NEW HAVEN
Job Corps Center New Haven, CT
Facility Planning Report Volume II
Supporting Data
Final December 2017
Department of Labor/ Office of Job Corps
NEW HAVEN
Job Corps Center New Haven, CT
Facility Planning Report Volume II
Supporting Data
Final December 2017
Gymnasium Building 7
VOLUME II - SUPPORTING DATA
EXECUTIVE SUMMARY
1.0 SITE LAYOUT AND PLANS
• Location Map
• Exisiting Site Plan
2.0 DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Environmental Management Report
• Radon Report
• Site Descriptions
• Building Descriptions
3.0 DEFICIENCIES
APPENDICES - CORRESPONDENCE AND REPORTS
Appendix A.
• Center Reveiw Meeting Minutes
• Survey Brief
• Student Questionnaire
Appendix B.
• Life Safety Defi ciencies and List
Appendix C.
• O&M Defi ciencies List
Appendix D.
• Active Warranty List
Executive Summary
The Facility Survey for the New Haven JCC was completed the week of July 10, 2017.
The information presented in Volume II, Supporting Data, represents the current status of the campus.
The information includes the following:
Existing site layout Overall status of existing building and structures Space utilization by building and function compared to recommended standards Status of environmental elements of the Center’s operations Details on the site and buildings and structures based on architectural, electrical, and mechanical survey and supporting documentation Presentation of the status of historical deficiencies and compilation of deficiencies documented through this survey Supporting documentation, as presented in the appendices of the center review meeting; survey brief and student questionnaire; life safety IA/IIA transmittal;
active warranties; and Federal Real Property Council (FRPC) Measures Matrix
Section 1.0 of this volume addresses site layout and plans while Section 2.0 presents details on the buildings and structures. Section 3.0 presents historic deficiencies and their status as well as new ones identified in this survey. The appendices provide additional information as noted below:
Appendix A. Survey Brief Questionnaire Appendix B. Life Safety Deficiencies and List Appendix C. O&M Deficiencies List Appendix D. Active Warranty Report
EXECUTIVE SUMMARY
1.0 - Site Layout and Plans
NEW HAVEN
JOB CORPS CENTER
NEW HAVEN, CONNECTICUT
NEW HAVEN JCC
4 MI20
2.0 - Descriptions
BUILDINGS AND STRUCTURES
00105 NEW HAVEN 12/04/2017
1Page: of Date:
0001 - MAIN BUILDING
0002 - UNC HALL WOMEN'S
DORMITORY
0003 - SPELLMAN HALL WOMEN'S
DORMITORY
0004 - MEN'S DORMITORY/VOCATIONS
0005 - PROPERTY DEPARTMENT
0007 - GYMNASIUM
0008 - MAINTENANCE
0009 - WELCOME CENTER
0020 - VOCATIONAL STORAGE
0021 - BROOKSIDE SECURITY OFFICE
0022 - VOCATIONAL STORAGE
0010 - GAZEBO (15FT X 30FT)
0011 - BUS SHELTER (8FT X 16FT)
0012 - PROPERTY SHED (10FT X 16FT)
0014 - CLOTHING STORAGE SHED (12Ft x 16Ft)
0015 - GREEN HOUSE (10FT X 14FT)
0016 - STORAGE SHED (10FT X 10FT)
0017 - STORAGE SHED (8FT X 10FT)
0018A - CLOTHING STORAGE SHED
(12FT X 16FT)
0019 - STORAGE SHED (8FT X 8FT)
0024 - STORAGE SHED (8FT X 31FT)
0025 - MAINTENANCE STORAGE 1 (20FT
X 38FT)
0026 - MAINTENANCE STORAGE 2 (15FT
X 25FT)
0027 - STORAGE SHED (6FT X 7FT)
0028 - CONEX STORAGE (8Ft x 40Ft) 0029 - CONEX STORAGE (8Ft x 40Ft) 0030 - DECK (12Ft x 12Ft) 0031 - DECK (20Ft x 20Ft) 0032 - FURNITURE STORAGE ( 8Ft x 40Ft)
Name GSF
36,115 6,500
6,500
29,393 1,000
15,526 2,008
1,234
1,260
Active Active
Active
Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active Active
Active Active Active
Active
Active Active Active Active Active Active
StatusType
Building Building
Building
Building Building Building Building Building Building Building Building Structure Structure Structure Structure
Structure Structure Structure Structure
Structure Structure Structure
Structure
Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Business/Ass Residential
Residential
Business/Res Storage Assembly Storage Business Storage Business Storage Assembly Storage Storage Storage
Business Storage Storage Storage
Storage Storage Storage
Storage
Storage Storage Storage Assembly Assembly Storage
Fair Good
Good
Good Good Fair
Good Good Good Good Good Good Good Good Good
Good Good Good Good
Good Good Good
Good
Good Good Good Good Good Good
ConditionAsset Number
0010500002 0010500003
0010500004
0010500005 0010500007 0010500009 0010500010 0010500011 0010508129 0010508139 0010508137 0010500012 0010500013 0010500006 0010508144
0010508132 0010508133 0010508134 0010508145
0010508136 0010508141 0010508142
0010508143
0010508135 0010508147 0010508148 0010508149 0010508150 0010508151
11 100,746
18 4,487
29 105,233
Buildings
Structures
Total
GSF
GSF
GSF
Summary
12/04/2017
Space Utilization By Function 00105 New Haven Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 132 Non Residents 25
157Total Students
(132)
(200)
(157)
DIFFERENCE
14,256
13,300
4,082
17,669
20,542
5,535
Lounge Other Shower/Toilet Sleeping excl. SPD(40 rooms; 145 beds) Storage
Academic (200) Non-Academic
8 -- ACT (Off-Ctr) 20 -- Carpentry + 30 -- Culinary Arts + 24 -- Emergency Med Techn 24 -- Facilities Maint. and Const. + 50 -- Nursing Assistant +
Vocational Theory (124)
Dining (1 Serving) Food Preparation Food Storage
1,466 1,891 1,718
12,102
2,575 4,718
3,657 3,204
3,061
1,729
3,520 1,123
1,320 1,056 1,584 9,504
2,000 2,000
1,500 1,800
1,800 2,000
1,240
2,512
2,598 -300
2,718
2,157 1,404
-216 1,261 -1,146
1,008
Vocations
3,413
7,242
1,453
12/04/2017
Space Utilization By Function 00105 New Haven Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SECURITY
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 298.15 46,809 65,238
(157)
(157)
(157)
(157)
(157)
DIFFERENCE
100,746
0.65
TOTAL GSF
NET TO GROSS RATIO
6,975
1,445
3,140
3,140
10,812
2,560
4,938
2,661
Aerobics/Exercise Arts & Crafts Canteen Gymnasium Multipurpose Room Recreation Office Recreation Storage Snack Bar Weight Room
Medical/Dental
Administration Child Development Center (0)
Operations & Maintenance Warehouse
SECURITY
9.20
7,345
2,560
2,770 2,168
1,759
1,445
3,140
1,256 1,884
1,115
-370
-982
RESIDENT
NON-RESIDENT
(132)
(25) 15
50 6,600
3,837
1,115
1,798
-479
18,429
Net Square Footage By Building Date: 12/04/2017 Page: 1
Center: NEW HAVEN (00105) of 4
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
6,306 2,996 2,800
1,074
0004 - MEN'S DORMITORY/VOCATIONS
0002 - UNC HALL WOMEN'S DORMITORY
0003 - SPELLMAN HALL WOMEN'S DORMITORY
0002 - UNC HALL WOMEN'S DORMITORY
0004 - MEN'S DORMITORY/VOCATIONS
0003 - SPELLMAN HALL WOMEN'S DORMITORY
0003 - SPELLMAN HALL WOMEN'S DORMITORY
0002 - UNC HALL WOMEN'S DORMITORY
0004 - MEN'S DORMITORY/VOCATIONS
0002 - UNC HALL WOMEN'S DORMITORY
0004 - MEN'S DORMITORY/VOCATIONS
0003 - SPELLMAN HALL WOMEN'S DORMITORY
0003 - SPELLMAN HALL WOMEN'S DORMITORY
0004 - MEN'S DORMITORY/VOCATIONS
0002 - UNC HALL WOMEN'S DORMITORY
Bldg Name Actual NSF Difference
12,102
1,466
1,718
1,891
Sub Total: 17,669
9,504
1,320
1,584
1,056
14,256
2,598
-300
( 132
3,413
20 rooms; 81 beds 10 rooms; 32 beds 10 rooms; 32 beds
Page: 2
Center: NEW HAVEN (00105) of 4
EDUCATION
FOOD SERVICE
Academic
Vocational Theory (124)
Carpentry
Culinary Arts
Facilities Maint. and Const.
Non-Academic
Nursing Assistant
Emergency Med Techn
Food Preparation
Food Storage
Dining (1 Serving)
Function Suggested
NSF
1,729
2,477 1,180
3,204
1,902 1,159
3,576
1,123
3,520
0001 - MAIN BUILDING
0004 - MEN'S DORMITORY/VOCATIONS
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0004 - MEN'S DORMITORY/VOCATIONS
0004 - MEN'S DORMITORY/VOCATIONS
0004 - MEN'S DORMITORY/VOCATIONS
0022 - VOCATIONAL STORAGE
0001 - MAIN BUILDING
0004 - MEN'S DORMITORY/VOCATIONS
0020 - VOCATIONAL STORAGE
0004 - MEN'S DORMITORY/VOCATIONS
0003 - SPELLMAN HALL WOMEN'S DORMITORY
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0004 - MEN'S DORMITORY/VOCATIONS
0004 - MEN'S DORMITORY/VOCATIONS
0004 - MEN'S DORMITORY/VOCATIONS
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0001 - MAIN BUILDING
Bldg Name Actual NSF Difference
2,575
1,729
3,657
3,204
3,061
4,718
1,123
3,520
Sub Total:
Sub Total:
20,542
5,535
2,000
1,240
1,500
1,800
1,800
2,000
2,000
2,512
13,300
4,082
2,157
1,404
1,261
2,718
-1,146
-216
1,008
7,242
1,453
Page: 3
Center: NEW HAVEN (00105) of 4
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
Multipurpose Room
Snack Bar
Arts & Crafts
Gymnasium
Weight Room
Canteen
Aerobics/Exercise
Recreation Storage
Recreation Office
Medical/Dental
Administration
Child Development Center
Warehouse
Operations & Maintenance
Function Suggested
NSF
7,345
2,560
2,638
2,168
1,464
0007 - GYMNASIUM
0007 - GYMNASIUM
0007 - GYMNASIUM
0007 - GYMNASIUM
0007 - GYMNASIUM
0007 - GYMNASIUM
0007 - GYMNASIUM
0007 - GYMNASIUM
0007 - GYMNASIUM
0001 - MAIN BUILDING
0009 - WELCOME CENTER
0001 - MAIN BUILDING
0001 - MAIN BUILDING
0005 - PROPERTY DEPARTMENT
0008 - MAINTENANCE
0009 - WELCOME CENTER
Bldg Name Actual NSF Difference
7,345
2,560
2,770
2,168
1,759
Sub Total:
Sub Total:
Sub Total:
Sub Total:
10,812
2,560
4,938
2,661
1,445
3,140
1,884
1,256
6,975
1,445
3,140
3,140
1,115
-370
2,168
-982
3,837
1,115
1,798
-479
Page: 4
Center: NEW HAVEN (00105) of 4
SECURITY
SECURITY
Function Suggested
NSF
0021 - BROOKSIDE SECURITY OFFICE
0009 - WELCOME CENTER
Bldg Name Actual NSF Difference
Sub Total: 521
( 157
Environmental Management Report Center: NEW HAVEN (00105)
Page: 1 Date: 12/04/2017 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
No Building 5, storage shed
Gasoline (25 gals), propane (10 lbs), oil-based paint (30 gals) Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Non-Compliance3
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
Fuel oil boilers Minor Source - Exempt
Non-Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazardous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
Building 1
Building 4
Building 1
10,000
4,000
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Diesel Fuel
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Connecticut Waste Processing No N/A
N/A N/A N/A
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
No Survey Performed None N/A
N/A N/A N/A No Yes
CO, PM-10
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary Containment
4 Petroleum - Heating Oil 275 Building 8 Yes No
Tank Status Active
Active
Active
Active
Tank Status Prevention/Detection
Radon
Date: 12/04/2017Center : New Haven (00105) Page: 1 of 1
0001 - MAIN BUILDING
0002 - UNC HALL WOMEN'S DORMITORY
0003 - SPELLMAN HALL WOMEN'S DORMITORY
0004 - MEN'S DORMITORY/VOCATIONS
0005 - PROPERTY DEPARTMENT
0007 - GYMNASIUM
0008 - MAINTENANCE
0009 - WELCOME CENTER
0020 - VOCATIONAL STORAGE
0021 - BROOKSIDE SECURITY OFFICE
0022 - VOCATIONAL STORAGE
Bldg Name
08/29/2003
08/29/2003
08/29/2003
Test Date
Yes
Yes
Yes
No
N/A
No
No
No
No
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
Satellite view of New Haven JCC
Page: 1 Date: 12/04/2017 of 5
Paving Type for Roads & Parking Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterSouth Central RegionalPublic Water Authority
None 0None
The domestic water supply is provided by the South Central Regional Water Authority. Buildings on the Wintergreen site have one master meter with the exception of Building 7, which is separately metered. Buildings on the Brookside site have one master meter.
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
No 0 5None Municipal
There are no fire hydrants at the Center, however, the number of fire hydrants provided by the city around the Center is adequate. The Center is supported by the New Haven Fire Department which has a five minute response time.
Number of Deficiencies = 3
Number of Deficiencies = 1
Number of Deficiencies = 1
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures11 18Hilly
Surrounding
Outdoor Recreation
Suburban
Basketball Public Road
Brookside Site
Child Care Center Play Area
Wintergreen Site
Chain Link
Chain Link
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good
Number of Deficiencies = 2
Fencing
Other Features
Page: 2 Date: 12/04/2017 of 5
Comments:
Sewage Treatment Flow
The Center sewer system is served by the City of New Haven Water Pollution Control Authority.
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: Buildings on the Wintergreen site have one master meter with the exception of Building 7, which is separately metered. Building 4 on the Brookside site is supplied with natural gas and a meter.
Southern Connecticut Gas Company
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 2
Drain Type On-Site Storm Water Management
Surface Run-off N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Comments: Stormwater from roof drainage is underground.
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
6. Central Plant: None
Page: 3 Date: 12/04/2017 of 5
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
United Illuminating Company
The campus is located on two adjacent sites separated by Brookside Avenue. One site consists of seven buildings (1, 2, 3, 5, 7, 8 and 9) and the other site of four buildings (4, 20, 21 and 22). Primary underground electrical power service for the Wintergreen site enters at three locations from utility-owned primary power overhead distribution located along Wintergreen Avenue. These three entries feed two pad-mounted, step-down, utility-owned transformers with corresponding wall-mounted secondary utility meters located in Building 1 (in the main electrical room) and Building 7 (on the exterior wall) and one pole-mounted, utility-owned step-down transformer and corresponding meter serving Building 8. Building 1 also serves Buildings 2, 3, 5 and 9. The systems serving Buildings 1, 2, 3 and 7 are 120/208V, 3-phase, 4 wire, the system serving Building 8 is 120/240V, 1-phase, 3 wire.
New primary underground electrical power service for the Brookside site enters at three locations from utility-owned primary power overhead distribution located along Brookside Avenue. These three entries feed one pad-mounted, step-down, utility-owned transformer with corresponding wall-mounted secondary utility meter located in the Building 4 electrical room, and two pole-mounted, utility-owned, step-down transformers and corresponding meters serving Buildings 21 and 22. Building 4 serves Building 21. The systems serving Buildings 4 and 22 are 120/208V, 3-phase, 4 wire, the systems serving Buildings 20 & 21 are 120/208V, 1-phase, 3 wire. A 250 kW (312,5 kVA) generator (Onan, 250 ODFN, 3-phase, 120/208V, PF 0.8, 4747 hours), located near the SE Building 1 corner with a 1000A Onan automatic transfer switch (ATS), located in the main electrical room in Building 1, serves essential building loads in Building 1. Cogeneration once utilized in Building 1, was removed, with transformer and disconnect switch abandoned in place.
Pole and Pad Utility
Utility Utility
No
4.67/2.7 kV, 3-Phase, 4 Wire
120/208V, 3-Phase, 4 W and 120/240V, 1-Phase, 3 WOverhead & Underground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 47. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Diesel
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole, Bollard Building Sport Light
Photocell Photocell Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center Utility, Center Yes Good
Comments: 50-foot high wood poles, each with two 400W flood, light high pressure sodium fixtures, utilized for roadway and parking lighting, controlled by the fixture-mounted photocells, are leased by the Center from the local electrical utility company. The rest of the metal pole-mounted, wall-mounted and bollard type light fixtures belong to and are maintained by the Center. 25-foot high metal poles, each with a 250W shoe type metal-halide light fixture, are controlled by fixture-mounted photocells. The 2 1/2 foot high bollards are controlled by photocell and time switch through the lighting contactor in Building 7. 30-foot high metal poles, each with a pole-mounted sports type metal halide light fixture, for playfield lighting are controlled by time clock and photocell through the lighting contactor in Building 7. About 15-foot high decorative metal poles, each with colonial style light fixture, are utilized for walkway/parking lighting throughout the second site (across from Building 4).
ATS MTS
Yes No
Number of Deficiencies = 3
Metering Individual
Page: 4 Date: 12/04/2017 of 5
Comments:
Telephone Company
On-site Line Owner
Building 1 is utilized as the main communication service entrance for the Center, where the main network closet (MC) and DEMARC point are located. The telephone/data equipment is provided with 3 UPS units (two 2200XL APC and a 1500 AVR) utilized as surge protection and power backup the system, until the emergency generator with an automatic transfer switch starts. Center has 5 T1 lines, 4 through AT&T and one dedicated voice line through ChoiceOne Communications, provided and managed by JCDC. Cisco VoIP, the Center's communication system managed by JCDC, is part of Job Corps United Communications Cluster. System hardware is not on site and routed through Limestone, ME Job Corps Data Center. 4 AT&T T1 lines are setup for load balancing and redundancy on 2 Cisco 3800 routers. The system hardware, manufactured by Cisco and housed in the MC, includes 2 Cisco Catalyst 3500 series switches; a Catalyst 6500 series switch, providing Ethernet; a Cisco 1800 series router, for Ethernet expansion; Blue Coat, for WAN service and 2 Cisco 3800 series routers. The Center has 6 analog phone lines (POTS), which provide fax services as well as backup/emergency services, with five POTS lines serving Building 1 and one serving RA office in the dorm of Building 4. Addressable fire alarm panels in Buildings 1, 2, 3, and 4 are monitored by the central annunciator panel in Welcome Center Building 9 (non-occupied after hours). FA panel in Building 7 reports to the FA panel in Building 1. Last FA inspection was conducted by Fireworks LLC ((203) 271-7079) September 19/20, 2016. Cable TV is provided in Dormitory Buildings 2, 3 and 4 and Gymnasium Building 7. Dormitory Buildings 2, 3, 4 and lower floor of Building 4 wing exit doors are provided with door alarms sounding at the door. Magnetic door alarm contacts in Buildings 5 & 8 are connected to Gemini security panels, in Building 1 to Honeywell panel. Low voltage & communications wiring is underground.
AT&T/ChoiceOne Communications
Maint. Responsibility
Center Center
Magnetic Door/ Alarms/Security Panels
01/19/1988
01/19/1988
03/01/2001
01/19/1988
05/04/2010
Center
Center
Center
Center
Private
Active
Active
Active
Active
Abandoned
Underground, Regulated
Underground, Regulated
Aboveground
Underground, Regulated
Aboveground
Building 1
Building 4
Building 8
Building 1
Building 21
Yes
Yes
No
No
No
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Heating Oil
Petroleum - Diesel Fuel
Propane
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install DateID
Reg.
10000
Number of Deficiencies = 1
9. Electrical (Communication/Alarm/Security)
Heating
Heating
Heating
Generator
Heating
Purpose
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Number of Deficiencies = 11
Fire Alarm Security
Page: 5 Date: 12/04/2017 of 5
ACCESSIBILITY
Yes
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Earthquake Risk
Medium Low LowLow LowIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Number of Deficiencies = 1
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
The asphalt paving has deteriorated throughout the campus.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
Comments: Center has an active composting operation.
NO
NO
NO
NO
NO
Yes
NO
NO
42 %
Building Descriptions and Structures
BUILDING 1 - MAIN BUILDING
Building Descriptions
Page: 1 of 53
Building: 0001 - MAIN BUILDING
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry
Wall Roof Rigid Rigid
Comments: Main vestibule has automatic sliding doors leading into corridor.
Metal Units - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business/Assembly 36,115 21,524 2 Owned 1965 Not Evaluated
Comments: Audio/visual devices are not provided in the public toilet rooms with exception of the public toilet rooms in the dining area.
WC door swings are not ABA compliant
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1. Number of Deficiencies = 1
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Material
The roof is at the end of its service life.
Drainage Year Life
Remaining Type Area Served
EPDM Interior Roof Drains 1996 0 Flat Entire Building
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 53
Building: 0001 - MAIN BUILDING
INTERIOR FINISH
Carpet Ceramic Tile Quarry Tile Vinyl Tile
CMU Drywall Exposed Structure
Metal Units - Metal Frame Wood Units - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Dumbwaiter Elevator Comments: The dumbwaiter is no longer in use.
Awning Units - Steel Frame; Single Glazing;
Acoustical Tile Gypsum Board
Windows6.
Floors1.
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4. Number of Deficiencies = 1
Ceilings
Page: 3 of 53
Building: 0001 - MAIN BUILDING
Mechanical
Mechanical
Mechanical
Mechanical
Mechanical
Mechanical
Restroom
Culinary Arts
Kitchen
Dishwashing
Janitor's Closet
Toilet/Shower
Ventilation Area ServedExhaust Ventilation
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Two Trane rooftop air handling units (models TCD102B300DA and TCD120B300DA) are provided with hot water coils. These units serve the dining and serving areas.
The main and culinary arts kitchens are provided with makeup air from Trane model DF0A115 gas direct-fired makeup air units.
Ceiling recessed cabinet unit heaters are located at entry doors.
The north wing of the upper level, which contains CTP, medical/dental, and administration spaces is provided with an underfloor radiant heating system.
Two National US Three-Pass Scotch Generator model G-125-LW boilers with Cyclonetic gas-oil burners provide heating hot water. Each boiler has a maximum gross output rating of 4,180 MBH.
Heating hot water is also used to make domestic hot water. Heating hot water is circulated throughout the building, primarily to 14 air handlers.
Comments:
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1. Number of Deficiencies = 4
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Direct
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Single Duct
Unit Heater
Makeup Air Unit
Unit Heater
Underfloor Radiant
Single Duct
None
Two-Pipe
None
Two-Pipe
Two-Pipe
Two-Pipe
Electronic
Electronic
Electronic
Electronic
Electric
Electronic
Mechanical
Natural
Mechanical
Natural
Natural
Mechanical
None
None
None
None
None
None
Dining Hall
Storage
Kitchen
Vestibules
Classrooms and Offices
Ventilation2.
Page: 4 of 53
Building: 0001 - MAIN BUILDING
Packaged Direct
Expansion (Air Source)
Packaged Direct
Expansion (Air Source)
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Window Unit
Fan Coil
Single Duct
None
None
Refrigerant
Refrigerant
Pneumatic
Electric
Electric
Pneumatic
Natural
Mechanical
Natural
Mechanical
None
None
None
None
Dining Hall
Offices
Storage
Entire Building
Two Trane rooftop air handling units (models TCD102B300DA and TCD120B300DA) provide cooling to the dining and serving areas.
There are four split ductless systems that cool storage areas and equipment rooms. There are two Mitsubishi systems (models PU18EK and PU12EK) and two Samsung model US24A2RC systems.
Air handling units with hot water coils have evaporator coils matched to the following condensing units:
Two Trane model TTA048C300A0 Two Trane model TTA060C300A0 Two Trane model TTA090A300CB One Trane model TTR018C100A1 One Trane model TTA048A300A0 One Trane model TTA072A3000A0 One Trane model TTA060A300A One Trane model BTA036D300A0
Additionally, there are two split DX air conditioners serving lower level culinary arts spaces:
Rheem model RAWD-076CAZ Rheem model RAWD-100CAZ
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Number of Deficiencies = 1Air Conditioning
Page: 5 of 53
Building: 0001 - MAIN BUILDING
The gas-fired water heater is a 180 gallon, A.O. Smith model HW670932 with a heat input and output capacity of 660,000 BTUH and 513,800 BTUH, respectively. The water heater was installed in 2000.
Most of the domestic hot water is provided by four A.O Smith hot water storage tanks (180 gallon, A.O Smith model # TJV200M) with heat exchangers that receive heating hot water from the boilers.
Comments:
Comments:
Cast Iron Outdoor None
The outdoor grease trap has a capacity of 5,000 gallons.
Electric Water Cooler Hose Bibb Lavatory Portable Emergency Eyewash Sink Urinal Water Closet (Flush Valve)
Oil, Gas (Natural)
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet
Chemical
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING Number of Deficiencies = 1
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
Location UL300 Compliance Status Main Kitchen (two hoods)
Culinary Arts Kitchen
Compliant
Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 6 of 53
Building: 0001 - MAIN BUILDING
Comments: Underground service for this building is provided from a pad-mounted, utility-owned transformer located south of the building. The service entrance has a 2-section Siemens switchboard (MDP), which consists of a 2,000A main disconnect switch section and a 2,000A molded case circuit breaker (CB) distribution section. This building provides services to Buildings 2, 3, 5 and 9. The power meter for all these buildings is located in this electrical room. The MDP serves Buildings 2 & 3 ((2) 225A CB), ATS (600A CB), panels A, B, CA & D ((4) 150A CB), panel C (100A CB), panel M (400A CB), bakery (vacant-400A CB), elevator (100A CB), and exhaust fans (35A CB). There is a 250 kW (312.5 kVA) emergency generator (Onan, 250 ODFN, 3-ph., 120/208V, PF 0.8, 4747 hours), located near the SE Building 1 corner with a 1000A, 3-pole Onan automatic transfer switch (ATS), located in the Building 1 main electrical room, and 600A emergency panelboard (EMD). The EMD serves Building 9, panels BR, BRE, E & KE.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. Most fluorescent light fixtures use T8-fluorescent lamps. Cove lighting supplements ambient lighting provided by HID in the dining area.
Comments: Most building areas do not have designated emergency lighting fixtures and the only source of emergency lighting is the lighting fixtures connected to the emergency panel backed up by the emergency generator. Selected compact fluorescent light fixtures utilized for corridor lighting and linear fluorescent light fixtures, in the serving area and in the medical/dental offices are served from the emergency panel backed up by emergency generator. Battery backup exit signs, emergency light fixtures and combination emergency light/exit signs are also provided (in the dining area).
LED
Comments: Building-mounted exterior LED light fixtures are controlled by photocells located on the roof utilizing lighting contactors located in the electrical closets.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent and HID
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Toilets
Dining/Lunch Rooms
Dishwashing
Food Preparation
Storage Rooms
Classrooms
Medical/Dental
Wards (Patient)
Area Recommended Level
Recorded Level Light Type
Generator Backup Battery Backup
Main Switchboard 120/208V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 4
Exterior Lighting1. Number of Deficiencies = 1
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 1
LIGHTING
Page: 7 of 53
Building: 0001 - MAIN BUILDING
FIRE ALARM
Comments: The addressable fire alarm control/annunciator panel (Notifier APF 1010 ) is located in the corridor of the administration area. Remote annunciator panel (Notifier) is located at the main building lobby (south entrance). The building's FA control/annunciator panel is monitored by the center's central annunciator panel located in Welcome Center Building 9 (non-occupied after hours). Also, FA control/annunciator panel in Building 7 reports to the FA control/annunciator panel in Building 1. Audio/visual (A/V) alarm devices are installed on the exterior building walls for added protection. Main fire alarm annunciator panel supplies 24V power to the annunciator panel in Building 9.
Comments: This building is utilized as the main communication service entrance for the center, with the main network closet (MC) and DEMARC point. The telephone/data equipment is provided with 3 UPS units (two 2200 XL APC and a 1500 AVR) utilized as surge protection and power backup for the system, until the emergency generator with an automatic transfer switch started. 5 T1 lines, 4 of which through AT&T and one dedicated voice line through ChoiceOne Communications, are provided and managed by JCDC. Cisco VoIP, the center's communication system, managed by JCDC, is part of Job Corps United communications Cluster. 4 AT&T T1 lines are setup for load balancing & redundancy on 2 Cisco 3800 routers. The system hardware includes 2 Catalyst 3500 and 1 Catalyst 6500 series switch, a Cisco 1800 series router, & Blue Coat. The magnetic door alarm contacts in the adm. and medical/dental offices exterior doors & motion detectors are connected to a Honeywell security panel. Automatic doors are provided.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Exterior Audio/Visual Device Heat Detector Magnetic Door Holder Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Connected to Main System Magnetic Door/Alarm None TV with VCR
Telephone Security Public Address Television
Number of Deficiencies = 4
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Roof is failing.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas Yes YesZone
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Good Mechanical: Good Electrical: Good
This building has been recommended for renovation in the Long Range Development Plan.
RENOVATION RECOMMENDATION
Type Location N/A N/A
There are no sleeping rooms in this building. There are carbon monoxide sensors in the Wellness Area only.
CARBON MONOXIDE DETECTION
Detection Required No
Number of Deficiencies = 0
IMPAIRMENT
Page: 8 of 53
Building: 0001 - MAIN BUILDING
IMPAIRMENT
Potentially Impaired
DOL Responded
DOL Determination
Potential Impaired Comments DOL Determination Discussion/Comments
BUILDING 2 - UNC HALL WOMEN'S DORMITORY
Page: 9 of 53
Building: 0002 - UNC HALL WOMEN'S DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry
Wall Roof Rigid Rigid
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Residential 6,500 4,455 1 Owned 1965 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Built-up Roofing Scuppers 2006 9 Flat Entire Building
3. Roof
Page: 10 of 53
Building: 0002 - UNC HALL WOMEN'S DORMITORY
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall Painted CMU
Wood Units - Metal Frame
Mechanical
Mechanical
Mechanical
Laundry
Mechanical Room
Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
None
Double Hung - Steel Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Two Utica model UB95M-200 boilers provide heating hot water. Each boiler has a maximum heat output of 200 MBH. The boilers were installed in 2008. Heating hot water is circulated through coils installed in three Magic Air model HB20-36-2W air handlers.
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Hot Water Boiler
Single Duct Two-Pipe Electronic Mechanical None Entire Building
Page: 11 of 53
Building: 0002 - UNC HALL WOMEN'S DORMITORY
The building is provided with domestic hot water from two Weil Mclain model Plus 100 Series 3 heat exchanger water heaters. Each has a 199,900 BTUH, absorbing heat from hot water generated by the heating boilers. The water heaters were installed in 2008.
Comments:
Cast Iron None None
Bathtub Electric Water Cooler Hose Bibb Laundry Tray Lavatory Portable Emergency Eyewash Shower Sink Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Single Duct Refrigerant Electronic Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
There are 3 rooftop condensing units matched to evaporator coils in the three air handlers. The condensing units are Heil model H4A460GKA100, each with a cooling capacity of 5 tons. The units were installed in 2008.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Page: 12 of 53
Building: 0002 - UNC HALL WOMEN'S DORMITORY
Comments: Underground service for this building is provided from a 225A circuit breaker in the MDP located in the Building 1 main electrical room. The service is terminated in a wire trough which feeds two 250A, MLO panelboards. This building is metered from the meter located in Building 1.
FIRE ALARM
Comments: The fire alarm control/annunciator panel Gamewell FCI (installed 2015) is located in the R.A. office. The system is fully addressable and has two Notifier modules (for alarm and trouble) to interconnect to the center's Notifier network system, and to central fire alarm annunciator panel located in Welcome Center Building 9 (non-occupied after hours). Audio/visual (A/V) alarm devices are installed on the building exterior walls for added protection.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Exterior Audio/Visual Device Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. Surface-mounted task lights above the beds are provided in the sleeping rooms, about 50% of which use T12 lamps. Sky lights are provided with small globes, utilizing incandescent lamps.
Comments: Tritium gas exit signs have an expiration date of 09/2014.
LED
Comments: Building-mounted exterior LED/ fixtures are controlled by a photocell located on the roof utilizing a lighting contactor located in the counselor office.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Lounges
Toilets
Storage Rooms
Laundry Room
Shower
Sleeping Rooms
Shaving, Make-Up, Grooming
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 2
ELECTRICAL SERVICES Number of Deficiencies = 3
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 1
Page: 13 of 53
Building: 0002 - UNC HALL WOMEN'S DORMITORY
Comments: The building is connected to the center's LAN system by fiber optic cabling, utilizing a Cisco Catalyst 3500 series switch. There is a local magnetic door/alarm security system at each exit door. This system is only local and does not annunciate in the RA office.
Connected to Main System Magnetic Door/Alarm None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location Battery Operated
120V w/Battery Backup
Corridor
Mechanical Room
A CO detector monitoring system (120V w/battery backup) is provided in the water storage tank mechanical room. Gas fired boilers are located in the adjacent mechanical room. The CO detector provides a local alarm (80 dB) if the detected CO level exceeds 10 ppm. Another battery operated carbon monoxide detector is located in the lounge at the exit from the main electrical room.
CARBON MONOXIDE DETECTION
Detection Required Yes
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 3 - SPELLMAN HALL WOMEN'S DORMITORY
Page: 14 of 53
Building: 0003 - SPELLMAN HALL WOMEN'S DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
Brick Masonry
Wall Roof Rigid Rigid
Metal Units - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Residential 6,500 4,311 1 Owned 1965 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Built-up Roofing Scuppers 2006 9 Flat Entire Building
3. Roof
Page: 15 of 53
Building: 0003 - SPELLMAN HALL WOMEN'S DORMITORY
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall Exposed Structure
Wood Units - Metal Frame
Mechanical Toilet/Shower
Ventilation Area Served
VERTICAL CIRCULATION
None
Double Hung - Steel Frame; Double Glazing;
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Two Utica model UB95M-200 boilers provide heating hot water. Each boiler has a maximum heat output of 200 MBH. The boilers were installed in 2008. Heating hot water is circulated through coils installed in three Magic Air model HB20-36-2W air handlers.
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Hot Water Boiler
Single Duct Two-Pipe Electronic Mechanical None Entire Building
Page: 16 of 53
Building: 0003 - SPELLMAN HALL WOMEN'S DORMITORY
The building is provided with domestic hot water from two Weil Mclain model Plus 100 Series 3 heat exchanger water heaters. Each has a 199,900 BTUH, absorbing heat from hot water generated by the heating boilers. The water heaters were installed in 2008.
Comments:
Cast Iron None None
Bathtub Electric Water Cooler Hose Bibb Laundry Tray Lavatory Portable Emergency Eyewash Shower Sink Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Single Duct Refrigerant Electronic Mechanical None Entire Building
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
There are 3 rooftop condensing units matched to evaporator coils in the three air handlers. The condensing units are Heil model H4A460GKA100, each with a cooling capacity of 5 tons. The units were installed in 2008.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 17 of 53
Building: 0003 - SPELLMAN HALL WOMEN'S DORMITORY
Comments: Underground service for this building is provided from a 225A circuit breaker in the MDP located in the Building 1 main electrical room. The service is terminated in a wire trough which feeds two 250A, MLO panelboards. This building is metered from the meter located in Building 1.
FIRE ALARM
Comments: The fire alarm control/annunciator panel (Notifier APF 1010) is located in the Counselor office. The system is fully addressable and connected to the center's central fire alarm annunciator panel located in Welcome Center Building 9 (non-occupied after hours). Audio/visual (A/V) alarm devices are installed on the building's exterior walls for added protection.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Exterior Audio/Visual Device Heat Detector Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. Surface-mounted task lights above the beds are provided in the sleeping rooms, about 50% of which use T12 lamps. Sky lights are provided with small globes, utilizing incandescent lamps.
LED
Comments: Building-mounted exterior LED fixtures are controlled by two photocells located on the roof.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Equipment Rooms (Elec/Mech)
Lounges
Toilets
Storage Rooms
Laundry Room
Shower
Sleeping Rooms
Shaving, Make-Up, Grooming
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Panelboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 1
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 2
Page: 18 of 53
Building: 0003 - SPELLMAN HALL WOMEN'S DORMITORY
Comments: The building is connected to the center's LAN system by fiber optic cabling, utilizing a Cisco Catalyst 3500 series switch. There is a local magnetic door/alarm security system at each exit door. This system is only local and does not annunciate in the RA office.
Connected to Main System Magnetic Door/Alarm None Local Cable Company
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location 120V w/Battery Backup
Battery Operated
Mechanical Room
Corridor
A CO detector monitoring system (120V w/battery backup) is provided in the water storage tank mechanical room. The gas fired boilers are located in the adjacent mechanical room. The CO detector provides a local alarm (80 dB) if the detected CO level exceeds 10 ppm. Another battery operated carbon monoxide detector is located in the lounge at the exit from the main electrical room.
CARBON MONOXIDE DETECTION
Detection Required Yes
Number of Deficiencies = 0
IMPAIRMENT
Potentially Impaired
DOL Responded
BUILDING 4 - MEN'S DORMITORY/VOCATIONS
Page: 19 of 53
Building: 0004 - MEN'S DORMITORY/VOCATIONS
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Concrete Concrete
The floor structure is prestressed concrete double tees. The roof structure is prestressed concrete single tees.
Brick Masonry
Wall Roof Rigid Rigid
Metal Units - Metal Frame Storefront - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors Business/Residential 29,393 18,483 2 Owned 1965 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material
The remaining useful life is based on visual observation during the PY17 Facility Survey.
Drainage Year Life
Remaining Type Area Served
Ballasted Built-up Roofing Interior Roof Drains 1996 2 Flat Entire Building
Comments:
3. Roof
Entire Building
Comments:
Page: 20 of 53
Building: 0004 - MEN'S DORMITORY/VOCATIONS
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
CMU Drywall Exposed Structure
Comments: There are wood fiber panels (Tectum) at corridors in the dormitories.
Metal Units - Metal Frame Wood Units - Metal Frame
VERTICAL CIRCULATION
Concrete Stairs Elevator
Double Hung - Metal Frame; Double Glazing;
Acoustical Tile Gypsum Board
Number of Deficiencies = 1
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating hot water is provided by a duel fuel (natural gas and #2 fuel oil) Smith model 28A-9 cast iron boiler with a heating capacity of 1,941 MBTUH (19.6 gph fuel oil, 2836 MBH gas) . Most of the building is supplied with conditioned air provided by a four pipe Carrier 10-zone air handling unit.
Each shop is provided with a four pipe, ceiling mounted Hastings air handler.
Finned tube baseboard convectors are located on dormitory perimeter walls.
Comments:
Comments:
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Multi- Zone/Single
AHU
Single Duct
Baseboard Convector
Unit Heater
Four-Pipe
Four-Pipe
Two-Pipe
Two-Pipe
Electronic
Electronic
Electronic
Electronic
Mechanical
Natural
Natural
Natural
None
None
None
None
Entire Building
Shop…