December 18, 2017

Mr. Leighton Smith U.S. Department of Veteran Affairs VA New Jersey Health Care System Safety/FMS (138) / Building 10 151 Knollcroft Road Lyons, New Jersey 07939

Re: Caulk bulk sampling, PLM / TEM sample analysis & final report at Building 135, VA Lyons, 151 Knollcroft Road, Lyons, New Jersey - Roof.

Dear Mr. Smith:

At your request, Briggs Associates collected bulk samples of building caulk from the exterior of Building 135 located on the VA Lyons campus at 151 Knollcroft Road, Lyons, New Jersey.

These samples were submitted to an accredited laboratory for asbestiform analysis. Testing activities were conducted in conjunction with ongoing building addition construction activities and the primary focus of the testing effort was the north side roof. Work was completed by EPA AHERA asbestos inspector (#ACC-0317-6-002) Douglas Ferry on December 7, 2017.

1.0 Purpose

The purpose of the asbestos inspection was to meet the requirements of the New Jersey Department of Health and Senior Services, New Jersey Department of Labor, New Jersey Department of Environmental Protection and the United States Environmental Protection Agency (U.S. EPA) National Emissions Standards for Hazardous Air Pollutants (NESHAP) regulation (Title 40 Code of Federal Regulations [CFRJ Part 61 Subpart M). The purpose of the state regulations and the NESHAP asbestos regulation is to protect human health and the environment by minimizing the release of asbestos when facilities that contain asbestos containing materials are renovated or demolished.

2.0 Methodology

Accessible building materials were inspected and assessed using the methods presented in the federal AHERA regulations (40 CFR, Part 763) as a guideline. The procedures mandated are considered the industry standard and are applied to all surveys performed by Briggs Associates. Multiple bulk samples of all homogeneous materials containing suspect ACM were collected in accordance with the numercial guidelines detailed in AHERA. A homogeneous material is defined as a surfacing material, thermal system insulation, or miscellaneous material that is uniform in use, color and texture. Suspect asbestos materials identified include the following:

• roof parapet caulk (gray and tan)

• skylight caulk (white)

• brick caulk (mauve, black and brown)

Asbestos Containing Materials Bulk Sampling Report Page 2 VA Lyons, Bldg. 135 Roof, 151 Knollcroft Road, Lyons, NJ

Bulk samples of suspect materials were collected, placed into individual polyethylene sampling bags and labeled for transport under chain of custody procedures to the laboratory. A field sampling log was filled out (depicting sample number, description of the material, location, condition, accessibility, friability and quantity), and a unique sample number was assigned to each sample. Bulk samples were transported to and analyzed at IATL laboratory in Mt. Laurel, New Jersey. IATL is accredited under the National Institute of Standards and Technology's National Voluntary Laboratory Accreditation Program (NVLAP) (Lab #101165-0).

All samples were analyzed using Polarized Light Microscopy/Dispersion Staining (PLM/DS) techniques in accordance with methodology approved by the U.S. EPA, method number 600/R-93/116 July 1993. The percentage of asbestos present in the samples was determined on the basis of a visual area estimation as set forth in 40 CFR Part 763, Appendix A, Subpart F, Section 1.2 and 1.7.2.4. The lower limit of reliable detection for asbestos using the PLM/DS method is approximately 1% by volume.

The EPA and the Occupational Safety and Health Administration (OSHA) have determined that asbestiform fibers observed within a homogeneous sample must be greater than 1% of total weight to be considered an asbestos containing material (ACM).

The EPA method for bulk sample analysis allows that samples which are visually determined to have 10% or less asbestos to be quantified using a Point Count procedure. Point count analysis using the semi-quantitative point count method of 400 points can more precisely determine the actual asbestos content on materials containing less than 10% asbestos. The laboratory was instructed to utilize the Point Count procedure where warranted.

However, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB’s) samples (i.e., floor tiles, mastics, roofing samples, caulks). Small fiber size and fibers which are frequently tightly bound within the matrix of a NOB obscures detection via PLM.

Therefore, in accordance with current New Jersey Departments of Labor and Health and Human Services requirements, non-friable organically bound (NOB’s) samples (i.e., floor tiles, mastics, roofing samples, caulks) that were identified as <1% asbestos by the PLM method were additionally prepared by gravimetric reduction and analyzed by the more precise Transmission Electron Microscopy (TEM) analysis.

3.0 Results

A total of seventeen (17) samples from six (6) homogeneous materials were submitted for analysis. The following results were identified:

i. all parapet (gray, tan) and skylight (white) caulk samples, collected from the various roof sections, yielded results of ‘None Detected’ or <0.1% chrysotile asbestos

ii. the mauve brick caulk sample, collected from the ground level SE side, yielded a result of ‘None Detected’

iii. the brown and black brick caulk samples, collected from the ground level SE front and rear section of the building, were determined to be ACM with results of 1.2%-13.7% chrysotile asbestos

Asbestos Containing Materials Bulk Sampling Report Page 3 VA Lyons, Bldg. 135 Roof, 151 Knollcroft Road, Lyons, NJ

4.0 Discussion

The rooftop parapet and skylight caulks were found to be Non-ACM by laboratory analysis. The brown brick caulk, located at vertical expansion joints around the exterior face of the building and the black brick caulk, located at the base of the building in various areas, were found to be ACMs by laboratory analysis.

Briggs Associates recommends that prior to any demolition activities all asbestos-containing caulks impacted by the scheduled work be removed and disposed of by a licensed asbestos abatement contractor using proper engineering controls and worker protection. Briggs Associates further recommends the use of a qualified environmental consulting firm to assist in the design of abatement strategies, cost effective remediation, and to perform observation during abatement activities and conduct area air monitoring during abatement activities.

Thank you for utilizing our industrial hygiene services. If you should have any questions please feel free to contact me at 609/298-5520.

Sincerely, Douglas Ferry Asbestos Building Inspector EPA Cert #ACC-0316-6-027

DF/

Notes

FRI - friable NAD - No asbestos detected NFI - nonfriable category 1 1 – analysis by PLM Trace - <1% asbestos 2 – analysis by TEM gravimetric reduction analysis

BRIGGS ASSOCIATES

ASBESTOS BULK SAMPLING SUMMARY

Name of Inspector: Douglas Ferry (AHERA # ACC-0317-6-002) Date: 12/18/17 Property Name: Veterans Administration - Building 135 Roof Project No.: 100-VA_Lyons-07 Property Address: 151 Knollcroft Road, Lyons, New Jersey Page: 1 of 1

Material Description HSA No. Functional Space Friability Condition Sample # Results POS /NEG

Parapet caulk - gray 01 Roof – by loading dock, north NF1 Fair 120717 B01 NAD1,2 NEG

Parapet caulk - gray 01 Roof – by loading dock, west NF1 Fair 120717 B02 NAD1,2 NEG

Parapet caulk - gray 01 Roof – middle of support bldg NF1 Fair 120717 B03 NAD1,2 NEG

Parapet caulk - gray 01 Roof – support unit, east NF1 Fair 120717 B04 NAD1,2 NEG

Parapet caulk - gray 01 Roof – support unit, east NF1 Fair 120717 B05 Trace Actinolite2 NEG

Skylight caulk - white 02 Roof – support unit NF1 Fair 120717 B06 Trace Actinolite2 NEG

Skylight caulk - white 02 Roof – support unit NF1 Fair 120717 B07 NAD1,2 NEG

Parapet caulk - tan 03 Roof – west wing NF1 Fair 120717 B08 NAD1,2 NEG

Parapet caulk - gray 01 Roof – west wing NF1 Fair 120717 B09 NAD1,2 NEG

Parapet caulk - gray 01 Roof – east wing NF1 Fair 120717 B10 NAD1,2 NEG

Parapet caulk - gray 01 Roof – east wing NF1 Fair 120717 B11 NAD1,2 NEG

Parapet caulk - gray 01 Roof – east wing NF1 Fair 120717 B12 NAD1,2 NEG

Brick caulk - black 04 Ground level – east wing, front NF1 Fair 120717 B13 1.8% Chrysotile1 POS

Brick caulk - black 04 Ground level – base of west wing NF1 Fair 120717 B14 2.1% Chrysotile2 POS

Notes

FRI - friable NAD - No asbestos detected NFI - nonfriable category 1 1 – analysis by PLM Trace - <1% asbestos 2 – analysis by TEM gravimetric reduction analysis

BRIGGS ASSOCIATES

ASBESTOS BULK SAMPLING SUMMARY

Name of Inspector: Douglas Ferry (AHERA # ACC-0317-6-002) Date: 12/18/17 Property Name: Veterans Administration - Building 135 Roof Project No.: 100-VA_Lyons-07 Property Address: 151 Knollcroft Road, Lyons, New Jersey Page: 2 of 2

Material Description HSA No. Functional Space Friability Condition Sample # Results POS /NEG

Brick caulk - mauve 05 Ground level – SE east wing NF1 Fair 120717 B15 NAD1,2 NEG

Brick caulk - brown 06 Ground level – south rear NF1 Fair 120717 B16 13.7% Chrysotile2 POS

Brick caulk - brown 06 Ground level – south rear NF1 Fair 120717 B17 1.2% Chrysotile1 POS

APPENDIX A

PLM LABORATORY DATA SHEETS,

CHAINS OF CUSTODY

Lab No.: 6403643 Client No.: 120717-B13

Analyst Observation: Black Caulk Client Description: Brick Caulk Black

Location: Ground Level East Wing (Front) Facility:

Percent Asbestos:

PC 1.8 Chrysotile

Percent Non-Asbestos Fibrous Material:

None Detected

Percent Non-Fibrous Material:

98.2

Lab No.: 6403644 Client No.: 120717-B14

Analyst Observation: Black Caulk Client Description: Brick Caulk Black

Location: Ground Level Bsmt Of East Wing

PC 2.1 Chrysotile

97.9

Laboratory Director

Approved By:

Date Analyzed:

12/8/2017Date Received:

Analyst:

Analytical Method -US EPA 600, R93-116. Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Linda Price

12/08/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - PLM Project: VA Lyons - Bldg 135 Project No.:

PLM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Rev #2, 12/12/2017

Dated : 12/12/2017 2:16:55 Page 1 of 5

Lab No.: 6403647 Client No.: 120717-B17

Analyst Observation: Brown Caulk Client Description: Brick Caulk Brown

Location: Ground Level South Rear

PC 1.2 Chrysotile

98.8

Laboratory Director

Approved By:

Date Analyzed:

12/8/2017Date Received:

Analyst:

Analytical Method -US EPA 600, R93-116. Please refer to the Appendix of this report for further information regarding your analysis.

Signature:

Linda Price

12/08/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - PLM Project: VA Lyons - Bldg 135 Project No.:

PLM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Dated : 12/12/2017 2:16:55 Page 2 of 5

Appendix to Analytical Report Customer Contact: Michael Hoodak Analysis: US EPA 600, R93-116

This appendix seeks to promote greater understanding of any observations, exceptions, special instructions, or circumstances that the laboratory needs to communicate to the client concerning the above samples. The information below is used to help promote your ability to make the most informed decisions for you and your customers.

Please note the following points of contact for any questions you may have.

iATL Customer Service: customerservice@iatl.com iATL Office Manager: cdavis@iatl.com iATL Account Representative: Shirley Clark Sample Login Notes: See Batch Sheet Attached Sample Matrix: Bulk Building Materials Exceptions Noted: See Following Pages

General Terms, Warrants, Limits, Qualifiers:

General information about iATL capabilities and client/laboratory relationships and responsibilities are spelled out in iATL policies that are listed at www.iATL.com and in our Quality Assurance Manual per ISO 17025 standard requirements. The information therein is a representation of iATL definitions and policies for turnaround times, sample submittal, collection media, blank definitions, quantification issues and limit of detection, analytical methods and procedures, sub-contracting policies, results reporting options, fees, terms, and discounts, confidentiality, sample archival and disposal, and data interpretation.

iATL warrants the test results to be of a precision normal for the type and methodology employed for each sample submitted. iATL disclaims any other warrants, expressed or implied, including warranty of fitness for a particular purpose and warranty of merchantability. iATL accepts no legal responsibility for the purpose for which the client uses test results. Any analytical work performed must be governed by our Standard Terms and Conditions. Prices, methods and detection limits may be changed without notification. Please contact your Customer Service Representative for the most current information.

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA LAP LLC, or any agency of local, state or province governments nor of any agency of the U.S. government.

This report shall not be reproduced except in full, without written approval of the laboratory.

Information Pertinent to this Report:

Analysis by US EPA 600 93-116: Determination of Asbestos in Bulk Building Materials by Polarized Light Microscopy (PLM).

Certifications:

NIST-NVLAP No. 101165-0• NY-DOH No. 11021• AIHA-LAP, LLC No. 100188•

Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.

Analytical Methodology Alternatives: Your initial request for analysis may not have accounted for recent advances in regulatory requirements or advances in technology that are routinely used in similar situations for other qualified projects. You may have the option to explore additional analysis for further information. Below are a few options, listed as the matrix followed by the appropriate methodology. Also included are links to more information on our website.

Bulk Building Materials that are Non-Friable Organically Bound (NOB) by Gravimetric Reduction techniques employing PLM and TEM: ELAP 198.6 (PLM-NOB), ELAP 198.4 (TEM-NOB)

Loose Fill Vermiculite Insulation, Attic Insulation, Zonolite (copyright), etc.: US EPA 600 R-4/004 (multi-tiered analytical process) Sprayed On Insulation/Fireproofing with Vermiculite (SOF-V): ELAP 198.8 (PLM-SOF-V)

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates 3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - PLM Project: VA Lyons - Bldg 135 Project No.:

Client: BRI811

Page 3 of 5Dated : 12/12/2017 2:16:55

Soil, sludge, sediment, aggregate, and like materials analyzed for asbestos or other elongated mineral particles (ex. erionite, etc.): ASTM D7521, CARB 435, and other options available

Asbestos in Surface Dust according to one of ASTM's Methods (very dependent on sampling collection technique – by TEM): ASTM D 5755, D5756, or D6480

Various other asbestos matrices (air, water, etc.) and analytical methods are available.

Disclaimers / Qualifiers:

There may be some samples in this project that have a "NOTE:" associated with a sample result. We use added disclaimers or qualifiers to inform the client about something that requires further explanation. Here is a list with highlighted disclaimers that may be pertinent to this project. For a full explanation of these and other disclaimers, please inquire at customerservice@iatl.com.

1) Note: No mastic provided for analysis.

2) Note: Insufficient mastic provided for analysis.

3) Note: Insufficient material provided for analysis.

4) Note: Insufficient sample provided for QC reanalysis.

5) Note: Different material than indicated on Sample Log / Description.

6) Note: Sample not submitted.

7) Note: Attached to asbestos containing material.

8) Note: Received wet.

9) Note: Possible surface contamination.

10) Note: Not building material. 1% threshold may not apply.

11) Note: Recommend TEM-NOB analysis as per EPA recommendations.

12) Note: Asbestos detected but not quantifiable.

13) Note: Multiple identical samples submitted, only one analyzed.

14) Note: Analyzed by EPA 600/R-93/116. Point Counting detection limit at 0.080%.

15) Note: Analyzed by EPA 600/R-93/116. Point Counting detection limit at 0.125%.

Recommendations for Vermiculite Analysis:

Several analytical protocols exist for the analysis of asbestos in vermiculite. These analytical approaches vary depending upon the nature of the vermiculite mineral being tested (e.g. un-processed gange, homogeneous exfoliated books of mica, or mixed mineral composites).Please contact your client representative for pricing and turnaround time options available.

iATL recommends initial testing using the EPA 600/R-93/116 method. This method is specifically designed for the analysis of asbestos in bulk building materials. It provides an acceptable starting point for primary screening of vermiculite for possible asbestos.

Results from this testing may be inconclusive. EPA suggests proceeding to a multi-tiered analysis involving wet separation techniques in conjunction with PLM and TEM gravimetric analysis (EPA 600/R-04/004).

Further information on this method and other vermiculite and asbestos issues can be found at the following: Agency for Toxic Substances and Disease Registry (ATSDR) www.atsdr.cdc.gov, United States Geological Survey (USGS) www.minerals.usgs.gov/minerals/, US EPA www.epa.gov/asbestos. The USEPA also has an informative brochure "Current Best Practices for Vermiculite Attic Insulation" EPA 747F03001 May 2003, that may assist the health and remediation professional.

The following is a summary of the analytical process outlines in the EPA 600/R-04/004 Method:

1)Analytical Step/Method: Initial Screening by PLM, EPA 600R-93/116 Requirements/Comments: Minimum of 0.1 g of sample. ~0.25% LOQ for most samples.

2)Analytical Step/Method:Wet Separation by PLM Gravimetric Technique, EPA R-04/004 Requirements/Comments: Minimum 50g** of dry sample. Analysis of "Sinks" only.

3)Analytical Step/Method:Wet Separation by PLM Gravimetric Technique, EPA R-04/004 Requirements/Comments: Minimum 50g** of dry sample. Analysis of "Floats" only.

4)Analytical Step/Method:Wet Separation by TEM Gravimetric Technique, EPA R-04/004 Requirements/Comments: Minimum 50g** of dry sample. Analysis of "Sinks" only.

5)Analytical Step/Method:Wet Separation by TEM Gravimetric Technique, EPA R-04/004

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates 3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - PLM Project: VA Lyons - Bldg 135 Project No.:

Page 4 of 5Dated : 12/12/2017 2:16:55

Requirements/Comments: Minimum 50g** of dry sample. Analysis of "Suspension" only.

LOQ, Limit of Quantitation estimates for mass and volume analyses.

*With advance notice and confirmation by the laboratory.

**Approximately 1 Liter of sample in double-bagged container (~9x6 inch bag of sample).

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates 3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - PLM Project: VA Lyons - Bldg 135 Project No.:

Page 5 of 5Dated : 12/12/2017 2:16:55

Lab No.: 6403631 Client No.: 120717-B01 Description: Grey Caulk

Location: Roof By Loading Dock North

Organic Fraction: 45.7 % Gravimetrically Reduced Subsample: 54.3%

% Asbestos Detected:

% Non-Asbestos Fibrous Material:

% Non-Fibrous Material:

54.3 Other

Lab No.: 6403632 Client No.: 120717-B02

Location: Roof By Loading Dock West

Organic Fraction: 17.4 % Gravimetrically Reduced Subsample: 82.6%

82.6 Other

Lab No.: 6403633 Client No.: 120717-B03

Location: Roof Middle Of Support Bldg

Organic Fraction: 51.5 % Gravimetrically Reduced Subsample: 48.5%

48.5 Other

Lab No.: 6403634 Client No.: 120717-B04

Location: Roof Support Unit East

Organic Fraction: 8.8 % Gravimetrically Reduced Subsample: 91.2%

91.2 Other

Lab No.: 6403635 Client No.: 120717-B05

Location: Roof Support Unit East

Organic Fraction: 16.1 % Gravimetrically Reduced Subsample: 83.9%

% Asbestos Detected:

Trace Actinolite, Detected at <0.25%

83.9 Other

Laboratory Director

Approved By:

Date Analyzed:

12/8/2017Date Received:

Analyst:

Please refer to the Preface of this report for further information regarding your analysis.

Signature:

Craig Liska

12/11/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

TEM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Dated : 12/12/2017 2:16:56 Page 1 of 8

Lab No.: 6403636 Client No.: 120717-B06 Description: Grey/White Caulk

Location: Roof Support Unit

Organic Fraction: 57.1 % Gravimetrically Reduced Subsample: 42.9%

% Asbestos Detected:

Trace Chrysotile, Detected at <0.25%

42.9 Other

Date Analyzed:

12/8/2017Date Received:

Analyst:

Please refer to the Preface of this report for further information regarding your analysis.

Signature:

Craig Liska

12/11/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

TEM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Dated : 12/12/2017 2:16:56 Page 2 of 8

Lab No.: 6403637 Client No.: 120717-B07 Description: Grey/White Caulk

Location: Roof Support Unit

Organic Fraction: 67.0 % Gravimetrically Reduced Subsample: 33.0%

Trace SiAl, Other Fiber

33 Other

Date Analyzed:

12/8/2017Date Received:

Analyst:

Please refer to the Preface of this report for further information regarding your analysis.

Signature:

Craig Liska

12/12/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

TEM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Dated : 12/12/2017 2:16:56 Page 3 of 8

Lab No.: 6403638 Client No.: 120717-B08 Description: Tan Caulk

Location: Roof West Wing

Organic Fraction: 22.8 % Gravimetrically Reduced Subsample: 77.2%

77.2 Other

Lab No.: 6403639 Client No.: 120717-B09

Location: Roof West Wing

Organic Fraction: 94.0 % Gravimetrically Reduced Subsample: 6.0%

6.0 Other

Lab No.: 6403640 Client No.: 120717-B10

Location: Roof East Wing

Organic Fraction: 91.4 % Gravimetrically Reduced Subsample: 8.6%

Trace SiAl, Other Fiber

8.6 Other

Lab No.: 6403641 Client No.: 120717-B11

Organic Fraction: 11.8 % Gravimetrically Reduced Subsample: 88.2%

88.2 Other

Lab No.: 6403642 Client No.: 120717-B12

Organic Fraction: 23.8 % Gravimetrically Reduced Subsample: 76.2%

76.2 Other

Date Analyzed:

12/8/2017Date Received:

Analyst:

Please refer to the Preface of this report for further information regarding your analysis.

Signature:

Craig Liska

12/11/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

TEM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Dated : 12/12/2017 2:16:56 Page 4 of 8

Lab No.: 6403645 Client No.: 120717-B15 Description: Pink Caulk

Location: Ground Level SE East Wing

Organic Fraction: 35.6 % Gravimetrically Reduced Subsample: 64.4%

64.4 Other

Date Analyzed:

12/8/2017Date Received:

Analyst:

Please refer to the Preface of this report for further information regarding your analysis.

Signature:

Craig Liska

12/12/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

TEM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Dated : 12/12/2017 2:16:56 Page 5 of 8

Lab No.: 6403646 Client No.: 120717-B16 Description: Brown Caulk

Location: Ground Level South Rear

Organic Fraction: 85.6 % Gravimetrically Reduced Subsample: 14.4%

13.7 Chrysotile

0.7 Other

Date Analyzed:

12/8/2017Date Received:

Analyst:

Please refer to the Preface of this report for further information regarding your analysis.

Signature:

Craig Liska

12/11/2017 Frank E. Ehrenfeld, III

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates

3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

TEM BULK SAMPLE ANALYSIS SUMMARY

Client: BRI811

Dated : 12/12/2017 2:16:56 Page 6 of 8

Appendix to Analytical Report:

Customer Contact: Michael Hoodak Analysis: ELAP Section 198.4

This appendix seeks to promote greater understanding of any observations, exceptions, special instructions, or circumstances that the laboratory needs to communicate to the client concerning the above samples. The information below is used to help promote your ability to make the most informed decisions for you and your customers.

Please note the following points of contact for any questions you may have.

iATL Customer Service: customerservice@iatl.com iATL Office Manager: cdavis@iatl.com iATL Account Representative: Shirley Clark Sample Login Notes: See Batch Sheet Attached Sample Matrix: Bulk material, Non-Friable Organically Bound material such as VSF, FT, M, RM, Tar, CB, Shingle, Tar Paper, Caulk, Glazing Exceptions Noted: See Following Pages

General Terms, Warrants, Limits, Qualifiers:

General information about iATL capabilities and client/laboratory relationships and responsibilities are spelled out in iATL policies that are listed at www.iATL.com and in our Quality Assurance Manual per ISO 17025 standard requirements. The information therein is a representation of iATL definitions and policies for turnaround times, sample submittal, collection media, blank definitions, quantification issues and limit of detection, analytical methods and procedures, sub-contracting policies, results reporting options, fees, terms, and discounts, confidentiality, sample archival and disposal, and data interpretation.

iATL warrants the test results to be of a precision normal for the type and methodology employed for each sample submitted. iATL disclaims any other warrants, expressed or implied, including warranty of fitness for a particular purpose and warranty of merchantability. iATL accepts no legal responsibility for the purpose for which the client uses test results. Any analytical work performed must be governed by our Standard Terms and Conditions. Prices, methods and detection limits may be changed without notification. Please contact your Customer Service Representative for the most current information.

This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA LAP LLC, or any agency of local, state or province governments nor of any agency of the U.S. government.

This report shall not be reproduced except in full, without written approval of the laboratory.

Information Pertinent to this Report:

Analysis by ELAP Section 198.4

Certifications:

- NIST-NVLAP No. 101165-0

- NY-DOH No. 11021

- AIHA-LAP, LLC No. 100188

All results are based on the samples as received at the lab. iATL assumes that appropriate sampling methods have been used and that the data upon which these results are based have been accurately supplied by the client.

The "Gravimetrically Reduced Subsample" is the portion of the submitted sample remaining following the ashing and acid treatment processes.

TEM analysis occurs on this portion of the sample.

Final results are calculated to represent the sample as submitted. Results are verifiable for only those operations and analyses performed in the laboratory.

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates 3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

Page 7 of 8Dated : 12/12/2017 2:16:57

Disclaimers / Qualifiers:

There may be some samples in this project that have a "NOTE:" associated with a sample result. We use added disclaimers or qualifiers to inform the client about something that requires further explanation. Here is a complete list with highlighted disclaimers pertinent to this project. For a full explanation of these and other disclaimers, please inquire at customerservice@iatl.com.

(1)Note: Sample not analyzed.

(2)Note: Sample not analyzed at request of client.

(3)Note: Sample analysis terminated. Clearance criteria exceeded (average >70.0 s/mm²). Set fails by AHERA 40 CFR 763.

(4)Note: Heavy loading (>0.1 s/cc) of non-asbestos particulate that might prohibit the required morphological, diffraction and elemental identification of asbestos. The absence of asbestos on the sample can not be concluded. Analysis for informational purposes only.

(5)Note: Heavy loading (>10% per grid opening) non-fibrous particulate. Sample analysis terminated. Clearance criteria exceeded (>10%). Sample voided by AHERA 40

CFR 763.

(5A)Note: Heavy loading (>25% per grid opening) non-fibrous particulate. Sample analysis terminated. Clearance criteria exceeded (>25%). Sample voided by NIOSH 7402.

(6)Note: Sample turbidity >1.0 NTU. Therefore MDL >> 0.1 MFL. Does not meet National Primary Drinking Water Standards.

(7)Note: Sample integrity compromised. Received sample cassette with top open (40 CFR 763 c-e).

(8)Note: Received sample cassettes with portion of filter missing. "PCM re-prep" (9)Note: Void - overloaded, unable to prep.

(10)Note: Void - filter damaged.

(11)Note: No volume supplied.

(12)Note: Heavy loading (>0.1 s/cc) of non-asbestos / non-fibrous particulate.

(13)Note: Method analytical sensitivity of <0.003 s/cc not attained due to volume of air sampled. NIOSH requires a minimum of 400L.

(13A)Note: Volume does not meet AHERA requirements.(<1188 L) (14)Note: Geometric Mean = 0.xxxx Structures/cc (15)Note: Samples received on 0.8 micron PCM filters. Samples must be submitted on 0.45 micron filter cassettes per AHERA guidelines (18)Note: *Results are for informational purposes only. Samples received on 0.8um PCM cassettes. Per AHERA 40 CFR 763 guidelines samples must be obtained on a 0.45um cassette.

(TEM NOB 1) Note: The above result represents only the analysis of NOB-residue submitted from the client.

(TEM NOB 2) Note: Insufficient material (<100mg) to verify results.

9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054

Telephone: 856-231-9449 Email: customerservice@iatl.com

CERTIFICATE OF ANALYSIS

Client: Briggs Associates 3 Crosswicks St Bordentown NJ 08505

12/12/2017Report Date:

Report No.: 553448 - TEM NOB Project: VA Lyons - Bldg 135 Project No.:

Page 8 of 8Dated : 12/12/2017 2:16:57

APPENDIX B

LABORATORY & INSPECTOR

CERTIFICATIONS