Updated Construction Bid Documents.pdf

PDF 4 MB Posted

Attached to
Generator Replacement Services Federal contract opportunity
Solicitation number
20342325Q00014
Issued by
Department of the Treasury Bureau of the Fiscal Service

About this file

These construction bid documents detail a generator replacement project for the Armed Forces Retirement Home (AFRH) in Gulfport, Mississippi. The project involves replacing two main generators (a 2.25MW diesel generator and a 2MW natural gas generator) located on an elevated platform, along with associated equipment including a fuel polishing system, aboveground storage tanks, and a propane generator. The bid documents include comprehensive electrical, plumbing, and structural plans, with a phased construction approach that involves demolishing existing generators, installing new generators, and completing commissioning for each phase.

The project is set aside for small businesses, with a solicitation (No. 20342325Q00014) issued by the Department of the Treasury Bureau of the Fiscal Service. The solicitation has undergone multiple amendments extending the proposal submission deadline, with the most recent amendment (Amendment 009) extending the deadline to June 9th at 10:00am ET. The government intends to award a firm fixed-price contract for generator replacement services, requiring vendors to have an unexpired SAM.gov registration and Unique Entity Identifier (UEI). The project includes detailed technical specifications for generator types, electrical systems, lightning protection, and site-specific installation requirements.

View the file

Other files for this federal contract opportunity

Other files attached to Generator Replacement Services, newest first.
File Type Posted
Amendment 017.pdf PDF
Amendment 016.pdf PDF
Addendum Cover Sheet.pdf PDF
Additional Specification Documents.pdf PDF
Amendment 015.pdf PDF
Amendment 014.pdf PDF
Amendment 013.pdf PDF
Amendment 012.pdf PDF
Amendment 011.pdf PDF
Operation Manual PLC-HMI Upgrade.pdf PDF
SGP-1297 Kohler Power Systems.pdf PDF
Power Distribution One Line Diagram.pdf PDF
Kohler ATS and Switchgear SGP-1297 D.pdf PDF
Enlarged Generator Pad and Main Elec. Rm.pdf PDF
Amendment 010.pdf PDF
Backup Generation System Report.pdf PDF
Electrical Site Plan - Power.pdf PDF
Amendment 009.pdf PDF
Amendment 008.pdf PDF
Amendment 007.pdf PDF
20342325Q00014 Updated.pdf PDF
Amendment 006.pdf PDF
Amendment 005.pdf PDF
Amendment 004.pdf PDF
Amendment 003.pdf PDF
Amendment 002.pdf PDF
Amendment 001.pdf PDF
20342325Q00014.pdf PDF
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:3

:4

A

M

G001

SB

FS

AFRH-041

COVER SHEET

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

LOCATION MAP

ARMED FORCES RETIREMENT HOME, GULFPORT CAMPUS

CONSTRUCTION BID DOCUMENTS

GENERATOR REPLACEMENT

G001 - COVER SHEET

S001 - STRUCTURAL SPECIFICATIONS

S101 - FOUNDATION PLAN

S201 - DETAILS

A101 - PLATFORM FENCING PLAN AND ELEVATIONS

P101 - PLUMBING PLANS

E001 - ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

E101 - ELECTRICAL PLAN - LOWER LEVEL OF PLATFORM

E102 - ELECTRICAL PLANS

E103 - ELECTRICAL WORK - MECHANCIAL 1032

E201 - PARTIAL EXISTING ELECTRICAL ONE-LINE DIAGRAM

E202 - PARTIAL NEW ELECTRICAL ONE-LINE DIAGRAM

E301 - ELECTRICAL DETAILS

SHEET INDEX

AFRH Project Numbers: AFRCRO-FAC-22-0033, AFRCRO-FAC-24-005

NO DATE REVISION

6 MVA UTILITY

TRANSFORMER

(EXISTING TO

REMAIN)

MAIN PARALLELING

SWITCHGEAR "MSG"

1200A, 3PH, 4W

15kV METAL CLAD WALK-

IN SWITCHGEAR

(EXISTING TO REMAIN)

NEW 2.25MW 13.8kV, 3PH, 4W

DIESEL GENERATOR "EG1"

NEW 2.005MW 13.8kV, 3PH, 4W

NATURAL GAS GENERATOR "EG2"

AST-1

FILL

STATION

AST-2

EX G

EX G

G

EX 4" BLW GRADE

EX 4" BLW GRADE

EX FW

EX FW

CONNECT TO EX GAS

PIPE BELOW GRADE

2" GAS BELOW GRADE

1 1/2" GAS UP SECURED

TO INSIDE OF CEMENT

COLUMN, COORDINATE

FINAL LOCATION

SEE GAS

CONNECTION DETAIL

1 1/2" GAS UP

THROUGH CEMENT

PODIUM, COORDINATE

FINAL LOCATION

1 1/2" GAS PIPE

SECURED TO

UNDERSIDE OF

CEMENT PODIUM

VALVE BOX, COORDINATE

FINAL LOCATION

4" FO

2" FO

2" FO

FUEL POLISHER

4" FO DN

3-WAY

ISOLATION

L-VALVE

3-WAY

ISOLATION

L-VALVE

2" FO

4" FO

2" FO

EXISTING

WELL PUMP

MECHANICAL ROOM 1032

FOR WORK IN THIS

AREA SEE 1/P101

EX G

EX G

EX G

EX FW

EX FW

EMERGENCY

GENERATOR

BY EC

DIRT

LEG

UNION

FLEX CONNECTION

SHUT-OFF VALVE

1 1/2" STEEL PIPING

G

G

1 1/2" STEEL PIPE SECURED

& HUNG FROM UNDERSIDE

OF CONCRETE PODIUM

PIPE SLEEVE THRU

CONCRETE PODIUM

PRESSURE REDUCING

VALVE INLET PSI 5 - OUTLET PSI 3

DIRT

LEG

3/4" STEEL PIPING

SHEER WALL

2" SDR 11 PE

3408/2406 PIPING

1 1/2" STEEL PIPING SECURED TO THE

BACKSIDE OF THE CONCRETE

COLUMN

N

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:2

:0

A

M

P101

ELP

RB

AFRH-041

PLUMBING PLANS

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

NTS

PLUMBING NEW WORK PLAN

NTS

PLUMBING OVERALL SITE PLAN

12" = 1'-0"

GENERATOR GAS CONNECTION DETAIL

PLUMBING GENERAL NOTES

* FIELD VERIFY LOCATION AND INVERTS OF EXISTING SITE UTILITIES PRIOR TO INSTALLATION.

NO DATE REVISION

1 07.25.25 ADDENDUM #1

AST-2 DIESEL MAIN STORAGE 25,000 10 43'-7" HIGHLAND TANK 25000FGCYL120 ALL

AST-1 DIESEL MAIN STORAGE 25,000 10 43'-7" HIGHLAND TANK 25000FGCYL120 ALL

Manufacturer Model Notes

EQUIPMENT

NAME

FUEL TYPE TANK TYPE

CAPACITY

(GAL)

DIAMETER

(FT)

LENGTH

Basis of Design

ABOVEGROUND STORAGE TANK SCHEDULE

25-JUL-25

ELECTRICAL SYMBOLS LEGEND

1 KEYED NOTE

REFER TO KEYNOTE SCHEDULE ON DRAWING

SINGLE POLE SWITCH

TWO POLE, SINGLE POLE SWITCH

3-WAY SWITCH

4-WAY SWITCH

J J JUNCTION BOX

PANELBOARD

REFER TO PANEL SCHEDULES FOR ADDITIONAL INFORMATION

PULL BOX

DIMENSIONS AS INDICATED ON DRAWINGS

DUPLEX WALL RECEPTACLE

NEMA 5-20R UNLESS NOTED OTHERWISE

QUADRAPLEX WALL RECEPTACLE

NEMA 5-20R UNLESS NOTED OTHERWISE

BRANCH CIRCUITS TO DEVICES OR EQUIPMENT

- SHORT TICKS INDICATE HOTS

- LONG TICK INDICATES NEUTRAL

- NO TICK MARKS INDICATES ONE HOT AND ONE NEUTRAL

INCLUDE A GROUND CONDUCTOR IN ALL CONDUITS AND RACEWAYS

PER NEC REQUIREMENTS. GROUND CONDUCTORS ARE NOT

INDICATED WITH TICK MARKS.

REFER TO PANEL SCHEDULES FOR WIRE AND CONDUIT SIZES AND

QUANTITIES.

HOME RUN TO INDICATED PANEL AND CIRCUIT NUMBER(S)

- SHORT TICKS INDICATE HOTS

- LONG TICK INDICATES NEUTRAL

- NO TICK MARKS INDICATES ONE HOT AND ONE NEUTRAL

INCLUDE A GROUND CONDUCTOR IN ALL CONDUITS AND RACEWAYS

PER NEC REQUIREMENTS. GROUND CONDUCTORS ARE NOT

INDICATED WITH TICK MARKS.

REFER TO PANEL SCHEDULES FOR WIRE AND CONDUIT SIZES AND

QUANTITIES.

3P-30AF/NF SAFETY DISCONNECT SWITCH (NON-FUSED)

NUMBER OF POLES AND FRAME SIZE AS INDICATED

SAFETY DISCONNECT SWITCH (FUSED)

NUMBER OF POLES, FRAME SIZE, AND FUSE SIZE AS INDICATED

3P-30AF/30

1-PHASE MOTOR

EQUIPMENT TAG AS INDICATED

GREY SYMBOLS INDICATE ELEMENT EXISTING TO REMAIN

3-PHASE MOTOR

EQUIPMENT TAG AS INDICATED

DASHED GREY LINES AROUND EQUIPMENT INDICATE NEC

REQUIRED CLEARANCES

DASHED SYMBOLS INDICATE ELEMENT TO BE DEMOLISHEDSOLID HATCHING OVER LIGHTING FIXTURES INDICATES FIXTURE

SHALL BE POWERED VIA LIFE SAFETY CIRCUIT AND RELAYED VIA

UL924 LISTED DEVICE FOR FULL BRIGHTNESS DURING FIRE ALARM

OR NORMAL POWER LOSS.

REFER TO LIGHTING FIXTURE SCHEDULE FOR ASSOCIATED

SYMBOL FOR EACH FIXTURE TYPE. EXIT SIGN, CEILING MOUNTED

FACES, CHEVRONS, AND ORIENTATION AS INDICATED ON DRAWINGS

EXIT SIGN, FLAG MOUNTED

FACES AND CHEVRONS AS INDICATED ON DRAWINGS

EXIT SIGN, WALL MOUNTED

CHEVRONS AS INDICATED ON DRAWINGS

1P 1 POLE (2P, 3P, 4P, ETC.)

A AMPERE

AC ABOVE COUNTER, AIR CONDITIONER

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

AF AMP FRAME

A.F.F. ABOVE FINISHED FLOOR

A.F.G. ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT, CENTER LINE

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCOFM CLINICAL CENTER OFFICE OF FACILITY

MANAGEMENT

CCTV CLOSED CIRCUIT TELEVISION

CIT CENTER FOR INFORMATION TECHNOLOGY

CKT CIRCUIT

CLG CEILING

COMB COMBINATION

CMPR COMPRESSOR

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER CIRCULATING PUMP

DDCM DIVISION OF DESIGN AND CONSTRUCTION

MANAGEMENT

DEPT DEPARTMENT

DET DETAIL

DEP DIVISION OF ENVIRONMENTAL

PROTECTION

DFOM DIVISION OF FACILITIES OPERATIONS AND

MAINTENANCE

DFM DIVISION OF THE FIRE MARSHAL

DFP DIVISION OF FACILITIES PLANNING

DFS DIVISION OF FACILITIES STEWARDSHIP

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DOHS DIVISION OF OCCUPATIONAL HEALTH AND

SAFETY

DPR DAMPER

DPSM DIVISION OF PHYSICAL SECURITY

MANAGEMENT

DRS DIVISION OF RADIATION SAFETY

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DTR DIVISION OF TECHNICAL RESOURCES

DWG, DWGS DRAWING, DRAWING(S)

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FACNET FACILITIES NETWORK SYSTEM

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FT FEET

FU FUSE

FSS FUSED SAFETY SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFCI, GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HOA HAND-OFF-AUTOMATIC

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING, AND AIR

CONDITIONING

HWP HYDRONIC WATER PUMP

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IN INCHES

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT-HOUR

LOC LOCATE, LOCATION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSBD MAIN SWITCHBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTS MANUAL TRANSFER SWITCH

MTR MOTOR, MOTORIZED

N.C. NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NFSS NON-FUSED SAFETY SWITCH

NIC NOT IN CONTRACT

NIH NATIONAL INSTITUTES OF HEALTH

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OHPE OFFICE OF HOSPITAL PHYSICAL ENVIRONMENT

OL OVERLOADS

P PLATE

PA PUBLIC ADDRESS

PB PULL BOX, PUSH BUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PO PROJECT OFFICER

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

ELECTRICAL ABBREVIATIONS LIST

PWR POWER

QTY., QUAN QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP. TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UEB UTILITIES ENGINEERING BRANCH

UG UNDERGROUND

UH UNIT HEATER

U.N.O. UNLESS NOTED OTHERWISE

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR OR ULTRAVIOLET

V VOLT(S)

VA VOLT-AMPERE(S)

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT(S)

W/ WITH

WAO WORK AREA OUTLET

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

@ AT

' FEET

" INCHES

# NUMBER

Ø, Φ PHASE

GENERAL:

THIS PROJECT INCLUDES PHASED CONSTRUCTION FOR THE SCOPE OF WORK. REFER TO ALL MEP DRAWINGS FOR DETAILED

INFORMATION.

THE CONTRACTOR SHALL PROVIDE A COMPLETE PROJECT PHASING PLAN AND SCHEDULE USING THE PHASING INTENT ON THE CONTRACT DOCUMENTS AS A BASELINE. THE PHASING PLAN AND SCHEDULE SHALL BE INCLUSIVE OF ALL TRADES AND INDICATED ALL ANTICIPATED IMPACTS TO OPERATIONS, INCLUDING PLANT SHUTDOWNS, PIPE FREEZES, ETC. THE PLAN AND SCHEDULE SHALL BE

SUBMITTED TO THE OWNER AND EOR FOR REVIEW PRIOR TO THE START OF ANY WORK.

1. PHASE 1

1.1. DEMOLISH EXISTING EG1 AND ASSOCIATED EQUIPMENT

1.2. INSTALL NEW EG1 DIESEL ENGINE GENERAOTR AND ASSOCIATED EQUIPMENT

1.3. INSTALL LOAD BANK

1.4. INSTALL GEN-WP & MTS-WP

1.5. COMPLETE CX LEVEL 4 FOR EG1, GEN-WP & MTS-WP

2. PHASE 2

2.1. DEMOLISH EXISTING EG2 AND ASSOCIATED EQUIPMENT

2.2. INSTALL NEW EG2 NATURAL GAS ENGINE GENERAOTR AND ASSOCIATED EQUIPMENT

2.3. COMPLETE CX LEVEL 4 FOR EG2

3. PHASE 3

3.1. DEMOLISH EXISTING FUEL RECIRCULATION SYSTEM

3.2. INSTALL NEW FUEL POLISHING SYSTEM

3.3. COMPLETE CX LEVEL 4 FOR FUEL POLISHING SYSTEM

PHASING NOTES

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:4

:4

A

M

E001

TZ

DF

AFRH-041

ELECTRICAL SYMBOLS,

ABBREVIATIONS, AND

GENERAL NOTES

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

ELECTRICAL DRAWING INDEX

Sheet Number Sheet Name

E001 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

E101 ELECTRICAL PLAN - LOWER LEVEL OF PLATFORM

E102 ELECTRICAL PLANS

E103 ELECTRICAL WORK - MECHANICAL 1032

E201 PARTIAL EXISTING ELECTRICAL ONE-LINE DIAGRAM

E202 PARTIAL NEW ELECTRICAL ONE-LINE DIAGRAM

E301 ELECTRICAL DETAILS

ELECTRICAL GENERAL NOTES

1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL E SERIES CONTRACT

DRAWINGS.

2 THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET. I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR," THE

CONTRACTOR IS RESPONSIBLE FOR THAT WORK.

3 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK.

BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND

RELATED SPECIFICATION SECTIONS FOR THE PROPER INSTALLATION OF ALL WORK.

4 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS.

REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL REQUIREMENTS.

5 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS

TO THE SATISFACTION OF ALL CONCERNED TRADES.

6 COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS AND ALL AFFECTED TRADES PRIOR TO INSTALLATION.

7 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM

OF 3/4" UNLESS OTHERWISE NOTED.

8 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.

9 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION

BOXES IS UNIMPEDED.

10 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH

MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.

11 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE

NEMA 4X STAINLESS STEEL AND RATED FOR THAT APPLICATION.

12 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL

WITHOUT THE USE OF SPECIALIZED TOOLS.

13 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES, THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.

14 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED) AND ALL OTHER APPLICABLE CODES AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.

15 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.

16 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.

17 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING

LABORATORY.

18 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.

19 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNER'S REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR

SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.

20 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR

INSTALLATIONS.

21 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR

TO PERFORMING ANY WORK.

22 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN

CHASES, EXPOSED CEILING AREAS, JANITOR CLOSETS, AND MECHANICAL/ELECTRICAL ROOMS.

23 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL

GROUNDING AND/OR BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.

24 THE CONTRACTOR SHALL PROVIDE UPDATED TYPED PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS.

AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE BY THE

OWNER.

25 THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORK PERFORMED SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.

26 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.

27 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION.

THE CONTRACTOR SHALL COORDINATE THESE REQUIREMENTS WITH THE OWNER.

28 THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING

QUANTITIES OF MATERIALS REQUIRED TO COMPLETE THE PROJECT.

29 THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE, AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.

30 FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES INSTALLED THROUGH

EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.

31 THE CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK.

DO NOT LEAVE HOLES THROUGH WALLS AND/OR ROOFS OPEN TO THE ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.

32 THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF PRIOR TO STARTING THE PROJECT.

THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE OWNER SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF.

33 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED FOR EASE OF PULLING AND TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS FOR A CODE COMPLIANT INSTALLATION. NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING THE REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS. ALL JUNCTION BOXES AND OTHER PULL POINTS SHALL BE ACCESSABLE.

34 DISTRIBUTION EQUIPMENT SHALL BE AIC RATED, AND ANY CIRCUIT BREAKERS SELECTED AND SET BASED ON THE OUTCOME OF THE CONTRACTORS OVERCURRENT PROTECTIVE DEVICE COODINATION STUDY. STUDY SHALL INCLUDE ALL ELEMENTS OF THE EXISTING AND NEW DISTRIBUTION SYSTEM REQUIRED TO ACCURATELY SIZE AND RATE THE NEW EQUIPMENT ADDED AS PART OF THIS PROJECT.

35 ARC FLASH LABELS SHALL BE PROVIDED TO ALL NEW EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTOR'S ARC FLASH STUDY. ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY AND SHALL BE RELABELED AS REQUIRED.

36 THESE DRAWINGS DO NOT INDICATE ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES

AND EXISTING CONDITIONS.

37 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED. ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. SHARING OF NEUTRALS IS PROHIBITED. ALL CIRCUITS SHALL CONTAIN AN INDIVIDUAL GROUND WIRE. USE OF THE CONDUIT SYSTEM FOR THE GROUND PATH IS

PROHIBITED.

38 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRATOR UPSIZES THE WIRES (INCLUDING THE

GROUND) AND CONDUIT AS REQUIRED PER NEC.

39 THE COMPLETE BRANCH WIRING SYSTEM IS NOT SHOWN ON THE DRAWINGS. AN ABBREVIATED FORMAT IS USED TO INDICATE WHICH FIXTURES/DEVICES ARE CONNECTED TO A COMMON CIRCUIT OR SWITCH. THIS IS PROVIDED AS A GUIDE TO THE CONTRACTOR TO ILLUSTRATE

CIRCUITS AND CONTROL INTENT. ACTUAL WIRING MAY DIFFER DUE TO FIELD CONDITIONS. COLOR CODING OF WIRES SHALL BE AS PER NEC.

40 PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE IS TO BE CONNECTED TO NEAREST 120V RECEPTACLE CIRCUIT.

41 PROVIDE 120V CONNECTION TO ALL MOTORIZED DAMPERS INDICATED ON MECHANICAL PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS ARE TO BE PROVIDED FROM EMERGENCY (LIFE SAFETY) BRANCH PANEL. MOTORIZED DAMPERS WITHIN THE SAME AREA CAN BE CIRCUITED TO THE SAME CIRCUIT (I.E. DEDICATED CIRCUIT IS NOT REQUIRED).

42 DURING THE BIDDING PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (ARCHITECTURAL, SITE/LANDSCAPING, HVAC, PLUMBING, AND SPECIALTY TRADES). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT NOT INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL CONTRACTOR’S WORK. THIS WORK SHALL

BE INSTALLED AS PER NEC REQUIREMENTS AT NO ADDITIONAL COST TO THE OWNER.

ELECTRICAL DEMOLITION GENERAL NOTES

1 CONTRACTOR SHALL PROVIDE A MINIMUM TWO WEEKS WRITTEN NOTICE PRIOR TO ANY SHUT DOWN. NOTICE IS

TO INCLUDE BUT IS NOT LIMITED TO THE LOCATION, PANELS AND DURATION OF SHUT DOWN.

2 OWNER SHALL HAVE RIGHT OF FIRST REFUSAL TO ANY EQUIPMENT, DEVICES, ETC. DEMOLISHED FROM

RENOVATION AREA PRIOR TO DISPOSAL.

3 MAINTAIN CONTINUITY OF SERVICE TO AREAS OUTSIDE THE PROJECT BOUNDARY. PATCH AND REPAIR ALL CIRCUITS CUT OFF DURING DEMOLITION BY WIRING METHODS COMPATIBLE WITH THE EXISTING INSTALLATION.

4 THE ELECTRICAL CONTRACTOR SHALL REVIEW THE DRAWINGS OF ALL OTHER TRADES IN THIS CONTRACT. THE REMOVAL OF ELECTRICAL SERVICE TO ALL EQUIPMENT IDENTIFIED ON OTHER TRADE DRAWINGS IS THE

RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.

5 EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES THAT MAY BE

CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.

NO DATE REVISION

1 07.25.25 ADDENDUM #1

07/25/2025

EXISTING

WELL PUMP

MECHANICAL ROOM 1032

EXISTING WELL PUMP

FEEDER TO PANEL 1HAM

INTERCEPT AND

ROUTE TO MTS

PROPANE GENERATOR

MTS - MANUAL TRANSFER SWITCH

E101

A101

A101

A101

A101

LOAD BANK

ON 6" CONCRETE PAD

A101

A101

A101

A101

FRONT2

AIR INTAKE

N

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:4

:4

A

M

E101

TZ

DF

AFRH-041

ELECTRICAL PLAN -

LOWER LEVEL OF

PLATFORM

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

NTS

OVERALL SITE PLAN - LOWER LEVEL

1/8" = 1'-0"

ELECTRICAL NEW WORK PLAN - LOWER LEVEL

POWER PLAN KEYNOTES

NO DATE REVISION

1 07.25.25 ADDENDUM #1

2MW AVTRON MODEL 4900 LV LOAD BANK WITH THE MODEL 9800 MV

TRANSFORMER CONFIGURATION. MAINTAIN 6' HORIZONTAL CLEARANCE

FOR AIR INTAKE AND 8' HORIZONTAL CLEARANCE FOR AIR EXHAUST.

OUTDOOR, NON-WALKIN, NEMA 3R, SQUARE D MV LOAD BANK

SWITCHGEAR.

1" = 100'-0"

J

J

J

J J

J

GFI

WP

GFI

WP

J J

2.25MW 13.8kV, 3PH, 4W

DIESEL

GENERATOR

"EG1"

2.25MW 13.8kV, 3PH, 4W

DIESEL

GENERATOR

"EG2"

FUEL

RECIRCULATION

SYSTEM

25,000 GALLON

DIESEL GUEL

TANK

25,000 GALLON

DIESEL GUEL

TANK

6000 kVA

UTILITY

TRANSFOR

MER

(EXISTING

TO REMAIN)

150 kVA FIRE PUMP

TRANSFORMER

(EXISTING TO

REMAIN)

NEUTRAL

GROUNDING

RESISTANCE

(EXISTING TO

REMAIN)

MAIN

PARALLELING

SWITCHGEAR

"MSG" 1200A,

3PH, 4W

15kV METAL

CLAD WALK-IN

SWITCHGEAR

(EXISTING TO

REMAIN)

6 MVA UTILITY

TRANSFORMER

(EXISTING TO

REMAIN)

150 kVA FIRE PUMP

TRANSFORMER

(EXISTING TO

REMAIN)

NEUTRAL GROUNDING

RESISTANCE

(EXISTING TO REMAIN)

MAIN PARALLELING

SWITCHGEAR "MSG"

1200A, 3PH, 4W

15kV METAL CLAD WALK-

IN SWITCHGEAR

(EXISTING TO REMAIN)

NEW 2MW 13.8kV, 3PH, 4W

DIESEL GENERATOR "EG1"

NEW 2MW 13.8kV, 3PH, 4W

NATURAL GAS GENERATOR "EG2"

NEW FUEL

POLISHING

SYSTEM

EARLY STREAMER

EMISSIONS (ESE)

LIGHTNING PROTECTION

POLE (REFER TO DETAIL 1

/E301). ANCHOR MOUNTING

BASE TO TOP OF THE

CONCRETE PLATFORM

DOWNLEAD

CONDUCTORS TO

GROUND ARRAYS

GROUND ROD

ARRAYS

(TYPICAL)

GROUND ROD

ARRAYS

(TYPICAL)

EG2-1

EG2-3

EG2-2

EG2-4,6

EG2-5,7

EG2-8

EG1-1

EG1-3

EG1-2

EG1-4,6

EG1-5,7

EG1

EG2

EG1-9,11

P-1 P-2

P-3

EG1-8,10 EG1-12,14

A101

A101

A101

A101

EG1 REMOTE

ANNUNCIATOR

EG2 REMOTE

ANNUNCIATOR

DIESEL FUEL

TANK #1

FILL

STATION

DIESEL FUEL

TANK #2

E102

E102

EXISTING

WELL PUMP

MECHANICAL ROOM 1032

EXISTING WELL PUMP

FEEDER TO PANEL 1HAM

INTERCEPT AND

ROUTE TO MTS

PROPANE GENERATOR ON 6" PAD

MTS - MANUAL TRANSFER SWITCH

A101

A101

A101

A101

N

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:4

:4

A

M

E102

TZ

DF

AFRH-041

ELECTRICAL PLANS

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

NTS

ELECTRICAL DEMOLITION PLAN

NTS

ELECTRICAL NEW WORK PLAN

NTS

OVERALL SITE PLAN - LEVEL 1

POWER PLAN KEYNOTES

NO DATE REVISION

1 07.25.25 ADDENDUM #1

DISCONNECT FEEDER TO LOAD CENTER INSIDE GENERATOR ENCLOSURE.

DISCONNECT POWER FROM EXISTING FUEL RECIRCULATING SYSTEM.

SEAL EXISTING STUB-UP OPENINGS WITH A STAINLESS-STEEL COVER

PLATE, SECURELY FASTENED AND WEATHER-RESISTANT, TO MAINTAIN

ENCLOSURE INTEGRITY AND PREVENT MOISTURE OR DEBRIS INTRUSION.

COORDINATE EXACT STUB-UP LOCATIONS AND DIMENSIONS WITH THE

GENERATOR MANUFACTURER PRIOR TO CORING OR CUTTING OPENINGS IN

THE ENCLOSURE FOR ELECTRICAL CONDUIT ENTRIES. CONFIRM

COMPATIBILITY WITH MANUFACTURER’S RECOMMENDED ENCLOSURE

PENETRATION GUIDELINES.

EXISTING LIGHTNING PROTECTION SYSTEM SHALL BE INTEGRATED WITH

THE NEW LIGHTNING PROTECTION SYSTEM.

PROVIDE CAT6 CABLE BETWEEN GENERATOR ENCLOSURE AND

ASSOCIATED GENERATOR ANNUNCIATOR IN 3/4" CONDUIT.

PROPANE GENERATOR TO BE CONNECTED TO THE OWNER PROVIDED

PORTABLE PROPANE TANK WHEN NEEDED.

REFER TO STRUCTURAL DRAWINGS FOR PLATFORM LAYOUT.

1/8" = 1'-0"

1/8" = 1'-0"

1" = 100'-0"

J J

GFI

WP

NEW PROPANE

GENERATOR

NEW MANUAL

TRANSFER

SWITCH

1LAM-15

1LAM-13

1LAM-17

1LAM-16

MINIMUM

FROM

FACE OF BUILDING

10' - 0"

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:4

:4

A

M

E103

TZ

DF

AFRH-041

ELECTRICAL WORK -

MECHANICAL 1032

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

1/8" = 1'-0"

ELECTRICAL WORK - MECHANCIAL 1032

NO DATE REVISION

1 07.25.25 ADDENDUM #1

125A

WELL

PUMP

MTS-WP

125 A

(25000 WSR)

G GEN-WP

GGEN - EG1

2000kW

GGEN - EG2

2000kW

FIRE PUMP

EXISTING TO REMAIN

125 GENERATOR

MOUNTED

13.2 KV 3-PHASE, 4-WIRE

DIESEL FUEL

13.2 KV 3-PHASE, 4-WIRE

NATURAL GAS

480/277V, 3-PHASE, 4-WIRE

NEMA 3R ENCLOSURE

PROPANEGENERATOR FEEDER

3 - #1 AWG & #6 AWG GROUND IN 2" CONDUIT

2 2

2 MVA LOAD BANK

NEMA 3R ENCLOSURE

1 1

1200AF

175AT

DISTRIBUTION PANEL 1HAM, 400A, 480Y/277V, MLO

MECHANICAL ROOM 1032 - EXISTING TO REMAIN

PARALLELING SWITCHGEAR - MSG

13.2KV 1200A, 3-PHASE, 4-WIRE

6 MVA TRANSFOREMER

22.86 KV Δ : 13.2KV WYE

Z = 7.5%

25 KV PRIMARY

LOAD INTERUPPER

FUSIBLE SWITCH

50/51 27/59

87 81 3286

40 90

15KV METALCALD SWITCHGEAR

1200A, 3-PHASE, 4-WIRE

EXISITING TO REMAIN

AUTOTRANSFER

CONTROL

250A

1200AF

350AT

1200AF

350AT

UTILITY FEED

1200AF

350AT

1200AF

175AT

1200AF

175AT

NGR NGR

150KVA

13.2KV Δ : 480V Δ

Z = 4.5%

15 KV LOAD

INTERUPPER

FUSIBLE SWITCH

EXISTING TO REMAINEXISTING TO REMAIN

100kW/125kVA

3 3

4 4

LOAD BANK SWITCHGEAR

13.2KV 1200A, 3-PHASE, 4-WIRE

2 MVA TRANSFORMER

13.2kV WYE PRI

480V WYE SEC

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:4

:4

A

M

E202

TZ

DF

AFRH-041

PARTIAL NEW

ELECTRICAL ONE-LINE

DIAGRAM

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

NTS

PARTIAL NEW ELECTRICAL ONE-LINE DIAGRAM

NO DATE REVISION

1 07.25.25 ADDENDUM #1

4 - #1/0 (15kV) & 1 - #4 AWG (15kV) GROUND IN 4" CONDUIT

133% INSULATION LEVEL FOR 15KV CABLE, MV-105

1 - #2 (15kV) IN 1.5" CONDUIT.

133% INSULATION LEVEL FOR 15KV CABLE, MV-105

1 - #6 AWG (15kV) GROUND IN 1.5" CONDUIT.

133% INSULATION LEVEL FOR 15KV CABLE, MV-105

NEUTRAL GROUND RESISTOR (NGR) IS EXISTING TO REMAIN.

REFER TO GENERATOR SCHEDULE ON DRAWING E301 FOR ADDITIONAL

DETAILS.

PROVIDE TAP PLATE IN PARALLELING SWITCHGEAR - MSG FOR LOAD BANK

SWITCHGEAR CONNECTION.

KEYNOTES

Generator Schedule

Equipment Name

Location Fuel Type Rating Type

Rating kW

Rating

KVA

Voltage Rating

Frequency (Hz)

Phases Wire RPM Enclosure

Enclosure Dimensions Basis of Design

Length (in) Width

(in) Height

(in) Manufacturer Model Notes

GEN-EG1 Elevated Platform Diesel Standby 2000 2500 13.2 kV 60 3 4 1800 Level II, Hurricane

Rated 384 144 158 Caterpillar 3516C Level 1, Type 10, Class 96

GEN-EG2 Elevated Platform Natural Gas Standby 2000 2500 13.2 kV 60 3 4 1800 Level II, Hurricane

Rated 462 144 158 Caterpillar G3520 Level 1, Type 10, Class 96

GEN-WP

Outside of Mechanical

Room 1032 Propane Standby 100 125 480 V 60 3 4 1800 Level II, NEMA 3R 129.4 40 56.2 Generac SG100 Level 1, Type 10, Class 96

EX GEN-EG1 Elevated Platform Diesel Standby 2250 2812.5 13.2 kV 60 3 4 1800 306 140 - Kohler 2250REOZDC Level 1, Type 10, Class 96

EX GEN-EG2 Elevated Platform Diesel Standby 2250 2812.5 13.2 kV 60 3 4 1800 306 140 - Kohler 2250REOZDC Level 1, Type 10, Class 96

DATE:

DRAWN BY:

CHECKED BY:

PROJ. NO:

DRAWING NO:

DRAWING TITLE:

PROJECT NAME:

THIS SQUARE APPEARS 1/2"x1/2"

ON FULL SIZE SHEETS

CLIENT:

1655 FORT MYER DRIVE

SUITE 830

ARLINGTON,VA 22209

PH: 412.287.7333

www.aeworks.com

PROFESSIONAL:

COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.

SUBMISSION:

AE WORKS®

A u to d e s k D o c s /A

F R

H -0

G u lf p o rt

G e n e ra to rs /A

F R

H -0

G u lf G e n

M E

P

R

.r v t

/2

/2

:4

:5

A

M

E301

TZ

DF

AFRH-041

ELECTRICAL DETAILS

AFRH GULFPORT

GENERATOR

REPLACEMENT

1800 Beach Dr, Gulfport, MS 39507

ARMED FORCES

RETIREMENT HOME

GULFPORT, MS

06.30.25

CONSTRUCTION BID

DOCUMENTS

1800 Beach Dr, Gulfport, MS 39507

NOT TO SCALE

EARLY STREAMER EMMISION - LIGHTNING PROTECTION DETAIL

37.0 :TOTAL DEMAND LOAD (A)

13.3 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

37.0 :TOTAL CONNECTED LOAD (A)

13.3 :TOTAL CONNECTED LOAD (KVA)

NOTES: 44.6 39.2 29.8 :CONNECTED LOAD/PHASE (A)

5.2 4.6 3.6 :CONNECTED LOAD/PHASE (KVA)

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 GENERATOR BLOCK HEATER 1 20.0 A 1.00 0.18 20.0 A 1 RECEPTACLE AT GENERATOR 16

13 GENERATOR BATTERY CHARGER 1 20.0 A 1.00 1.00 20.0 A 1 EXISTING JUNCTION BOX 14

11 EXISTING JUNCTION BOX 1 20.0 A 1.00 1.00 20.0 A 1 EXISTING JUNCTION BOX 12

9 EXSITING FAN SCHEDULE 1 20.0 A 0.83 1.00 20.0 A 1 EXISTING JUNCTION BOX 10

7 EXISTING FAN SCHEDULE 1 20.0 A 0.66 1.00 20.0 A 1 EXISTING JUNCTION BOX 8

5 EXISTING FAN COIL UNIT 1 20.0 A 0.58 1.00 20.0 A 1 EXISTING JUNCTION BOX 6

3 EXISTING RECEPTACLES 1 20.0 A 0.54 1.00 20.0 A 1 EXISTING JUNCTION BOX 4

1 EXISTING RECEPTACLES 1 20.0 A 0.54 1.00 20.0 A 1 EXISTING JUNCTION BOX 2

NO DESCRIPTION P TRIP A B C TRIP P DESCRIPTION NO

CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT

A.I.C. RATING 10,000 AMPS SYMMETRICAL MOUNTING: SURFACE

BUS RATING: 100 AMPS MCB RATING: 100.0 A FED FROM:

RATINGS: 208Y/120 MAINS TYPE: MCB LOCATION:

EXISTING PANEL 1LAM

37.5 :TOTAL DEMAND LOAD (A)

9.0 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

37.5 :TOTAL CONNECTED LOAD (A)

9.0 :TOTAL CONNECTED LOAD (KVA)

NOTES: 37.5 37.5 :CONNECTED LOAD/PHASE (A)

4.5 4.5 :CONNECTED LOAD/PHASE (KVA)

17 SPACE 1 -- -- -- -- 1 SPACE 18

15 SPACE 1 -- -- -- -- 1 SPACE 16

13 SPACE 1 -- -- 0.50 14

11 0.50 0.50

20.0 A 2 PUMP NO. 3

PUMP NO. 2 2 20.0 A

0.50 0.50 10

7 2.00 0.50

20.0 A 2 PUMP NO. 1

SPACE HEATER 2 25.0 A

2.00 0.00 6

3 LIGHTING 1 20.0 A 1.00 0.00

20.0 A 2 JACKET WATER HEATER

1 BATTERY CHARGER 1 20.0 A 1.00 0.00 20.0 A 1 NEMA 5-20R GFI 2

NO DESCRIPTION P TRIP A B TRIP P DESCRIPTION NO

CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT

A.I.C. RATING 10,000 AMPS SYMMETRICAL MOUNTING: SURFACE

BUS RATING: 100 AMPS FED FROM:

RATINGS: 120/240 MAINS TYPE: MLO LOCATION:

PANEL EG1

38.3 :TOTAL DEMAND LOAD (A)

9.2 :TOTAL DEMAND LOAD (KVA)

100.00% :TOTAL DEMAND FACTOR

38.3 :TOTAL CONNECTED LOAD (A)

9.2 :TOTAL CONNECTED LOAD (KVA)

NOTES: 34.8 41.7 :CONNECTED LOAD/PHASE (A)

4.2 5.0 :CONNECTED LOAD/PHASE (KVA)

17 SPACE 1 -- -- -- -- 1 SPACE 18

15 SPACE 1 -- -- 0.00 20.0 A 1 SPARE 16

13 SPACE 1 -- -- 0.00 20.0 A 1 SPARE 14

11 SPARE 1 20.0 A 0.00 0.00 20.0 A 1 SPARE 12

9 SPARE 1 20.0 A 0.00 0.00 20.0 A 1 SPARE 10

7 2.00 1.00 20.0 A 1 FUEL POLISHING SYSTEM 8

SPACE HEATER 2 30.0 A

2.00 1.00 6

3 LIGHTING 1 20.0 A 1.00 1.00

20.0 A 2 JACKET WATER HEATER

1 BATTERY CHARGER 1 20.0 A 1.00 0.18 20.0 A 1 NEMA 5-20R GFI 2

NO DESCRIPTION P TRIP A B TRIP P DESCRIPTION NO

CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT

A.I.C. RATING 10,000 AMPS SYMMETRICAL MOUNTING: SURFACE

BUS RATING: 100 AMPS FED FROM:

RATINGS: 120/240 MAINS TYPE: MLO LOCATION:

PANEL EG2

CONNECT TO EXISTING FEEDER MADE AVAILABLE BY DEMOLITION

3 - #3 AWG & #8 AWG G IN 1.25" CONDUIT.

CONNECT TO EXISTING FEEDER MADE AVAILABLE BY DEMOLITION

3 - #3 AWG & #8 AWG G IN 1.25" CONDUIT.

NO DATE REVISION

1 07.25.25 ADDENDUM #1

Sheets
P101 - PLUMBING PLANS

File details come from the government source that posted it. Updated .