212400 Clean Agent Fire Suppression.pdf
PDF 166 KB Posted
- Attached to
- Tape Library Fire Suppression Federal contract opportunity
- Solicitation number
- SCD-334545-GD
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SCD-334545-GD Amendment 1.pdf | ||
| SF1413-13e (1).pdf | ||
| Fermilab Subcontractor Injury Illness Data Questionnaire.pdf | ||
| 010010 General Requirements.pdf | ||
| 014100 Quality Requirements.pdf | ||
| FRA General Terms and Conditions for Construction (06.2022).pdf | ||
| SOW.pdf | ||
| 013100 ESH Requirements.pdf | ||
| General Decision Number IL20220008 Mod 13.pdf | ||
| 2022 Construction Insurance Requirements.pdf | ||
| SARC.pdf | ||
| Exhibit II - Payment Bond FL-42.pdf | ||
| SCD-334545-GD.pdf | ||
| 013300 Submittals.pdf | ||
| PUR-466_Proposal Certifications (1).pdf | ||
| Exhibit II - Bid Bond FL-41.pdf | ||
| Exhibit II Proposal Form.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FCC Tape Library Fire Suppression 10-5-97
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-1
SECTION 21 24 00
SPEICAL HAZARD CLEAN AGENT FIRE SUPPRESSION SYSTEM
PART 1 GENERAL
1.01 SCOPE OF WORK:
A. The Subcontractor shall be responsible for all equipment, materials, labor, logistical and technical resources, and coordination necessary for the complete execution of the work.
B. The work in this section includes, but is not necessarily limited to:
1. Installation of a new Novec 1230 clean agent system serving a tape library cabinet 30’ long x 44” wide x 82” high, with a total of 12 frames (cabinets).
2. Installation of a new low voltage, addressable-type releasing control panel, including: smoke detection, manual releasing stations, abort buttons, shut-down relays, and notification.
3. Performance of acceptance testing of completed system, including documentation.
1.02 WORK BY OTHERS:
A. The following work associated with the work of this section is Not in Contract
(N.I.C.) and will be provided by Fermilab. Termination of all connections between the new fire alarm system and FIRUS.
1.03 RELATED WORK:
A. The following sections prescribe items of related work. Coordinate work prescribed by this section with work prescribed by these sections:
1. Not applicable
1.04 COORDINATION WITH OTHER TRADES
A. Coordinate all work under this section with all related work as applicable and as indicated elsewhere in the plans and specifications.
B. Failure to properly coordinate with related trades and related work shall be corrected as part of the work of this section at no extra cost to Fermilab.
1.05 PRODUCT LISTINGS & APPROVALS
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-2
A. All system components for which UL listing categories exist shall be listed by
Underwriter's Laboratories Inc. (UL) and/or approved by Factory Mutual (FM) for the intended application.
1. All components shall be listed in the current edition of the UL Fire
Protection Equipment Directory or the FM Approval Guide or both.
Components shall be delivered to the project site with factory applied, UL and/or FM stickers. System components which do not meet these requirements are not acceptable.
2. Components for which UL listing or FM approval are "pending" are not acceptable.
B. The Subcontractor shall be trained by the manufacturer to install, test and maintain clean agent fire suppression systems.
B. All system components are subject to the approval of Fermilab with regard to their fitness for the intended application.
1.06 ACCEPTABLE EQUIPMENT MANUFACTURERS:
A. Equipment and components which comply with the requirements of these specifications as manufactured by the following are acceptable:
1 3M
2 Fenwal
1.07 APPLICABLE STANDARDS AND CRITERIA
A. The fire alarm system shall be installed in accordance with the following standards:
1. NFPA 70, National Electrical Code, 2020
2. NFPA 72, National Fire Alarm & Signaling Code, 2022
3. NFPA 75, Standard for the Protection of Electronic Computer/Data
Processing Equipment, 2020
4. NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, B. In the event of differences between the requirements of the specified standards and these specifications, the more stringent requirement(s) shall apply.
1.08 AS-BUILT DRAWINGS
A. In addition to the requirements of Section 10.0 "As-Built Drawings" in Exhibit
A, the Subcontractor shall provide one set of the AutoCad files for the shop drawings, updated to reflect all red-line markups on the construction "asbuilt" drawings set. These updated drawing files shall also include:
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-3
1. All junction boxes and terminal cabinets.
2. Locations of all electrical enclosures of any kind that contain one or more splices shall be noted "splice."
3. Addresses for all addressable components.
B. This submittal shall also include a complete printout of the system program.
This printout shall be produced and dated upon completion of all required
Subcontractor testing/verification.
1.09 GENERAL DESCRIPTION OF THE SYSTEM
A. The new fire alarm system shall be a 24 VDC, addressable system consisting of a fire alarm control panel, dedicated signaling line (addressable) and notification appliance circuits, and associated initiating devices and notification appliances, as indicated on the drawings
C. All system wiring shall be installed in conduit.
D. The new fire alarm system shall provide a unique "address" for each addressable device in the system, including an associated, user programmable message identifying the type of device and its location.
E. The new fire alarm system shall be connected to Fermilab's existing FIRUS as specified herein, except for FIRE alarm to be monitored by existing building’s fire alarm system. Include all necessary programing and addressable relays to interface to existing fire alarm system.
1.10 CIRCUIT PERFORMANCE AND SUPERVISION
A. All wiring required for proper system operation, except as specifically allowed herein, shall be electrically supervised for opens, shorts between pairs
(notification appliance circuits only), and shorts to ground. Wiring faults on supervised circuits shall initiate trouble conditions.
B. All multiplexed and addressable data circuits shall be "Class B" two-wire circuits, conforming to NFPA 72 definition of Pathway Survivability level 1 circuits.
C. All evacuation signaling circuits shall be "Class B" two-wire circuits, each for visual and horn circuits, conforming to NFPA 72’s definition of Pathway
Survivability level 1 circuits.
D. Any single open or single ground condition on any non-addressable initiating device circuit or non-addressable auxiliary function circuit shall cause a trouble signal.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-4
E. All AC power connections and standby battery connections shall be electrically supervised such that disconnection of any fire alarm system (primary or backup) power supply shall cause a trouble signal.
1.11 COMPONENT SUPERVISION
A. All control components shall be placement supervised such that removal of any control panel module shall cause a trouble signal.
B. All power supplies/battery chargers shall be supervised for loss of normal AC operating power. Loss of AC power to any power supply/battery charger shall cause a trouble signal.
C. All power supplies shall continuously monitor the presence of the batteries, battery voltage, and charging status, causing a trouble signal in response to a low battery, missing battery or charger failure condition.
D. The availability of operating power to the fire alarm system, including all required components thereof, shall be supervised to the point of connection to the dependent equipment. Loss of operating power to any required system component(s) shall cause a trouble signal. Trouble signals caused by loss of operating power shall be distinct from trouble signals caused by wiring faults in signaling line, initiating device, or notification appliance circuits.
E. All manual fire alarm stations, detectors, evacuation signaling devices and auxiliary function relays or other devices shall be supervised such that removal of any manual fire alarm station, detector, evacuation signaling device, auxiliary function relay or other device shall cause a trouble signal. Removal and replacement of addressable smoke detectors for cleaning shall not cause a fire alarm signal. Systems which are incapable of providing immunity from false alarms caused by routine cleaning of detectors are not acceptable.
Systems which require detectors or alarm functions to be disabled in software to avoid false alarms during cleaning are not acceptable.
F. Proper operation of addressable devices shall be automatically tested by the system via a continuous polling interrogation/response operation. Failure of one or more addressable devices shall cause a trouble signal.
1.12 POWER SUPPLIES
A. All fire alarm system AC power connections shall be hardwired via dedicated circuits serving no other load(s). Each AC circuit/switch shall be labeled and locked, see detail on drawings. All associated conductors and connections shall be installed entirely within approved electrical enclosures, conduits or raceway. Circuit breakers shall be clearly labeled "Fire Alarm System Power" and shall be locked (padlocks provided by Fermilab).
B. All portions of the fire alarm system, including LCD displays, shall be designed and equipped to be capable of operating on standby
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-5
(rechargeable) battery power.
C. Speaker and Strobe light circuits shall be powered from dedicated power supplies serving no other loads. Design load for strobe light power supplies shall not exceed 66% of their (continuous) rated capacity. Battery size shall be calculated by determining required amp-hour capacity (load x time) and multiplying by 0.66.
D. Design load connected to all power supplies, except dedicated power supplies for speaker and strobe light circuits, and for all standby batteries and uninterruptible power supplies shall not exceed 80% of their (continuous) rated capacity. Battery size shall be calculated by determining required amp-hour capacity (load x time) and multiplying by 0.80.
E. Standby battery capacity shall be sufficient to maintain the entire system in a non-alarm condition for 24 hours, followed by 5 minutes in full load alarm condition (all fire alarm initiating devices in alarm, and all evacuation signals, annunciators and auxiliary functions activated simultaneously), on battery power only.
F. All power supplies, shall be capable of recharging their associated batteries, from a fully discharged condition to a capacity sufficient to allow the system to perform consistent with the requirements of this section, in 24 hours maximum.
Standby battery capacity may be upsized to meet this requirement.
G. All batteries shall be maintenance-free type. Wet-cell lead-acid standby batteries are prohibited.
H. Battery chargers shall be compatible with the batteries provided.
1.13 EMI/RF PROTECTION
A. All fire alarm control equipment, devices and wiring shall be protected as necessary to prevent electro-magnetic/radio frequency interference or induced voltages caused by AC power circuits, electrical transformers, motors or switchgear, electronic equipment, fluorescent lighting fixtures, hand held portable radios, cellular phones or other devices.
B. The system shall be designed and installed so as operate properly in the electromagnetic environment in which it is installed, and to be unaffected (with all control cabinet face plates installed) by the operation of hand held, portable radios of up to 5 watts, or portable cellular telephones of up to 1 watt, within
12 inches of any system component(s).
C. All circuits shall be segregated, shielded, and equipped with EMI filters as necessary to eliminate induced voltages and audio and/or electrical crosstalk between circuits. Where necessary, separate, isolated power supplies, CLEAN AGENT FIRE SUPPRESSION November 2021 212400-6 shielded equipment cabinets, or other appropriate means of eliminating induced voltages and interference/crosstalk shall be provided.
A. The AC grounding and bonding system shall consist of bare copper cables for the grounding of all associated AC electrical equipment for the fire alarm installation, in accordance with NEC Article 250. The fire alarm (DC) grounding system shall be in accordance with NEC Article 760 and the manufacturer’s recommendation.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Subject to compliance with requirements, provide a 3M Novec 1230 system, or an approved equal by one of the following manufacturers..
1. 3M
2. Fenwal Protection Systems
B. Description: Clean agent fire extinguishing system shall be an engineered system for total flooding of the hazard area. All manual controls shall be behind locked cabinet doors or key operated, or both. All locks shall be keyed
"T-45" with key and lock assembly.
C. Design: Design clean-agent fire-extinguishing system and obtain approval from Authorities Having Jurisdiction. Design system for Class A, B, and C fires as appropriate for areas being protected, and include safety factor. Use clean agent indicated and in concentration suitable for normally occupied areas.
C. Performance requirements:
1. Minimum design concentration: As calculated, by volume in all areas and/or protected spaces at the minimum anticipated temperature within the protected area.
2. The system design shall not exceed a maximum exposure limit concentration level per NFPA 2001, unless provisions for room evacuation before agent release are provided. All personnel should be able to leave the protected space prior to the discharge or at least within 5 minutes of the commencement of discharge.
E. Verified Detection: Devices located in single zone. Sound alarm on activating single-detection device, and discharge extinguishing agent on actuating second-detection device.
2,02 RELEASING CONTROL PANEL
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-7
A. Description: Existing control panel is Fenwal 6000. All monitoring and releasing modules shall be UL listed for use with existing panel.
2.03 AIR SAMPLING SMOKE DETECTION
A. Air sampling smoke detection shall be manufactured by Xtrailis
B. Air sampling pipe shall be CPVC. Pipe joints shall airtight and permanently fixed by using CPVC cement, per the pipe manufacturer requirements.
C. Sampling ports in piping shall be pre-drilled in accordance with the manufacture’s drawings. Sampling ports shall be sized by vendor to equalize flow through ports. Sampling ports shall be identified by placement of red label or sticker with a hole punched in center over ports.
D. Air sampling piping calculations will be provided to Fermilab.
2.04 SYSTEM OPERATING SEQUENCE
A. Verified Detection:
1. Actuating First Detector (Pre-Alarm):
a. Visual and audible indication on local control panel.
b. Energized audible and visual alarms for the protected hazard area
c. Transfer relays to shut-down external equipment, dampers, HVAC, etc.
d. Signal the building main fire alarm system (alarm only).
Supervisory and Trouble signals to FIRUS.
B. Actuating Second (Pre-discharge)
1. Visual and audible indication on local control panel.
2. Energize audible and visual alarms inside the protected hazard area
(unique pattern).
3. Transfer relay to shut down power to protected area man-door security lock, that then allows man-door to be opened from Corridor side
(bypassing security system).
4. Transfer relays to shut down recirculating air-conditioning units serving protected area.
5. Start time delay for extinguishing-agent discharge for 30 seconds.
6. Initiate system abort sequence, if abort switch is pressed and held in
"abort" position. Release of hand pressure on the abort switch will cause agent discharge if the discharge time delay has expired.
C. Extinguishing-agent discharge (Release), pre-discharge time delay expires or manual release switch is operated.
1. Visual and audible indication on local control panel.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-8
2. Energize audible and visual alarms inside and outside the protected area
(unique pattern).
3. Transfer relay to send "Extinguishing Agent Release" to main fire alarm system panel.
4. Release clean agent suppression system agent.
2.05 SWTICHES
2.06 ALARM DEVICES
2.07 PIPING MATERIALS
A. Piping, Valves, and Discharge Nozzles: Comply with types and standards listed in NFPA 2001.
B. Plain end couplings are not allowed on any piping systems.
C. No welding allowed.
2.08 VALVES
A. General Valve Requirements:
1. UL Listed and FM Global approved for use in fire protection systems.
2. Compatible with type of clean agent used.
3. Automatic excessive pressure relief provision.
4. Low pressure gauge.
B. Container Valves: With fast acting rupture disc with solenoid actuator, capable of immediate and total agent discharge and suitable for intended flow capacity.
C. Valves in Sections of Closed Piping and Manifolds: Fabricate to prevent entrapment of liquid, or install valve and separate pressure relief device.
D. Valves in Manifolds: Check valve; installed to prevent loss of extinguishing agent when container is removed from manifold.
2.09 EXTINGUISHING AGENT CONTAINERS
A. Description: High strength alloy steel tanks complying with ASME Boiler and
Pressure Vessel Code: Section VIII, for unfired pressure vessels. Include minimum working-pressure rating that matches system charging pressure, valve, pressure switch, and pressure gage.
1. Finish: RED, enamel or epoxy paint.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-9
2. Manifold: Fabricate with valves, pressure switches, and co ̀ nnections for multiple storage containers, as indicated.
3. Storage-Tank Brackets: Factory- or field-fabricated retaining brackets consisting of steel straps and channels; suitable for container support, maintenance, and tank refilling or replacement.
B. Location: Located within hazard area, or as near as possible to reduce the required amount of pipe and fittings.
2.10 FIRE EXTINGUISHING CLEAN AGENT
A, Novec 1230 Clean Agent: Fluorinated Ketone.
1. Basis-of-Design Product: Subject to compliance with requirements, provide
Novec 1230 product by one of the following:
a. 3M
2.11 DISCHARGE NOZZLES
A. Equipment manufacturer's standard one-piece brass or aluminum alloy of type, size, discharge pattern, and capacity required for application
2.12 INFORMATIONAL SIGNAGE
2.13 SPECIAL CONNECTIONS
A. The A/V alarm signal shall be synchronized. The audible alarm signal shall
2.14 END-OF-LINE POWER SUPERVISORY RELAYS
A. End-of-line power supervisory relays shall be installed at the end of the monitored circuit and shall be arranged such that their operation upon power loss does not impair the receipt of signals from any device not already impaired by the power loss, and does not cause the loss of power to any additional device(s).
B. End-of-line power supervisory relays shall be provided for each 24VDC power circuit used for powering peripheral devices, 4-wire detectors, addressable control modules, etc.
PART 3 INSTALLATION
3.01 GENERAL REQUIREMENTS FOR INSTALLATION OF CONDUITS, RACEWAYS,
ENCLOSURES, J-BOXES, PULLBOXES, AND BACK BOXES
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-10
A. The requirements of this section apply to all fire alarm conduits, raceways, electrical enclosures, junction boxes, pull-boxes and device back boxes.
B. System conduit systems shall be dedicated to the fire alarm system and shall contain no unrelated conductors.
C. All conduit systems shall be routed and installed to minimize the potential for physical damage, mechanical or by fire, and so as not to interfere with existing building systems, facilities or equipment, and to facilitate service and minimize maintenance.
D. All conduits, except flexible conduit whips to devices, shall be solidly attached to building structural members, ceiling slabs or permanent walls. Conduits shall not be attached to other conduit, duct work, cable trays, other ceiling equipment, drop ceiling hangers/grids or partition walls, except where necessary to connect to initiating, evacuation signaling or auxiliary function devices.
E. Acceptable fasteners include toggle bolts on hollow masonry walls, concrete inserts or expansion shells on concrete or brick, and machine screws, welded threaded studs, or spring tension clamps on steel work.
1. Design load applied to fasteners shall not exceed 25% of the rated load for the fastener used.
2. Fasteners attached to concrete ceilings shall be vibration and shock resistant.
3. Holes cut to a depth of more than 1.5 inches in reinforced concrete beams or to a depth of more than 0.75 inches in concrete joists shall not cut the main reinforcing bars. Holes not used shall be filled.
F. All system conduits shall be routed/installed either parallel or perpendicular to building structural members. Changes in direction shall be made with symmetrical bends or cast-metal fittings. Field-made bends shall be made with a conduit bending machine or hand bender with a full-formed shoe to limit bend radii to permitted values and maintain conduit cross-section. Hickey-made bends are prohibited.
G. All system conduits shall be installed at a height so as not to obstruct any portion of a window, doorway, stairway or a passageway, and shall not interfere with the operation of any mechanical or electrical equipment.
H. All exposed penetrations of walls shall be provided with escutcheon plates on either side of the wall.
3.02 SEPARATION OF CONDUCTORS
A. Conductors shall be separated into two categories:
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-11
1. Data circuits, including signaling line circuits, etc., and low voltage non-data circuits, including notification appliances circuits.
2. AC power circuits.
B. Each category of conductors shall be installed in physically separated, dedicated conduits, and shall not interface with one another except at common associated control equipment. Addressable modules or elements used to provide system “addresses” for non-addressable-type initiating devices shall be considered “control equipment” for the purposes of this section. Fire alarm system conductors shall be further segregated as necessary to prevent electrical and/or audio crosstalk between conductors installed in common conduits.
3.03 GENERAL REQUIREMENTS INSTALLATION OF CONDUCTORS, CABLES AND
DEVICES
A. The requirements of this section apply to all fire alarm system conductors, including all signaling line, initiating device, notification appliance, auxiliary function, remote signaling, AC and DC power and grounding/shield drain circuits, and any other wiring installed by the Subcontractor pursuant to the requirements of these Specifications.
B. All fire alarm system conductors shall be:
1. New. Wire that has scrapes, nicks, gouges or crushed insulation shall not be used.
2. UL listed.
3. Continuous (except bare shield drain conductors) between devices and between devices and intermediary terminal cabinets.
4. Addressable circuits shall be 18 AWG solid twisted jacketed cables, minimum. Notification appliance circuits shall be 14 AWG solid, minimum. AC power circuits shall be 12 AWG stranded, minimum.
Where the system manufacturer's installation recommendations require larger conductors, larger conductors shall be provided.
3.04 TYPES OF CONDUCTORS AND CABLES
A. All low voltage fire alarm circuits shall be installed as non-power limited circuits
FPL type in accordance with Article 760 of NFPA 70. All other fire alarm circuits shall be installed in accordance with the applicable requirements of
NFPA 70, 2005 edition.
B. All system conductors, shield drain conductors and grounding conductors, shall be solid copper or bunch tinned (bonded) stranded copper. Stranded copper conductors are acceptable for shield drain conductors and grounding conductors only.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-12
C. All signaling line circuits, including all addressable initiating device circuits shall be multi-conductor jacketed twisted cable.
D. All non-addressable initiating device circuits shall be twisted pairs. Notification appliance circuits auxiliary function circuits, and AC power circuits shall be
THHN/THWN parallel conductors.
E. The use of aluminum wire is prohibited.
3.05 WIRING METHODS
A. Splices in fire alarm system conductors are specifically prohibited, except for soldered and taped splices in shield drain conductors, as necessary to maintain continuity of the shield between devices. All splices shall be mechanically secure before soldering.
B. All conductor terminations, except splices in shield drain conductors, and including field connections to supervisory resistors, diodes, relays or other devices, shall be to numbered terminals or terminal strips and shall be readily accessible for inspection, service, testing and maintenance.
1. All conductor terminations shall be within junction boxes, device back boxes, terminal cabinets, control panels or other suitable metal enclosures.
2. Terminals and terminal strips shall be suitable for the size and number of conductors connected to them.
3. Each conductor termination shall be uniquely numbered with durable plastic tags or uniquely identifiable by a combination of numbers and color codes. These conductor numbers shall be shown on the
Subcontractor's record drawings (floor plans and detailed wiring diagrams) in a manner allowing ready identification of all conductor terminations.
4. All terminations are subject to the approval of Fermilab.
C. All control panel wiring shall be fully dressed and bundled with nylon tie wraps at 3-inch intervals. Bundled wiring shall be routed parallel to terminal strips within control panels, with individual conductors turned out at 90° angles to their associated terminal connections. AC power conductors shall be bundled and routed separately from low voltage conductors. A minimum 2-inch separation shall be maintained between AC power conductors and low voltage conductors wherever possible. All control cabinets shall be sized to accommodate the requirements of this Paragraph.
D. Control panels shall not be used as raceways. Conductors which do not terminate within a control panel shall not be routed through that control panel.
E. Conductors looped around terminals are not acceptable.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-13
F. Wire nuts appropriately sized for the gauge of wires, are acceptable in junction boxes only. Wires shall be stripped, mechanically twisted, and trimmed prior to installing wire nut. Wire nuts shall be secured with electrical tape, "Crimp" or "Self Stripping" wire connectors are not acceptable.
G. T-tapping of fire alarm circuits is prohibited, unless approved by the Engineer.
3.06 DEVICE BACKBOXES/TERMINAL CABINETS/JUNCTION BOXES/PULL BOXES
A. Junction boxes may be installed as necessary to minimize the overall length of conduit required, consistent with these Specifications. All conductors shall be pulled through junction boxes, without splices.
B. Pull-boxes shall be installed in each fire alarm system conduit at intervals not to exceed 100 feet. Pull-boxes shall be 4-inch square, minimum.
C. Terminal cabinets may be installed as appropriate where distance or number of conduit bends make continuous conductors between devices impractical.
1. Terminal cabinets shall be 6 x 6 x 4 inches minimum, provided with pressure-plate type barrier terminal strips and screw mounted covers.
Terminal strips shall be securely and permanently mounted to the cover of the terminal cabinet. Terminals shall be clearly numbered with indelible marker for identification, using a consistent numbering convention throughout the project.
2. Terminal cabinets shall be readily accessible for inspection and servicing. Terminal cabinet locations requiring the use of scaffolds or ladders over 6 feet in length for inspection and servicing will not be accepted.
D. All device back boxes, junction boxes and terminal cabinets shall be sized to accommodate the number of conductors contained therein, extension rings or extension boxes are not acceptable.
E. All device back-boxes, junction boxes, and terminal cabinets shall be listed for outdoor use where installed in damp or wet locations.
3.07 SHIELDED CABLES
A. All circuits shall be twisted and shielded as recommended by the system manufacturer(s) and as necessary to prevent electrical and/or audio crosstalk between conductors installed in common conduits.
B. All conductor shielding shall be continuous (with splices) for the length of the circuit, grounded at the associated control panel only.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-14
C. Shield drain conductors and foil shall be trimmed and taped at each splice to prevent grounding of the shield at any location other than the associated control panel.
3.08 GENERAL REQUIREMENTS FOR PATCHING
A. Removal, modification, and repair of all finished surfaces shall be coordinated with, and is subject to the approval of the Construction Coordinator.
B. The Subcontractor shall be responsible for all patching and touch-up painting necessitated by the performance of his work.
3.09 FIRESTOPPING
A. All holes made by the Subcontractor in or through walls, floors and ceilings shall be sealed around the conduit(s) by the fire alarm Sub-Contractor, restoring the walls, floors and ceilings to their original condition, fire resistance and integrity.
B. Firestopping in fire rated walls and floor slabs shall be accomplished using a durable, UL-listed firestop assembly providing a fire rating equivalent or greater to that of the fire barrier. Firestopping material shall be manufactured by 3M or Hilti.
3.10 CLEAN AGENT PIPING INSTALLATION
A. Install clean-agent extinguishing piping and other components level and plumb, according to manufacturers' written instructions.
B. Each pipe section shall be cleaned internally after preparation and before assembly by means of swabbing, using a suitable nonflammable cleaner.
Pipe network shall be free of particulate matter and oil residue before installing nozzles or discharge devices.
C. Install extinguishing-agent containers anchored to substrate.
D. All pipe threads shall be sealed with Teflon tape pipe sealant applied to the male threads only.
E. Install pipe and fittings, valves, and discharge nozzles according to requirements listed in NFPA 2001.
1. Install valves designed to prevent entrapment of liquid or install pressure relief devices in valved sections of piping systems.
2. Support piping using supports and methods according to the manufacturer.
F. Clean-Agent Fire Extinguishing Systems Test:
1. Flow Test: Using nitrogen or other inert gas, perform a flow test on the piping network to verify that flow is continuous and unobstructed through piping and nozzles.
2. Pressure/Leak Test: test the piping in a closed circuit per manufacturer instructions.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-15
3. Room Pressurization Test: After all construction work is complete, conduct a room pressurization test in accordance with NFPA 2001 in each clean agent suppression system hazard area. Test shall confirm enclosures ability to retain the agent concentration level for the required hold time. If the test fails, the suppression system contractor shall coordinate room sealing with the general contractor. Additional tests shall be conducted until successful test results are achieved. Include final test results in project ‘Closeout Submittals’.
G. System will be considered defective if it does not pass tests and inspections
3.11 GENERAL REQUIREMENTS FOR SYSTEM TESTING
A. The fire alarm system shall be tested and documented in accordance with the requirements of these Specifications and approved test protocols prepared by the Subcontractor as outlined in Paragraph C.1.14.
B. System testing shall include three distinct phases as follows:
1. Insulation testing of all new system wiring with a meggar, performed and documented by the Subcontractor. This testing shall be completed prior to connection of any electrical devices.
2. A 100% test of all control equipment, annunciation devices, detectors, notification appliances, remote signaling apparatus, and auxiliary functions, performed and documented by the Subcontractor.
3. An Acceptance Test performed and documented by the Subcontractor, in the presence of the appropriate Fermilab representatives.
C. Fermilab reserves the right to witness all Subcontractor testing. Fermilab shall be given 5 working days (minimum) notice of all tests; 10 days for the acceptance test.
D. The Subcontractor shall provide all materials, equipment, coordination and personnel necessary to perform and document all required tests. All test equipment shall be subject to the approval of Fermilab.
3.12 INSULATION TESTING
A. All fire alarm system conductors shall be tested for integrity of insulation, prior to connection of any equipment, using a meggar operating at 500 Volts; two
(2) minutes per circuit, minimum. This testing shall be coordinated with the installation schedule to prevent over-voltage damage to system components.
B. All test values shall be recorded in ohms. All circuits measuring less than 10M ohms to ground, or between conductors installed in the same conduit, shall be replaced.
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-16
C. Upon completion of insulation testing, the Subcontractor shall provide written certification to Fermilab documenting successful completion of all required insulation testing in accordance with these Specifications.
3.13 SUBCONTRACTOR'S 100% TEST
A. All alarm initiating devices, notification appliances, auxiliary function relays, control panels, annunciation equipment, FIRUS connections, standby power supplies and associated circuits shall be functionally tested to verify proper operation and supervision.
B. Correct annunciation of all alarm, supervisory and trouble conditions, including any user programmable text messages, shall be verified.
C. Correct operation of all automatic auxiliary functions shall be verified.
D. Proper automatic transmission of fire alarm, supervisory alarm, and trouble signals via the FIRUS system shall be verified.
E. The Subcontractor's 100% test shall be conducted with the final system program installed in non-volatile memory. In the event that errors are identified in the system program, the program shall be corrected and all required testing repeated with the new software iteration. The intent of this paragraph is that all required system tests, except insulation testing, be conducted with the final system program installed.
F. Upon completion of Subcontractor's Operational and Supervisory Testing, the
Subcontractor shall provide written certification to Fermilab documenting successful completion of all required tests in accordance with these
Specifications.
3.14 FERMILAB'S ACCEPTANCE TEST
A. Upon completion of the project, an Acceptance Test of the fire alarm system shall be performed in the presence of Fermilab's designated
Representative(s).
1. In preparation for the Acceptance Test, the Subcontractor shall submit
As-built Drawings, as required elsewhere in these
Specifications.
2. The Subcontractor's As-built Drawings will be reviewed for conformance to the applicable Specification requirements. Upon approval of the As-built Drawings, Fermilab will mark up one copy to reflect the Acceptance Test plan.
B. The Acceptance Test will be directed by Fermilab in accordance with the
Acceptance Test plan. The Acceptance Test shall be performed by the
Subcontractor and shall include at a minimum:
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-17
1. Functional testing of 100% of the new and affected existing initiating devices.
2. Functional testing of 100% of the evacuation signaling devices. This testing shall include audibility testing with a dBa meter.
3. Supervisory testing of 100% of the initiating devices and 100% of the initiating device circuits.
4. Supervisory testing of 10% of the evacuation signaling devices and
100% of the evacuation signaling circuits.
5. Supervisory testing of all power supplies/standby batteries.
6. Functional testing of all auxiliary functions.
7. Two, consecutive full load tests (all fire alarm initiating devices in alarm and all evacuation signals, annunciators and auxiliary functions activated simultaneously), one under standby battery power and one under normal power, 15 minutes duration each, minimum.
8. Verification of proper annunciation of all signals.
9. Verification of proper automatic transmission of fire alarm, supervisory alarm, and trouble signals via FIRUS.
10. Verification of proper system operation under a variety of fault conditions, including power failures, opens, ground faults, and short circuits.
11. Any additional tests deemed necessary by the Fermilab
Representative(s) witnessing the testing.
C. 100% successful performance during Acceptance Testing is expected, based on the Subcontractor's Insulation Testing Documentation and 100% Test
Certification required, in accordance with NFPA 72. In the event of system performance inconsistent with the Subcontractor's testing certifications, Fermilab will make a determination as to whether or not the test results constitute failure of the Acceptance Test. Failure of the Acceptance Test shall invalidate the Subcontractor's System Certification, in which case recertification (including 100% Subcontractor retesting) and a repeat of the
Acceptance Test shall be required at no additional cost to Fermilab.
3.15 TRAINING FOR FERMILAB FIRE DEPARTMENT AND BUILDING SERVICES
PERSONNEL
A. Upon project completion, the Subcontractor shall provide on-site training for Fire
System Maintenance personnel.
3.16 WARRANTY
A. The Subcontractor shall warranty all materials, equipment and workmanship for in-service portions of the fire alarm system during the installation period and thereafter, for a period of one year, including the following related services:
CLEAN AGENT FIRE SUPPRESSION November 2021 212400-18
1. Provide emergency service for the new fire alarm systems, or for in-service portions thereof, within four hours of a request for such service by Fermilab during the installation and warranty periods. This service shall be provided on a 24-hour per day, seven days per week basis, without additional cost.
2. The Subcontractor shall provide regularly scheduled testing and normal system maintenance, in accordance with the requirements of
NFPA 72, 2010, for in-service portions of the system during the construction period, and thereafter, for the completed system until such time as it has been accepted by Fermilab.
3. If Fermilab experiences more than two spurious or unexplained false alarms in any 48-hour period, while the system is under warranty, the
Subcontractor shall, upon request, provide the necessary labor, material and technical expertise to promptly correct the problem(s) without additional cost.
B. The warranty period shall begin upon Final Approval and Acceptance of the completed system.
END OF SECTION 2124100
File details come from the government source that posted it. Updated .