260812_-_TARTA_9A_BID_PERMIT_DRAWING_SET.pdf

PDF 23 MB Posted

Attached to
Paratransit Garage Improvements
Solicitation number
2026-REQ-068
Issued by
Lucas County, Ohio

About this file

This is a bid permit drawing set for the Toledo Area Regional Transit Authority (TARTA) in Ohio, detailing the paratransit garage improvements project. The project scope encompasses resurfacing existing asphalt parking areas, modifying and extending fencing systems, and installing security gates and barriers to enhance the facility's overall condition, security, accessibility, and functionality. The drawing set provides comprehensive technical specifications and site plans necessary for bidders to understand the physical layout, existing conditions, and proposed modifications to the paratransit garage facility. The drawings serve as the primary reference documents for contractors preparing bids and establishing accurate project costs and timelines.

The project may require a Project Labor Agreement (PLA) as specified by TARTA, which bidders should account for in their proposals and cost estimates. The bid permit drawings establish the technical baseline and requirements that all bidders must follow, ensuring consistency in scope interpretation across all submitted proposals. These drawings are essential documents in the competitive bidding process, providing the detailed specifications required for contractors to assess site conditions, material requirements, labor needs, and project feasibility prior to submitting their bids to TARTA.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER

TOLEDO AREA REGIONAL TRANSIT AUTHORITY

612 N. HURON ST.

TOLEDO, OHIO 43604

CONTACT PERSON:

RICHARD L. BOWEN & ASSOCIATES INC.

2019 CENTER STREET, SUITE 500

CLEVELAND, OHIO 44113

216.491.9300 (PH)

216.283.5110 (FX)

CONTACT PERSON: KEN EMLING

CIVIL ENGINEER

ARCHITECT

DGL CONSULTING ENGINEERS

3455 BRIARFIELD BLVD.

SUITE E

MAUMEE, OHIO 43537

419.535.1015 (PH)

CONTACT PERSON: KYLE LAYTON

ELECTRICAL ENGINEER

HEAPY ENGINEERING

1422 EUCLID AVENUE

SUITE 1162

CLEVELAND, OHIO 44115

216.744.7393 (PH)

CONTACT PERSON: TIM KRZYWICKI

LANDSCAPE ARCHITECT

EDGE1422 EUCLID AVENUE

33 SOUTH MICHIGAN STREET, SUITE 100

TOLEDO, OHIO 43604

419.255.5335 (PH)

CONTACT PERSON: SEAN ALLEN

1. ALL EXISTING CONDITIONS TO BE VERIFIED PRIOR TO COMMENCEMENT OF WORK. IN THE EVENT OF ANY DISCREPANCIES, REPORT SAID ANOMALIES TO THE

ARCHITECT.

2. LOCATE ALL EXISTING UTILITIES AND SERVICES PRIOR TO START OF WORK.

3. ADHERE TO ALL ACCEPTED INDUSTRY PRACTICES.

4. FOLLOW ALL INSTALLATION PROCEDURES PER MANUFACTURER'S INSTRUCTIONS.

5. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT FOR ALL DIMENSION QUESTIONS.

6. CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE APPLICABLE CODES INCLUDING ACCESSIBILITY STANDARDS AND

REQUIREMENTS OF "AMERICANS WITH DISABILITIES ACT."

7. MAINTAIN ALL EGRESS SIGNAGE AND ROUTES DURING CONSTRUCTION.

8. MAINTAIN TEMPORARY CONSTRUCTION BARRIERS AND CLEAR SIGNAGE DURING CONSTRUCTION.

UNDERGROUND UTILITIES

TWO WORKING DAYS BEFORE DIGGING CALL #800-362-2764 (TOLL FREE). OHIO UTILITIES

PROTECTION SERVICE . NON-MEMBERS MUST BE CALLED DIRECTLY

ISSUES AND REVISIONS

DateNo.

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

RLB NO.:

CHECKED BY:

DRAWN BY:

Description

O H

C en te r S t.

, S ui te

C le ve la nd

O hi o

P

A

S ta te S t.

, S ui te

E rie

P A w w w .r lb a.

co m

© RICHARD L. BOWEN + ASSOCIATES, INC.

8/

/2

9:

:5

A

M C

:\U se rs \n pa nd av \D oc um en ts

\T as k 9A

_C ov er S he et

O nl y_ np an da v8 6V

.r vt

T A

R T

A P

A R

A T

R A

N S

IT

G

A R

A G

E

S

IT

E

IM

P R

O V

E M

E N

T S

13828.09A

K N

A P

P S

T

T O

LE

D

O , O

H

C O

V E

R S

H E

E T

DJK

KJE

CS

AUGUST 12, 2026

130 KNAPP ST., TOLEDO, OH 43604BID/PERMIT SET

TARTA PARATRANSIT GARAGE - SITE IMPROVEMENTS

DRAWING INDEX

NUMBER NAME

GENERAL

CS COVER SHEET

CIVIL

C0.1 CIVIL NOTES

CD1.1 DEMOLITION PLAN - SITE IMPROVEMENTS

C1.0 SCHEMATIC PLAN - SITE IMPROVEMENTS

C1.1 PARKING LOT PLAN - BASE BID

C2.1 GRADING & EROSION CONTROL PLAN - BASE BID

C3.0 FENCING PLAN - BASE BID

C4.0 GATE SPECIFICATIONS

C5.0 ALTERNATE 1 - SIDEWALK PLAN

C5.1 ALTERNATE 1 - SIDEWALK GRADING PLAN

LANDSCAPE

L1.1 LANDSCAPE PLAN

ELECTRICAL

E001 ELECTRICAL ABBREVIATIONS, SYMBOLS, LEGENDS, NOTES

ES100 ELECTRICAL SITE PLAN

INDEX OF DRAWINGSPROJECT TEAMVICINITY MAP

PROJECT SITE

MAUMEE RIVER

EM

R

AL

D

A

VE

EMRALD AVE.

W

ILLIAM

ST.

W

ADE S

T.

GENERAL PROJECT NOTES

12/08/26 BID/PERMIT SET

8/12/26

ISSUES AND REVISIONS

DateNo.

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

CIV

IL

NO

TE

S

JL

KWL

C0.1

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C0 .1

NO

TE

S

TA

RT

A

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

GENERAL NOTES

EARTHWORK

GENERAL UTILITY NOTES

STORM SEWERS

MANUFACTURED INLET FILTER INLET FILTER SPECIFICATIONS

MECHANICAL

PROPERTIES

TEST

METHOD MARV

SECTION

ASPHALT PAVEMENT SECTION*MILLING SECTION

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

TYPICAL FENCE PANEL ARRANGEMENT

TYPICAL PAINTED CROSSWALK DETAIL

CONCRETE SECTION

TYPICAL ASPHALT PATH SECTION

TYPICAL ASPHALT PATH SECTIONPIPE BOLLARD IN PAVEMENT

NOT TO SCALE

TYPICAL CONCRETE ISLAND DETAIL

CONCRETE STAIR DETAIL

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

06.26.262 CD Set

08.11.263 Bid & Permit

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

DE

MO

LIT

ION

P

LA

N -

SI

TE

IM

PR

OV

EM

EN

TS

JL

KWL

CD1.1

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

CD

1.1

D

EM

O

TA

RT

A

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

0 30 60

SCALE: 1" = 30'

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

DEMOLITION PLAN

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

SC

HE

MA

TIC

P

LA

N -

SI

TE

IM

PR

OV

EM

EN

TS

JL

KWL

C1.0

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C1 .0

SC

HE

M

TA

RT

A

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

0 30 60

SCALE: 1" = 30'

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

SCHEMATIC PLAN

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

PA

RK

ING

LO

T P

LA

N -

BA

SE

BI

D

JL

KWL

C1.1

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C1 .1

PL

AN

T

AR

TA

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

0 10 20

SCALE: 1" = 10'

PARKING LOT C PLAN

PARKING LOT B PLAN PARKING LOT A PLAN

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

GR

AD

ING

ER

OS

ION

CO

NT

RO

L

PL

AN

- B

AS

E B

ID

JL

KWL

C2.1

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C2 .1

GR

AD

T

AR

TA

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

0 10 20

SCALE: 1" = 10'

PARKING LOT C PLAN

PARKING LOT B PLAN PARKING LOT A PLAN

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

FE

NC

ING

P

LA

N -

BA

SE

BI

D

JL

KWL

C3.0

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C3 .0

FE

NC

E

TA

RT

A

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

0 20 40

SCALE: 1" = 20'

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

04FENCING PLAN

SCALE: 1" = 20'

ACCESS GATES ENLARGED PLAN

SCALE: 1" = 10'

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-10

GA

TE

SP

EC

IFI

CA

TIO

NS

JL

KWL

C4.0

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C4 .0

GA

TE

T

AR

TA

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

48" [4']

84" [7']

BELOW

FROST

LEVEL

(3' MIN.)

LEFT HAND

OPERATOR

HEIGHT

VARIES

LENGTH VARIES

PRIVATE SIDE

PUBLIC SIDE

3" SETBACK (MIN.) FACE OF OPERATOR TO FACE OF YOKE (CLEAR OPENING) VARIES

8" SETBACK (6" MIN.)

WIND BRACING

PAD TO PAD WILL VARY WITH GATE LENGTH

(MAY ALSO BE VIEWED AS CLEAR OPENING)

18" [1'-6"]

13" [1'-1"]

STYLE "E" YOKE SHOWN

GATE GUARD

BARRIER SCREENING (REQ'D.)

BELOW

FROST

LEVEL

(3' MIN)

LEFTHAND - VERTICAL PIVOT GATE (VPG)

2) LENGTH AND HEIGHT VARIES, CONSULT WITH AUTOGATE SALES FOR MORE INFORMATION.

1) ALL OF OUR GATES ARE TYPICALLY DRAWN FROM THE PRIVATE SIDE LOOKING OUT.

3) SHOWN WITH STANDARD 5' STYLE "E" YOKE. SEE DRAWING #105 FOR YOKE STYLES.

NOTES:

4) CONTOURS AND CURBS WILL REQUIRE CUSTOM DRAWINGS. (CONSULT WITH AUTOGATE).

RIGHTHAND - VERTICAL PIVOT GATE (VPG)

GRADE/PAD LEVEL

CONCRETE OPERATOR PAD

CONCRETE YOKE PAD

VIEWED FROM THE PRIVATE SIDE

ELEVATION VIEW

5" ABOVE GRADE (TYP.)

*3" WITH BOTTOM EDGE

48" [4']

84" [7']

BELOW

FROST

LEVEL

(3' MIN.)

RIGHT HAND

OPERATOR

HEIGHT

VARIES

LENGTH VARIES

PRIVATE SIDE

PUBLIC SIDE

FACE OF OPERATOR TO FACE OF YOKE (CLEAR OPENING) VARIES 3" SETBACK (MIN.)

8" SETBACK (6" MIN.)

WIND BRACING

PAD TO PAD WILL VARY WITH GATE LENGTH

(MAY ALSO BE VIEWED AS CLEAR OPENING)

18" [1'-6"]

13" [1'-1"]

STYLE "E" YOKE SHOWN

GATE GUARD

BARRIER SCREENING (REQ'D.)

BELOW

FROST

LEVEL

(3' MIN)

GRADE/PAD LEVEL

CONCRETE OPERATOR PAD

CONCRETE YOKE PAD

VIEWED FROM THE PRIVATE SIDE

ELEVATION VIEW

5" ABOVE GRADE (TYP.)

*3" WITH BOTTOM EDGE

PLAN VIEW PLAN VIEW

BUCKEYE "500" VERTICAL PIVOT GATE (VPG)

Drawn By:

Dwg./AG#:

Title:

MKS

Date Drawn:

Checked By:

AutoGate Gate Entry Systems

Berlin Heights, Ohio

FAX (419) 588-3514

THE INFORMATION CONTAINED

ON THIS DOCUMENT IS

CONFIDENTIAL. ANY

DISSEMINATION, UNAPPROVED

DISCLOSURE OR COPYING OF

THIS INFORMATION IS

STRICTLY PROHIBITED

NOTICE

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN INCHES

ANGLES ± 1°

X/X ± 1/32, .XX ± .01, .XXX ± .005

M:\DRAWING FILES\AG UPDATED DWGS JUNE 2025 FROM CAM\500 BUCKEYE FLAT TOP VPG.DWG

DMR

500 BUCKEYE FLAT TOP VPG

Rev.: Date:

DO NOT SCALE

Description: Drn. By:Ckd. By:

04/19/07

UPDATED PRINT - OPERATOR SHOWN MORE ACCURATELY 03/04/13 SLD MKS

VPG WAS VPL & INCREASED BARRIER SCREEN COVERAGE 04/29/15 MKS DMR

COMBINED LEFT AND RIGHT HAND GATES ON ONE PRINT 07/20/16 MKS KAY

A

B

C

D UPDATED PRINT - OPERATOR SHOWN MORE ACCURATELY 05/20/25 CJW BKW

OPTION #1:

(4) or (5) MIN. 12" AUGURED HOLES, WITH WIRE TIED RE-BAR, ON 10" TO 12" TOP PAD

OPTION #2:

FULL CONCRETE PAD WITH TIED RE-BAR WHERE

APPLICABLE PER GOVERNING CODE OR STANDARD.

48"

84"

Ø12" TYP.

OPTION:

CENTER

COLUMN

BELOW

LOCAL

FROST

DEPTH

(3' MIN.)

10" to 12" TOP

PAD THICKNESS

B

48"

84"

BELOW

LOCAL

FROST

DEPTH

(3' MIN.)

6"- 8"

NOTES:

1) ALL PAD DEPTHS SHOULD BE BELOW LOCAL FROST DEPTH

2) TOP OF PAD MUST BE FLAT AND LEVEL

3) USE REBAR THAT CONFORMS WITH LOCAL CODES OR JOB SPECS.

4) REBAR MUST BE INSTALLED 6"-8" BELOW TOP SURFACE.

5) CONCRETE COMPRESSIVE STRENGTH MINIMUM 3000 PSI.

5) DRAWING IS FOR REFERENCE ONLY, SUPERCEDED BY LOCAL AND SITE GOVERNING CODES

32" REF.

68" REF.

28" REF.

REBAR ARRANGEMENT

(SECURELY WIRE TIE ALL

13 INTERSECTING POINTS)

TIE (13x)

32" REF.

68" REF.

28" REF.

REBAR ARRANGEMENT

(SECURELY WIRE TIE ALL

9 INTERSECTING POINTS)

TIE (9x)

12" REF.

TYP.

OPTION #1:

OPTION #2:

Operator PAD Layout / Options

102-P

Drn. By:

Dwg.:

Title:

MKS

Date:

Ckd. By:

12/21/05 AutoGate Gate Entry Systems

Berlin Heights, Ohio

FAX (419) 588-3514

THE INFORMATION CONTAINED

ON THIS DOCUMENT IS

CONFIDENTIAL. ANY

DISSEMINATION, UNAPPROVED

DISCLOSURE OR COPYING OF

THIS INFORMATION IS

STRICTLY PROHIBITED

NOTICE

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN INCHES

ANGLES ± 1°

X/X ± 1/32, .XX ± .01, .XXX ± .005

Date:

A CONDUIT LOCATIONS WERE MOVED OUTSIDE THE PAD 07/18/08

Rev.: Description:

DO NOT SCALE

Drn. By:Ckd. By:

MKS

B 10" TO 12" PAD THICKNESS WAS 8" TO 10" 01/24/13 SLD

C ENHANCED REBAR DETAIL 11/5/15 KAY

KLL

DMR

C:\USERS\BFRITZ2\DESKTOP\102-P PAD LAYOUT.DWG

DMR

DMR

KAY 11/5/15

OPTIONAL FREE EXIT

VEHICLE PROBE

AC

C

ES

S

C O

N

TR

O

LS

(M in

. 1 5'

FR

EE

E

XI

T

LO

O

P an d/ or

P R

O

BE

(T yp

. 2 0' to

PUBLIC SIDE

PRIVATE/SECURED SIDE

INFRARED PHOTO / SAFETY BEAM

STANDARD PAD YOKE

ENTRY KEYPAD

EXIT KEYPAD

6" BOLLARD (Typ.) RECOMMENDED

TYPICAL CONDUIT RUNS

#1. LOOP "HOMERUNS" (HR)

#2. 120V POWER SUPPLY (20 AMP CIRCUIT)

#3. ACCESS SIGNAL TO REMOTE (IF APPLICABLE)

#4. KEYPAD/CARD/PHONE SIGNAL & POWER

#5. IFR POWER/PROBE HR (IF APPLICABLE)

#6. IF INFRARED HEATER IS NEEDED RUN

ADDTIONAL 15 AMP CIRCUIT

LOOP HOMERUN

FREE EXIT LOOP

* CUSTOM SIZES AVALABLE

* OPTIONAL LOOP - NOT REQ'D

ON SOME INSTALLATIONS

REVERSING OR FREE EXIT LOOP

STANDARD SIZE (6' X 10')

(MINIMUM OF 4' FROM GATE)

REVERSING LOOP

STANDARD SIZE (6' X 10')

(MINIMUM OF 4' FROM GATE)

#3

#5

#1 #4

#2

#4

#1

LEFTHAND OPERATOR

CONCRETE OPERATOR PAD

ROAD / DRIVE WIDTH

LEFTHAND

OPERATOR

IFR BEAM or REFLECTOR

OPTIONAL FREE EXIT

VEHICLE PROBE

AC

C

ES

S

C O

N

TR

O

LS

(M in

. 1 5'

FR

EE

E

XI

T

LO

O

P an d/ or

P R

O

BE

(T yp

. 2 0' to

INFRARED PHOTO / SAFETY BEAM

STANDARD PAD YOKE

ENTRY KEYPAD

EXIT KEYPAD

See: Dwg. #111 & 112

FOR MORE DETAILS

6" BOLLARD (Typ.) RECOMMENDED

TYPICAL CONDUIT RUNS

#1. LOOP "HOMERUNS" (HR)

#2. 120V POWER SUPPLY (15AMP CIRCUIT)

#3. ACCESS SIGNAL TO REMOTE (IF APPLICABLE)

#4. KEYPAD/CARD/PHONE SIGNAL & POWER

#5. IFR POWER/PROBE HR (IF APPLICABLE)

#6. IF INFRARED HEATER IS NEEDED RUN

ADDTIONAL 15 AMP CIRCUIT

LOOP HOMERUN

#3

#5

#4

#1

#2

#4

#1

RIGHTHAND OPERATOR

CONCRETE OPERATOR PAD

ROAD / DRIVE WIDTH

RIGHTHAND

OPERATOR

IFR BEAM or REFLECTOR

FREE EXIT LOOP

* CUSTOM SIZES AVALABLE

* OPTIONAL LOOP - NOT REQ'D

ON SOME INSTALLATIONS

REVERSING OR FREE EXIT LOOP

STANDARD SIZE (6' X 10')

(MINIMUM OF 4' FROM GATE)

REVERSING LOOP

STANDARD SIZE (6' X 10')

(MINIMUM OF 4' FROM GATE)

LOOP HOMERUN

LOOP HOMERUN

NORMALLY, THE GATE LENGTH MUST EXCEED THIS WIDTH BY AT LEAST 12"

(FOR CURB and/or CONTOUR APPLICATIONS - See: Dwg. #120, 121, 122 & 151)

PUBLIC SIDE

PRIVATE/SECURED SIDE

NORMALLY, THE GATE LENGTH MUST EXCEED THIS WIDTH BY AT LEAST 12"

(FOR CURB and/or CONTOUR APPLICATIONS - See: Dwg. #120, 121, 122 & 151)

See: Dwg. #111 & 112

FOR MORE DETAILS

100 Operator & Accessory Site Layouts (LH & RH)

Dr. By:

Dwg.:

Title:

MKS

Date: 07/21/16 AutoGate Gate Entry Systems

Berlin Heights, Ohio

FAX (419) 588-3514

THE INFORMATION CONTAINED

ON THIS DOCUMENT IS

CONFIDENTIAL. ANY

DISSEMINATION, UNAPPROVED

DISCLOSURE OR COPYING OF

THIS INFORMATION IS

STRICTLY PROHIBITED

NOTICE

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN INCHES

ANGLES ± 1°

X/X ± 1/32, .XX ± .01, .XXX ± .005

Rev.: Description: Date:

DO NOT SCALE

Drn. By:Ckd. By:

MKS 07/21/16 AUTOGATEINC.LOCAL\SHARES\USERS\BFRITZ2\DOCUMENTS\DOCUMENTS\AUTOGATE SPEC TECH AND VIDEO\STD VPG DWG DRAWINGS\100 OPERATOR AND ACCESSORY SITE LAYOUT.DWG

Ckd. By: KAY

100 Operator & Accessory Site Layouts (LH & RH)

STA

TE OF OHIO

PROFESS I ONAL ENG I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ER E DR

August 11, 2026 August 11, 2026

06.05.261 Schematic

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

AL

TE

RN

AT

E 1

- S

IDE

WA

LK

PL

AN

EJW

JL

C5.0

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C5 .0

SW

LK

S

CH

EM

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

0 20 40

SCALE: 1" = 20'

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

ALTERNATE 2 - PATIO AREA

ALTERNATE 1 - SIDEWALK PLAN

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

DGL NO.:

CHECKED BY:

DRAWN BY:

24177-9A

AL

TE

RN

AT

E 1

- S

IDE

WA

LK

GR

AD

ING

PL

AN

EJW

JL

C5.1

A ug

, 2

6 -

6:

pm Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

C:

\U se rs\ lito a\A pp Da ta\ Lo ca l\T em p\A cP ub lis h_

2\2

-9

A

CD

.dw g:

C5 .1

SW

LK

G

RA

D

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

DG

L

CO

N

SU

LT

IN

G

E N

G

IN

EE

RS

, L

LC

B

RI

AR

FI

EL

D

BL

VD

. S U

IT

E

E M

AU

M

EE

, O

H

PH

O

N E:

.5

.1 w w w

.d gl

-lt d.

co m

0 20 40

SCALE: 1" = 20'

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

0 K

NA

PP

ST

RE

ET

TO

LE

DO

, O

H 4

ALTERNATE 2 - PATIO GRADING

ALTERNATE 1 - SIDEWALK GRADING PLAN

STA

TE OF OHIO

PROFESS IONAL ENG

I N

EE

R

JOSHUA

LAU

E-87832

EG I S T ERED

R

August 11, 2026 August 11, 2026

06.05.261 Schematic

LAWN

LAWN

LAWN

LAWN

LAWN

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

DETENTION AREA

6' BESSEMER BENCH

WITH BACK BY KEYSTONE

RIDGE DESIGNS.

DT

DT

DT

DT

UP

RIP RAP DITCH

LAWN

UNDISTURBED SOIL

OR COMPACTED

BACKFILL

EXISTING SOIL

BACKFILL PLANTING MIX

FINISH GRADE

HARDWOOD BARK MULCH

NOTES:

1. TOP OF ROOT BALL TO BE 2"-3" ABOVE ADJACENT FINISH

GRADE

2. REMOVE ROPE AND BURLAP FROM TOP 1/3 OF ROOT BALL.

CUT TOP 1/3 OF WIRE BASKET FROM ROOT BALL. REMOVE ALL

LABELS,TAGS OR OTHER FOREIGN MATERIALS FROM LIMBS.

o o o ooo ooo

ON CENTER

MIXED PLANTING

(PERENNIAL / BULB)

TYPICAL BULB

CLUSTER PLANTING

(5 BULBS IN 12" DIA. CIRCLE)

TYPICAL PERENNIAL

CONTAINER PLANTING

BEDLINE

NOTE: QUANTITIES ON PLAN ARE FOR

PERENNIALS. LAYOUT PERENNIAL

PLANTS FIRST, THEN PLANTS BULBS

EQUIDISTANT TO PERENNIALS AS

SHOWN.

VARIES

(EQ.)

V A

RI

ES

(E Q

PARKING

PARKING

PERENNIAL MIX 1 (139 sf) 32 - Hemerocallis x 'Big Time Happy' 32 - Nepeta x 'Cat's Pajamas'

PERENNIAL MIX 1 (146 sf) 34 - Hemerocallis x 'Big Time Happy' 34 - Nepeta x 'Cat's Pajamas'

PX

PX

105 sf

HB

PERENNIAL MIX 1 (273 sf) 63 - Hemerocallis x 'Big Time Happy' 63 - Nepeta x 'Cat's Pajamas'

UP

PERENNIAL MIX 2 (228 sf) 35 - Echinacea x 'PAS702918' 35 - Hemerocallis x 'Big Time Happy' 35 - Nepeta x 'Cat's Pajamas'

DT

PX

AG

DT

AG

ISSUES AND REVISIONS

DateNo.

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

RLB NO.:

CHECKED BY:

DRAWN BY:

TA

RT

A

- P

AR

AT

RA

NS

IT

G

AR

AG

E

13828.09

0 K

NA

PP

S

TR

EE

T, T

OL

ED

O, O H

LU

CA

S

CO

UN

TY

LA

ND

SC

AP

E

PL

AN

BW

SA

L1.1

/7/

3:

:46 P

M Description

C en ter S t, S uit e 5

/ C lev ela nd

, O hio

Ph on e:

(2

) 4

-9

F ax

6)

1-ww w.

rlb a.c om

Fil e P ath

2026© RICHARD L. BOWEN + ASSOCIATES, INC.

1 06/12/26 SCHEMATIC

2 08/05/26 CD SET

3 08/11/26 CD SET

EXISTING PARATRANSIT GARAGE

WADE S

TREET

DOCTOR M

LK JUNIOR DRIVE

WILLIAMS STREET

EM

ER

ALD

A

VE

NUE

ALTERNATE 1 LANDSCAPE PLAN1

S

O

UT

H M

IC

HI

G A

N S

TR

EE

T, S

UI

TE

TO

LE

D O

, O H

9.

5.

w w w

.e d ge la

.c om

PLANTING CONSTRUCTION NOTES:

EXISTING TREE TO BE REMOVED.

REPAIR LAWN AREA, FILL VOIDS WITH TOPSOIL AS

REQUIRED AND MEET ADJACENT SURFACES FLUSH.

PROVIDE POSITIVE DRAINAGE ACROSS ALL

SURFACES.

LANDSCAPE AREA, PROVIDE MINIMUM DEPTH OF 18"

PLANTING SOIL MIX. SEE SPECIFICATIONS FOR SOIL

MIX. HOLD TOP OF SOIL DOWN 3" FROM TOP OF

CURB AND/OR ADJACENT PAVEMENT TO ALLOW FOR

INSTALLATION OF MULCH. PROVIDE POSITIVE

DRAINAGE ACROSS ALL SURFACES.

EXISTING PLANTING TO REMAIN, PRESERVE AND

PROTECT.

KEYPLAN

AB

N.I.C.

A

N.I.C.

AB

N.I.C.

B

NORTH60'30'15'0'

ALTERNATE 2 PLANT SCHEDULE

SYMBOL CODE QTY BOTANICAL NAME COMMON NAME SIZE CONTAINER REMARKS

TREES

AG 4 AMELANCHIER X GRANDIFLORA 'AUTUMN

BRILLIANCE' AUTUMN BRILLIANCE SERVICEBERRY 2.5" CAL. B&B MATCH SHAPE

AND SIZE.

UP 2 ULMUS X 'HOMESTEAD' HOMESTEAD ELM 2.5" CAL. B&B MATCH SHAPE

AND SIZE.

SHRUBS

DT 80 DESCHAMPSIA CESPITOSA TUFTED HAIR GRASS 1 GAL. CONT.

PX 71 DIERVILLA X 'G2X885411' KODIAK RED DIERVILLA 3 GAL. CONT.

PERENNIALS AND MIXES

558 SF PERENNIAL MIX 1

129 HEMEROCALLIS X 'BIG TIME HAPPY' BIG TIME HAPPY DAYLILY 1 GAL. FLAT 18" O.C.

129 NEPETA X 'CATS PAJAMAS' CAT'S PAJAMAS CATMINT 1 GAL. FLAT 18" O.C.

8 HEMEROCALLIS X 'STELLA DE ORO' STELLA DE ORO DAYLILY 1 GAL. FLAT 18" O.C.

228 SF PERENNIAL MIX 2

ECHINACEA X 'PAS702918' POWWOW WHITE CONEFLOWER 1 GAL. FLAT 18" O.C.

HEMEROCALLIS X 'BIG TIME HAPPY' BIG TIME HAPPY DAYLILY 1 GAL. FLAT 18" O.C.

NEPETA X 'CAT'S PAJAMAS' CAT'S PAJAMAS CATMINT 1 GAL. FLAT 18" O.C.

105 SF HEMEROCALLIS X 'BIG TIME HAPPY' BIG TIME HAPPY DAYLILY 1 GAL. FLAT 18" O.C.

GENERAL NOTES - LANDSCAPE PLANTING

1. EACH CONTRACTOR IS TO VERIFY WITH OWNER AND UTILITY

COMPANIES THE LOCATIONS OF ALL UTILITIES PRIOR TO

CONSTRUCTION, TO DETERMINE IN THE FIELD THE ACTUAL LOCATIONS

AND ELEVATIONS OF ALL EXISTING UTILITIES, WHETHER SHOWN ON THE

PLANS OR NOT. THE CONTRACTOR SHALL CALL UTILITY PROTECTION

SERVICE 72 HOURS PRIOR TO CONSTRUCTION.

2. EXAMINE FINISH SURFACE, GRADES, TOPSOIL QUALITY AND DEPTH.

DO NOT START ANY WORK UNTIL UNSATISFACTORY CONDITIONS HAVE

BEEN CORRECTED. VERIFY LIMITS OF WORK BEFORE STARTING.

3. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PERFORM ALL

WORK IN A MANNER THAT PROTECTS COMPLETED WORK BY OTHERS,

SUCH AS CURBS, UTILITIES, STORM DRAINAGE, FENCES, DRIVEWAY

APRONS, DRIVES, VEGETATION, ETC. THE CONTRACTOR SHALL BE

RESPONSIBLE FOR THE COST OF SATISFACTORY REPAIR OF ALL

DAMAGE IN KIND RESULTING FROM HIS FAILURE TO COMPLY.

4. ALL PLANTING OPERATIONS SHALL ADHERE TO THE AMERICAN

STANDARD FOR NURSERY STOCK (ANSI Z60.1) 2014. CONTRACTOR IS

RESPONSIBLE FOR ALL PLANT QUANTITIES SHOWN ON THE PLANS

5. QUANTITIES OF PLANTS AS SHOWN BY PLANT SYMBOLS ON THE PLAN

SHALL GOVERN OVER THE QUANTITIES SHOWN IN THE PLANT LIST. THE

CONTRACTOR IS TO VERIFY PLANT LIST TOTALS WITH QUANTITIES

SHOWN ON PLAN. THE LANDSCAPE ARCHITECT SHALL BE ALERTED BY

THE CONTRACTOR OF ANY DISCREPANCIES PRIOR TO FINAL BID

NEGOTIATION.

6. ALL WORK SHALL MEET OR EXCEED THE REQUIREMENTS OF ALL

APPLICABLE FEDERAL, STATE AND LOCAL LAWS, ORDINANCES AND

REQUIREMENTS.

7. ALL MATERIALS SHALL BE SUBJECT TO APPROVAL BY THE

LANDSCAPE ARCHITECT. THE OWNER SHALL RECEIVE TAGS FROM EACH

PLANT SPECIES AND A LIST OF PLANT SUPPLIERS.

8. PLANT SHALL BE PRUNED PRIOR TO DELIVERY ONLY UPON THE

APPROVAL OF THE LANDSCAPE ARCHITECT.

9. LIFTING STRAPS, ROOTBALL STRAPS AND WIRE BASKETS ARE TO BE

REMOVED AND BURLAP IS TO BE ROLLED BACK ONE-THIRD ON ALL B&B

PLANT MATERIAL. ANY SYNTHETIC BURLAP SHALL BE COMPLETELY

REMOVED FROM ANY PLANT MATERIAL

10. SHADE TREE MEASUREMENT: CALIPER SHALL BE MEASURED AT SIX

INCHES ABOVE THE ROOTBALL. HEIGHT SHALL BE MEASURED FROM

THE CROWN OF THE ROOT BALL TO THE TOP OF MATURE GROWTH.

SPREAD SHALL BE MEASURED TO THE END OF BRANCHING EQUALLY

AROUND THE CROWN FROM THE CENTER OF THE TRUNK.

MEASUREMENTS ARE NOT TO INCLUDE ANY TERMINAL GROWTH. SINGLE

TRUNK TREES SHALL BE FREE OF "V" CROTCHES THAT COULD BE

POINTS OF WEAK LIMB STRUCTURE OR DISEASE INFESTATION. WHERE

TREES ARE PLANTED IN ROWS, THEY SHALL BE UNIFORM IN SIZE AND

SHAPE

11. SHRUBS MEASUREMENT: HEIGHT SHALL BE MEASURED FROM THE

GROUND TO THE TOP OF THE PLANT. SPREAD SHALL BE MEASURED TO

THE END OF BRANCHING EQUALLY AROUND THE SHRUB MASS.

MEASUREMENTS ARE NOT TO INCLUDE ANY TERMINAL GROWTH.

12. NO SUBSTITUTIONS OF PRODUCTS, PLANT TYPES OR SIZES SHALL

BE MADE WITHOUT THE WRITTEN APPROVAL OF THE OWNER,

LANDSCAPE ARCHITECT. REQUESTS FOR SUBSTITUTION SHALL BE IN

WRITING, AND SHALL STATE THE REASONS FOR THE SUBSTITUTION

REQUEST, THE SUGGESTED ALTERNATIVE, AND THE CHANGES IN COST.

REQUESTS FOR SUBSTITUTION IN PLANT MATERIALS SHALL STATE THE

NAMES OF NURSERIES WHO HAVE BEEN UNABLE TO SUPPLY THE

ORIGINALLY SPECIFIED MATERIAL.

13. FINISHED PLANTING BEDS SHALL BE GRADED SO AS NOT TO IMPEDE

DRAINAGE AWAY FROM BUILDINGS.

Scale: NTS

TREE PLANTING DETAIL5

5'

5'

3" LAYER HARDWOOD BARK MULCH, KEEP

MULCH 3" BACK FROM TRUNK WITH

1" DEPTH OF TOP-DRESSING OF EPA RATED

CLASS IV COMPOST FOR ENTIRE MULCH RING

AREA

FINISHED GRADE

RIPPED NATIVE SOIL AMENDED WITH 2" DEPTH

OF COMPOST AND TILLED TO A DEPTH OF 10"

- MIX THOROUGHLY

24" DEPTH OF RIPPED NATIVE SOIL

REMOVE ALL METAL TIES. ROPES, BURLAP,

AND WIRE BASKET (IF ANY) FROM ROOTBALL

ENTIRELY

SET BALL ON FIRMLY PACKED SOIL BASE TO

PREVENT SETTLING -TOP OF ROOT BALL TO BE

2" ABOVE FINISHED GRADE

BACKFILL TREE EXCAVATION WITH

EXCAVATED SOIL FROM HOLE

EXISTING UNDISTURBED NATIVE SOIL - DRIVE

STAKES 18" MIN. INTO UNDISTURBED SOIL

USE 2 HARDWOOD STAKES AND OPPOSING

FLEXIBLE TIES WHEN STAKING IS NECESSARY

3x ROOTBALL - MIN.

5' DIA. MULCH RING

5' SQ. MIN. PREPARED AREA

NOTE:

REMOVE EXCESS SOIL FROM ROOTBALL TO

EXPOSE ROOT FLAIR AND TRIM ANY

SECONDARY/ADVENTITIOUS, GIRDLING AND

POTENTIAL GIRDLING ROOTS WITH CLEAN

SHARP PRUNING TOOLS.

5' DIA. MULCH

RING - TYP.

TREE IN CENTER

OF SPACE - TYP.

25 SQ. FT.

PREPARED AREA

PER TREE - TYP.

ADJACENT LAWN OR

PLANTING BED - SEE PLAN

ALTERNATE 1 PLANTING SCHEDULE

SYMBOL CODE QTY BOTANICAL NAME COMMON NAME SIZE CONTAINER REMARKS

TREES

UP 2 ULMUS X 'HOMESTEAD' HOMESTEAD ELM 2.5" CAL. B&B MATCH SHAPE

AND SIZE.

SHRUBS

DT 260 DESCHAMPSIA CESPITOSA TUFTED HAIR GRASS 1 GAL. CONT.

Scale: NTS SHRUB PLANTING DETAIL4Scale: NTS

PERENNIAL PLANTING DETAIL3

ALTERNATE 2 - PATIO AREA2

NORTH60'30'15'0'

S-BEO26-00-00-000-00, BESSEMER BENCH WITH

BACK, 6,' BY KEYSTONE RIDGE DESIGNS. FINISH

POWDER COATED, STEEL. COLOR TO BE SELECTED

BY OWNER. SURFACE MOUNTED. INSTALL PER

MANUFACTURER RECOMMENDATIONS.

BASE BID SCOPE OF WORK:

ALL EXISTING LANDSCAPING TO REMAIN. PROTECT AND RESTORE AS

REQUIRED TO ACCOMMODATE NEW WORK.

SEE ALTERNATE 2 SCOPE- THIS SHEET

AutoCAD SHX Text

MIN.

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text L

AutoCAD SHX Text D

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text S

AutoCAD SHX Text J.

AutoCAD SHX Text

BOCKBRADER

AutoCAD SHX Text A

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text I

AutoCAD SHX Text H

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text T

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text C

AutoCAD SHX Text

TIMOTHY

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text A

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text H

AutoCAD SHX Text O

AutoCAD SHX Text I

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text G

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text D

ELECTRICAL SYMBOLS

EXISTING OUTLET OR DEVICE TO REMAIN. MAINTAIN EXISTING CIRCUITING.

DASH SYMBOL INDICATES PARTICULAR OUTLET OR DEVICE TO BE REMOVED AND CIRCUITRY MADE CONTINUOUS WHERE

REQUIRED.

ELECTRICAL CONNECTION.

20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE).

SPECIAL PURPOSE RECEPTACLE. REFER TO NOTE ON PLAN.

20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" MH UNLESS NOTED OTHERWISE) TWO GANG ASSEMBLY.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH BOTTOM OUTLET CONTROLLED BY WALL SWITCH. (18" MH UNLESS

NOTED OTHERWISE).

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED

OTHERWISE).

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R (HORIZONTAL 18" MH UNLESS NOTED OTHERWISE) WITH

TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.

20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R WITH GROUND FAULT CIRCUIT INTERRUPTER (18" MH UNLESS NOTED OTHERWISE), WITH TAYMAC #MM420G EXTRA DUTY GRAY COVER, VERTICAL MOUNT.

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, ON EMERGENCY POWER (18" MH UNLESS NOTED OTHERWISE).

20A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-20R (18" MH UNLESS NOTED OTHERWISE).

30A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-30R (18" MH UNLESS NOTED OTHERWISE).

50A-125/250V-1PH-4W SINGLE RECEPTACLE, NEMA 14-50R (18" MH UNLESS NOTED OTHERWISE).

JUNCTION BOX.

SINGLE POLE SWITCH (46" MH UNLESS NOTED OTHERWISE).

TWO POLE WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

MULTI-WAY WALL SWITCH, # INDICATES NUMBER OF WAYS (46" MH UNLESS NOTED OTHERWISE).

SWITCH WITH NEON PILOT LIGHT. ONE-GANG ASSEMBLY (46" MH UNLESS NOTED OTHERWISE).

KEY OPERATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

LIGHTING DIMMER SWITCH (46" MH UNLESS NOTED OTHERWISE) 1000 WATTS UNLESS OTHERWISE INDICATED.

HP RATED WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

DISCONNECT SWITCH.

MOTOR STARTER.

COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.

ELECTRIC MOTOR.

PHOTOELECTRIC SENSOR.

LIGHTING CONTACTOR.

CEILING MOUNTED OCCUPANCY SENSOR.

WALL MOUNTED OCCUPANCY SENSOR.

CEILING MOUNTED DAYLIGHT SENSOR.

OCCUPANCY SENSOR POWER PACK.

GF

WP

WP/GF

EM

20A

30A

50A

J

P

K

DM

H

OS

OS

DS

OP

PC

F

F

F

F

AM

C/I

PIV

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (46" MH UNLESS NOTED OTHERWISE).

LC

FACP

LOW-VOLTAGE MOMENTARY WALL SWITCH (46" MH UNLESS NOTED OTHERWISE).

L

SECURITY SYMBOLS WITH ELECTRICAL REQUIREMENTS

CC

CCTV SYSTEM WALL MOUNTED CAMERA (REFER TO CAMERA SCHEDULE FOR MOUNTING HEIGHT AND CAMERA SPECIFICATIONS). SUBSCRIPT "X" INDICATES ENTRY IN CAMERA SCHEDULE. 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE

ACCESSIBLE CEILING PER DIV 26. CAMERA AND CABLING PER DIV 28.

PS

LOCAL LOW VOLTAGE POWER SUPPLY FOR EXTERIOR CAMERA. SUBSCRIPT "X" INDICATES ASSOCIATED CAMERA. 120V POWER INTO LOCAL JUNCTION BOX ABOVE CEILING AND CONNECTION TO POWER SUPPLY PER DIV 26. POWER SUPPLY

MOUNTED ABOVE CEILING AND LOW VOLTAGE WIRING TO LOCAL CAMERA PER DIV 28.

IC

WALL MOUNTED INTERCOM DOOR STATION (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO

ABOVE ACCESSIBLE CEILING PER DIV 26. INTERCOM AND CABLING PER DIV 28.

DM

DOOR POSITION SWITCH WITH WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. PROVIDE ONE CONTACT FOR EACH LEAF IN MULTI-DOOR

OPENINGS. REFER TO SECURITY ROUGH-IN DETAILS.

EL

ELECTRONIC DOOR LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY

ROUGH-IN DETAILS.

EM

ELECTRONIC MAG LOCK AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN

DETAILS.

ES

ELECTRONIC STRIKE AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY ROUGH-IN

DETAILS.

LB

RX

REQUEST TO EXIT SWITCH IN DOOR HARDWARE BY OTHERS. LOW VOLTAGE WIRING PER DIV 28. CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. REFER TO SECURITY

ROUGH-IN DETAILS.

HD

HANDICAP DOOR OPERATOR MOTOR ASSEMBLY BY OTHERS. 120V POWER CONNECTION AND CONDUIT FROM DOOR FRAME TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR ACTUATOR BUTTONS PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.

HA

WALL/PEDESTAL MOUNT HANDICAP DOOR ACTUATOR BUTTON, FURNISHED BY OTHERS. BOX AS REQUIRED BY SYSTEM MANUFACTURER WITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. ALL LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR MOTOR PER DIV 28. REFER TO SECURITY

ROUGH-IN DETAILS.

HO

FA

WALL/FLOOR MOUNTED ELECTROMAGNETIC DOOR HOLD OPEN WITH POWER SUPPLY INSTALLED BY OTHERS. 120V POWER AND CONNECTION, BOX AS REQUIRED BY MANUFACTURER AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. LOW VOLTAGE WIRING FROM POWER SUPPLY TO HOLD OPEN AND INTERFACE WITH SMS PER DIV 28. SUBSCRIPT "FA" INDICATES DEVICES POWERED FROM FIRE ALARM SYSTEM AND INTERFACE FROM SMS TO FIRE ALARM SYSTEM REQUIRED FOR DOOR RELEASE PER DIV 28. REFER TO SECURITY ROUGH-IN DETAILS.

CR

WALL MOUNTED PROXIMITY CARD READER (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. CARD READER AND CABLING PER DIV 28. REFER

TO SECURITY ROUGH-IN DETAILS.

CR EL

ELEVATOR CAB MOUNTED CARD READER. READER TO BE INSTALLED IN ELEVATOR CAB AS COORDINATED WITH ELEVATOR CONTRACTOR. WIRING FROM CAB THRU TRAVELING CABLE TO ELEVATOR CONTROLLER IN ELEVATOR MACHINE ROOM AND INTERFACE WITH ELEVATOR CONTROLLER AND SMS PER DIV 28, COORDINATE WITH ELEVATOR

CONTRACTOR. REFER TO SECURITY ROUGH-IN DETAILS.

KC

WALL MOUNTED COMBINATION KEYPAD/CARD READER (46" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. DEVICE AND CABLING PER DIV 28.

K WALL MOUNTED SECURITY KEYPAD ENTRY STATION (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. KEYPAD AND CABLING PER DIV 28.

MD

WALL MOUNTED MOTION DETECTOR (90" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. MOTION DETECTOR, WALL MOUNT HARDWARE, AND CABLING PER DIV 28.

PP W

WALL MOUNTED PANIC/DURESS BUTTON (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO

ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.

X WALL MOUNTED SECURITY SYSTEM WIRING OUTLET MOUNTED BELOW COUNTER TOP. 2-GANG BOX WITH 2-1" CONDUITS TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. GROMMETED FACEPLATE AND SECURITY

SYSTEM CABLING PER DIV 28.

CM

WALL MOUNTED MONITOR OUTLET FOR CCTV SYSTEM (84" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 1" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACK, FACEPLATE AND CABLING PER DIV 28.

MIC

CEILING MOUNTED SECURITY/CCTV SYSTEM AUDIO MICROPHONE. 1-GANG BOX MOUNTED IN CEILING PER DIV 26.

MICROPHONE AND CABLING PER DIV 28.

BR

WALL MOUNTED BIOMETRIC READER (46" MH UNLESS NOTED OTHERWISE). 2-GANG BOX WITH 0.75" CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. READER AND CABLING PER DIV 28. REFER TO

SECURITY ROUGH-IN DETAILS.

X

X

MD

PB W

WALL MOUNTED PUSH BUTTON FOR LOCAL ELECTRONIC DOOR RELEASE (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. BUTTON AND CABLING PER DIV 28.

ELECTRONIC LATCH BOLT MONITORING. HARDWARE AND INSTALLATION BY OTHERS. LOW VOLTAGE WIRING PER DIV 28.

CONDUIT PATHWAYS FROM DOOR FRAME TO COMMON SECURITY JUNCTION BOX ABOVE CEILING PER DIV 26. REFER TO

SECURITY ROUGH-IN DETAILS.

CEILING MOUNTED MOTION DETECTOR. 1-GANG BOX MOUNTED IN CEILING PER DIV 26. DETECTOR AND CABLING PER

DIV 28.

DC

LOCAL IP BASED 2-DOOR ACCESS CONTROL PANEL SERVING LOCAL CARD READER/SECURITY CONTROLLED DOORS.

LOCATE ABOVE ADJACENT ACCESSIBLE CEILING. PROVIDE DATA DROP IN 0.75" CONDUIT TO LOCAL DATA CLOSET.

EXTEND 1" CONDUIT WITH DOOR SECURITY WIRING TO LOCAL SECURITY SYSTEM JUNCTION BOX. REFER TO SECURITY

ROUGH-IN DETAILS.

JB M

SECURITY SYSTEM JUNCTION BOX TO BE LOCATED ABOVE ACCESSIBLE CEILING (MIN 6"X6"X4"). ROUTE LOCAL DOOR SECURITY WIRING CONDUITS/RACEWAYS TO JUNCTION BOX. EXTEND 1" CONDUIT WITH DOOR SECURITY WIRING TO LOCAL 2-DOOR CONTROL PANEL/REMOTE DOOR CONTROL PANEL AS INDICATED ON DRAWINGS. REFER TO SECURITY

ROUGH-IN DETAILS.

PL

SITE POLE FOR MOUNTING SECURITY CAMERAS (REFER TO SPECIFICATIONS FOR SIZE/TYPE). PROVIDE POLE WITH CONCRETE BASE AS INDICATED ON PLANS. EXTEND AND CONNECT TO SITE CONDUIT SYSTEM AS INDICATED ON PLANS.

PROVIDE NEMA 3R JUNCTION BOX AT BASE OF POLE FOR CAMERA EQUIPMENT (120V POWER SUPPLY, FIBER

CONVERTERS, ETC.). REFER TO SECURITY ROUGH-IN DETAILS.

TECHNOLOGY SYMBOLS WITH ELEC. REQUIREMENTS

WALL MOUNTED PHONE OUTLET (46" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLING PER DIV 27. REFER TO FACEPLATE DETAILS.

CONDUIT SLEEVE / FIRE RATED SLEEVE ASSEMBLY THRU WALL (1-2" SLEEVE UNLESS NOTED OTHERWISE) PER DIV 26.

WALL MOUNTED VOICE/DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLING PER DIV 27. REFER TO FACEPLATE DETAILS.

ABBREVIATIONS

AAP - AREA ALARM PANEL - MEDICAL GAS

ACC - ACCESS

ADJ - ADJUSTABLE

AF - ARC FAULT CIRCUIT INTERRUPTER

AFCI - ARC FAULT CIRCUIT INTERRUPTER

AFF - ABOVE FINISHED FLOOR TO BOTTOM OF ITEM

AFG - ABOVE FINISHED GRADE TO BOTTOM OF ITEM

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOE - BOTTOM OF EQUIPMENT

BOT - BOTTOM

BTWN - BETWEEN

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CKT - CIRCUIT

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

CORR - CORRIDOR

CTR - CENTER

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DIV - DIVISION

DN - DOWN

DWG - DRAWING

EA - EACH

EC - ELECTRICAL CONTRACTOR (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATION OR ELEVATOR

EM - EMERGENCY

EQ - EQUAL

EQS - EQUIPMENT SUPPLIER

EQUIP - EQUIPMENT

E/R - EXISTING TO BE RELOCATED

EX - EXISTING TO REMAIN

EXP - EXPANSION

EXT - EXTERIOR

FCE - FIRE CONTROL EQUIPMENT

FF - FINISHED FLOOR ELEVATION

FLR - FLOOR

FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)

FT - FEET

FTG - FOOTING

GC - GENERAL CONTRACTOR

GF - GROUND FAULT CIRCUIT INTERRUPTER

GFCI - GROUND FAULT CIRCUIT INTERRUPTER OR

GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GFFT - GROUND FAULT FEED THRU

HC - HVAC CONTRACTOR (DIVISION 23)

HP - HORSE POWER OR HIGH POINT

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

IN - INCHES

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTH

LBS - POUNDS

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE OR MOUNTING HEIGHT TO CENTER LINE OF

ITEM

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NIC - NOT IN CONTRACT

NOM - NOMINAL

NTS - NOT TO SCALE

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING CONTRACTOR (DIVISION 22)

PLBG - PLUMBING

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

S - SURFACE MOUNTED

SC - SECURITY CONTRACTOR

SCH - SCHEDULE

SHT - SHEET

SMS - SECURITY MANAGEMENT SYSTEM

SPEC - SPECIFICATIONS

SQ - SQUARE

SS - STAINLESS STEEL

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TC - TECHNOLOGY CONTRACTOR

TEMP - TEMPERATURE

TOE - TOP OF EQUIPMENT

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VFD - VARIABLE FREQUENCY DRIVE

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WP - WEATHERPROOF

ZVC - ZONE VALVE CABINET

E2

B

E2

LUMINAIRE SYMBOLS

LIGHTING FIXTURE. CAPITAL LETTER DENOTES FIXTURE TYPE, LOWER CASE LETTER DENOTES

SWITCHING ARRANGEMENT.

LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.

EXIT LIGHTING FIXTURE, ARROWS AS INDICATED, EGRESS LIGHT PACK AS INDICATED.

A a

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R WITH 2 INTEGRAL USB CHARGERS (18" MH UNLESS NOTED OTHERWISE).

NOTE:

ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO

MODIFICATIONS ON OTHER DRAWINGS.

ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT

NECESSARILY BE USED ON THIS PROJECT.

FIRE ALARM SYMBOLS

FIRE ALARM BELL & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM SPEAKER & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM HORN & SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM SIGNAL LIGHT (88" AFF). # WHEN SHOWN INDICATES CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.

FIRE ALARM CONTROL PANEL.

ADDRESSABLE MODULE. SUBSCRIPT "I" INDICATES INPUT. SUBSCRIPT "C" INDICATES CONTROL.

POST INDICATOR VALVE.

REMOTE ANNUNCIATOR PANEL.

NOTIFICATION APPLIANCE CIRCUIT EXTENDER PANEL.

AIR SAMPLING SMOKE DETECTOR BASE UNIT.

DETAIL: B = DETAIL DESIGNATION

E2 = SHEET WHERE DETAIL IS LOCATED

SECTION: 1 = SECTION DESIGNATION

E2 = SHEET WHERE SECTION IS LOCATED

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

GENERAL FLOOR PLAN NOTES

WIRE & CONDUIT IN WALL OR ABOVE CEILING.

WIRE & CONDUIT IN OR BELOW SLAB OR GRADE.

EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; "X" DENOTES PANEL NAME; NUMBER(S)

DENOTES CIRCUIT(S).

LADDER TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

CONDUIT FOR DATA CIRCUITRY.DAT

WIRE & CONDUIT FOR FIRE ALARM CIRCUITRY.FA

WIRE & CONDUIT FOR NURSE CALL CIRCUITRY.NC

EXISTING WIRE & CONDUIT TO REMAIN.EX

CONDUIT TO BE REMOVED.

WIRE & CONDUIT FOR NIGHT LIGHT CIRCUITRY.NL

CONDUIT FOR PHONE CIRCUITRY.PHO

WIRE & CONDUIT FOR SECURITY SYSTEM CIRCUITRY.SEC

WIRE RUN IN SURFACE WIREWAY.W

CABLE MANAGEMENT SYSTEM PATHWAY.CM

X - 1,2

WIRE & CONDUIT FOR EMERGENCY CIRCUITRY.EM

WIRE & CONDUIT FOR SOUND SYSTEM CIRCUITRY.S

WIRE & CONDUIT FOR INTERCOM SYSTEM CIRCUITRY.I

WIRE & CONDUIT FOR TELEVISION SYSTEM CIRCUITRY.TV

CABLE TRAY, 12" x 4" DEEP UNLESS NOTED OTHERWISE.

4"

4"

4"

T2 1 ELEVATION: 1 = ELEVATION DESIGNATION

T2 = SHEET WHERE ELEVATION IS LOCATED

RAP

NAC

ASSD

20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" MH UNLESS NOTED OTHERWISE). WHEN SHOWN, RECEPTACLE TO HAVE

"CONTROLLED" MARKINGS.

EDC

X ELECTRONIC DOOR CONTROL. SUBSCRIPT "X" INDICATES SPECIFIC DOOR. REFER TO ELECTRONIC DOOR CONTROL

SCHEDULE FOR REQUIREMENTS.

LIGHTING CONTROL DETAIL NOTE. APPLIES TO THE LIGHTING CONTROL SEQUENCE OF OPERATIONS

SCHEDULE FOR ROOM CONTROL.

3 DEVICE QUANTITY - POWER NOTE. REFER TO DEVICE QUANTITIES - POWER SCHEDULE.

WALL MOUNTED DATA OUTLET (18" MH UNLESS NOTED OTHERWISE). BOX WITH CONDUIT(S) TO ABOVE ACCESSIBLE CEILING PER DIV 26. JACKS, FACEPLATE AND CABLING PER DIV 27. SUBSCRIPT "X" DESIGNATES QUANTITY OF DATA

CABLES. REFER TO FACEPLATE DETAILS.

X

WA

WALL/PEDESTAL MOUNT WAVE ACTIVATED DOOR DEVICE, FURNISHED BY OTHERS. BOX AS REQUIRED BY SYSTEM MANUFACTURER WITH INSTALLATION AND CONDUIT TO COMMON SMS JUNCTION BOX ABOVE ACCESSIBLE CEILING PER DIV 26. ALL LOW VOLTAGE WIRING AND INTERFACE WITH SMS AND DOOR MOTOR PER DIV 28. REFER TO SECURITY

ROUGH-IN DETAILS.

CEILING MOUNTED VACANCY SENSOR.

WALL MOUNTED VACANCY SENSOR.

VS

VS

WALL MOUNTED LOCAL LOCK OVERRIDE KEYSWITCH WITH STAINLESS STEEL FACEPLATE (46" MH UNLESS NOTED OTHERWISE). 1-GANG BOX WITH 0.75" CONDUIT WITH WIRING. DEVICE AND CABLING PER DIV 28.

KS

WALL MOUNTED WATCH TOUR BUTTON WITH STAINLESS STEEL FACEPLATE (46" MH UNLESS NOTED OTHERWISE). 1-GANG

BOX WITH 0.75" CONDUIT WITH WIRING. DEVICE AND CABLING PER DIV 28.

WT

P: 216-862-5846 www.heapy.com

ISSUES AND REVISIONS

DateNo.

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

RLB NO.:

CHECKED BY:

DRAWN BY:

Description

C en te r

S t, S ui te

C le ve la nd

O hi o

P ho ne

(2

1-

F ax

6)

-8 w w w .r lb a.

co m

N O

T F

O R

C

N S

T R

U C

T

IO

N

© RICHARD L. BOWEN + ASSOCIATES, INC.

PROJECT NO.

8/ 7/

:0

8:

P M

C :\B

IM

\M od el

\2

6-

8.

-M

E P

-C en tr al

_t jc os sm an .r vt

T O

P A

R A

T R

A N

S

IT

G A

R A

G E

13828.10

C en tr al

A ve

T ol ed o, O

H

E

LE

C T

R

IC

A L

A B

B R

E V

IA

T

IO

N

S

S Y

M B

O

LS

, L E

G E

N D

S , N

O T

E S

TJC

JJT

E0012026-07008.01

1 08/07/20

CONSTRUCTION

DOCUMENTS

A. PROVIDE A GROUND WIRE WITH ALL FEEDERS AND BRANCH CIRCUITS.

B. CONDUITS SHALL BE SIZED FOR .75” MINIMUM.

C. PROVIDE UNISTRUT SUPPORTS FROM THE FLOOR FOR DISCONNECT SWITCHES AND MOTOR STARTERS AT EQUIPMENT IN MECHANICAL

AREAS, WHERE REQUIRED.

D. ALL JUNCTION BOXES, ETC. ARE TO BE FLUSH MOUNTED UNLESS OTHERWISE NOTED.

E. FIRESTOP ALL PENETRATIONS THRU FIRE RATED WALLS.

F. SIZING AND QUANTITY OF ALL SYSTEM WIRES AND CONDUITS SHALL BE PER MANUFACTURER’S OR SUPPLIER’S RECOMMENDATIONS.

G. IF IN DOUBT ABOUT ANY ELECTRICAL OR SYSTEM ITEMS, ASK OWNER/ARCHITECT PRIOR TO ROUGH-IN.

H. ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL SWITCHES, RECEPTACLES, ETC. WITH RESPECTIVE CONTRACTORS PRIOR TO ROUGH-INS. ALL MOUNTING HEIGHTS OF DEVICES WHICH ARE MOUNTED ADJACENT TO EACH OTHER SHALL BE

AT THE SAME DISTANCE MEASURED ABOVE THE FINISHED FLOOR.

I. ALL RECEPTACLE COVER PLATES SHALL BE LABELED WITH THE PANEL NAME AND CIRCUIT NUMBER. UTILIZE STANDARD TAPE MARKING

SYSTEM (BROTHER P. TOUCH).

J. PROVIDE CONCRETE PADS FOR ALL ELECTRIC EQUIPMENT ASSOCIATED WITH DIV 26 WORK. NOT ALL CONCRETE PADS ARE INDICATED OR

SPECIFIED ON THE DRAWINGS.

K. THIS CONTRACTOR SHALL LOCATE ALL EXISTING UNDERGROUND UTILITIES, MISCELLANEOUS CONDUITS AND PIPING PRIOR TO DIGGING, ANY DAMAGE TO ABOVE MENTIONED ITEMS SHALL BE HIS RESPONSIBILITY TO REPAIR.

L. COORDINATE EXACT ROUTE OF ALL UNDERGROUND CONDUITS AT THE SITE PRIOR TO EXCAVATION. UTILIZE LONG SWEEPING BENDS ON

ALL UNDERGROUND CONDUITS.

M. ELECTRICAL CONTRACTOR SHALL PERMANENTLY MARK PANEL AND CIRCUIT DESIGNATIONS ON ALL ELECTRICAL JUNCTION BOXES.

N. ALL DUCTS EXTENDING FROM UNDER PAVEMENT SHALL BE CONCRETE ENCASED FOR A MINIMUM OF FIVE (5) FEET BEYOND THE EDGE OF

THE PAVEMENT.

O. ALL EMPTY CONDUITS SHALL BE INSTALLED WITH PULL WIRE.

P. NEW WIRE AND CONDUITS SHALL NOT BE RUN EXPOSED UNLESS APPROVED BY THE ARCHITECT, ENGINEER OR OWNER.

Q. BRANCH CIRCUIT WIRE SIZING CHART TO BE UTILIZED AS GUIDELINE FOR VOLTAGE DROP COMPENSATION, INCREASE CONDUIT SIZING

PER WIRE SIZE.

A) 20A – 120V CIRCUITS:

#12 WIRE – 60FT. LENGTH MAX.

#10WIRE – 94FT. LENGTH MAX.

#8 WIRE – 137FT. LENGTH MAX

#6 WIRE – 218FT. LENGTH MAX.

B) 20A – 277V CIRCUITS:

#12 WIRE – 138FT. LENGTH MAX.

#10WIRE – 219FT. LENGTH MAX.

#8 WIRE – 318FT. LENGTH MAX.

#6 WIRE – 504FT. LENGTH MAX.

R. THE ELECTRICAL CONTRACTOR SHALL RE-SUPPORT ANY EXISTING WIRING OR CONDUITS REQUIRING SUPPORT.

S. EACH BIDDER SHALL VISIT THE SITE DURING THE BID PERIOD TO REVIEW EXISTING AND NEW FEEDER ROUTING.

T. REMOVAL PLANS MAY NOT NECESSARILY SHOW ALL ITEMS REQUIRED TO BE REMOVED. EACH BIDDER SHALL VISIT THE SITE PRIOR TO BID TO DETERMINE THE FULL EXTENT OF REMOVALS REQUIRED. MAINTAIN CIRCUIT CONTINUITY OF EXISTING CIRCUITS CUT OFF BY

REMOVALS, VERIFY CIRCUITS PRIOR TO REMOVAL.

U. THIS CONTRACTOR SHALL VERIFY AVAILABILITY OF SPARE BREAKERS AND SPACE FOR NEW BREAKERS WITHIN EXISTING PANELS.

INCLUDE IN BID ANY MODIFICATIONS TO EXISTING PANELS REQUIRED FOR THE ADDITION OF THIS NEW CIRCUITRY WITHIN THE

RENOVATED AREAS.

V. RELOCATE AND RECONNECT ACTIVE PORTIONS OF THE ELECTRICAL SYSTEM OUTSIDE OF THE SCOPE OF DEMOLITION, AS REQUIRED, TO MAINTAIN A COMPLETE AND OPERATIONAL SYSTEM THAT IS FUNCTIONALLY EQUIVALENT TO THE PRE-EXISTING SYSTEM PRIOR TO

DEMOLITION.

W. ALL NEW AND EXISTING PANELBOARDS AFFECTED BY THIS PROJECT SHALL BE PROVIDED WITH A NEW TYPE WRITTEN DIRECTORY.

X. LABEL ALL CIRCUIT BREAKERS MADE SPARE DUE TO REMOVALS AS “SPARE” TO SERVE FUTURE LOADS.

Y. ALL ELECTRICAL INTERRUPTIONS OF SERVICES SHALL BE MADE WHEN THE LOAD IS AT A MINIMUM AND SHALL BE SCHEDULED FOR OTHER THAN NORMAL DAYTIME WORKING HOURS. THE ELECTRICAL CONTRACTOR SHALL INCLUDE NECESSARY COST FOR OVERTIME LABOR

WITHIN ALL BIDS.

Z. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OF ASSOCIATED ELECTRICAL WORK UNDER THIS CONTRACT. ALL PATCHING SHALL MATCH EXISTING FINISHES AND BE DONE BY CRAFTSMAN SKILLED IN THE WORK. ALL CUTTING AND

PATCHING SHALL BE SUBJECT TO APPROVAL BY THE ARCHITECT, ENGINEER OR OWNER.

AA. ALL EXISTING CONDUIT, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED SHALL BE REMOVED. THE MAJORITY OF ELECTRICAL WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL ITEMS ASSOCIATED WITH THE DEMOLITION WORK.

GENERAL NOTES

PROJECT NARRATIVE:

POWER WILL BE PROVIDED FOR NEW GATES ALONG WITH CONTROL SYSTEMS CONDUITS.

SHEET LIST

SHEET NUMBER SHEET NAME

E001 ELECTRICAL ABBREVIATIONS, SYMBOLS, LEGENDS, NOTES

ES100 ELECTRICAL SITE PLAN

0 K

NA

PP

ST

RE

E

TO

LE

DO

, O H 4

8-10-2026

AS

P H W

ALK

A S P H W A L K

RELOCATE EX STM

J

J

J

J

ES100

APPROXIMATE LOCATION OF MECHANICAL ROOM

APPROXIMATE LOCATION

OF PANEL RP-B IN

MAINTENANCE BAY

APPROXIMATE LOCATION

OF TELECOM ROOM ON

2ND FLOOR

GATE OPERATOR & PAD

PEDESTRIAN GATE

PROPOSED PIVOT GATES

GATE OPERATOR & PAD

LOOP DETECTOR

IN PAVEMENT

LOOP DETECTOR

IN PAVEMENT

CARD READER

1. 3000 LB. CONCRETE.

2. SCHEDULE 80 PVC DUCT. SIZE AS NOTED ON PLANS.

3. MIN. 3" SPACING BETWEEN CONDUITS AND MIN. 3"

ENCASEMENT (TYPICAL). PROVIDE CONDUIT SPACERS

6'-0" O.C.

4. RED DYE, RED DUST OR YELLOW MARKER TAPE ON

COMPACTED FILL.

DETAIL NOTES

1' -6

TAMPED

BACKFILL

FINISH GRADE

2' -3

C

O V

E R

1'-7"

1 4" CONCRETE WALLS-FOUR SIDES.

2 3/8" DIA. REINFORCED STEEL 10" CC BOTH WAYS.

3 1/4" CHECKERED STEEL PLATE.

4 2" L WELDED TO PLATE TWO SIDES ONLY - 1/4" CLEARANCE FIT.

5 UNDERGROUND DUCT OR DIRECT BURIAL CABLE AS INDICATED.

6 CONDUCTORS-LOOP/PULL OR SPLICE.

DETAIL NOTES

.2C DIA.

7C

DIA.

11C

DIA

2' -4

2' -6

C

O V

E R

.2'-2"

SQUARE

METAL SLEEVE WITH ANNULAR

JOINT, PACKED WITH LOOSE

GLASS FIBER AND CAULKED ON

BOTH SIDES

METAL FRAME, PACKED

WITH LOOSE GLASS

FIBER AND CAULKED ON

BOTH SIDES

STUD OR METAL PANEL WALL

MASONRY OR CONCRETE WALL

A ALL PENETRATIONS FROM MECHANICAL SPACE SHALL BE SEALED IN THIS MANNER.

B ALL PENETRATIONS THRU WALLS SHALL BE SEALED IN THIS MANNER.

C WHEN WALL IS FIRE RATED; DETAIL SHALL BE SIMILAR BUT FOLLOW MATERIAL INSTALLATION REQUIREMENTS PER

MANUFACTURER AND FIRE PROOFING SPECIFICATIONS.

GENERAL DETAIL NOTES

SCALE: NONE

TYPICAL CONDUIT AND WALL PENETRATIONS

SCALE: NONE

CONCRETE ENCASED UNDERGROUND DUCT

SCALE: NONE

SMALL GROUND PULLBOX

P: 216-862-5846 www.heapy.com

ISSUES AND REVISIONS

DateNo.

NOTICE

THIS ARCHITECTURAL AND

ENGINEERING DRAWING IS GIVEN

IN CONFIDENCE. NO USE OR

DISSEMINATION MAY BE MADE

WITHOUT PRIOR WRITTEN

CONSENT OF THE ARCHITECT.

ALL RIGHTS ARE HEREBY

SPECIFICALLY RESERVED.

DRAWING NO.

RLB NO.:

CHECKED BY:

DRAWN BY:

Description

C en te r

S t, S ui te

C le ve la nd

O hi o

P ho ne

(2

1-

F ax

6)

-8 w w w .r lb a.

co m

N O

T F

N S

T R

U C

T

IO

N

© RICHARD L. BOWEN + ASSOCIATES, INC.

PROJECT NO.

8/

/2

4:

:1

P

M C

:\B

IM

\M od el \2

6-

8.

-M E

P -C en tr al _D

S M itc he ll9 F

Y 5X

.r vt

T O

P A

R A

T R

A N

S

IT

G A

R A

G E

13828.10

C en tr al

A ve

T ol ed o, O

H

E

LE

C T

R

IC

A L

S

IT

E P

LA

N

TJC

JJT

ES1002026-07008.01

SCALE: 1" = 30'-0"

ELECTRICAL SITE

SCALE: 1/8" = 1'-0"

ELECTRICAL SITE

1 08/07/20

CONSTRUCTION

DOCUMENTS

N

0 9030 6015

N

PLAN NOTES

1. REFER TO 100 OPERATOR & ACCESSORY SITE LAYOUTS (LH & RH) ON SHEET C4.0 FORE MORE INFORMATION.

2. PROVIDE JUNCTION BOX AND DISCONNECT SWITCH FOR GATE POWER. EC SHALL COORDINATE DEVICE LOCATION WITH ARCHITECT AND EQUIPMENT MANUFACTURER PRIOR TO ROUGH-IN AND INSTALLATION.

3. PROVIDE TWO (2) 1" CONDUITS AND…