Summary of SUNY College of Environmental Science and Forestry Moon Library ADA Upgrades and Renovation
This is a comprehensive set of bid documents and construction drawings for the Moon Library ADA Upgrades and Renovation project located at 1 Forestry Drive, Syracuse, New York, prepared by Dwyer Architectural, LLC. The project involves the complete renovation of the lower level of the Moon Library to enhance accessibility, functionality, and the overall student experience. The scope of work includes: renovation and reconfiguration of existing toilet rooms to meet current ADA accessibility standards; creation of a new dedicated student space with flexible furnishings, improved lighting, and updated technology infrastructure; construction of a new fully accessible entrance on the north side of the building with vestibule; addition of a new vestibule to the existing south entrance to improve thermal performance and air infiltration control; hazardous materials abatement including asbestos, lead-containing paint, and PCB caulk removal; structural modifications including new masonry walls, metal decking, and stainless steel canopy support systems; and comprehensive plumbing system updates including new fixtures, piping for sanitary, storm, and domestic water systems. The project is identified as Project No. 24-055, with bid documents issued for May 8, 2026.
The project includes significant hazardous materials abatement requirements in compliance with 12 NYCRR Part 56, OSHA 1926.1101, NESHAPS 40 CFR Part 61, and AHERA 40 CFR Part 763. Approximate quantities for removal include: 5,560 linear feet of assumed AC thermal systems insulation; 75 linear feet of trace AC gray thermal systems insulation; 6 square feet of asbestos-contaminated ceiling tiles; 300 square feet of AC 9"x9" gray floor tile and associated mastic; 1,060 to 4,500 square feet of upper and lower level floor tile (depending on scope); 6 to 10 square feet of PCB-containing exterior window caulk. The contractor must coordinate all work with the Owner's representative and environmental consultant (Ravi Engineering & Land Surveying, P.C.). Minority/Women Business Enterprise (MWBE) contracting goals are established at 15% for both MBE and WBE, with a Service-Disabled Veteran-Owned Business (SDVOB) goal of 4%. The project mandates strict compliance with all hazardous materials regulations, comprehensive documentation of pre-existing conditions, maintenance of security in regulated work areas, and proper disposal of all contaminated materials through certified waste shipment records.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 201071 Project Specs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
abbieboglione Image
GENERAL ASBESTOS ABATEMENT NOTES APPLICABLE TO HM-SERIES
1. THE ASBESTOS ABATEMENT PLANS ARE BASED ON THE LIMITED PRE-RENOVATION HAZARDOUS MATERIALS INSPECTION REPORT PREPARED BY RAVI ENGINEERING & LAND SURVEYING, P.C. (RE&LS) DATED SEPTEMBER 2025, AND THE ARCHITECTURAL DEMO DRAWINGS PROVIDED BY DWYER, DATED
SEPTEMBER 2025.
2. THE ASBESTOS ABATEMENT CONTRACTOR (REFERRED TO AS "CONTRACTOR" HEREIN) SHALL
COORDINATE ALL ASBESTOS REMOVAL WORK WITH THE OWNER'S REPRESENTATIVE, OTHER
CONTRACTORS, AND PROJECT DRAWINGS.
3. APPROVAL OF THE QUANTITY AND EXTENT OF ADDITIONAL WORK (NOT SHOWN ON HM-SERIES) MUST BE APPROVED BY THE ENVIRONMENTAL CONSULTANT (RAVI ENGINEERING & LAND SURVEYING, P.C.) AND
OWNER PRIOR TO THE START OF WORK.
4. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, DIMENSIONS, AND QUANTITIES ASSOCIATED WITH HM-SERIES DRAWINGS AND SPECIFICATIONS PRIOR TO THE START OF WORK.
5. THE CONTRACTOR SHALL PERFORM ALL CONTRACT WORK IN ACCORDANCE WITH CONTRACT
DOCUMENTS INCLUDING DRAWINGS, SPECIFICATIONS, NEW YORK STATE DEPARTMENT OF LABOR
(NYSDOL) INDUSTRIAL CODE RULE 56, OSHA 1926.1101, NESHAPS 40 CFR PART 61, AHERA 40 CFR PART
763, AND ALL OTHER APPLICABLE CODES.
6. THE CONTRACTOR SHALL MAINTAIN SECURITY AS APPROVED TO BE ACCEPTABLE BY THE OWNER IN REGULATED ASBESTOS WORK AREAS AT ALL TIMES, FOR THE DURATION OF THE ASBESTOS ABATEMENT
PROJECT.
7. LOCATIONS FOR ASBESTOS DUMPSTERS AND PERSONAL / WASTE DECONTAMINATION UNITS SHALL BE
COORDINATED AND APPROVED WITH THE OWNER'S REPRESENTATIVE PRIOR TO MOBILIZATION.
8. IN ACCORDANCE WITH INDUSTRIAL CODE RULE 56, THE CONTRACTOR SHALL COORDINATE SHUT DOWN AND LOCK OUT OF ELECTRICAL POWER WITHIN THE REGULATED WORK AREAS WITH THE OWNER'S REPRESENTATIVE. ALL TEMPORARY POWER TO THE REGULATED WORK AREAS SHALL BE BROUGHT IN FROM OUTSIDE THE REGULATED WORK AREAS THROUGH A GROUND-FAULT CIRCUIT INTERRUPTER AT
THE SOURCE OF THE POWER THAT SHALL BE PROVIDED BY THE CONTRACTOR.
9. THE CONTRACTOR SHALL IDENTIFY THE LOCATION OF WATER SUPPLY PRIOR TO ESTABLISHMENT OF PERSONAL DECONTAMINATION UNITS. THE CONTRACTOR SHALL COORDINATE LOCATIONS OF WATER
SUPPLY WITH THE OWNER AND PLUMBING CONTRACTOR.
10. IN ACCORDANCE WITH INDUSTRIAL CODE RULE 56, THE CONTRACTOR SHALL CLEAN AND REMOVE NON-CONTAMINATED OBJECTS (FURNITURE, HARDWARE, LIGHTING, ETC.) FROM THE REGULATED WORK AREAS PRIOR TO BEGINNING PHASE IIA PREP ACTIVITIES. CLEANED OBJECTS SHALL BE TURNED OVER TO THE OWNER. CLEANED OBJECTS REMOVED AND REFUSED BY THE OWNER SHALL BE DISPOSED OF
AS NON-CONTAMINATED CONSTRUCTION DEBRIS BY THE CONTRACTOR.
11. VARIATIONS (+/- 10%) IN QUANTITIES AND LOCATIONS OF PREVIOUSLY IDENTIFIED
ASBESTOS-CONTAINING MATERIALS SHALL BE CONSIDERED AS HAVING NO IMPACT ON CONTRACT PRICE AND/OR SCHEDULE OF THIS CONTRACT. ADDITIONAL QUANTITIES SHALL BE VERIFIED BY A CERTIFIED
PROJECT MONITOR DURING REMOVAL ACTIVITIES.
12. THE OWNER SHALL BE RESPONSIBLE TO CONTRACT FOR NYSDOL PROJECT MONITORING/AIR SAMPLING
TECHNICIAN SERVICES. OSHA PERSONAL AIR MONITORING IS THE RESPONSIBILITY OF THE
CONTRACTOR. OSHA PERSONAL AIR MONITORING SHALL BE PERFORMED DAILY IN ACCORDANCE WITH
OSHA 1926.1101.
13. THE CONTRACTOR SHALL REQUEST AND RECEIVE WRITTEN APPROVAL FROM THE PROJECT MONITOR
AND OWNER'S REPRESENTATIVE PRIOR TO BEGINNING ASBESTOS ABATEMENT ACTIVITIES.
14. IN ACCORDANCE WITH INDUSTRIAL CODE RULE 56, THE CONTRACTOR SHALL HEPA VACUUM EXISTING
NON-MOVABLE EQUIPMENT PRIOR TO COVERING WITH PROTECTIVE PLASTIC SHEETING.
15. UNDER NO CIRCUMSTANCES SHALL CONTAMINATED WASTEWATER ENTER THE SANITARY SEWER SYSTEM. ALL WASTEWATER SHALL BE FILTERED THROUGH A SYSTEM EQUIPPED WITH A 5.0 MICRON, OR SMALLER, PARTICLE SIZE COLLECTION CAPABILITY IN ACCORDANCE WITH 12 NYCRR PART 56.
16. IF LIQUID (INCLUDING WATER, SOLVENTS, SURFACTANTS, AND / OR ENCAPSULANTS) LEAKS THROUGH THE CONTAINMENT AREAS, OR FROM THE DECONTAMINATION UNITS, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL WATER DAMAGE AND REPAIR. THE CONTRACTOR SHALL DOCUMENT ALL
PRE-EXISTING WATER DAMAGE PRIOR TO ESTABLISHING CONTAINMENT AREAS.
17. IF KNOWN OR SUSPECT ASBESTOS-CONTAINING MATERIAL IS DISCOVERED, NOT PREVIOUSLY IDENTIFIED, THE CONTRACTOR SHALL CEASE OPERATIONS AND NOTIFY THE OWNER AND/OR OWNER'S
REPRESENTATIVE IMMEDIATELY.
18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ANY SITE-SPECIFIC VARIANCES WHICH MAY BE REQUIRED FOR THE PROJECT. APPROVAL FROM THE OWNER IS REQUIRED PRIOR TO SUBMISSION OF A VARIANCE PETITION TO ANY REGULATORY AGENCY. FAILURE TO OBTAIN PRIOR OWNER APPROVAL
MAY RESULT IN THE OWNER NOT PERMITTING THE VARIANCE TO BE USED ON THE PROJECT.
19. THE DISTURBANCE OF ANY KNOWN OR SUSPECT ASBESTOS-CONTAINING MATERIAL FOR WHICH HAS NOT BEEN DETERMINED TO BE NON-ASBESTOS-CONTAINING BY LABORATORY ANALYSIS, SHALL BE
PERFORMED BY A LICENSED ASBESTOS ABATEMENT CONTRACTOR.
20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL TOOLS, EQUIPMENT, SUPPLIES, ETC.
REQUIRED FOR THEIR WORK. THE OWNER OR OWNER'S REPRESENTATIVE SHALL NOT BE HELD LIABLE FOR THEFT OR DAMAGE OF THESE ITEMS. TOOLS SHALL BE REMOVED AND PLACED IN AN OWNER
APPROVED SECURE STORAGE AREA FOLLOWING EACH WORK DAY SHIFT.
21. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE REGULATED WORK AREAS IN A CLEAN AND SAFE CONDITION. THE CONTRACTOR SHALL ENSURE THAT UNCERTIFIED PERSONNEL OR
UNAUTHORIZED VISITORS DO NOT ENTER ACTIVE REGULATED WORK AREAS AT ANY TIME.
22. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING TEMPORARY PROTECTION TO KEEP THE BUILDING IN A WATERTIGHT CONDITION AND TO PREVENT UNAUTHORIZED ACCESS AT ALL TIMES FOR THE DURATION OF THE PROJECT. REPAIR OR DAMAGE CAUSED AS A RESULT OF IMPROPER TEMPORARY
PROTECTION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL
DOCUMENT ALL PRE-EXISTING WATER DAMAGE PRIOR TO ESTABLISHING CONTAINMENT AREAS.
23. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION AND DISPOSAL OF DEMOLISHED
MATERIALS REQUIRED TO ACCESS AND ABATE KNOWN AND/OR SUSPECT ASBESTOS-CONTAINING
MATERIALS SCHEDULED FOR REMOVAL.
24. ALL ASBESTOS-CONTAINING MATERIAL SHALL BE PROPERLY PACKAGED PRIOR TO BEING REMOVED
FROM THE REGULATED WORK AREAS. ASBESTOS WARNING LABELS SHALL BE APPLIED TO THE
ASBESTOS WASTE BAGS. ALL ASBESTOS WASTE MATERIALS THAT ARE REMOVED FROM THE SITE SHALL BE ACCOMPANIED BY AN ASBESTOS WASTE SHIPMENT RECORD/MANIFEST TO BE VERIFIED AND SIGNED BY THE ON SITE ENVIRONMENTAL CONSULTANT THAT INSPECTS THE SHIPMENT PRIOR TO BEING REMOVED FROM THE SITE. THE COMPLETED WASTE SHIPMENT RECORD MUST BE PROVIDED TO THE ENVIRONMENTAL CONSULTANT WITHIN 14 CALENDAR DAYS OF WASTE SHIPMENT LEAVING THE SITE. ALL
ORIGINAL COMPLETED WASTE SHIPMENT RECORDS MUST BE INCLUDED WITH THE CLOSEOUT
SUBMISSION.
25. ALL REQUIRED PRE-ABATEMENT SUBMITTALS, AS INDICATED IN THE SPECIFICATIONS, SHALL BE
RECEIVED AND APPROVED BY THE ENVIRONMENTAL CONSULTANT (RAVI ENGINEERING & LAND
SURVEYING, P.C.) PRIOR TO STARTING ABATEMENT.
26. ALL REQUIRED POST-ABATEMENT SUBMITTALS, AS INDICATED IN THE SPECIFICATIONS, SHALL BE RECEIVED AND APPROVED BY THE ARCHITECT (DWYER) AND THE ENVIRONMENTAL CONSULTANT (RAVI
ENGINEERING & LAND SURVEYING, P.C.) FOLLOWING THE COMPLETION OF ABATEMENT.
27. IN THE EVENT THERE IS A CONFLICT BETWEEN DRAWINGS AND SPECIFICATIONS, THE MOST STRINGENT
REGULATION SHALL APPLY.
ASBESTOS ABATEMENT KEY NOTES APPLICABLE TO HM-SERIES
CONTRACTOR SHALL ESTABLISH A NEGATIVE PRESSURE ENCLOSURE PER 12 NYCRR
PART 56 TO REMOVE THE NON-AC WALL SYSTEM INCLUDING GYPSUM WALL BOARD,
PLASTER WALL BOARD, AND CMU BLOCK (AS NECESSARY) AS FOLLOWS:
· FOLLOWING THE OPENING OF THE WALL SYSTEM, AND PRIOR TO THE REMOVAL OF
WALL SYSTEM DEBRIS FROM THE REGULATED WORK AREA, A CERTIFIED
ASBESTOS INSPECTOR SHALL ASSESS THE INSULATION WITHIN THE CHASE TO
DETERMINE THE FOLLOWING: 1) IS THE MATERIAL A SUSPECT OR KNOWN
ASBESTOS-CONTAINING MATERIAL; 2) THE CONDITION OF THE SUSPECT OR
KNOWN ASBESTOS-CONTAINING MATERIAL; 3) COLLECT AND ANALYZE SAMPLES
AT THE DISCRETION OF THE OWNER TO DETERMINE ASBESTOS CONTENT.
· IF IT IS DETERMINED THAT THE INSULATION (PIPING, ELBOWS, & FITTINGS) IS
FIBERGLASS, WALL DEBRIS SHALL BE DISPOSED OF AS GENERAL CONSTRUCTION
DEBRIS. CONTAINMENT CAN BE DISMANTLED AND NO FURTHER ACTION IS
REQUIRED.
· IF IT IS DETERMINED THAT THE INSULATION IS AN ACM AND THE INSULATION IS
INTACT, WALL DEBRIS SHALL BE DISPOSED OF AS GENERAL CONSTRUCTION
DEBRIS.
· IN THE CASE THE INSULATION IS DETERMINED TO BE AN ACM AND THE INSULATION
IS NOT INTACT, WALL DEBRIS SHALL BE DISPOSED OF AS RACM.
· IF THE INSULATION IS DETERMINED TO BE A SUSPECT ASBESTOS-CONTAINING
MATERIAL OR KNOWN ASSUMED AC (VARIOUS COLORS) THERMAL SYSTEMS
INSULATION (PIPING, ELBOWS, & FITTINGS), CONTRACTOR SHALL REMOVE
INSULATION, INCLUDING FIBERGLASS INSULATION, (PIPING, FITTINGS, ELBOWS)
WITHIN WALL CHASES, IN ITS ENTIRETY, AND DISPOSE OF AS RACM.
CONTRACTOR SHALL ESTABLISH A NEGATIVE PRESSURE ENCLOSURE EXTENDING
FROM THE FLOOR TO THE GRID (DROP CEILING) AND SEAL AT THE GRID SUPPORTS.
CONTRACTOR AND PROJECT MONITOR SHALL REMOVE A SINGLE (ONE) CEILING TILE
PER FUNCTIONAL SPACE, OR AS REQUIRED TO SUFFICIENTLY ASSESS THE ENTIRETY
OF THE PROPOSED REGULATED WORK AREA, IN ORDER TO INSPECT THE
SURROUNDING CEILING TILES DIRECTLY BELOW THE PIPING SYSTEM WHICH
CONTAINS TRACE AC GRAY THERMAL INSULATION. IF NO DEBRIS IS OBSERVED ON
THE CEILING TILES, THE CEILING TILES SHALL BE REMOVED AND DISPOSED OF AS
GENERAL CONSTRUCTION DEBRIS. IF DEBRIS, OR IDENTIFIABLE SUSPECT MATERIALS
ARE LOCATED ON THE CEILING TILES, THEY SHALL BE REMOVED, HANDLED AND
DISPOSED OF AS A RACM. SHOULD ABATEMENT OF CEILING TILES BE REQUIRED,
REMOVALS OF CEILING TILES UNDER ABATEMENT CONDITIONS SHALL BE LIMITED TO
CEILING TILES DIRECTLY BELOW THE TRACE AC GRAY THERMAL SYSTEM INSULATION.
CONSTRUCTION OF THE NEGATIVE PRESSURE ENCLOSURE SHALL BE CONTINUED TO
EXTEND FROM THE CEILING SUPPORT GRID TO THE UNDERSIDE OF THE DECKING
ABOVE. FOLLOWING COMPLETION OF THE NEGATIVE PRESSURE ENCLOSURE AND
OBSERVANCE OF APPROPRIATE WAIT TIMES, THE CONTRACTOR SHALL REMOVE THE
TRACE AC GRAY THERMAL INSULATION, IN ITS ENTIRETY, INCLUDING ALL INSULATION
(FIBERGLASS) FROM ELBOWS, FITTING AND PIPE RUNS. REMOVALS SHALL BE
COMPLETE TO THE POINT THAT NO VISIBLE RESIDUE REMAINS. MATERIALS ABATED
SHALL BE HANDLED AND DISPOSED OF AS A RACM. CONTRACTOR SHALL
COORDINATE REMOVAL LOCATIONS WITH ARCHITECTURAL DEMO DRAWINGS AND
MECHANICAL DRAWINGS.
CONTRACTOR SHALL REMOVE NON-AC BLACK COVE BASE AND NON-AC COVE BASE
MASTIC (VARIOUS COLORS), THRESHOLDS, AC 9” X 9” GRAY FLOOR TILE AND
ASSOCIATED AC BLACK MASTIC, FULL DEPTH, ALL LAYERS, IN ITS ENTIRETY, TO THE
SUBSTRATE AND DISPOSE OF AS AN ACM. REMOVALS SHALL BE COMPLETE TO THE
POINT THAT NO VISIBLE RESIDUE REMAINS.
CONTRACTOR SHALL REMOVE AC GRAY EXTERIOR WINDOW GLAZING/CAULK
BETWEEN GLASS AND METAL, FULL DEPTH, ALL LAYERS, TO THE SUBSTRATE.
CONTRACTOR SHALL BE AWARE THAT WINDOW GLAZING / CAULK IS AN ACM AND PCB
BULK PRODUCT WASTE. CONTRACTOR SHALL REMOVE IN ACCORDANCE WITH 12
NYCRR PART 56 AND DISPOSE OF IN ACCORDANCE WITH 40 CFR 761. REMOVE,
HANDLE AND STORE AS AN ACM, AND DISPOSE OF AS PCB-BULK PRODUCT WASTE.
REMOVALS SHALL BE COMPLETE TO THE POINT THAT NO VISIBLE RESIDUE REMAINS.
GENERAL LEAD-CONTAINING PAINT NOTES APPLICABLE TO HM-SERIES
1. SURFACES CONTAINING LEAD-CONTAINING PAINT ARE ASSUMED TO BE PRESENT IN THE
RENOVATION AREAS. ALTERATIONS TO PAINTED SURFACES CONTAINING LEAD SHALL BE
PERFORMED BY ALL CONTRACTORS IN ACCORDANCE WITH 29 CFR 1926.62.
2. ALL REQUIRED PRE-ABATEMENT SUBMITTALS SHALL BE RECEIVED AND APPROVED BY THE
ENVIRONMENTAL CONSULTANT (RAVI ENGINEERING & LAND SURVEYING, P.C.) PRIOR TO STARTING
ALTERATIONS.
3. IN THE EVENT THERE IS A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MOST
STRINGENT REGULATION SHALL APPLY.
GENERAL PCB CAULK ABATEMENT NOTES APPLICABLE TO HM-SERIES
1. THE CONTRACTOR SHALL PERFORM ALL CONTRACT WORK IN ACCORDANCE WITH CONTRACT
SPECIFICATIONS AND THE TOXIC SUBSTANCES CONTROL ACT (TSCA) REGULATIONS 40 CFR 761.
2. THE CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS, DIMENSIONS AND QUANTITIES OF
MATERIALS BEFORE START OF WORK.
3. VARIATIONS (+/- 10%) IN QUANTITIES AND LOCATIONS OF PREVIOUSLY IDENTIFIED PCB-CONTAINING MATERIALS SHALL BE CONSIDERED AS HAVING NO IMPACT ON CONTRACT PRICE AND/OR SCHEDULE OF THIS CONTRACT. ADDITIONAL QUANTITIES SHALL BE VERIFIED BY A CERTIFIED PROJECT MONITOR DURING
REMOVAL ACTIVITIES
4. ALL WORKERS SHALL POSSESS A VALID OSHA HAZWOPER TRAINING CERTIFICATE.
5. OSHA DAILY PERSONAL AIR MONITORING FOR PCB EXPOSURE SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
6. ALL REMOVAL WORK SHALL BE COORDINATED WITH THE OWNER.
7. THE CONTRACTOR SHALL MAINTAIN SECURITY IN THE PCB WORK AREAS AT ALL TIMES, FOR THE DURATION
OF THE PCB CAULK ABATEMENT PROJECT.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF GROUNDS, INCLUDING BUT NOT LIMITED TO, PAVEMENT, CONCRETE, SOIL, GRASS AND LANDSCAPING. DAMAGE TO EXISTING CONDITIONS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. CONTRACTOR SHALL DOCUMENT ALL PRE-EXISTING DAMAGE
PRIOR TO STARTING CONSTRUCTION.
9. IF THE BUILDING ENVELOPE BECOMES EXPOSED OR COMPROMISED AFTER CAULK ABATEMENT, THE CONTRACTOR SHALL PROVIDE TEMPORARY WEATHER AND SECURITY PROTECTION AND SHALL MAINTAIN
UNTIL PERMANENT BUILDING ENVELOPE HAS BEEN RESTORED.
10. IF WATER LEAKS THROUGH CONTAINMENT AREAS OR RESULTS FROM IMPROPER WEATHER PROTECTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WATER DAMAGE.
11. PCB BULK-PRODUCT WASTE DRUM STORAGE LOCATIONS AND TRANSPORT ROUTES SHALL BE
COORDINATED WITH THE OWNER.
12. ALL TEMPORARY POWER TO THE PCB WORK AREAS SHALL BE BROUGHT IN FROM OUTSIDE OF THE PCB WORK AREAS THROUGH A GROUND FAULT CIRCUIT INTERRUPTER AT THE SOURCE OF THE POWER THAT
SHALL BE PROVIDED BY THE CONTRACTOR.
13. THE CONTRACTOR SHALL PROVIDE SAFETY DATA SHEETS (SDS) FOR ANY CHEMICAL AGENTS TO BE USED
FOR PCB CAULK ABATEMENT.
14. PCBS MAY HAVE LEACHED INTO POROUS BUILDING MATERIALS. THESE BUILDING MATERIALS CANNOT BE REMOVED EFFECTIVELY WITHOUT DEFACING THE SUBSTRATE. ALL LOCATIONS WHERE PCB-CONTAINING CAULKS HAVE BEEN REMOVED SHALL BE WIPED CLEAN AND MANAGED IN-PLACE AS A PCB-CONTAMINATED
BUILDING MATERIAL.
15. THE CONTRACTOR'S MEANS AND METHODS TO COMPLETE THE WORK SHALL PREVENT OR MINIMIZE THE GENERATION OF DUST IN ALL CASES. VISIBLE DUST LEAVING THE WORK AREA SHALL NOT BE PERMITTED UNDER ANY CIRCUMSTANCES. THE CONTRACTOR SHALL ENSURE THAT OPERABLE WINDOWS AND AIR
INTAKES ADJACENT TO THE WORK AREAS ARE NOT IMPACTED.
16. THE CONTRACTOR SHALL CAPTURE AND PROPERLY DISPOSE OF ALL WATER/WASTEWATER GENERATED DURING EXECUTION OF THE ABATEMENT PROJECT. UNDER NO CIRCUMSTANCES SHALL CONTAMINATED
WASTEWATER ENTER THE STORM OR SANITARY SEWER SYSTEM.
17. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TRANSPORTATION AND DISPOSAL OF ALL WASTES
GENERATED DURING EXECUTION OF THE PROJECT.
18. ALL REQUIRED PRE-ABATEMENT SUBMITTALS, AS INDICATED IN THE SPECIFICATIONS, SHALL BE RECEIVED AND APPROVED BY THE ENVIRONMENTAL CONSULTANT (RAVI ENGINEERING & LAND SURVEYING, P.C.)
PRIOR TO STARTING ABATEMENT.
19. ALL REQUIRED POST-ABATEMENT SUBMITTALS, AS INDICATED IN THE SPECIFICATIONS, SHALL BE RECEIVED AND APPROVED BY THE ARCHITECT (DWYER) AND THE ENVIRONMENTAL CONSULTANT (RAVI ENGINEERING
& LAND SURVEYING, P.C.) FOLLOWING THE COMPLETION OF ABATEMENT.
20. IN THE EVENT THERE IS A CONFLICT BETWEEN DRAWINGS AND SPECIFICATIONS, THE MOST STRINGENT
REGULATION SHALL APPLY.
PCB CAULK ABATEMENT KEY NOTES APPLICABLE TO HM-SERIES
CONTRACTOR SHALL REMOVE PCB-CONTAINING GRAY EXTERIOR WINDOW GLAZING / CAULK
BETWEEN GLASS AND METAL, FULL DEPTH, ALL LAYERS, TO THE SUBSTRATE. CONTRACTOR
SHALL BE AWARE THAT WINDOW GLAZING / CAULK IS AN ACM AND PCB BULK PRODUCT
WASTE. CONTRACTOR SHALL REMOVE IN ACCORDANCE WITH 12 NYCRR PART 56 AND
DISPOSE OF IN ACCORDANCE WITH 40 CFR 761. REMOVE, HANDLE AND STORE AS AN ACM,
AND DISPOSE OF AS PCB-BULK PRODUCT WASTE. REMOVALS SHALL BE COMPLETE TO THE
POINT THAT VISIBLE RESIDUE REMAINS.
CONTRACTOR SHALL REMOVE PCB-CONTAINING DARK GRAY EXTERIOR WINDOW CAULK
BETWEEN BRICK AND METAL, FULL DEPTH, ALL LAYERS, TO THE SUBSTRATE, AND DISPOSE
OF AS PCB-BULK PRODUCT WASTE. REMOVALS SHALL BE COMPLETE TO THE POINT THAT NO
VISIBLE RESIDUE REMAINS.
PCB CAULK ABATEMENT LEGEND APPLICABLE TO HM-SERIES
SQUARE FEET
PCB-CONTAINING GRAY EXTERIOR WINDOW GLAZING / CAULK
PCB-CONTAINING DARK GRAY EXTERIOR WINDOW CAULK
APPROXIMATE PCB CAULK
ABATEMENT QUANTITIES
APPLICABLE TO HM-SERIES
(FOR BIDDING ONLY)
WIG 6 SF
WIG
SF
WIG
WIC
WIC 10 SF
WICAPPROXIMATE ASBESTOS ABATEMENT
QUANTITIES APPLICABLE TO HM-SERIES
(FOR BIDDING ONLY)
FT
WIG
ASBESTOS ABATEMENT LEGEND APPLICABLE TO HM-SERIES
ASBESTOS-CONTAINING
ASBESTOS-CONTAINING MATERIAL
REGULATED ASBESTOS-CONTAINING MATERIAL
SQUARE FEET
LINEAR FEET
ASSUMED AC (VARIOUS COLORS) THERMAL SYSTEMS INSULATION (PIPING, ELBOWS,
& FITTINGS)
TRACE AC GRAY THERMAL SYSTEMS INSULATION (PIPING, ELBOWS, & FITTINGS)
ASBESTOS-CONTAMINATED 2' X 4' GRAY ACOUSTICAL CEILING TILE
AC 9" X 9" GRAY FLOOR TILE AND ASSOCIATED AC BLACK FLOOR TILE MASTIC
AC GRAY EXTERIOR WINDOW GLAZING/CAULK
APPROXIMATE AREA OF TRACE AC GRAY THERMAL SYSTEMS INSULATION (PIPING,
ELBOWS, & FITTINGS) ASSOCIATED WITH ACOUSTICAL CEILING TILE
APPROXIMATE AREA OF AC 9" X 9" GRAY FLOOR TILE AND ASSOCIATED AC BLACK
FLOOR TILE MASTIC, LIMITED TO UPPER LEVEL ONLY
LF
AC
SF
ACM
RACM
FT
WIG
TSI 75 LF
WIG 6 SF
ACT 300 SF
FT 5,560 SF
TSI
TSI 30 LF
TSI
TSI
ACT
TSI
ACT
DateDescription
Copyright 2025, Dwyer Architectural, LLC
No.
Sheet Title
Sheet No.
Project Information
Issue Date:
CON No.:
Client Project No.:
Project No.: 24-055
SUNY COLLEGE OF
ENVIRONMENTAL SCIENCE AND
FORESTRY
MOON LIBRARY ADA
UPGRADES AND
RENOVATION
1 FORESTRY DRIVE SYRACUSE, NY
13210
A red seal and a blue signature indicates an original document.
Note: Per NYSED Office of the Professions Commisioner's Regulations Part 69.5b, it is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter in any way an item bearing the seal of an architect.
Consultants
Drawn By: Reviewer:
www.dwyerarch.com // ph: 315.473.1800
85 Allen Street, Suite 210 Rochester, NY 14608
110 W Fayette Street, Suite 225 Syracuse, NY 13202
EXPIRES: 09/30/2027
HM-100
BID DOCUMENTS
ADZ BLR
HAZARDOUS MATERIALS
ABATEMENT PLAN -
GENERAL NOTES
MAY 8, 2026
ACCESS
PIT
UP
OUTLINE OF UPPER LEVEL
DOWN
1075 SF
ROOM
2096 SF
MECHANICAL EQUIPMENT ROOM
102 SF
003A
CORRIDOR
285 SF
ROOM
1094 SF
IT SERVICES
172 SF
009C
ROOM
115 SF
009B
ROOM
129 SF
009A
ROOM
320 SF
ROOM
117 SF
009D
ROOM
104 SF
009F
ROOM
105 SF
009G
ROOM
319 SF
009E
ROOM
216 SF
STAFF/ROOM
116 SF
013B
ROOM
112 SF
013C
ROOM
698 SF
ROOM
391 SF
OFFICES
123 SF
009H
ROOM
90 SF
009I
ROOM
122 SF
007C
ROOM
1648 SF
CORRIDOR
163 SF
ARCHIVES
454 SF
ARCHIVES
910 SF
ARCHIVES
109 SF
COAT ROOM
61 SF
STORAGE
40 SF
NUMBER
607 SF
NUMBER
PIPE & DUCT TUNNEL
580 SF
NUMBER
PIPE & DUCT TUNNEL
32 SF
0A
ELEVATOR
35 SF
003B
CLOSET
73 SF
0A
STAIR
347 SF
LOBBY
211 SF
001A
MEN'S TOILET
367 SF
001B
WOMEN'S TOILET
54 SF
JAN. CLOSET
92 SF
003E
MEN'S TOILET
132 SF
003D
WOMENS TOILET
86 SF
003C
CORRIDOR
RAMP
1012 SF
U.S FOREST SERVICE
1048 SF
ROOM SUITE
301 SF
005A
ROOM
FT
FT
FT
FT
FT
FT
FTFT
FT
FT
FT
WIC
WIG
WIC
WIG
WIC
WIG
WIC
WIG
WIC
WIG
WIC
WIG
FT
TSI
ACT
TSI
ACT
TSI
ACT
TSI
TSI
TSI
ELEV. MECH. ROOM
GENERAL LEAD-CONTAINING PAINT NOTES APPLICABLE TO HM-101
1. SURFACES CONTAINING LEAD-CONTAINING PAINT ARE ASSUMED TO BE PRESENT IN THE
RENOVATION AREAS. ALTERATIONS TO PAINTED SURFACES CONTAINING LEAD SHALL BE
PERFORMED BY ALL CONTRACTORS IN ACCORDANCE WITH 29 CFR 1926.62.
2. ALL REQUIRED PRE-ABATEMENT SUBMITTALS SHALL BE RECEIVED AND APPROVED BY THE
ENVIRONMENTAL CONSULTANT (RAVI ENGINEERING & LAND SURVEYING, P.C.) PRIOR TO STARTING
ALTERATIONS.
3. IN THE EVENT THERE IS A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MOST
STRINGENT REGULATION SHALL APPLY.
ASBESTOS ABATEMENT LEGEND APPLICABLE TO HM-101
ASBESTOS-CONTAINING
SQUARE FEET
LINEAR FEET
ASSUMED AC (VARIOUS COLORS) THERMAL SYSTEMS INSULATION (PIPING, ELBOWS,
& FITTINGS)
TRACE AC GRAY THERMAL SYSTEMS INSULATION (PIPING, ELBOWS, & FITTINGS)
ASBESTOS-CONTAMINATED 2' X 4' GRAY ACOUSTICAL CEILING TILE
AC 9" X 9" GRAY FLOOR TILE AND ASSOCIATED AC BLACK FLOOR TILE MASTIC
AC GRAY EXTERIOR WINDOW GLAZING/CAULK
APPROXIMATE AREA OF TRACE AC GRAY THERMAL SYSTEMS INSULATION (PIPING,
ELBOWS, & FITTINGS) ASSOCIATED WITH ACOUSTICAL CEILING TILE
LF
AC
SF
FT
WIG
TSI
TSI
ACT
APPROXIMATE ASBESTOS ABATEMENT
QUANTITIES APPLICABLE TO HM-101
(FOR BIDDING ONLY)
TSI 75 LF
WIG 6 SF
ACT 300 SF
FT 4,500 SF
TSI 30 LF
PCB CAULK ABATEMENT LEGEND APPLICABLE TO HM-101
SQUARE FEET
PCB-CONTAINING GRAY EXTERIOR WINDOW GLAZING / CAULK
PCB-CONTAINING DARK GRAY EXTERIOR WINDOW CAULK
APPROXIMATE PCB CAULK
ABATEMENT QUANTITIES
APPLICABLE TO HM-101
(FOR BIDDING ONLY)
WIG 6 SF
WIG
SF
WIC 10 SF
WIC
DateDescription
Copyright 2025, Dwyer Architectural, LLC
No.
Sheet Title
Sheet No.
Project Information
Issue Date:
CON No.:
Client Project No.:
Project No.: 24-055
SUNY COLLEGE OF
ENVIRONMENTAL SCIENCE AND
FORESTRY
MOON LIBRARY ADA
UPGRADES AND
RENOVATION
1 FORESTRY DRIVE SYRACUSE, NY
13210
A red seal and a blue signature indicates an original document.
Note: Per NYSED Office of the Professions Commisioner's Regulations Part 69.5b, it is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter in any way an item bearing the seal of an architect.
Consultants
Drawn By: Reviewer:
www.dwyerarch.com // ph: 315.473.1800
85 Allen Street, Suite 210 Rochester, NY 14608
110 W Fayette Street, Suite 225 Syracuse, NY 13202
EXPIRES: 09/30/2027
HAZARDOUS MATERIALS
ABATEMENT PLAN -
LOWER LEVEL PLAN
HM-101
MAY 8, 2026
BID DOCUMENTS
ADZ BLR
1/8" = 1'-0"
HAZARDOUS MATERIALS ABATEMENT PLAN - LOWER LEVEL PLAN
HM-101
Terrace
FT
SW CORNER
ASBESTOS ABATEMENT LEGEND APPLICABLE TO HM-102
ASBESTOS-CONTAINING
SQUARE FEET
AC 9" X 9" GRAY FLOOR TILE AND ASSOCIATED AC BLACK FLOOR TILE MASTIC
APPROXIMATE AREA OF AC 9" X 9" GRAY FLOOR TILE AND ASSOCIATED AC BLACK FLOOR TILE
MASTIC, LIMITED TO UPPER LEVEL ONLY
AC
SF
FT
APPROXIMATE ASBESTOS ABATEMENT
QUANTITIES APPLICABLE TO HM-102
(FOR BIDDING ONLY)
FT 1,060 SF
GENERAL LEAD-CONTAINING PAINT NOTES APPLICABLE TO HM-102
1. SURFACES CONTAINING LEAD-CONTAINING PAINT ARE ASSUMED TO BE PRESENT IN THE
RENOVATION AREAS. ALTERATIONS TO PAINTED SURFACES CONTAINING LEAD SHALL BE
PERFORMED BY ALL CONTRACTORS IN ACCORDANCE WITH 29 CFR 1926.62.
2. ALL REQUIRED PRE-ABATEMENT SUBMITTALS SHALL BE RECEIVED AND APPROVED BY THE
ENVIRONMENTAL CONSULTANT (RAVI ENGINEERING & LAND SURVEYING, P.C.) PRIOR TO STARTING
ALTERATIONS.
3. IN THE EVENT THERE IS A CONFLICT BETWEEN THE DRAWINGS AND SPECIFICATIONS, THE MOST
STRINGENT REGULATION SHALL APPLY.
DateDescription
Copyright 2025, Dwyer Architectural, LLC
No.
Sheet Title
Sheet No.
Project Information
Issue Date:
CON No.:
Client Project No.:
Project No.: 24-055
SUNY COLLEGE OF
ENVIRONMENTAL SCIENCE AND
FORESTRY
MOON LIBRARY ADA
UPGRADES AND
RENOVATION
1 FORESTRY DRIVE SYRACUSE, NY
13210
A red seal and a blue signature indicates an original document.
Note: Per NYSED Office of the Professions Commisioner's Regulations Part 69.5b, it is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter in any way an item bearing the seal of an architect.
Consultants
Drawn By: Reviewer:
www.dwyerarch.com // ph: 315.473.1800
85 Allen Street, Suite 210 Rochester, NY 14608
110 W Fayette Street, Suite 225 Syracuse, NY 13202
EXPIRES: 09/30/2027
HAZARDOUS MATERIALS
ABATEMENT PLAN -
UPPER LEVEL PLAN
HM-102
BID DOCUMENTS
ADZ BLR
HAZARDOUS MATERIALS ABATEMENT PLAN - UPPER LEVEL PLAN
MAY 8, 2026
1/8" = 1'-0"HM-102
23 MECHANIC STREET, SPRINGVILLE, NY 14141
D at e:
Tim e:
/2
1/
:5
1:
A M www.dwyerarch.com // ph: 315.473.1800
85 Allen Street, Suite 210 Rochester, NY 14608
110 W Fayette Street, Suite 225 Syracuse, NY 13202
DateDescription
Copyright 2025, Dwyer Architectural, LLC
No.
Sheet Title
Sheet No.
Project Information
Issue Date: MAY 08, 2026
BID DOCUMENTS
CON No.:
Client Project No.:
Project No.: 24-055
SUNY COLLEGE OF
ENVIRONMENTAL SCIENCE
AND
FORESTRY
MOON LIBRARY ADA
UPGRADES AND
RENOVATION
1 FORESTRY DRIVE SYRACUSE,
NY
13210
A red seal and a blue signature indicates an original document.
Note: Per NYSED Office of the Professions Commisioner's Regulations Part 69.5b, it is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter in any way an item bearing the seal of an architect.
Consultants
Drawn By: CCW Reviewer: GPS
S-001
STRUCTURAL
NOTES AND
LEGENDS
WP WORK POINT
W/O WITHOUT
W/ WITH
UNO UNLESS NOTED OTHERWISE
TYP TYPICAL
T/ TOP OF
T&B TOP AND BOTTOM
THRU THROUGH
THK THICK
STL STEEL
STD STANDARD
SOG SLAB ON GROUND
SCHED SCHEDULE
REQD REQUIRED
REF REFERENCE
RAD RADIUS
PL PLATE
OD OUTSIDE DIAMETER
OC ON CENTER
MIN MINIMUM
MH MANHOLE
MAX MAXIMUM
LLV LONG LEG VERTICAL
IJ FILLER ISOLATION JOINT
ID INSIDE DIAMETER
HVY HEAVY
HS HIGH STRENGTH
GRTG GRATING
GALV GALVANIZE
FV FIELD VERIFY
FD FIELD DIMENSION
FS FAR SIDE
FACE/ FACE OF
EXST EXISTING
EQL EQUAL
EL ELEVATION
EW EACH WAY
DWG DRAWING
DIA DIAMETER
CJ CONTRACTOR JOINT
CONN CONNECTION
CONC CONCRETE
C/C CENTER TO CENTER
BLDG BUILDING
BOT/ BOTTOM OF
BC BOLT CIRCLE
BTB BACK TO BACK
B/ BACK OF
APPROX APPROXIMATELY
ABBREVIATION TERM
ABBREVIATIONS:
1.
2.
3.
4.
5.
6.
THE CONTRACTOR SHALL SUBMIT A SCHEDULE OF PROPOSED WORK TO THE OWNER'S
CONSTRUCTION MANAGER FOR REVIEW. WORK SHALL NOT START UNTIL SUCH TIME AS THE
OWNER'S CONSTRUCTION MANAGER APPROVES THE CONTRACTOR'S SCHEDULE.
THE CONTRACTOR SHALL VERIFY ALL FIELD CONDITIONS AND DIMENSIONS PRIOR TO
STARTING CONSTRUCTION AND THE OWNER'S CONSTRUCTION MANAGER SHALL BE NOTIFIED
IN WRITING, OF ANY PROBLEM AREAS WHICH MAY HAVE AN EFFECT ON THE INTENDED SCOPE
OF WORK.
DISMANTLING, REMOVAL AND DISPOSITION OF ALL EXISTING STRUCTURES, CONCRETE AND
REINFORCING STEEL SHALL BE AS DIRECTED BY THE OWNER'S CONSTRUCTION MANAGER.
THE CONTRACTOR SHALL PROVIDE ADEQUATE BRACING AND TEMPORARY SHORING AS
REQUIRED FOR EXISTING BUILDINGS OR STRUCTURES INVOLVED WITH CONSTRUCTION
ACTIVITIES.
THE CONTRACTOR SHALL MAINTAIN THE WORKSITE IN AN ORDERLY CONDITION AND PROVIDE
FOR REGULAR CLEANUP OF THE CONSTRUCTION AREAS UNDER HIS JURISDICTION ON A DAILY
BASIS.
UPON COMPLETION OF ALL WORK, THE CONTRACTOR SHALL REMOVE DEMOLISHED AND
SCRAP MATERIALS (COORDINATE WITH OWNER), HIS TEMPORARY FACILITIES, EQUIPMENT,
SURPLUS MATERIALS AND SUPPLIES. FINAL CLEANUP SHALL LEAVE PREMISES IN AN ORDERLY
CONDITION.
SITE:
6.
7.
8.
9.
FABRICATE AND PLACE REINFORCING STEEL IN ACCORDANCE WITH ACI 318 BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE, ACI SP-66 DETAILING MANUAL, ACI 301
SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS.
PROVIDE REINFORCING STEEL CONFORMING TO ASTM A615 GRADE 60. SUBMIT REINFORCING
STEEL SHOP DRAWINGS FOR APPROVAL PRIOR TO THE START OF CONSTRUCTION.
PROVIDE ACI CLASS B REINFORCING BAR SPLICES BUT NOT LESS THAN 12 INCHES OF LAP.
PROVIDE CORNER REINFORCING BARS AT ALL EXTERIOR CORNERS OF CONCRETE WORK.
CORNER BARS TO MATCH HORIZONTAL REINFORCING.
1.
2.
3.
4.
5.
6.
7.
THE CONTRACTOR SHALL VERIFY THE LOCATION OF UNDERGROUND SERVICE UTILITIES
PRIOR TO BEGINNING CONSTRUCTION WORK.
THE CONTRACTOR SHALL OBTAIN A RELEASE FROM THE OWNER'S CONSTRUCTION
MANAGER BEFORE EXCAVATING BEGINS.
THE CONTRACTOR SHALL REVIEW AVAILABLE GEOTECHNICAL INVESTIGATION REPORT AND
ITS RECOMMENDATIONS.
PERFORM ALL EXCAVATIONS IN ACCORDANCE WITH OSHA "CONSTRUCTION STANDARDS FOR
TRENCHING AND EXCAVATION, 29 CFR, PART 1926, SUBPART P" GUIDELINES.
WHERE EXISTING FOUNDATIONS ARE ENCOUNTERED DURING EXCAVATION FOR NEW
FOUNDATIONS, THE ENGINEER OF RECORD IS TO BE NOTIFIED IN WRITING. THE ENGINEER OF
RECORD WILL DETERMINE THE EXTENT THE EXISTING FOUNDATIONS SHALL BE REMOVED.
FOUNDATIONS WHERE MATS AND SPREAD FOOTINGS ARE USED SHALL BE SUPPORTED ON
UNDISTURBED SUITABLE BEARING SOILS OR COMPACTED STRUCTURAL FILL HAVING A
MINIMUM BEARING CAPACITY AS SHOWN IN THE DESIGN CRITERIA. THE CONTRACTOR SHALL
EMPLOY A QUALIFIED SOILS ENGINEER TO VERIFY SUITABLE FOUNDATION AND PAVEMENT
BEARING GRADES. IF UNSUITABLE SOILS ARE EXPOSED, AS DEEMED BY THE SOILS
ENGINEER, THEY SHALL BE OVER EXCAVATED (REMOVED) AND REPLACED WITH
STRUCTURAL FILL FROM THE DEPTH OF OVER EXCAVATION TO THE BEARING ELEVATION
SHOWN ON THE DRAWINGS.
COMPACTED SUB BASE STRUCTURAL FILL SHALL CONFORM TO NYSDOT SPECIFICATION
304.12M, TYPE 2 SUBBASE. BACKFILLING SHALL BE DONE IN 9 INCH MAXIMUM LAYERS
COMPACTED TO 95% MODIFIED PROCTOR (ASTM D1556, D1557 AND D2922). THE THICKNESS
OF COMPACTED STRUCTURAL FILL SHALL BE IN ACCORDANCE WITH THE DESIGN DRAWINGS.
IN THE EVENT THAT A THICKNESS IS NOT SHOWN, USE A MINIMUM COMPACTED THICKNESS
OF 6 INCHES. BACKFILLING ABOVE AND ON TOP OF SPREAD FOOTINGS AND WALLS MAY
UTILIZE EXCAVATED MATERIALS AS DEEMED SUITABLE BY A QUALIFIED SOILS ENGINEER.
EXCAVATION AND BACKFILL:
1.
2.
3.
4.
5.
REFER TO ACI 318, BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE FOR
CONCRETE CONSTRUCTION REQUIREMENTS.
PROVIDE CONCRETE WITH A MINIMUM COMPRESSIVE STRENGTH OF 4,000 PSI AT 28 DAYS.
SUBMIT ENGINEERED CONCRETE MIX DESIGNS, INCLUDING BACKUP DATA FOR EACH TYPE
OF CONCRETE PROPOSED FOR USE PRIOR TO THE START OF CONSTRUCTION. IDENTIFY
WHERE EACH DIFFERENT CONCRETE MIX IS INTENDED TO BE USED.
PROVIDE AIR ENTRAINMENT PER ACI 318 FOR ALL EXTERIOR CONCRETE. LIMIT WATER
CEMENT RATIO FOR ALL CONCRETE TO 0.45. FOR INTERIOR SLAB-ON-GRADE, LIMIT CEMENT
CONTENT TO 540 POUNDS PER CUBIC YARD.
PROVIDE FOUR TEST CYLINDERS FOR EVERY 50 CUBIC YARDS, OR LESS (EACH DAY) AND
FURNISH TEST REPORTS FOR 7 AND 28 DAY COMPRESSION TESTS.
WATER MAY BE ADDED INITIALLY TO CONCRETE WHICH ARRIVES AT THE SITE IF AFTER
ADDITION OF THE WATER THE MAXIMUM WATER/CEMENT RATIO IS NOT EXCEEDED.
RETEMPERING AFTER INITIAL SLUMP ADJUSTMENT IS NOT PERMITTED.
BEAMS AND COLUMNS 1 1/2 IN
SLABS AND WALLS 3/4 IN
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE GROUND
NO 6 BAR AND LARGER 2 IN
NO 5 BAR AND SMALLER 1 1/2 IN
CONCRETE EXPOSED TO WEATHER OR IN CONTACT WITH THE GROUND
CONCRETE CAST AGAINST EARTH OR FILL 3 IN
CONCRETE AND GROUT:
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
PROVIDE THE FOLLOWING CONCRETE COVER IN ACCORDANCE WITH ACI 318:
PROVIDE ANCHOR BOLTS THAT CONFORM TO F1554 GR. 36KSI, SUPPLEMENT S1 WITH HEAVY HEX NUTS AND FLAT
WASHERS, UNLESS NOTED OTHERWISE. HOT DIP GALVANIZE ALL ANCHOR BOLT ASSEMBLIES.
SET CAST-IN-PLACE ANCHOR BOLTS WITH TEMPLATES TO ELEVATIONS SHOWN ON DRAWINGS PRIOR TO CONCRETE BEING
PLACED. "WET-STICKING" ANCHORS IS STRICTLY PROHIBITED.
VERIFY THAT ALL OPENINGS, INSERTS, ANCHOR BOLTS, EMBEDDED PIPING, REBAR, DOWELS, CONDUITS, GROUNDING WIRES, DUCTWORK, ETC. ARE IN PLACE BEFORE PLACING CONCRETE. "WET-STICKING" EMBEDMENTS IS STRICTLY
PROHIBITED.
PROVIDE REINFORCING STEEL FREE OF OIL, MUD, HARDENED CONCRETE, LOOSE SCALE AND RUST.
BRACE, TIE, AND SUPPORT REINFORCING WITH CHAIRS IN ACCORDANCE WITH ACI 315.
DO NOT WELD REINFORCING STEEL UNLESS INDICATED ON THE DRAWINGS.
EDGE TOOL TOP HORIZONTAL EDGE OF PIERS
TOOL ALL CONCRETE EDGES AND FILL WITH SEMI-RIGID EPOXY JOINT FILLER WITH 100 PERCENT SOLIDS AND A TYPE A
SHORE DUROMETER HARDNESS OF 80 ACCORDING TO ASTM D2240.
DO NOT USE CONCRETE CONSTRUCTION JOINTS UNLESS SHOWN ON DRAWINGS OR APPROVED IN WRITING BY THE
ENGINEER.
DO NOT PLACE CONCRETE INTO ANY FORM OR EXCAVATION CONTAINING TRASH, FREE WATER, ICE, OR FROZEN GROUND.
USE APPROPRIATE METHODS TO MINIMIZE FREE-FALL DISTANCE OF CONCRETE. DO NOT USE VIBRATORS TO TRANSPORT CONCRETE. DO NOT ALLOW CONCRETE TO FLOW HORIZONTALLY WITHIN FORMS OVER A DISTANCE EXCEEDING 5 FEET.
PROVIDE A CLEAR, NON-YELLOWING, WATER BASED CURING AND SEALING COMPOUND ON FLOOR SLABS AND EXPOSED
SURFACES UNLESS NOTED OTHERWISE.
REFER TO ACI 305 FOR REQUIREMENTS FOR PLACING CONCRETE IN HOT WEATHER AND TO ACI 306 FOR REQUIREMENTS
FOR PLACING CONCRETE IN COLD WEATHER.
CONCRETE AND GROUT CONTINUED:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
MASONRY STRUCTURES ARE DESIGNED IN ACCORDANCE WITH ACI 530, “BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES” AND "SPECIFICATIONS FOR MASONRY STRUCTURES" (ACI 530.1), LATEST EDITIONS.
CONCRETE MASONRY UNITS TO BE LIGHT WEIGHT HOLLOW CORE BLOCK, CONFORMING TO ASTM C90.
SOLID BRICK MASONRY UNITS TO HAVE A MINIMUM NET AREA COMPRESSIVE STRENGTH OF 5,500 PSI.
MORTAR TO BE TYPE N CONFORMING TO ASTM C270.
GROUT TO BE IN ACCORDANCE WITH ASTM C476 AND HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI AT 28
DAYS.
REINFORCED CONCRETE MASONRY ASSEMBLIES TO HAVE A MINIMUM NET AREA COMPRESSIVE STRENGTH OF F'M=1500
PSI.
VERTICAL REINFORCEMENT BARS TO BE IN ACCORDANCE WITH ASTM A615, GRADE 60.
PROVIDE VERTICAL REINFORCEMENT BARS AS SHOWN ON DRAWINGS, PROVIDE ADDITIONAL VERTICAL
REINFORCEMENT BARS AT STRUCTURE CORNERS AND JAMBS OF WALL OPENINGS.
GROUT CELLS CONTAINING REINFORCING BARS, ANCHOR RODS OR HARDWARE SOLID. MECHANICALLY CONSOLIDATE
GROUT IN PLACE TO ENSURE VOIDS DO NOT DEVELOP IN THE GROUTED CELLS.
LIMIT HEIGHT OF GROUT PLACEMENTS TO FOUR (4) FOOT LIFTS UNLESS SPECIFIC HIGH LIFT GROUTING PROCEDURES
ARE FOLLOWED.
PROVIDE 9 GAUGE LADDER-TYPE JOINT REINFORCEMENT AT 16 ” ON CENTER TYPICALLY AND 8 INCHES ON CENTER AT
PARAPETS.
PROVIDE BENT BARS IN BOND BEAMS AT BUILDING CORNERS TO MATCH BOND BEAM REINFORCING. BOND BEAM
REINFORCEMENT TO RUN CONTINUOUSLY THRU CONTROL JOINTS.
LINTELS FOR MASONRY SHALL BEAR ON SOLID OR SOLIDLY GROUTED HOLLOW CONCRETE BLOCKS.
BEARING PLATES AND ANCHOR RODS FOR BEAMS, JOISTS OR GIRDERS WILL BE LOCATED AND SUPPORTED VIA
TEMPLATES PRIOR TO GROUTING IN PLACE. DO NOT WET STICK ANCHORS IN WALLS.
PLACE POINTS OF BEARING ON TWO (2) COURSES OF HOLLOW MASONRY GROUTED SOLID OR TWO COURSES OF SOLID
MASONRY.
USE PREFABRICATED "L" AND "T" HORIZONTAL JOINT REINFORCEMENT AT WALL INTERSECTIONS.
PROTECT CONCRETE MASONRY UNITS FROM ABSORBING MOISTURE AND WATER DURING SHIPMENT, AND AT THE SITE
DURING CONSTRUCTION.
TEMPORARY BRACE THE STRUCTURE DURING CONSTRUCTION TO WITHSTAND LATERAL LOADS AND PRESSURES UNTIL
ADEQUATE DESIGN STRENGTH IS ACHIEVED.
TAKE NECESSARY PRECAUTIONS FOR MIXING AND PLACING MORTAR AND GROUT IN EITHER HOT OR COLD WEATHER, AS
SET FORTH IN THE ACI "MASONRY STRUCTURE BUILDING CODE COMMENTARY".
SUPPORT SLABS AND PORTIONS OF WALLS REMAINING ABOVE NEW OPENINGS UNTIL LINTELS ARE INSTALLED AND HAVE
REACHED DESIGN CAPACITY.
TOOTH AND PATCH IN NEW MASONRY THAT INTERFACES WITH EXISTING MASONRY CONSTRUCTION. TOOTH EVERY OTHER COURSE AND PROVIDE A MINIMUM DEPTH OF THE TOOTH EQUAL TO 1/2 THE LENGTH OF THE NEW OR EXISTING
MATERIAL, WHICHEVER IS LONGER.
CONCRETE MASONRY:
1.
2.
3.
4.
5.
6.
ALL CANOPY SUPPORTING STEEL TO BE STAINLESS STEEL GRADE 316.
ALL CANOPY SUPPORTING STEEL TO STEEL CONNECTIONS TO USE STAINLESS STEEL BOLTS GRADE 316.
DETAIL, FABRICATE AND ERECT STRUCTURAL STEEL IN ACCORDANCE WITH THE SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, INC (AISC) MANUAL.
THE HIRING OF A THIRD-PARTY COMPANY TO PERFORM STEEL SPECIAL INSPECTIONS IN ACCORDANCE WITH THE IBC, AISC, AND/OR STATE SPECIFIC CODES IS THE RESPONSIBILITY OF THE OWNER. THE SPECIAL INSPECTION REPORTS TO BE GIVEN
TO THE OWNER.
SUBMIT STEEL FABRICATION DRAWINGS TO THE ENGINEER OF RECORD FOR REVIEW. FABRICATION DRAWINGS TO CONTAIN SHOP FABRICATION DETAILS, FIELD ASSEMBLY DETAILS AND ERECTION DIAGRAMS. SCHEDULE SUBMISSIONS TO ALLOW
ADEQUATE TIME FOR REVIEW PRIOR TO STEEL FABRICATION.
WELDING TO BE PERFORMED BY CERTIFIED WELDERS IN ACCORDANCE WITH AWS - STRUCTURAL WELDING CODE
(ANSI/AWS D1.1 & D1.3)
STRUCTURAL STEEL:
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
A.
B.
C.
SHEAR CONNECTIONS NOT DETAILED ARE TO BE DESIGNED IN ACCORDANCE WITH THE AISC STEEL CONSTRUCTION MANUAL, [LATEST EDITION]. CONNECTIONS TO BE SIZED FOR THE REACTION POSTED ON THE DRAWINGS. IF NO REACTION IS POSTED ON THE DRAWINGS, BEAM CONNECTIONS ARE TO BE SIZED FOR THE LESSER OF: HALF THE TOTAL ALLOWABLE UNIFORM LOAD FOR THE APPLICABLE BEAM LENGTH OR MAXIMUM ALLOWABLE WEB SHEAR.
MINIMUM CONNECTION SHALL BE TWO BOLTS.
MOMENT CONNECTIONS NOT DETAILED ARE TO BE DESIGNED AS FULLY RESTRAINED IN ACCORDANCE WITH THE AISC STEEL CONSTRUCTION MANUAL, [LATEST EDITION]. CONNECTIONS TO BE SIZED FOR THE REACTION POSTED ON THE DRAWINGS. IF NO REACTION IS POSTED ON THE DRAWINGS, THE CONNECTIONS ARE TO BE DESIGNED TO DEVELOP
THE FULL FACTORED ELASTIC MOMENT CAPACITY OF THE BEAM.
MOMENT CONNECTIONS NOT DETAILED ARE TO BE DESIGNED AS FULLY RESTRAINED IN ACCORDANCE WITH THE AISC STEEL CONSTRUCTION MANUAL, [LATEST EDITION]. CONNECTIONS TO BE SIZED FOR THE REACTION POSTED ON THE DRAWINGS. IF NO REACTION IS POSTED ON THE DRAWINGS, THE CONNECTIONS ARE TO BE DESIGNED TO DEVELOP
THE FULL FACTORED ELASTIC MOMENT CAPACITY OF THE BEAM.
DESIGN BRACING CONNECTIONS NOT DETAILED FOR THE FORCES POSTED ON THE DRAWINGS. PROVIDE A MINIMUM OF
TWO BOLTS FOR ANGLES AND FOUR BOLTS FOR WT SECTIONS.
SHOP CONNECTIONS MAY BE WELDED OR BOLTED, FIELD CONNECTIONS WILL BE BOLTED UNLESS NOTED OTHERWISE.
MINIMUM FILLET WELD SIZE TO BE 3/16 INCHES UNLESS NOTED OTHERWISE.
TYPICAL BOLT SPACING IS TO BE 3 INCHES, MINIMUM EDGE SPACING IS TO BE 1 1/2 INCHES UNLESS NOTED OTHERWISE.
WHEN CONNECTIONS ARE NOT DETAILED, BOLT HOLES ARE TO BE AT TYPICAL WORKABLE GAGE IN ACCORDANCE WITH
THE AISC STEEL CONSTRUCTION MANUAL, 15TH EDITION.
BOLT HOLES ARE TO BE STANDARD, OVERSIZED HOLES ARE NOT PERMITTED UNLESS NOTED OTHERWISE. SLOTTED
HOLES MAY BE USED WITH THE CONSENT OF THE ENGINEER OF RECORD.
WHERE SLOTTED HOLES ARE USED, PROVIDE A STEEL PLATE WASHER OR CONTINUOUS BAR OF AT LEAST 5/16 INCH THICKNESS, WITH STANDARD HOLES, OVER ALL SLOTTED HOLES WHICH ARE IN THE OUTER PLIES OF ALL CONNECTIONS. THE PLATE WASHER IS TO COMPLETELY COVER THE SLOTTED HOLES AFTER ERECTION. WASHERS ARE
TO BE PLACED UNDER BOTH THE BOLT HEAD AND NUT.
SPACING BETWEEN DOUBLE ANGLES IS 3/8 INCHES, IF LEGS ARE UNEQUAL LONG LEGS ARE TO BE BACK TO BACK
UNLESS NOTED OTHERWISE.
DOUBLE ANGLE INTERMITTENT CONNECTIONS NOT DETAILED ARE TO BE CONNECTED BY INTERMITTENT PLATES, SUCH THAT THE SINGLE ANGLE SLENDERNESS RATIO (L/RZ) BETWEEN INTERMITTENT PLATES DOES NOT EXCEED 75 PERCENT OF THE DOUBLE ANGLE SLENDERNESS RATIO (L/RX OR L/RY) OF THE TOTAL UNBRACED LENGTH. MINIMUM OF
TWO (2) INTERMITTENT PLATES PER BRACING.
ALL GUSSET PLATES, CONNECTION PLATES AND CONNECTION ANGLES UNLESS NOTED OTHERWISE ARE TO BE A
MINIMUM 3/8 INCHES THICK UNLESS OTHERWISE NOTED.
UNLESS NOTED OTHERWISE, INSTALL BOLTS IN JOINTS IN ACCORDANCE WITH THE RCSC SPECIFICATION AS JOINT TYPE ST, "SNUG TIGHT" - PER RCSC SPECIFICATION TABLE 4.1 AND SECTION 8.1. INSPECTION IS PER RCSC SECTION 9.1.
UNLESS NOTED OTHERWISE, BOLTS HAVE BEEN DESIGNED WITH THREADS INCLUDED IN THE SHEAR PLANE.
NOTCH ALL RE-ENTRANT CORNERS OF COPED BEAMS TO A RADIUS OF 1/2 INCHES.
COPE THE BEAM FLANGES OF BEAMS FRAMING INTO THE WEBS OF COLUMNS WHERE THE BEAM'S FLANGES ARE WIDER THAN THE DEPTH BETWEEN THE COLUMN'S FLANGES TO FIT, DO NOT REMOVE THE ENTIRE FLANGES OF THE BEAMS IN
THIS CONDITION.
DO NOT FIELD CUT STRUCTURAL STEEL WITHOUT THE WRITTEN CONSENT OF THE ENGINEER OF RECORD. FLAME
CUTTING OF HOLES IS NOT PERMITTED.
FABRICATE BEAMS WITH THE NATURAL CAMBER UP. PROVIDE ADDITIONAL CAMBER SHOWN ON THE DRAWINGS.
ALL TUBE AND PIPE SECTIONS EXPOSED TO WEATHER WILL HAVE OPEN ENDS CAPPED WITH 1/4 INCH PLATE.
STRUCTURAL STEEL JOISTS
ALL STEEL JOISTS TO BE IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE "STANDARD SPECIFICATIONS, LOAD TABLES AND WEIGHT TABLES FOR STEEL JOISTS AND JOIST GIRDERS", AND THE AISC "MANUAL OF STEEL
CONSTRUCTION".
ALL JOIST CONNECTIONS TO END BEARING PLATES WILL BE WELDED UNLESS OTHERWISE NOTED.
ALL HORIZONTAL BRIDGING WILL BE AS NOTED ON DRAWINGS.
34.
35.
36.
37.
38.
39.
40.
41.
42.
GRIND SMOOTH ALL BURRS AND SHARP EDGES ON FABRICATED OR FIELD ALTERED WALKWAYS, HANDRAILS, LADDERS
AND CAGES.
STEEL BAR GRATING TO BE IN ACCORDANCE WITH NAAMM TYPE 19-W-4 (1 1/4" X 3/16" BEARING BARS). FIELD WELD IN ACCORDANCE WITH NAAMM, METAL BAR GRATING MANUAL UNLESS NOTED OTHERWISE. ALL GRATING WILL BE
GALVANIZED AFTER FABRICATION UNLESS NOTED OTHERWISE.
GRATING IS TO SPAN SHORT DIRECTION UNLESS NOTED OTHERWISE.
ALL GRATING CUT-OUTS TO BE BANDED PRIOR TO GALVANIZING.
STAIR TREADS TO BE IN ACCORDANCE WITH NAAMM TYPE 15-W-4 (1 1/4" X 3/16" BEARING BARS) WITH CHECKERED PLATE NOSINGS. STAIR TREADS TO BE GALVANIZED, CHECKERED NOSINGS TO BE PAINTED SAFETY YELLOW.
HANDRAILS AND TOE KICK PLATES TO BE PAINTED SAFETY YELLOW.
PROVIDE ADDITIONAL STEEL REQUIRED FOR ERECTION IN ACCORDANCE WITH OSHA 1926 AT NO COST TO THE OWNER.
REMOVE THIS ADDITIONAL STEEL UNLESS DIRECTED OTHERWISE BY THE OWNER.
PROVIDE TEMPORARY BRACING AND SHORING AS REQUIRED FOR THE SAFETY, STABILITY AND ALIGNMENT OF THE STRUCTURE. THE TEMPORARY BRACING IS TO REMAIN IN PLACE UNTIL THE MAIN LATERAL FORCE RESISTING SYSTEM
IS INSTALLATION IS COMPLETE, INCLUDING DIAPHRAGMS.
ERECTION PROCEDURES, SEQUENCES AND COORDINATION OF WORK WITH OTHER TRADES IS THE RESPONSIBILITY OF
THE CONTRACTOR.
7.
8.
9.
10.
11.
12.
13.
MATERIALS:
WIDE FLANGE SHAPES, WT SECTIONS ASTM A992
S SHAPES, CHANNELS, ANGLES ASTM A36
HOLLOW STRUCTURAL SECTIONS (HSS), RECT & ROUND ASTM A500 GRADE B
PLATE & BAR ASTM A572 GRADE 50
PIPE ASTM A53 GRADE B
1/2 INCH DIA BOLTS ASTM F3125 GRADE A325-N
5/8 INCH DIA BOLTS ASTM A307-N
3/4 INCH DIA BOLTS ASTM F3125 GRADE A325-N
1 INCH DIA BOLTS ASTM F3125 GRADE A490-N
ANCHOR RODS ASTM F1554 GRADE 55, SUPPLEMENT S1
WELDING ELECTRODE E70XX
STRUCTURAL BOLTED ASSEMBLIES CONSIST OF ONE (1) HIGH STRENGTH BOLT, ONE (1) ASTM A563 GRADE DH AND ONE (1)
ASTM F436 HARDENED WASHER UNDER THE TURNED ELEMENT UNLESS NOTED OTHERWISE.
ALL BOLTED ASSEMBLIES FOR SECONDARY CONNECTIONS (STAIR TREADS, LADDERS AND HANDRAIL) CONSIST OF ONE (1) 5/8 ICNH DIAMETER ASTM A307 HEX HEAD BOLT, ONE (1) ASTM A563 GRADE DH AND ONE (1) ASTM F436 HARDENED WASHER
UNDER THE TURNED ELEMENT.
BOLT ASSEMBLY FINISH TO BE HOT DIP GALVANIZED IN ACCORDANCE WITH ASTM A153 UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL TO BE PAINTED AFTER FABRICATION IN ACCORDANCE WITH SPECIFICATION SSPC-SP2. PAINT DRY FILM
THICKNESS TO BE 2 MILS.
NO PAINTING WITHIN CONTACT SURFACES OF SLIP-CRITICAL HIGH STRENGTH BOLTED CONNECTIONS AND 6 INCHES OF
FIELD WELDED CONNECTIONS.
ALL STRUCTURAL STEEL TO RECEIVE SPRAY APPLIED FIRE PROTECTION SHALL BE LEFT UNCOATED.
STRUCTURAL STEEL CONTINUED:
ICE IMPORTANCE FACTOR: 1.15
NOMINAL ICE THICKNESS: 1.5"
ICE LOADING:
DESIGN UPLIFT PRESSURE: 15 PSF
DESIGN HORIZONTAL WALL PRESSURE: 19.10 PSF
INTERNAL PRESSURE COEFFICIENT +/- 0.18
COMPONENTS AND CLADDING:
EXPOSURE CATEGORY: B
WIND IMPORTANCE FACTOR: 1.00
BASIC DESIGN WIND SPEED: 109 MPH
WIND LOADING:
WIDTH OF SNOW DRIFT: 4'-0"
DRIFT SURCHARGE: 22 PSF
THERMAL FACTOR: 1.2
SNOW LOAD IMPORTANCE FACTOR: 1.1
FLAT ROOF SNOW LOAD: 42 PSF
GROUND SNOW LOAD: 50 PSF
SNOW LOADING:
ROOF LIVE LOAD: 5 PSF
DEAD LOAD: 6 PSF
EXTERIOR CANOPY:
FLOOR LIVE LOAD: 60 PSF
FLOOR DEAD LOAD: 71 PSF
CORIDOR FLOOR INFILL:
RISK CATEGORY: III
GOVERNING BUILDING CODE: 2020 NEW YORK STATE BUILDING CODE
DESIGN CRITERIA:
EXP 01/31/2028
CERTIFICATE OF AUTHORIZATION NUMBER: 0023683
1 2 3
A
B
C
S-301
19' - 11" 19' - 0" 19' - 0"
6"
5"
5"
4' - 0"
EXTERIOR BRICK INFILL
TO MATCH EXISTING
11' - 9"
11' - 2"
EXTERIOR DOOR CMU
INFILL, TIE INTO EXISTING
S-301
S-101
S-301
S-301
A
B
5"
/1 S-101
L6 x4 x3 /8
(LL
V)
L6 x4 x3 /8
(LL
V)
NOTES:
1. INDICATES THE SPAN DIRECTION OF 6" NON-COMPOSITE SLAB OVER 1.5C18
METAL DECK (Fy=33KSI) PROVIDE 36/7 AND 4#10 SIDE LAP.
6'
- 0
SEE DETAIL 2 / S-501 FOR
ANCHORING TO CMU DETAILS
1/2" DIA HILTI KWIK-BOLT TZ2-CS
ANCHOR BOLT WITH 4 1/2"
EMBEDMENT AT 24" ON CENTER
23 MECHANIC STREET, SPRINGVILLE, NY 14141
D at e:
Tim e:
/2
1/
:5
1:
A M www.dwyerarch.com // ph: 315.473.1800
85 Allen Street, Suite 210 Rochester, NY 14608
110 W Fayette Street, Suite 225 Syracuse, NY 13202
DateDescription
Copyright 2025, Dwyer Architectural, LLC
No.
Sheet Title
Sheet No.
Project Information
Issue Date: MAY 08, 2026
BID DOCUMENTS
CON No.:
Client Project No.:
Project No.: 24-055
SUNY COLLEGE OF
ENVIRONMENTAL SCIENCE
AND
FORESTRY
MOON LIBRARY ADA
UPGRADES AND
RENOVATION
1 FORESTRY DRIVE SYRACUSE,
NY
13210
A red seal and a blue signature indicates an original document.
Note: Per NYSED Office of the Professions Commisioner's Regulations Part 69.5b, it is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter in any way an item bearing the seal of an architect.
Consultants
Drawn By: CCW Reviewer: GPS
S-101
STRUCTURAL PLAN
- FIRST FLOOR
SCALE: 1/4" = 1'-0"1 STRUCTURAL FOUNDATION PLAN - FIRST FLOOR
N
1. SEE S-001 FOR S-SERIES NOTES AND LEGENDS.
GENERAL NOTES
N
KEYPLAN
20' - 0"20' - 0"20' - 0"
0"
0"
0"
0"
4321E ED DCBAUPUP
AREA OF WORK
SCALE: 1/2" = 1'-0"2 STRUCTURAL GRATING ENLARGED PLAN - FIRST FLOOR
N
/1 S-101
FIRST FLOOR
ELEV 182'-6"
UPPER LEVEL
ELEV 182'-6"
NEW MASONRY WALL
TO ALIGN AND TIE
INTO EXISTING
3' - 4"
(F
IE
LD
V
ER
IF
Y)
7'
- 4
EXISTING EXTERIOR
WALL TO REMAIN
FIRST FLOOR
ELEV 182'-6"
UPPER LEVEL
ELEV 182'-6"
6" NON COMPOSITE METAL DECK
/1 S-101
S-501
SIM
S-501 1LLV6x4
A B
22' - 5"
FIRST FLOOR
ELEV 182'-6"
UPPER LEVEL
ELEV 182'-6"
/1 S-101
SEE PLAN 2 / S-101 FOR
ANCHOR BOLT DETAILS
L6x4x3/8
LEDGER ANGLE
NOTES:
1. CONTRACTOR TO CONFIRM THE EXISTING CMU WALL IS GROUTED SOLID.
SEE DETAIL 2 / S-501 FOR ANCHORING TO CMU SPECIFICATIONS AND NOTES.
6' - 0"
EXISTING
REINFORCED
CONCRETE BEAM
FIRST FLOOR
ELEV 182'-6"
UPPER LEVEL
ELEV 182'-6"
6" NON COMPOSITE METAL DECK
/1 S-101
S-501
S-501 1LLV6x4
23 MECHANIC STREET, SPRINGVILLE, NY 14141
D at e:
Tim e:
/2
1/
:5
1:
A M www.dwyerarch.com // ph: 315.473.1800
85 Allen Street, Suite 210 Rochester, NY 14608
110 W Fayette Street, Suite 225 Syracuse, NY 13202
DateDescription
Copyright 2025, Dwyer Architectural, LLC
No.
Sheet Title
Sheet No.
Project Information
Issue Date: MAY 08, 2026
BID DOCUMENTS
CON No.:
Client Project No.:
Project No.: 24-055
SUNY COLLEGE OF
ENVIRONMENTAL SCIENCE
AND
FORESTRY
MOON LIBRARY ADA
UPGRADES AND
RENOVATION
1 FORESTRY DRIVE SYRACUSE,
NY
13210
A red seal and a blue signature indicates an original document.
Note: Per NYSED Office of the Professions Commisioner's Regulations Part 69.5b, it is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter in any way an item bearing the seal of an architect.
Consultants
Drawn By: CCW Reviewer: GPS
S-301
STRUCTURAL
SECTIONS
SCALE: 3/8" = 1'-0"2 STRUCTURAL FOUNDATION SECTION - FACING WEST
1. SEE S-001 FOR S-SERIES NOTES AND LEGENDS.
GENERAL NOTES
SCALE: 3/8" = 1'-0"3 STRUCTURAL FOUNDATION SECTION - FACING EAST TO CMU WALL
SCALE: NTS1 STRUCTURAL SECTION - FACING NORTH
SCALE: 3/8" = 1'-0"4 STRUCTURAL FOUNDATION SECTION - FACING EAST TO CONCRETE WALL
A
B
C
3'
- 0
5/ 8"
3'
- 0
5/ 8"
3'
- 0
5/ 8"
3'
- 0
5/ 8"
3'
- 0
5/ 8"
3'
- 0
5/ 8"
3'
- 0
5/ 8"
1'
- 2
1"
3'
- 0
1/ 8"
3'
- 0
1/ 8"
3'
- 0
1/ 8"
3'
- 0
1/ 8"
3'
- 0
1/ 8"
3'
- 0
1/ 8"
3'
- 0
1/ 8"
1'
- 2
MC7x22.7
MC7x22.7
MC7x22.7
MC7x22.7
MC7x22.7
4"
6"
5"
10' - 0"
3' - 8"
10' - 5 7/8"
5"
S-401
MC7x22.7
L5 x3 x1 /4
L5 x3 x1 /4
S-501
S-501
S-501
TYP
TYP
TYP
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
W6x8.5
NOTES:
1. ALL STEEL MEMBERS ARE 316 STAINLESS STEEL.
2. ALL BOLTS ARE 304 STAINLESS STEEL.
S-501
TYP
A B C 22' - 5" 22' - 6"
9" 4" 20' - 5" 4" 1' - 2" 4" 20' - 8" 4" 7"
L5x3x1/4
W6x8.5 W6x8.5 MC7x22.7
W6x8.5 W6x8.5 W6x8.5 W6x8.5W6x8.5
W6x8.5W6x8.5
MC7x22.7 W6x8.5
MC7x22.7 MC7x22.7
L5x3x1/4
EXISTING BUILDING COLUMN EXISTING BUILDING COLUMNEXISTING BUILDING COLUMNEXISTING BUILDING COLUMN
3'
- 2
1/ 4"1'
- 7
T/ EXISTING CONC BEAM
/1 S-401
S-501
S-501
TYP
TYP
W6x8.5
3" 3" TYP 3"
NOTES:
1. ALL STEEL MEMBERS ARE 316 STAINLESS STEEL.
2. ALL BOLTS ARE 304 STAINLESS STEEL.
23 MECHANIC STREET, SPRINGVILLE, NY 14141
D at e:
Tim e:
/2
1/
:5
1:
A M www.dwyerarch.com // ph: 315.473.1800
85 Allen Street, Suite 210 Rochester, NY 14608
110 W Fayette Street, Suite 225 Syracuse, NY 13202
DateDescription
Copyright 2025, Dwyer Architectural, LLC
No.
Sheet Title
Sheet No.
Project Information
Issue Date: MAY 08, 2026
BID DOCUMENTS
CON No.:
Client Project No.:
Project No.: 24-055
SUNY COLLEGE OF
ENVIRONMENTAL SCIENCE
AND
FORESTRY
MOON LIBRARY ADA
UPGRADES AND
RENOVATION
1 FORESTRY DRIVE SYRACUSE,
NY
13210
A red seal and a blue signature indicates an original document.
Note: Per NYSED Office of the Professions Commisioner's Regulations Part 69.5b, it is a violation of the law for any person, unless acting under the direction of a licensed architect, to alter in any way an item bearing the seal of an architect.
Consultants
Drawn By: CCW Reviewer: GPS
S-401
STRUCTURAL
ENLARGED PLAN -
SHADE ADDITION
SCALE: 3/8" = 1'-0"1 STRUCTURAL FRAMING ENLARGED PLAN - SHADE ADDITION - ADD ALTERNATE #2 N
1. SEE S-001 FOR S-SERIES NOTES AND LEGENDS.
GENERAL NOTES
N
KEYPLAN
20' - 0"20' - 0"20' - 0"
0"
0"
0"
0"
4321E ED DCBAUPUP
AREA OF WORK
SCALE: 3/8" = 1'-0"2 STRUCTURAL FRAMING SECTION - SUN ADDITION - ADD ALTERNATE #2
KEYED NOTES
1 WT5 MEMBERS TO ALIGN WITH GLASS WINDOW PANELS ABOVE. VERIFY IN FIELD
2 ANCHOR TO EXISTING BEAM PER DETAIL 4 / S-502 SPACED 3" FROM EACH W6 AND FROM
ENDS OF LEDGER ANGLE
2 2
#5 @ 12" OC
4" C
OV
ER
METAL DECK
(SEE PLAN)
#4 @ 12" OC
#5 @ 12" REBAR, TO BE
SUPPORTED ON CHAIRS
METAL DECK
(SEE PLAN)
#4 @ 12" OC
6" 6" 4"
C
OV
ER
L6x4(LLV) LEDGER ANGLE L6x4(LLV) LEDGER ANGLE EXISTING CMU1/2" DIA HILTI KWIK-BOLT TZ2-CS ANCHOR BOLT
WITH 4 1/2" EMBEDMENT AT 24" ON CENTER
METAL DECK (SEE PLAN)
L6x4(LLV) LEDGER ANGLE
NOTES:
1. CONTRACTOR TO CONFIRM EXISTING CMU WALL IS GROUTED
SOLID. INSTALL HILTI HIT-IC 1/2" DIA WITH 3 3/16" EMBEDMENT
WITH HIT-HY 270 ADHESIVE AND HIT-SC 22x85 SIEVE SLEEVE AT
8" OC FOR ANCHORING TO HOLLOW CMU BLOCK.
EXISTING CONCRETE
SEE PLAN 2 / S-101 FOR
ANCHOR BOLT DETAILS
METAL DECK (SEE PLAN)
L6x4(LLV) LEDGER ANGLE
DRILL AND EPOXY INTO
EXISTING CONCRETE #4
@ 12" (2'-0" LONG)3"
1' - 0"
INSTALL BONDING AGENT TO EXISTING CONCRETE
1/4 1/4
W6
MC7
PLAN VIEW
A A
W6
MC7
1 1/2" MIN
COPE AS REQUIRED
SECTION VIEW A-A
(2) 1/2" DIA 304 SS BOLTS
1/4" x 3 1/2" x 3 1/2" PLATE
/1 S-401
3 1 /2"
1 1 /2"
1"
NOTES:
1. ALL STEEL MEMBERS ARE 316 STAINLESS STEEL.
2. ALL BOLTS ARE 304 STAINLESS STEEL.
EXISTING CONCRETE
COLUMN
EXISTING EXTERIOR
BUILDING WALL
3" 6" 1' - 10" 6"
MC7
1" MIN
HILTI HIT-HY 200 V3 WITH 3/4" DIA HAS-R
304/316 SS BOLT, 6" EMBEDMENT TYP
3' - 8"10"
/1 S-401
B
B
SECTION VIEW B-B
ELEVATION VIEW
EXISTING CONCRETE COLUMN
MC7
6"
2" 2 1
/2"
1" 1"
NOTES:
1. ALL STEEL MEMBERS ARE 316 STAINLESS STEEL.
2. ALL BOLTS ARE 304 STAINLESS STEEL.
1 1/2"
1" 1 1
/2" MC7x22.7
MC7x22.7
(2) 1/2" DIA 304 SS BOLTS
1/4 1/4
1/4" x 3 1/2" x 3 1/2"
PLATE1/2" MIN
COPE BEAM AS
REQUIRED
/1 S-401
NOTES:
1. ALL STEEL MEMBERS ARE 316 STAINLESS STEEL.
2. ALL BOLTS ARE 304 STAINLESS STEEL.
2 1 /2"
L5x3 LEDGER
HILTI HIT-HY 200 V3 WITH
1/2" DIA HAS-R 304/316 SS
BOLT, 4" EMBEDMENT TYP
EXISTING CONCRETE BEAM
/2 S-401
NOTES:
1. ALL STEEL MEMBERS ARE 316 STAINLESS STEEL.
2. ALL BOLTS ARE 304 STAINLESS STEEL.
L5x3 LEDGER ANGLE
1/4 1/4
1/4" x 3 1/2" x 3 1/2" PLATE WITH
(2) 1/2" DIA 304 SS BOLTS
EXISTING CONCRETE BEAM
1" 1 1
/2"
1 1/2"
/2 S-401
W6
1 7 /8"
NOTES:
1. ALL STEEL MEMBERS ARE 316 STAINLESS STEEL.
2. ALL BOLTS ARE 304 STAINLESS STEEL.
3'-0"+/- VERIFY IN FIELD
STAINLESS STEEL CANOPY (BY OTHERS)
W6
W6
3/4" MIN TYP
1/4" TEKS 5.0 HEAVY DUTY
SELF-DRILLING FASTENERS
SPACED 12" OC MAX
NOTES:
1. ALL STEEL MEMBERS…