TEC Modernization & Addition Technical Specifications Summary

This document comprises the detailed technical specifications for the TEC Modernization & Addition project (Contract No. 2026-1683) located at 20234 Mack Street, Hayward, California, issued by AC Transit for a zero-emission bus facility modernization. The project involves renovation and expansion of an existing Training and Education Center, including approximately 1,164 square feet of second-floor renovation within the existing building envelope and a new 1,350-square-foot building addition. Scope includes upgrading existing bus maintenance bays to hydrogen-safe configurations for fuel cell bus servicing, installing a new mezzanine level, adding canopy coverage, replacing paving at main entrances, and reconfiguring interior spaces including lobbies, offices, and classrooms. The specifications detail work across 32 construction divisions covering selective demolition, concrete work, structural steel, thermal and moisture protection, openings, finishes, specialties, equipment, conveying systems, fire suppression, plumbing, HVAC, electrical systems, communications, and exterior improvements. Design professionals of record include Architect Loretto Seles (C37354), Structural Engineer Josh Gebelein (S5015), Fire-Protection Engineer Rich Silva (38104), Mechanical Engineers Rich Silva for plumbing and Steve Lian (M42470) for HVAC, and Electrical Engineer Kiran Upadhyay (E21415).

The specifications establish detailed requirements for materials, products, execution standards, and quality control across all construction trades, with emphasis on compliance with ACI standards for concrete work, ASTM International standards for materials testing, and ACI certification requirements for concrete field personnel. Special inspection and field quality control testing will be performed by an independent testing agency acceptable to authorities having jurisdiction, with requirements for preconstruction mixture testing, daily concrete strength verification, and documented inspections of formwork, reinforcement placement, and finishing work. The contract includes provisions for managing construction joints, vapor retarders, concrete curing methods, and repair procedures, with specific tolerances referenced to ACI 117 standards. Environmental considerations include cold and hot-weather concreting procedures, waste management, and protection of existing utilities and facilities. FTA-funded capital improvements indicate federal funding involvement, though the specifications document does not detail pricing, bid amounts, set-asides, or contract term information.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TEC MODERNIZATION & ADDITION

DETAILED (100%) DESIGN

HAYWARD, CA

CONTRACT NO. 2023-1586

SPECIFICATIONS

REVISION 0

December 2025

(THIS PAGE INTENTIONALLY LEFT BLANK)

TEC Modernization and Addition Project #: 2026-1683

SEALS PAGE 03 10 00

DOCUMENT 00 01 07

SEALS PAGE

1.1 DESIGN PROFESSIONALS OF RECORD

Architect:

Loretto Seles.

C37354.

Responsible for the following Sections:

02 41 19 SELECTIVE DEMOLITION

03 53 00 CONCRETE TOPPING

05 01 70.63 DECORATIVE METAL REFINISHING

05 12 13 ARCHITECTURALLY EXPOSED STRUCTURAL STEEL FRAMING

05 50 00 METAL FABRICATIONS

05 51 19 METAL GRATING STAIRS

05 52 13 METAL RAILINGS

07 14 16 COLD FLUID-APPLIED WATERPROOFING

07 21 00 BUILDING INSULATION

07 25 00 WEATHER BARRIERS

07 46 19 STEEL SIDING

07 54 23 THERMOPLASTIC POLYOLEFIN (TPO) ROOFING

07 62 00 SHEET METAL FLASHING AND TRIM

07 71 00 ROOF SPECIALTIES

07 72 00 ROOF ACCESSORIES

07 84 13 PENETRATION FIRESTOPPING

07 84 43 JOINT FIRESTOPPING

07 92 00 JOINT SEALANTS

07 95 13.13 INTERIOR EXPANSION JOINT COVER ASSEMBLIES

07 95 13.16 EXTERIOR EXPANSION JOINT COVER ASSEMBLIES

08 11 13 STEEL DOORS AND FRAMES

08 31 13 ACCESS DOORS AND FRAMES

08 33 23 OVERHEAD COILING DOORS

08 35 13 FOLDING DOORS

08 44 13 GLAZED ALUMINUM CURTAIN WALLS

08 45 23 FIBERGLASS-SANDWICH-PANEL ASSEMBLIES

08 51 13 ALUMINUM WINDOWS

L I C E N S E D A R C H I T E C T

S T A T E O F C A L I F O R

N I A

LO

RETTO S SELES

C37354

RE N . 8 - 31-27

00 01 07 SEALS PAGE

08 71 00 DOOR HARDWARE

08 80 00 GLAZING

08 88 13 FIRE-RATED GLAZING

08 91 19 FIXED LOUVERS

09 21 16 GYPSUM BOARD ASSEMBLIES

09 22 16 NON-LOAD-BEARING STEEL FRAMING

09 30 13 CERAMIC TILING

09 51 00 ACOUSTICAL CEILINGS

09 62 29 CORK FLOORING

09 65 13 RUBBER WALL BASE

09 65 19 RESILIENT TILE FLOORING

09 68 13 TILE CARPETING

09 84 33 SOUND-ABSORBING WALL UNITS

09 84 36 SOUND-ABSORBING CEILING UNITS

09 90 00 PAINTING AND COATING

09 96 00 HIGH PERFORMANCE COATINGS

10 14 00 SIGNAGE

10 14 26 POST AND PANEL/PYLON SIGNAGE

10 21 13 METAL TOILET COMPARTMENTS

10 22 23.23 MOVABLE PANEL SYSTEM

10 28 00 TOILET AND BATH ACCESSORIES

10 44 00 FIRE PROTECTION SPECIALTIES

10 56 29 STORAGE RACKS-HEAVY GOODS

10 73 00 STRUCTURAL CANOPY SYSTEM

11 11 39 BUS ROOF WORKING PLATFORM-CATWALK

14 21 23 ELECTRIC TRACTION PASSENGER ELEVATORS

14 24 13 HYDRAULIC FREIGHT ELEVATORS

31 20 00 EARTH MOVING

31 23 19 DEWATERING

32 13 16 DECORATIVE CONCRETE PAVING

32 13 73 CONCRETE PAVING JOINT SEALANTS

32 93 00 PLANTS

Structural Engineer:

Josh Gebelein

S5015.

Responsible for the following Sections:

03 10 00 CONCRETE FORMING AND ACCESSORIES

03 20 00 CONCRETE REINFORCING

03 30 00 CAST-IN-PLACE CONCRETE

05 12 00 STRUCTURAL STEEL FRAMING

05 31 00 STEEL DECKING

05 40 00 COLD FORMED METAL FRAMING

05 53 13 BAR GRATING

06 10 00 ROUGH CARPENTRY

06 16 00 SHEATHING

06 17 15 ENGINEERED STRUCTURAL WOOD

31 63 29 DRILLED CONCRETE PIERS AND SHAFTS

Fire-Protection Engineer:

Rich Silva.

38104

Responsible for the following Sections:

21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION

21 05 23 GENERALD-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING

21 05 29 HANGERS AND SUPPORT FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT

21 05 48 VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING AND

EQUIPMENT

21 05 53 IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT

21 10 00 WATER-BASED FIRE-SUPPRESSION SYSTEMS

Signed Dec 23, 2025

01/07/2026

260107-066

Sensitive

NOT USED

Mechanical Engineer, Plumbing:

Rich Silva.

38104.

Responsible for the following Sections:

22 05 00 COMMON WORK RESULTS FOR PLUMBING

22 05 23 GENERAL DUTY VALVES FOR PLUMBING SUPPORT

22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

22 05 48 VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

22 05 53 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

22 05 93 TESTING, ADJUSTING, AND BALANCING FOR PLUMBING

22 07 19 PLUMBING PIPING INSULATION

22 11 16 DOMESTIC WATER PIPING

22 11 19 DOMESTIC WATER PIPING SPECIALITIES

22 13 16 SANITARY WASTE AND VENT PIPING

22 13 19 SANITARY WASTE PIPING SPECIALTIES

22 13 19.13 SANITARY DRAINS

22 14 14 STORM DRAINAGE PIPING

22 14 23 STORM DRAINAGE PIPING SPECIALITIES

22 42 00 COMMERCIAL PLUMBING FIXTURES

22 47 00 DRINKING FOUNTAINS AND WATER COOLERS

NOT USED

01/07/2026

260107-067

Mechanical Engineer, HVAC:

Steve Lian.

M42470.

Responsible for the following Sections:

23 01 30.52 EXISTING HVAC AIR DISTRIBUTIONSYSTEM CLEANING

23 05 00 COMMON WORK RESULTS FOR HVAC

23 05 29 HANGARS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

23 05 48 VIBRATION AND SEISMIC CONTROLS FOR HVAC

23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 07 13 DUCT INSULATION

23 07 19 HVAC PIPING INSULATION

23 09 01 HVAC CONTROLS

23 23 00 REFRIGERANT PIPING

23 31 13 METAL DUCTS

23 33 00 AIR DUCT ACCESSORIES

23 33 46 FLEXIBLE DUCTS

23 34 00 HVAC FANS

23 36 00 AIR TERMINAL UNITS

23 37 13.13 AIR DIFFUSERS

23 37 13.23 REGISTERS AND GRILLES

23 41 00 PARTICULATE AIR FILTERS

23 72 19 FIXED PLATE AIR-TO-AIR ENERGY RECOVERY UNITS

23 72 23.29 PACKAGED, LARGE-CAPACITY, ROOFTOP AIR-CONDITIONING UNITS

23 74 14 MODULAR DX ROOFTOP UNITS

23 81 29 VARIABLE REFRIGERANT-FLOW HVAC SYSTEMS

Sensitive

Electrical Engineer:

Kiran Upadhyay

E21415.

Responsible for the following Sections:

26 05 19 LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

26 05 33.13 CONDUITS FOR ELECTRICAL SYSTEMS

26 05 43 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS

26 05 48 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS

26 08 00 COMMISSIONING OF ELECTRICAL SYSTEMS

26 27 26 WIRING DEVICES

26 50 00 LIGHTING

27 05 28 PATHWAYS FOR COMMUNICATIONS SYSTEMS

27 15 13 COMMUNICATIONS COPPER HORIZONTAL CABLING

27 21 33 DATA COMMUNICATIONS WIRELESS ACCESS POINTS

27 41 00 AUDIO-VIDEO SYSTEMS

28 46 21.11 ADDRESSABLE FIRE ALARM SYSTEMS

END OF DOCUMENT 00 01 07

EG

AT

FOET

Exp.

S

RE

IN

OFILAC

R

A

RE

FORP

RE

SI

T

DE

NOISSE

N

NI

G

LA

E

No. E21415 03/31/26

EL ECT I CR

AL

K

IR

AN

KUMAR UPADHYAY

TABLE OF CONTENTS 00 01 10

DIVISION 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS

00 01 01 PROJECT TITLE PAGE

00 01 07 SEALS PAGE

00 01 10 TABLE OF CONTENTS

00 01 15 LIST OF DRAWINGS

00 01 20 LIST OF PROCUREMENT SCHEDULES

00 11 13 NOTICE INVITING BIDS

00 21 13 INSTRUCTIONS TO BIDDERS

00 25 13 PREBID MEETING

00 31 46 PERMITS

00 40 00 PROCUREMENT FORMS AND SUPPLEMENTS

00 41 13 BID FORM

00 52 13 CONTRACT FORM

00 60 00 PROJECT FORMS

00 61 13 PERFORMNCE AND PAYMENT BOND FORMS

00 62 11 SUBMITTAL REVIEW TRANSMITTAL

00 62 76 APPLICATION AND CERTIFICATION FOR PAYMENT

00 62 83 FOUR WEEK LOOK AHEAD SCHEDULE

00 63 25 SUBSTITUTION REQUEST FORM

00 63 36 FIELD CHANGE NOTICE FORM

00 63 63 CONTRACT CHANGE ORDER FORM

00 63 64 DAILY EXTRA WORK REPORT

00 63 65 ALLOWANCE DRAW AUTHORIZATION FORM

00 65 16 CERTIFICATE OF SUBSTANTIAL COMPLETION FORM

00 72 00 GENERAL CONDITIONS

00 73 00 SUPPLEMENTAL GENERAL CONDITIONS

00 73 10 SUPPLEMENTARY CONDITIONS

00 73 16 INSURANCE REQUIREMENTS

00 73 39 DISADVANTAGED/SMALL BUSINESS ENTERPRISE (DBE, SBE) OR

REQUIREMENTS

00 73 43 PREVAILING WAGES

01 00 00 GENERAL REQUIREMENTS

01 20 00 PRICE AND PAYMENT PROCEDURES

01 21 00 ALLOWANCES

00 01 10 TABLE OF CONTENTS

01 25 00 SUBSTITUTION PROCEDURES

01 26 00 CONTRACT MODIFICATION PROCEDURES

01 31 00 PROJECT MANAGEMENT COORDINATION

01 32 00 CONSTRUCTION PROGRESS DOCUMENTATION

01 33 00 SUBMITTAL PROCEDURES

01 35 00 SPECIAL PROCEDURES

01 40 00 QUALITY REQUIREMENTS

01 42 00 REFERENCES

01 48 00 CONTROL OF WORK

01 50 00 TEMPORARY FACILITIES AND CONTROLS

01 55 26 TRAFFIC CONTROL SYSTEM

01 58 13 PROJECT INFORMATION SIGNS

01 60 00 PRODUCT REQUIREMENTS

01 70 00 EXECUTION AND CLOSEOUT REQUIREMENTS

01 74 19 CONSTRUCTION WASTE MANAGEMENT

01 77 00 CLOSEOUT PROCEDURES

01 78 00 PROJECT RECORD DOCUMENT

01 78 23 OPERATION AND MAINTENANCE DATA

01 79 00 DEMONSTRATION AND TRAINING

DIVISION 02 – EXISTING CONDITIONS

02 41 19 SELECTIVE DEMOLITION

DIVISION 03 – CONCRETE

03 10 00 CONCRETE FORMING AND ACCESSORIES

03 20 00 CONCRETE REINFORCING

03 30 00 CAST-IN-PLACE CONCRETE

03 53 00 CONCRETE TOPPING

DIVISION 05 – METALS

05 01 70.63 DECORATIVE METAL REFINISHING

05 12 00 STRUCTURAL STEEL FRAMING

05 12 13 ARCHITECTURALLY EXPOSED STRUCTURAL STEEL FRAMING

05 31 00 STEEL DECKING

05 40 00 COLD FORMED METAL FRAMING

05 50 00 METAL FABRICATIONS

05 51 19 METAL GRATING STAIRS

05 52 13 METAL RAILINGS

05 53 13 BAR GRATING

DIVISION 06 – WOOD, PLASTICS, AND COMPOSITES

06 10 00 ROUGH CARPENTRY

06 16 00 SHEATHING

06 17 15 ENGINEERED STRUCTURAL WOOD

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

07 14 16 COLD FLUID-APPLIED WATERPROOFING

07 21 00 BUILDING INSULATION

07 25 00 WEATHER BARRIERS

07 46 19 STEEL SIDING

07 54 23 THERMOPLASTIC POLYOLEFIN (TPO) ROOFING

07 62 00 SHEET METAL FLASHING AND TRIM

07 71 00 ROOF SPECIALTIES

07 72 00 ROOF ACCESSORIES

07 84 13 PENETRATION FIRESTOPPING

07 84 43 JOINT FIRESTOPPING

07 92 00 JOINT SEALANTS

07 95 13.13 INTERIOR EXPANSION JOINT COVER ASSEMBLIES

07 95 13.16 EXTERIOR EXPANSION JOINT COVER ASSEMBLIES

DIVISION 08 - OPENINGS

08 11 13 STEEL DOORS AND FRAMES

08 31 13 ACCESS DOORS AND FRAMES

08 33 23 OVERHEAD COILING DOORS

08 35 13 FOLDING DOORS

08 44 13 GLAZED ALUMINUM CURTAIN WALLS

08 45 23 FIBERGLASS-SANDWICH-PANEL ASSEMBLIES

08 51 13 ALUMINUM WINDOWS

08 71 00 DOOR HARDWARE

08 80 00 GLAZING

08 88 13 FIRE-RATED GLAZING

08 91 19 FIXED LOUVERS

DIVISION 09 - FINISHES

09 21 16 GYPSUM BOARD ASSEMBLIES

09 22 16 NON-LOAD-BEARING STEEL FRAMING

09 30 13 CERAMIC TILING

09 51 00 ACOUSTICAL CEILINGS

09 62 29 CORK FLOORING

09 65 13 RUBBER WALL BASE

09 65 19 RESILIENT TILE FLOORING

09 68 13 TILE CARPETING

09 84 33 SOUND-ABSORBING WALL UNITS

09 84 36 SOUND-ABSORBING CEILING UNITS

09 90 00 PAINTING AND COATING

09 96 00 HIGH PERFORMANCE COATINGS

DIVISION 10 - SPECIALTIES

10 14 00 SIGNAGE

10 14 26 POST AND PANEL/PYLON SIGNAGE

10 21 13 METAL TOILET COMPARTMENTS

10 22 23.23 MOVABLE PANEL SYSTEM

10 28 00 TOILET AND BATH ACCESSORIES

10 44 00 FIRE PROTECTION SPECIALTIES

10 56 29 STORAGE RACKS-HEAVY GOODS

10 73 00 STRUCTURAL CANOPY SYSTEM

DIVISION 11 - EQUIPMENT

11 11 39 BUS ROOF WORKING PLATFORM-CATWALK

DIVISION 14 - CONVEYING EQUIPMENT

14 21 23 ELECTRIC TRACTION PASSENGER ELEVATORS

14 24 13 HYDRAULIC FREIGHT ELEVATORS

DIVISION 21 - FIRE SUPPRESSION

21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION

21 05 23 GENERALD-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION

PIPING

21 05 29 HANGERS AND SUPPORT FOR FIRE-SUPPRESSION PIPING AND

EQUIPMENT

21 05 48 VIBRATION AND SEISMIC CONTROLS FOR FIRE-SUPPRESSION PIPING

AND EQUIPMENT

21 05 53 IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT

21 10 00 WATER-BASED FIRE-SUPPRESSION SYSTEMS

DIVISION 22 – PLUMBING

22 05 00 COMMON WORK RESULTS FOR PLUMBING

22 05 23 GENERAL DUTY VALVES FOR PLUMBING SUPPORT

22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

22 05 48 VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND

EQUIPMENT

22 05 53 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

22 05 93 TESTING, ADJUSTING, AND BALANCING FOR PLUMBING

22 07 19 PLUMBING PIPING INSULATION

22 11 16 DOMESTIC WATER PIPING

22 11 19 DOMESTIC WATER PIPING SPECIALITIES

22 13 16 SANITARY WASTE AND VENT PIPING

22 13 19 SANITARY WASTE PIPING SPECIALTIES

22 13 19.13 SANITARY DRAINS

22 14 14 STORM DRAINAGE PIPING

22 14 23 STORM DRAINAGE PIPING SPECIALITIES

22 42 00 COMMERCIAL PLUMBING FIXTURES

22 47 00 DRINKING FOUNTAINS AND WATER COOLERS

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

23 01 30.52 EXISTING HVAC AIR DISTRIBUTIONSYSTEM CLEANING

23 05 00 COMMON WORK RESULTS FOR HVAC

23 05 29 HANGARS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

23 05 48 VIBRATION AND SEISMIC CONTROLS FOR HVAC

23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 07 13 DUCT INSULATION

23 07 19 HVAC PIPING INSULATION

23 09 01 HVAC CONTROLS

23 23 00 REFRIGERANT PIPING

23 31 13 METAL DUCTS

23 33 00 AIR DUCT ACCESSORIES

23 33 46 FLEXIBLE DUCTS

23 34 00 HVAC FANS

23 36 00 AIR TERMINAL UNITS

23 37 13.13 AIR DIFFUSERS

23 37 13.23 REGISTERS AND GRILLES

23 41 00 PARTICULATE AIR FILTERS

23 72 19 FIXED PLATE AIR-TO-AIR ENERGY RECOVERY UNITS

23 72 23.29 PACKAGED, LARGE-CAPACITY, ROOFTOP AIR-CONDITIONING UNITS

23 74 14 MODULAR DX ROOFTOP UNITS

23 81 29 VARIABLE REFRIGERANT-FLOW HVAC SYSTEMS

DIVISION 26 – ELECTRICAL

26 05 19 LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

26 05 33.13 CONDUITS FOR ELECTRICAL SYSTEMS

26 05 43 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS

26 05 48 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS

26 08 00 COMMISSIONING OF ELECTRICAL SYSTEMS

26 27 26 WIRING DEVICES

26 50 00 LIGHTING

DIVISION 27 – COMMUNICATIONS

27 05 28 PATHWAYS FOR COMMUNICATIONS SYSTEMS

27 15 13 COMMUNICATIONS COPPER HORIZONTAL CABLING

27 21 33 DATA COMMUNICATIONS WIRELESS ACCESS POINTS

27 41 00 AUDIO-VIDEO SYSTEMS

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 46 21.11 ADDRESSABLE FIRE ALARM SYSTEMS

DIVISION 31 – EARTHWORK

31 20 00 EARTH MOVING

31 23 19 DEWATERING

31 63 29 DRILLED CONCRETE PIERS AND SHAFTS

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 13 16 DECORATIVE CONCRETE PAVING

32 13 73 CONCRETE PAVING JOINT SEALANTS

32 93 00 PLANTS

END OF TABLE OF CONTENTS

THIS PAGE WAS INTENTIONALLY LEFT BLANK

SELECTIVE DEMOLITION 02 41 19

SECTION 02 41 19

SELECTIVE DEMOLITION

PART 1 – GENERAL

1.1 SUMMARY

Section Includes:

Demolition and removal of selected portions of building or structure.

1.2 DEFINITIONS

Remove: Detach items from existing construction and legally dispose of them off-site, unless indicated to be removed and salvaged or removed and reinstalled.

Remove and Reinstall: Detach items from existing construction, prepare them for reuse, and reinstall them where indicated.

Existing to Remain: Existing items of construction that are not to be removed and that are not otherwise indicated to be removed, removed and salvaged, or removed and reinstalled.

1.3 QUALITY ASSURANCE

Standards: Comply with ANSI A10.6 and NFPA 241.

1.4 PROJECT CONDITIONS

Notify Architect of discrepancies between existing conditions and Drawings before proceeding with selective demolition.

Storage or sale of removed items or materials on-site is not permitted.

Utility Service: Maintain existing utilities indicated to remain in service and protect them against damage during selective demolition operations.

Maintain fire-protection facilities in service during selective demolition operations.

1.5 WARRANTY

Existing Warranties: Remove, replace, patch, and repair materials and surfaces cut or damaged during selective demolition, by methods and with materials so as not to void existing warranties.

PART 2 – PRODUCTS

Not Used

PART 3 – EXECUTION

3.1 EXAMINATION

Verify that utilities have been disconnected and capped.

Survey existing conditions and correlate with requirements indicated to determine extent of selective demolition required.

Inventory and record the condition of items to be removed and reinstalled and items to be removed and salvaged.

02 41 19 SELECTIVE DEMOLITION

When unanticipated mechanical, electrical, or structural elements that conflict with intended function or design are encountered, investigate and measure the nature and extent of conflict. Promptly submit a written report to Architect.

Perform surveys as the Work progresses to detect hazards resulting from selective demolition activities.

3.2 UTILITY SERVICES AND MECHANICAL/ELECTRICAL SYSTEMS

Existing Services/Systems: Maintain services/systems indicated to remain and protect them against damage during selective demolition operations.

Service/System Requirements: Locate, identify, disconnect, and seal or cap off indicated utility services and mechanical/electrical systems serving areas to be selectively demolished.

Arrange to shut off indicated utilities with utility companies.

If services/systems are required to be removed, relocated, or abandoned, before proceeding with selective demolition, provide temporary services/systems that bypass area of selective demolition and that maintain continuity of services/systems to other parts of building.

Cut off pipe or conduit in walls or partitions to be removed. Cap, valve, or plug and seal remaining portion of pipe or conduit after bypassing.

a. Where entire wall is to be removed, existing services/systems may be removed with removal of the wall.

3.3 SELECTIVE DEMOLITION, GENERAL

General: Demolish and remove existing construction only to the extent required by new construction and as indicated. Use methods required to complete the Work within limitations of governing regulations and as follows:

Proceed with selective demolition systematically, from higher to lower level. Complete selective demolition operations above each floor or tier before disturbing supporting members on the next lower level.

Neatly cut openings and holes plumb, square, and true to dimensions required. Use cutting methods least likely to damage construction to remain or adjoining construction. Use hand tools or small power tools designed for sawing or grinding, not hammering and chopping, to minimize disturbance of adjacent surfaces. Temporarily cover openings to remain.

Cut or drill from the exposed or finished side into concealed surfaces to avoid marring existing finished surfaces.

Do not use cutting torches until work area is cleared of flammable materials. At concealed spaces, such as duct and pipe interiors, verify condition and contents of hidden space before starting flame-cutting operations. Maintain fire watch and portable fire-suppression devices during flame-cutting operations.

Maintain adequate ventilation when using cutting torches.

Remove decayed, vermin-infested, or otherwise dangerous or unsuitable materials and promptly dispose of off-site.

Remove structural framing members and lower to ground by method suitable to avoid free fall and to prevent ground impact or dust generation.

Locate selective demolition equipment and remove debris and materials so as not to impose excessive loads on supporting walls, floors, or framing.

Removed and Reinstalled Items:

SELECTIVE DEMOLITION 02 41 19

Clean and repair items to functional condition adequate for intended reuse. Paint equipment to match new equipment.

Pack or crate items after cleaning and repairing. Identify contents of containers.

Protect items from damage during transport and storage.

Reinstall items in locations indicated. Comply with installation requirements for new materials and equipment. Provide connections, supports, and miscellaneous materials necessary to make item functional for use indicated.

Existing Items to Remain: Protect construction indicated to remain against damage and soiling during selective demolition. When permitted by Architect, items may be removed to a suitable, protected storage location during selective demolition and reinstalled in their original locations after selective demolition operations are complete.

3.4 SELECTIVE DEMOLITION PROCEDURES FOR SPECIFIC MATERIALS

Concrete: Demolish in small sections. Cut concrete to a depth of at least 3/4 inch at junctures with construction to remain, using power-driven saw. Dislodge concrete from reinforcement at perimeter of areas being demolished, cut reinforcement, and then remove remainder of concrete indicated for selective demolition. Neatly trim openings to dimensions indicated.

Concrete Slabs-on-Grade: Saw-cut perimeter of area to be demolished, then break up and remove.

3.5 DISPOSAL OF DEMOLISHED MATERIALS

General: Except for items or materials indicated to be reused, salvaged, reinstalled, or otherwise indicated to remain Owner's property, remove demolished materials from Project site and legally dispose of them in an EPA-approved landfill.

Do not allow demolished materials to accumulate on-site.

Remove and transport debris in a manner that will prevent spillage on adjacent surfaces and areas.

Burning: Do not burn demolished materials.

Disposal: Transport demolished materials off Owner's property and legally dispose of them.

3.6 CLEANING

Clean adjacent structures and improvements of dust, dirt, and debris caused by selective demolition operations. Return adjacent areas to condition existing before selective demolition operations began.

END OF SECTION 02 41 19

02 41 19 SELECTIVE DEMOLITION

THIS PAGE WAS INTENTIONALLY LEFT BLANK

CONCRETE FORMING AND ACCESSORIES 03 10 00

SECTION 03 10 00

CONCRETE FORMING AND ACCESSORIES

PART 1 – GENERAL

1.1 SUMMARY

Section Includes:

Form-facing material for cast-in-place concrete.

Shoring, bracing, and anchoring.

Related Requirements:

Section 03 30 00 “Cast-in-Place Concrete” for formwork related to cast in place concrete.

Section 32 13 16 "Decorative Concrete Paving" for formwork related to decorative concrete pavement and walks.

1.2 DEFINITIONS

Form-Facing Material: Temporary structure or mold for the support of concrete while the concrete is setting and gaining sufficient strength to be self-supporting.

Formwork: The total system of support of freshly placed concrete, including the mold or sheathing that contacts the concrete, as well as supporting members, hardware, and necessary bracing.

1.3 ACTION SUBMITTALS

Product Data: For each of the following:

Exposed surface form-facing material.

Concealed surface form-facing material.

Forms for cylindrical columns.

Form-release agent.

PART 2 – PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

Concrete Formwork: Erect, shore, brace, and maintain formwork, shores, and reshores in accordance with ACI 301, to support vertical, lateral, static, and dynamic loads, and construction loads that might be applied, until structure can support such loads, so that resulting concrete conforms to the required shapes, lines, and dimensions.

Provide wood panel forms in accordance with APA's "Concrete Forming Design/Construction Guide."

Provide formwork sufficient to limit deflection of form-facing material to 1/240 of center-to-center spacing of supports.

2.2 FORM-FACING MATERIALS

As-Cast Surface Form-Facing Material:

Provide continuous, true, and smooth concrete surfaces.

03 10 00 CONCRETE FORMING AND ACCESSORIES

Furnish in largest practicable sizes to minimize number of joints.

Acceptable Materials: As required to comply with Surface Finish designations specified in Sec-tion 03 30 00 "Cast-In-Place Concrete, and as follows:

a. Plywood, metal, or other approved panel materials.

Concealed Surface Form-Facing Material: Lumber, plywood, metal, plastic, or another approved ma-terial.

Provide lumber dressed on at least two edges and one side for tight fit.

Forms for Cylindrical Columns, Pedestals, and Supports: Metal, glass-fiber-reinforced plastic, paper, or fiber tubes that produce surfaces without spiral or vertical seams not exceeding specified formwork surface class.

Provide forms with sufficient wall thickness to resist plastic concrete loads without detrimental deformation.

2.3 RELATED MATERIALS

Chamfer Strips: Wood, metal, PVC, or rubber strips, 3/4 by 3/4 inch (19 by 19 mm), minimum.

Form-Release Agent: Commercially formulated form-release agent that does not bond with, stain, or adversely affect concrete surfaces and does not impair subsequent treatments of concrete surfaces.

Formulate form-release agent with rust inhibitor for steel form-facing materials.

Form release agent for form liners shall be acceptable to form liner manufacturer.

PART 3 – EXECUTION

3.1 INSTALLATION OF FORMWORK

Comply with ACI 301.

Construct formwork, so concrete members and structures are of size, shape, alignment, elevation, and position indicated, within tolerance limits of ACI 117 and to comply with the Surface Finish des-ignations specified in Section 03 30 00 "Cast-In-Place Concrete" for as-cast finishes.

Limit concrete surface irregularities as follows:

Surface Finish-3.0: ACI 117 Class A, 1/8 inch (3.0 mm).

Construct forms tight enough to prevent loss of concrete mortar.

Minimize joints.

Exposed Concrete: Symmetrically align joints in forms.

Construct removable forms for easy removal without hammering or prying against concrete surfaces.

Provide crush or wrecking plates where stripping may damage cast-concrete surfaces.

Provide top forms for inclined surfaces steeper than 1.5 horizontal to 1 vertical.

Install keyways, reglets, recesses, and other accessories, for easy removal.

Do not use rust-stained, steel, form-facing material.

Set edge forms, bulkheads, and intermediate screed strips for slabs to achieve required elevations and slopes in finished concrete surfaces.

CONCRETE FORMING AND ACCESSORIES 03 10 00

Provide and secure units to support screed strips

Use strike-off templates or compacting-type screeds.

Provide temporary openings for cleanouts and inspection ports where interior area of formwork is inaccessible.

Close openings with panels tightly fitted to forms and securely braced to prevent loss of concrete mortar.

Locate temporary openings in forms at inconspicuous locations.

Chamfer exterior corners and edges of permanently exposed concrete unless otherwise noted on plans.

At construction joints, overlap forms onto previously placed concrete not less than 12 inches.

Form openings, chases, offsets, sinkages, keyways, reglets, blocking, screeds, and bulkheads re-quired in the Work.

Determine sizes and locations from trades providing such items.

Obtain written approval of Architect prior to forming openings not indicated on Drawings.

Construction Joints:

Construct joints true to line with faces perpendicular to surface plane of concrete.

Install so strength and appearance of concrete are not impaired, at locations indicated or as approved by Architect.

Clean forms and adjacent surfaces to receive concrete. Remove chips, wood, sawdust, dirt, and other debris just before placing concrete.

Coat contact surfaces of forms with form-release agent, according to manufacturer's written instruc-tions, before placing reinforcement.

3.2 INSTALLATION OF EMBEDDED ITEMS

Place and secure anchorage devices and other embedded items required for adjoining work that is attached to or supported by cast-in-place concrete.

Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

Install anchor rods, accurately located, to elevations required and complying with tolerances in Section 7.5 of AISC 303.

Clean embedded items immediately prior to concrete placement.

3.3 REMOVING AND REUSING FORMS

Formwork for sides of beams, walls, columns, and similar parts of the Work that does not support weight of concrete may be removed after cumulatively curing at not less than 50 deg F for 48 hours after placing concrete. Concrete has to be hard enough to not be damaged by form-removal opera-tions, and curing and protection operations need to be maintained.

Clean and repair surfaces of forms to be reused in the Work.

Split, frayed, delaminated, or otherwise damaged form-facing material are unacceptable for ex-posed surfaces.

Apply new form-release agent.

03 10 00 CONCRETE FORMING AND ACCESSORIES

When forms are reused, clean surfaces, remove fins and laitance, and tighten to close joints.

Align and secure joints to avoid offsets.

Do not use patched forms for exposed concrete surfaces unless approved by Architect.

3.4 FIELD QUALITY CONTROL

Special Inspections: Owner will engage a special inspector and qualified testing and inspecting agency to perform field tests and inspections and prepare test reports.

Inspections:

Inspect formwork for shape, location, and dimensions of the concrete member being formed.

END OF SECTION 03 10 00

CONCRETE REINFORCING 03 20 00

SECTION 03 20 00

CONCRETE REINFORCING

PART 1 – GENERAL

1.1 SUMMARY

Section Includes:

Steel reinforcement bars.

Welded-wire reinforcement.

Related Requirements:

Section 03 30 00 “Cast in Place Concrete” for reinforcing used in cast-in-place concrete.

Section 32 13 16 "Decorative Concrete Paving" for reinforcing related to decorative concrete pavement and walks.

1.2 ACTION SUBMITTALS

Product Data: For the following:

Each type of steel reinforcement.

Zinc repair material.

Bar supports.

Couplers, formsavers, stud weldable rebar, and other manufactured reinforcement products.

Shop Drawings: Comply with ACI SP-066:

Include placing drawings that detail fabrication, bending, and placement.

Include bar sizes, lengths, materials, grades, bar schedules, stirrup spacing, bent bar diagrams, bar arrangement, location of splices, lengths of lap splices, details of mechanical splice couplers, details of welding splices, tie spacing, hoop spacing, and supports for concrete reinforcement.

For structural thermal break insulated connection system, indicate general configuration, insu-lation dimensions, tension bars, compression pads, shear bars, and dimensions.

Construction Joint Layout: Indicate proposed construction joints required to build the structure.

Location of construction joints is subject to approval of Architect.

1.3 INFORMATIONAL SUBMITTALS

Welding certificates.

Reinforcement To Be Welded: Welding procedure specification in accordance with

AWS D1.4/D1.4M.

Material Test Reports: For the following, from a qualified testing agency:

Steel Reinforcement:

a. For reinforcement to be welded, mill test analysis for chemical composition and carbon equivalent of the steel in accordance with ASTM A706.

03 20 00 CONCRETE REINFORCING

1.4 QUALITY ASSURANCE

Welding Qualifications: Qualify procedures and personnel in accordance with AWS D1.4/D 1.4M.

1.5 DELIVERY, STORAGE, AND HANDLING

Steel Reinforcement: Deliver, store, and handle steel reinforcement to prevent bending and damage.

Store reinforcement to avoid contact with earth.

PART 2 – PRODUCTS

2.1 STEEL REINFORCEMENT

Reinforcing Bars: ASTM A615, Grade 60, deformed.

Low-Alloy Steel Reinforcing Bars: ASTM A706, deformed.

Headed-Steel Reinforcing Bars: ASTM A970, type HA.

Manufacturers and type:

a. HRC, 555 or 670.

b. Barsplice, BNH or BNX.

c. Or approved equal.

Plain-Steel Welded-Wire Reinforcement: ASTM A1064, plain, fabricated from as-drawn steel wire into flat sheets.

2.2 REINFORCEMENT ACCESSORIES

Joint Dowel Bars: ASTM A615, Grade 60, plain-steel bars, cut true to length with ends square and free of burrs.

Bar Supports: Bolsters, chairs, spacers, and other devices for spacing, supporting, and fastening reinforcing bars and welded-wire reinforcement in place.

Manufacture bar supports from steel wire, plastic, or precast concrete in accordance with CRSI's "Manual of Standard Practice," of greater compressive strength than concrete and as follows:

Mechanical Splice Couplers: ACI 318 Type 1, same material of reinforcing bar being spliced; tension-compression type.

Manufacturers and type:

a. Dayton, Bar-Lock L-Series.

b. HRC, 500 or 510 Xtender.

c. Barsplice.

d. Or approved equal.

Steel Tie Wire: ASTM A1064/A1064M, annealed steel, not less than 0.0508 inch in diameter.

Finish: Plain.

Zinc Repair Material: ASTM A780.

2.3 FABRICATING REINFORCEMENT

Fabricate steel reinforcement according to CRSI's "Manual of Standard Practice."

CONCRETE REINFORCING 03 20 00

PART 3 – EXECUTION

3.1 PREPARATION

Protection of In-Place Conditions:

Do not cut or puncture vapor retarder.

Repair damage and reseal vapor retarder before placing concrete.

Clean reinforcement of loose rust and mill scale, earth, ice, and other foreign materials that reduce bond to concrete.

3.2 INSTALLATION OF STEEL REINFORCEMENT

Comply with CRSI's "Manual of Standard Practice" for placing and supporting reinforcement.

Accurately position, support, and secure reinforcement against displacement.

Locate and support reinforcement with bar supports to maintain minimum concrete cover.

Do not tack weld crossing reinforcing bars.

Preserve clearance between bars of not less than 1 inch, not less than one bar diameter, or not less than 1-1/3 times size of large aggregate, whichever is greater.

Provide concrete coverage in accordance with ACI 318 and as indicated on Drawings.

Where reinforcement, anchors and embedded steel cannot be set with the full concrete cover specified, the EOR shall review and has the option to permit the reduced cover where the af-fected items are coated with zinc galvanization repair or equivalent protection.

Set wire ties with ends directed into concrete, not toward exposed concrete surfaces.

Splices: Lap splices as indicated on Drawings.

Stagger splices in accordance with ACI 318.

Mechanical Splice Couplers: Install in accordance with manufacturer's instructions.

Weld reinforcing bars in accordance with AWS D1.4, where indicated on Drawings.

Install welded-wire reinforcement in longest practicable lengths.

Support welded-wire reinforcement in accordance with CRSI "Manual of Standard Practice."

a. For reinforcement less than W4.0 or D4.0, continuous support spacing to not exceed 12 inches.

Lap edges and ends of adjoining sheets at least one wire spacing plus 2 inches for plain wire.

Offset laps of adjoining sheet widths to prevent continuous laps in either direction.

Lace overlaps with wire.

Reinforcement ends cut when coring or cutting through hardened concrete that will be permanently exposed shall be coated with zinc galvanization repair.

3.3 JOINTS

Construction Joints: Install so strength and appearance of concrete are not impaired, at locations indicated or as approved by Architect.

Place joints perpendicular to main reinforcement.

03 20 00 CONCRETE REINFORCING

Continue reinforcement across construction joints unless otherwise indicated.

Doweled Joints: Install dowel bars and support assemblies at joints where indicated. Lubricate one-half of dowel length, to prevent concrete bonding to one side of joint.

3.4 INSTALLATION TOLERANCES

Comply with ACI 117.

3.5 FIELD QUALITY CONTROL

Special Inspections: Owner will engage a special inspector and qualified testing and inspecting agency to perform field tests and inspections and prepare test reports.

Inspections:

Steel-reinforcement placement.

Steel-reinforcement mechanical splice couplers.

Steel-reinforcement welding.

END OF SECTION 03 20 00

CAST-IN-PLACE CONCRETE 03 30 00

SECTION 03 30 00

CAST-IN-PLACE CONCRETE

PART 1 – GENERAL

1.1 SUMMARY

Section Includes:

Concrete standards.

Concrete materials.

Admixtures.

Fiber reinforcement.

Vapor retarders.

Curing materials.

Accessories.

Repair materials.

Concrete mixture materials.

Concrete mixture class types.

Concrete mixing.

Related Requirements:

Section 03 10 00 "Concrete Forming and Accessories" for form-facing materials.

Section 03 20 00 "Concrete Reinforcing" for steel reinforcing bars and welded-wire reinforce-ment.

Section 03 53 00 "Concrete Topping" for concrete floor toppings.

Section 31 20 00 "Earth Moving" for drainage fill under slabs-on-ground.

Section 32 13 16 "Decorative Concrete Paving" for decorative concrete pavement and walks.

1.2 DEFINITIONS

Cementitious Materials: Portland cement or blended hydraulic cement alone or in combination with one or more of the following:

Fly ash, slag cement, other pozzolans, and silica fume; materials subject to compliance with requirements.

Water/Cementitious Materials (w/cm) Ratio: The ratio by weight of mixing water to cementitious ma-terials.

1.3 PREINSTALLATION MEETINGS

Preinstallation Conference: Conduct conference at the project site.

Require representatives of each entity directly concerned with cast-in-place concrete to attend, including the following:

03 30 00 CAST-IN-PLACE CONCRETE

a. Contractor's superintendent.

b. Independent testing agency responsible for inspections and acceptance testing of con-crete at Project site.

c. Concrete Subcontractor.

Review the following:

a. Special inspection and testing and inspecting agency procedures for field quality con-trol.

b. Construction joints, control joints, isolation joints, and joint-filler strips.

c. Vapor-retarder installation.

d. Anchor rod and anchorage device installation tolerances.

e. Cold- and hot-weather concreting procedures.

f. Concrete finishes and finishing.

g. Curing procedures.

h. Forms and form-removal limitations.

i. Shoring and reshoring procedures.

j. Methods for achieving specified floor and slab flatness and levelness.

k. Floor and slab flatness and levelness measurements.

l. Concrete repair procedures.

m. Concrete protection.

n. Initial curing of standard-cured and field curing of field-cured test cylinders

(ASTM C31.)

o. Protection of field cured field test cylinders.

p. Distribution of test reports.

1.4 ACTION SUBMITTALS

Product Data:

Portland cement.

Blended hydraulic cement.

Fly ash.

Silica fume.

Natural or other pozzolans.

Aggregates.

Admixtures:

a. Include limitations of use. Admixtures that do not comply with reference ASTM Inter-national requirements must be submitted with test data for approval.

Fiber reinforcement.

Vapor retarders.

Curing materials.

Joint fillers.

Repair materials.

Design Mixtures: For each concrete mixture, include the following:

Mixture identification.

Compressive strength at 28 days or other age as specified.

Compressive strength required at stages of construction.

Durability exposure classes for Exposure Categories F, S, W, and C.

Maximum w/cm ratio.

Calculated equilibrium and fresh density for lightweight concrete.

Slump or slump flow limit.

Air content.

Nominal maximum aggregate size.

Fiber content, if used.

Intended placement method.

Submit adjustments to design mixtures when characteristics of materials, Project conditions, weather, test results, or other circumstances warrant changes.

Shop Drawings:

Construction Joint Layout: Indicate proposed construction joints required to construct the struc-ture.

a. Location of construction joints is subject to approval of the Architect and EOR.

Concrete Schedule: For each location of each class of concrete indicated in "Concrete Mixture Class Types" Article, including the following:

Concrete class designation.

Location within Project.

Exposure class designation.

Formed surface finish designation and final finish.

Final finish for floors.

1.5 INFORMATIONAL SUBMITTALS

Qualification Data: For the following:

Installer: Include copies of applicable ACI certificates.

Material Certificates: For each of the following:

Cementitious materials.

Admixtures.

Fiber reinforcement.

Curing compounds.

Bonding agents.

Adhesives.

Vapor retarders.

Joint-filler strips.

Repair materials.

Material Test Reports: For the following:

Portland cement.

Blended hydraulic cement.

Performance-based hydraulic cement.

Fly ash.

Silica fume.

Natural or other pozzolans.

Aggregates.

Admixtures.

Floor surface flatness and levelness measurements report, indicating compliance with specified tol-erances in accordance with ACI 117 and in compliance with ASTM E1155 (ASTM E1155M).

Research Reports:

For concrete admixtures in accordance with ICC's Acceptance Criteria AC198.

For sheet vapor retarder, showing compliance with ICC's Acceptance Criteria AC380.

Preconstruction Test Reports: For each mix design.

Minutes of preinstallation conference.

1.6 QUALITY ASSURANCE

Installer Qualifications: A qualified Installer who employs Project personnel qualified as an ACI-certified Concrete Flatwork Associate and Concrete Flatwork Finisher and a supervisor who is a cer-tified ACI Advanced Concrete Flatwork Finisher/Technician or an ACI Concrete Flatwork Finisher with experience installing and finishing concrete.

Post-Installed Concrete Anchors Installers: ACI-certified Adhesive Anchor Installer.

Ready-Mixed Concrete Manufacturer Qualifications: A firm experienced in manufacturing ready-mixed concrete products and that complies with ASTM C94 requirements for production facilities and equipment.

Field Quality-Control Testing Agency Qualifications: An independent agency, acceptable to authori-ties having jurisdiction, qualified in accordance with ASTM C1077 and ASTM E329 for testing indi-cated.

Personnel conducting field tests on plastic concrete properties are to be qualified as an ACI Concrete Field Testing Technician, Grade 1, in accordance with policies from ACI CPP 610.1 or an equivalent certification program.

1.7 PRECONSTRUCTION TESTING

Preconstruction Testing Service: Engage a qualified testing agency to perform preconstruction testing on each concrete mixture.

Include the following information in each test report:

a. Admixture dosage rates.

b. Slump.

c. Air content.

d. Seven-day compressive strength.

e. 28-day compressive strength.

f. 56-day compressive strength for mixes with type IL cement.

g. Evaluation of permeability-reducing admixtures.

1.8 DELIVERY, STORAGE, AND HANDLING

Comply with ASTM C94 and ACI 301.

1.9 FIELD CONDITIONS

Cold-Weather Placement: Comply with ACI 301 as follows:

Protect concrete work from physical damage or reduced strength that could be caused by frost, freezing actions, or low temperatures.

When air temperature has fallen to, or is expected to fall below 40 deg F during the protection period, maintain delivered concrete mixture temperature within the temperature range required by ACI 301.

Do not use frozen materials or materials containing ice or snow.

Do not place concrete in contact with surfaces less than 35 deg F, other than reinforcing steel.

Hot-Weather Placement: Comply with ACI 301 and ACI 305.1, and as follows:

Maintain concrete temperature at time of discharge to not exceed 95 deg F.

Fog-spray forms, steel reinforcement, and subgrade just before placing concrete. Keep sub-grade uniformly moist without standing water, soft spots, or dry areas.

1.10 WARRANTY

Manufacturer's Warranty: Manufacturer agrees to furnish replacement sheet vapor retarder/termite barrier material and accessories for sheet vapor retarder/ termite barrier and accessories that do not comply with requirements or that fail to resist penetration by termites within specified warranty period.

Warranty Period: 10 years from date of Substantial Completion.

PART 2 – PRODUCTS

2.1 CONCRETE STANDARDS

ACI Publications: Comply with ACI 301 unless modified by requirements in the Contract Documents.

2.2 CONCRETE MATERIALS

Source Limitations:

Obtain all concrete mixtures from a single ready-mixed concrete manufacturer for entire Project.

Obtain each type of admixture from single source from single manufacturer.

Cementitious Materials:

Portland Cement: ASTM C150, Type II, gray. Other Types may be used, subject to EOR ap-proval.

Blended Hydraulic Cement: ASTM C595, Type IL, portland-limestone cement. Cement blend shall be limited to a maximum of 10% limestone unless otherwise approved by the EOR.

Fly Ash: ASTM C618, Class F.

Other pozzolans are subject to EOR approval.

Normal-Weight Aggregates:

Coarse Aggregate: ASTM C33, Class 3M.

Maximum Coarse-Aggregate Size: 1-1/2 inches nominal for foundations, 1 inch nominal for all other use.

Fine Aggregate: ASTM C33.

Alkali-Silica Reaction: Comply with one of the following for each aggregate used:

a. Expansion Result of Aggregate: Not more than 0.04 percent at one year when tested in accordance with ASTM C1293.

b. Expansion Results of Aggregate and Cementitious Materials in Combination: Not more than 0.10 percent at an age of 16 days when tested in accordance with ASTM C1567.

Do not use this option with fly ash with an alkali content greater than 4.0 percent. Sub-mit supporting data for each aggregate showing expansion in excess of 0.10 percent when tested in accordance with ASTM C1260.

c. Alkali Content in Concrete: Not to exceed 4 lb./cu. yd. for aggregate with expansion greater than or equal to 0.04 percent and less than 0.12 percent or 3 lb./cu. yd. for aggregate with expansion greater than or equal to 0.12 percent and less than 0.24 percent. Test aggregate reactivity in accordance with ASTM C1293. Calculate alkali content of concrete in accordance with ACI 301. Do not use this option with natural pozzolan or fly ash that has a calcium oxide content greater than 18 percent or an alkali content greater than 4.0 percent; or for an aggregate with expansion at one year greater than or equal to 0.24 percent when tested in accordance with ASTM C1293.

2.3 ADMIXTURES

Air-Entraining Admixture: ASTM C260.

Chemical Admixtures: Do not use calcium chloride or admixtures containing calcium chloride.

Water-Reducing Admixture: ASTM C494, Type A.

Retarding Admixture: ASTM C494, Type B.

Water-Reducing and -Retarding Admixture: ASTM C494, Type D.

High-Range, Water-Reducing Admixture: ASTM C494, Type F.

High-Range, Water-Reducing and -Retarding Admixture: ASTM C494, Type G.

Admixtures with special properties, with documentation of claimed performance enhancement, ASTM C494, Type S.

Defoamer, compatible with other admixtures and formulated for use in concrete.

Mixing Water for Concrete Mixtures and Water Used to Make Ice: ASTM C1602. Include documen-tation of compliance with limits for alkalis, sulfates, chlorides, or solids content of mixing water from Table 2 in ASTM C1602.

2.4 FIBER REINFORCEMENT

Synthetic Fiber: Polypropylene complying with ASTM C1116, Type III, type and size as indicated on Drawings, or on approved mix designs. Master Builders MasterFiber or approved equal.

2.5 VAPOR RETARDERS

Sheet Vapor Retarder, Class C: ASTM E1745, Class C; not less than 15 mils thick. Include manufac-turer's recommended adhesive or pressure-sensitive joint tape.

Stego Wrap or approved equal.

2.6 CURING MATERIALS

Evaporation Retarder: Waterborne, monomolecular film forming, manufactured for application to fresh concrete.

Absorptive Cover: AASHTO M 182, Class 2, burlap cloth made from jute or kenaf, weighing approx-imately 9 oz./sq. yd. when dry.

Moisture-Retaining Cover: ASTM C171, polyethylene film burlap-polyethylene sheet.

Color:

a. Ambient Temperature Below 50 deg F: Black.

b. Ambient Temperature between 50 and 85 deg F: Any color.

c. Ambient Temperature Above 85 deg F: White.

Curing Paper: 8 ft. wide paper, consisting of two layers of fibered kraft paper laminated with double coating of asphalt.

Water: Potable water that does not cause staining of the surface.

Clear, Waterborne, Membrane-Forming, Nondissipating Curing Compound: ASTM C309, Type 1, Class B.

2.7 ACCESSORIES

Expansion- and Isolation-Joint-Filler Strips: ASTM D1751, asphalt-saturated cellulosic fiber.

Bonding Agent: ASTM C1059, Type II, nonredispersible, acrylic emulsion or styrene butadiene.

http://www.specagent.com/LookUp/?ulid=11018&mf=&src=wd

2.8 REPAIR MATERIALS

Repair Underlayment: Cement-based, polymer-modified, self-leveling product that can be applied in thicknesses from 1/8 inch and that can be feathered at edges to match adjacent floor elevations.

Cement Binder: ASTM C150/C150M portland cement or hydraulic or blended hydraulic cement, as defined in ASTM C219.

Primer: Product of underlayment manufacturer recommended for substrate, conditions, and ap-plication.

Aggregate: Well-graded, washed gravel, 1/8 to 1/4 inch or coarse sand, as recommended by underlayment manufacturer.

Compressive Strength: Not less than 4000 psi at 28 days when tested in accordance with

ASTM C109.

Repair Overlayment: Cement-based, polymer-modified, self-leveling product that can be applied in thicknesses from 1/4 inch and that can be filled in over a scarified surface to match adjacent floor elevations.

Cement Binder: ASTM C150 portland cement or hydraulic or blended hydraulic cement, as de-fined in ASTM C219.

Primer: Product of topping manufacturer recommended for substrate, conditions, and applica-tion.

Aggregate: Well-graded, washed gravel, 1/8 to 1/4 inch or coarse sand as recommended by topping manufacturer.

Compressive Strength: Not less than 5000 psi at 28 days when tested in accordance with

ASTM C109.

2.9 CONCRETE MIXTURE MATERIALS

Prepare design mixtures for each type and strength of concrete, proportioned on the basis of labora-tory trial mixture or field test data, or both, in accordance with ACI 301.

Use a qualified testing agency for preparing and reporting proposed mixture designs, based on laboratory trial mixtures.

Cementitious Materials: Limit percentage, by weight, of cementitious materials other than portland or hydraulic cement in concrete assigned to Exposure Class F3 as follows:

Fly Ash or Other Pozzolans: 25 percent by mass.

Silica Fume: 10 percent by mass.

Total of Fly Ash or Other Pozzolans, and Silica Fume: 40 percent by mass.

Admixtures: Use admixtures in accordance with manufacturer's written instructions.

2.10 CONCRETE MIXTURE CLASS TYPES

Class Foundation: Normal-weight low carbon concrete used for footings, grade beams, and tie beams.

Exposure Class: ACI 318 Class F0, Class S1, Class P1, Class C1.

Minimum Compressive Strength: 4000 psi at 28 days.

Maximum w/cm Ratio: 0.45.

Slump Limit: as indicated on approved mix design.

Class Slab: Normal-weight low carbon concrete used for interior slabs-on-ground, curbs and pads.

Exposure Class: ACI 318 Class F0, Class S1, Class P1, Class C1.

Minimum Compressive Strength: 4000 psi at 28 days.

Maximum w/cm Ratio: 0.45.

Slump Limit: as indicated on approved mix design.

Air Content:

a. Do not use an air-entraining admixture or allow total air content to exceed 3 percent for concrete used in trowel-finished floors.

Class F: Normal-weight low carbon concrete used for concrete toppings.

Exposure Class: ACI 318 Class F0, Class S1, Class P1, Class C1.

Minimum Compressive Strength: 4000 psi at 28 days.

Maximum w/cm Ratio: 0.45.

Slump Limit: as indicated on approved mix design.

Limit water-soluble, chloride-ion content in hardened concrete to 1.00 percent by weight of ce-ment.

a. Total air content must not to exceed 3 percent for concrete used in trowel-finished floors.

2.11 CONCRETE MIXING

Ready-Mixed Concrete: Measure, batch, mix, and deliver concrete in accordance with ASTM C94 and furnish delivery ticket.

Project-Site Mixing: Measure, batch, and mix concrete materials and concrete in accordance with ASTM C94. Mix concrete materials in appropriate drum-type batch machine mixer.

For mixer capacity of 1 cu. yd. or smaller, continue mixing at least 1-1/2 minutes, but not more than five minutes after ingredients are in mixer, before any part of batch is released.

For mixer capacity larger than 1 cu. yd., increase mixing time by 15 seconds for each additional 1 cu. yd.

Provide batch ticket for each batch discharged and used in the Work, indicating Project identifi-cation name and number, date, mixture type, mixture time, quantity, and amount of water added.

Record approximate location of final deposit in structure.

PART 3 – EXECUTION

3.1 EXAMINATION

Verification of Conditions:

Before placing concrete, verify that installation of concrete forms, accessories, reinforcement, and embedded items is complete and that required inspections have been performed.

Do not proceed until unsatisfactory conditions have been corrected.

3.2 PREPARATION

Provide reasonable auxiliary services to accommodate field testing and inspections, acceptable to testing agency, including the following:

Daily access to the Work.

Incidental labor and…