This document is a Report on Backup Generation System for the Armed Forces Retirement Home in Gulfport, Mississippi, prepared by Hood EE Consulting, PLLC on July 23, 2012. The report details an investigation into why two Kohler 2250 kW, 13.8 kV diesel engine generator sets tripped at approximately 43% of generator load. The investigation revealed several critical issues, including incorrect current transformer (CT) polarity in the generator compartment, improper relay settings, and potential grounding problems with the generators.

Key findings include improperly wired differential CTs causing relay malfunctions, relay settings that deviated from manufacturer recommendations, and a lack of secure ground connections for Generator 2's neutral. The report recommends several corrective actions: inserting differential relay word bits into trip equations, performing a comprehensive system power study, testing relays, ensuring proper overcurrent device coordination, installing a real-time automation controller, resolving generator grounding issues, and implementing safety grounding and lightning protection measures. These recommendations aim to improve the reliability and protection of the backup generation system at the facility.

View the file

Other files for this federal contract opportunity

Other files attached to Generator Replacement Services, newest first.
File Type Posted
Amendment 017.pdf PDF
Updated Construction Bid Documents.pdf PDF
Additional Specification Documents.pdf PDF
Amendment 016.pdf PDF
Addendum Cover Sheet.pdf PDF
Amendment 015.pdf PDF
Amendment 014.pdf PDF
Amendment 013.pdf PDF
Amendment 012.pdf PDF
Amendment 011.pdf PDF
Operation Manual PLC-HMI Upgrade.pdf PDF
Electrical Site Plan - Power.pdf PDF
SGP-1297 Kohler Power Systems.pdf PDF
Power Distribution One Line Diagram.pdf PDF
Kohler ATS and Switchgear SGP-1297 D.pdf PDF
Enlarged Generator Pad and Main Elec. Rm.pdf PDF
Amendment 010.pdf PDF
Amendment 009.pdf PDF
Amendment 008.pdf PDF
Amendment 007.pdf PDF
20342325Q00014 Updated.pdf PDF
Amendment 006.pdf PDF
Amendment 005.pdf PDF
Amendment 004.pdf PDF
Amendment 003.pdf PDF
Amendment 002.pdf PDF
Amendment 001.pdf PDF
20342325Q00014.pdf PDF
Show all 28

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Table Of Contents

Device Information Report Generated: July 23 2012 03:55:54 pm To Device Generator 1_ 7_21_12 as found From Device Generator 1_ 7_21_12 as left

Hidden Settings Changed Settings UnChanged Settings Missing Settings Invalid Settings

7/23/2012file://C:\Documents and Settings\Danny Hood\Application Data\SEL\AcSELerator\QuickS...

Global Top

Compared Settings

Setting

Current Value (Generator 1_ 7_21_12 as found)

Compared Value (Generator 1_ 7_21_12 as left)

LER 15 60

SS1 0 1

Settings that could not be compared

Setting Generator 1_ 7_21_12 as found

Generator 1_ 7_21_12 as left

Group 1 Top

Current Value (Generator 1_ 7_21_12 as found)

Compared Value (Generator 1_ 7_21_12 as left)

25ANG1 20 15

25ANG2 20 15

32P1P -0.0500 -0.1000

32P2P -0.1000 OFF

40XD1 -1.8 -2.0

40XD2 -1.8 -2.0

40Z1P 21.5 21.4 40Z2P 33.6 40.7 E32 N Y E81 2 N E87 T G O87P 0.20 0.30

SLP2 60 100

TAPD 2.97 3.10

Settings that could not be compared

Setting Generator 1_ 7_21_12 as found

Generator 1_

Group 2 Top

No changes

Port 1 Top

Port 2 Top

Port 3 Top

Port F Top

Current Value (Generator 1_ 7_21_12 as found)

Compared Value (Generator 1_ 7_21_12 as left)

SPEED 2400 19200

Settings that could not be compared

Setting Generator 1_ 7_21_12 as found

Generator 1_

SER Top

Report Generated: July 23 2012 04:07:41 pm To Device Generator 2_ 7_21_12 as found From Device Generator 2_ 7_21_12 as left

Hidden Settings Changed Settings UnChanged Settings Missing Settings Invalid Settings

Current Value (Generator 2_ 7_21_12 as found)

Compared Value (Generator 2_ 7_21_12 as left)

LER 15 60

SS1 0 1

Settings that could not be compared

Setting Generator 2_ 7_21_12 as found

Generator 2_

Current Value (Generator 2_ 7_21_12 as found)

Compared Value (Generator 2_ 7_21_12 as left)

25ANG1 20 15

25ANG2 20 15

27VSP 16.0 26.0

32P1P -0.0500 -0.1000

32P2P -0.1000 OFF

40XD1 -1.8 -2.0

40XD2 -1.8 -2.0

40Z1P 21.5 21.4 40Z2P 33.6 40.7 E32 N Y E87 T G O87P 0.20 0.30

SLP2 60 100

TAPD 2.97 3.10

Settings that could not be compared

Setting Generator 2_ 7_21_12 as found

Generator 2_

Current Value (Generator 2_ 7_21_12 as found)

Compared Value (Generator 2_ 7_21_12 as left)

SPEED 2400 19200

Settings that could not be compared

Setting Generator 2_ 7_21_12 as found

Generator 2_

Report Generated: July 23 2012 04:23:10 pm To Device Generator 1_ 7_21_12 as found From Device Generator 2_ 7_21_12 as found

Hidden Settings Changed Settings UnChanged Settings Missing Settings Invalid Settings

Current Value (Generator 1_ 7_21_12 as found)

Compared Value (Generator 2_ 7_21_12 as found)

27VSP 26.0 16.0

E81 2 N

Settings that could not be compared

Setting Generator 1_ 7_21_12 as found

Generator 2_ 7_21_12 as found

Report Generated: July 23 2012 04:19:58 pm To Device Generator 1_ 7_21_12 as left From Device Generator 2_ 7_21_12 as left

Hidden Settings Changed Settings UnChanged Settings Missing Settings Invalid Settings

Relay Element Settings 2-65

SEL-300G Instruction Manual Date Code 20100830

LOSS-OF-POTENTIAL (60LOP) PROTECTION

Element Description

Functional Description The SEL-300G provides an easy method to detect loss of relaying potential caused by blown potential fuses or operation of molded case circuit breakers in the potential circuit secondary. The relay declares a loss-of-potential if there is a 10 percent drop in the measured positive-sequence voltage with no corresponding change in positive-, negative-, or zero-sequence currents.

If the condition persists for 60 cycles, it latches in. 60LOP resets when V1 returns to greater than

0.43 • VNOM, and V0 and V2 are both less than 5 V secondary.

Setting Descriptions This function has no settings and is always active.

Relay Word Bits

Relay Word Bit Function Description Typical Applications 60LOP Loss of Relaying Potential Detected Indication, Control

100% STATOR GROUND PROTECTION ELEMENTS

Element Description

Functional Description The SEL-300G provides a two-zone function designed to detect stator winding ground faults on resistance and high-impedance grounded generators. The Zone 1 element, 64G1, uses a fundamental-frequency neutral overvoltage element that is sensitive to faults in the middle and upper portions of the winding. The Zone 2 element, 64G2, uses a third-harmonic voltage differential function to detect faults in the upper and lower portions of the winding. By using the two zones together, the relay provides 100 percent stator ground fault coverage.

Note: Most generators produce enough third-harmonic voltage for proper application of the 64G2 element; however, some generators (e.g., those with 2/3 pitch winding) may not. In those cases the element based on the third-harmonic voltage, such as the 64G2, cannot be used for 100 percent Stator Ground Protection.

When a ground fault occurs high in the winding of a resistance or high-impedance grounded generator, a voltage appears at the generator neutral. The neutral voltage magnitude during the fault is proportional to the fault location within the winding. For instance, if a fault occurs 85 percent up the winding from the neutral point, the neutral voltage is 85 percent of the generator rated line-neutral voltage. The SEL-300G asserts the 64G1 Relay Word bit when neutral voltage is greater than the 64G1P setting.

TAW AFRH REPORT.pdf
Compare - Gen 1 As Found_ Gen 1 As Left
Compare - Gen 2 As Found_ Gen 2 As Left
Compare - Gen 1 As Found_ Gen 2 As Found
Compare - Gen 1 As Left_ Gen 2 As Left
60LOP Description