCE WIREWAY AND

DISCONNECTS TO REMAIN.

2. AT EXISTING PANEL 5, PROVIDE NEW 60A-3ɸ

BREAKER TO EXISTING SPACE. (SQUARE D

NQOD)

3. ROUTE NEW RACEWAY (UP) AT EXTERIOR OF

THE BUILDING TO SECOND FLOOR.

0 2' 4' 8'

A. ALL EXTERIOR WALL PENETRATIONS TO BE

SEALED WITH (VA EAST ORANGE FACILITIES)

APPROVED WEATHER PROTECTIVE MATERIALS.

B. LIGHTER LINE WEIGHT INDICATES EXISTING TO

REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT

INDICATES NEW WORK.

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

NEW DOUBLE

TUB PNL 7A

PANEL

7A

PANEL

7B

PANEL

7C

FED FROM

EDP-A (1-127)

SEE RISER DIAGRAM

THIS SHEET

AREA OF WORK

KEY PLAN - BUILDING 7

N

1 CB

P7A

P7B P9

P7C

400A

3P

350A

3P

400A

3P

300A

3P

300A

3P

175A

3P

200A

3P

100A

3P

125A

3P

300A

3P

(8) #250

IN 4" C

(4) #500

IN 4" C

(4) #250

IN 4" C

(4) #500

IN 4" C

(4) #1/0

IN 2" C

(4) #3/0

IN 2" C

(4) #2

IN 1.5" C

(4) #2

IN 1.5" C

(4) #2

IN 1.5" C

EMERGENCY DISTRIBUTION EDP-A 1600A

BUS, 65000 AIC (40.22Kaic )

208Y/120V, 3ɸ, 4W

(EX)

EDP-A

PP 6 DP-B SUMP

PUMP

PP 4 PP 13 PB39A B-133 PP 8

B-143

B-159

B-158B

B-158B

B-158B

MCC1 / MCC1A

TO

MCCE7A

TO

EDP/ATS1

(4) #600 KCM

(1) #1 GND

IN 4" C

P7A

2-1/2" C

(3) 250 MCM

(1) 250 MCM N

(1) 4 AWG EG

(VIF) 4-250 MCM

2-1/2" C

(EX)

(EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX)

SEE PANEL

SCHEDULE

SHEET E-401

PNL 1 CB

200AMCB

NEMA 3R

B-144A

2-1/2" C

(3) 250 MCM

(1) 250 MCM N

(1) 4 AWG EG

PANEL

1CB

FED FROM

EDP-A (1-127)

(2) 2"C

BRANCH CIRCUITS

4" C

4-250 MCM

FEEDER TO

PNL ICB

(NEW)

PANEL ICB

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

SHEET NOTES:

SHEET KEY NOTES:

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

E-171

BUILDING 7 PARTIAL PLANS

ELECTRICAL

BUILDING 7 - BASEMENT PARTIAL PLAN - (B-143) ELECTRICAL

1/16" = 1'-0"

BUILDING 7 - RISER DIAGRAM

1/4" = 1'-0"

BUILDING 7 - BASEMENT PARTIAL PLAN - (B-143) ELECTRICAL

1/16" = 1'-0"

1. RELOCATE EXISTING PANEL 7 (A,B,C) FEEDER TO

PANEL 7A LOCATION. RETAIN AND REUSE PANEL

TUB AS JUNCTION BOX. SECURE COVER AT

PANEL AND LABEL AS JUNCTION BOX.

2. EXISTING BRANCH CIRCUITS AT PANELS 7A, 7B,

7C TO BE RELOCATED /EXTENDED TO NEW

PANEL 7A. RELOCATE FEEDER TO PANEL P9 TO

P7A WITH BRANCH CIRCUITS. RETAIN AND REUSE

PANEL TUBS AS JUNCTION BOX. SECURE

COVERS AT OLD PANELS AND LABEL AS

JUNCTION BOXES. SEE PANEL SCHEDULES ON

SHEET E-401.

3. EXISTING PANEL ICB TO BE REMOVED. RETAIN

WIREWAY ADJACENT TO PANEL FOR ROUTING OF

NEW FEEDER AND BRANCH CIRCUITS. SEAL ANY

UNUSED OPENINGS AT WIREWAY UPON

REMOVAL OF PANEL.

4. NEW PANEL ICB. EXTEND EXISTING FEEDER AND

BRANCH CIRCUITS TO NEW PANEL LOCATION.

SEE RISER DIAGRAM THIS SHEET. NEMA 3R

ENCLOSURE WITH RAIN TIGHT (MEYERS HUBS)

AT RACEWAY PENETRATIONS.

A. LIGHTER LINE WEIGHT INDICATES EXISTING TO

REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT

INDICATES NEW WORK.

0 2' 4' 8'

0 2' 4' 8'

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

E-401

ELECTRICAL PANEL SCHEDULES

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

Suite C

Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net

02/05/2020

E-402

ELECTRICAL PANEL SCHEDULES

SAFETY REVIEW RESUBMISSION 11/20/19REV 1

N

R

A

N

046636

E

E N

I

G

H

K

I

A

W

O

N

A

T

R

F

SEAL

R

P

O

O

I

SS

O E

H

RC

A

I

L

A

N

L

E

N

C

I

M

H

E

A

L

S

SHORE EXISTING 2-HR RATED CMU

MASONRY WALL ABOVE OPENING PRIOR

TO REMOVING WALL AND INSTALLING

LINTEL - SEE STRUCTURAL

L5 X 3-1/2 X 5/16 (LLV),

BEAR 6" MINIMUM EACH END

MAX SPAN = 8'-0"

PAINT TO MATCH BLOCK WALL COLOR

H.M. DOOR FRAME,

4" AT HEAD

1/2"

EXISTING WALL TO REMAIN

OPEN VAULT

PAINTED COMMERCIAL 24 GA. METAL ROOF

PANEL SYSTEM W/ GUTTER AND DOWNSPOUT

PAINTED ARCHITECTURAL DRAINABLE

FIXED LOUVER SYSTEM W/ CONTINUOUS

PAN TO SIT ON CONCRETE WALL. EQUAL SPACING

PER ELEVATION. MAX. WIDTH PER PANEL - 48".

TYPICAL ALL ELEVATIONS

SILL FLASHING END DAM AT

EXISTING BUILDING WALL

CONTINUOUS ALUM. SILL FLASHING

AT BASE BY LOUVER VENDOR

METAL FLASHING, 24 GA. MIN

CUT IN REGLET, METAL

COUNTER FLASHING - 4"H,

AND SEALANT

CLOSURE STRIPS

COLD FORM JOISTS, BOXED BEAM AT ENDS

SEE STRUCTURAL

1'-0"

BREAK METAL TO MATCH

LOUVER SYSTEM

2'-11

8"

6"

2x4 METAL TUBES TO MATCH

LOUVER FINISHTO PROVIDE LATERAL

SUPPORTFOR LOUVER PANELS,

SECURE TO EX. WALL

AND COLD FORM BEAM

1'-10"

TOP OF STEEL COL.

2'-0"

TOP OF STL. ANGLE

0'-0"

TOP OF WALL

11'-0"

OPEN VAULT

PAINTED COMMERCIAL 24 GA. METAL ROOF

PANEL SYSTEM W/ GUTTER

PAINTED ARCHITECTURAL

DRAINABLE FIXED LOUVER,

TYPICAL,

SEE SPECIFICATION

CONTINUOUS SILL FLASHING

AT BASE BY LOUVER

VENDOR

TYPICAL ALL 4 SIDES

BREAK METAL END CAP

METAL DECKING ON

COLD FORM JOISTS

SEE STRUCT.

BREAK METAL TO MATCH

LOUVER SYSTEM

2x4 METALTUBES TO MATCH

LOUVER FINISHTO PROVIDE LATERAL

SUPPORTFOR LOUVER PANELS,

SECURE TO EX. WALL

AND ROOF STRUCTURE

1/2"

EXISTING MEMBRANE ROOF

NEW TERMINATION BAR UNDER

NEW CONT. SILL FLASHING

0'-0"

TOP OF WALL

4'-9 3/4"

TOP OF STEEL COL.

4'-7"

TOP OF STEEL COL.

STEEL BEAM

SEE STRUCTURAL

BREAK METAL GUTTER AND

DOWNSPOUT TO CONC.

SPLASH BLOCK ON LOWER

EXISTING ROOF.

EXISTING CONC. WALK

EXISTING CONC. WALL

TYP.

GENERAL NOTE:

BLANK OF I NTERIOR OF ALL LOUVERS

NOT BEING UTILIZED BY MECHANICAL

FOR VENTING. SEE MECH. DWGS.

EXISTING CONC. WALL

LOUVER

12" DEEP PLENUM FULL SIZE OF LOUVER

SECTION WITH BOTTOM SEALED 2" DEEP

MOTORIZED BACKDRAFT

DAMPER

WALL HOUSING

EXHAUST FAN

SCREENED INLET

3/4" DRAIN WITH INDIRECT WASTE TO SUMP OR

FLOOR DRAIN

1-1/2" FOIL FACED DUCT WRAP FIBERGLAS

INSULATION, TYP.

VA PROJECT NUMBER

Building Number

Drawing Number

Project Title

Date Checked Drawn

Drawing Title

Approved:

VA FORM 08-6231

A

B C

D E

21 4 5 6 7

321 4 5 6 7

A B

C D

E

Dwg. of

LocationLocation

Office of

Construction and Facilities

Management

PROJECT MANAGER:

ACG Project Number

CONSULTANTS:

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120

Cary, North Carolina 27511 www.acg-pa.com 919-858-7420

NC License #: C-1848

U.S. Department of Veterans Affairs

© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#

IMPROVE ELECTRICAL

DEFICIENCIES, II A & B

561-18-135

VA NJ HEALTH CARE SYSTEM

385 TREMONT AVENUE

EAST ORANGE, NJ 07018

X

18-096

ISSUED FOR CONSTRUCTION

FULLY SPRINKLERED

1, 2, 5, 7

Foresite Group, Inc.

2128 Moores Mill Rd.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .