5400 Mill Street, Suite A, Reno, NV 89502 (775) 827-2717 Fax (775) 324-5577 www.WiseCandT.com
June 16, 2021 Wise Project No. 21-142
Air National Guard Reno 1776 National Guard Way Reno, NV 89502
Attn: Lea Laney
Re: ASBESTOS RENOVATION SURVEY
NORTH OFFICE AREA OF BUILDING 76
1776 National Guard Way Reno, NV 89502
Wise Consulting and Training (WISE) was contracted to conduct an asbestos renovation survey at the above referenced location. A consultant from WISE conducted the survey field work on June 2, 2021.
The scope of work that necessitated this survey includes the intended renovation of an office area in the north portion of the building.
The purpose of the survey was to determine if Asbestos Containing Material (ACM) exists in the building materials that will be disturbed by an intended project. With this knowledge, the Owner or the Owner’s agent can determine what abatement action is necessary for appropriate health and safety precautions and to comply with all applicable federal, state, and local regulatory requirements prior to and during the proposed building demolition or renovation.
The survey work included conducting a visual inspection of the proposed work area to determine the types of building materials present, then developing and implementing a sampling plan of all accessible suspect asbestos containing materials in the intended project area. The sampling plan was based on establishing homogeneous materials presence based on age, location and approximate quantity of materials using both the site construction history and the appearance of the materials.
Nine samples were collected resulting in thirty-two analyses for asbestos content by EPA Method 600/R-93-116. The reason for sample splits is that more than one material was present in a sample and each material must be analyzed separately per EPA mandated laboratory protocols. Point Count as needed
FINDINGS
The following table summarizes the material description, location, sample numbers, and friability determination of any homogeneous materials determined to be ACM. Per EPA and OSHA regulation definitions, ACM are materials containing greater than one percent (>1%) asbestos.
Air National Guard Reno, Lea Laney Wise Project No.21-142 Asbestos Renovation Survey – North Office Area of Building 76 June 16, 2021 1776 National Guard Way, Reno, NV 89502 Page 2 of 3
© WISE Consulting & Training, Inc. 2021
ACM Summary Data
Material Description Material Location Sample Number & Asbestos Content *Friability
Black Mastic Presumed Throughout Office Area
21142-4 3% Chrysotile PF
12” Tan Floor Tile Where Present in Bottom Layer under other Floor Tile
21142-4 3% Chrysotile PF
*Friability Note: Friable (F) - because the material will easily release asbestos fibers with renovation or demolition action and therefore Friable materials are Regulated ACM for disturbance and waste handling; Potentially Friable (PF) - because the materials may release asbestos fibers under standard renovation or demolition actions, so determination of removal procedures and waste handling is required by a licensed asbestos contractor or consultant; Non-Friable (NF) - because standard renovation and demolition action are proven to not release elevated levels of asbestos fibers.
Notes:
1. The Black Floor Tile, Grey Floor Tile, and Yellow Mastic in the renovation area were determined to not be ACM, but because these Tile are adhered to the ACM Tan Floor Tile and/or the ACM Black Mastic, it is our recommendation for removal purposes that all flooring layers in this area be considered ACM.
The materials that did not indicate regulated quantities of asbestos based on the analytical results attached to this report are listed below.
• Knockdown Texture, Joint Compound, and Drywall – In renovation area
• Cove Base Mastic – In renovation area
• Ceiling Tile – In renovation area
CONCLUSION and RECOMMENDATIONS
In conclusion, the ACM detected in this survey was the Black Mastic throughout the renovation area and the Tan 12” Floor Tile on the bottom layer in some locations that we consider Potentially Friable. If the ACM will be disturbed by the intended project, we recommend that the ACM be removed by a licensed abatement contractor and that clearance inspection and air testing of the abatement work be conducted by an independent state licensed asbestos consultant per applicable asbestos regulations.
If you choose to submit this Asbestos Renovation Survey to the Washoe County Health District (WCHD), Air Quality Management Division, to receive an Acknowledgment of Asbestos Assessment, the instructions on how to submit online follow:
https://www.washoecounty.us/health/files/airquality/Forms_and_Applications/AAA%20through%20ACA.pd f WCHD will typically ask for renovation plans. If you need to meet with them, their office is at 1001 E.
9th Street, Building B, #171, Reno, Nevada, 89502. By submitting to them, you have verifiable documentation that this survey was performed and may receive directions from WCHD on how to comply with local and Federal EPA asbestos regulations.
https://www.washoecounty.us/health/files/airquality/Forms_and_Applications/AAA%20through%20ACA.pdf https://www.washoecounty.us/health/files/airquality/Forms_and_Applications/AAA%20through%20ACA.pdf
Air National Guard Reno, Lea Laney Wise Project No.21-142 Asbestos Renovation Survey – North Office Area of Building 76 June 16, 2021 1776 National Guard Way, Reno, NV 89502 Page 3 of 3
© WISE Consulting & Training, Inc. 2021
CLOSURE
This report consists of this written report, the laboratory analytical report, and the sample location sketch. If any portions of this report are missing, the report should be considered incomplete.
It was not the intent of this survey to find buried materials, or to evaluate any other materials than the homogeneous materials specifically determined to be suspect ACM for the purpose of the intended renovation work. If additional suspect materials are encountered during renovation that were previously undetected, the consultant requests to be notified so that sampling or other appropriate responses can be determined.
The condition of ACM may change over time. In addition, asbestos content varies from location to location within materials due to mixing and application processes. This report relates to the specific sample locations and material conditions at the time the survey was conducted. No other claims, warranties or guarantees are either expressed or implied.
Thank you for the opportunity to be of service on this project. Please let us know if you have any questions regarding this report.
Prepared by:
Nathaniel Jenne, Environmental Inspector NV Asbestos Consultant #IM 2203
Reviewed and approved by:
J. Tom Wise, President NV Asbestos Consultant #IJPM 43 NV Environmental Manager #EM 1618
Enc.: Asbestos Sample Location Sketches
PLM Analytical Report No. 21027123 PLM 400 Point Count Analytical Report No. 21028255
SanAir ID#: 21027123
Project #: 21-142
Project Name: NANG
Report Date: 6/8/2021
Analysis Report prepared for Wise Consulting
Dear Nathaniel Jenne, We at SanAir would like to thank you for the work you recently submitted. The 9 sample(s) were received on Thursday, June 03, 2021 via FedEx. The final report(s) is enclosed for the following sample(s): 21142-1, 21142-2, 21142-3, 21142-4, 21142-5, 21142-6, 21142-7, 21142-8, 21142-9.
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample conditions:
- 3 samples in Discrepancy w/ COC condition. (#4, #5, #6)
- 6 samples in Good condition.
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
21-142Project Number:
P.O. Number:
Project Name: NANG 6/2/2021Collected Date:
6/3/2021 9:50:00 AMReceived Date:
6/8/2021 4:35:34 PM
21027123 SanAir ID Number
FINAL REPORT
Wise ConsultingName:
Address: 5400 Mill Street
Suite A Reno, NV 89502 775-827-2717Phone:
Analyst: Upshaw, Zoe
Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
21142-1 / 21027123-001 DW,JC,KDT,CBM Back Office 1,2,3,4, Drywall
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
21142-1 / 21027123-001 DW,JC,KDT,CBM Back Office 1,2,3,4, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
21142-1 / 21027123-001 DW,JC,KDT,CBM Back Office 1,2,3,4, Texture
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
21142-1 / 21027123-001 DW,JC,KDT,CBM Back Office 1,2,3,4, Mastic
Grey Non-Fibrous
Homogeneous
100% Other None Detected
21142-2 / 21027123-002 DW,JC,KDT,CBM Back Storage 1,2,3,4, Drywall
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
21142-2 / 21027123-002 DW,JC,KDT,CBM Back Storage 1,2,3,4, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
21142-2 / 21027123-002 DW,JC,KDT,CBM Back Storage 1,2,3,4, Texture
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other < 1% Chrysotile
21142-2 / 21027123-002 DW,JC,KDT,CBM Back Storage 1,2,3,4, Mastic
Tan Non-Fibrous
Homogeneous
100% Other None Detected
21142-3 / 21027123-003 DW,JC,KDT,CBM Front Door 1,2,3,4, Drywall
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other None Detected
21142-3 / 21027123-003 DW,JC,KDT,CBM Front Door 1,2,3,4, Joint Compound
White Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/8/2021 Date: 6/8/2021
Approved Signatory:
21-142Project Number:
P.O. Number:
Project Name: NANG 6/2/2021Collected Date:
6/3/2021 9:50:00 AMReceived Date:
6/8/2021 4:35:34 PM
21027123 SanAir ID Number
FINAL REPORT
Wise ConsultingName:
Address: 5400 Mill Street
Suite A Reno, NV 89502
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
21142-3 / 21027123-003 DW,JC,KDT,CBM Front Door 1,2,3,4, Texture
White Non-Fibrous
Homogeneous
5% Cellulose 95% Other < 1% Chrysotile
21142-3 / 21027123-003 DW,JC,KDT,CBM Front Door 1,2,3,4, Mastic
Tan Non-Fibrous
Homogeneous
100% Other None Detected
21142-4 / 21027123-004 Rubber FT,M,FT,M Computer Lab 5,6,7,8, Rubber Floor Tile
Black Non-Fibrous
Homogeneous
100% Other None Detected
21142-4 / 21027123-004 Rubber FT,M,FT,M Computer Lab 5,6,7,8, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
21142-4 / 21027123-004 Rubber FT,M,FT,M Computer Lab 5,6,7,8, Floor Tile
Grey Non-Fibrous
Homogeneous
100% Other None Detected
21142-4 / 21027123-004 Rubber FT,M,FT,M Computer Lab 5,6,7,8, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
21142-4 / 21027123-004 Rubber FT,M,FT,M Computer Lab 5,6,7,8, Floor Tile
Tan Non-Fibrous
Homogeneous
97% Other 3% Chrysotile
21142-4 / 21027123-004 Rubber FT,M,FT,M Computer Lab 5,6,7,8, Mastic
Black Non-Fibrous
Homogeneous
97% Other 3% Chrysotile
21142-5 / 21027123-005 Rubber FT,M,FT,M Back Storage 5,6,7,8, Rubber Floor Tile
Black Non-Fibrous
Homogeneous
100% Other None Detected
21142-5 / 21027123-005 Rubber FT,M,FT,M Back Storage 5,6,7,8, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
Analyst:
Analysis Date: 6/8/2021 Date: 6/8/2021
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
21-142Project Number:
P.O. Number:
Project Name: NANG 6/2/2021Collected Date:
6/3/2021 9:50:00 AMReceived Date:
6/8/2021 4:35:34 PM
21027123 SanAir ID Number
FINAL REPORT
Wise ConsultingName:
Address: 5400 Mill Street
Suite A Reno, NV 89502
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
21142-5 / 21027123-005 Rubber FT,M,FT,M Back Storage 5,6,7,8, Floor Tile
Grey Non-Fibrous
Homogeneous
100% Other None Detected
21142-5 / 21027123-005 Rubber FT,M,FT,M Back Storage 5,6,7,8, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
21142-5 / 21027123-005 Rubber FT,M,FT,M Back Storage 5,6,7,8, Floor Tile
Not Analyzed
21142-5 / 21027123-005 Rubber FT,M,FT,M Back Storage 5,6,7,8, Mastic
Not Analyzed
21142-6 / 21027123-006 Rubber FT,M,FT,M Front Door 5,6,7,8, Rubber Floor Tile
Black Non-Fibrous
Homogeneous
100% Other None Detected
21142-6 / 21027123-006 Rubber FT,M,FT,M Front Door 5,6,7,8, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
21142-6 / 21027123-006 Rubber FT,M,FT,M Front Door 5,6,7,8, Floor Tile
Grey Non-Fibrous
Homogeneous
100% Other None Detected
21142-6 / 21027123-006 Rubber FT,M,FT,M Front Door 5,6,7,8, Mastic
Yellow Non-Fibrous
Homogeneous
100% Other None Detected
21142-6 / 21027123-006 Rubber FT,M,FT,M Front Door 5,6,7,8, Mastic
Not Analyzed
21142-7 / 21027123-007 CT Front Office 9
White Fibrous
Homogeneous
60% Cellulose 35% Glass
5% Other None Detected
Analyst:
Analysis Date: 6/8/2021 Date: 6/8/2021
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
21-142Project Number:
P.O. Number:
Project Name: NANG 6/2/2021Collected Date:
6/3/2021 9:50:00 AMReceived Date:
6/8/2021 4:35:34 PM
21027123 SanAir ID Number
FINAL REPORT
Wise ConsultingName:
Address: 5400 Mill Street
Suite A Reno, NV 89502
Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
21142-8 / 21027123-008 CT Computer Lab 9
White Fibrous
Homogeneous
60% Cellulose 35% Glass
5% Other None Detected
21142-9 / 21027123-009 CT Kitchen 9
White Fibrous
Homogeneous
60% Cellulose 35% Glass
5% Other None Detected
Analyst:
Analysis Date: 6/8/2021 Date: 6/8/2021
Approved Signatory:
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
21-142Project Number:
P.O. Number:
Project Name: NANG 6/2/2021Collected Date:
6/3/2021 9:50:00 AMReceived Date:
6/8/2021 4:35:34 PM
21027123 SanAir ID Number
FINAL REPORT
Wise ConsultingName:
Address: 5400 Mill Street
Suite A Reno, NV 89502
Disclaimer
This report is the sole property of the client named on the SanAir Technologies Laboratory chain-of-custody (COC). Results in the report are confidential information intended only for the use by the customer listed on the COC. Neither results nor reports will be discussed with or released to any third party without our client's written permission. The final report shall not be reproduced except in full without written approval of the laboratory to assure that parts of the report are not taken out of context. The information provided in this report applies only to the samples submitted and is relevant only for the date, time, and location of sampling. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample(s) in the condition in which they arrived at the laboratory and information provided by the client on the COC, such as: project number, project name, collection dates, po number, special instructions, samples collected by, sample numbers, sample identifications, sample type, selected analysis type, flow rate, total volume or area, and start stop times that may affect the validity of the results in this report. Samples were received in good condition unless otherwise noted on the report. SanAir assumes no responsibility or liability for the manner in which the results are used or interpreted. This report does not constitute and shall not be used to claim product certification, approval, or endorsement by NVLAP, NIST, or any other U.S. governmental agencies and may not be certified by every local, state, and federal regulatory agencies.
Samples are held for a period of 60 days. Fibers smaller than 5 microns cannot be seen with this method due to scope limitations.
For NY state samples, method EPA 600/M4-82-020 is performed.
NYELAP Disclaimer:
Polarized- light microscopy is not consistently reliable in detecting asbestos in floor covering and similar non-friable organically bound materials. Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing.
Asbestos Certifications NVLAP lab code 200870-0 City of Philadelphia: ALL-460 PA Department of Environmental Protection Number: 68-05397 California License Number: 2915 Colorado License Number: AL-23143 Connecticut License Number: PH-0105 Massachusetts License Number: AA000222 Maine License Number: LB-0075, LA-0084 New York ELAP lab ID: 11983 Rhode Island License Number: PCM00126, PLM00126, TEM00126 Texas Department of State Health Services License Number: 300440 Commonwealth of Virginia 3333000323 Washington State License Number: C989 West Virginia License Number: LT000616 Vermont License: AL166318 Louisiana Department of Environmental Quality: 212253, Cert 05088
Revision Date: 8/14/2020
Page 1 of 1Page 7 of 8
SanAir ID#: 21028255
Project #: 21-142
Project Name: NANG
Report Date: 6/14/2021
Analysis Report prepared for Wise Consulting
Dear Nathaniel Jenne, We at SanAir would like to thank you for the work you recently submitted. The 2 sample(s) were received on Wednesday, June 09, 2021 via Fax or Email request. The final report(s) is enclosed for the following sample(s):
21142-2, 21142-3.
These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.
Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory
Final Report Includes:
- Cover Letter
- Analysis Pages
- Disclaimers and Additional Information
Sample conditions:
- 2 samples in Good condition.
1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com
21-142Project Number:
P.O. Number:
Project Name: NANG 6/2/2021Collected Date:
6/9/2021 11:40:00 AMReceived Date:
6/14/2021 2:06:53 PM
21028255 SanAir ID Number
FINAL REPORT
Wise ConsultingName:
Address: 5400 Mill Street
Suite A Reno, NV 89502
Asbestos Bulk EPA PLM 400 Point Count Stereoscopic Components
SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers
21142-2 / 21028255-001 DW, JC, KDT, CBM Back Storage, Texture
White Non-Fibrous
Homogeneous
99.75% Other 0.25% Chrysotile
21142-3 / 21028255-002 DW, JC, KDT, CBM Front Door, Texture
White Non-Fibrous
Homogeneous
100% Other < 0.25% Chrysotile
Analyst:
Analysis Date: 6/14/2021 Date: 6/14/2021
Approved Signatory:
21-142Project Number:
P.O. Number:
Project Name: NANG 6/2/2021Collected Date:
6/9/2021 11:40:00 AMReceived Date:
6/14/2021 2:06:53 PM
21028255 SanAir ID Number
FINAL REPORT
Wise ConsultingName:
Address: 5400 Mill Street
Suite A Reno, NV 89502
Disclaimer
The final report cannot be reproduced, except in full, without written authorization from SanAir.
Fibers smaller than 5 microns cannot be seen with this method due to scope limitations. The accuracy of the results is dependent upon the client’s sampling procedure and information provided to the laboratory by the client. SanAir assumes no responsibility for the sampling procedure and will provide evaluation reports based solely on the sample and information provided by the client. This report may not be used by the client to claim product endorsement by NVLAP, AIHA or any other agency of the U.S. government; and may not be certified by every local, state and federal regulatory agencies.
Revision Date 1/17/2011 Page 1 of 1