36C10F19R0086-013.pdf
PDF Posted
- Attached to
- Replace Boiler Plant and Steam Distribution System Federal contract opportunity
- Solicitation number
- 36C10F19R0086
About this file
This is a sources sought notice from the Department of Veterans Affairs seeking capability statements from small business contractors to replace a boiler plant and steam distribution system at a VA medical center. The project scope includes renovating an existing 8,000 square foot boiler plant building and constructing a 2,087 square foot addition. The estimated budget is between $10-20 million. Responses are requested by October 3rd and should include company information, certifications, bonding capacity, and experience on similar projects. The notice states this is not a solicitation and responses will not be considered for award, but to conduct market research for a future solicitation.
36C10F19R0086 04 Structural Drawings.pdf
View the file
Other files for this federal contract opportunity
Show all 50
Replace Boiler Plant and Steam Distribution System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
th re e i n c h e s o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t 1 2 3 4 5
Drawing Title:Seal:
FULLY SPRINKLERED
ARCHITECT / ENGINEERS:
Project Title:
Date:
Project Number:
Drawing Number:
Drawn:Checked:
Building Number:
D C
B A
Revisions:
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
P 704.814.1320 F 704.321.0833
Project Phase:
D C
B A
1 2 3 4 5 6
Location:
CONSULTANTS:
Office of
Construction and Facilities
Management
MAIN OFFICE
502-14-102V
ALEXANDRIA VA HEALTH CARE SYSTEM
PINEVILLE, LA
LRSPC Project No. 17020
\\lrs-dc\Dwgfiles\17DWGS\17020 VAMC Alexandria\Struct\Revit 16\16009 A Central_struc_LRSPC - NEW.rvt
HDG PROJECT: 16009 SS001
STRUCTURAL GENERAL NOTES
BID DOCUMENTS
REPLACE BOILER PLANT &
STEAM DISTRIBUTION
SYSTEM
JUNE 14, 2019 RJMMSR
1.0. CODES AND STANDARDS:
1.1. INTERNATIONAL BUILDING CODE 2012 EDITION INCLUDING ALL SUBSEQUENT
SUPPLEMENTS AND AMENDMENTS THERETO.
1.2. "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES", AMERICAN
SOCIETY OF CIVIL ENGINEERS, ASCE 7-10.
1.3. "SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS", PUBLICATION 360-10 BY THE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION, AND AS AMENDED IN SPECIFICATIONS.
1.4. "SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS", PUBLICATION 341-10 BY
THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION.
1.5. "STRUCTURAL WELDING CODE - STEEL (AWS D1.1-04)" AND "STRUCTURAL WELDING
CODE REINFORCING STEEL (AWS D1.4-98)", AMERICAN WELDING SOCIETY.
1.6 "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318-11)",
AMERICAN CONCRETE INSTITUTE AND ALL SUCCEEDING REVISIONS.
1.7. "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" (ACI 530-11) AND
"SPECIFICATIONS FOR MASONRY STRUCTURES" (ACI 530.1-11), AMERICAN CONCRETE
INSTITUTE.
1.8. "MANUAL OF STANDARD PRACTICE", CONCRETE REINFORCING STEEL INSTITUTE,
LATEST EDITION.
1.9. "STANDARD FOR NONCOMPOSITE STEEL FLOOR DECK", ANSI/SDI NC-2010,
STEEL DECK INSTITUTE.
1.10. "STANDARD FOR STEEL ROOF DECK", ANSI/SDI RD-2010, STEEL DECK INSTITUTE.
1.11. "NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL
MEMBERS, WITH SUPPLEMENT 1, DATED 2010", S100-07/SI-10,
AMERICAN IRON AND STEEL INSTITUTE.
1.12. "STANDARD SPECIFICATIONS FOR OPEN WEB STEEL JOISTS, K-SERIES", K-10
STEEL JOIST INSTITUTE.
2.0. SPECIFICATIONS:
2.1. THE STRUCTURAL GENERAL NOTES ARE NOT A SUBSTITUTE OR A REPLACEMENT
FOR THE PROJECT SPECIFICATIONS. THESE NOTES ARE INTENDED AS A GUIDE TO
THE DESIGN AND/OR CONSTRUCTION REQUIREMENTS ESTABLISHED FOR THIS PROJECT.
NO CONTRACTOR SHOULD ATTEMPT TO DESIGN, BID, OR CONSTRUCT ANY PORTION OF
THE WORK HEREIN WITHOUT CONSULTING THE PROJECT SPECIFICATIONS. WHERE
CONFLICTS OCCUR BETWEEN THESE NOTES AND THE SPECIFICATIONS, THE MORE
STRINGENT REQUIREMENT SHALL APPLY UNLESS A WRITTEN CLARIFICATION IS
ISSUED BY THE COR.
2.2. CONTRACTOR AND STRUCTURAL STEEL FABRICATOR SHOULD ACQUAINT THEMSELVES WITH
THE REQUIREMENTS FOR DOMESTICALLY PRODUCED BOLTS AND FOR STEEL CONNECTION
DESIGN REQUIREMENTS NOTED HEREIN AND IN THE STRUCTURAL STEEL SPECIFICATIONS.
2.3. CONTRACTOR AND STRUCTURAL STEEL FABRICATOR SHOULD ACQUAINT THEMSELVES WITH
THE REQUIREMENTS FOR DOMESTICALLY PRODUCED BOLTS AND FOR STEEL CONNECTION
DESIGN REQUIREMENTS, INCLUDING SIGNED AND SEALED SHOP DRAWINGS AND
CONNECTION DESIGN CALCULATIONS, NOTED HEREIN AND IN THE STRUCTURAL STEEL
SPECIFICATIONS. REQUIREMENTS ARE MANDATORY. REFER TO SPECIFICATION
SECTION 051200 "STRUCTURAL STEEL"
2.4. STRUCTURAL STEEL SHALL BE FABRICATED BY A QUALIFIED FABRICATOR WHO PARTICIPATES
IN THE AISC CERTIFICATION PROGRAM AND IS DESIGNATED AS AN AISC CERTIFIED
PLANT "STANDARD FOR STEEL BUILDING STRUCTURES (STD)" AND THE STRUCTURAL
STEEL FABRICATOR MUST DEMONSTRATE A CONSISTENT RECORD OF AT LEAST TEN (10)
SUCCESSFUL PROJECTS OF EQUAL OR GREATER MAGNITUDE OVER THE PRECEDING FIVE
(5) YEARS. CONTRACTOR SHALL SUBMIT EVIDENCE TO THE COR VERIFYING
HIS PROPOSED FABRICATOR'S COMPLIANCE. FABRICATOR'S CREDENTIALS MUST BE IN
COMPLIANCE WITHIN 48 HOURS OF BID.
2.5. STRUCTURAL STEEL SHALL BE ERECTED BY A QUALIFIED INSTALLER WHO PARTICIPATES
IN THE AISC CERTIFICATION PROGRAM AND IS DESIGNATED AS AN AISC "CERTIFIED
STEEL ERECTOR (CSE)" AND THE ERECTOR MUST DEMONSTRATE A CONSISTENT RECORD
OF AT LEAST TEN (10) SUCCESSFUL PROJECTS OF EQUAL OR GREATER MAGNITUDE
OVER THE PRECEDING FIVE (5) YEARS. CONTRACTOR SHALL SUBMIT EVIDENCE TO
THE COR VERIFYING HIS ERECTOR'S COMPLIANCE. ERECTOR'S CREDENTIALS
MUST BE IN COMPLIANCE WITHIN 48 HOURS OF BID.
3.0. DESIGN LOADS:
3.1. SUPERIMPOSED GRAVITY LOADS:
AREA LIVE LOAD DEAD LOAD
MINIMUM UNIFORM ROOF LOAD 20 PSF 25 PSF
PENTHOUSE, MECHANICAL AREAS 150 PSF -
STORAGE, STAIRS 100 PSF -
ALL FRAMED FLOORS, U.N.O. 100 PSF 5 PSF
SLAB ON GRADE 200 PSF -
GRATING 300 PSF 20 PSF
CONCENTRATED LIVE LOAD OF 1420 POUNDS (4 AT 2'-8"x6'-1")
LIVE LOADS ARE REDUCED IN CONFORMANCE WITH ASCE 7-10
SECTION 4.8 "REDUCTION IN LIVE LOADS"
3.2. SEISMIC LOADS: (NEW ADDITION)
RISK CATEGORY IV
RISK IMPORTANCE FACTOR "IE" 1.5
SITE SOIL CLASSIFICATION D
MAPPED SPECTRAL RESPONSE "Ss/S1" 0.095g/0.0062g DESIGN SPECTRAL RESPONSE "Sds/Sd1" 0.101g/0.100g
SEISMIC DESIGN CATEGORY C
MEAN ROOF HEIGHT 16'-0"
STRUCTURAL SYSTEM NORTH/SOUTH EAST/WEST
ORDINARY REINFORCED ORDINARY REINFORCED
MASONRY SHEAR WALLS MASONRY SHEAR WALLS
RESPONSE MODIFICATION "R" 2.0 2.0
DEFLECTION AMPLIFICATION "CD" 1.75 1.75
PERIOD BY CODE FORMULA "TA" 0.145 SEC. 0.145 SEC.
PERIOD BY ELASTIC ANALYSIS "TE" 0.020 SEC. 0.044 SEC.
MAXIMUM PERMISSIBLE PERIOD "TU" 0.419 SEC. 0.1419SEC.
SEISMIC COEFFICIENT "CS" 0.089 0.089
SEISMIC BASE SHEAR "VO" 15.84 KIPS 15.84 KIPS
3.3. WIND LOADS PER ASCE 7-10: (NEW ADDITION)
ULTIMATE WIND SPEED (3-SECOND GUST) 120 MPH
RISK CATEGORY IV
ASCE 7 EXPOSURE CATEGORY B
MEAN ROOF HEIGHT 66'-0"
MAIN WIND FORCE RESISTING SYSTEM NORTH/SOUTH EAST/WEST
ORDINARY REINFORCED ORDINARY REINFORCED
MASONRY SHEAR WALLS MASONRY SHEAR WALLS
WINDWARD PRESSURE COEFFICIENT "CP" +0.80 +0.80
LEEWARD PRESSURE COEFFICIENT -0.50 -0.50
WIND BASE SHEAR "VO" 5.89 KIPS 28.57 KIPS
WIND PRESSURES FOR CLADDING AND OTHER COMPONENTS VARY WITH SHAPE
FACTORS FOR THOSE COMPONENTS - SEE APPROPRIATE ASCE 7-10 SECTIONS
3.4. DRIFTING SNOW LOADS PER ASCE 7-10:
50 YEAR GROUND SNOW LOAD "PG" 5.0 PSF
RISK CATEGORY IV
IMPORTANCE FACTOR "I" 1.20
ROOF EXPOSURE TYPE PARTIAL
EXPOSURE FACTOR "CE" 1.00
THERMAL FACTOR "CT" 1.00
MINIMUM ROOF SNOW LOAD (PG*I) 6.0 PSF
FLAT ROOF SNOW LOAD "PF" 4.2 PSF
RAIN-ON-SNOW SURCHAGE 5.0 PSF
FLAT ROOF DESIGN SNOW LOAD 6.0 PSF
4.0. FOUNDATIONS:
4.1. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL REPORT, DATED OCTOBER 30,2017, AND ADDENDUM DATED NOVEMBER 1, 2017 BY GEOTECHNICAL TESTING LABORATORY INC.
THIS REPORT IS AVAILABLE FOR INSPECTION AT THE OFFICE OF THE COR. THE
RECOMMENDATIONS OF THIS "REPORT" ARE HEREIN MADE A PART OF THE REQUIREMENTS
OF THESE CONTRACT DOCUMENTS.
4.2. ALL SHALLOW FOUNDATIONS WERE ANTICIPATED TO BE IN CUT INTO UNDISTURBED
RESIDUAL SOILS AT THE TIME OF DESIGN AND WERE DESIGNED TO BEAR ON STRATA
CAPABLE OF SUSTAINING A MINIMUM BEARING PRESSURE OF 2000/1500 PSF IN ACCORDANCE
WITH THE GEOTECHNICAL REPORT FOR COLUMN/WALL FTRGS RESPECTIVELY.THE
CONTRACTOR IS RESPONSIBLE FOR NOTIFYING THE COR SHOULD SUCH CONDITIONS ARISE.
4.3. FOOTINGS SHALL BEAR ON STRATA CAPABLE OF SUSTAINING A MINIMUM BEARING
PRESSURE OF 2000 PSF AT COLUMN FTGS & 1500 PSF AT WALL FTGS.
4.4. WHERE FOOTING EXCAVATIONS MUST REMAIN OPEN OVERNIGHT OR IF RAINFALL BECOMES
IMMINENT WHILE BEARING SOILS ARE EXPOSED, A 2" TO 4" THICK MUD MAT OF
UNREINFORCED LEAN (F'C = 2000 PSI) CONCRETE SHALL BE PLACED ON THE BEARING
SOILS BEFORE PLACEMENT OF THE FOOTING REINFORCING.
4.5. TOP OF FOOTING (T/FTG) ELEVATIONS ARE SHOWN ON THE DRAWINGS OR ARE TO BE
DETERMINED BY THE CONTRACTOR IN THE FIELD IN ACCORDANCE WITH THE GUIDELINES
SET FORTH IN THE DRAWINGS AND SPECIFICATIONS.
4.6. BOTTOM OF EXTERIOR FOOTINGS SHALL BEAR AT A MINIMUM DEPTH OF 1'-0" BELOW
FINAL GRADE FOR FROST PROTECTION.
4.7. TESTING AND INSPECTION:
A. ALL AREAS TO HAVE SLABS ON GRADE SHALL BE PROOF ROLLED IN ACCORDANCE WITH
THE "REPORT" AND UNDER OBSERVATION OF THE GEOTECHNICAL ENGINEER AND
APPROVED PRIOR TO PREPARATION FOR CONCRETE PLACEMENT.
AND APPROVED PRIOR TO PREPARATION FOR CONCRETE PLACEMENT.
B. ALL FOUNDATION BEARING/FOUNDING STRATA SHALL BE INSPECTED AND APPROVED BY
THE GEOTECHNICAL ENGINEER PRIOR TO ANY CONCRETE PLACEMENT.
C. GEOTECHNICAL ENGINEER SHALL BE THE SOLE JUDGE AS TO SUITABILITY OF ALL
FOUNDATION AND/OR SLAB BEARING/FOUNDING STRATA.
D. FOOTING BEARING ELEVATIONS SHALL BE ADJUSTED IN THE FIELD AS REQUIRED TO
MEET THE DESIGN BEARING PRESSURES BY ADDITIONAL EXCAVATION OR COMPACTION
AND/OR BACKFILLING OR BY OTHER MEANS ACCEPTABLE TO THE GEOTECHNICAL
ENGINEER.
4.8. UNACCEPTABLE SOILS: CONTRACTOR SHALL REMOVE AND REPLACE UNACCEPTABLE
SOILS IN ACCORDANCE WITH THE GEOTECHNICAL REPORT AND/OR AT THE DIRECTION
OF THE GEOTECHNICAL ENGINEER. ALL SOILS WITH PLASTICITY INDICES GREATER
THAN 15 OF WHICH MORE THAN 10% PASSES A #200 SIEVE SHALL BE REMOVED TO A
DEPTH OF NOT LESS THAN 4'-0" OR GREATER AS DIRECTED BY THE GEOTECHNICAL
ENGINEER WHERE SUCH MATERIAL OCCURS BELOW FOUNDATIONS.
4.9. ROCK EXCAVATION: PARTIALLY WEATHERED ROCK WAS NOT ENCOUNTERED IN SOIL
BORINGS ON THIS SITE. DENSE SOIL AND PARTIALLY WEATHERED ROCK IF THEY OCCUR
MAY REQUIRE HEAVY EXCAVATING EQUIPMENT WITH RIPPING TOOLS FOR REMOVAL.
CONFINED EXCAVATIONS (FOOTINGS, UTILITY TRENCHES, ETC.)
MAY REQUIRE RIPPING TOOLS AND PNEUMATIC HAMMERS. LIGHT BLASTING MAY BE
REQUIRED TO EFFICIENTLY REMOVE LARGE BOULDERS AND MATERIAL RESISTANT TO
RIPPING AND PNEUMATIC HAMMERS. PRIOR TO ANY PROPOSED BLASTING THE
CONTRACTOR SHALL OBTAIN APPROVAL AND COORDINATE HIS ACTIVITIES WITH THE
OWNER AND ALL GOVERNING AUTHORITIES.
4.10. ENGINEERED FILL: ALL FILL MATERIAL SHALL BE SELECTED IN ACCORDANCE WITH THE
GEOTECHNICAL REPORT. MATERIAL SHALL BE A CLEAN, LOW PLASTIC SOIL WITH A
PLASTICITY INDEX LESS THAN 20, LIQUID LIMIT LESS
THAN 40, UNIT WEIGHT OF 120 PCF (+/- 5 PCF), AND SHALL NOT CONTAIN MORE THAN
5% BY WEIGHT OF FIBROUS ORGANIC MATERIALS. PARTIALLY WEATHERED ROCK
MATERIALS MAY BE USED FOR STRUCTURAL FILL PROVIDED THE MATERIAL CAN REDUCED
TO MAXIMUM DIMENSIONS OF 3".
4.11. DEEP FILL: WHERE SEVERAL FEET OF STRUCTURAL FILL WILL BE REQUIRED TO ACHIEVE
THE FINAL GRADES, CONSTRUCTION SHALL BE DELAYED TO PERMIT THE UNDERLYING SOILS
SETTLE AND CONSOLIDATE UNDER THE WEIGHT OF THE NEWLY PLACED FILL OVERBURDEN.
SEVERAL WEEKS OF TIME MAY BE REQUIRED FOR THIS SETTLING TO OCCUR. SETTLEMENT
PINS SHALL BE INSTALLED AT THE TOP OF THE FILL AND MONITORED TO DETERMINE
WHEN THE CONSOLIDATION HAS REACHED A NEGLIGIBLE MOVEMENT THUS PERMITTING
CONSTRUCTION TO BEGIN. THE GEOTECHNICAL ENGINEER SHALL BE THE SOLE JUDGE AS
TO THE REQUIREMENTS FOR DELAY AND COMPLETION OF ADEQUATE CONSOLIDATION.
4.12. EXTENT OF FILL PLACEMENT: STRUCTURAL FILL SHALL EXTEND HORIZONTALLY BEYOND
THE EDGE OF BUILDING FOUNDATIONS AT LEAST A DISTANCE OF 10'-0" BUT NOT LESS
THAN THE HEIGHT OF THE FILL MATERIAL PLACED. SLOPES AT PERMANENT CUTS SHOULD
NOT EXCEED 2:1 (H:V). SLOPE AT PERMANENT FILLS SHOULD NOT EXCEED 2.5:1 (H:V)
AND SHOULD BE PROPERLY COMPACTED.
4.13. COMPACTION: ALL FILL SHALL BE PLACED IN LOOSE LIFTS NOT EXCEEDING 8 INCHES
IN THICKNESS AND COMPACTED TO A MINIMUM OF 95 PERCENT STANDARD PROCTOR (ASTM
D-698) EXCEPT THAT THE TOP 12 INCHES UNDER FOUNDATIONS AND THE BUILDING PAD
SHALL BE COMPACTED TO A MINIMUM OF 98 PERCENT STANDARD PROCTOR. MOISTURE
SHALL BE CONTROLLED TO WITHIN 3 PERCENT ABOVE OR BELOW OPTIMUM CONTENT.
4.14. MUD SLABS: PROVIDE 2" TO 4" THICK LEAN CONCRETE (2,000 PSI) "MUD-MAT" SLABS
WHERE FOUNDATION EXCAVATIONS WILL BE LEFT OPEN TO POTENTIAL RAINFALLS.
4.15. MODULUS OF SUBGRADE REACTION FOR SLABS ON GRADE: 125 PCI
4.16. FOUNDATION AND RETAINING WALL DESIGN PRESSURES:
Unit Weight Active Passive At-Rest Backfill (pcf) (Drained) (Drained) (Drained)
On-Site Silty Sand (SM) 115 35 390 50 Clayey Sand (SC) 115 40 350 60 Compacted Low Swell Potential Fill (SC or CL) 120 60 245 80 Washed, Free-Draining Concrete Sand (ASTM33) (SW or SP) 115 35 375 55
Friction Coeficient .45
4.17. FOUNDATION AND RETAINING WALLS SHALL HAVE A MINIMUM OF TWO FEET (2'-0")
OF FREE DRAINING GRANULAR FILL AGAINST THE BACK OF THE WALL OR SHALL HAVE
AN ACCEPTABLE COMMERCIAL GRADE OF DRAINAGE MAT PLACED AGAINST THE BACK OF
THE WALL.
4.25. FOUNDATION WALLS RETAINING EARTH SHALL BE BRACED AGAINST BACKFILL PRESSURES
UNTIL FLOOR SLABS AT TOP AND BOTTOM ARE IN PLACE. BACKFILLING IS STRICTLY
PROHIBITED UNTIL SLABS ARE IN PLACE.
4.18. FOUNDATION WALLS OR GRADE BEAMS HAVING EARTH PLACED ON EACH SIDE SHALL
HAVE BOTH FILLED SIMULTANEOUSLY TO MAINTAIN A COMMON ELEVATION.
4.19. REINFORCING IN ALL CONTINUOUS STRIP FOOTINGS SHALL HAVE CORNER BARS OR
DOWELS PROVIDED AT ALL CORNERS AND INTERSECTIONS.
4.20. IF UNDERPINNING OF EXISTING FOUNDATIONS ADJACENT TO THE NEW CONSTRUCTION
WILL BE REQUIRED, THE CONTRACTOR WILL BE RESPONSIBLE FOR ALL SUCH WORK
AND FOR PROVIDING FOR THE ADEQUACY AND PERMANENT SUPPORT FOR ALL EXISTING
BUILDINGS. CONTRACTOR SHALL RETAIN A PROFESSIONAL ENGINEER REGISTERED IN
NORTH CAROLINA TO DESIGN AND DETAIL ALL UNDERPINNING WORK BASED ON
CONDITIONS UNCOVERED AND DOCUMENTED IN THE FIELD. CALCULATIONS AND
DRAWINGS FOR ALL UNDERPINNING WORK, SIGNED AND SEALED BY THE CONTRACTOR'S
ENGINEER, SHALL BE SUBMITTED TO THE COR FOR RECORD ONLY.
5.0. CONCRETE:
5.1. CONCRETE SHALL HAVE 28-DAY COMPRESSIVE STRENGTHS AND DENSITIES AS FOLLOWS:
ELEMENT/MEMBER STRENGTH F'C DENSITY WC
FOOTINGS & SLABS ON GRADE 3 KSI 145 PCF
DRILLED PIERS (CAISSONS) 3 KSI 145 PCF
PIER CAPS & GRADE BEAMS 3 KSI 145 PCF
CAST-IN-PLACE WALLS 4 KSI 145 PCF
STAIR PAN FILL 3 KSI 115 PCF
EXTERIOR CONCRETE OR CONCRETE
EXPOSED TO WEATHER 4.5 KSI 145 PCF
ALL OTHER CONCRETE U.N.O. 4 KSI 145 PCF
5.2. CONCRETE MIX DESIGNS:
A. SUBMITTALS: SUBMIT WRITTEN REPORTS OF EACH PROPOSED CONCRETE MIX NOT
LESS THAN 15 DAYS PRIOR TO THE START OF WORK. DESIGN MIXES PREPARED
MORE THAN TWELVE (12) MONTHS PRIOR TO THE DATE OF THE SUBMITTAL ARE
NOT PERMITTED.
B. MIX DESIGNS, INCLUDING W/C RATIOS AND SLUMPS, SHALL BE PREPARED IN
ACCORDANCE WITH THE MOST CURRENT ACI 301 CHAPTER 4, EXCEPT WHERE
NOTED OTHERWISE IN THE PROJECT SPECIFICATIONS. CEMENT SHALL CONFORM TO
ASTM C 150 TYPE I OR AT CONTRACTOR'S OPTION, ASTM C 595 TYPE IP WHERE
FLY ASH IS PERMITTED IN ACCORDANCE WITH THE SPECIFICATIONS. NORMAL
WEIGHT AGGREGATE SHALL CONFORM TO ASTM C 33 AND LIGHT WEIGHT AGGREGATE
SHALL CONFORM TO ASTM C 330. NO ADMIXTURES CONTAINING CALCIUM CHLORIDE
SHALL BE PERMITTED IN ANY CONCRETE.
C. AGGREGATE SIZES SHALL BE:
FORMED CONCRETE ELEMENTS, U.N.O. #67 STONE (3/4" MAX.)
GRADE SLABS AND EARTH FORMED ELEMENTS #57 STONE (1" MAX.)
COARSE MASONRY GROUT PER SECTION 042900 #8 STONE (3/8" MAX.)
FINE MASONRY GROUT PER SECTION 042900 #4 STONE (3/16" MAX.)
D. WATER REDUCING ADMIXTURE SHALL BE USED IN ALL CONCRETE.
E. AIR ENTRAINING ADMIXTURE IN ACCORDANCE WITH ACI 301 TABLE 4.4.1.
SHALL BE USED IN ALL CONCRETE EXPOSED TO FREEZING AND THAWING DURING
CONSTRUCTION OR SERVICE CONDITIONS.
F. WATER/CEMENT RATIO SHALL NOT EXCEED 0.45 FOR ANY CONCRETE SUBJECTED TO
FREEZING/THAWING.
G. ALL PUMPED CONCRETE SHALL HAVE A WATER/CEMENT RATIO LESS THAN 0.50 AND
SHALL CONTAIN A HIGH RANGE WATER REDUCING ADMIXTURE (SUPERPLASTICIZER).
H. IN NO CASE SHALL A WATER/CEMENT RATIOS EXCEED THE FOLLOWING:
F'C 3000 PSI 0.60 MAX. W/C RATIO
F'C 4000 PSI 0.50 MAX. W/C RATIO
5.3. CURING:
A. LIQUID MEMBRANE CURING COMPOUND WITH A MINIMUM 30% SOLIDS CONTENT SHALL
BE APPLIED WITHIN TWO (2) HOURS AFTER COMPLETION OF FINISHING TO ALL
CONCRETE FLATWORK AND WALLS, U.N.O., OTHER THAN FOOTINGS AND GRADE BEAMS.
B. FLOORS IN AREAS RECEIVING QUARRY TILE, CERAMIC TILE AND LIQUID FLOOR
HARDENER SHALL BE CURED WITH SPECIFIED DISSIPATING LIQUID MEMBRANE
CURING COMPOUND OR WET CURED BY USE OF MOISTURE RETAINING COVER.
DISSIPATING CURING COMPOUND SHALL BE THOROUGHLY BROOMED AND WASHED
OFF PRIOR TO APPLICATION OF FLOOR FINISH.
5.4. WHEN COLD WEATHER CONDITIONS EXIST, PLACE AND CURE CONCRETE IN ACCORDANCE
WITH ACI 306 "COLD WEATHER CONCRETING". WHERE USE IS DESIRED, SUBMIT FOR
ENGINEER'S APPROVAL A NON-CORROSIVE, NON-CHLORIDE, ACCELERATING ADMIXTURE
FOR CONCRETE EXPOSED TO TEMPERATURES BELOW 40 DEGREES. UNIFORMLY HEAT WATER
AND AGGREGATES TO A TEMPERATURE OF NOT LESS THAN 50 DEGREES.
5.5. WHEN HOT WEATHER CONDITIONS EXIST, PLACE AND CURE CONCRETE IN ACCORDANCE
WITH ACI 305 "HOT WEATHER CONCRETING". COOL MATERIALS BEFORE MIXING TO
MAINTAIN CONCRETE PLACEMENT TEMPERATURE BELOW 90 DEGREES.
5.6. ALL CONSTRUCTION JOINTS SHOWN ON THE DRAWINGS SHALL BE INCORPORATED INTO
THE STRUCTURE UNLESS THE COR APPROVES THEIR ELIMINATION.
5.7. ADDITIONAL CONSTRUCTION JOINTS, REQUIRED TO FACILITATE CONSTRUCTION, ARE
SUBJECT TO THE APPROVAL OF THE COR AND MAY REQUIRE
ADDITIONAL REINFORCING. SUCH JOINTS SHALL BE CLEARLY DETAILED ON THE SHOP
DRAWINGS AND ALL REINFORCING SHALL PASS CONTINUOUSLY THROUGH THE JOINT.
5.8. REINFORCING IN ALL ABUTTING CONCRETE, INCLUDING FOOTINGS, SHALL BE
CONTINUOUS THROUGH OR AROUND ALL CORNERS OR INTERSECTIONS. DOWELS OR
SPLICES SHALL BE EQUAL IN SIZE AND SPACING TO THE REINFORCING IN THE
ABUTTING MEMBERS.
5.9. REFER TO ARCHITECTURAL DRAWINGS FOR DOOR AND WINDOW OPENINGS, DRIPS,
REGLETS, WASHES, MASONRY ANCHORS, BRICK LEDGE ELEVATIONS, SLAB DEPRESSIONS
AND MISCELLANEOUS EMBEDDED PLATES, BOLTS, ANCHORS, ANGLES, ETC.
5.10. REFER TO ARCHITECTURAL DRAWINGS FOR CONCRETE FINISHES. WHERE FINISH IS
NOT SPECIFIED, CONFORM TO REQUIREMENTS OF ACI 301.
5.11. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR UNDERFLOOR,
PERIMETER AND OTHER DRAINS AND FOR SLEEVES, OUTLET BOXES, CONDUIT, ANCHORS,
ETC. THE VARIOUS TRADES ARE RESPONSIBLE FOR THEIR ITEMS.
5.12. BASE PLATES, ANCHOR BOLTS, SUPPORT ANGLES AND OTHER STEEL EXPOSED TO EARTH
OR GRANULAR FILL SHALL BE COVERED WITH A MINIMUM OF 3" OF CONCRETE.
5.13. FILL SLABS, NOT SHOWN ON THE STRUCTURAL DRAWINGS, SHALL BE REINFORCED WITH
A MINIMUM OF 6X6-W1.4XW1.4 WWM UNLESS NOTED OTHERWISE ON OTHER DRAWINGS
OR IN THE SPECIFICATIONS.
5.14. SLABS ON STEEL DECK SHALL BE PLACED SO THE FINISH SURFACE IS SCREEDED TO
WITHIN 1/4" OF THE TOP OF SLAB (T/SL) ELEVATION SHOWN ON THE DRAWINGS.
SCREED SUPPORTS SHALL BE PLACED OVER OR IMMEDIATELY ADJACENT TO BEAM OR
GIRDER LINES - SCREED SUPPORTS SHALL NOT BE LOCATED ON DECK SPANNING
BETWEEN BEAMS OR GIRDERS.
5.15. FINISHING TOLERANCE SHALL BE WITHIN CLASS B IN ACCORDANCE WITH ACI 301
AND CONSIDERATION SHALL BE GIVEN TO SEQUENCING OF CONCRETE PLACEMENT TO
FACILITATE CONTROL OF FINISH ELEVATIONS.
5.16. NON-SHRINK GROUT SHALL BE PRE-MIXED, NON-CORROSIVE, NON-METALLIC,
NON-STAINING CONTAINING SILICA SANDS, PORTLAND CEMENT, SHRINKAGE
COMPENSATING AND WATER REDUCING AGENTS. PRODUCT SHALL ONLY REQUIRE THE
ADDITION OF WATER. MINIMUM COMPRESSIVE STRENGTH SHALL BE 2500 PSI AFTER
ONE DAY AND 7000 PSI AFTER 28 DAYS. GROUT SHALL BE FREE OF GAS PRODUCING
OR AIR RELEASING AND OXIDIZING AGENTS AND CONTAIN NO CORROSIVE IRON,
ALUMINUM OR GYPSUM.
5.17. PROVIDE CONCRETE GROUT - NOT MORTAR - FOR REINFORCED MASONRY LINTEL AND
BOND BEAMS WHERE INDICATED ON DRAWINGS OR AS SCHEDULED.
5.18. TOLERANCE FOR ANCHOR BOLTS AND OTHER EMBEDDED ITEMS SHALL BE PER THE
AISC CODE OF STANDARD PRACTICE SECTION 7.5.
5.19. UNLESS OTHERWISE SHOWN IN THE ARCHITECTURAL DRAWINGS, PROVIDE 3/4" CHAMFERS
AT ALL COLUMN, WALL, SLAB OR BEAM EDGES THAT ARE EXPOSED TO VIEW IN THE
FINISHED STRUCTURE.
6.0. REINFORCING STEEL:
6.1. REINFORCING SHALL BE DOMESTIC NEW BILLET STEEL CONFORMING TO ASTM A615,
GRADE 60 OR 60S INCLUDING STIRRUPS AND TIES, EXCEPT THAT REINFORCING WHICH
IS REQUIRED TO BE WELDED SHALL CONFORM TO ASTM A706.
6.2. FIELD BENDING OF CONCRETE REINFORCING STEEL IS NOT PERMITTED WITHOUT
WRITTEN APPROVAL OF THE COR.
6.3. WELDED WIRE REINFORCING SHALL CONFORM TO ASTM A1064.
6.4. ALL REINFORCING SHALL BE DETAILED, FABRICATED AND PLACED IN ACCORDANCE
WITH ACI SP-66 "ACI DETAILING MANUAL - 2004" AND THE "CRSI MANUAL OF
STANDARD PRACTICE", LATEST EDITION.
6.5. MINIMUM CONCRETE COVER OVER REINFORCING SHALL BE U.N.O.:
A. UNFORMED SURFACE CAST AGAINST EARTH........................ 3 IN.
B. FORMED SURFACE EXPOSED TO EARTH/WEATHER.................... 2 IN.
C. FORMED SLABS AND WALLS NOT EXPOSED TO
EARTH/WEATHER FOR #11 AND SMALLER BAR.................... 3/4 IN.
D. ALL OTHER FORMED ELEMENTS NOT EXPOSED
TO EARTH/WEATHER....................................... 1-1/2 IN.
6.6. DEVELOPMENT LENGTHS AND LAP SPLICES SHALL BE IN ACCORDANCE WITH
ACI 318 CHAPTER 12 AS INDICATED BELOW AND AS INDICATED ON THE DRAWINGS.
WHERE SPLICES ARE NOT CALLED OUT ON THE DRAWINGS, USE CLASS "B". THE BASIC
DEVELOPMENT LENGTH (LD) IS SHOWN AS A MULTIPLE OF THE BAR DIAMETER (DB) IN
THE TABLE BELOW. THE TENSION DEVELOPMENT LENGTHS SHALL BE MULTIPLIED
BY EACH OF THE APPLICABLE FACTORS IN PARAGRAPH "C" AS INDICATED FOR TENSION.
THE COMPRESSION DEVELOPMENT LENGTHS DO NOT REQUIRE ANY MODIFICATION. THE
COMPRESSION LAP SPLICE LENGTH IS NOTED IN PARAGRAPH "C". FINAL LENGTHS SHALL
BE ROUNDED UP TO THE NEAREST WHOLE INCH.
A. TWO TENSION DEVELOPMENT LENGTH CASES ARE NOTED IN THE TABLE BELOW. THESE
TWO CASES ADDRESS CONDITIONS OF MINIMUM BAR SPACING AND MINIMUM CLEAR
CONCRETE COVER. BOTH SPACING AND COVER MUST COMPLY IN SELECTING CASE 1 OF
THE TENSILE DEVELOPMENT LENGTH. WHERE THERE IS ANY QUESTION OF SPACING OR
COVER THE LARGER DEVELOPMENT LENGTH (CASE 2) SHALL BE USED.
CASE 1: BAR SPACING GREATER THAN 2DB AND CLEAR COVER GREATER THAN DB
CASE 2: BAR SPACING EQUAL/LESS THAN 2DB OR CLEAR COVER EQUAL/LESS THAN DB
B. DEVELOPMENT LENGTHS (LD) FOR REINFORCING FY = 60 KSI:
F'C COMPRESSION TENSION
PSI ALL CASES CASE 1 CASE 2
3000 22 DB 55 DB 82 DB
4000 19 DB 48 DB 72 DB
C. DEVELOPMENT LENGTH MODIFIERS: MULTIPLICATION FACTORS APPLY TO
THE BASIC "LD" INDICATED ABOVE AND ARE CUMULATIVE OVER EACH OF THE
REQUIREMENTS NOTED BELOW.
I. COMPRESSION: CLASS "C" LAP SPLICE REQUIREMENT.......... 30 DB
II. TENSION: CLASS "A" LAP SPLICE REQUIREMENT (EQUALS LD).... 1.0
III. TENSION: CLASS "B" LAP SPLICE REQUIREMENT................ 1.3
IV. TENSION: TOP BARS WITH > 12" OF CONCRETE BELOW........... 1.3
V. TENSION: BARS SMALLER THAN #7............................ 0.8
VI. TENSION: BARS IN LIGHTWEIGHT AGGREGATE CONCRETE.......... 1.3
6.7. A CLASS "B" SPLICE IS REQUIRED WHEREVER ALL REINFORCING BARS CROSSING
A SECTION ARE SPLICED.
6.8. REINFORCING BARS SHALL BE WELDED ONLY WHERE SHOWN ON THE STRUCTURAL
DRAWINGS AND WELDS SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING
CODE - REINFORCING STEEL" (AWS D1.4). NO OTHER REINFORCING MAY BE WELDED
WITHOUT THE APPROVAL OF THE COR. TACK WELDING OF ANY
REINFORCING IS STRICTLY PROHIBITED.
6.9. WELDED WIRE MAT/FABRIC SHALL BE LAPPED 1'-0" AT ALL SPLICES.
6.10. ALL REINFORCING TERMINATING AT THE TOPS OF COLUMNS AND PILASTERS SHALL
BE HOOKED, U.N.O.
6.11. SUBMIT SHOP DRAWINGS FOR FABRICATION, BENDING, AND PLACEMENT OF CONCRETE
REINFORCEMENT. COMPLY WITH ACI DETAILING MANUAL (SP-66) SHOWING BAR
SCHEDULES, STIRRUP SPACING, DIAGRAMS OF BENT BARS, ARRANGEMENT OF CONCRETE
REINFORCEMENT. INCLUDE SPECIAL REINFORCEMENT REQUIRED AT OPENINGS THROUGH
CONCRETE STRUCTURES. INCLUDE ALL ACCESSORIES SPECIFIED/REQUIRED TO
SUPPORT REINFORCING.
6.12. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION
AND SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING RESPONSIBILITY
FOR DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER TRADES.
6.13. SUBMIT THREE (3) 24" X 36" PRINTS OF EACH SHOP DRAWING FOR REVIEW. SEE
PROJECT SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
6.14. ALTERNATIVELY, WHERE ACCEPTABLE TO COR, DRAWINGS MAY BE ELECTRONICALLY
SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED. REVIEW COMMENTS ONLY WILL
BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
6.15. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
6.16. CONTRACTOR SHALL NOTIFY THE COR A MINIMUM OF 48 HOURS
PRIOR TO ALL CONCRETE POURS IN ORDER TO PERMIT REINFORCING STEEL REVIEW
IF REQUIRED BY THE COR.
7.0. STRUCTURAL STEEL:
7.1. ALL STRUCTURAL STEEL SHALL BE OF THE GRADES INDICATED BELOW, UNLESS NOTED
OTHERWISE ON PLANS OR DETAILS:
A. WIDE FLANGE SHAPES ASTM A992 GR50.
B. OTHER ROLLED SHAPES ASTM A36 TYPICALLY, U.N.O.
C. ANCHOR BOLTS ASTM F1554 GR36 U.N.O.
D. STRUCTURAL TUBING (SQUARE AND RECTANGULAR) ASTM A500, GRADE B, FY=46 KSI.
E. STRUCTURAL TUBING (ROUND) ASTM A500, GRADE B, FY=42 KSI.
F. PLATES AND BARS ASTM A36 U.N.O.
G. MISCELLANEOUS ASTM A36 U.N.O.
7.2. ALL STRUCTURAL STEEL SHALL BE DETAILED AND, FABRICATED IN ACCORDANCE WITH
THE AISC CODE OF STANDARD PRACTICE AS MODIFIED IN THESE NOTES AND THE
PROJECT SPECIFICATIONS.
7.3. SUBMIT SHOP DRAWINGS FOR DETAILS, FABRICATION, AND ERECTION OF STRUCTURAL
STEEL. COMPLY WITH AISC "STEEL CONSTRUCTION MANUAL", AISC "DETAILING FOR
STEEL CONSTRUCTION", AND AISC "ENGINEERING FOR STEEL CONSTRUCTION"
PUBLICATIONS.
7.4. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION.
DRAWINGS SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING
RESPONSIBILITY FOR DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER
TRADES.
7.5. SUBMIT THREE (3) 24" X 36" PRINTS OF EACH SHOP DRAWING FOR REVIEW. SEE
PROJECT SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
7.6. ALTERNATIVELY, WHERE ACCEPTABLE TO COR, DRAWINGS MAY BE ELECTRONICALLY
SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED. REVIEW COMMENTS ONLY
WILL BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
7.6. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
7.7. CONNECTION DESIGN: SEE SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
A. FABRICATOR IS RESPONSIBLE FOR THE DESIGN OF CONNECTIONS NOT DESIGNED
ON THE STRUCTURAL DRAWINGS.
B. ALL CONNECTIONS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE WHERE THE PROJECT IS LOCATED. SHOP DRAWING CONTAINING
CONNECTION DESIGNS SHALL BE SIGNED AND SEALED. A NOTE INDICATING
"CONNECTION DESIGN ONLY" SHOULD ACCOMPANY THE SEAL. FABRICATOR SHALL
SUBMIT SIGNED AND SEALED CALCULATIONS FOR ALL CONNECTIONS DESIGNED AS
PART OF HIS WORK AND APPEARING ON HIS SHOP DRAWINGS.
C. GENERALLY, CONNECTIONS SHOWN ON THE DRAWINGS ARE SCHEMATIC AND ARE
INTENDED TO SHOW THE RELATIONSHIP OF THE MEMBERS.
D. CONNECTIONS SHALL BE DESIGNED FOR ONE-HALF (1/2) THE MAXIMUM TOTAL
UNIFORM LOAD ON THE MEMBER, AS DEFINED IN TABLE 3-6, "MAXIMUM TOTAL
UNIFORM LOAD" IN THE AISC "SPECIFICATIONS FOR STRUCTURAL STEEL
BUILDINGS", PUBLICATION 360-05 OR FOR THE REACTIONS AS SHOWN ON
THE DRAWINGS OR A MINIMUM OF 10 KIPS, WHICHEVER IS GREATEST.
E. MEMBER FORCES AND REACTIONS HAVE BEEN REDUCED IN CONFORMANCE TO CODE
PROVISIONS RELATED TO COMBINATIONS OF LOADS THAT INCLUDE WIND AND
SEISMIC FORCES. NO FURTHER REDUCTIONS IN FORCES OR INCREASES IN
ALLOWABLE STRESSES ARE PERMITTED.
F. CONNECTIONS SHOWN ON DRAWINGS ARE ULTIMATE (LRFD) LOAD REACTIONS.
G. CONNECTIONS MAY BE BOLTED OR WELDED, U.N.O. ON THE DRAWINGS:
7.8. BOLTED CONNECTIONS:
A. SLIP CRITICAL CONNECTIONS WITH A325SC OR A490SC BOLTS SHALL BE USED
IN ALL BOLTED MOMENT PLATE CONNECTIONS. OVERSIZED OR LONG-SLOTTED
HOLES ARE PERMITTED.
B. BEARING-TYPE CONNECTIONS WITH A325N OR A490N BOLTS SHALL BE USED FOR
ALL OTHER BOLTED CONNECTIONS. OVERSIZED AND LONG-SLOTTED HOLES ARE
NOT PERMITTED U.N.O. IN SINGLE TAB PLATE CONNECTIONS ONLY BEARING-
TYPE FASTENERS ARE PERMITTED, FASTENERS SHALL NOT BE TORQUED, AND
SHORT SLOTTED HOLES ARE REQUIRED.
C. ANCHOR BOLTS OR OTHER BOLTS, WHERE INDICATED, SHALL CONFORM TO ASTM
F1554 GR36 U.N.O.
D. PROTRUDING BOLT HEADS, SHAFTS OR NUTS SHALL NOT EXTEND NOR PROHIBIT
THE APPLICATION OF ARCHITECTURAL FINISHES OR PLACEMENT OF STEEL DECK
AT ITS CORRECT LOCATION AND ELEVATION.
E. CONNECTION DESIGNER IS RESPONSIBLE FOR VERIFYING THE AXIAL CAPACITY
AFTER A SECTION IS REDUCED FOR BOLT HOLES. MEMBER SIZE MAY BE
INCREASED OR PLATES ADDED TO MAINTAIN REQUIRED CAPACITY.
F. SHOP DRAWINGS SHALL INDICATE THE TYPE OF BOLT USED IN EACH
CONNECTION, ALLOWABLE VALUES FOR THE VARIOUS BOLT TYPES AND CAPACITY
OF EACH CONNECTION SHOWN.
G. DOMESTIC FASTENERS (AMERICAN OR CANADIAN) ARE REQUIRED IN ALL
STRUCTURAL STEEL WORK ON THIS PROJECT. IMPORTED FASTENERS ARE
PROHIBITED.
7.9. WELDED CONNECTIONS:
A. ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL WELDING CODE
- STEEL" (AWS D1.1) OF THE AMERICAN WELDING SOCIETY.
B. ELECTRODES FOR WELDING SHALL COMPLY WITH THE REQUIREMENTS OF AWS
D1.1 TABLE 4.1.1.
C. SHOP DRAWINGS SHALL INDICATE WELD TYPE, REQUIRED ELECTRODES AND
CAPACITY FOR EACH CONNECTION DETAILED ON THE SHOP DRAWINGS.
D. PERFORM VISUAL INSPECTIONS OF ALL WELDS.
E. PERFORM NON-DESTRUCTIVE TESTS OF WELDS AS FOLLOWS:
1. PARTIAL PENETRATION WELDS - ONE SPOT TEST PER WELD USING
MAGNETIC PARTICLE TESTING TECHNIQUES.
2. FULL PENETRATION WELDS - TEST ENTIRE LENGTH OF ALL WELDS.
USE RADIOGRAPHIC OR ULTRASONIC TESTING TECHNIQUES.
7.10. WHERE CANTILEVER BEAMS OCCUR ON PLAN AND THE SIZE IS NOTED ONLY FOR THE
BACK-SPAN, THE CANTILEVER IS INTENDED TO BE THE SAME SIZE AS THE BACK-
SPAN.
7.11. SPLICING OF STEEL MEMBERS, UNLESS SHOWN ON THE DRAWINGS, IS PROHIBITED
WITHOUT WRITTEN APPROVAL OF THE COR.
7.12. NO CHANGE IN SIZE OR POSITION OF ANY STRUCTURAL ELEMENT NOR HOLES, SLOTS,
CUTS, ETC. SHALL BE MADE UNLESS DETAILED AND NOTED AS A PROPOSED CHANGE
ON THE SHOP DRAWINGS AND REVIEWED AND ACCEPTED BY THE STRUCTURAL
ENGINEER.
7.13. NO FINAL BOLTING OR WELDING SHALL BE PERFORMED UNTIL AS MUCH OF THE
STRUCTURE AS WILL BE STIFFENED THEREBY HAS BEEN PROPERLY ALIGNED.
7.14. FABRICATE ALL BEAMS WITH MILL CAMBERS UP.
7.15. MINIMUM PLATE THICKNESS SHALL BE 3/8" U.N.O.; MINIMUM BOLT DIAMETER SHALL
BE 3/4" U.N.O.; MINIMUM SHOP WELD SHALL BE 3/16" AND MINIMUM FIELD WELD
SHALL BE 1/4" U.N.O.
7.16. ALL RE-ENTRANT CORNERS (SUCH AS COPES AND BLOCKS) SHALL BE CUT AND SHAPED
NOTCH FREE WITH A RADIUS OF AT LEAST 1/2".
7.17. FIELD USE OF GAS CUTTING TORCHES IS PROHIBITED FOR CORRECTING FABRICATION
ERRORS IN PRIMARY STRUCTURAL FRAMING.
7.18. PARAGRAPH 4.4.1 OF THE AISC CODE OF STANDARD PRACTICE SHALL BE SUPERSEDED
BY THE FOLLOWING: INDICATION OF COMPLIANCE BY THE
OWNER OF SHOP DRAWINGS PREPARED BY THE FABRICATOR INDICATES THAT THE
FABRICATOR HAS CORRECTLY INTERPRETED THE CONTRACT REQUIREMENTS. SUCH
INDICATION DOES NOT RELIEVE THE FABRICATOR OF THE RESPONSIBILITY ASSIGNED
TO HIM FOR THE DESIGN AND DETAILING OF CONNECTIONS ASSIGNED TO HIM, NOR
FOR THE ACCURACY OF DIMENSIONS ON THE SHOP DRAWINGS, NOR FOR GENERAL FIT
UP OF PARTS TO BE ASSEMBLED IN FIELD.
7.19. PARAGRAPHS 7.2 THROUGH 7.6 OF THE AISC CODE OF STANDARD PRACTICE SHALL BE
SUPERSEDED AS FOLLOWS: ALL REFERENCES TO "OWNER" SHALL BE REPLACED
WITH REFERENCES TO "CONTRACTOR".
7.20. EXPANSION BOLTS SHALL PROVIDE A MINIMUM SAFETY FACTOR OF FOUR (4) TIMES
THE FOLLOWING MINIMUM SERVICE LOAD CAPACITIES, U.N.O.
SLEEVE ANCHORS (2000 PSI MASONRY) WEDGE ANCHORS (3000 PSI CONCRETE)
DIA. SHEAR TENSION DIA. SHEAR TENSION
1/4" 270 LB. 300 LB. 1/2" 1950 LB. 1250 LB.
1/2" 930 LB. 600 LB. 3/4" 3750 LB. 2250 LB.
No. Description Date
3/4"
(3)#5 CONT.
GRADE OR
SIDEWALK
OUTLINE OF EQUIPMENT
M
IN
2'
0"
3/ 4"
1'
0"
1' - 6" 1' - 0"
(2)#5 CONT.
#4@12" O.C.
4'-0"
#4@12" O.C.
EA. T&B
1' - 0"
1'-0" @ GRADE
6" MIN. @ SIDEWALK
PAINT12" WIDE STRIP SAFETY
YELLOW AROUND PERIMETER
COORD. W/MEP
C5
SS002
C O
O R
D . W
/M E
P th re e i n c h e s o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t 1 2 3 4 5
Drawing Title:Seal:
FULLY SPRINKLERED
ARCHITECT / ENGINEERS:
Project Title:
Date:
Project Number:
Drawing Number:
Drawn:Checked:
Building Number:
D C
B A
Revisions:
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
P 704.814.1320 F 704.321.0833
Project Phase:
D C
B A
1 2 3 4 5 6
Location:
CONSULTANTS:
Office of
Construction and Facilities
Management
MAIN OFFICE
502-14-102V
ALEXANDRIA VA HEALTH CARE SYSTEM
PINEVILLE, LA
LRSPC Project No. 17020
\\lrs-dc\Dwgfiles\17DWGS\17020 VAMC Alexandria\Struct\Revit 16\16009 A Central_struc_LRSPC - NEW.rvt
HDG PROJECT: 16009 SS002
STRUCTURAL GENERAL NOTES
BID DOCUMENTS
REPLACE BOILER PLANT &
STEAM DISTRIBUTION
SYSTEM
JUNE 14, 2019 RJMMSR
8.0. STEEL DECK:
8.1. STEEL DECKS SHALL HAVE THE DEPTHS, MINIMUM GAGES, AND PROPERTIES SHOWN
BELOW. DECK HAS BEEN SELECTED BASED ON A MINIMUM THREE SPAN CONDITION.
SUPPLIER SHALL EVALUATE THE ABILITY OF HIS STEEL DECK TO ACCOMMODATE THE
LOAD CONDITIONS INDICATED IN THE GENERAL NOTES FOR ALL SPAN CONDITIONS
REQUIRED FOR HIS PROPOSED DETAILING. WHERE SUPPLIER DETAILS SINGLE OR
TWO SPAN CONDITIONS ON HIS SHOP DRAWINGS DECK WITH A GREATER THICKNESS
MAY BE REQUIRED SUBJECT TO APPROVAL BY THE COR.
DECK TYPE DEPTH GAGE "I" /FT. "SP"/FT. "SN"/FT. FY
TYPE "B" ROOF DECK 1 1/2" 20 GA. .210 IN. .232 IN. .245 IN. 33 KSI
TYPE "C" FORM DECK 9/16" 24 GA. .017 IN. .056 IN. .056 IN. 60 KSI
8.2. STEEL DECK AT ROOFS SHALL BE GALVANIZED PER ASTM A525 G60.
8.3 STEEL DECK USED FOR SUPPORT OF FLOOR SLABS SHALL BE PRIMER PAINTED ONLY.
8.4. STEEL ROOF DECK:
A. STEEL ROOF DECK SHALL BE DESIGNED TO FUNCTION AS A DIAPHRAGM FOR
TRANSMISSION OF LATERAL LOADS. CONNECTIONS OF DECK UNITS TO EACH OTHER
AND TO SUPPORTS SHALL BE DESIGNED BY THE DECK MANUFACTURER CONSISTENT
WITH THE DECK PROPERTIES AND SHALL BE DESIGNED TO TRANSMIT A SHEAR
FORCE PER LINEAL FOOT AT THE DIAPHRAGM BOUNDARIES DENOTED AS "Q=XX PLF"
(MINIMUM 200 PLF) WHERE SHOWN ON THE DRAWINGS.
B. FASTEN STEEL ROOF DECK UNITS TO STEEL SUPPORTING MEMBERS BY NOT LESS
THAN 5/8" DIAMETER FUSION WELDS OR ELONGATED WELDS OF EQUAL PERIMETER.
ALTERNATIVELY, FASTEN WITH "HILTI" X-ENP-19, X-EDN19 OR X-EDNK22
FASTENERS CONFORMING TO THE REQUIREMENTS OF THE "HILTI" PUBLISHED
INSTALLATION INSTRUCTIONS. ATTACHMENTS SHALL BE SPACED NOT MORE THAN
12" O/C. AT EVERY SUPPORT AND AT CLOSER SPACINGS WHERE REQUIRED FOR
DIAPHRAGM SHEAR RESISTANCE.
C. FOR STEEL ROOF DECK SPANS EXCEEDING 5'-0", MECHANICALLY FASTEN SIDE
LAPS AT MID-SPAN USING "HILTI" #10 SELF-TAPPING SCREW OR "HILTI" S-SLC01
OR S-SLC02 SIDELAP CONNECTORS AS SHOWN ON DRAWINGS. PROVIDE ADDITIONAL
SIDELAP FASTENERS WHERE REQUIRED FOR LATERAL FORCE RESISTANCE.
D. DO NOT HANG PIPES OR DUCTS FROM STEEL ROOF DECK.
8.5. NON-COMPOSITE STEEL FORM DECK:
A. FASTEN NON-COMPOSITE STEEL FORM DECK THINNER THAN 22 GAUGE TO STEEL
SUPPORTING MEMBERS WITH WELDING WASHERS HAVING A NOMINAL 3/8" DIAMETER
HOLE. FASTEN FORM DECK 22 GAUGE AND THICKER WITH NOT LESS THAN 5/8"
DIAMETER FUSION WELDS OR ELONGATED WELDS OF EQUAL PERIMETER. MINIMUM
ATTACHMENT SHALL BE IN CONFORMANCE WITH WELD PATTERNS A, B OR C AS
RECOMMENDED AND DESCRIBED BY THE STEEL DECK INSTITUTE FOR THE APPROPRIATE
DECK SPAN CONDITION. ALTERNATIVELY, FASTEN WITH "HILTI" X-ENP-19,
X-EDN19 OR X-EDNK22 FASTENERS CONFORMING TO THE REQUIREMENTS OF THE
"HILTI" PUBLISHED INSTALLATION INSTRUCTIONS.
B. SLOTTED, GALVANIZED, STEEL FORM DECK WITH VENTS PROVIDING A MINIMUM 1.5%
OPEN AREA SHALL BE PROVIDED AT ALL AREAS WITH LIGHTWEIGHT VERMICULITE
CONCRETE ROOF TOPPINGS.
C. DO NOT HANG PIPES OR DUCTS FROM VERMICULITE ROOF SYSTEM.
D. FASTEN NON-COMPOSITE STEEL FORM DECK TO LIGHTGAGE STEEL FRAMING MEMBERS
WITH SCREWS OF SIZE AND SPACING NECESSARY TO ACHIEVE A MINIMUM DIAPHRAGM
SHEAR CAPACITY OF 100 POUNDS PER LINEAL FOOT BASED ON THE MINIMUM
CAPACITY OF EITHER THE FORM DECK OR THE LIGHTGAGE FRAMING MEMBERS.
8.6. STEEL DECK SUBMITTALS: STEEL DECK MANUFACTURER SHALL SUBMIT SHOP DRAWINGS
FOR REVIEW AND ACCEPTANCE BY THE COR INDICATING DECK TYPE,
GAUGE AND PROTECTIVE TREATMENT, AS WELL AS TYPE, SIZE AND LAYOUT OF DECK
CONNECTIONS.
8.7. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION AND
SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING RESPONSIBILITY FOR
DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER TRADES.
8.8. SUBMIT THREE (3) 24" X 36" PRINTS OF EACH SHOP DRAWING FOR REVIEW.
SEE PROJECT SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
8.9. ALTERNATIVELY, WHERE ACCEPTABLE TO COR, DRAWINGS MAY BE ELECTRONICALLY
SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED. REVIEW COMMENTS ONLY
WILL BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
8.10. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
9.0 STEEL JOISTS:
9.1. ALL STEEL JOISTS SHALL BE DESIGNED, FABRICATED, AND ERECTED IN ACCORDANCE
WITH THE SJI SPECIFICATIONS.
9.2. JOIST ENDS SHALL BE FIXED AND BRIDGING SHALL BE PLACED PRIOR TO APPLICATION
OF ANY LOADS.
9.3. END SUPPORT:
A. MINIMUM BEARING REQUIREMENTS SHALL BE IN ACCORDANCE WITH THE SJI
SPECIFICATION. EXTENDED JOIST ENDS FOR BEARING ON MASONRY SHALL BE
PROVIDED BY THE JOIST MANUFACTURER WHERE REQUIRED TO ACCOMMODATE
BEARING CONDITIONS SHOWN ON THE DRAWINGS.
B. K SERIES JOISTS SHALL BE WELDED TO SUPPORTS WITH 1/8" FILLET WELDS,
ONE EACH SIDE, 2" LONG.
C. JOISTS SHALL BE WELDED TO SUPPORTS AS FOLLOWS U.N.O.:
K SERIES: 1/8" FILLET WELDS, ONE EACH SIDE, 2" LONG
D. K SERIES JOISTS AT COLUMN CENTERLINES SHALL BE BOLTED TO STRUCTURAL
STEEL SUPPORTS WITH 2 @ 1/2" DIAMETER BOLTS (MINIMUM). WHERE JOISTS
DO NOT SPACE ON CENTERLINES, BOLT CONNECTIONS FOR EACH JOIST ADJACENT
TO CENTERLINE.
E. BOLT JOISTS AS INDICATED BELOW TO STRUCTURAL STEEL SUPPORTS AT COLUMN
CENTERLINES OR BOLT CONNECTIONS FOR EACH JOIST ADJACENT TO CENTERLINE.
K SERIES: 2 @ 1/2" DIAMETER BOLTS (MINIMUM)
9.4. JOIST BRIDGING:
A. SHALL BE PLACED PER THE SJI SPECIFICATION U.N.O. AND SHALL BE:
K SERIES: HORIZONTAL RODS OR ANGLES AT TOP & BOTTOM CHORDS
B. BRIDGING THAT TERMINATES AT OR IS INTERRUPTED BY STRUCTURAL STEEL
MEMBERS, SHALL BE WELDED OR BOLTED THERETO. PROVIDE DIAGONAL ("X")
BRIDGING FOR ENDS OF BRIDGING LINES TERMINATING AT WALLS/BEAMS.
C. WHERE "OPEN-WEB" JOIST LENGTHS ARE 40 FEET AND LONGER, INSTALL A CENTER
ROW OF BOLTED DIAGONAL ("X") BRIDGING TO PROVIDE LATERAL STABILITY
BEFORE SLACKENING OF HOISTING LINES.
9.5. SPECIAL JOISTS:
A. JOISTS MARKED "XXKSP" (DEPTH = "XX" AS SHOWN ON PLAN) INDICATE STEEL
JOISTS SUPPORTING ROOF TOP MECHANICAL EQUIPMENT WITH LOADS SHOWN ON THE
PLAN. JOIST SUPPLIER SHALL DESIGN AND INDICATE THESE JOISTS AND LOADS
ON THE JOIST SHOP DRAWINGS SUBMITTED FOR REVIEW.
B. CONTRACTOR SHALL VERIFY THAT MECHANICAL ROOF TOP EQUIPMENT FURNISHED IS
PLACED ONLY ON DESIGNATED JOISTS (XXKSP) SUCH THAT THE DISTRIBUTION OF
OPERATING WEIGHT DOES NOT EXCEED THE DESIGN LOADS GIVEN IN PLAN.
9.6. SUBMITTALS: JOIST MANUFACTURER SHALL SUBMIT SHOP DRAWINGS INCLUDING BILLS
OF MATERIAL FOR REVIEW AND ACCEPTANCE BY THE COR. SUBMIT
CALCULATIONS FOR SPECIAL "KSP" JOISTS INDICATING SUPPLIERS CONFORMANCE WITH
SPECIFIED DESIGN CRITERIA. ALL SHOP DRAWINGS SUBMITTED SHALL BEAR THE
EMBLEM OF MEMBERSHIP OF THE STEEL JOIST INSTITUTE INDICATING SUPPLIER'S
COMPLIANCE WITH SJI SPECIFICATIONS. SHOP DRAWINGS SUBMITTED FOR JOISTS FROM
NON-SJI MEMBERS ARE NOT ACCEPTABLE AND WILL BE REJECTED.
9.7. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMISSION.
DRAWINGS SHALL BEAR THE CONTRACTOR'S APPROVAL STAMP ACCEPTING RESPONSIBILITY
FOR DIMENSIONS, QUANTITIES AND COORDINATION WITH THE OTHER TRADES.
9.8. SUBMIT THREE (3) 24" X 36" PRINTS OF EACH SHOP DRAWING FOR REVIEW. SEE
PROJECT SPECIFICATIONS FOR SPECIFIC REQUIREMENTS.
9.9. ALTERNATIVELY, WHERE ACCEPTABLE TO COR, DRAWINGS MAY BE ELECTRONICALLY
SUBMITTED, PROVIDED LEGIBILITY IS MAINTAINED. REVIEW COMMENTS ONLY WILL
BE ELECTRONICALLY FORWARDED TO THE CONTRACTOR.
9.10. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
9.11. HOLES IN JOIST CHORDS ARE NOT PERMITTED, EXCEPT AT BEARING END BOLTED
CONNECTIONS.
9.12. JOIST ENDS AT ROOF DIAPHRAGM BOUNDARIES SHALL BE CAPABLE OF TRANSMITTING
THE DIAPHRAGM BOUNDARY SHEAR PER LINEAL FOOT TIMES THE JOIST SPACING TO THE
SUPPORTING STRUCTURE. DIAPHRAGM BOUNDARY SHEARS IN EXCESS OF THE 200 PLF
MINIMUM BOUNDARY SHEAR ARE INDICATED ON THE DRAWINGS. THE JOIST
MANUFACTURER'S PRODUCT SHALL BE DESIGNED TO TRANSMIT THE BOUNDARY SHEAR
INDICATED ON THE DRAWINGS OR A MINIMUM BOUNDARY SHEAR OF 200 PLF, UNLESS
SPECIAL JOIST END CONDITIONS ARE DETAILED OTHERWISE ON THE DRAWINGS.
9.13. JOISTS SHALL BE STOCKPILED IN A VERTICAL POSITION RESTING ON EITHER TOP OR
BOTTOM CHORDS AND KEPT FREE OF MUD AND DIRT.
9.14. NO JOISTS WHICH ARE DAMAGED, KINKED, BENT OR HAVE BROKEN WELDS SHALL BE
PLACED IN THE STRUCTURE. THE ERECTOR SHALL CULL ALL SUCH JOISTS.
10.0. STRUCTURAL MASONRY:
10.1. ALL STRUCTURAL MASONRY SHALL CONFORM TO MOST CURRENT ACI 530 STANDARDS AS
APPROPRIATE TO THE MATERIAL.
10.2. MASONRY STRENGTH AND GRADE:
A. CONCRETE MASONRY UNITS (CMU):
I. UNITS SHALL BE LIGHTWEIGHT CELLULAR UNITS CONFORMING TO ASTM C 90,
GRADE N-2. CONCRETE MASONRY NET AREA UNIT STRENGTH SHALL BE NO LESS
THAN 1900 PSI IN ACCORDANCE WITH ASTM C 140, WITH A UNIT WEIGHT NOT
EXCEEDING 105 PCF. SEE SPECIFICATIONS.
II. DESIGN COMPRESSIVE STRENGTH OF CMU (F'M) = 2500 PSI.
10.3. SUBMITTALS: CONTRACTOR SHALL SUBMIT FOR APPROVAL TEST REPORTS ON MASONRY
UNITS SHOWING UNIT WEIGHT, COMPRESSIVE STRENGTH, ABSORPTION, VOLUME
CHANGE AND SHRINKAGE PER ASTM C90 NO LATER THAN 15 WORKING DAYS PRIOR TO
THE COMMENCEMENT OF MASONRY CONSTRUCTION.
10.4. MORTAR SHALL CONFORM TO ASTM C 270. MORTAR SHALL BE TYPE "S" AND SHALL
HAVE A 28-DAY COMPRESSIVE STRENGTH OF 3750 PSI.
10.5. MASONRY GROUT FILL SHALL CONFORM TO ASTM C 476. GROUT, EITHER FINE OR
COARSE AGGREGATE PER SPECIFICATIONS, SHALL HAVE A 28-DAY COMPRESSIVE
STRENGTH OF 3000 PSI. MASONRY CONCRETE FILL SHALL CONFORM TO THE
REQUIREMENTS NOTED UNDER "CONCRETE" IN THE GENERAL NOTES.
10.6. GROUTING:
A. ALL BOND BEAMS SHALL BE FILLED WITH GROUT AND REINFORCED AS
INDICATED ON THE DRAWINGS (DETAILS OR SCHEDULES). MORTAR FILL IS
NOT PERMITTED.
B. ALL MASONRY WALL CELLS OR CAVITIES INDICATED AS REINFORCED SHALL BE
GROUTED FOR THE FULL HEIGHT OF THE WALL, UNLESS SPECIFICALLY NOTED
OTHERWISE ON THE DRAWINGS. UN-REINFORCED WALLS INDICATED AS GROUTED
SHALL BE GROUTED FULL HEIGHT, UNLESS SPECIFICALLY NOTED OTHERWISE.
MORTAR FILL IS NOT PERMITTED.
C. ALL MASONRY CELLS OR CAVITIES BELOW GRADE SHALL BE GROUTED SOLID
UNLESS SPECIFICALLY NOTED OTHERWISE ON THE DRAWINGS. MORTAR FILL IS
NOT PERMITTED.
D. VERTICAL GROUTING SHALL BE LOW LIFT OR HIGH LIFT AS FOLLOWS:
I. LOW LIFT GROUTING SHALL BE USED FOR ALL CAVITY WALLS AND MAY BE
USED FOR ALL WALLS AT THE OPTION OF THE CONTRACTOR. LIFTS SHALL
NOT EXCEED 4'-0" IN HEIGHT.
II. HIGH LIFT GROUTING IS PERMISSIBLE ONLY FOR FILLING OF CELLULAR
MASONRY UNITS AND SHALL NOT EXCEED ONE STORY IN HEIGHT. CLEAN
OUT HOLES SHALL BE PROVIDED AT THE BASE OF EACH GROUTED CELL.
E. GROUTING SHALL BE STOPPED 1-1/2" BELOW THE TOP OF A COURSE TO FORM A
KEY AT THE JOINT.
F. GROUTING OF MASONRY BEAMS OR LINTELS SHALL BE DONE IN ONE CONTINUOUS
OPERATION.
10.7. REINFORCING:
A. ALL BARS MARKED "CONTINUOUS" SHALL BE LAPPED PER "CMU MASONRY LAP SPLICE
SCHEDULE" SHOWN ON THE STRUCTURAL DRAWINGS AND MUST COMPLY WITH THE
MOST CURRENT EDITION OF THE APPLICABLE BUILDING CODE.
B. FOUNDATION DOWELS MAY SLOPE A MAXIMUM OF 1:6 TO ALIGN WITH WALL
CAVITIES OR VERTICAL CMU CORES. GREATER SLOPES WILL REQUIRE
REPLACEMENT OF THE FOUNDATION DOWELS.
C. SPLICED REINFORCING SHALL BE LAPPED UNDER "REINFORCING" ABOVE OR AS
SHOWN ON DRAWINGS, WHICHEVER IS GREATEST. ALL SPLICES SHALL BE WIRED
TOGETHER OR HELD IN PLACE WITH BAR POSITIONERS.
D. VERTICAL REINFORCING BARS SHALL HAVE A MINIMUM CLEARANCE OF 3/4"
FROM MASONRY AND SHALL BE HELD IN POSITION TOP AND BOTTOM AND AT
INTERVALS NOT EXCEEDING 4'-0". ACCESSORIES FOR SUCH SUPPORT SHALL
BE USED. PROVIDE "AA WIRE PRODUCTS COMPANY" (OR APPROVED EQUAL) REBAR
POSITIONER AA225 OR AA239 FOR VERTICAL BARS AND AA238 FOR HORIZONTAL
BARS OR APPROVED EQUAL PRODUCTS FROM OTHER SUPPLIERS.
E. HORIZONTAL JOINT REINFORCING SHALL BE LAPPED NO LESS THAN 6" ALL
SPLICES, INCLUDING CORNERS AND TEES WHERE NO CONTROL JOINT IS USED.
F. ALL HORIZONTAL JOINT REINFORCING SHALL STOP AT CONTROL JOINTS.
G. HORIZONTAL REINFORCING IN BOND BEAMS SHALL BE CONTINUOUS THROUGH
CONTROL JOINTS.
10.8. MASONRY SHOWN ON THE STRUCTURAL DRAWINGS DEFINES THE STRUCTURAL EXTENTS
AND REQUIREMENTS FOR MASONRY FOR SUPPORTING MEMBERS, FLOORS, ROOFS OR
WALLS AND SHALL BE BUILT IN CONFORMANCE WITH THE REQUIREMENTS OF THESE
DRAWINGS AND NOTE 1 ABOVE. REFER TO THE ARCHITECTURAL DRAWINGS FOR
THE TOTAL SCOPE OF THE MASONRY AND FOR LOCATIONS AND DETAILS OF OPENINGS,
SPECIAL COURSING OR OTHER MASONRY DETAILS.
10.9. MASONRY CONTRACTOR SHALL PROVIDE FOR AND COORDINATE WITH OTHER TRADES
FOR PLACEMENT OF ALL ITEMS TO BE EMBEDDED OR BUILT INTO THE MASONRY.
10.10. ELECTRICAL CONDUIT, OR EQUIPMENT FROM OTHER TRADES, SHALL NOT OCCUR IN
GROUTED AND REINFORCED CELLS. WHERE CONFLICTS OCCUR THE CONTRACTOR SHALL
NOTIFY THE ENGINEER FOR DIRECTION PRIOR TO PROCEEDING.
14.5. NO OPENINGS NOR ANY CHANGES IN SIZE, DIMENSION OR LOCATION SHALL BE MADE
IN ANY STRUCTURAL ELEMENTS WITHOUT WRITTEN APPROVAL OF THE STRUCTURAL
ENGINEER.
14.6. OPENINGS 1'-0" OR LESS ON A SIDE ARE GENERALLY NOT SHOWN ON THE STRUCTURAL
DRAWINGS. REFER TO DRAWINGS OF OTHER CONSULTANTS FOR SUCH OPENINGS.
14.7. FIREPROOFING OF STRUCTURAL ELEMENTS IS NOT SHOWN ON THE STRUCTURAL
DRAWINGS. REFER TO THE SPECIFICATIONS AND ARCHITECTURAL DRAWINGS FOR FIRE
RATING REQUIREMENTS, MATERIALS AND METHODS.
14.8. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD
IMPOSED ON THE STRUCTURE. SUCH LOADS SHALL NOT EXCEED THE CAPACITY OF THE
STRUCTURE AT ANY TIME.
14.9. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION, AND ANY
TEMPORARY BRACING OR SUPPORT REQUIRED TO ACCOMMODATE THE CONTRACTOR'S
MEANS AND METHODS ARE THE RESPONSIBILITY OF THE CONTRACTOR.
14.10. THE CONTRACTOR SHALL INFORM THE STRUCTURAL ENGINEER, CLEARLY AND
EXPLICITLY IN WRITING, OF ANY DEVIATION OR SUBSTITUTION OF REQUIREMENTS
OF THE CONTRACT DOCUMENTS. CONTRACTOR IS NOT RELIEVED OF ANY REQUIREMENTS
OF THE CONTRACT DOCUMENTS BY VIRTUE OF THE STRUCTURAL ENGINEER'S REVIEW
OF SHOP DRAWINGS, PRODUCT DATA, ETC., UNLESS THE CONTRACTOR HAS CLEARLY
AND EXPLICITLY INFORMED THE STRUCTURAL ENGINEER IN WRITING OF ANY
DEVIATIONS OR SUBSTITUTIONS AT TIME OF SUBMISSION, AND THE STRUCTURAL
ENGINEER HAS GIVEN WRITTEN APPROVAL FOR THE SPECIFIC DEVIATIONS OR
SUBSTITUTIONS.
14.11. ALL THINGS WHICH, IN THE OPINION OF THE CONTRACTOR, APPEAR TO BE
DEFICIENCIES, OMISSIONS, CONTRADICTIONS OR AMBIGUITIES IN THE DRAWINGS OR
SPECIFICATIONS, SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL
ENGINEER. CORRECTIONS OR WRITTEN INTERPRETATIONS SHALL BE ISSUED BEFORE
AFFECTED WORK MAY PROCEED.
14.12. IF THE CONTRACTOR CANNOT CONSTRUCT ANY PORTION OF THE WORK IDENTIFIED IN
THE DRAWINGS IN ACCORDANCE WITH THESE DRAWINGS AND SPECIFICATIONS, THEN
THE CONTRACTOR IS RESPONSIBLE FOR CONTACTING THE STRUCTURAL ENGINEER PRIOR
TO PROCEEDING WITH THE WORK. WORK THAT DOES NOT COMPLY WITH THE DRAWINGS
MAY REQUIRE REMOVAL, TESTING, OR ENGINEERING EVALUATION AT THE
CONTRACTOR'S EXPENSE.
14.13. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO ORDERING
MATERIALS OR PROCEEDING WITH NEW WORK IN AREAS AFFECTED BY EXISTING
CONDITIONS. STRUCTURAL ENGINEER SHALL BE INFORMED IN WRITING OF
CONFLICTS BETWEEN EXISTING AND PROPOSED NEW CONSTRUCTION.
14.14 CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL DIMENSIONS SHOWN ON THE
CONTRACT DOCUMENTS. INCONSISTENCIES ON THE STRUCTURAL DRAWINGS OR
BETWEEN THE STRUCTURAL DRAWINGS AND ANY OTHER CONTRACT, SHOP, FABRICATION,
OR OTHER DRAWINGS OR INFORMATION SHALL BE BROUGHT TO THE ATTENTION OF THE
STRUCTURAL ENGINEER PRIOR TO PROCEEDING WITH AFFECTED WORK.
14.15. DO NOT SCALE THESE DRAWINGS, USE THE DIMENSIONS SHOWN.
14.16. CONTRACTOR SHALL PROVIDE IN HIS SCHEDULE FOR A SHOP DRAWING REVIEW AND
RETURN TIME OF A MINIMUM OF FIFTEEN (15) WORKING DAYS IN THE STRUCTURAL
ENGINEER'S OFFICE.
15.0 STRUCTURAL ABBREVIATIONS:
ABBREV. DEFINITION ABBREV. DEFINITION
A.B. ANCHOR BOLTS HOF HORIZONTAL OUTER FAC
ABV ABOVE HK HOOK
ADDNL ADDITIONAL HORZ HORIZONTAL
AFF ABOVE FINISHED FLOOR IF INNER FACE
ALT ALTERNATE INT INTERIOR
ARCH ARCHITECTURAL JT JOINT
B, BOT BOTTOM K KIPS (1000 LBS)
B/XXX BOTTOM OF XXX L, LEN LENGTH
BAL. BALANCE LAT LATERAL
BB BOND BEAM LBS POUNDS
BCX BOTTOM CHORD EXTENSION LE LEFT END
BL BRICK LEDGE LLH LONG LEG HORIZONTAL
BLDG BUILDING LLO LONG LEG OUTSTANDING
BLW BELOW LLV LONG LEG VERTICAL
BM BEAM LONG LONGITUDINAL
BRG BEARING MAS MASONRY
BRK BRICK MAX MAXIMUM
MCJ MASONRY CONTROL JOINT
BTWN BETWEEN MECH MECHANICAL
CJ CONST., CONTROL JOINT MFR MANUFACTURER
CL,CLR CLEAR MIN MINIMUM
CMU CONC. MASONRY UNIT MTL METAL
COL COLUMN NOM NOMINAL
CONC CONCRETE OC, O/C ON CENTER
CONN CONNECTION OF OUTER FACE, OPP. FACE
CONST CONSTRUCTION OH OPPOSITE HAND
CONT CONTINUOUS OPP OPPOSITE
CTR CENTER OPNG OPENING
CTRD CENTERED PC PRECAST
DBA DEFORMED BAR ANCHOR PL PLATE
DET,DTL DETAIL RE RIGHT END
DIM DIMENSION REINFG REINFORCING
DK DECK REINF REINFORCEMENT
DWGS DRAWINGS REQD REQUIRED
DWL DOWEL RET RETAINING
EA EACH SOG SLAB ON GRADE
EE EACH END SC SLIP CRITICAL
EF EACH FACE SCHED SCHEDULE
EFF EFFECTIVE SECT SECTION
EJ EXPANSION JOINT S, SHRT SHORT
EL,ELEV ELEVATION SL SLAB
EOC EDGE OF CONCRETE SPA SPACING
EOD EDGE OF DECK STFNR STIFFENER
EOM EDGE OF MASONRY STL STEEL
EOS EDGE OF SLAB SUPPL SUPPLIER
ES EACH SIDE SUPT SUPPORT
EW EACH WAY T TOP
EXIST EXISTING T/XXX TOP OF XXX
EXP EXPANSION TCX TOP CHORD EXTENSION
EXT EXTERIOR, EXTENSION THK THICK, THICKNESS
FK FOOT-KIPS TO THROUGHOUT
FL, FLR FLOOR TRAN TRANSVERSE
FOB FACE OF BRICK TYP TYPICAL
FOM FACE OF MASONRY UNO UNLESS NOTED OTHERWISE
FOS FACE OF STUD VERT VERTICAL
FP FULL PENETRATION VEF VERTICAL EACH FACE
FT FOOT, FEET VIF VERTICAL INNER FACE
FTG FOOTING VOF VERTICAL OUTER FACE
GB GRADE BEAM W WIDE, WIDTH
GEN GENERAL WF WELDED WIRE FABRIC
HEF HORIZONTAL EACH FACE WWM WELDED WIRE MAT
HIF HORIZONTAL INNER FACE XE EXTENDED END JOIST
11.0 LIGHT GAGE STEEL FRAMING:
11.1. ALL MEMBERS SHALL BE DESIGNED IN ACCORDANCE WITH THE MOST RECENT EDITION
OF THE AMERICAN IRON AND STEEL INSTITUTE (AISI) "SPECIFICATION FOR THE
DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS".
11.2. ALL FRAMING MEMBERS SHALL BE FORMED FROM CORROSION-RESISTANT STEEL,
CORRESPONDING TO THE REQUIREMENTS OF ASTM A653, WITH A MINIMUM YIELD
STRENGTH OF 50 KSI FOR MEMBERS WITH THICKNESSES OF 54 MILS AND HIGHER AND
33 KSI FOR MEMBERS WITH THICKNESSES OF 33 AND 43 MILS.
11.3. ALL MEMBERS SHOWN ARE STANDARD DESIGNATIONS OF "STEEL STUD MANUFACTURERS
ASSOCIATION".
11.4. MEMBERS INDICATED ON THE STRUCTURAL DRAWINGS ARE BASED ON MINIMUM
PROPERTIES OF PRODUCTS PRODUCED BY "STEEL STUD MANUFACTURERS ASSOCIATION".
SUBSTITUTION OF MATERIALS IS ACCEPTABLE,…