Updated Construction Bid Documents.pdf
PDF 4 MB Posted
- Attached to
- Generator Replacement Services Federal contract opportunity
- Solicitation number
- 20342325Q00014
About this file
These construction bid documents detail a generator replacement project for the Armed Forces Retirement Home (AFRH) in Gulfport, Mississippi. The project involves replacing two main generators (a 2.25MW diesel generator and a 2MW natural gas generator) located on an elevated platform, along with associated equipment including a fuel polishing system, aboveground storage tanks, and a propane generator. The bid documents include comprehensive electrical, plumbing, and structural plans, with a phased construction approach that involves demolishing existing generators, installing new generators, and completing commissioning for each phase.
The project is set aside for small businesses, with a solicitation (No. 20342325Q00014) issued by the Department of the Treasury Bureau of the Fiscal Service. The solicitation has undergone multiple amendments extending the proposal submission deadline, with the most recent amendment (Amendment 009) extending the deadline to June 9th at 10:00am ET. The government intends to award a firm fixed-price contract for generator replacement services, requiring vendors to have an unexpired SAM.gov registration and Unique Entity Identifier (UEI). The project includes detailed technical specifications for generator types, electrical systems, lightning protection, and site-specific installation requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 017.pdf | ||
| Amendment 016.pdf | ||
| Addendum Cover Sheet.pdf | ||
| Additional Specification Documents.pdf | ||
| Amendment 015.pdf | ||
| Amendment 014.pdf | ||
| Amendment 013.pdf | ||
| Amendment 012.pdf | ||
| Amendment 011.pdf | ||
| Operation Manual PLC-HMI Upgrade.pdf | ||
| SGP-1297 Kohler Power Systems.pdf | ||
| Power Distribution One Line Diagram.pdf | ||
| Kohler ATS and Switchgear SGP-1297 D.pdf | ||
| Enlarged Generator Pad and Main Elec. Rm.pdf | ||
| Amendment 010.pdf | ||
| Backup Generation System Report.pdf | ||
| Electrical Site Plan - Power.pdf | ||
| Amendment 009.pdf | ||
| Amendment 008.pdf | ||
| Amendment 007.pdf | ||
| 20342325Q00014 Updated.pdf | ||
| Amendment 006.pdf | ||
| Amendment 005.pdf | ||
| Amendment 004.pdf | ||
| Amendment 003.pdf | ||
| Amendment 002.pdf | ||
| Amendment 001.pdf | ||
| 20342325Q00014.pdf |
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:3
:4
A
M
G001
SB
FS
AFRH-041
COVER SHEET
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
LOCATION MAP
ARMED FORCES RETIREMENT HOME, GULFPORT CAMPUS
CONSTRUCTION BID DOCUMENTS
GENERATOR REPLACEMENT
G001 - COVER SHEET
S001 - STRUCTURAL SPECIFICATIONS
S101 - FOUNDATION PLAN
S201 - DETAILS
A101 - PLATFORM FENCING PLAN AND ELEVATIONS
P101 - PLUMBING PLANS
E001 - ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES
E101 - ELECTRICAL PLAN - LOWER LEVEL OF PLATFORM
E102 - ELECTRICAL PLANS
E103 - ELECTRICAL WORK - MECHANCIAL 1032
E201 - PARTIAL EXISTING ELECTRICAL ONE-LINE DIAGRAM
E202 - PARTIAL NEW ELECTRICAL ONE-LINE DIAGRAM
E301 - ELECTRICAL DETAILS
SHEET INDEX
AFRH Project Numbers: AFRCRO-FAC-22-0033, AFRCRO-FAC-24-005
NO DATE REVISION
6 MVA UTILITY
TRANSFORMER
(EXISTING TO
REMAIN)
MAIN PARALLELING
SWITCHGEAR "MSG"
1200A, 3PH, 4W
15kV METAL CLAD WALK-
IN SWITCHGEAR
(EXISTING TO REMAIN)
NEW 2.25MW 13.8kV, 3PH, 4W
DIESEL GENERATOR "EG1"
NEW 2.005MW 13.8kV, 3PH, 4W
NATURAL GAS GENERATOR "EG2"
AST-1
FILL
STATION
AST-2
EX G
EX G
G
EX 4" BLW GRADE
EX 4" BLW GRADE
EX FW
EX FW
CONNECT TO EX GAS
PIPE BELOW GRADE
2" GAS BELOW GRADE
1 1/2" GAS UP SECURED
TO INSIDE OF CEMENT
COLUMN, COORDINATE
FINAL LOCATION
SEE GAS
CONNECTION DETAIL
1 1/2" GAS UP
THROUGH CEMENT
PODIUM, COORDINATE
FINAL LOCATION
1 1/2" GAS PIPE
SECURED TO
UNDERSIDE OF
CEMENT PODIUM
VALVE BOX, COORDINATE
FINAL LOCATION
4" FO
2" FO
2" FO
FUEL POLISHER
4" FO DN
3-WAY
ISOLATION
L-VALVE
3-WAY
ISOLATION
L-VALVE
2" FO
4" FO
2" FO
EXISTING
WELL PUMP
MECHANICAL ROOM 1032
FOR WORK IN THIS
AREA SEE 1/P101
EX G
EX G
EX G
EX FW
EX FW
EMERGENCY
GENERATOR
BY EC
DIRT
LEG
UNION
FLEX CONNECTION
SHUT-OFF VALVE
1 1/2" STEEL PIPING
G
G
1 1/2" STEEL PIPE SECURED
& HUNG FROM UNDERSIDE
OF CONCRETE PODIUM
PIPE SLEEVE THRU
CONCRETE PODIUM
PRESSURE REDUCING
VALVE INLET PSI 5 - OUTLET PSI 3
DIRT
LEG
3/4" STEEL PIPING
SHEER WALL
2" SDR 11 PE
3408/2406 PIPING
1 1/2" STEEL PIPING SECURED TO THE
BACKSIDE OF THE CONCRETE
COLUMN
N
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:2
:0
A
M
P101
ELP
RB
AFRH-041
PLUMBING PLANS
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
NTS
PLUMBING NEW WORK PLAN
NTS
PLUMBING OVERALL SITE PLAN
12" = 1'-0"
GENERATOR GAS CONNECTION DETAIL
PLUMBING GENERAL NOTES
* FIELD VERIFY LOCATION AND INVERTS OF EXISTING SITE UTILITIES PRIOR TO INSTALLATION.
NO DATE REVISION
1 07.25.25 ADDENDUM #1
AST-2 DIESEL MAIN STORAGE 25,000 10 43'-7" HIGHLAND TANK 25000FGCYL120 ALL
AST-1 DIESEL MAIN STORAGE 25,000 10 43'-7" HIGHLAND TANK 25000FGCYL120 ALL
Manufacturer Model Notes
EQUIPMENT
NAME
FUEL TYPE TANK TYPE
CAPACITY
(GAL)
DIAMETER
(FT)
LENGTH
Basis of Design
ABOVEGROUND STORAGE TANK SCHEDULE
25-JUL-25
ELECTRICAL SYMBOLS LEGEND
1 KEYED NOTE
REFER TO KEYNOTE SCHEDULE ON DRAWING
SINGLE POLE SWITCH
TWO POLE, SINGLE POLE SWITCH
3-WAY SWITCH
4-WAY SWITCH
J J JUNCTION BOX
PANELBOARD
REFER TO PANEL SCHEDULES FOR ADDITIONAL INFORMATION
PULL BOX
DIMENSIONS AS INDICATED ON DRAWINGS
DUPLEX WALL RECEPTACLE
NEMA 5-20R UNLESS NOTED OTHERWISE
QUADRAPLEX WALL RECEPTACLE
NEMA 5-20R UNLESS NOTED OTHERWISE
BRANCH CIRCUITS TO DEVICES OR EQUIPMENT
- SHORT TICKS INDICATE HOTS
- LONG TICK INDICATES NEUTRAL
- NO TICK MARKS INDICATES ONE HOT AND ONE NEUTRAL
INCLUDE A GROUND CONDUCTOR IN ALL CONDUITS AND RACEWAYS
PER NEC REQUIREMENTS. GROUND CONDUCTORS ARE NOT
INDICATED WITH TICK MARKS.
REFER TO PANEL SCHEDULES FOR WIRE AND CONDUIT SIZES AND
QUANTITIES.
HOME RUN TO INDICATED PANEL AND CIRCUIT NUMBER(S)
- SHORT TICKS INDICATE HOTS
- LONG TICK INDICATES NEUTRAL
- NO TICK MARKS INDICATES ONE HOT AND ONE NEUTRAL
INCLUDE A GROUND CONDUCTOR IN ALL CONDUITS AND RACEWAYS
PER NEC REQUIREMENTS. GROUND CONDUCTORS ARE NOT
INDICATED WITH TICK MARKS.
REFER TO PANEL SCHEDULES FOR WIRE AND CONDUIT SIZES AND
QUANTITIES.
3P-30AF/NF SAFETY DISCONNECT SWITCH (NON-FUSED)
NUMBER OF POLES AND FRAME SIZE AS INDICATED
SAFETY DISCONNECT SWITCH (FUSED)
NUMBER OF POLES, FRAME SIZE, AND FUSE SIZE AS INDICATED
3P-30AF/30
1-PHASE MOTOR
EQUIPMENT TAG AS INDICATED
GREY SYMBOLS INDICATE ELEMENT EXISTING TO REMAIN
3-PHASE MOTOR
EQUIPMENT TAG AS INDICATED
DASHED GREY LINES AROUND EQUIPMENT INDICATE NEC
REQUIRED CLEARANCES
DASHED SYMBOLS INDICATE ELEMENT TO BE DEMOLISHEDSOLID HATCHING OVER LIGHTING FIXTURES INDICATES FIXTURE
SHALL BE POWERED VIA LIFE SAFETY CIRCUIT AND RELAYED VIA
UL924 LISTED DEVICE FOR FULL BRIGHTNESS DURING FIRE ALARM
OR NORMAL POWER LOSS.
REFER TO LIGHTING FIXTURE SCHEDULE FOR ASSOCIATED
SYMBOL FOR EACH FIXTURE TYPE. EXIT SIGN, CEILING MOUNTED
FACES, CHEVRONS, AND ORIENTATION AS INDICATED ON DRAWINGS
EXIT SIGN, FLAG MOUNTED
FACES AND CHEVRONS AS INDICATED ON DRAWINGS
EXIT SIGN, WALL MOUNTED
CHEVRONS AS INDICATED ON DRAWINGS
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER, AIR CONDITIONER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
A.F.F. ABOVE FINISHED FLOOR
A.F.G. ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT, CENTER LINE
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCOFM CLINICAL CENTER OFFICE OF FACILITY
MANAGEMENT
CCTV CLOSED CIRCUIT TELEVISION
CIT CENTER FOR INFORMATION TECHNOLOGY
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DDCM DIVISION OF DESIGN AND CONSTRUCTION
MANAGEMENT
DEPT DEPARTMENT
DET DETAIL
DEP DIVISION OF ENVIRONMENTAL
PROTECTION
DFOM DIVISION OF FACILITIES OPERATIONS AND
MAINTENANCE
DFM DIVISION OF THE FIRE MARSHAL
DFP DIVISION OF FACILITIES PLANNING
DFS DIVISION OF FACILITIES STEWARDSHIP
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DOHS DIVISION OF OCCUPATIONAL HEALTH AND
SAFETY
DPR DAMPER
DPSM DIVISION OF PHYSICAL SECURITY
MANAGEMENT
DRS DIVISION OF RADIATION SAFETY
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DTR DIVISION OF TECHNICAL RESOURCES
DWG, DWGS DRAWING, DRAWING(S)
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACNET FACILITIES NETWORK SYSTEM
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FT FEET
FU FUSE
FSS FUSED SAFETY SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFCI, GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HAND-OFF-AUTOMATIC
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
HWP HYDRONIC WATER PUMP
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IN INCHES
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT-HOUR
LOC LOCATE, LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NFSS NON-FUSED SAFETY SWITCH
NIC NOT IN CONTRACT
NIH NATIONAL INSTITUTES OF HEALTH
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OHPE OFFICE OF HOSPITAL PHYSICAL ENVIRONMENT
OL OVERLOADS
P PLATE
PA PUBLIC ADDRESS
PB PULL BOX, PUSH BUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PO PROJECT OFFICER
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
ELECTRICAL ABBREVIATIONS LIST
PWR POWER
QTY., QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP. TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UEB UTILITIES ENGINEERING BRANCH
UG UNDERGROUND
UH UNIT HEATER
U.N.O. UNLESS NOTED OTHERWISE
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV UNIT VENTILATOR OR ULTRAVIOLET
V VOLT(S)
VA VOLT-AMPERE(S)
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT(S)
W/ WITH
WAO WORK AREA OUTLET
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
@ AT
' FEET
" INCHES
# NUMBER
Ø, Φ PHASE
GENERAL:
THIS PROJECT INCLUDES PHASED CONSTRUCTION FOR THE SCOPE OF WORK. REFER TO ALL MEP DRAWINGS FOR DETAILED
INFORMATION.
THE CONTRACTOR SHALL PROVIDE A COMPLETE PROJECT PHASING PLAN AND SCHEDULE USING THE PHASING INTENT ON THE CONTRACT DOCUMENTS AS A BASELINE. THE PHASING PLAN AND SCHEDULE SHALL BE INCLUSIVE OF ALL TRADES AND INDICATED ALL ANTICIPATED IMPACTS TO OPERATIONS, INCLUDING PLANT SHUTDOWNS, PIPE FREEZES, ETC. THE PLAN AND SCHEDULE SHALL BE
SUBMITTED TO THE OWNER AND EOR FOR REVIEW PRIOR TO THE START OF ANY WORK.
1. PHASE 1
1.1. DEMOLISH EXISTING EG1 AND ASSOCIATED EQUIPMENT
1.2. INSTALL NEW EG1 DIESEL ENGINE GENERAOTR AND ASSOCIATED EQUIPMENT
1.3. INSTALL LOAD BANK
1.4. INSTALL GEN-WP & MTS-WP
1.5. COMPLETE CX LEVEL 4 FOR EG1, GEN-WP & MTS-WP
2. PHASE 2
2.1. DEMOLISH EXISTING EG2 AND ASSOCIATED EQUIPMENT
2.2. INSTALL NEW EG2 NATURAL GAS ENGINE GENERAOTR AND ASSOCIATED EQUIPMENT
2.3. COMPLETE CX LEVEL 4 FOR EG2
3. PHASE 3
3.1. DEMOLISH EXISTING FUEL RECIRCULATION SYSTEM
3.2. INSTALL NEW FUEL POLISHING SYSTEM
3.3. COMPLETE CX LEVEL 4 FOR FUEL POLISHING SYSTEM
PHASING NOTES
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:4
:4
A
M
E001
TZ
DF
AFRH-041
ELECTRICAL SYMBOLS,
ABBREVIATIONS, AND
GENERAL NOTES
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
ELECTRICAL DRAWING INDEX
Sheet Number Sheet Name
E001 ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES
E101 ELECTRICAL PLAN - LOWER LEVEL OF PLATFORM
E102 ELECTRICAL PLANS
E103 ELECTRICAL WORK - MECHANICAL 1032
E201 PARTIAL EXISTING ELECTRICAL ONE-LINE DIAGRAM
E202 PARTIAL NEW ELECTRICAL ONE-LINE DIAGRAM
E301 ELECTRICAL DETAILS
ELECTRICAL GENERAL NOTES
1 THE FOLLOWING GENERAL NOTES AS LISTED BELOW SHALL APPLY TO ALL ELECTRICAL REQUIREMENTS AS INDICATED ON ALL E SERIES CONTRACT
DRAWINGS.
2 THE CONTRACTOR IS RESPONSIBLE FOR THE ENTIRE DOCUMENT SET. I.E. IF WORK IS SHOWN ON OTHER DRAWINGS AS "BY CONTRACTOR," THE
CONTRACTOR IS RESPONSIBLE FOR THAT WORK.
3 DRAWINGS FOR THIS WORK ARE DIAGRAMMATIC AND INTENDED TO CONVEY THE EXTENT, GENERAL ARRANGEMENT AND LOCATIONS OF THE WORK.
BECAUSE OF THE SCALE OF THE DRAWINGS, CERTAIN BASIC ITEMS SUCH AS ACCESS PANELS, CONDUITS, CABINET SIZES, PENETRATION SLEEVES, PULL BOXES, BACKBOXES AND JUNCTION BOXES MAY NOT BE SHOWN. INCLUDE ALL ITEMS WHERE REQUIRED BY CODE, MANUFACTURER AND
RELATED SPECIFICATION SECTIONS FOR THE PROPER INSTALLATION OF ALL WORK.
4 DUE TO SCALE OF THE DRAWINGS, ALL ELECTRICAL DEVICE SYMBOLS ARE SHOWN ON DRAWINGS AS CLOSE AS POSSIBLE TO THEIR INTENDED LOCATION. CONTRACTOR SHALL COORDINATE IN THE FIELD THE PROPER INSTALLATION OF ALL EQUIPMENT, DEVICES, CONTROLS AND CONDUITS.
REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL REQUIREMENTS.
5 COORDINATE WITH ALL TRADES AND SYSTEM INTEGRATORS ANY CONDITIONS RELATED TO THE INSTALLATION OF ALL SYSTEMS. THE CONTRACTOR SHALL COORDINATE WITH THE APPROPRIATE TRADE ALL INSTALLATION REQUIREMENTS IMPACTING THE PLACEMENT OF ALL SYSTEM COMPONENTS
TO THE SATISFACTION OF ALL CONCERNED TRADES.
6 COORDINATE EXACT LOCATION(S) OF ALL DATA AND TELEPHONE OUTLETS, ELECTRICAL RECEPTACLES WITH THE ARCHITECTURAL PLANS, FURNITURE PLANS AND ALL AFFECTED TRADES PRIOR TO INSTALLATION.
7 ALL CONDUITS SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH NFPA 70 AND PROJECT SPECIFICATIONS. ALL CONDUITS SHALL BE A MINIMUM
OF 3/4" UNLESS OTHERWISE NOTED.
8 PROVIDE ALL EQUIPMENT CLEARANCES IN ACCORDANCE WITH NEC REQUIREMENTS. ARRANGE EQUIPMENT TO FACILITATE UNRESTRICTED ACCESS FOR MAINTENANCE AND SERVICE AROUND ALL EQUIPMENT, COMPONENTS AND/OR CABLE TERMINATIONS.
9 WHERE EQUIPMENT AND/OR JUNCTION BOXES ARE INSTALLED ABOVE FINISHED CEILINGS, THE CONTRACTOR SHALL PROVIDE ACCESS HATCHES LISTED FOR THE INTENDED APPLICATION. ACCESS HATCHES SHALL BE LOCATED SO THAT SERVICE ACCESS TO THE EQUIPMENT AND/OR JUNCTION
BOXES IS UNIMPEDED.
10 ALL PENETRATIONS OF WALLS AND/OR FLOORS SHALL BE FIRE STOPPED IN ACCORDANCE WITH THE ASTM AND NFPA REQUIREMENTS. REFER TO RELATED SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION. INSTALLATION OF FIRE-STOPS SHALL BE PERFORMED BY APPLICATOR/INSTALLER QUALIFIED AND TRAINED BY THE MANUFACTURER. INSTALLATION SHALL BE PERFORMED IN STRICT ACCORDANCE WITH
MANUFACTURER'S DETAILED INSTALLATION PROCEDURES.
11 ALL EQUIPMENT ENCLOSURES LOCATED OUTSIDE OR IN ALL AREAS WITH HIGH MOISTURE OR A RELATIVE HUMIDITY OF 75% OR GREATER SHALL BE
NEMA 4X STAINLESS STEEL AND RATED FOR THAT APPLICATION.
12 ALL INTERIOR AND/OR EXTERIOR COMPONENTS, DEVICES OR SYSTEMS EQUIPMENT EXPOSED TO THE GENERAL POPULATION SHALL BE INSTALLED IN SECURED EQUIPMENT ENCLOSURES WITH TAMPER SWITCHES AND INSTALLED IN SUCH A MANNER THAT RESISTS TAMPERING AND/OR REMOVAL
WITHOUT THE USE OF SPECIALIZED TOOLS.
13 FOR EQUIPMENT INSTALLATIONS REQUIRING COORDINATION WITH OTHER TRADES, THE CONTRACTOR SHALL PROVIDE ALL TEMPLATES, BACKBOXES AND EQUIPMENT ANCHOR BOLTS FOR MOUNTING OR FLUSH MOUNTING PREPARATION (E.G. PEDESTALS OR OTHER DEVICES REQUIRING MOUNTING ON WALLS, CONCRETE PADS OR OTHER MATERIALS). COORDINATE DELIVERY OF TEMPLATES AND EQUIPMENT WITH ALL AFFECTED CONTRACTORS.
14 ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (LATEST VERSION BEING ENFORCED) AND ALL OTHER APPLICABLE CODES AND STANDARDS BEING ENFORCED BY THE AUTHORITY HAVING JURISDICTION.
15 THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS OR INSTRUCTIONS FOR CONSTRUCTION SAFETY. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR ANY WORKMAN'S OR TRANSIENT'S SAFETY, OR FOR THE ADEQUACY OF EQUIPMENT, BUILDING COMPONENTS, WORK AIDS, OR ANY NECESSITY TO WORK ON ENERGIZED ELECTRICAL COMPONENTS. FURTHER, NO SUPERINTENDENCE IS INCLUDED OR IMPLIED.
16 ALL SYSTEMS AND EQUIPMENT SHALL BE INSTALLED AND WIRED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS.
17 ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE TESTED AND LISTED BY A NATIONALLY RECOGNIZED TESTING
LABORATORY.
18 THE CONTRACTOR SHALL COORDINATE CONDUIT ROUTING (PLAN AND ELEVATION) WITH THE LIGHTING (NEW AND EXISTING), CEILING ELEVATION, STRUCTURE, DUCTWORK, PIPING, ETC. REQUIRED FOR THE COMPLETION OF THE PROJECT, PRIOR TO INSTALLATION.
19 THE CONTRACTOR SHALL SECURE AND PROTECT THE BUILDING AND/OR WORK AREA WITH FIRE RETARDANT TEMPORARY PLYWOOD PARTITIONS (WITH LOCKING DOORS), ETC. CLOSE ALL EXISTING OPENINGS AS REQUIRED. COORDINATE THIS WORK WITH THE OWNER'S REPRESENTATIVE PRIOR TO STARTING. IF TEMPORARY PARTITIONS IMPEDE THE FLOW OF EGRESS TO REQUIRED EGRESS DOORS AND STAIRS, THE CONTRACTOR
SHALL PROVIDE EXIT SIGNS, AND SIGNAGE INDICATING SUCH.
20 THE CONTRACTOR SHALL CAULK ALL JOINTS BETWEEN METAL FRAMES AND EXISTING CONDITIONS. THIS APPLIES TO BOTH INTERIOR AND EXTERIOR
INSTALLATIONS.
21 THE DIMENSIONS SHOWN ON THE DRAWINGS ARE FOR THE CONVENIENCE OF THE CONTRACTOR ONLY. VERIFY ALL DIMENSIONS IN THE FIELD PRIOR
TO PERFORMING ANY WORK.
22 THE CONTRACTOR SHALL INSTALL ALL CONDUITS CONCEALED UNLESS NOTED OTHERWISE. EXPOSED CONDUIT SHALL ONLY BE INSTALLED IN
CHASES, EXPOSED CEILING AREAS, JANITOR CLOSETS, AND MECHANICAL/ELECTRICAL ROOMS.
23 ALL ELECTRICAL EQUIPMENT SHALL BE GROUNDED AND/OR BONDED PER THE REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. PROVIDE ALL
GROUNDING AND/OR BONDING COMPONENTS NOT EXPLICITLY SHOWN ON THE DOCUMENTS.
24 THE CONTRACTOR SHALL PROVIDE UPDATED TYPED PANELBOARD DIRECTORIES, INDICATING THE LOADS SERVED BY THE RESPECTIVE PANELS.
AMEND AS REQUIRED FOR AS-BUILT CONDITIONS. PROVIDE ELECTRONIC VERSIONS OF THE PANELBOARD SCHEDULES FOR FUTURE USE BY THE
OWNER.
25 THE CONTRACTOR SHALL REVIEW THE WORK REQUIRED WITH THE APPLICABLE UTILITY COMPANIES SERVING THE PROJECT. ALL WORK PERFORMED SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE INDIVIDUAL UTILITY COMPANIES.
26 THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE OWNER PRIOR TO STARTING ALL PHASES OF THE PROJECT. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER WHAT WORK, IF ANY, HAS TO BE COMPLETED DURING SECOND OR THIRD SHIFT.
27 THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY POWER CONNECTIONS TO KEEP AREAS UP AND OPERATIONAL DURING THE CONSTRUCTION.
THE CONTRACTOR SHALL COORDINATE THESE REQUIREMENTS WITH THE OWNER.
28 THE VERBIAGE ON THE DRAWINGS INDICATING TYPES OF MATERIALS TO BE ENCOUNTERED IS INTENDED TO AID THE ELECTRICAL CONTRACTOR IN UNDERSTANDING THE VARIOUS CONDITIONS LIKELY TO BE ENCOUNTERED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING
QUANTITIES OF MATERIALS REQUIRED TO COMPLETE THE PROJECT.
29 THE LOCATIONS OF EXISTING UTILITIES, STRUCTURE, AND OTHER CONDITIONS SHOWN ON THE PLANS ARE APPROXIMATE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY AND REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BEGINNING ANY WORK.
30 FURNISH AND INSTALL ALL REQUIRED LINTELS AND SLEEVES. ALL CONDUITS SHALL HAVE SLEEVES INSTALLED. ALL SLEEVES INSTALLED THROUGH
EXTERIOR WALLS SHALL HAVE LINK SEALS INSTALLED.
31 THE CONTRACTOR SHALL MAINTAIN THE BUILDING IN WEATHERTIGHT AND WATERPROOF CONDITION THROUGHOUT THE DURATION OF THEIR WORK.
DO NOT LEAVE HOLES THROUGH WALLS AND/OR ROOFS OPEN TO THE ELEMENTS WHEN NO WORK IS OCCURRING IN THOSE AREAS.
32 THE CONTRACTOR SHALL GENERATE A DETAILED METHOD OF PROCEDURE (MOP) DOCUMENT INDICATING HOW HE/SHE INTENDS TO PERFORM EACH STEP IN THE PROJECT. THIS MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF PRIOR TO STARTING THE PROJECT.
THE MOP MAY BE REVISED BASED ON CHANGES IN THE PROJECT CONSTRUCTION, ETC. AT ALL POINTS IN THE PROJECT THE OWNER SHALL BE MADE AWARE OF CHANGES TO THE MOP, AND A REVISED MOP SHALL BE PRESENTED TO THE OWNER AND ENGINEER FOR SIGN OFF.
33 PROVIDE ALL JUNCTION BOXES, PULL BOXES AND OTHER PULL POINTS AS REQUIRED FOR EASE OF PULLING AND TO MEET THE MAXIMUM NUMBER OF BENDS PER NEC REQUIREMENTS FOR A CODE COMPLIANT INSTALLATION. NOT ALL CONDUITS, PULL BOXES AND OTHER RACEWAY ITEMS ARE INDICATED ON THE DOCUMENTS. THE CONTRACTOR SHALL PROVIDE A COMPLETE RACEWAY SYSTEM MEETING THE REQUIREMENTS OUTLINED IN THE DRAWINGS AND SPECIFICATIONS. ALL JUNCTION BOXES AND OTHER PULL POINTS SHALL BE ACCESSABLE.
34 DISTRIBUTION EQUIPMENT SHALL BE AIC RATED, AND ANY CIRCUIT BREAKERS SELECTED AND SET BASED ON THE OUTCOME OF THE CONTRACTORS OVERCURRENT PROTECTIVE DEVICE COODINATION STUDY. STUDY SHALL INCLUDE ALL ELEMENTS OF THE EXISTING AND NEW DISTRIBUTION SYSTEM REQUIRED TO ACCURATELY SIZE AND RATE THE NEW EQUIPMENT ADDED AS PART OF THIS PROJECT.
35 ARC FLASH LABELS SHALL BE PROVIDED TO ALL NEW EQUIPMENT BASED ON THE OUTCOME OF THE CONTRACTOR'S ARC FLASH STUDY. ANY EQUIPMENT MODIFIED AS PART OF THIS PROJECT SHALL ALSO BE INCLUDED IN THE ARC FLASH STUDY AND SHALL BE RELABELED AS REQUIRED.
36 THESE DRAWINGS DO NOT INDICATE ALL CONDUITS INTERCONNECTING EQUIPMENT, AND WHERE CONDUITS ARE INDICATED, THE ROUTING IS APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR THE ROUTING AND INSTALLATION OF ALL CONDUIT IN COORDINATION WITH OTHER TRADES
AND EXISTING CONDITIONS.
37 MULTIWIRE BRANCH CIRCUITS ARE NOT PERMITTED. ALL SINGLE POLE BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. SHARING OF NEUTRALS IS PROHIBITED. ALL CIRCUITS SHALL CONTAIN AN INDIVIDUAL GROUND WIRE. USE OF THE CONDUIT SYSTEM FOR THE GROUND PATH IS
PROHIBITED.
38 MULTIPLE SMALL 20A/1P BRANCH CIRCUITS MAY SHARE A SINGLE CONDUIT PROVIDED THE CONTRATOR UPSIZES THE WIRES (INCLUDING THE
GROUND) AND CONDUIT AS REQUIRED PER NEC.
39 THE COMPLETE BRANCH WIRING SYSTEM IS NOT SHOWN ON THE DRAWINGS. AN ABBREVIATED FORMAT IS USED TO INDICATE WHICH FIXTURES/DEVICES ARE CONNECTED TO A COMMON CIRCUIT OR SWITCH. THIS IS PROVIDED AS A GUIDE TO THE CONTRACTOR TO ILLUSTRATE
CIRCUITS AND CONTROL INTENT. ACTUAL WIRING MAY DIFFER DUE TO FIELD CONDITIONS. COLOR CODING OF WIRES SHALL BE AS PER NEC.
40 PROVIDE 120V 20A 5-20R RECEPTACLE AT ALL FAN COIL UNITS FOR CONDENSATE PUMP POWER AND HOT WATER RECIRCULATING PUMPS, WHETHER SHOWN ON PLANS OR NOT. RECEPTACLE IS TO BE CONNECTED TO NEAREST 120V RECEPTACLE CIRCUIT.
41 PROVIDE 120V CONNECTION TO ALL MOTORIZED DAMPERS INDICATED ON MECHANICAL PLANS, WHETHER SHOWN ON DIVISION 26 DRAWINGS OR NOT. FIRE/SMOKE DAMPER CIRCUITS ARE TO BE PROVIDED FROM EMERGENCY (LIFE SAFETY) BRANCH PANEL. MOTORIZED DAMPERS WITHIN THE SAME AREA CAN BE CIRCUITED TO THE SAME CIRCUIT (I.E. DEDICATED CIRCUIT IS NOT REQUIRED).
42 DURING THE BIDDING PROCESS, THE ELECTRICAL CONTRACTOR SHALL REVIEW DRAWINGS AND SPECIFICATIONS OF ALL OTHER TRADES (ARCHITECTURAL, SITE/LANDSCAPING, HVAC, PLUMBING, AND SPECIALTY TRADES). ALL ITEMS REQUIRING POWER INDICATED ON THESE DRAWINGS BUT NOT INDICATED ON THE ELECTRICAL DRAWINGS SHALL BE CONSIDERED A PART OF THE ELECTRICAL CONTRACTOR’S WORK. THIS WORK SHALL
BE INSTALLED AS PER NEC REQUIREMENTS AT NO ADDITIONAL COST TO THE OWNER.
ELECTRICAL DEMOLITION GENERAL NOTES
1 CONTRACTOR SHALL PROVIDE A MINIMUM TWO WEEKS WRITTEN NOTICE PRIOR TO ANY SHUT DOWN. NOTICE IS
TO INCLUDE BUT IS NOT LIMITED TO THE LOCATION, PANELS AND DURATION OF SHUT DOWN.
2 OWNER SHALL HAVE RIGHT OF FIRST REFUSAL TO ANY EQUIPMENT, DEVICES, ETC. DEMOLISHED FROM
RENOVATION AREA PRIOR TO DISPOSAL.
3 MAINTAIN CONTINUITY OF SERVICE TO AREAS OUTSIDE THE PROJECT BOUNDARY. PATCH AND REPAIR ALL CIRCUITS CUT OFF DURING DEMOLITION BY WIRING METHODS COMPATIBLE WITH THE EXISTING INSTALLATION.
4 THE ELECTRICAL CONTRACTOR SHALL REVIEW THE DRAWINGS OF ALL OTHER TRADES IN THIS CONTRACT. THE REMOVAL OF ELECTRICAL SERVICE TO ALL EQUIPMENT IDENTIFIED ON OTHER TRADE DRAWINGS IS THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
5 EXERCISE EXTREME CAUTION WHEN REMOVING/ RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES THAT MAY BE
CONNECTED TO THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.
NO DATE REVISION
1 07.25.25 ADDENDUM #1
07/25/2025
EXISTING
WELL PUMP
MECHANICAL ROOM 1032
EXISTING WELL PUMP
FEEDER TO PANEL 1HAM
INTERCEPT AND
ROUTE TO MTS
PROPANE GENERATOR
MTS - MANUAL TRANSFER SWITCH
E101
A101
A101
A101
A101
LOAD BANK
ON 6" CONCRETE PAD
A101
A101
A101
A101
FRONT2
AIR INTAKE
N
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:4
:4
A
M
E101
TZ
DF
AFRH-041
ELECTRICAL PLAN -
LOWER LEVEL OF
PLATFORM
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
NTS
OVERALL SITE PLAN - LOWER LEVEL
1/8" = 1'-0"
ELECTRICAL NEW WORK PLAN - LOWER LEVEL
POWER PLAN KEYNOTES
NO DATE REVISION
1 07.25.25 ADDENDUM #1
2MW AVTRON MODEL 4900 LV LOAD BANK WITH THE MODEL 9800 MV
TRANSFORMER CONFIGURATION. MAINTAIN 6' HORIZONTAL CLEARANCE
FOR AIR INTAKE AND 8' HORIZONTAL CLEARANCE FOR AIR EXHAUST.
OUTDOOR, NON-WALKIN, NEMA 3R, SQUARE D MV LOAD BANK
SWITCHGEAR.
1" = 100'-0"
J
J
J
J J
J
GFI
WP
GFI
WP
J J
2.25MW 13.8kV, 3PH, 4W
DIESEL
GENERATOR
"EG1"
2.25MW 13.8kV, 3PH, 4W
DIESEL
GENERATOR
"EG2"
FUEL
RECIRCULATION
SYSTEM
25,000 GALLON
DIESEL GUEL
TANK
25,000 GALLON
DIESEL GUEL
TANK
6000 kVA
UTILITY
TRANSFOR
MER
(EXISTING
TO REMAIN)
150 kVA FIRE PUMP
TRANSFORMER
(EXISTING TO
REMAIN)
NEUTRAL
GROUNDING
RESISTANCE
(EXISTING TO
REMAIN)
MAIN
PARALLELING
SWITCHGEAR
"MSG" 1200A,
3PH, 4W
15kV METAL
CLAD WALK-IN
SWITCHGEAR
(EXISTING TO
REMAIN)
6 MVA UTILITY
TRANSFORMER
(EXISTING TO
REMAIN)
150 kVA FIRE PUMP
TRANSFORMER
(EXISTING TO
REMAIN)
NEUTRAL GROUNDING
RESISTANCE
(EXISTING TO REMAIN)
MAIN PARALLELING
SWITCHGEAR "MSG"
1200A, 3PH, 4W
15kV METAL CLAD WALK-
IN SWITCHGEAR
(EXISTING TO REMAIN)
NEW 2MW 13.8kV, 3PH, 4W
DIESEL GENERATOR "EG1"
NEW 2MW 13.8kV, 3PH, 4W
NATURAL GAS GENERATOR "EG2"
NEW FUEL
POLISHING
SYSTEM
EARLY STREAMER
EMISSIONS (ESE)
LIGHTNING PROTECTION
POLE (REFER TO DETAIL 1
/E301). ANCHOR MOUNTING
BASE TO TOP OF THE
CONCRETE PLATFORM
DOWNLEAD
CONDUCTORS TO
GROUND ARRAYS
GROUND ROD
ARRAYS
(TYPICAL)
GROUND ROD
ARRAYS
(TYPICAL)
EG2-1
EG2-3
EG2-2
EG2-4,6
EG2-5,7
EG2-8
EG1-1
EG1-3
EG1-2
EG1-4,6
EG1-5,7
EG1
EG2
EG1-9,11
P-1 P-2
P-3
EG1-8,10 EG1-12,14
A101
A101
A101
A101
EG1 REMOTE
ANNUNCIATOR
EG2 REMOTE
ANNUNCIATOR
DIESEL FUEL
TANK #1
FILL
STATION
DIESEL FUEL
TANK #2
E102
E102
EXISTING
WELL PUMP
MECHANICAL ROOM 1032
EXISTING WELL PUMP
FEEDER TO PANEL 1HAM
INTERCEPT AND
ROUTE TO MTS
PROPANE GENERATOR ON 6" PAD
MTS - MANUAL TRANSFER SWITCH
A101
A101
A101
A101
N
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:4
:4
A
M
E102
TZ
DF
AFRH-041
ELECTRICAL PLANS
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
NTS
ELECTRICAL DEMOLITION PLAN
NTS
ELECTRICAL NEW WORK PLAN
NTS
OVERALL SITE PLAN - LEVEL 1
POWER PLAN KEYNOTES
NO DATE REVISION
1 07.25.25 ADDENDUM #1
DISCONNECT FEEDER TO LOAD CENTER INSIDE GENERATOR ENCLOSURE.
DISCONNECT POWER FROM EXISTING FUEL RECIRCULATING SYSTEM.
SEAL EXISTING STUB-UP OPENINGS WITH A STAINLESS-STEEL COVER
PLATE, SECURELY FASTENED AND WEATHER-RESISTANT, TO MAINTAIN
ENCLOSURE INTEGRITY AND PREVENT MOISTURE OR DEBRIS INTRUSION.
COORDINATE EXACT STUB-UP LOCATIONS AND DIMENSIONS WITH THE
GENERATOR MANUFACTURER PRIOR TO CORING OR CUTTING OPENINGS IN
THE ENCLOSURE FOR ELECTRICAL CONDUIT ENTRIES. CONFIRM
COMPATIBILITY WITH MANUFACTURER’S RECOMMENDED ENCLOSURE
PENETRATION GUIDELINES.
EXISTING LIGHTNING PROTECTION SYSTEM SHALL BE INTEGRATED WITH
THE NEW LIGHTNING PROTECTION SYSTEM.
PROVIDE CAT6 CABLE BETWEEN GENERATOR ENCLOSURE AND
ASSOCIATED GENERATOR ANNUNCIATOR IN 3/4" CONDUIT.
PROPANE GENERATOR TO BE CONNECTED TO THE OWNER PROVIDED
PORTABLE PROPANE TANK WHEN NEEDED.
REFER TO STRUCTURAL DRAWINGS FOR PLATFORM LAYOUT.
1/8" = 1'-0"
1/8" = 1'-0"
1" = 100'-0"
J J
GFI
WP
NEW PROPANE
GENERATOR
NEW MANUAL
TRANSFER
SWITCH
1LAM-15
1LAM-13
1LAM-17
1LAM-16
MINIMUM
FROM
FACE OF BUILDING
10' - 0"
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:4
:4
A
M
E103
TZ
DF
AFRH-041
ELECTRICAL WORK -
MECHANICAL 1032
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
1/8" = 1'-0"
ELECTRICAL WORK - MECHANCIAL 1032
NO DATE REVISION
1 07.25.25 ADDENDUM #1
125A
WELL
PUMP
MTS-WP
125 A
(25000 WSR)
G GEN-WP
GGEN - EG1
2000kW
GGEN - EG2
2000kW
FIRE PUMP
EXISTING TO REMAIN
125 GENERATOR
MOUNTED
13.2 KV 3-PHASE, 4-WIRE
DIESEL FUEL
13.2 KV 3-PHASE, 4-WIRE
NATURAL GAS
480/277V, 3-PHASE, 4-WIRE
NEMA 3R ENCLOSURE
PROPANEGENERATOR FEEDER
3 - #1 AWG & #6 AWG GROUND IN 2" CONDUIT
2 2
2 MVA LOAD BANK
NEMA 3R ENCLOSURE
1 1
1200AF
175AT
DISTRIBUTION PANEL 1HAM, 400A, 480Y/277V, MLO
MECHANICAL ROOM 1032 - EXISTING TO REMAIN
PARALLELING SWITCHGEAR - MSG
13.2KV 1200A, 3-PHASE, 4-WIRE
6 MVA TRANSFOREMER
22.86 KV Δ : 13.2KV WYE
Z = 7.5%
25 KV PRIMARY
LOAD INTERUPPER
FUSIBLE SWITCH
50/51 27/59
87 81 3286
40 90
15KV METALCALD SWITCHGEAR
1200A, 3-PHASE, 4-WIRE
EXISITING TO REMAIN
AUTOTRANSFER
CONTROL
250A
1200AF
350AT
1200AF
350AT
UTILITY FEED
1200AF
350AT
1200AF
175AT
1200AF
175AT
NGR NGR
150KVA
13.2KV Δ : 480V Δ
Z = 4.5%
15 KV LOAD
INTERUPPER
FUSIBLE SWITCH
EXISTING TO REMAINEXISTING TO REMAIN
100kW/125kVA
3 3
4 4
LOAD BANK SWITCHGEAR
13.2KV 1200A, 3-PHASE, 4-WIRE
2 MVA TRANSFORMER
13.2kV WYE PRI
480V WYE SEC
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:4
:4
A
M
E202
TZ
DF
AFRH-041
PARTIAL NEW
ELECTRICAL ONE-LINE
DIAGRAM
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
NTS
PARTIAL NEW ELECTRICAL ONE-LINE DIAGRAM
NO DATE REVISION
1 07.25.25 ADDENDUM #1
4 - #1/0 (15kV) & 1 - #4 AWG (15kV) GROUND IN 4" CONDUIT
133% INSULATION LEVEL FOR 15KV CABLE, MV-105
1 - #2 (15kV) IN 1.5" CONDUIT.
133% INSULATION LEVEL FOR 15KV CABLE, MV-105
1 - #6 AWG (15kV) GROUND IN 1.5" CONDUIT.
133% INSULATION LEVEL FOR 15KV CABLE, MV-105
NEUTRAL GROUND RESISTOR (NGR) IS EXISTING TO REMAIN.
REFER TO GENERATOR SCHEDULE ON DRAWING E301 FOR ADDITIONAL
DETAILS.
PROVIDE TAP PLATE IN PARALLELING SWITCHGEAR - MSG FOR LOAD BANK
SWITCHGEAR CONNECTION.
KEYNOTES
Generator Schedule
Equipment Name
Location Fuel Type Rating Type
Rating kW
Rating
KVA
Voltage Rating
Frequency (Hz)
Phases Wire RPM Enclosure
Enclosure Dimensions Basis of Design
Length (in) Width
(in) Height
(in) Manufacturer Model Notes
GEN-EG1 Elevated Platform Diesel Standby 2000 2500 13.2 kV 60 3 4 1800 Level II, Hurricane
Rated 384 144 158 Caterpillar 3516C Level 1, Type 10, Class 96
GEN-EG2 Elevated Platform Natural Gas Standby 2000 2500 13.2 kV 60 3 4 1800 Level II, Hurricane
Rated 462 144 158 Caterpillar G3520 Level 1, Type 10, Class 96
GEN-WP
Outside of Mechanical
Room 1032 Propane Standby 100 125 480 V 60 3 4 1800 Level II, NEMA 3R 129.4 40 56.2 Generac SG100 Level 1, Type 10, Class 96
EX GEN-EG1 Elevated Platform Diesel Standby 2250 2812.5 13.2 kV 60 3 4 1800 306 140 - Kohler 2250REOZDC Level 1, Type 10, Class 96
EX GEN-EG2 Elevated Platform Diesel Standby 2250 2812.5 13.2 kV 60 3 4 1800 306 140 - Kohler 2250REOZDC Level 1, Type 10, Class 96
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
THIS SQUARE APPEARS 1/2"x1/2"
ON FULL SIZE SHEETS
CLIENT:
1655 FORT MYER DRIVE
SUITE 830
ARLINGTON,VA 22209
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
G u lf p o rt
G e n e ra to rs /A
F R
H -0
G u lf G e n
M E
P
R
.r v t
/2
/2
:4
:5
A
M
E301
TZ
DF
AFRH-041
ELECTRICAL DETAILS
AFRH GULFPORT
GENERATOR
REPLACEMENT
1800 Beach Dr, Gulfport, MS 39507
ARMED FORCES
RETIREMENT HOME
GULFPORT, MS
06.30.25
CONSTRUCTION BID
DOCUMENTS
1800 Beach Dr, Gulfport, MS 39507
NOT TO SCALE
EARLY STREAMER EMMISION - LIGHTNING PROTECTION DETAIL
37.0 :TOTAL DEMAND LOAD (A)
13.3 :TOTAL DEMAND LOAD (KVA)
100.00% :TOTAL DEMAND FACTOR
37.0 :TOTAL CONNECTED LOAD (A)
13.3 :TOTAL CONNECTED LOAD (KVA)
NOTES: 44.6 39.2 29.8 :CONNECTED LOAD/PHASE (A)
5.2 4.6 3.6 :CONNECTED LOAD/PHASE (KVA)
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 GENERATOR BLOCK HEATER 1 20.0 A 1.00 0.18 20.0 A 1 RECEPTACLE AT GENERATOR 16
13 GENERATOR BATTERY CHARGER 1 20.0 A 1.00 1.00 20.0 A 1 EXISTING JUNCTION BOX 14
11 EXISTING JUNCTION BOX 1 20.0 A 1.00 1.00 20.0 A 1 EXISTING JUNCTION BOX 12
9 EXSITING FAN SCHEDULE 1 20.0 A 0.83 1.00 20.0 A 1 EXISTING JUNCTION BOX 10
7 EXISTING FAN SCHEDULE 1 20.0 A 0.66 1.00 20.0 A 1 EXISTING JUNCTION BOX 8
5 EXISTING FAN COIL UNIT 1 20.0 A 0.58 1.00 20.0 A 1 EXISTING JUNCTION BOX 6
3 EXISTING RECEPTACLES 1 20.0 A 0.54 1.00 20.0 A 1 EXISTING JUNCTION BOX 4
1 EXISTING RECEPTACLES 1 20.0 A 0.54 1.00 20.0 A 1 EXISTING JUNCTION BOX 2
NO DESCRIPTION P TRIP A B C TRIP P DESCRIPTION NO
CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT
A.I.C. RATING 10,000 AMPS SYMMETRICAL MOUNTING: SURFACE
BUS RATING: 100 AMPS MCB RATING: 100.0 A FED FROM:
RATINGS: 208Y/120 MAINS TYPE: MCB LOCATION:
EXISTING PANEL 1LAM
37.5 :TOTAL DEMAND LOAD (A)
9.0 :TOTAL DEMAND LOAD (KVA)
100.00% :TOTAL DEMAND FACTOR
37.5 :TOTAL CONNECTED LOAD (A)
9.0 :TOTAL CONNECTED LOAD (KVA)
NOTES: 37.5 37.5 :CONNECTED LOAD/PHASE (A)
4.5 4.5 :CONNECTED LOAD/PHASE (KVA)
17 SPACE 1 -- -- -- -- 1 SPACE 18
15 SPACE 1 -- -- -- -- 1 SPACE 16
13 SPACE 1 -- -- 0.50 14
11 0.50 0.50
20.0 A 2 PUMP NO. 3
PUMP NO. 2 2 20.0 A
0.50 0.50 10
7 2.00 0.50
20.0 A 2 PUMP NO. 1
SPACE HEATER 2 25.0 A
2.00 0.00 6
3 LIGHTING 1 20.0 A 1.00 0.00
20.0 A 2 JACKET WATER HEATER
1 BATTERY CHARGER 1 20.0 A 1.00 0.00 20.0 A 1 NEMA 5-20R GFI 2
NO DESCRIPTION P TRIP A B TRIP P DESCRIPTION NO
CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT
A.I.C. RATING 10,000 AMPS SYMMETRICAL MOUNTING: SURFACE
BUS RATING: 100 AMPS FED FROM:
RATINGS: 120/240 MAINS TYPE: MLO LOCATION:
PANEL EG1
38.3 :TOTAL DEMAND LOAD (A)
9.2 :TOTAL DEMAND LOAD (KVA)
100.00% :TOTAL DEMAND FACTOR
38.3 :TOTAL CONNECTED LOAD (A)
9.2 :TOTAL CONNECTED LOAD (KVA)
NOTES: 34.8 41.7 :CONNECTED LOAD/PHASE (A)
4.2 5.0 :CONNECTED LOAD/PHASE (KVA)
17 SPACE 1 -- -- -- -- 1 SPACE 18
15 SPACE 1 -- -- 0.00 20.0 A 1 SPARE 16
13 SPACE 1 -- -- 0.00 20.0 A 1 SPARE 14
11 SPARE 1 20.0 A 0.00 0.00 20.0 A 1 SPARE 12
9 SPARE 1 20.0 A 0.00 0.00 20.0 A 1 SPARE 10
7 2.00 1.00 20.0 A 1 FUEL POLISHING SYSTEM 8
SPACE HEATER 2 30.0 A
2.00 1.00 6
3 LIGHTING 1 20.0 A 1.00 1.00
20.0 A 2 JACKET WATER HEATER
1 BATTERY CHARGER 1 20.0 A 1.00 0.18 20.0 A 1 NEMA 5-20R GFI 2
NO DESCRIPTION P TRIP A B TRIP P DESCRIPTION NO
CKT CIRCUIT BREAKER LOAD (KVA) BREAKER CIRCUIT CKT
A.I.C. RATING 10,000 AMPS SYMMETRICAL MOUNTING: SURFACE
BUS RATING: 100 AMPS FED FROM:
RATINGS: 120/240 MAINS TYPE: MLO LOCATION:
PANEL EG2
CONNECT TO EXISTING FEEDER MADE AVAILABLE BY DEMOLITION
3 - #3 AWG & #8 AWG G IN 1.25" CONDUIT.
CONNECT TO EXISTING FEEDER MADE AVAILABLE BY DEMOLITION
3 - #3 AWG & #8 AWG G IN 1.25" CONDUIT.
NO DATE REVISION
1 07.25.25 ADDENDUM #1
| Sheets |
| P101 - PLUMBING PLANS |
File details come from the government source that posted it. Updated .