This document contains the working drawings and related details for the Sonner Hall HVAC Replacement project being undertaken by James Madison University, a public university located in Harrisonburg, Virginia. The primary goal of this project is to replace three existing mechanical rooftop units and associated distribution ductwork, as well as to replace the return air ductwork serving the building plenums. The project will also involve the removal and replacement of existing ceilings as needed to facilitate the integration of the new mechanical equipment.
The project is being procured through IFB 216-B3216-015. The working drawings provide details on the demolition and new installation work required, including plans, elevations, details, and schedules. The bid due date, award details, and contract term are not specified in the document. Pricing terms, set asides, incumbents, funding sources, and other commercial details are also not included in the provided materials.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum.doc | DOC document | |
| Awarded to Riddleberger Brothers Inc | — | |
| It is James Madison University’s intent to award, IFB 216-B3216-015, Sonner Hall HVAC Renovations, to Riddleberger Brothers, Inc. | — | |
| dgs-30-272_pre-bid_question_form.doc | DOC document | |
| Bid Form.doc | DOC document | |
| jmuco-7a(1).docx | DOCX document | |
| 2024-01-19_JMU Sonner Hall HVAC Replacement_Project Manual_rev1 (1).pdf | ||
| NOTICE OF IFB_2.20.24.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONCRETE MASONRY (CMU)
CONCRETE
BRICK
STONE
STEEL
ALUMINUM
POROUS FILL
SOIL
RIGID INSULATION
BATT INSULATION
SOUND ATTENUATION BATTS
GYPSUM DRYWALL
PLASTER OR SAND
PLYWOOD
FRAMING
LUMBER
(BLOCKING)
FINISH WOOD
CERAMIC TILE
ACOUSTICAL PANELS
E
C WINDOW TYPE
DEMOLITION KEYED
NOTE
COLUMN LINE
WORK OR DATUM
POINT
DOOR NUMBER123A
ROOMNAME
ROOM NUMBER
2 PARTITION TYPE
1A
A101
SIM
DRAWING WHERE
SHOWN
BUILDING SECTION
CALL-OUT
A101
2A
3B
3A
2B
INTERIOR
ELEVATION
CALL-OUT
DRAWING WHERE
SHOWN
1A
A101
DETAIL CALL-OUT
DRAWING WHERE
SHOWN
1A
A101
SIM
DRAWING WHERE
SHOWN
DETAIL SECTION
CALL-OUT
A101
2A
3B
3A
2B
EXTERIOR
ELEVATION
CALL-OUT
DRAWING WHERE
SHOWN
REVISION CLOUD
REVISION NUMBER
PLAN KEYED NOTE
SECTION KEYED
NOTE
ELEVATION KEYED
NOTE
INTERSTATE 81
PROJECT LOCATION
SONNER HALL
S . M
A
IN
S T
P O
R T R
E P
U B
LIC
R
D
BRIDGEFORTH
STADIUM
SEE SHEET AC.01 FOR ENLARGED PLAN
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :5
P
M
T001
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
T
IT
L E S
H E E T
WORKING DRAWINGS
216-B3216-015
Sonner Hall HVAC Replacement
481 Bluestone Drive Harrisonburg, Virginia 22807
James Madison University
Price Studios, LLC (dba PSH+) 207 Foushee Street
RICHMOND, VA 23220
PHONE: (804) 823-2900
CONTACT: Sydnor Tetterton EMAIL: stetterton@pshplus.com
James Madison University
HARRISONBURG, VA
PHONE: (540) 568-6720
CONTACT: Clark Driver
EMAIL: drive2ch@jmu.edu
AGENCY REP.
ARCHITECT
MEP ENGINEER
CMTA
315 W BROAD STEET - SUITE 300
RICHMOND, VA 23220
PHONE: (804) 495-8461 EXT. 1322
CONTACT: DREW ROBERTS, P.E.
EMAIL: DRoberts@cmta.com
VICINITY MAP
DRAWING ABBREVIATIONS
MATERIALS LEGEND
DRAWING SYMBOLS CONTACT INFORMATION
INCL.
SHEET
NO DESCRIPTION
REV.
NO.
REVISION
DATE
TITLE SHEET
■ T001 TITLE SHEET 1 01/19/2024
GENERAL
■ AC01 CODE DATA SHEET 1 01/19/2024
DEMOLITION
■ AD111 DEMOLITION PLAN - LOWER LEVEL
■ AD112 DEMOLITION PLAN - UPPER LEVEL
■ AD131 DEMOLITION PLAN - LOWER LEVEL CEILING
■ AD132 DEMOLITION PLAN - UPPER LEVEL CEILING
ARCHITECTURAL
■ A012 GENERAL NOTES & DETAILS 1 01/19/2024
■ A111 LOWER LEVEL FLOOR PLAN
■ A122 UPPER LEVEL FLOOR PLAN
■ A131 LOWER LEVEL FLOOR REFLECTED CEILING PLAN
■ A132 UPPER LEVEL FLOOR REFLECTED CEILING PLAN
■ A141 ROOF PLAN 1 01/19/2024
■ A301 BUILDING SECTIONS 1 01/19/2024
■ A302 BUILDING SECTIONS 1 01/19/2024
■ A303 BUILDING SECTIONS 1 01/19/2024
ELECTRICAL
■ E-001 ELECTRICAL LEGEND 1 01/19/2024
■ ED-101 LEVEL ONE - DEMOLITION - LIGHTING
■ ED-102 LEVEL TWO - DEMOLITION - LIGHTING
■ ED-201 LEVEL ONE - DEMOLITION - POWER
■ ED-202 LEVEL TWO - DEMOLITION - POWER
■ ED-203 ROOF - DEMOLITION - POWER
■ E-101 LEVEL ONE - NEW WORK - LIGHTING 1 01/19/2024
■ E-102 LEVEL TWO - NEW WORK - LIGHTING 1 01/19/2024
■ E-201 LEVEL ONE - NEW WORK - POWER 1 01/19/2024
■ E-202 LEVEL TWO - NEW WORK - POWER 1 01/19/2024
■ E-203 ROOF - NEW WORK
■ E-501 ELECTRICAL DETAILS & SCHEDULES 1 01/19/2024
MECHANICAL
■ M-001 MECHANICAL LEGEND 1 01/19/2024
■ MD-101 LEVEL ONE - DEMOLITION - MECHANICAL
■ MD-102 LEVEL TWO - DEMOLITION - MECHANICAL 1 01/19/2024
■ MD-103 ROOF - DEMOLITION - MECHANICAL
■ MD-201 LEVEL ONE - DEMOLITION - HYDRONICS
■ MD-202 LEVEL TWO - DEMOLITION - HYDRONICS 1 01/19/2024
■ M-101 LEVEL ONE - NEW WORK - MECHANICAL 1 01/19/2024
■ M-102 LEVEL TWO - NEW WORK - MECHANICAL 1 01/19/2024
■ M-103 ROOF - NEW WORK - MECHANICAL 1 01/19/2024
■ M-201 LEVEL ONE - NEW WORK - HYDRONICS
■ M-202 LEVEL TWO - NEW WORK - HYDRONICS 1 01/19/2024
■ M-501 MECHANICAL DETAILS
■ M-502 MECHANICAL DETAILS 1 01/19/2024
■ M-601 MECHANICAL SCHEDULES 1 01/19/2024
■ M-801 MECHANICAL CONTROLS 1 01/19/2024
■ M-802 MECHANICAL CONTROLS 1 01/19/2024
■ M-803 MECHANICAL CONTROLS 1 01/19/2024
■ M-901 MECHANICAL CALCULATIONS
SHEET INDEX
AFF ABOVE FINISH FLOOR
AP ACCESS PANEL
ACT ACOUSTICAL CEILING
TILE
ADJ ADJACENT,
ADJUSTABLE
A/C AIR CONDITIONING
ALT ALTERNATE
ALUM ALUMINUM
AB ANCHOR BOLT
APPROX APPROXIMATE(LY)
ARCH ARCHITECT(URAL)
@ AT
BP BASE PLATE
BSMT BASEMENT
BM BEAM
BRG BEARING
BIT BITUMNOUS
BLKG BLOCKING
BD BOARD
BOT BOTTOM
BRK BRICK
BLDG BUILDING
CR CARD READER
CPT CARPET
CO CASED OPENING
CSMT CASEMENT
CLG CEILING
C/H CEILING HEIGHT
CL CENTER LINE
CT CERAMIC TILE
CLR CLEAR(ANCE)
CLS CLOSET
COL COLUMN
CONST CONCRETE
CMU CONCRETE MASONRY
UNIT
COMP CONSTRUCTION
CONT CONTINUOUS
CFCI CONTRACTOR
FURNISHED
CONTRACTOR
INSTALLED
CJ CONTROL JOINT
CG CORNER GUARD
CORR CORRIDOR
CR/BG CRASH RAIL/BUMPER
GUARD
DP DAMPROOFING
DET DEATAIL
DEG DEGREE
DEMO DEMOLITION
D DEPTH
DIAG DIAGONAL
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DIV DIVISION
DR DOOR, DRAIN
DBL DOUBLE
DN DOWN
DS DOWN SPOUT
DWG(S) DRAWING(S)
DF DRINKING FOUNTAIN
EA EACH
EWC ELECTRIC WATER
COOLER
ELEC ELECTRICAL
ELEV ELEVATOR, ELEVATION
EMER EMERGENCY
ENGR ENGINEER(ING)
EQ EQUAL
EQUIP EQUIPMENT
ASBESTOS DISCLOSURE STATEMENT
LEAD MATERIALS DISCLOSURE
AN ASBESTOS INSPECTION WAS NOT PERFORMED BECAUSE ALL PORTIONS OF THE
EXISTING BUILDING THAT MAY BE AFFECTED BY THE WORK WERE ORGINALLY
CONSTRUCTED AFTER JANUARY 1, 1985.
AN INSPECTION TO IDENTIFY LEAD CONTAINING OR COATED BUILDING COMPONENTS HAS
NOT BEEN CONDUCTED BECAUSE THE BUILDING WAS CONSTRUCTED AFTER JANUARY 1,
1985 AND THE OWNER HAS NO KNOWLEDGE OF LEAD CONTAINING OR COATED BUILDING
COMPONENTS IN THE BUILDING. IT IS THE CONTRACTOR's RESPONSIBILITY TO COMPLY
WIHT VIRGINIA OCCUPATIONAL SAFETY & HEALTH (VOSH) REGULATIONS AS THEY PERTAIN
TO EMPLOYEE EXPOSURES TO LEAD. ALL LEAD AND LEAD COATED BUILDING
COMPONENTS SHALL BE RECYCLED TO THE EXTENT POSSIBLE.
EPDM ETHYLENE
PROPYLENE DIENE
MONOMER (ROOF
MEMBRANE)
EXIST EXISTING
ETR EXISTING TO REMAIN
EB EXPANSION BOLT
EJ EXPANSION JOINT
EXT EXTERIOR
EIFS EXTERIOR INSULATION
AND FINISH SYSTEM
FB FACE BRICK
F FAHRENHEIT
FT FEET, FOOT
FF FINISH FLOOR
FIN FINISH(ED)
FA FIRE ALARM
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FHC FIRE HOSE CABINET
FRTW FIRE RETARDANT
TREATED WOOD
FD FLOOR DRAIN
FTG FOOTING
FDN FOUNDATION
FBO FURNISHED BY
OTHERS
GA GAGE, GAUGE
GALV GALVANIZED
GEN GENERAL
GC GENERAL
CONTRACTOR
GL GLAZZ, GLAZING
GND GROUND
GWB GYPSUM WALL BOARD
HRL HANDRAIL
HDWR HARDWARE
HWD HARDWOOD
HVAC HEATING VENTILATING
& AIR CONDITIONING
HD HEAVY DUTY
HGT HEIGHT
H HIGH
HC HOLLOW CORE
HM HOLLOW METAL
HORIZ HORIZONTAL
HB HOSE BIB
HW HOT WATER HEATER
HR HOUR
IN INCH
INCL INCLUDE(D)(ING)
INSUL INCULAT(E)(ATION)
ID INSIDE DIAMETER
INT INTERIOR
JAN JANITOR('S CLOSET)
JST JOIST
JCT JUNCTION
KB KEYBOARD
KP KICK PLATE
KIT KITCHEN
KS KNEE SPACE
LAM LAMINATE(D)
LAV LAVATORY
LH LEFT HAND
L LENGTH, LONG
LW LIGHTWEIGHT
LNTLL LINTEL
LL LIVE LOAD
LVR LOUVER
LVT LUXURY VINYL TILE
LB POUND
MFR MANUFACTURER
MAS MASONRY
MO MASONRY OPENING
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MTL METAL
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MLDG MOULDING
MNTG MOUNTING
NOM NOMINAL
N NORTH
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO.# NUMBER
OFF OFFICE
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
OD OUTSIDE DIAMETER,
OVERFLOW DRAIN
OF OUTSIDE FACE
OA OVERALL
OH OVERHEAD
OFCI OWNER FURNISHED
CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED
OWNER INSTALLED
PNT(D) PAINT(ED)
PNL PANEL
PVMT PAVEMENT
PERP PERPENDICULAR
PLAS PLASTER, PLASTIC
PLAM PLASTIC LAMINATE
PL PLATE
PLGL PLATE GLASS
PLWD PLYWOOD
PVC POLYVINYL CHLORIDE
LB(S) POUND(S)
PSF POUNDS PER SQUARE
FOOT
PSI POUNDS PER SQUARE
INCH
PREFIN PREFINSHED
PT PRESSURE TREATED,
PORCELAIN TILE
PROP PROPERTY
QTY QUALITY
QT QUARRY TILE
RAD RADIUS
REC RECEIVE, RECEPTACLE
REFL Reflected
REF REFRIGERATOR
REG REGULAR, REGISTER
REINF REINFORCED
REBAR REINFORCING BAR
REM REMOVE
REQ REQUIRE, REQUIRED
RES RESILIENT
RET RETURN
RA RETURN AIR
REV REVISION
RH RIGHT HAND
R. RISER
RD ROOF DRAIN
RM ROOM
RO ROUGH OPENING
RB RUBBER, RUBBER
BASE
SCH SCHEDULE
SCUP SCUPPER
SECT SECTION
SHT SHEET
SIM SIMILAR
SC SOLID CORE
SCW SOLID CORE WOOD
SSM SOLID SURFACE
MATERIAL
SPEC SPECIFICATION
SPR SPRINKLER
SS STAINLESS STEEL,
SERVICE SINK
SP STAND PIPE
STL STEEL
STN STONE
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SYS SYSTEM
TEL TELEPHONE
T GL TEMPERED GLASS
TEMP TEMPERED,
TEMPORARY
TERR TERRAZZO
THK THICK(NESS)
THRU THROUGH
TLT TOILET
T&G TONGUE & GROVE
TOM TOP OF MASONRY
TOSL TOP OF SLAB
TOS TOP OF STEEL
TOW TOP OF WALL
T TREAD
TYP TYPICAL
UC UNDERCOUNTER,
UNDER CUT
UNFIN UNFINISHED
UNO UNLESS NOTED
OTHERWISE
VB VAPOR BARRIER
VTR VENT THROUGH ROOF
VIF VERIFY IN FIELD
VERT VERTICAL
VEST VESTIBULE
VCT VINYL COMPOSITION
TILE
VWC VINYL WALL COVERING
VIT VITREOUS CHINA
WSCT WAINSCOT
WC WALL COVERING,
WATER CLOSET
WH WALL HUNG, WATER
HEATER
WR WASTE RECEPACLE
WP WATER PROOF
WT WEIGHT
WWF WELDED WIRE FABRIC
W WIDTH, WIDE
WNDW WINDOW
WG WIRE GLASS
W/ WITH
W/O WITHOUT
WD WOOD
WB WOOD BASE
HIGH PERFORMANCE BUILDING STATEMENT
IN ACCORD WITH THE HIGHER PERFORMANCE BUILDING ACT, THE BUILDING IS
EXEMPT FROM COMPLIANCE BECAUSE THE COST OF THE RENOVATION DOES NOT
EXCEED 50% OF THE VALUE OF THE BUILDING.
CODE DATA
BUILDING OCCUPANCY
USE GROUP:
TYPE OF CONSTRUCTION
CONSTRUCTION TYPE:
GENERAL BUILDING LIMITATIONS
EXISTING FLOOR AREA:
EXISTING HEIGHT OF BUILDING:
FIRE PROTECTION SYSTEMS
AUTOMATIC SPRINKLER SYSTEM:
STANDPIPE SYSTEM:
FIRE ALARM & DETECTION SYSTEMS:
SMOKE CONTROL:
SMOKE & HEAT VENTS:
FIRE COMMAND CENTER:
FIRE DEPARTMENT CONNECTIONS:
EMERGENCY COMMUNICATIONS:
PORTABLE FIRE EXTINGUISHERS:
APPLICABLE CODES
2018 Virginia Construction Code (VCC) 2018 Virginia Existing Building Code (VEBC)
2018 Virginia Mechanical Code 2018 Virginia Plumbing Code NFPA 70, National Electric Code: 2017
2023 Construction & Professional Services Manual - REV 0 (CPSM)
2010 ADA Standards for Accessible Design (ASAD)
2023 JMU Design & Construction Guidelines
B - Business (EXISTING)
3B (AS DEFINED BY 1984 BOCA MODEL CODE)
10,088 SF LEVEL ONE,
10,294 LEVEL TWO
38 FEET ABOVE GRADE (LAKESIDE)
YES (EXISTING)
NO
YES (EXISTING)
NO
NO
YES (REF. FIRE ALARM DWG's BY OTHERS)
YES
YES (REF. FIRE ALARM DWG's BY OTHERS)
YES - EXISTING TO REMAIN
VECC COMPLIANCE STATEMENT
IN ACCORD WITH THE VIRGINIA ENERGY CONSERVATION CODE (VECC), THE BUILDING
SHALL COMPLY WITH VECC SECTIONS C402 THROUGH C405 AND C408.
REVISIONS
Revision 1 01/19/2024
VEBC ALTERATION LEVEL 1
PROJECT INFORMATION
PROJECT NAME:
ADDRESS:
USE:
AGENCY:
AGENCY ADDRESS:
AGENCY PROJECT MANAGER:
PHONE:
JMU Sonner Hall HVAC Replacement 481 Bluestone Dr. Harrisonburg, Virginia 22807 Academic Offices
Commonwealth of Virginia - James Madison University James Madison University Harrisonburg, Virginia Clark Driver
(540) 568-6720
PROJECT SYNOPSIS
THE AGENCY IS INITIATING A MECHANICAL SYSTEM REPLACEMENT PROJECT THAT INCLUDES THE REPLACEMENT OF (3) EXISTING MECHANICAL ROOF TOP UNITS AND ASSOCIATED DISTRIBUTION DUCTING.
RETURN AIR DUCTWORK SERVING THE BUILDING PLENUMS WILL ALSO BE REPLACED. MOST OF THE BUILDING's LIGHTING WAS UPGRADED TO LED FIXTURES IN 2017 BUT SELECT FIXTURES ARE BEING
REPLACED WHERE APPROPRIATE. NO SPRINKLER MODIFICATIONS ARE PLANNED.
BUILDING OCCUPANCY
USE GROUP:
TYPE OF CONSTRUCTION
CONSTRUCTION TYPE:
GENERAL BUILDING LIMITATIONS
EXISTING FLOOR AREA:
EXISTING HEIGHT OF BUILDING:
FIRE PROTECTION SYSTEMS
AUTOMATIC SPRINKLER SYSTEM:
STANDPIPE SYSTEM:
FIRE ALARM & DETECTION SYSTEMS:
SMOKE CONTROL:
SMOKE & HEAT VENTS:
FIRE COMMAND CENTER:
FIRE DEPARTMENT CONNECTIONS:
EMERGENCY COMMUNICATIONS:
PORTABLE FIRE EXTINGUISHERS:
APPLICABLE CODES
2018 Virginia Construction Code (VCC) 2018 Virginia Existing Building Code (VEBC)
2018 Virginia Mechanical Code 2018 Virginia Plumbing Code NFPA 70, National Electric Code: 2017
2023 Construction & Professional Services Manual - REV 0 (CPSM)
2010 ADA Standards for Accessible Design (ASAD)
2023 JMU Design & Construction Guidelines
B - Business (EXISTING)
3B (AS DEFINED BY 1984 BOCA MODEL CODE)
10,088 SF LEVEL ONE,
10,294 LEVEL TWO
38 FEET ABOVE GRADE (LAKESIDE)
YES (EXISTING)
NO
YES (EXISTING)
NO
NO
YES (REF. FIRE ALARM DWG's BY OTHERS)
YES
YES (REF. FIRE ALARM DWG's BY OTHERS)
YES - EXISTING TO REMAIN
VEBC ALTERATION LEVEL 1
NEWMAN LAKE
BLUESTONE D
RIV
E
IN
TERSTATE 8
1 S O
UTH B
O
UND
IN
TERSTATE 8
1 N O
RTH B
O
UND
SONNER HALL
"P" LOT
AGENCY & GC STAGING AREA
TEMPORARY FENCING
NOTES:
1. THE AREA INDICATED AT THE SOUTH END OF THE "P" LOT IS THE DESIGNATED STAGING AREA FOR
BOTH THE AGENCY & THE CONTRACTOR.
2. THE AGENCY INTENDS TO STAGE SHIPPING CONTAINERS IN THIS AREA TO TEMPORARILY STORE
SELECT BUILDING FIXTURES AND FURNITURE DURING CONSTRUCTION.
3. THIS AREA SHALL ACCOMMODATE THE CONTRACTOR's DUMPSTER, PORTA-POTTY & ANY STORAGE
FACILITIES THAT THE CONTRACTOR REQUIRES TO EXECUTE THE WORK.
4. FENCING SHALL COMPLY WITH JMU DESIGN & CONSTRUCTION GUIDELINES SECTION 32.1.4 & BE APPROVED BY THE AGENCY's PROJECT MGR.
A. FENCE SHALL BE 8' TALL WITH TOP RAIL & SIGHT-RESTRICTIVE FABRIC SCREENING.
B. FENCING SHALL BLACK VINYL COATED, 9 GAUGE, 2" WEAVE WITH CLASS 2 HOT DIPPED
GALVANIZED WIRING.
C. ALL POSTS AND RAILS SHALL BE AT LEAST SCHEDULE 40 HOT DIPPED GALVANIZED OR HIGH-
TENSILE GALVANIZED STEEL PIPING. POSTS SHALL BE DRIVEN AND ALL EXPOSED METAL
PAINTED BLACK. TOP & BOTTOM RAILS, GATES AND HARDWARE SHALL ALSO BE PAINTED
BLACK.
D. GATES & HARDWARE SHALL BE DOUBLE LOCKED USING CONTRACTOR AND JMU SUPPLIED
LOCKS.
5. SUBMIT A SITE PLAN DETAILING THE CONTRACTOR'S INTENDED LAYOUT, FENCING CONFIGURATION
AND ACCESS POINTS TO THE AGENCY PROJECT MGR FOR REVIEW AND APPROVAL PRIOR TO
MOBILIZATION.
6. DO NOT CLOSE OR BLOCK STREETS, WALKWAYS ETC. WITHOUT DIRECT PERMISSION FROM THE
DIRECTOR OF FACILITIES ENGINEERING & CONSTRUCTION.
HARTMAN HALL
AGENCY PREFERRED
CRANE LOCATION
BLUESTO
NE D
RIV
E
P -
LO
T (P
AR
K
IN
G
SHOWKER HALL
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :5
P
M
AC01
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
C O
D E D
A T A S
H E E T
WORKING DRAWINGS
216-B3216-015
6" = 1'-0"AC01
4 SITE MAP
N
S
W E
REVISIONS
Revision 1 01/19/2024
CONFERENCE
ROOM
OFFICE
OFFICE
1030A
OFFICE
OFFICE
OFFICE
MECHANICAL
M1040
ELEV
M1041
STOR
1000A
STOR
1000B
STORAGE
ELEC
M1001
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
1026 OFFICE
OFFICE
BREAK
ROOM
OFFICE
OFFICE
OFFICE
CALL
CENTER
COPY
WOMEN
T1034
CONFERENCE
ROOM
JAN.
J1002
OFFICE
SERVICE
OFFICE
MEN
T1004
OFFICE
OFFICE
OFFICE
OFFICE
B
B
CHASE 1
CHASE 2
ELEVATOR
EXISTING DOOR TO REMAIN
EXISTING PARTITION TO REMAIN
EXISTING PARTITION
TO BE DEMOLISHED
DEMOLITION KEY NOTE1
1 HR FIRE BARRIER
NEW PARTITION
PLAN KEY NOTE1
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :5
P
M
AD111
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
D E M
O L
IT
IO
N
P L A N
L O
W E R L
E V E L
WORKING DRAWINGS
216-B3216-015
1. CONTRACTOR TO CONTACT OWNER PRIOR TO START OF DEMOLITION TO ALLOW OWNER TIME TO
REMOVE ANY MOVABLE EQUIPMENT.
2. COORDINATE PHASING OF DEMOLITION WITH THE OWNER.
3. ALL FIRE EXTINGUISHERS AND CABINETS TO REMAIN.
4. PROTECT ALL EXISTING WALL FINISHES THROUGH OUT THE CONSTRUCTION PERIOD.
5. REPAIR ALL CEILINGS TO MATCH EXISTING CEILINGS WHERE WALLS ARE TO BE DEMOLISHED AND
EXISTING CEILING IS TO REMAIN.
6. CONTRACTOR TO MATCH ALL EXISTING CONDITIONS FOR ALL REQUIRED MODIFICATIONS IN
RENOVATED AREAS (U.N.O.). THIS INCLUDES FINISH PATTERNS AND COLORS,
7. REPAIR HOLES IN EXISTING WALLS TO REMAIN WHERE WALL MOUNTED ITEMS ARE TO BE
REMOVED. MATCH FINISHES IN KIND, UNO.
8. CONTRACTOR TO PROTECT ALL EXISTING FLOORS, WALLS & CEILINGS DURING CONSTRUCTION
AND PROVIDE TEMPORARY PARTITIONS AS NEEDED. CONTRACTOR IS RESPONSIBILE FOR
REPAIR AND REPLACEMENT OF ALL DAMAGED FLOORING, WALLS, CEILINGS, ETC. FINISHES TO
MATCH EXISTING, UNO.
9. THE CONTRACTOR WILL BE RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL
DEMOLISHED MATERIALS. LEGALLY DISPOSE OF WASTE PER ENVIRONMENTAL PROTECTION
AGENCY (EPA) AND COMMONWEALTH OF VIRGINIA REQUIREMENTS.
10.. UNLESS SPECIFICALLY NOTED, ALL FLOOR COVERINGS & WALL BASE SHALL REMAIN. PROTECT
THROUGH-OUT CONSTRUCTION.
11. ADDITIONAL DEMOLITION MAY BE REQUIRED TO ACCOMMODATE NEW CONSTRUCTION SHOWN
ON OTHER SHEETS. CONTRACTOR TO REVIEW EXISTING CONDITIONS AND INCLUDE IN BASE BID
ALL DEMOLITION REQUIRED FOR A COMPLETE INSTALLATION.
12. WHERE PARTITIONS, EQUIPMENT, OR ACCESSORIES, ETC. ARE REMOVED AND NO REPLACEMENT FINISH IS CALLED FOR, THE GENERAL CONTRACTOR SHALL REPAIR TO MATCH ADJACENT FINISH.
13. IF ANY PORTION OF THE SPRINKLER SYSTEM IS TAKEN OUT OF SERVICE, PROVIDE A FIRE WATCH UNTIL THE SYSTEM IS FULLY OPERABLE. Ref. THE MEP DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
14. UNLESS NOTED OTHERWISE, ALL EXISTING CEILING GRIDS SHALL BE REMOVED EXCEPT FOR THE
L SHAPED PROFILE AROUND THE PERIMETER OF THE ROOM. EXISTING CEILING TILES TO BE
REMOVED. UNLESS NOTED OTHERWISE, LIGHTS SHALL BE REMOVED & RE-INSTALLED; ref.
ELECTRICAL DRAWINGS.
15. UNLESS NOTED OTHERWISE, ALL EXISTING CARPET AND WALL BASE TO REMAIN.
16. REMOVE & REINSTALL ALL WALL MOUNTED ITEMS TO REMAIN AS NEEDED TO EXECUTE WORK.
17. REFERENCE SPECIFICATION SECTION 02 41 00 - DEMOLITION FOR ADDITIONAL REQUIREMENTS.
18. COMPLY WITH NFPA 241 STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION &
DEMOLITION OPERATIONS.
19. IF REQUIRED, TEMPORARY LIGHTING SHALL BE PROVIDED BY THE CONTRACTOR.
20. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BID.
21. IF WORK REQUIRES REMOVAL OR ALTERATION OF MECHANICAL EQUIPMENT, REMOVE ANY
REFRIGERANT ACCORDING TO 40 CFR 82 & THE REGULATIONS OF THE AUTHORITIES HAVING
JURISDICTION.
22. UNLESS NOTED OTHERWISE, EXISTING WALL FINISHES AND COVERINGS TO REMAIN. PATCH &
REPAIR AS NEEDED.
GENERAL DEMOLITION NOTES
KEYED DEMO PLAN NOTES A
1/8" = 1'-0"A211 AD111
1 DEMOLITION PLAN - LOWER LEVEL
4'0 8' 16'
SCALE : 1/8" = 1' - 0"
A WALLS SHOWN DASHED TO BE REMOVED TO FACILITATE WORK
B APPROXIMATE EXTENT OF MECHANICAL CHASE ABOVE SHOWN DASHED; VERIFY
IN FIELD. PROTECT ALL EXISTING FINISHES TO REMAIN.
N
S
W E
PLAN LEGEND
REVISIONS
DNOFFICE
OFFICE
2037 OFFICE
OFFICE
OFFICE
OFFICE
2031 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
BREAKROOM
STORE
ROOM
OFFICE
OFFICE
CONFERENCE
ROOM
LOUNGE
WOMEN
T2006
OFFICE
CONF RM
OFFICE
OFFICE
OFFICE
2015STORAGE
OFFICE
SERVICE
MEN
T2003
OFFICE
OFFICE
CONF RM
OFFICE
OFFICE
ELEV
E299
JAN
J2002
AA
A
CHASE 1
CHASE 2
EXISTING DOOR TO REMAIN
EXISTING PARTITION TO REMAIN
EXISTING PARTITION
TO BE DEMOLISHED
DEMOLITION KEY NOTE1
1 HR FIRE BARRIER
NEW PARTITION
PLAN KEY NOTE1
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :0
P
M
AD112
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
D E M
O L
IT
IO
N
P L A N
U
P P E R L
E V E L
WORKING DRAWINGS
216-B3216-015
1/8" = 1'-0"A211 AD112
1 DEMOLITION PLAN - UPPER LEVEL
1. CONTRACTOR TO CONTACT OWNER PRIOR TO START OF DEMOLITION TO ALLOW OWNER TIME TO
REMOVE ANY MOVABLE EQUIPMENT.
2. COORDINATE PHASING OF DEMOLITION WITH THE OWNER.
3. ALL FIRE EXTINGUISHERS AND CABINETS TO REMAIN.
4. PROTECT ALL EXISTING WALL FINISHES THROUGH OUT THE CONSTRUCTION PERIOD.
5. REPAIR ALL CEILINGS TO MATCH EXISTING CEILINGS WHERE WALLS ARE TO BE DEMOLISHED AND
EXISTING CEILING IS TO REMAIN.
6. CONTRACTOR TO MATCH ALL EXISTING CONDITIONS FOR ALL REQUIRED MODIFICATIONS IN
RENOVATED AREAS (U.N.O.). THIS INCLUDES FINISH PATTERNS AND COLORS,
7. REPAIR HOLES IN EXISTING WALLS TO REMAIN WHERE WALL MOUNTED ITEMS ARE TO BE
REMOVED. MATCH FINISHES IN KIND, UNO.
8. CONTRACTOR TO PROTECT ALL EXISTING FLOORS, WALLS & CEILINGS DURING CONSTRUCTION
AND PROVIDE TEMPORARY PARTITIONS AS NEEDED. CONTRACTOR IS RESPONSIBILE FOR
REPAIR AND REPLACEMENT OF ALL DAMAGED FLOORING, WALLS, CEILINGS, ETC. FINISHES TO
MATCH EXISTING, UNO.
9. THE CONTRACTOR WILL BE RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL
DEMOLISHED MATERIALS. LEGALLY DISPOSE OF WASTE PER ENVIRONMENTAL PROTECTION
AGENCY (EPA) AND COMMONWEALTH OF VIRGINIA REQUIREMENTS.
10.. UNLESS SPECIFICALLY NOTED, ALL FLOOR COVERINGS & WALL BASE SHALL REMAIN. PROTECT
THROUGH-OUT CONSTRUCTION.
11. ADDITIONAL DEMOLITION MAY BE REQUIRED TO ACCOMMODATE NEW CONSTRUCTION SHOWN
ON OTHER SHEETS. CONTRACTOR TO REVIEW EXISTING CONDITIONS AND INCLUDE IN BASE BID
ALL DEMOLITION REQUIRED FOR A COMPLETE INSTALLATION.
12. WHERE PARTITIONS, EQUIPMENT, OR ACCESSORIES, ETC. ARE REMOVED AND NO REPLACEMENT FINISH IS CALLED FOR, THE GENERAL CONTRACTOR SHALL REPAIR TO MATCH ADJACENT FINISH.
13. IF ANY PORTION OF THE SPRINKLER SYSTEM IS TAKEN OUT OF SERVICE, PROVIDE A FIRE WATCH UNTIL THE SYSTEM IS FULLY OPERABLE. Ref. THE MEP DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
14. UNLESS NOTED OTHERWISE, ALL EXISTING CEILING GRIDS SHALL BE REMOVED EXCEPT FOR THE
L SHAPED PROFILE AROUND THE PERIMETER OF THE ROOM. EXISTING CEILING TILES TO BE
REMOVED. UNLESS NOTED OTHERWISE, LIGHTS SHALL BE REMOVED & RE-INSTALLED; ref.
ELECTRICAL DRAWINGS.
15. UNLESS NOTED OTHERWISE, ALL EXISTING CARPET AND WALL BASE TO REMAIN.
16. REMOVE & REINSTALL ALL WALL MOUNTED ITEMS TO REMAIN AS NEEDED TO EXECUTE WORK.
17. REFERENCE SPECIFICATION SECTION 02 41 00 - DEMOLITION FOR ADDITIONAL REQUIREMENTS.
18. COMPLY WITH NFPA 241 STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION &
DEMOLITION OPERATIONS.
19. IF REQUIRED, TEMPORARY LIGHTING SHALL BE PROVIDED BY THE CONTRACTOR.
20. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BID.
21. IF WORK REQUIRES REMOVAL OR ALTERATION OF MECHANICAL EQUIPMENT, REMOVE ANY
REFRIGERANT ACCORDING TO 40 CFR 82 & THE REGULATIONS OF THE AUTHORITIES HAVING
JURISDICTION.
22. UNLESS NOTED OTHERWISE, EXISTING WALL FINISHES AND COVERINGS TO REMAIN. PATCH &
REPAIR AS NEEDED.
GENERAL DEMOLITION NOTES
KEYED DEMO PLAN NOTES 1
4'0 8' 16'
SCALE : 1/8" = 1' - 0"
A WALLS SHOWN DASHED TO BE REMOVED TO FACILITATE WORK
B APPROXIMATE EXTENT OF MECHANICAL CHASE ABOVE SHOWN DASHED; VERIFY
IN FIELD. PROTECT ALL EXISTING FINISHES TO REMAIN.
N
S
W E
PLAN LEGEND
1 1
11 1 1 1 1
1 1 11
1 1 1 1 2 1 1 1
DUCTWORK IN CHASE ABV
CEILING
DUCTWORK IN
CHASE ABV CEILING
RECESSED CAN LIGHT FIXTURES
EXISTING TO REMAIN, UNO
REMOVE / REINSTALL AS NEEDED
TO EXECUTE THE WORK
EXIT SIGN - EXISTING TO REMAIN
REMOVE & RE-INSTALL AS NEEDED
TO EXECUTE THE WORK
EXHAUST FAN
(ETR) EXISTING TO REMAIN
UNLESS NOTED OTHERWISE
REMOVE & RE-INSTALLED
RETURN REGISTER
2'x2' SUSPENDED
CEILING GRID + TILES
TO BE REMOVED &
REPLACED, UNO
PERIMETER TRIM TO
REMAIN
GYPSUM CEILING
EMERGENCY WALL MOUNTED
EGRESS LIGHTING - EXISTING TO
REMAIN
REMOVE & RE-INSTALLED
2'x2' LIGHT FIXTURE
REMOVE & RE-INSTALLED
2'x4' LIGHT FIXTURE
NEW OR
REMOVE & RE-INSTALLED
DIFFUSER
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :0
P
M
AD131
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
D E M
O L
IT
IO
N
P L A N
L O
W E R L
E V E L C
E
IL
IN
G
WORKING DRAWINGS
216-B3216-015
1/8" = 1'-0"A211 AD131
1 LOWER LEVEL DEMO RCP
1. CONTRACTOR TO CONTACT OWNER PRIOR TO START OF DEMOLITION TO ALLOW OWNER TIME TO
REMOVE ANY MOVABLE EQUIPMENT.
2. COORDINATE PHASING OF DEMOLITION WITH THE OWNER.
3. ALL FIRE EXTINGUISHERS AND CABINETS TO REMAIN.
4. PROTECT ALL EXISTING WALL FINISHES THROUGH OUT THE CONSTRUCTION PERIOD.
5. REPAIR ALL CEILINGS TO MATCH EXISTING CEILINGS WHERE WALLS ARE TO BE DEMOLISHED AND
EXISTING CEILING IS TO REMAIN.
6. CONTRACTOR TO MATCH ALL EXISTING CONDITIONS FOR ALL REQUIRED MODIFICATIONS IN
RENOVATED AREAS (U.N.O.). THIS INCLUDES FINISH PATTERNS AND COLORS,
7. REPAIR HOLES IN EXISTING WALLS TO REMAIN WHERE WALL MOUNTED ITEMS ARE TO BE
REMOVED. MATCH FINISHES IN KIND, UNO.
8. CONTRACTOR TO PROTECT ALL EXISTING FLOORS, WALLS & CEILINGS DURING CONSTRUCTION
AND PROVIDE TEMPORARY PARTITIONS AS NEEDED. CONTRACTOR IS RESPONSIBILE FOR
REPAIR AND REPLACEMENT OF ALL DAMAGED FLOORING, WALLS, CEILINGS, ETC. FINISHES TO
MATCH EXISTING, UNO.
9. THE CONTRACTOR WILL BE RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL
DEMOLISHED MATERIALS. LEGALLY DISPOSE OF WASTE PER ENVIRONMENTAL PROTECTION
AGENCY (EPA) AND COMMONWEALTH OF VIRGINIA REQUIREMENTS.
10.. UNLESS SPECIFICALLY NOTED, ALL FLOOR COVERINGS & WALL BASE SHALL REMAIN. PROTECT
THROUGH-OUT CONSTRUCTION.
11. ADDITIONAL DEMOLITION MAY BE REQUIRED TO ACCOMMODATE NEW CONSTRUCTION SHOWN
ON OTHER SHEETS. CONTRACTOR TO REVIEW EXISTING CONDITIONS AND INCLUDE IN BASE BID
ALL DEMOLITION REQUIRED FOR A COMPLETE INSTALLATION.
12. WHERE PARTITIONS, EQUIPMENT, OR ACCESSORIES, ETC. ARE REMOVED AND NO REPLACEMENT FINISH IS CALLED FOR, THE GENERAL CONTRACTOR SHALL REPAIR TO MATCH ADJACENT FINISH.
13. IF ANY PORTION OF THE SPRINKLER SYSTEM IS TAKEN OUT OF SERVICE, PROVIDE A FIRE WATCH UNTIL THE SYSTEM IS FULLY OPERABLE. Ref. THE MEP DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
14. UNLESS NOTED OTHERWISE, ALL EXISTING CEILING GRIDS SHALL BE REMOVED EXCEPT FOR THE
L SHAPED PROFILE AROUND THE PERIMETER OF THE ROOM. EXISTING CEILING TILES TO BE
REMOVED. UNLESS NOTED OTHERWISE, LIGHTS SHALL BE REMOVED & RE-INSTALLED; ref.
ELECTRICAL DRAWINGS.
15. UNLESS NOTED OTHERWISE, ALL EXISTING CARPET AND WALL BASE TO REMAIN.
16. REMOVE & REINSTALL ALL WALL MOUNTED ITEMS TO REMAIN AS NEEDED TO EXECUTE WORK.
17. REFERENCE SPECIFICATION SECTION 02 41 00 - DEMOLITION FOR ADDITIONAL REQUIREMENTS.
18. COMPLY WITH NFPA 241 STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION &
DEMOLITION OPERATIONS.
19. IF REQUIRED, TEMPORARY LIGHTING SHALL BE PROVIDED BY THE CONTRACTOR.
20. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BID.
21. IF WORK REQUIRES REMOVAL OR ALTERATION OF MECHANICAL EQUIPMENT, REMOVE ANY
REFRIGERANT ACCORDING TO 40 CFR 82 & THE REGULATIONS OF THE AUTHORITIES HAVING
JURISDICTION.
22. UNLESS NOTED OTHERWISE, EXISTING WALL FINISHES AND COVERINGS TO REMAIN. PATCH &
REPAIR AS NEEDED.
GENERAL DEMOLITION NOTES
1 EXISTING INTERIOR CEILING GRID & TILES TO BE REMOVED. PERIMETER TRIM OF GRID TO
REMAIN TO THE GREATEST EXTENT POSSIBLE. REMOVE EXISTING LIGHTS, OCCUPANCY
SENSORS & HVAC GRILLES, RE-INSTALL AFTER COMPLETION OF ABOVE CEILING WORK.
2 EXISTING DRYWALL CEILING / BULKHEAD TO BE REMOVED TO FACILITATE DUCT
REPLACEMENT. WHERE HATCHED, LIMIT DEMO AS INDICATED TO AVOID DISTURBING
EXISTING TRANSITION TO VERTICAL SURFACES.
3 EXISTING DRYWALL @ VAULTED AREA HATCHED TO BE REMOVED FROM VERTICAL & SLOPED
SURFACES.
4 EXISTING ROOF ACCESS LADDER & HATCH TO REMAIN
KEYED DEMO PLAN NOTES 1
4'0 8' 16'
SCALE : 1/8" = 1' - 0"
N
S
W E
LEGEND - RCP SYMBOLS
1 1 1
1 1 1 1
1 1
1 1 1 11 1 1 111
A132
RECESSED CAN LIGHT FIXTURES
EXISTING TO REMAIN, UNO
REMOVE / REINSTALL AS NEEDED
TO EXECUTE THE WORK
EXIT SIGN - EXISTING TO REMAIN
REMOVE & RE-INSTALL AS NEEDED
TO EXECUTE THE WORK
EXHAUST FAN
(ETR) EXISTING TO REMAIN
UNLESS NOTED OTHERWISE
REMOVE & RE-INSTALLED
RETURN REGISTER
2'x2' SUSPENDED
CEILING GRID + TILES
TO BE REMOVED &
REPLACED, UNO
PERIMETER TRIM TO
REMAIN
GYPSUM CEILING
EMERGENCY WALL MOUNTED
EGRESS LIGHTING - EXISTING TO
REMAIN
REMOVE & RE-INSTALLED
2'x2' LIGHT FIXTURE
REMOVE & RE-INSTALLED
2'x4' LIGHT FIXTURE
NEW OR
REMOVE & RE-INSTALLED
DIFFUSER
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :0
P
M
AD132
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
D E M
O L
IT
IO
N
P L A N
U
P P E R L
E V E L C
E
IL
IN
G
WORKING DRAWINGS
216-B3216-015
1/8" = 1'-0"A211 AD132
1 UPPER LEVEL DEMO RCP
1. CONTRACTOR TO CONTACT OWNER PRIOR TO START OF DEMOLITION TO ALLOW OWNER TIME TO
REMOVE ANY MOVABLE EQUIPMENT.
2. COORDINATE PHASING OF DEMOLITION WITH THE OWNER.
3. ALL FIRE EXTINGUISHERS AND CABINETS TO REMAIN.
4. PROTECT ALL EXISTING WALL FINISHES THROUGH OUT THE CONSTRUCTION PERIOD.
5. REPAIR ALL CEILINGS TO MATCH EXISTING CEILINGS WHERE WALLS ARE TO BE DEMOLISHED AND
EXISTING CEILING IS TO REMAIN.
6. CONTRACTOR TO MATCH ALL EXISTING CONDITIONS FOR ALL REQUIRED MODIFICATIONS IN
RENOVATED AREAS (U.N.O.). THIS INCLUDES FINISH PATTERNS AND COLORS,
7. REPAIR HOLES IN EXISTING WALLS TO REMAIN WHERE WALL MOUNTED ITEMS ARE TO BE
REMOVED. MATCH FINISHES IN KIND, UNO.
8. CONTRACTOR TO PROTECT ALL EXISTING FLOORS, WALLS & CEILINGS DURING CONSTRUCTION
AND PROVIDE TEMPORARY PARTITIONS AS NEEDED. CONTRACTOR IS RESPONSIBILE FOR
REPAIR AND REPLACEMENT OF ALL DAMAGED FLOORING, WALLS, CEILINGS, ETC. FINISHES TO
MATCH EXISTING, UNO.
9. THE CONTRACTOR WILL BE RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL
DEMOLISHED MATERIALS. LEGALLY DISPOSE OF WASTE PER ENVIRONMENTAL PROTECTION
AGENCY (EPA) AND COMMONWEALTH OF VIRGINIA REQUIREMENTS.
10.. UNLESS SPECIFICALLY NOTED, ALL FLOOR COVERINGS & WALL BASE SHALL REMAIN. PROTECT
THROUGH-OUT CONSTRUCTION.
11. ADDITIONAL DEMOLITION MAY BE REQUIRED TO ACCOMMODATE NEW CONSTRUCTION SHOWN
ON OTHER SHEETS. CONTRACTOR TO REVIEW EXISTING CONDITIONS AND INCLUDE IN BASE BID
ALL DEMOLITION REQUIRED FOR A COMPLETE INSTALLATION.
12. WHERE PARTITIONS, EQUIPMENT, OR ACCESSORIES, ETC. ARE REMOVED AND NO REPLACEMENT FINISH IS CALLED FOR, THE GENERAL CONTRACTOR SHALL REPAIR TO MATCH ADJACENT FINISH.
13. IF ANY PORTION OF THE SPRINKLER SYSTEM IS TAKEN OUT OF SERVICE, PROVIDE A FIRE WATCH UNTIL THE SYSTEM IS FULLY OPERABLE. Ref. THE MEP DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
14. UNLESS NOTED OTHERWISE, ALL EXISTING CEILING GRIDS SHALL BE REMOVED EXCEPT FOR THE
L SHAPED PROFILE AROUND THE PERIMETER OF THE ROOM. EXISTING CEILING TILES TO BE
REMOVED. UNLESS NOTED OTHERWISE, LIGHTS SHALL BE REMOVED & RE-INSTALLED; ref.
ELECTRICAL DRAWINGS.
15. UNLESS NOTED OTHERWISE, ALL EXISTING CARPET AND WALL BASE TO REMAIN.
16. REMOVE & REINSTALL ALL WALL MOUNTED ITEMS TO REMAIN AS NEEDED TO EXECUTE WORK.
17. REFERENCE SPECIFICATION SECTION 02 41 00 - DEMOLITION FOR ADDITIONAL REQUIREMENTS.
18. COMPLY WITH NFPA 241 STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION &
DEMOLITION OPERATIONS.
19. IF REQUIRED, TEMPORARY LIGHTING SHALL BE PROVIDED BY THE CONTRACTOR.
20. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BID.
21. IF WORK REQUIRES REMOVAL OR ALTERATION OF MECHANICAL EQUIPMENT, REMOVE ANY
REFRIGERANT ACCORDING TO 40 CFR 82 & THE REGULATIONS OF THE AUTHORITIES HAVING
JURISDICTION.
22. UNLESS NOTED OTHERWISE, EXISTING WALL FINISHES AND COVERINGS TO REMAIN. PATCH &
REPAIR AS NEEDED.
GENERAL DEMOLITION NOTES
1 EXISTING INTERIOR CEILING GRID & TILES TO BE REMOVED. PERIMETER TRIM OF GRID TO
REMAIN TO THE GREATEST EXTENT POSSIBLE. REMOVE EXISTING LIGHTS, OCCUPANCY
SENSORS & HVAC GRILLES, RE-INSTALL AFTER COMPLETION OF ABOVE CEILING WORK.
2 EXISTING DRYWALL CEILING / BULKHEAD TO BE REMOVED TO FACILITATE DUCT
REPLACEMENT. WHERE HATCHED, LIMIT DEMO AS INDICATED TO AVOID DISTURBING
EXISTING TRANSITION TO VERTICAL SURFACES.
3 EXISTING DRYWALL @ VAULTED AREA HATCHED TO BE REMOVED FROM VERTICAL & SLOPED
SURFACES.
4 EXISTING ROOF ACCESS LADDER & HATCH TO REMAIN
KEYED DEMO PLAN NOTES 1
4'0 8' 16'
SCALE : 1/8" = 1' - 0"
N
S
W E
LEGEND - RCP SYMBOLS
GENERAL CONDITIONS:
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2018 (VCC) VIRGINIA CONSTRUCTION CODE AND THE 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN DATED
SEPTEMBER 15, 2010.
2. THE DOCUMENTS REFLECT CONDITIONS REASONABLY INTERPRETED FROM THE EXISTING VISIBLE CONDITIONS &/OR FROM DRAWINGS & INFORMATION FURNISHED BY THE OWNER. THE CONTRACTOR SHALL VISIT THE SITE AND BE RESPONSIBLE FOR VERIFYING EXISTING CONDITIONS AND THEIR IMPACT ON THE SCOPE OF THE WORK. ANY DISCREPANCIES BETWEEN EXISTING AND INDICATED CONDITIONS SHALL BE REPORTED IMMEDIATELY TO THE DESIGNATED PROJECT MANAGER. WORK
SHALL PROCEED ONLY WITH THE PROJECT MANAGER'S APPROVAL.
3. SHOULD THE CONTRACTOR REQUIRE ANY ADDITIONAL DETAILS OR VERBAL CLARIFICATION NECESSARY FOR THE PROPER EXECUTION OF THE WORK, A WRITTEN REQUEST FOR INFORMATION SHALL BE SUBMITTED TO THE PROJECT MGR. IN A TIMELY MANNER SO AS NOT TO IMPEDE THE PROJECT SCHEDULE.
4. THE CONTRACTOR SHALL BE AFFORDED ACCESS TO THE SITE IN ACCORDANCE WITH THE RULES AND REGULATIONS OF JAMES MADISON UNIVERSITY. THE REASONABLE USE OF THE CAMPUS WATER & ELECTRICITY AS REQUIRED FOR THE EXECUTION OF THE WORK IS AVAILABLE TO THE CONTRACTOR AT NO CHARGE TO THE CONTRACTOR. THE CONTRACTOR MAY USE THE TOILET ROOMS AS DIRECTED BY THE DESIGNATED PROJECT MANAGER.
5. CONTRACTOR SHALL INSTALL AND/ OR CONSTRUCT ALL PRODUCTS AND MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND INDUSTRY
STANDARDS.
6. ALL MATERIALS SHALL BE AS INDICATED IN THE DOCUMENTS. SUBSTITUTION REQUESTS SHALL BE SUBMITTED IN WRITING TO THE PROJECT MGR.
7. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING WORK. ANY DAMAGE TO EXISTING WORK CAUSED AS A RESULT OF THE EXECUTION OF THIS PROJECT SHALL BE REPAIRED BY THE GENERAL CONTRACTOR, AS REQUIRED AT THE SOLE EXPENSE OF THE GENERAL CONTRACTOR.
8. THE CONTRACTOR SHALL SECURE THE CONSTRUCTION AREA AND RESTRICT ACCESS TO AUTHORIZED PERSONNEL ONLY.
9. UNLESS INSTRUCTED OTHERWISE BY JMU's PROJECT MGR. , THE REMOVAL AND DISPOSAL OF DEMOLITION AND/OR CONSTRUCTION MATERIAL SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL KEEP THE CONSTRUCTION SITE FREE AND CLEAR OF ALL DEBRIS THROUGHOUT THE COURSE OF THE PROJECT. UPON COMPLETION OF THE WORK, THE ENTIRE CONSTRUCTION AREA IS TO BE THOROUGHLY CLEANED.
10. THE ELECTRICAL, PLUMBING, MECHANICAL & FIRE PROTECTION (SPRINKLER) WORK PRESENTED IN THESE DOCUMENTS IS INTENDED TO SHOW THE GENERAL ARRANGEMENT AND LOCATION OF EXISTING AND PROPOSED FIXTURES, EQUIPMENT AND ACCESSORIES. THE CONTRACTOR SHALL MODIFY EXISTING SYSTEMS TO
ACCOMMODATE THE NEW WORK AND AS REQUIRED TO MEET ALL APPLICABLE CODES.
11. THE CONTRACTOR SHALL PROVIDE "RECORD" DRAWINGS & SPECIFICATIONS FOR THE OWNER'S RECORDS INDICATING ANY AND ALL MODIFICATIONS TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION WORK. DRAWINGS SHALL BE REPRODUCIBLE, AND SHALL BE DATED AND SIGNED BY THE CONTRACTOR
AND APPROPRIATE SUBCONTRACTOR(S).
12. ALL WORK SHALL BE GUARANTEED BY THE CONTRACTOR FOR A PERIOD OF ONE YEAR AS DEFINED BY THE GENERAL CONDITIONS OF THE CONSTRUCTION
CONTRACT ARTICLE 45.
13. TEST ALL SYSTEMS PRIOR TO CLOSE-OUT TO ENSURE THAT ALL SYSTEMS ARE WORKING PROPERLY.
14. ALL PROSPECTIVE BIDDERS SHALL VISIT THE JOB SITE AND BECOME ACQUAINTED WITH THE PROJECT SITE AND SCOPE PRIOR TO SUBMISSION OF BID.
15. THE CONTRACTOR AND ITS SUB-CONTRACTORS SHALL BID THE COMPLETE DRAWING & SPECIFICATION SET INCLUDING ALL DISCIPLINES AS THESE ARE INTENDED
TO BE COMPLIMENTARY DOCUMENTS.
FIELD COORDINATION:
1. THE GENERAL CONTRACTOR SHALL VERIFY AND LOCATE UTILITIES, EXISTING FACILITIES AND EQUIPMENT.
2. SURVEY AND LAYOUT ALL IMPROVEMENTS, UTILITIES, STRUCTURES AND COMPONENTS.
3. COORDINATE THE WORK OF ALL TRADES.
4. VERIFY LOCATION OF UTILITIES AND EXISTING CONDITIONS. NOTIFY THE PROJECT MANAGER OF CONDITIONS DIFFERING FROM THOSE INDICATED ON THE
DRAWINGS.
5. VERIFY DIMENSIONS ON DRAWINGS WITH DIMENSIOSN AT THE PROJECT SITE. DO NOT SCALE CONTRACT DOCUMENTS.
6. COORDINATE ALL INSPECTIONS WITH THE DESIGNATED PROJECT MANAGER & UNIVERSITY INSPECTORS
GENERAL CONSTRUCTION NOTES:
1. ALL PENETRATIONS THROUGH FLOOR SLABS SUCH AS PIPING, CONDUITS, DUCTS, PNEUMATIC TUBES, ETC., SHALL BE PACKED AND SEALED WITH APPROPRIATE FIRE-RATED MATERIAL IN COMPLIANCE WITH APPLICABLE BUILDING CODES. PENETRATIONS SHALL BE SEALED WATER TIGHT. REFERENCE DETAILS FOR SPECIFIC
INFORMATION.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND INSTALLATION OF ADEQUATE SHORING AND BRACING REQUIRED FOR THE PROPER EXECUTION
OF ALL WORK.
3. NEW WORK EXTENDING EXISTING CONDITIONS SHALL ALIGN WITH AND MATCH EXISTING WORK EXCEPT WHERE OTHERWISE DIMENSIONED OR DETAILED.
4. STRUCTURAL STUDS SHALL BE USED WHEREVER NON SELF-SUPPORTING WALL-HUNG FIXTURES, EQUIPMENT, OR CABINETRY OCCURS. INSTALL BLOCKING IN
ACCORDANCE WITH TYPICAL BLOCKING DETAIL. BRACE ALL PARTITIONS AS REQUIRED.
5. MAINTAIN EXISTING EXITS AND PATHS OF EGRESS NOT WITHIN THE PROJECT AREA. IF THE PROJECT IMPACTS THESE ELEMENTS, COORDINATE TO THE
SATISFACTION OF THE UNIVERSITIES PROJECT MANAGER.
SITE REQUIREMENTS:
1. PARKING TO BE COORDINATED WITH AND APPROVED BY THE DESIGNATED PROJECT MANAGER.
2. MAINTAIN BUILDING ACCESS & EGRESS DURING CONSTRUCTION PERIOD.
PROJECT PHASING:
1. SUBMIT A PROJECT SCHEDULE AND PHASING PLAN TO THE AGENCY'S DESIGNATED PROJECT MANAGER PRIOR TO INITIATING ACTIVITIES. DO NO INITIATE WORK
WITHOUT AGENCY APPROVAL.
2. PHASE THE WORK TO MINIMIZE IMPACT UPON THE BUILDING'S USE AND OCCUPANCY.
FINISH WORK:
1. PATCH & REPAIR ALL CEILING AND WALL FINISHES IN KIND THAT ARE DISTURBED BY DEVICE REMOVAL, REPLACEMENT AND/OR NEW INSTALLATION WORK.
2. CAULK AND SEAL ALL PENETRATIONS; ref. ELECTRICAL DRAWINGS.
3. WHERE PAINTING IS REQUIRED, PAINT WALL OR CEILING TO EXTENT NECESSARY TO BLEND WITH EXISTING. EXECUTE TO THE SATISFACTION OF THE AGENCY'S
PROJECT MANAGER.
4. IF RATED PARTITIONS ARE ENCOUNTERED, NOTIFY THE PROJECT MANAGER.
SUBMITTALS:
1. REFERENCE SPECIFICATION SECTION 01 30 00 - ADMINISTRATIVE REQUIREMENTS FOR SUBMITTAL REQUIREMENTS.
SCHEDULE:
1. REFERENCE SPECIFICATION SECTION 01 32 16 - CONSTRUCTION PROGRESS SCHEDULE FOR SCHEDULE REQUIREMENTS.
QUALITY ASSURANCES:
1. THE GENERAL CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES, REGULATIONS, ORDINANCES AND REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION, INCLUDING ACCESSIBILITY GUIDELINES. SUBMIT COPIES OF INSPECTION REPORTS, NOTICES AND SIMILAR DOCUMENTS TO JMU's DESIGNATED PROJECT MANAGER.
2. SHALL PROVIDE PRODUCTS OF ACCEPTABLE MANUFACTURERS WHICH HAVE BEEN IN SATISFACTORY USE IN SIMILAR SERVICE FOR THREE YEARS.
3. SHALL USE EXPERIENCED INSTALLERS. FURNISH EVIDENCE OF EXPERIENCE TO JMU's DESIGNATED PROJECT MANAGER IF REQUESTED.
4. SHALL DELIVER, HANDLE, AND STORE MATERIALS IN STRICT ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
BASE AS SCHEDULED
GWB ON 2X4 WOOD STUDS
CEILING AS
SCHEDULED
1 EXISTING PARTITIONS
EXISTING FLOOR OR ROOF
METAL DECK
BUILDING INSULATION
(N T
S
V E
R
IF
Y I N
F
IE
L D
DETAIL PROVIDED FOR GENERAL REFERENCE ONLY TO ILLUSTRATE EXISTING PARTITION
CONSTRUCTION
BASE - MATCH EXISTING IN KIND
NOTE: DO NOT ATTACH GWB OR STUDS
TO DEFLECTION TRACK
STEEL STUDS @ 24" O.C. MAX OR AS REQUIRED
BY MFR's WALL HEIGHT LIMITS & MAXIMUM DEFLECTION - GAUGE PER MFR's REQ'Ts
NOTE: REFER TO PARTITION WIDTH
LEGEND FOR STUD WIDTH
1" THICK GYPSUM BD LINER PANEL
CONTINUOUS 22 GAUGE 2" WIDE METAL STRAP.
ATTACH GWB AT 8" O.C.
CONTINUOUS 30 MIL DEEP LEG DEFLECTION
TRACK ATTACHED TO DECK AT 12" O.C. MAX
STEEL C-H STUD
2 SHAFT WALL PARTITION
VARIES
VIF
J-SHAPED UNEQUAL LEG RUNNERS
5/8" GWB
ACOUSTICAL SEALANT, TOOLED FLUSH WITH
DRYWALL
SOUND ATTENUATION BATT INSUL, FILL STUD WIDTH
CEILING AS
SCHEDULED
CHASE SIDE
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :0
P
M
A012
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
G E N
E R A L N
O T E S
D E T A
IL
S
WORKING DRAWINGS
216-B3216-015
3" = 1'-0"A012
1 PARTITION TYPE 1
3" = 1'-0"A012
2 PARTITION TYPE 2
REVISIONS
UP
CONFERENCE
ROOM
OFFICE
OFFICE
1030A
OFFICE
OFFICE
OFFICE
MECHANICAL
M1040
ELEV
M1041
STOR
1000A
STOR
1000B
STORAGE
ELEC
M1001
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
1026 OFFICE
BREAK
ROOM
OFFICE
OFFICE
OFFICE
CALL
CENTER
COPY
WOMEN
T1034
CONFERENCE
ROOM
JAN.
J1002
OFFICE
SERVICE
OFFICE
MEN
T1004
OFFICE
OFFICE
OFFICE
OFFICE
A301
ELEVATOR
E199
STAIR
S199
PRD
OFFICE
1030B
A302
A302
A301
A303
A303
OFFICE
1014B
CHASE 1
CHASE 2
EXISTING DOOR TO REMAIN
EXISTING PARTITION TO REMAIN
EXISTING PARTITION
TO BE DEMOLISHED
DEMOLITION KEY NOTE1
1 HR FIRE BARRIER
NEW PARTITION
PLAN KEY NOTE1
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :1
P
M
A111
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
L O
W E R L
E V E L F
L O
O R P
L A N
WORKING DRAWINGS
216-B3216-015
1/8" = 1'-0"A211 A111
1 LOWER LEVEL FLOOR PLAN AND NOTES
GENERAL PLAN NOTES
1. ALL NEW PARTITIONS SHALL BE PARTITION TYPE '2' UNLESS NOTED OTHERWISE.
2. PROTECT EXISTING FINISHES TO REMAIN.
3. ALL DIMENSIONS ARE TO FACE OF WALL FINISH OR COLUMN CENTERLINE
UNLESS NOTED OTHERWISE.
4. UNLESS NOTED OTHERWISE, FIXTURES, FURNISHINGS AND EQUIPMENT (FF&E)
ARE BY THE AGENCY; NOT IN CONTRACT.
5. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
PLAN LEGEND
1 RECONSTRUCTED CHASE WALL. REPAINT ENTIRE WALL, CORNER TO CORNER.
REPLACE WALL BASE IN KIND FOR FULL LENGTH OF WALL.
2 APPROX EXTENT OF MECHANICAL CHASE ABV. (SHOWN DASHED), VERIFY IN THE
FIELD
3 PROVIDE 24"x24" min. WALL ACCESS PANEL. EXACT LOCATION: TBD
FLOOR PLAN KEY NOTES
4'0 8' 16'
SCALE : 1/8" = 1' - 0"
N
S
W E
DNOFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
2031 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
2045 BREAKROOM
STORE
ROOM
OFFICE
OFFICE
CONFERENCE
ROOM
LOUNGE
WOMEN
T2006
OFFICE
CONF RM
OFFICE
OFFICE
OFFICE
2015STORAGE
OFFICE
SERVICE
MEN
T2003
OFFICE
OFFICE
CONF RM
OFFICE
OFFICE
ELEV
E299
JAN
J2002
RECEPTION
WAITING
RECEPTION
CORRIDOR
C2998
CLO.
A301
STAIR
S299
ENTRY
VESTIBULE
C2000
CORRIDOR
C2997
A302
A302
A301
2 2
A303
A303
CHASE 1
CORRIDOR
C2999
3 3
CHASE 2
EXISTING DOOR TO REMAIN
EXISTING PARTITION TO REMAIN
EXISTING PARTITION
TO BE DEMOLISHED
DEMOLITION KEY NOTE1
1 HR FIRE BARRIER
NEW PARTITION
PLAN KEY NOTE1
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :1
P
M
A122
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
U P P E R L
E V E L F
L O
O R P
L A N
WORKING DRAWINGS
216-B3216-015
1/8" = 1'-0"A211 A122
1 UPPER LEVEL FLOOR PLAN AND NOTES
GENERAL PLAN NOTES
1. ALL NEW PARTITIONS SHALL BE PARTITION TYPE '2' UNLESS NOTED OTHERWISE.
2. PROTECT EXISTING FINISHES TO REMAIN.
3. ALL DIMENSIONS ARE TO FACE OF WALL FINISH OR COLUMN CENTERLINE
UNLESS NOTED OTHERWISE.
4. UNLESS NOTED OTHERWISE, FIXTURES, FURNISHINGS AND EQUIPMENT (FF&E)
ARE BY THE AGENCY; NOT IN CONTRACT.
5. REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
PLAN LEGEND
1 RECONSTRUCTED CHASE WALL. REPAINT ENTIRE WALL, CORNER TO CORNER.
REPLACE WALL BASE IN KIND FOR FULL LENGTH OF WALL.
2 APPROX EXTENT OF MECHANICAL CHASE ABV. (SHOWN DASHED), VERIFY IN THE
FIELD
3 PROVIDE 24"x24" min. WALL ACCESS PANEL. EXACT LOCATION: TBD
FLOOR PLAN KEY NOTES
4'0 8' 16'
SCALE : 1/8" = 1' - 0"
N
S
W E
J
J
J
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OSOS
OS
OS
OS OS OS
OSOSOSOS
OS
OS
OS
OS
OS
OS
OS
RECESSED CAN LIGHT FIXTURES
EXISTING TO REMAIN, UNO
REMOVE / REINSTALL AS NEEDED
TO EXECUTE THE WORK
EXIT SIGN - EXISTING TO REMAIN
REMOVE & RE-INSTALL AS NEEDED
TO EXECUTE THE WORK
EXHAUST FAN
(ETR) EXISTING TO REMAIN
UNLESS NOTED OTHERWISE
REMOVE & RE-INSTALLED
RETURN REGISTER
2'x2' SUSPENDED
CEILING GRID + TILES
TO BE REMOVED &
REPLACED, UNO
PERIMETER TRIM TO
REMAIN
GYPSUM CEILING
EMERGENCY WALL MOUNTED
EGRESS LIGHTING - EXISTING TO
REMAIN
REMOVE & RE-INSTALLED
2'x2' LIGHT FIXTURE
REMOVE & RE-INSTALLED
2'x4' LIGHT FIXTURE
NEW OR
REMOVE & RE-INSTALLED
DIFFUSER
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
1012OFFICE
MEN
T1004
OFFICE
SERVICE
JAN.
J1002
CONFERENCE
ROOM
COPY
WOMEN
T1034
CALL
CENTER
BREAK
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
CONFERENCE
ROOM
OFFICE
OFFICE
1030A
OFFICE
OFFICE
OFFICE
MECHANICAL
M1040
STORAGE
ELEC
M1001ELEV
M1041
STOR
1000A
STOR
1000B
OFFICE
OFFICE
OFFICE
A301
OFFICE
1030B
PRD
1031 A
A
A
A
A
A
A
A
A
A
A
A A
A
A
A A
A
A A
A
C
C
C
A302
A
A
A
A
A
B
B
A302
A301
A303
A303
A AAA
A A A
A
AAA
A
OFFICE
1014B
F
A
A
A
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :1
P
M
A131
NOVEMBER 10, 2023
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
L O
W E R L
E V E L F
L O
O R R
E F L E C T E D
C E
IL
IN
G
P L A N
WORKING DRAWINGS
216-B3216-015
GENERAL NOTES - REFLECTED CEILING PLAN
KEYED NOTES - REFLECTED CEILING PLAN 1
1.
FIELD VERIFY INDICATED LIGHT FIXTURE LOCATIONS - UPDATE FIELD SET TO IDENTIFY
DEVIATIONS. RE-INSTALL FIXTURES ACCORDINGLY.
2.
LIGHTS, SPRINKLER HEADS, HVAC GRILLES SMALLER THAN 2 BY 2 FEET, TO BE
CENTERED ON TILE, TYPICAL, UNLESS NOTED OTHERWISE
3.
REFER TO MEP DRAWINGS FOR EXACT LOCATION AND SPECIFICATION OF
EMERGENCY EGRESS AND LIGHTING EXIT FIXTURES.
4.
ALL LIGHT FIXTURES ARE DIMENSIONED TO CENTER OF FIXTURE, UNLESS NOTED
OTHERWISE
5. SEE SPECIFICATION DIVISION 09 FOR ACT CEILING TYPE
6. ALL CEILING HEIGHTS ARE EXISTING; VERIFY IN THE FIELD.
7.
PRIOR TO MODIFICATIONS TO CEILINGS, THE CONTRACTOR SHALL VERIFY EXISTING
CONDITIONS. THE CONTRACTORS SHALL REVIEW THIS INFORMATION WITH THE PROJ
MGR. & BRING ANY SUSPECTED DISCREPANCIES TO THE ATTENTION OF THE OWNERS
REPRESENATIVE FOR RESOLUTION PRIOR TO CONSTRUCTION.
8. IF DISTURBED, CENTER EXIT SIGNS OVER DOORS UNLESS NOTED OTHERWISE.
9. ALIGN FACE OF SOFFIT WITH FACE OF PARTITION, TYPICAL.
10.
SEE MECHANICAL, ELECTRICAL, AND EQUIPMENT DRAWINGS FOR ADDITIONAL
CEILING FIXTURE SYMBOLOGY.
11. LIGHTS TO BE CENTERED ON TILE, TYPICAL UNLESS NOTED OTHERWISE.
12. WIRING DEVICES ARE TO MATCH EXISTING
13. EACH SPACE TO BE INDIVIDUALLY SWITCHED UNLESS NOTED OTHERWISE.
14.
COVER PLATES ON WALLS SHALL MATCH EXISTING, PLATES TO BE STANDARD SIZE
(OVERSIZED PLATES ARE NOT ACCEPTABLE).
15.
COORDINATE ALL FIRE SAFETY EQUIPMENT, INCLUDING EXIT SIGNS, EMERGENCY
BACK-UP LIGHTS, AUDIO AND VISUAL ALARMS, PULL STATIONS, ETC AS REQUIRED BY
ALL APPLICABLE CODES AND ORDINANCES HAVING JURISDICTION ON THIS PROJECT
WITH CONTRACTOR. REFER TO MEP DRAWINGS FOR EXACT LOCATION AND
SPECIFICATION OF EMERGENCY EGRESS AND LIGHTING AND EXIT FIXTURES.
16.
CONTRACTOR SHALL PROVIDE LIGHT FIXTURE CUT SHEETS FOR ARCHITECT'S
APPROVAL, PRIOR TO ORDERING. NO SUBSTITUTIONS SHALL BE SUBMITTED UNLESS
AVAILABILITY OF FIXTURE IS PROHIBITIVE TO MEETING THE PROJECT SCHEDULE.
17.
ALL UNDER CABINET LIGHTING TO BE HARD WIRED. REFER TO ELECTRICAL DRAWINGS
FOR DETAILS
18.
PROVIDE T-BAR HOLD DOWN CLIPS ON ALL FIXTURES WITHIN 20 FEET OF AN
EXTERIOR DOOR.
19.
UNLESS NOTED OTHERWISE, EXISTING CEILING GRID TO REMAIN; PROVIDE NEW
ACOUSTICAL CEILING TILE
20.
FIELD VERIFY PROPOSED DIFFUSER LAYOUT RELATIVE TO EXISTING GRID LAYOUT.
NOTIFY PROJECT MANAGER IF GRID PRIMARY SUPPORT PROHIBIT PROPOSED
LAYOUT.
21.
REFERENCE ELECTRICAL DRAWINGS FOR WIRELESS ACCESS POINTS & CONDUIT
REQUIREMENTS
LEGEND - RCP SYMBOLS
A NEW CEILING GRID WITH NEW CEILING TILES. EXISTING PERIMETER TRIM SHALL
REMAIN TO THE GREATEST EXTENT POSSIBLE. REINSTALL EXISTING LIGHTS &
GRILLES.
B NEW DRYWALL CEILING &/OR BULKHEAD. REPLACE & REPAINT CEILING WHITE, UNO.
IF CONSTRUCTION REQUIRES REMOVAL OF ANY EXISTING FRAMING, REPLACE IN KIND.
C EXISTING EXTERIOR SOFFIT / CEILING TO REMAIN
D VAULTED INTERIOR DRYWALL CEILINGS TO BE REPLACED WHERE SHOWN, PAINT
CEILING WHITE. IF CONSTRUCTION REQUIRES REMOVAL OF ANY EXISTING FRAMING,
REPLACE IN KIND.
E REINSTALL PROJECTOR AFTER PAINTING. COORDINATE w/ UNIVERSITY MEDIA
RESOURCES.
F CEILING ACCESS PANEL: 24"x36"; VERIFY SIZE & COORDINATE EXACT LOCATION IN THE
FIELD
1/8" = 1'-0"A211 A131
1 LOWER LEVEL RCP
4'0 8' 16'
SCALE : 1/8" = 1' - 0"
N
S
W E
J
J
OS
OS
OS
OS
OS
OS
OS
OS
OS
OSOS
OS
OS OS
OS
OS OS
OS OS
OS
OS
OS
OS
OS
OS
OS OS OS OS OS OS
OS OS OS
OS
OS
OSOSOSOS
OS
OS
OSOS OS
RECEPTION
BREAKROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
RECEPTION
WOMEN
T2006
LOUNGE
CONFERENCE
ROOM
OFFICE
OFFICE
STORE
ROOM
ELEV
E299
JAN
J2002
WAITING
OFFICE
CONF RM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
CONF RM
OFFICE
STORAGE
OFFICE
SERVICE
MEN
T2003
A301
A
A
A A
A
A
A
A
A
A
A
A
A
A
A
A
A
B
B
BB
B B
C C
C C
D
D
B
D
A302
A
A
A
A
C
C
A302
A301
A303
A303
AA
A
A
A
A A A A A
A
A
AA
AAA
EXIST. ROOF
ACCESS HATCH
EXIST. ROOF ACCESS HATCH
B
B
B
B
E
RECESSED CAN LIGHT FIXTURES
EXISTING TO REMAIN, UNO
REMOVE / REINSTALL AS NEEDED
TO EXECUTE THE WORK
EXIT SIGN - EXISTING TO REMAIN
REMOVE & RE-INSTALL AS NEEDED
TO EXECUTE THE WORK
EXHAUST FAN
(ETR) EXISTING TO REMAIN
UNLESS NOTED OTHERWISE
REMOVE & RE-INSTALLED
RETURN REGISTER
2'x2' SUSPENDED
CEILING GRID + TILES
TO BE REMOVED &
REPLACED, UNO
PERIMETER TRIM TO
REMAIN
GYPSUM CEILING
EMERGENCY WALL MOUNTED
EGRESS LIGHTING - EXISTING TO
REMAIN
REMOVE & RE-INSTALLED
2'x2' LIGHT FIXTURE
REMOVE & RE-INSTALLED
2'x4' LIGHT FIXTURE
NEW OR
REMOVE & RE-INSTALLED
DIFFUSER
A132
1' - 4" (+/-)
EXISTING VERTICAL
DRYWALL TO REMAIN,
DO NOT DISTURB
EXISTING CORNER BEAD
TO REMAIN, DO NOT
DISTURB
CUT EXISTING DRYWALL
BACK FROM CORNER 12"
MIN.
EXISTING BULKHEAD
FRAMING ESTIMATED -
VERIFY IN FIELD
NEW DRYWALL
NEW BULKHEAD FINISH
SHOWN DASHED, WORK TO
EXISTING CORNER BEAD
EXISTING DUCTWORK TO
BE REMOVED & REPLACED
EXIST. LIGHT - REMOVE
& RE-INSTALL; TYP.
CHECKED:
DATE:
DRAWN:
F
IL
E N
A M
E
P L O
T T
IM
E
DEB PROJECT #:
STATE BUILDING OFFICIAL APPROVAL STAMP
C
U se rs \s te tt e rt o n \D o cu m e n ts
\2 -0
J
M U
S o n n e r
H a ll
H V A C rv t2 st e tt e rt o n A F N
J.
rv t
/1
/2
:2 :2
P
M
A132
NOVEMBER 10, 2023
Author
Checker
S o n n e r
H a ll
H V A C R e p la ce m e n t
Ja m e s
M a d is o n U n iv e rs it y
B lu e s to n e D ri v e
H a rr is o n b u rg
V ir g in ia
U P P E R L
E V E L F
L O
O R R
E F L E C T E D
C E
IL
IN
G
P L A N
WORKING DRAWINGS
216-B3216-015
1/8" = 1'-0"A211 A132
1 UPPER LEVEL RCP
GENERAL NOTES - REFLECTED CEILING PLAN
KEYED NOTES - REFLECTED CEILING PLAN 1
1.
FIELD VERIFY INDICATED LIGHT FIXTURE LOCATIONS - UPDATE FIELD SET TO IDENTIFY
DEVIATIONS. RE-INSTALL FIXTURES ACCORDINGLY.
2.
LIGHTS, SPRINKLER HEADS, HVAC GRILLES SMALLER THAN 2 BY 2 FEET, TO BE
CENTERED ON TILE, TYPICAL, UNLESS NOTED OTHERWISE
3.
REFER TO MEP DRAWINGS FOR EXACT LOCATION AND SPECIFICATION OF
EMERGENCY EGRESS AND LIGHTING EXIT FIXTURES.
4.
ALL LIGHT FIXTURES ARE DIMENSIONED TO CENTER OF FIXTURE, UNLESS NOTED
OTHERWISE
5. SEE SPECIFICATION DIVISION 09 FOR ACT CEILING TYPE
6. ALL CEILING HEIGHTS ARE EXISTING; VERIFY IN THE FIELD.
7.
PRIOR TO MODIFICATIONS TO CEILINGS, THE CONTRACTOR SHALL VERIFY EXISTING
CONDITIONS. THE CONTRACTORS SHALL REVIEW THIS INFORMATION WITH THE PROJ
MGR. & BRING ANY SUSPECTED DISCREPANCIES TO THE ATTENTION OF THE OWNERS
REPRESENATIVE FOR RESOLUTION PRIOR TO CONSTRUCTION.
8. IF DISTURBED, CENTER EXIT SIGNS OVER DOORS UNLESS NOTED OTHERWISE.
9. ALIGN FACE OF SOFFIT WITH FACE OF PARTITION, TYPICAL.
10.
SEE MECHANICAL, ELECTRICAL, AND EQUIPMENT DRAWINGS FOR ADDITIONAL
CEILING FIXTURE SYMBOLOGY.
11. LIGHTS TO BE CENTERED ON TILE, TYPICAL UNLESS NOTED OTHERWISE.
12. WIRING…