36C24220B0035-0001005.pdf
PDF Posted
- Solicitation number
- 36C24220B0035
About this file
This notice is for a federal solicitation seeking proposals for an electrical upgrade project at a Department of Veterans Affairs facility in East Orange, New Jersey. Key details include:
-
Scope of work involves replacing the campus switchyard building and associated electrical equipment including controls, site work, and replacing normal and emergency power switchgear in two vaults. Additional work includes replacing substations and electrical panels in various campus buildings.
-
Estimated cost is between $5-10 million. Proposals are due by the date specified in the solicitation to be released on or about April 20, 2020.
-
The project has a NAICS code of 236220 and is set aside for Service-Disabled Veteran Owned Small Businesses. The response submittal address, date and time will be in the solicitation.
-
Work includes civil site work like retaining wall relocation, structural elements like installing concrete pads and a canopy structure, and architectural elements such as metal wall panels and a standing seam roof for the canopy.
-
Construction is to be completed within 730 calendar days of award. The contractor must submit a preliminary schedule and contingency plan for electrical outages.
36C24220B0035 0001 S02 Drawings 04-Electrical.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24220B0035-0002000.docx | DOCX document | |
| 36C24220B0035-0001001.pdf | ||
| 36C24220B0035-0001003.pdf | ||
| 36C24220B0035-0001004.pdf | ||
| 36C24220B0035-0001000.docx | DOCX document | |
| 36C24220B0035-0001002.pdf | ||
| 36C24220B0035-020.pdf | ||
| 36C24220B0035-015.docx | DOCX document | |
| 36C24220B0035-021.pdf | ||
| 36C24220B0035-019.pdf | ||
| 36C24220B0035-017.pdf | ||
| 36C24220B0035-016.pdf | ||
| 36C24220B0035-018.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Δ DELTA
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC FREQUENCY
CONTROL, OR AVAILABLE FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP OR A AMPERE
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISH FLOOR
BFG BELOW FINISH GRADE
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CATV COMMUNITY ANTENNA TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CLG CEILING
CM CENTRAL MONITOR/METERING ASSEMBLY
COAX COAX CABLE
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL OR DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX, EXIST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METALLIC CONDUIT
FP FIRE PROTECTION
FT FEET OR FOOT
FS FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRS GALVANIZED RIGID STEEL
GTB GROUND TERMINAL BOX
ELECTRICAL ABBREVIATIONS
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAH KILOVOLT AMPERE PER HOUR kW KILOWATT kWH KILOWATT HOUR kWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LRA LOCKED ROTOR AMPS
LTCP LOCAL TEMPERATURE CONTROL PANEL
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT OR MICROWAVE
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
P POLE
PA PUBLIC ADDRESS
PB PANELBOARD, PULL BOX, OR PUSHBUTTON
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PF POWER FACTOR
PH PHASE
PNL PANEL
POD POWER OPERATED DAMPER
POS POSITION
PRI, PRIM PRIMARY
PVC POLYVINYL CHLORIDE (PLASTIC)
R RELOCATED
RECPT RECEPTACLE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
REQD REQUIRED
SCC SHORT CIRCUIT CAPACITY
SEC SECONDARY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL
BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS,
THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE
LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, THE
LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, AND THE VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT
AND FEEDERS WHERE THE BUILDING CONSTRUCTION IS NOT SUITABLE
FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR
SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS,
FLOORS, CEILINGS AND ROOFS IN ACCORDANCE WITH THE
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTINGS
REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES,
TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO SUIT THE
PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES
DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO
INSTALLATION SO AS TO AVOID CONFLICT DURING CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR
DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE
NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER.
PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL,
BREAKER OR PARTICULAR EQUIPMENT MANUFACTURER'S
SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES
SHALL BE TERMINATED ON THE DEVICE'S SCREW TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET,
FIXTURE, OR EQUIPMENT UNLESS NOTED OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS
OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC
CONDUIT MAY BE USED ON VIBRATING EQUIPMENT.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT
SHALL BE LABEL LISTED BY AN APPROVED THIRD PARTY TESTING
AGENCY.
17. DIMENSIONS, QUANTITIES AND LOCATIONS OF EXISTING CONDUIT AND
EQUIPMENT AS SHOWN ON THESE DRAWINGS ARE BASED ON RECORD
DRAWINGS AND CASUAL OBSERVATION AND ARE NOT NECESSARILY
COMPLETELY ACCURATE. CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING ANY AND ALL EXISTING EQUIPMENT AND CONDITIONS THAT
MIGHT AFFECT THE WORK.
GENERAL NOTES
J
J
S
E
JUNCTION BOX, PURPOSE AS NOTED
JUNCTION BOX IN WALL, PURPOSE AS NOTED:
18" AFF STANDARD UNO
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SWITCH: 44" AFF STANDARD UNO
SWITCH MODIFIERS:
M - MOTOR RATED
3 - THREE-WAY
T - DIGITAL TIMER SWITCH
PANELBOARD
EQUIPMENT ELECTRICAL CONNECTION
HOMERUN - 120V OR 277V
HOMERUN - 208V OR 480V
120V DUPLEX RECEPTACLE: 18" AFF STANDARD, UNO
RECEPTACLE MODIFIERS:
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
WP - WEATHERPROOF
DED - DEDICATED
KK
KIRK-KEY MANUAL INTERLOCK
UNDERGROUND ELECTRICALUGE
CONTACTOR OR MOTOR STARTER
5"
UNDERGROUND DUCT, (2) 5" CONDUIT
PANELBOARD
SYMBOL LEGEND
INDICATOR LIGHT (G=GREEN, R=RED,
A=AMBER, W-WHITE)
MOTOR WITH HORSEPOWER
BOND TO GROUNDING ELECTRODE SYSTEM
CONTACT (NORMALLY CLOSED)
THERMAL OVERLOAD RELAY
CONTACT (NORMALLY OPEN)
REMOVABLE ELEMENT
FUSE
HOMERUN CONDUIT
THERMOSTAT
METER
CURRENT TRANSFORMER
SINGLE POLE SWITCH
M
CT
S
T
2 AWG BARE TINNED CU UNO
UNDERGROUND CONDUIT
G
G G
DEMOLITION (ITEM TO BE REMOVED) WHEN NOTED
KK
KIRK-KEY MANUAL INTERLOCK
CIRCUIT BREAKER
DRIVEN GROUND ROD
GROUND BOND BY EXOTHERMIC WELD
PM
POWER METER/MONITOR
FIRE ALARM PULL STATION
F
F
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM PULL SPEAKER AND STROBE
48"
90"
90"
90"
F
S
F
S
FIRE ALARM SMOKE DETECTOR
W WALL PHONE
SWITCH - MOUNTED 48" AFF
B PUSHBUTTON
LINEAR INDUSTRIAL (LED) CHAIN HUNG
WALL MOUNTED EXIT SIGN (AC)
WALL MOUNTED EMERGENCY LIGHT (WALL PACK)
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
E-001
ELECTRICAL NOTES, LEGENDS, AND
ABBREVIATIONS
NEW WORK:
A. PROVIDE ARC FLASH CALCULATIONS AND
RESPECTIVE LABELING AT ALL RESPECTIVE
ELECTRICAL EQUIPMENT REVISED OR MODIFIED
BY THIS RENOVATION. SEE SPECIFICATIONS
260573.
B. SEE SPECIFICATIONS 013526 SAFETY
REQUIREMENTS FOR LOCK OUT TAG OUT
PROCEDURES, AND ELECTRICAL SAFETY
REQUIREMENTS. ELECTRICAL SHUTDOWNS NEED
TO BE SCHEDULED WITH COR WITH AT LEAST
TWO WEEKS MINIMUM NOTICE. SEE
SPECIFICATIONS 260511 1.9C.
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
DocuSign Envelope ID: CA86D127-DB02-414A-9C7B-04E0EE29525A
2/4/2020
X X
X X
XXX
XXXX
XXXX
XXXX
X
X
X X
X X
X X
X X X X X X X X X X X
X X
X X
X X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
(EX)
BUILDING #24
CONCRETE
ASPHALT DRIVEWAY
(EX)
DECONTAMINATION
CENTER
(EX) ELECTRICAL YARD
(EX) ELECTRICAL YARD
(EX)
PAD MOUNTED
TRANSFORMER
X
(EX)
26,400V
VA PRIMARY
SWITCH
(EX)
26,400V
VA PRIMARY
SWITCH
(EX)26,400V
UTILITY
SWITCH /
CONNECTIONS
(EX)26,400V
UTILITY
SWITCH /
CONNECTIONS
(EX)
EMERGENCY
GENERATOR SET
X X X X X X X X X X X
(EX) RETAINING WALL (TYP)
(EX) RETAINING WALL (TYP)
(EX) MV MANHOLE
(EX) ATS/
SWITCHGEAR
U
G
E
U G
E
(EX) MV DUCT BANK (VIF)
(EX) MV DUCT BANK (VIF)
NEW MH OVER (EX)
DUCT BANK
U
G
E
UGE
U G
E
UGE UGE
U
G
E
U G
E
U
G
E
U
G
E
U
G
E
UGE
"A"
"A"
PNL SG
(4)3 AWG
(1)8 AWG EG
1-1/2"C
(EX)
PNL SWGR
(EX)26,400V ELECTRICAL
DISTRIBUTION EQUIPMENT
AND SERVICES ARE OWNED,
OPERATED AND MAINTAINED
BY THE UTILITY PROVIDER
(NIC)
52-1
52-4
52-5
52-3TIE
52-6
52-9 (SP)
52-10
52-11
52-12
52-13
52-14
SPACE
52-7
52-8 (SP)
52-2
52-15
52-16
X X X X X X X X X X X
J
J
J
J
(2)
(4)
(1)
(3)
(EX)PNL AC
S
(7)
(5)
S
(5)
(7)
"A" S
(8)
(6)
"A"
S
(6)
(8)
S S
(9)
(11)
(9)
(11)
"A"
S
(12)
(10)
S
(10)
(12)
(EX)PNL DC
J J
ADD (1) 100A 3P
DEVICE AT EXISTING
PANEL SWGR
GENERAL NOTES:
1.
2.
3.
4.
CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS,
OR AS SPECIFIED.
PROVIDE #4 REINFORCING RODS ON TOP AND
BOTTOM OF DUCTS WHEN CROSSING OR
PLACED IN ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL
BE 610mm (24").
GENERAL NOTES:
1.
2.
3.
4.
CONCRETE SHALL BE 2000 P.S.I. @ 28
DAYS, OR AS SPECIFIED.
PROVIDE #4 REINFORCING RODS ON TOP
AND BOTTOM OF DUCTS WHEN CROSSING
OR PLACED IN ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE
SHALL BE 610mm (24").
5" PVC 40 RACEWAY FOR ELECTRICAL
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
1. PG&E 26,400V SERVICE ENTRANCE FEEDER
(1) (N300), (2) (1-61). OPERATION AND
MAINTENANCE OF THE DEVICES IS
RESPONSIBILITY OF THE UTILITY PROVIDER.
2. OVERCURRENT PROTECTION 1200A (VACUUM
SWITCH), OWNED AND MAINTAINED BY EAST
ORANGE VAMC. EXISTING DEVICES TO
REMAIN, FIELD VERIFY EXISTING
CONDITIONS.
SEE SHEET E-601.
3. SERVICE ENTRANCE TRANFORMERS, 5000
KVA 26,400-4160Y/2400V 3PH.
TRANSFORMERS SHALL BE REPLACED.
5000/6250 KVA OA/FA OIL FILLED
TRANSFORMER 55 DEG C RISE.
4. 1200 AMP 4160V 3PH, 3W FEEDER BELOW
GRADE. REMOVE FROM SECONDARY OF
TRANSFORMER TO EXISTING PRIMARY
SWITCHGEAR. SEE SHEET E-601 AND
COORDINATE WITH INSTALLATION OF NEW
5KV SWITCHGEAR. FEEDER SHALL BE
REMOVED UPON ACTIVATION OF NEW
SWITCHGEAR.
5. 5 KV SWITCHGEAR WITH DISTRIBUTION
CIRCUIT BREAKERS SERVICING 5KV
DISTRIBUTION TO EAST ORANGE VAMC
CAMPUS. SEE SHEET E-601. MV CABLE
TERMINATIONS ARE ACCESSIBLE FROM THE
EAST SIDE EXTERIOR DOOR PANELS TO
BUILDING 24. SWITCHGEAR TO BE DE
ACTIVATED AND REMOVED WITH EXCEPTION
OF REAR TERMINAL/SPLICE CABINET UPON
ACTIVATION OF NEW SWITCHGEAR.
6. NEW (1200A) 5KV (4160V) FEEDER BELOW
GRADE. PROVIDE NEW RACEWAYS, MV
CABLES, AND TERMINATIONS.
7. NEW 5KV DISTRIBUTION SWITCHGEAR (NEMA
3R, WALK IN ENCLOSURE) WITH EXTERIOR
ACCESS DOORS TO 5KV CONNECTIONS.
MANUFACTURED ASSEMBLY PROVIDED BY
ELECTRICAL EQUIPMENT PROVIDER. 15KV
METAL CLAD SWITCHGEAR WITH VACU
BREAK SWITCH ASSEMBLIES.
8. OVERHEAD 5KV DISTRIBUTION CIRCUITS IN
CABLE TRAY (HOT DIPPED GALVANIZED
STEEL , WITH COVER) TO RE FEED 5KV
DISTRIBUTION CIRCUITS. CABLE TRAY TO BE
SIZED FOR RESPECTIVE 5KV DISTRIBUTION
CABLES, PROVIDE SHOP DRAWING FOR
APPROVAL. SEE SHEET E-601.
9. SEE CIVIL/SITE DOCUMENTS. A PORTION OF
THE EXISTING RETAINING WALL AND OR
FENCING TO BE REMOVED.
10. (TYPICAL) AREA LUMINAIRE MOUNTED TO
EXISTING STRUCTURE TO BE REPLACED
WITH LED AREA LIGHT (WITH PHOTOCELL).
RETAIN AND REUSE EXISTING BRANCH
CIRCUITS, REPLACE EXISTING SWITCH AND
RECEPTACLE AT EACH LOCATION (3R)
ENCLOSURE/GASKET.
11. DISCONNECT EXISTING 24.6KV CABLES AT
TRANSFORMER AND RETAIN FOR REUSE.
PROVIDE FOR TESTING AND EVALUATION
PRIOR TO RECONNECTION. PROVIDE NEW
TERMINATIONS AND RECONNECT PRIMARY
26.4KV TO NEW TRANSFORMERS.
COORDINATE WITH 5KV DISTRIBUTION
SWITCHGEAR REPLACEMENT.
12. NEW DUCT BANK EXTENDED FROM NEW 5KV
SWITCHGEAR TO EXISTING 5KV DISTRIBUTION
DUCT BANK LOCATIONS. PROVIDE MANHOLE
AT THIS LOCATION FOR FUTURE ROUTING OF
5KV DISTRIBUTION CABLES TO THE EXISTING
5KV CAMPUS DISTRIBUTION LOOP
RACEWAYS. UNDER A FUTURE PROJECT,
CAMPUS 5KV DISTRIBUTION CABLES WILL BE
REPLACED. AT THAT TIME THE 5KV
DISTRIBUTION WILL BE ROUTED DIRECTLY
FROM THE NEW SWITCHGEAR.
13. UTILITY CONTROL CABINET, COORDINATE
WIRING WITH UTILITY PROVIDER. PROVIDE
2"C BACK TO EXISTING CONTROL/METERING
CABINET AT BLDG 24.
14. EXISTING PANELBOARD AT ELECTRICAL
YARD. PROVIDE NEW FEEDER FROM
LRP-SWGR (4 #8,#10G, 1-1/2"C) 60A-3P .
RETAIN AND REUSE EXISTING PANELBOARD.
15. EXISTING (DC) CONTROL CABINET/PANEL TO
REMAIN. RETAIN EXISTING SERVICES.
EXTEND REQUIRED CONTROLS TO NEW
SWITCHGEAR BUILDING.
16. 1-1/2"C (FA,PA,PHONE) SEE SHEET E-502.
17. COORDINATE WITH MANUFACTURES SHOP
DRAWINGS. EXTEND/EXPAND TRANSFORMER
PAD AS REQUIRED FOR NEW TRANSFORMER.
PARTIAL PLAN SITE ELECTRICAL
1" = 16'
ES-101
PARTIAL SITE PLAN ELECTRICAL
0 8' 16' 32'
DUCTBANK LAYOUT (DISTRIBUTION FEEDERS)
NO SCALE
DUCTBANK LAYOUT (SERVICE FEEDERS)
NO SCALE
EXISTING SITE :
A. VERIFY IN FIELD THE LOCATIONS OF EXISTING
MEDIUM VOLTAGE UNDERGROUND DUCT BANKS
AND MEDIUM VOLTAGE DISTRIBUTION SYSTEM.
PROTECT DURING CONSTRUCTION AS
REQUIRED.
B. WHERE NEW CONSTRUCTION ( FOOTINGS AND
OR FOUNDATIONS ) CROSS THE EXISTING DUCT
BANKS COORDINATE WITH STRUCTURAL DETAILS
TO ENSURE NEW WORK BRIDGES OVER THE
EXISTING DUCT BANKS WHICH WILL REMAIN AT
THIS TIME.
C. SEE SHEET E-001 FOR LIGHT FIXTURE
SCHEDULE.
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
3000A
208Y-120V
3PH,4W
1000KVA
4160/208Y-120V
NEW
SUBSTATION AE
NEW ROTARY DOCKING
STATION 3000AMP
AT GRADE LEVEL (ABOVE)
3000NG
3000NG
AREA WELL OPENING (ABOVE) TO BE
COVERED AND MADE WEATHER PROOF.
SEE ARCHITECTURAL/STRUCTURAL
DETAILS
NEW WALL
GND BUS
EXISTING (TO REMAIN)
800KW/1000KVA
DIESEL GEN SET
GENERATOR FEEDER (BUS DUCT)
TO SWITCHBOARD AE
(REVISED/RELOCATED)
(CT)
F
R
SS
SS
F
F
PNL AE-21
(EX)
TXF (A1)
(EX)
TXF (A)
(EX)
SS
G G
G
G
G
G
G
G
F F
TXF (X RAY)
A-241
(EX)
PNL VAE/
VAEA
400/3
GENERATOR
CONTROLS
(EX)
GENERATOR
CONTROLS
(EX)
R
EM
R
R
R R
R
R
R
R
R
R
R
(CT)
(CT)
NEW (RATED DOOR)
CHGR
R
R
(CT)
JUNCTION BOXJUNCTION BOX
(CT)
(CT)
750KVA
4160/208Y-120V
3000A
208Y-120V 3PH,4W
NEW
SUBSTATION AN
4" CONCRETE
PAD UNDER SWITCHGEAR
ASSEMBLY(PAINTED YELLOW)
(CT)
R
R
R
R
(EX) SUMP/ELEC TO
REMAIN.
AE-7
200NG
(VAE-3)
(VAE-1)
REVISE/MODFIY EXISTING
PAD UNDER SWITCHGEAR ASSENBLY
TERMINAL BOX AT TOP
OF TRANSFORMER
TANK - BUSHINGS
5KV VACUM FAULT
INTERUPTER AT
TRANSFORMER
5KV VACUM FAULT
INTERUPTER AT
TRANSFORMER
B
M
2P
M
2P
VAEA-5,7
VAEA-5,7
REVISE/MODFIY EXISTING
15KV DISTRIBUTION TO
SUBSTATIONS
EM/NL
VAE-3
EM/NL
VAE-3
EM/NL
VAE-3
EM/NL
EM
EM
EM
VAE-*
VAE-1
VAE-1
X1
X1
X1
VAE-1
D001
EXISTING (TO REMAIN)
800KW/1000KVA
DIESEL GEN SET
SUBSTATION AN
(TO BE REMOVED)
5KV LOAD
BREAK SW
200e (AF)
750KVA
4160/208Y-120V
3000A
208Y-120V 3PH,4W
SUBSTATION AE
(TO BE REMOVED)
3000A
208Y-120V 3PH,4W
5KV LOAD
BREAK SW
200e (AF)
1000KVA
4160/208Y-120V
EXPAND EXISTING WALL
OPENING, AND REMOVE
SLIDING DOOR ASSEMBLY
GENERATOR FEEDER (BUS DUCT)
TO SWITCHBOARD AE
(REVISED/RELOCATED)
T-MDP (ER)
SUBSTATION TIE SWITCH
TO BE REMOVED
TXF (A1)
(EX)
TXF (A)
(EX)
GROUND BUS/CABINET
TO BE REMOVED. SEE
NEW WORK PLANS
TXF (X RAY)
A-241
(EX)
GENERATOR
CONTROLS
(EX)
PNL VAE
PNL AE-21
(EX)
(TO REMAIN)
(CT)
(CT)
(CT)
(CT)
(BD)
(BD)
(CT)
(CT)
F
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
SS
(VAE-3)
G G
G
G
G
G
G
400/3
G
SS
SS
CHGR CHGR
R
R
F
F
R
F F
R
GENERATOR
CONTROLS
(EX)
R
R
(EX) SUMP/ELEC TO
REMAIN.
MODIFY EXISTING WALL TO
CREATE OPENING FOR NEW
RATED DOOR ASSEMBLY,
SEE NEW WORK PLAN.
(VAE-1)
REMOVE AND RELOCATE
TO VAULT B
G R
E G
G
D
R I V
E
O
R
E
S
K
O
S
T
R
E
E
TL
G
S
O
U
H
C
E
N
T
R
R
E
E
T
DN
(E X
F
IR
S
T F
L R
A R
E A
W E
L L
E
N T
R Y
E
X I
P
A T
H W
A Y
QTY.
(2)
D001
NO.
MISCELLANEOUS
THICK.
FRAME INFORMATION
HEIGHTWIDTH MAT'LTYPE MAT'LTYPE RATING
3 HR
REMARKS
1 3/4"7'-0"3'-0" A METAL HMTYPE I
7'-0"
2"
2" 6'-0" 2"
HRDWR.
SET 1
DEPTH
5 3/4"
DOOR INFORMATION
HINGES
FLUSH BOLTS
DUST PROOF STRIKE
PASSAGE SET
COORDINATOR
ASTRAGAL
DOOR CLOSER
KICK PLATES
GASKETING
TA2714
ML2010
2600 SERIES
BY DOOR MANUF.
DC6210xA11
K1050F
S888 x HEAD & JAMBS
HARDWARE SET 1
32D
32D
26D
32D
32D
MK
RO
RO
CO
RO
CO
RO
PE
MANUFACTURERS:
CORBIN RUSSWIN
McKINNEY
PEMKO
ROCKWOOD
CO
MK
PE
RO
NOTE:
HARDWARE MANUFACTURER'S LISTED AS BASIS OF DESIGN.
ALTERNATE MANUFACTURERS ACCEPTABLE, SUBJECT TO
REVIEW BY ARCHITECT AND C.O.R .FOR EQUAL QUALITY
COMPLIANCE.
DOOR SET IN CONCRETE P.I.P. WALL
* DOOR AND FRAME TO BE GALVANIZED.
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
A-VAULT POWER DEMOLITION PLAN ENLARGEMENT
1/4" = 1'-0"
E-101
A-VAULT POWER PLAN ENLARGEMENT
1/4" = 1'-0"
A VAULT ELECTRICAL PLANS
BUILDING 1, A (LEVEL)
A-VAULT POWER PLAN ENLARGEMENT
1" = 50'-0"
DEMOLITION:
A. DEMOLITION WORK SHALL INCLUDE BUT NOT BE
LIMITED TO THE ELECTRICAL SYSTEMS, DEVICES
AND EQUIPMENT SHOWN ON THE DEMOLITION
PLAN. FIELD VERIFY EXISTING CONDITIONS.
COORDINATE THE DE-ENERGIZING OF FEEDERS
WITH COR AND VA FACILITIES.
B. FEEDERS ARE TO BE REMOVED TO A POINT
WHERE THEY EXIT THE SUBSTATION VAULT.
PROVIDE NEW JUNCTION BOX TO
REROUTE/EXTEND FEEDERS TO NEW
SWITCHGEAR LOCATION. ALL EXISTING AND NEW
JUNCTION BOXES AND CABLE TRAYS ARE TO BE
ACCESSIBLE AT ALL TIMES.
NEW WORK:
A. PROVIDE NEW RACEWAYS OR CABLE TRAY FOR
REROUTING OF FEEDERS. CABLE TRAY TO
MATCH EXISTING (24"W LADDER TYPE). SEE
SHEET E-600 THROUGH E-604 FOR RISER
DIAGRAMS. CONTRACTOR TO PROVIDE
CONDUCTOR FILL CALCULATIONS FOR NEW
CABLE TRAY ASSEMBLIES.
B. SEE SHEET E-001 FOR LIGHT FIXTURE
SCHEDULE.
1. EMERGENCY POWER FEEDER TO SUBSTATION
AE. SEE SHEET E-603
2. OVERHEAD TIE CONNECTION BETWEEN AN/AE
SUBSTATIONS.
3. EMERGENCY GENERATOR FEEDER TO DOCKING
STATION. SEE SHEET E-603.
4. GENERATOR DOCKING STATION FOR REMOTE
(TEMPORARY GENERATOR). TRYSTAR 303PCM
OR EQUAL. 3000 AMP 208/120V 3PG,4W RATED IN
NEMA 3R ENCLOSURE, PAD MOUNTED, CAM
LOCK CONNECTIONS .PROVIDE CONCRETE
BOLLARDS AS SHOWN, SEE CIVIL/SITE DETAILS.
5. UTILIZE EXISTING (3000A) BUS DUCT. PROVIDE
TAP/JUNCTION BOXES AT BOTH ENDS TO ALLOW
FOR CABLE TERMINATIONS/CONNECTIONS AS
SHOWN.
6. RELOCATED (GENERATOR CONTROLS)
BATTERIES AND CHARGER. PROVIDE FOR
TEMPORARY RELOCATION DURING
CONSTRUCTION UNTIL EXISTING SWITCHGEAR
BATTERIES ARE REMOVED. RETAIN AND REUSE
EXISTING CIRCUIT.
7. 1"C BETWEEN EXISTING GENERATOR CONTROL
CABINET AND NEW SUBSTATION AE BREAKER
CONTROLS AND MONITORING. EQUIPMENT
MANUFACTURER TO PROVIDE FOR
INTERCONNECTION AND AUTO START
CONTROLS/WIRING.
AE SWITCHGEAR CONTROLS:
SHALL PROVIDE FOR THE INTERCONNECTION OF
THE EXISTING GENERATOR CONTROLS WITH THE
SWITCHGEAR AUTO TRANSFER.
SWITCHGEAR SHALL AUTOMATICALLY DETECT LOSS
OF SOURCE,START THE GENERATOR AND RELATED
BREAKER CONTROLS.
SWITCHGEAR SHALL AUTOMATICALLY DETECT
RETURN OF SOURCE,RELATED BREAKER CONTROLS
TO RETURN TO NORMAL SOURCE, AND INITIATE COOL
DOWN CYCLE/GENREATOR SHUT DOWN.
8. NEW CABLE TRAY (24"W LADDER TYPE) TO
MATCH EXISTING. CONTRACTOR TO
COORDINATE MOUNTING/SUPPORT WITH
EXISTING CONDITIONS AND AVOID CONFLICT
WITH EXISTING RACEWAYS/CABLE TRAY NOT
BEING REMOVED. COORDINATE WITH CABLE
TRAY AND OTHER SERVICES FOR FEEDERS THAT
CAN NOT BE REMOVED OR RELOCATED UNTIL
AFTER THE ORIGINAL SUBSTATIONS ARE
REMOVED.
9. NEW JUNCTION BOXES (HIGH ON WALL) TO
TRANSITION BETWEEN REVISED/REROUTED
FEEDERS AT THE SUBSTATION AND EXISTING
FEEDERS OUTSIDE THE SUBSTATION AND
EXISTING FEEDERS OUTSIDE THE SUBSTATION
VAULT. COORDINATE WITH EXISTING
CONDITIONS, PROVIDE JUNCTION BOXES
SUITABLE FOR RELATED CABLING AND
SPECIFIED SPLICES/CABLE TERMINATIONS. SEE
SHEETS E600 THOUGH E-604.
10. NEW GROUND BUS TO REPLACE EXISTING
GROUNDING CABINET. SEE DETAIL SHEET E-501.
RETAIN AND/OR REPLACE EXISTING GROUNDING
CONNECTIONS AT THIS LOCATION EXISTING
GROUND BUS AT SUBSTATION VAULT TO REMAIN.
11. RELOCATED AREA LIGHT. REINSTALL AT REVISED
LOCATION, EXTEND/RETAIN EXISTING CIRCUIT.
12. NEW FIRE RATED DOOR ASSEMBLY. NEW
6'-0"X7'-0" PAIR RATED DOOR(WITH 2"FRAME ON
BOTH SIDES AND 4"HEAD)-SEE DOOR SCHEDULE
IN SPECIFICATION 087100.
13. PROVIDE NEW REMOTE STOP SWITCH FOR
GENERATOR. TIE TO EXISTING GENERATOR
CONTROLS. E STOP PUSHBUTTON, TAMPER
PROOF FLIP COVER. CALIBRATION
TECHNOLOGIES IN SB-ES1 OR EQUAL.
14. SEE DETAIL 8/E-501.
0 2' 4' 8'
0 2' 4' 8'
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
DOOR SCHEDULE
NTS
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
EXISTING (TO REMAIN)
800KW/1000KVA
DIESEL GEN SET
SUBSTATION BN
(TO BE REMOVED)
5KV LOAD
BREAK SW
200e (AF)
750KVA
4160/208Y-120V
3000A
208Y-120V 3PH,4W
SUBSTATION BE
(TO BE REMOVED)
3000A
208Y-120V 3PH,4W
5KV LOAD
BREAK SW
200e (AF)
1000KVA
4160/208Y-120V
(EX) SUMP/ELEC TO BE
REMAIN.
WP,GFI
SUB BN TO SUB BE
TIE SWITCH
TO BE REMOVED
PNL
VBE
F
(EX)
MDP-B
1200 /3 DISC
LDP-A
PNL VBN
GROUND BUS/CABINET
TO BE REMOVED. SEE
NEW WORK PLANS
GENERATOR
CONTROLS
(EX)
(BD)
(BD)
R
R
R
R
R
G
SS
CHGR
C H
G R
R
F F
R
R
(BD)
SS
R
R
R
(EX)
G GG
G
G
G
G
GG
R R
R R R
F
S
R
R
(EX)
GENERATOR
CONTROLS
EXPAND EXISTING WALL
OPENING, AND REMOVE
SLIDING DOOR ASSEMBLY
AT EXISTING AREAWAY, REMOVE
FENCING AT TOP OF RETAINING
WALL FOR THE PORTION OF
THE AREAWAY BEING MODIFIED.
SEE NEW WORK PLAN AND
DETAILS.
MODIFY EXISTING WALL TO
CREATE OPENING FOR NEW
RATED DOOR ASSEMBLY,
SEE NEW WORK PLAN.
EXISTING (TO REMAIN)
800KW/1000KVA
DIESEL GEN SET
NEW
SUBSTATION BN
NEW
SUBSTATION BE
NEW ROTARY DOCKING
STATION 3000AMP
AT GRADE LEVEL (ABOVE)
PROVIDE UNISTRUT
FRAMING/SUPPORT
3000NG
(EX)
MDP-B
3000A
208Y-120V
3PH,4W
1000KVA
4160/208Y-120V
GND BUS
5KV VACUM FAULT
INTERUPTER AT
TRANSFORMER
750KVA
4160/208Y-120V
3000A
208Y-120V 3PH,4W
AREA WELL OPENING (ABOVE) TO BE
COVERED AND MADE WEATHER PROOF.
SEE ARCHITECTURAL/STRUCTURAL
DETAILS
GENERATOR
CONTROLS
(EX)
SS
F
SS
PNL VBN
(EX)
GG
F
S
GG
G
G
G
G
PNL VBE/VBEA
R
R
F
R
G
R
EM
R
R
R
R
R
R
R
R
R
R
(BD)
R
(EX) SUMP/ELEC TO BE
REMAIN.
WP,GFI
J U
N C
T I O
N
B
O X
REVISE/MODFIY EXISTING
PAD UNDER SWITCHGEAR ASSENBLY
3000NG
CHGR
R
(EX)
(CT)
(CT)
(CT)
(CT)
(CT)
(CT)
(CT)
(CT)
(EX)
GENERATOR
CONTROLS
3000NG
3000NG
14 14
TERMINAL BOX AT TOP
OF TRANSFORMER
TANK - BUSHINGS
5KV VACUM FAULT
INTERUPTER AT
TRANSFORMER
B
M
2P
VBEA-5,7
REVISE/MODFIY EXISTING
15KV DISTRIBUTION TO
SUBSTATIONS
4" CONCRETE
PAD UNDER SWITCHGEAR
ASSEMBLY(PAINTED YELLOW)
EM
EM
EM
EM/NL
VBE-2
(VBE-2)
EM/NL
VBE-2
EM/NL
VBE-2
EM/NL
VBE-2
(VBE-2)
VBE-2
X
VBE-2
VBE-2
X1
X1
VBE-2
X1
NEW (RATED DOOR)
D001
O R
E S
R
E E
T
O
R
E
S
R
E
E
T
(E X
F
IR
S
T F
L R
A R
E A
W E
L L
(E N
T R
Y /E
X
IT
P A
T H
W A
Y
QTY.
(2)
D001
NO.
MISCELLANEOUS
THICK.
FRAME INFORMATION
HEIGHTWIDTH MAT'LTYPE MAT'LTYPE RATING
3 HR
REMARKS
1 3/4"7'-0"3'-0" A METAL HMTYPE I
7'-0"
2"
2" 6'-0" 2"
HRDWR.
SET 1
DEPTH
5 3/4"
DOOR INFORMATION
HINGES
FLUSH BOLTS
DUST PROOF STRIKE
PASSAGE SET
COORDINATOR
ASTRAGAL
DOOR CLOSER
KICK PLATES
GASKETING
TA2714
ML2010
2600 SERIES
BY DOOR MANUF.
DC6210xA11
K1050F
S888 x HEAD & JAMBS
HARDWARE SET 1
32D
32D
26D
32D
32D
MK
RO
RO
CO
RO
CO
RO
PE
MANUFACTURERS:
CORBIN RUSSWIN
McKINNEY
PEMKO
ROCKWOOD
CO
MK
PE
RO
NOTE:
HARDWARE MANUFACTURER'S LISTED AS BASIS OF DESIGN.
ALTERNATE MANUFACTURERS ACCEPTABLE, SUBJECT TO
REVIEW BY ARCHITECT AND C.O.R .FOR EQUAL QUALITY
COMPLIANCE.
DOOR SET IN CONCRETE P.I.P. WALL
* DOOR AND FRAME TO BE GALVANIZED.
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
B-VAULT POWER DEMOLITION PLAN ENLARGEMENT
1/4" = 1'-0"
E-102
B-VAULT POWER PLAN ENLARGEMENT
1/4" = 1'-0"
B VAULT ELECTRICAL PLANS
BUILDING 1, C (LEVEL)
0 2' 4' 8'
B-VAULT POWER PLAN ENLARGEMENT
1" = 50'-0"
1. EMERGENCY POWER FEEDER TO SUBSTATION
BE. SEE SHEET E-604
2. OVERHEAD TIE CONNECTION BETWEEN BN/BE
SUBSTATIONS.
3. EMERGENCY GENERATOR FEEDER TO DOCKING
STATION. SEE SHEET E-603.
4. GENERATOR DOCKING STATION FOR REMOTE
(TEMPORARY GENERATOR). TRYSTAR 303PCM
OR EQUAL. 3000 AMP 208/120V 3PG,4W RATED IN
NEMA 3R ENCLOSURE, PAD MOUNTED, CAM
LOCK CONNECTIONS .PROVIDE CONCRETE
BOLLARDS AS SHOWN, SEE CIVIL/SITE DETAILS.
5. UTILIZE EXISTING (3000A) BUS DUCT. PROVIDE
TAP/JUNCTION BOXES AT BOTH ENDS TO ALLOW
FOR CABLE TERMINATIONS/CONNECTIONS AS
SHOWN.
6. RELOCATED (GENERATOR CONTROLS)
BATTERIES AND CHARGER.
7. 1"C BETWEEN EXISTING GENERATOR CONTROL
CABINET AND NEW SUBSTATION AE BREAKER
CONTROLS AND MONITORING. EQUIPMENT
MANUFACTURER TO PROVIDE FOR
INTERCONNECTION AND AUTO START
CONTROLS/WIRING.
BE SWITCHGEAR CONTROLS:
SHALL PROVIDE FOR THE INTERCONNECTION OF
THE EXISTING GENERATOR CONTROLS WITH THE
SWITCHGEAR AUTO TRANSFER.
SWITCHGEAR SHALL AUTOMATICALLY DETECT LOSS
OF SOURCE,START THE GENERATOR AND RELATED
BREAKER CONTROLS.
8. SWITCHGEAR SHALL AUTOMATICALLY DETECT
RETURN OF SOURCE,RELATED BREAKER
CONTROLS TO RETURN TO NORMAL SOURCE,
AND INITIATE COOL DOWN CYCLE/GENREATOR
SHUT DOWN.
9. NEW CABLE TRAY (24"W LADDER TYPE) TO
MATCH EXISTING. CONTRACTOR TO
COORDINATE MOUNTING/SUPPORT WITH
EXISTING CONDITIONS AND AVOID CONFLICT
WITH EXISTING RACEWAYS/CABLE TRAY NOT
BEING REMOVED. COORDINATE WITH CABLE
TRAY AND OTHER SERVICES FOR FEEDERS THAT
CAN NOT BE REMOVED OR RELOCATED UNTIL
AFTER THE ORIGINAL SUBSTATIONS ARE
REMOVED.
10. NEW JUNCTION BOXES (HIGH ON WALL) TO
TRANSITION BETWEEN REVISED/REROUTED
FEEDERS AT THE SUBSTATION AND EXISTING
FEEDERS OUTSIDE THE SUBSTATION AND
EXISTING FEEDERS OUTSIDE THE SUBSTATION
VAULT. COORDINATE WITH EXISTING
CONDITIONS, PROVIDE JUNCTION BOXES
SUITABLE FOR RELATED CABLING AND
SPECIFIED SPLICES/CABLE TERMINATIONS. SEE
SHEETS E600 THOUGH E-604.
11. NEW GROUND BUS TO REPLACE EXISTING
GROUNDING CABINET. SEE DETAIL SHEET E-501.
RETAIN AND/OR REPLACE EXISTING GROUNDING
CONNECTIONS AT THIS LOCATION EXISTING
GROUND BUS AT SUBSTATION VAULT TO REMAIN.
12. RELOCATED AREA LIGHT. REINSTALL AT REVISED
LOCATION FIXTURE THAT WAS REMOVED FORM B
VAULT AREAWAY. EXTEND/RETAIN EXISTING
CIRCUIT.
13. NEW FIRE RATED DOOR ASSEMBLY. NEW
6'-0"X7'-0" PAIR RATED DOOR(WITH 2"FRAME ON
BOTH SIDES AND 4"HEAD)-SEE DOOR SCHEDULE
IN SPECIFICATION 087100.
14. FOR REVISION/EXTENSION OF FEEDER TO MDP-B
PROVIDE WIREWAY (6X6) EXTENSION AT SIDE OF
PANEL (TUB) FOR ROUTING CABLES. FIELD
COORDINATE INSTALLATION WITH EXISTING
CONDITIONS.
15. EXISTING JUNCTION BOXES FOR FEEDERS
EXITING THE SUBSTATION VAULT. RETAIN AND
REUSE JUNCTION BOXES. PROVIDE
SPLICE/CABLE TERMINATIONS AT THESE
LOCATIONS.
16. PROVIDE NEW REMOTE STOP SWITCH FOR
GENERATOR. TIE TO EXISTING GENERATOR
CONTROLS. E STOP PUSHBUTTON, TAMPER
PROOF FLIP COVER. CALIBRATION
TECHNOLOGIES IN SB-ES1 OR EQUAL.
17. SEE DETAIL 8/E-501.
0 2' 4' 8'
DEMOLITION:
A. DEMOLITION WORK SHALL INCLUDE BUT NOT BE
LIMITED TO THE ELECTRICAL SYSTEMS, DEVICES
AND EQUIPMENT SHOWN ON THE DEMOLITION
PLAN. FIELD VERIFY EXISTING CONDITIONS.
COORDINATE THE DE-ENERGIZING OF FEEDERS
WITH COR AND VA FACILITIES.
B. FEEDERS ARE TO BE REMOVED TO A POINT
WHERE THEY EXIT THE SUBSTATION VAULT.
PROVIDE NEW JUNCTION BOX TO
REROUTE/EXTEND FEEDERS TO NEW
SWITCHGEAR LOCATION. ALL EXISTING AND NEW
JUNCTION BOXES AND CABLE TRAYS ARE TO BE
ACCESSIBLE AT ALL TIMES.
NEW WORK:
A. PROVIDE NEW RACEWAYS OR CABLE TRAY FOR
REROUTING OF FEEDERS. CABLE TRAY TO
MATCH EXISTING (24"W LADDER TYPE). SEE
SHEET E-600 THROUGH E-604 FOR RISER
DIAGRAMS. CONTRACTOR TO PROVIDE
CONDUCTOR FILL CALCULATIONS FOR NEW
CABLE TRAY ASSEMBLIES.
B. SEE SHEET E-001 FOR LIGHT FIXTURE
SCHEDULE.
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
DOOR SCHEDULE
NTS
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
(EX)
PANEL
'LPC-9'
(EX)
PANEL
'PP-7-1'
(EX)
PANEL
'PP-8-1'
(EX)
PANEL
'PP-7-2'
(EX)
PANEL
'PP-8-2'
(EX)
GROUND
BUS
(EX)
PANEL 'SWB-D'
(EX)
SUBSTATION
'CN-2'
(EX)
PANEL 'VCE'
(EX)
GROUND
BUS
(EX)
SUBSTATION
'CE'
(EX)
CABLE TAP
BOX 119" AFF
(EX) (3) 3-1/2"C
GENERATOR
121" AFF
(EX) AREA
WELL
(UP) TO LEVEL 1
(SEE PARTIAL PLAN THIS
SHEET)
(EX)
ACCESS LADDER
(3) 3-1/2" C
(3) 3-1/2" C
JA
C
O B
C
IR
C
LE
G R
E G
G
D
R I V
E
O R
E S
R
E E
T
CN-2
3A
TO C-VAULT
F
IR
S T
F L R
A R
E A
W E
L L
M A
N H
O L E
T
Y P
E
X
V
D
S
T B
V
I F
(E X
) 5 K
V D
IS
T
B , (V
IF
E
X
S
T
B
V
I F
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
C-VAULT POWER PLAN ENLARGEMENT
1/4" = 1'-0"
E-103
C-VAULT POWER PLAN ENLARGEMENT
1" = 50'-0"
C VAULT ELECTRICAL PLANS
1. ADD EXTENSION (BOX) TO EXISTING PULL BOX
FOR REROUTING/EXTENSION OF FEEDERS.
COORDINATE WITH FIELD CONDITIONS.
2. EXISTING GENERATOR FEEDER TO SUBSTATION
CE IS TO BE REVISED AND REROUTED TO
REMOTE TEMPORARY GENERATOR DOCKING
STATION. VERIFY IN FIELD (3) 3-1/2"C 4-600 MCM
EACH.
3. NEW EMERGENCY FEEDER TO SUBSTATION CE
ROUTED WITH EXISTING RACEWAYS.
TERMINATIONS/SPLICES TO BE MADE AT
EXISTING/MODIFIED TOP BOX. SEE SHEET E-605.
4. EMERGENCY FEEDER TO SUBSTATION CE FROM
REMOTE DOCKING STATION. SEE SHEET E-605.
5. EMERGENCY FEEDER RACEWAYS ROUTED UP
AREA WAY TO LEVEL A AND LOCATION OF NEW
TEMPORARY GENERATOR DOCKING STATION.
6. GENERATOR DOCKING STATION FOR REMOTE
TEMPORARY GENERATOR. TRYSTAR 303 PCM OR
EQUAL, 1200 AMP 208/120V 3PH 4W RATED WITH
NEMA 3R ENCLOSURE. PAD MOUNTED WITH
CAMLOCK CONNECTIONS. PROVIDE REQUIRED
UNISTRUT SUPPORT AND/OR ACCESSORIES FOR
INSTALLATION.
0 2' 4' 8'
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
PANEL
PP9
PANEL
EMP-CB
RM C112
RM C-E-108
FED FROM
SUBSTATION BE
BKR 14
FED FROM
LCP-E6 BKR 5
PNL
EMP-BC
RM B-E-107
ELECTRICAL
CLOSET
FED FROM
LCP-E6
BKR 2
PNL EMP-AD
A-E-102
ELECTRICAL
CLOSET
FED FROM
LCP-E3-2
(B-E-103)
PNL
EMP-AC
AE-238
ELECTRICAL
CLOSET
FED FROM
LCP-E3-1
(B-E-103)
AREA OF WORK
KEY PLAN - BUILDING 1
N
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
BUILDING 1 - C-LEVEL RM C-E-108 & C-112 PARTIAL ELECTRICAL PLANS
3/8" = 1'-0"
E-111
BUILDING 1 PARTIAL PLANS
ELECTRICAL
00 2' 4' 8'0
BUILDING - 1 A-LEVEL RM A-E-102 PARTIAL ELECTRICAL PLAN
3/8" = 1'-0"
BUILDING 1 - B-LEVEL RM B-E-107 PARTIAL ELECTRICAL PLAN
3/8" = 1'-0"
BUILDING 1 - A-LEVEL RM AE-238 PARTIAL ELECTRICAL PLAN
3/8" = 1'-0"
A. LIGHTER LINE WEIGHT INDICATES EXISTING TO
REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT
INDICATES NEW WORK.
B. FIELD VERIFY FEEDERS TO PANELS DESIGNATED
FOR REPLACEMENT. COORDINATE OUTAGES
WITH COR.
1. REMOVE AND REPLACE PANEL PP9 AT EXISTING
LOCATION. SEE PANEL SCHEDULE SHEET E-401.
2. REMOVE AND REPLACE PANEL EMP-CB. PROVIDE
NEW INTERIOR AND BREAKERS IN EXISTING TUB.
SEE PANEL SCHEDULE SHEET E-401.
3. REMOVE AND REPLACE PANEL EMP-BC AT
EXISTING LOCATION. SEE PANEL SCHEDULE
SHEET E-401.
4. REMOVE AND REPLACE PANEL EMP-AD AT
EXISTING LOCATION. SEE PANEL SCHEDULE
SHEET E-401.
5. REMOVE AND REPLACE PANEL EMP-AC AT
EXISTING LOCATION. SEE PANEL SCHEDULE
SHEET E-401.
LEVEL C
RM C-E-108
LEVEL C
RM C-112
LEVEL B
RM B-E-107
LEVEL A
RM A-E-102
LEVEL A
RM AE-238
00 2' 4' 8'000 2' 4' 8'0
00 2' 4' 8'0
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
2-231
2-230
OFFICE
2-230A 2-230A
PANEL
2A
TO
PANEL
MDP
VERIFY EXISTING
FEEDER.
AREA OF WORK
KEY PLAN - BUILDING 2
N
(EX)
(3) #6 IN 2"C
(EX)
(4) #4 IN 1.25"C
(EX)
(3) #3 IN 1.25"C
(EX)
(4) #3/0 IN 3"C
(EX)
(4) #3/0 IN 2"C
(EX) (3) #1/0 IN 2"C
(EX) (3) #4
IN 2.5"C
B-104
B-104
B-104
RM 1-200
RM 2-200
PANEL
1A
PANEL
PP1
PANEL
PP-2
PANEL
MDP
PANEL
A
PANEL
PP3
PANEL
AC-1
PANEL
AC-2
PANEL
2A
(EX)
PANEL
3A
(EX)
ELEV.
175A
B-104
NO
MCB
EB
EB3
EXISTING FEEDER
TO EXISTING ELEC. WATER
HEATER
(EX) 2 SETS OF: (4)#500KCM IN (2)
4"C TO BUILDING #1 SUBSTATION
AN, BREAKER #14
GROUND FLOOR (BASEMENT)
1ST FLOOR
2ND FLOOR
3RD FLOOR
MECHANICAL PENTHOUSE
ROOF
2ND
FLOOR HALL
EXISTING FEEDER
(EX) (EX)
(EX)(EX)
(EX) (EX) (EX) (EX) (EX)
(EX)
PANEL
1A
TO
PANEL
MDP
VERIFY EXISTING
FEEDER.
PANEL
3A
(EX)
FEEDER/RISER
FROM PANEL 2A
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
BUILDING 2 - FLOOR 2 PARTIAL ELECTRICAL PLAN
1/4" = 1'-0"
E-121
BUILDING 2 PARTIAL PLANS
ELECTRICAL
BUILDING 2 - RISER DIAGRAM
N.T.S.
BUILDING 2 - FLOOR 1 PARTIAL ELECTRICAL PLAN
1/4" = 1'-0"
BUILDING 2 - FLOOR 1 PARTIAL ELECTRICAL PLAN
1/4" = 1'-0"
REPLACE EXISTING PANEL 1A WITH NEW PANEL
INTERIOR AND BREAKERS. SEE PANEL
SCHEDULE SHEET E-401. RETAIN AND REUSE
EXISTING PANEL TUB AND COVER. COORDINATE
SHUTDOWN AND REPLACEMENT WITH COR.
REPLACE EXISTING PANEL 2A WITH NEW PANEL
INTERIOR AND BREAKERS. SEE PANEL
SCHEDULE SHEET E-401. RETAIN AND REUSE
EXISTING PANEL TUB. FEEDER/RISER SERVICES
PANELS 2A/3A. COORDINATE SHUTDOWN AND
REPLACEMENT WITH COR.
REPLACE EXISTING PANEL 3A WITH NEW PANEL
INTERIOR AND BREAKERS. SEE PANEL
SCHEDULE SHEET E-401. RETAIN AND REUSE
EXISTING PANEL TUB. PANEL IS FED FROM
RISER AT PANEL 2A. COORDINATE SHUTDOWN
AND REPLACEMENT WITH COR.
1.
2.
3.
0 2' 4' 8'
0 2' 4' 8'0 2' 4' 8'
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
AREA OF WORK
KEY PLAN - BUILDING 5
N
BASEMENT
SECOND FLOOR
5-2-108
OFFICE
CONFERENCE
ROOM
CHIEF
SUPPLY
5-2-106A
STAIRWAY
5-2-106B
CLOSET
5-2-105C
ELEV.1
FISCAL
CONFERENCE
ROOM
TELEPHONE
CLOSET
5-2-101
STAIRWAY
OFFICE
5-2-100
CORRIDOR
ELEVATOR
LOBBY
MENS
TOILET
OFFICE
5-2-105A
SUPPLY SERVICE
5-2-107 5-2-106
5-2-105
5-2-105B
5-2-102A
5-2-102
5-2-103
5-2-104
5-2-103A
EX
72"
EX
72"
EX
40"
EX
72"
EX
72"
EX
72"
EX
72"
EX
72"
EX
72"
72"72"
EX
72"
NEW PANEL 5A2
FED FROM PP5
SEE RISER
SHEET E-152
72"
72"72"
5A2-13
5A2-15
(3) 3 AWG
(1) 3 AWG N
(1) 8 AWG EG
1-1/4" C
(ROUTED ABOVE
EXISTING CEILING)
5A2-115A2-9
5A2-75A2-55A2-35A2-1
5A2-145A2-125A2-105A2-85A2-65A2-45A2-2
S
SSS
S S
S
S
S
S
S
SS
5-1-114
OFFICE
5-1-113
OFFICE
5-1-111
OFFICE
WOMENS
TOILET
OFFICE
A
C L O S E T
5-1-106A
HALLWAY
MENS
TOILET
ROOM
OFFICE
5-1-109
FISCAL
VBRI
OFFICE
5-1-107
CLOSET
ELEVATOR
LOBBY
5-1-100B
ELEV 1
ROOM
5-1-100C
STAIRWAY
5-1-100
HALLWAY
5-1-115
SUPERVISOR
5-1-109B
HALLWAY
5-1-109C
STAIRWAY
5-1-110A
STAIRWELL
5-1-106
5-1-105
5-1-100A
COPY
5-1-112
5-1-112A
MECHANICAL
5-1-108
TRAVEL
5-1-102
5-1-101A
VBRI
OFFICE
5-1-101B
VBRI
OFFICE
5-1-101C
VBRI
OFFICE
5-1-101D
EX
72"
5A2-21
S
EX
72"
5A2-19
S
EX
72"
S
EX
72"
S
EX
72"
5A2-24
S
EX
60"
5A2-18
S
EX
5A2-17
EX
72"
5A2-28
S
EX
72"
S
5A2-30
EX
72"
S
5A2-31
EX
72"
5A2-27
S
EX
72"
S
EX
72"
S
5A2-23 5A2-25
EX
72"
5A2-29
S
EX
72"
S
5A2-16
5A2-20
5A2-22
EX
72"
S
5A2-26
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
E-151
BUILDING 5 PARTIAL PLANS
BUILDING 5 - FLOOR 2 PARTIAL PLAN
1/4" = 1'-0"
1. EXISTING SERVICE ENTRANCE WIREWAY AND
DISCONNECTS TO REMAIN.
2. AT EXISTING PANEL 5, PROVIDE NEW 60A-3ɸ
BREAKER TO EXISTING SPACE. (SQUARE D NQOD)
3. ROUTE NEW RACEWAY (UP) AT EXTERIOR OF THE
BUILDING TO SECOND FLOOR.
4. FEEDER TO NEW PANEL (5A2) UP AND ACROSS
THE SECOND FLOOR ACCESSIBLE CEILING.
5. PROVIDE NEW WALL TO CONTAIN PANEL (5A2).
WALL TO BE THE SAME LENGTH AS EXISTING
CLOSET WALL. CONSTRUCT WALL OF 6" 24 GAUGE
STEEL STUDS AND 5/8" GYPSUM BOARD
EXTENDING 6" ABOVE THE CEILING. PANEL FACE
TO BE FLUSH WITH WALL SURFACE. PAINT WALL
WALL AND PANEL COVER TO MATCH EXISTING
ADJACENT WALL SURFACES. PROVIDE NEW BASE
MATCHING EXISTING, AND MODIFY CEILING GRID
AND TILES AS REQUIRED TO CLOSE WITH NEW
WALL SURFACE.
A. ALL EXTERIOR WALL PENETRATIONS TO BE
SEALED WITH (VA EAST ORANGE FACILITIES)
APPROVED WEATHER PROTECTIVE MATERIALS.
B. LIGHTER LINE WEIGHT INDICATES EXISTING TO
REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT
INDICATES NEW WORK.
0 2' 4' 8'
BUILDING 5 - FLOOR 1 PARTIAL PLAN
1/4" = 1'-0"
0 2' 4' 8'
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
MECHANICAL
ROOM
IRM
CLOSET
5-B-100
CORRIDOR
5-B-103
5-B-103A
FILE
STORAGE
5-B-102
TO
TUNNEL
EX
PP5
EX
LP1
EX
PP4
EX
LP2
1-1/4"C
(3) 3 AWG
(1) 3 AWG N
(1) 8 AWG EG
AREA OF WORK
KEY PLAN - BUILDING 5
N
BASEMENT
SECOND FLOOR
M
EX
JB
EXISTING
PAD MOUNTED
TRANSFORMER
B-103 B-103
B-103 B-103
B-103
EX
PNL 4
FL1&2
EX
PANEL
EX
PANEL
EX
PNL 5
FL1
EX
ECB
175A
100A
B-103
B-103
EX
E-MON
D-MON
KWH
B-103
EX
NSS
TO 5KV
SWITCH
EXISTING
EXISTING
NEW
PNL 5A2
A/C
FL2
RM 5-2-102
(3) 3 AWG
(1) 3 AWG N
(1) 8 AWG EG
1-1/4" C
AT PNL 5, ADD (1)
100A -3P BREAKER TO
FEED PNL 5A2. MATCH
EXISTING (SQ D NQOD)
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
BUILDING 5 - BASEMENT PARTIAL PLAN
1/4" = 1'-0"
E-152
BUILDING 5 PARTIAL PLANS
ELECTRICAL AND DIAGRAMS
BUILDING 5 - RISER DIAGRAM
N.T.S.
TO TRANSFORMER
1. EXISTING SERVICE ENTRANCE WIREWAY AND
DISCONNECTS TO REMAIN.
2. AT EXISTING PANEL 5, PROVIDE NEW 60A-3ɸ
BREAKER TO EXISTING SPACE. (SQUARE D
NQOD)
3. ROUTE NEW RACEWAY (UP) AT EXTERIOR OF
THE BUILDING TO SECOND FLOOR.
0 2' 4' 8'
A. ALL EXTERIOR WALL PENETRATIONS TO BE
SEALED WITH (VA EAST ORANGE FACILITIES)
APPROVED WEATHER PROTECTIVE MATERIALS.
B. LIGHTER LINE WEIGHT INDICATES EXISTING TO
REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT
INDICATES NEW WORK.
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
NEW DOUBLE
TUB PNL 7A
PANEL
7A
PANEL
7B
PANEL
7C
FED FROM
EDP-A (1-127)
SEE RISER DIAGRAM
THIS SHEET
AREA OF WORK
KEY PLAN - BUILDING 7
N
1 CB
P7A
P7B P9
P7C
400A
3P
350A
3P
400A
3P
300A
3P
300A
3P
175A
3P
200A
3P
100A
3P
125A
3P
300A
3P
(8) #250
IN 4" C
(4) #500
IN 4" C
(4) #250
IN 4" C
(4) #500
IN 4" C
(4) #1/0
IN 2" C
(4) #3/0
IN 2" C
(4) #2
IN 1.5" C
(4) #2
IN 1.5" C
(4) #2
IN 1.5" C
EMERGENCY DISTRIBUTION EDP-A 1600A
BUS, 65000 AIC (40.22Kaic )
208Y/120V, 3ɸ, 4W
(EX)
EDP-A
PP 6 DP-B SUMP
PUMP
PP 4 PP 13 PB39A B-133 PP 8
B-143
B-159
B-158B
B-158B
B-158B
MCC1 / MCC1A
TO
MCCE7A
TO
EDP/ATS1
(4) #600 KCM
(1) #1 GND
IN 4" C
P7A
2-1/2" C
(3) 250 MCM
(1) 250 MCM N
(1) 4 AWG EG
(VIF) 4-250 MCM
2-1/2" C
(EX)
(EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX) (EX)
SEE PANEL
SCHEDULE
SHEET E-401
PNL 1 CB
200AMCB
NEMA 3R
B-144A
2-1/2" C
(3) 250 MCM
(1) 250 MCM N
(1) 4 AWG EG
PANEL
1CB
FED FROM
EDP-A (1-127)
(2) 2"C
BRANCH CIRCUITS
4" C
4-250 MCM
FEEDER TO
PNL ICB
(NEW)
PANEL ICB
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
SHEET NOTES:
SHEET KEY NOTES:
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
E-171
BUILDING 7 PARTIAL PLANS
ELECTRICAL
BUILDING 7 - BASEMENT PARTIAL PLAN - (B-143) ELECTRICAL
1/16" = 1'-0"
BUILDING 7 - RISER DIAGRAM
1/4" = 1'-0"
BUILDING 7 - BASEMENT PARTIAL PLAN - (B-143) ELECTRICAL
1/16" = 1'-0"
1. RELOCATE EXISTING PANEL 7 (A,B,C) FEEDER TO
PANEL 7A LOCATION. RETAIN AND REUSE PANEL
TUB AS JUNCTION BOX. SECURE COVER AT
PANEL AND LABEL AS JUNCTION BOX.
2. EXISTING BRANCH CIRCUITS AT PANELS 7A, 7B,
7C TO BE RELOCATED /EXTENDED TO NEW
PANEL 7A. RELOCATE FEEDER TO PANEL P9 TO
P7A WITH BRANCH CIRCUITS. RETAIN AND REUSE
PANEL TUBS AS JUNCTION BOX. SECURE
COVERS AT OLD PANELS AND LABEL AS
JUNCTION BOXES. SEE PANEL SCHEDULES ON
SHEET E-401.
3. EXISTING PANEL ICB TO BE REMOVED. RETAIN
WIREWAY ADJACENT TO PANEL FOR ROUTING OF
NEW FEEDER AND BRANCH CIRCUITS. SEAL ANY
UNUSED OPENINGS AT WIREWAY UPON
REMOVAL OF PANEL.
4. NEW PANEL ICB. EXTEND EXISTING FEEDER AND
BRANCH CIRCUITS TO NEW PANEL LOCATION.
SEE RISER DIAGRAM THIS SHEET. NEMA 3R
ENCLOSURE WITH RAIN TIGHT (MEYERS HUBS)
AT RACEWAY PENETRATIONS.
A. LIGHTER LINE WEIGHT INDICATES EXISTING TO
REMAIN, VERIFY IN FIELD. HEAVIER LINE WEIGHT
INDICATES NEW WORK.
0 2' 4' 8'
0 2' 4' 8'
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
E-401
ELECTRICAL PANEL SCHEDULES
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
Suite C
Auburn, AL 36830 o | 334.887.6064 f | 334.887.6024 w | www.fg-inc.net
02/05/2020
E-402
ELECTRICAL PANEL SCHEDULES
SAFETY REVIEW RESUBMISSION 11/20/19REV 1
N
R
A
N
046636
E
E N
I
G
H
K
I
A
W
O
N
A
T
R
F
SEAL
R
P
O
O
I
SS
O E
H
RC
A
I
L
A
N
L
E
N
C
I
M
H
E
A
L
S
SHORE EXISTING 2-HR RATED CMU
MASONRY WALL ABOVE OPENING PRIOR
TO REMOVING WALL AND INSTALLING
LINTEL - SEE STRUCTURAL
L5 X 3-1/2 X 5/16 (LLV),
BEAR 6" MINIMUM EACH END
MAX SPAN = 8'-0"
PAINT TO MATCH BLOCK WALL COLOR
H.M. DOOR FRAME,
4" AT HEAD
1/2"
EXISTING WALL TO REMAIN
OPEN VAULT
PAINTED COMMERCIAL 24 GA. METAL ROOF
PANEL SYSTEM W/ GUTTER AND DOWNSPOUT
PAINTED ARCHITECTURAL DRAINABLE
FIXED LOUVER SYSTEM W/ CONTINUOUS
PAN TO SIT ON CONCRETE WALL. EQUAL SPACING
PER ELEVATION. MAX. WIDTH PER PANEL - 48".
TYPICAL ALL ELEVATIONS
SILL FLASHING END DAM AT
EXISTING BUILDING WALL
CONTINUOUS ALUM. SILL FLASHING
AT BASE BY LOUVER VENDOR
METAL FLASHING, 24 GA. MIN
CUT IN REGLET, METAL
COUNTER FLASHING - 4"H,
AND SEALANT
CLOSURE STRIPS
COLD FORM JOISTS, BOXED BEAM AT ENDS
SEE STRUCTURAL
1'-0"
BREAK METAL TO MATCH
LOUVER SYSTEM
2'-11
8"
6"
2x4 METAL TUBES TO MATCH
LOUVER FINISHTO PROVIDE LATERAL
SUPPORTFOR LOUVER PANELS,
SECURE TO EX. WALL
AND COLD FORM BEAM
1'-10"
TOP OF STEEL COL.
2'-0"
TOP OF STL. ANGLE
0'-0"
TOP OF WALL
11'-0"
OPEN VAULT
PAINTED COMMERCIAL 24 GA. METAL ROOF
PANEL SYSTEM W/ GUTTER
PAINTED ARCHITECTURAL
DRAINABLE FIXED LOUVER,
TYPICAL,
SEE SPECIFICATION
CONTINUOUS SILL FLASHING
AT BASE BY LOUVER
VENDOR
TYPICAL ALL 4 SIDES
BREAK METAL END CAP
METAL DECKING ON
COLD FORM JOISTS
SEE STRUCT.
BREAK METAL TO MATCH
LOUVER SYSTEM
2x4 METALTUBES TO MATCH
LOUVER FINISHTO PROVIDE LATERAL
SUPPORTFOR LOUVER PANELS,
SECURE TO EX. WALL
AND ROOF STRUCTURE
1/2"
EXISTING MEMBRANE ROOF
NEW TERMINATION BAR UNDER
NEW CONT. SILL FLASHING
0'-0"
TOP OF WALL
4'-9 3/4"
TOP OF STEEL COL.
4'-7"
TOP OF STEEL COL.
STEEL BEAM
SEE STRUCTURAL
BREAK METAL GUTTER AND
DOWNSPOUT TO CONC.
SPLASH BLOCK ON LOWER
EXISTING ROOF.
EXISTING CONC. WALK
EXISTING CONC. WALL
TYP.
GENERAL NOTE:
BLANK OF I NTERIOR OF ALL LOUVERS
NOT BEING UTILIZED BY MECHANICAL
FOR VENTING. SEE MECH. DWGS.
EXISTING CONC. WALL
LOUVER
12" DEEP PLENUM FULL SIZE OF LOUVER
SECTION WITH BOTTOM SEALED 2" DEEP
MOTORIZED BACKDRAFT
DAMPER
WALL HOUSING
EXHAUST FAN
SCREENED INLET
3/4" DRAIN WITH INDIRECT WASTE TO SUMP OR
FLOOR DRAIN
1-1/2" FOIL FACED DUCT WRAP FIBERGLAS
INSULATION, TYP.
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of
Construction and Facilities
Management
PROJECT MANAGER:
ACG Project Number
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120
Cary, North Carolina 27511 www.acg-pa.com 919-858-7420
NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
IMPROVE ELECTRICAL
DEFICIENCIES, II A & B
561-18-135
VA NJ HEALTH CARE SYSTEM
385 TREMONT AVENUE
EAST ORANGE, NJ 07018
X
18-096
ISSUED FOR CONSTRUCTION
FULLY SPRINKLERED
1, 2, 5, 7
Foresite Group, Inc.
2128 Moores Mill Rd.
This is the start of the file's text. The full file is on GovTribe.