B08_Solicitation_attach_5_Drawing_Spec_4_of_4.pdf
PDF 5 MB Posted
- Attached to
- JECA HVAC Replacement Federal contract opportunity
- Solicitation number
- 140P6324B0003
About this file
This package of documents relates to solicitation number 140P6324B0003 for HVAC replacement services at Jewel Cave National Monument in Custer, South Dakota. The opportunity is being offered by the National Park Service Midwest Region on behalf of the Department of the Interior.
The documents include plans, specifications, schedules and diagrams detailing the scope of work. Mechanical equipment such as air handlers, condensing units, boilers and pumps will be replaced. Electrical work includes a new main panelboard, reinstallation of lighting and devices, and extension of conduit and wiring to support the new equipment. Bidders are advised to verify existing conditions and coordinate outages with the owner. The contractor will be responsible for restoration work, fire alarm integration, and compliance with all specifications.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B09_Solicitation_Amendment_3_Attach_1_Q_and_A_2_Jan_17_2024__0003.docx | DOCX document | |
| Sol_140P6324B0003_Amd_0003.pdf | ||
| Sol_140P6324B0003_Amd_0002.pdf | ||
| Sol_140P6324B0003_Amd_0001.pdf | ||
| B09_Solicitation_Amendment_1_Attach_1_Site_Visit_List_0001.pdf | ||
| B09_Solicitation_Amendment_1_Attach_2_Question_and_Answers_0001.docx | DOCX document | |
| B08_Solicitation_attach_1_SOW.pdf | ||
| Sol_140P6324B0003.pdf | ||
| B08_Solicitation_attach_2_Drawing_Spec_1_of_4.pdf | ||
| B08_Solicitation_attach_7_WD_SD20230025_Nov_17__2023.pdf | ||
| B08_Solicitation_attach_6_Government_Clarification_Responses.pdf | ||
| B08_Solicitation_attach_4_Drawing_Spec_3_of_4.pdf | ||
| B08_Solicitation_attach_3_Drawing_Spec_2_of_4.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. SEE ARCHITECTURAL SHEETS FOR EXACT AREAS AND WALLS
AFFECTED BY THE DEMOLITION AND REMODEL.
B. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT.
COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES.
PROVIDE TEMPORARY POWER AND LIGHTS AS REQUIRED TO ALLOW
THE WORK OF OTHER TRADES TO PROCEED OR AS REQUIRED TO
ALLOW THE OWNER TO OCCUPY THE SPACE.
C. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING ARE
EXISTING. THE LOCATIONS OF THE EQUIPMENT AND DEVICES WERE
OBTAINED FROM EXISTING DRAWING AND FIELD INVESTIGATION. THE
LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE
INFORMATION SHOWN IS NOT GUARANTEED. THE CONTRACTOR IS
RESPONSIBLE FOR THE VERIFICATIONS OF ALL EXISTING CONDITIONS
PRIOR TO SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF
BIDS NEED TO BE FULLY COORDINATED WITH THE OWNER.
D. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE
VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE
INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES IS
NOT GUARANTEED.
E. LUMINAIRES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE
LOCATED ON CEILINGS OR WALLS, SHALL HAVE LUMINAIRES, DEVICE
AND ALL ASSOCIATED CIRCUIT WIRING AND CONDUIT REMOVED BACK
TO NEAREST JUNCTION BOX, OR DEVICE NOT INDICATED TO BE
REMOVED. ACTUAL CIRCUITING MUST BE DETERMINED IN THE FIELD.
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT,
DEVICES AND CONNECTIONS NECESSARY TO ENSURE CIRCUIT
CONTINUITY OF THE REMAINING DEVICES.
F. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.
ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE
REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY THE
CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF
ANY PCB BALLAST OR HAZARDOUS LAMPS.
G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE
LABELING OF SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT
BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE
CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE
CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND PANEL
LOADING WILL ALLOW.
H. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE
PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING
PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO
THE DEMOLITION WORK DONE BY THE ELECTRICAL CONTRACTOR,
UNDER THE TERMS OF THIS SPECIFICATION. CLOSE AND SEAL ALL
OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.
I. EXISTING FIRE ALARM DEVICES, EMERGENCY LIGHTS AND EXIT SIGNS
SHALL BE COMPLETE AND OPERABLE AT ALL TIMES. PROVIDE
TEMPORARY DEVICES IN AREAS BEING WORKED ON TO ALLOW FOR A
WORKABLE SYSTEM DURING CONSTRUCTION.
J. PROVIDE MINIMUM [2] DAYS ADVANCE NOTICE OF OUTAGES.
COORDINATE WITH OWNER FOR ALL ANTICIPATED OUTAGES. OWNER
HAS FINAL APPROVAL ON TIME AND EXTENT OF POWER OUTAGE.
K. PROTECT EXISTING FURNITURE, CARPET AND OTHER
APPURTENANCES FROM DAMAGE DURING THE COURSE OF
CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO THE
OWNER.
L. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR
SALVAGED ARE SHOWN AS FULL-TONE LINES ON DEMO PLANS. ALL
OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN
AS HALF-TONE.
A. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS
INDICATED OTHERWISE.
B. ALL AUXILIARY CABLE ABOVE CEILING SHALL BE PLENUM RATED
WHERE REQUIRED.
C. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE
WHERE INSTALLED IN ACOUSTICAL TILE CEILING.
D. PROVIDE 120 VOLT POWER CIRCUIT(S) FOR AUXILIARY SYSTEMS AS
REQUIRED FOR COMPLETE AND OPERATIONAL SYSTEMS.
E. FOR EXISTING CIRCUITS IN EXISTING PANELBOARDS '(EXTG)', VERIFY
ALL LOADS AND UPDATE PANEL SCHEDULE. SUBMIT FOR ENGINEER'S
REVIEW.
A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR
CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS
NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT
FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC, SHALL
ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR SIZES AS
NEEDED TO LIMIT VOLTAGE DROP TO LEVELS RECOMMENDED BY
NEC. THE CONTRACTOR SHALL ALSO COORDINATE INSPECTIONS
WITH THE AHJ.
B. SEE ARCHITECTURAL SHEETS FOR REFLECTED CEILING PLANS.
C. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRAL WIRES BUT CAN
SHARE AN INSULATED GREEN GROUND WIRE IN MINIMUM 3/4" EMT
CONDUIT.
D. NO BOXES SHALL BE MOUNTED BACK TO BACK.
E. CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE OR
FIRE/SMOKE RATED WALLS AND FLOORS.
F. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN
ACCORDANCE WITH NEC PARAGRAPHS 230.8, 300.5(G) AND 300.7(A).
ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY NEC AND NFPA.
G. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT
ACCESS.
H. ALL CABLING ABOVE CEILING SHALL BE PROPERLY SUPPORTED (NOT
FROM CEILING SYSTEM).
I. CONTRACTOR SHALL COORDINATE FINAL PANEL DIRECTORIES WITH
OWNER.
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E 00
ELECTRICAL INFO SHEET
07310034- 7- E 00 ELECTRICAL INFO SHEET
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,
DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR
ALL REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE
MECHANICAL DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT
TO BE REMOVED. UPDATE PANELBOARD SCHEDULES TO REFLECT
ALL CHANGES.
D2 REMOVE EXISTING CEILING LUMINAIRES AND DEVICES SHOWN,
FOR CEILING REMOVAL AND MECHANICAL WORK. CLEAN AND
STORE LUMINAIRES AND DEVICES FOR IN-PLACE
REINSTALLATION. COORDINATE TEMPORARY STORAGE LOCATION
WITH OWNER. EXISTING WIRING TO BE PROTECTED DURING
DEMOLITION/CONSTRUCTION FOR REUSE.
D3 REMOVE INDICATED CONDUCTORS AND CONDUIT FROM EMPTY
DISCONNECT ENCLOSURE BEING USED AS A JUNCTION BOX.
COVER OR PLUG EMPTY HOLES, PER NEC REQUIREMENTS.
D4 FIELD VERIFY EXISTING CONDUCTOR SIZES. REMOVE
CONDUCTORS FROM EXISTING CONDUIT FOR INSTALLATION OF
NEW CONDUCTORS. EXISTING CONDUIT TO REMAIN TO EXTENT
POSSIBLE. SEE SHEET E502 FOR ADDITIONAL INFORMATION.
1 NEW PANEL 'MDP' TO REPLACE EXISTING 'MDP'. SEE E101, E502,
AND E601 FOR COMPLETE INFORMATION.
2 REINSTALL CEILING LUMINAIRES AND DEVICES IN NEW CEILING AT
ORIGINAL LOCATIONS, UNLESS SHOWN OTHERWISE. RECONNECT
TO EXISTING WIRING, EXTEND AS REQUIRED.
3 PROVIDE NEW CONDUCTORS AND RE-ROUTE/EXTEND EXISTING
CONDUIT TO NEW 'MDP' LOCATION AS REQUIRED FOR A FULLY
FUNCTIONAL SYSTEM. NEW CONDUCTORS TO MATCH EXISTING
CONDUCTOR SIZE. EXISTING CONDUIT SHALL BE REUSED TO
EXTENT POSSIBLE, IF IN ACCEPTABLE CONDITION.
4 COORDINATE REQUIREMENTS WITH MECHANICAL CONTRACTOR
FOR BOILER SHUT OFF REQUIREMENTS.
5 PROVIDE UNISTRUT MOUNTING FOR 600A/3 'MDP' DISCONNECT AT
THIS LOCATION. FIELD COORDINATE ORIENTATION TO ENSURE
WORKING CLEARANCE REQUIREMENTS PER NEC.
E 00 ELECTRICAL INFO SHEET
E 01 ELECTRICAL SPECIFICATIONS
E 02 ELECTRICAL SPECIFICATIONS
E 03 ELECTRICAL SPECIFICATIONS
E001 SUB-GRADE PLAN - DEMOLITION
E002 FIRST FLOOR PLAN - DEMOLITION
E003 SECOND FLOOR PLAN - DEMOLITION
E004 THIRD FLOOR PLAN - DEMOLITION
E101 SUB-GRADE PLAN - ELECTRICAL
E102 FIRST FLOOR PLAN - ELECTRICAL
E103 SECOND FLOOR PLAN - ELECTRICAL
E104 THIRD FLOOR PLAN - ELECTRICAL
E401 ELECTRICAL DETAILS
E501 POWER RISER DIAGRAM - DEMOLITION
E502 POWER RISER DIAGRAM
E601 ELECTRICAL SCHEDULES
S
SYMBOL LEGEND
PC
J
J
OS
MS
IC
S
S
M
N
TV
VC
N E
N S
N
N D
N 2
G
K1
V
A
F
F
F
F
FS
D
PS
TS
R
M
M
T
DH
WALL MOUNTED STRIP LUMINAIRE
SYMBOL NOTES:
STROBE
HORN
MANUAL PULL STATION
HORN STROBE
PHOTOCELL
VOICE AND DATA
JUNCTION BOX - CEILING MOUNT
JUNCTION BOX - WALL MOUNT
VOICE OUTLET
DATA OUTLET
OCCUPANCY SENSOR
MOTION SENSOR
CEILING FAN
HEAT DETECTOR
SMOKE DETECTOR
REMOTE INDICATOR LIGHT
SPRINKLER TAMPER SWITCH
DUCT SMOKE DETECTOR
FLOW SWITCH
POST INDICATING VALVE SWITCH
POLE MOUNTED SITE LUMINAIRE
NURSE CALL
SPEAKER
BEDSIDE STATION
INTERCOM SPEAKER STATION
VOLUME CONTROL STATION
MICROPHONE JACK
TELEVISION OUTLET
CCTV CAMERA
SOUND, TELEVISION, AND SECURITY
FUSE
EMERGENCY PULL STATION
DISCONNECT SWITCH
STAFF STATION
DUTY STATION
DOME LIGHT
MASTER STATION
EMERGENCY GENERATOR
POWER DISTRIBUTION ONE LINE
CONDUIT UP
CONDUIT DOWN
INDICATES BUSHED CONDUIT
VOICE/DATA OUTLET
DOUBLE BED BEDSIDE STATION
DRAW OUT VACUUM
CIRCUIT BREAKER
LIGHTNING SURGE ARRESTOR
THERMAL OVERLOAD RELAY
PLUG-IN OR DRAWOUT
CONNECTOR
CIRCUIT BREAKER
FUSED DISCONNECT SWITCH
VOLTMETER
AMMETER
X:Y
CURRENT TRANSFORMER -
(RATIO)
KIRK KEY INTERLOCK
MAGNETIC DOOR HOLDER
"C" INDICATES CEILING MOUNTED
"F" INDICATES FLOOR MOUNTED
"S" INDICATES SURFACE MOUNTED
"G" INDICATES GROUND FAULT INTERRUPTING
"IG" INDICATES ISOLATED GROUND
"AC" INDICATES MOUNTING 6" ABOVE COUNTERTOP
OR BACKSPLASH
"WP" INDICATES WEATHERPROOF
"XP" INDICATES EXPLOSION PROOF
"U" INDICATES USB CHARGER
"R" INDICATES EXISTING DEVICE REMOVED AND
RELOCATED
LOWER CASE LETTER BY SWITCHES AND FIXTURES
INDICATE ASSOCIATED UNIT FOR SWITCHING
LIGHTING
LUMINAIRE
WALL MOUNTED LUMINAIRE
RECESSED LUMINAIRE
WALL MOUNTED LUMINAIRE
SURFACE MOUNTED LUMINAIRE
TRACK LIGHTING
DIMMER SWITCH
TIMER SWITCH
WIRING DEVICES - SWITCHES
SINGLE POLE SWITCH
KEY OPERATED SWITCH
SINGLE POLE SWITCH WITH PILOT
THERMAL ELEMENT SWITCH
FOUR-WAY SWITCH
TWO POLE SWITCH
THREE-WAY SWITCH
STRIP / INDUSTRIAL LUMINAIRE
LUMINAIRE - NIGHT LIGHTING
LUMINAIRE - EMERGENCY SYSTEM
EMERGENCY BATTERY PACK LUMINAIRE
REMOTE EMERGENCY HEAD
WALL WASH LUMINAIRE
PENDANT MOUNTED LUMINAIRE
POWER POLE
METER SOCKET
POWER EQUIPMENT
WIRING DEVICES - RECEPTACLES
COMBINATION STARTER SAFETY SWITCH
RELAY - CONTROL AS NOTED
PUSHBUTTON STATION
MOTOR CONNECTION
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
EMERGENCY RECEPTACLE
SPECIAL PURPOSE RECEPTACLE, NEMA
CONFIGURATION NOTED
PLUG-IN STRIP - LENGTH AND QUANTITY
OF OUTLETS AS SHOWN
SAFETY SWITCH
DROP CORD RECEPTACLE ASSEMBLY
FUSIBLE SWITCH (FUSETRON)
PANELS AND CABINETS
DISTRIBUTION PANEL
SWITCHBOARD, SWITCHGEAR, MCC
EQUIPMENT OR TERMINAL CABINET
DRY TYPE TRANSFORMER
BRANCH CIRCUIT PANEL
CONDUIT AND BOXES
FIRE ALARM SYSTEM
HORN (PA, PUBLIC ADDRESS)
TRANSFORMER
EXIT LIGHT - WALL MOUNT WITH
DIRECTIONAL ARROWS AS INDICATED,
FILLED-IN QUARTERS INDICATE
ILLUMINATION SIDES
EXIT LIGHT - CEILING OR PENDANT
MOUNT WITH DIRECTIONAL ARROWS AS
INDICATED, FILLED-IN QUARTERS
INDICATE ILLUMINATION SIDES
EMERGENCY EXIT LIGHT COMBO
LOW VOLTAGE MOMENTARY
CONTACT SWITCH
H
S
S
N P PILLOW SPEAKER
FB FLOOR BOX
FP FLOOR POKE-THROUGH DEVICE
N M
WIRELESS ACCESS POINT
S S2
S3
S4
SD
SK
SP
STE
ST
SFT
X
CONTROLLED RECEPTACLE
WB WALL AV BOX
F SPEAKER STROBES
F SPEAKERS
RC ROOM CONTROLLER
PP POWER PACK
ABBREVIATIONS
TEL TELEPHONE
TEMP TEMPERATURE
TVSS TRANSIENT VOLTAGE
SURGE SUPPRESSOR
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UPS UNINTERRUPTIBLE
POWER SYSTEM
VFD VARIABLE FREQUENCY
DRIVE
W WEST
W/ WITH
W/O WITHOUT
WHM WATTHOUR METER
WT WEIGHT
XFMR TRANSFORMER
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
AFF ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
APPROX APPROXIMATE
AUTO AUTOMATIC
AVG AVERAGE
L ANGLE
BKR BREAKER
C OR CL CENTER LINE
C OR CND CONDUIT (ELECTRICAL
SHEETS)
CKT CIRCUIT
CLG CEILING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CPT CONTROL POWER
TRANSFORMER
DC DIRECT CURRENT
DEG DEGREE
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DWG DRAWING
E EAST
EA EACH
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR
ELECTRICAL
ELEV ELEVATOR
EMD ESTIMATED MAXIMUM
DEMAND
ENCL ENCLOSURE
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER
COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
FA FIRE ALARM
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLUOR FLUORESCENT
AWG GAUGE
HP HORSE POWER
HR HOUR
HTG HEATING
HTR HEATER
HZ HERTZ
FAAP FIRE ALARM
ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL
PANEL
FAEP FIRE ALARM EXTENDER
PANEL
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CUH CABINET UNIT HEATER
EMI ELECTROMAGNETIC
INTERFERENCE
SOUTH
SCHED SCHEDULE
SF SQUARE FOOT (FEET)
SPEC SPECIFICATIONS
SPKR SPEAKER
SQ SQUARE
STD STANDARD
STL STEEL
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
S
GFI GROUND FAULT CIRCUIT
INTERRUPTER
SCCR SHORT CIRCUIT
CURRENT RATING
SPD SURGE PROTECTIVE
DEVICE
SPDT SINGLE POLE, DOUBLE
THROW
VFC VARIABLE FREQUENCY
CONTROLLER
ID INSIDE DIAMETER
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
KCMIL KCM KILO CIRCULAR MIL
KV KILOVOLTS
KVA KILOVOLT AMPERES
KVAR KILOVOLT AMPERES
REACTIVE
KW KILOWATT
LBS POUNDS
LRA LOCKED ROTOR AMPS
LTG LIGHTING
QTY QUANTITY
REC RECEPTACLE
REFR REFRIGERATOR
REINF REINFORCEMENT
REQD REQUIRED
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OH OVERHEAD
OPNG OPENING
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PSI POUNDS PER SQUARE IN.
MCCB MOLDED CASE CIRCUIT
BREAKER
OCPD OVERCURRENT
PROTECTIVE DEVICE
RFI RADIO FREQUENCY
INTERFERENCE
REF. DEMO NOTES ( )
PROJECT ELECTRICAL REFERENCED DEMOLITION NOTES
X
DX
PROJECT ELECTRICAL REFERENCED NOTES
NORTH
ARROW
MATCHLINE
AREA A
AREA B
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
XXXX
DX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
150 SF
ROOM
NUMBER
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
ROOM AREA DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR DRAWING
TITLE
SCALE OF THE DRAWING
REF. NOTES ( )
GENERAL NOTESGENERAL DEMO NOTES
ELECTRICAL SHEET LIST
GEN. POWER & AUX SYSTEMS NOTES
TRUE
NORTH
PLAN
NORTH
NORTH
DATE INITIAL
02/24/202302/24/2023
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E 01
ELECTRICAL
SPECIFICATIONS
07310034- 7- E 01 ELECTRICAL SPECIFICATIONS
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
02/24/2023
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E 02
ELECTRICAL
SPECIFICATIONS
07310034- 7- E 02 ELECTRICAL SPECIFICATIONS
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E 03
ELECTRICAL
SPECIFICATIONS
07310034- 7- E 03 ELECTRICAL SPECIFICATIONS
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
J
J
M
M
M
H
H
PANEL 'ELEVP'
PANEL 'P'
EXTG PANEL 'MDP'
PANEL 'E'
D1
D1D1
PANEL 'N'
PANEL 'C'
D1
D1
D2
ATS
D2
D2
D2
D2
D2
MECH
STAIR
ENTRY
STORAGE
RESTROOM
OFFICE
ELEV
ELEV
XFMR
METER
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E001
SUB-GRADE PLAN -
DEMOLITION
07310034- 7- E001 SUB-GRADE PLAN - DEMOLITION
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
REF. DEMO NOTES ( ):DX
D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,
DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL
REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL
DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.
UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.
D2 REMOVE EXISTING CEILING LUMINAIRES AND DEVICES SHOWN, FOR
CEILING REMOVAL AND MECHANICAL WORK. CLEAN AND STORE
LUMINAIRES AND DEVICES FOR IN-PLACE REINSTALLATION. COORDINATE
TEMPORARY STORAGE LOCATION WITH OWNER. EXISTING WIRING TO BE
PROTECTED DURING DEMOLITION/CONSTRUCTION FOR REUSE.
KEY PLAN NORTH
SCALE: 1/4" = 1'-0"
SUB-GRADE FLOOR PLAN - ELECTRICAL DEMOLITION
S S
SS
S
S
S
S
H
S
D1
PANEL 'F'
PANEL 'A'
FAEP
FAAP
PANEL 'RR'
D2
(TYP. ALL LUMINAIRES AND
CEILING DEVICES SHOWN)
LOBBY
VESTIBULE
CORRIDOR
ELEVATOR
LOBBY
HOISTWAY
ELEVATOR
GUIDES
STAIR
COURTYARD
LOBBY EXHIBIT
PARK STORE
HALL
SECRETARY
STORAGE
OFFICE
EXHIBIT ROOM
CORRIDOR
OFFICE
OFFICE
OFFICE
WORKROOM
114 VESTIBULE
MECH
WOMENS
MENS
CORRIDOR
117A
CORRIDOR
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E002
FIRST FLOOR PLAN -
DEMOLITION
07310034- 7- E002 FIRST FLOOR PLAN - DEMOLITION
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
REF. DEMO NOTES ( ):DX
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,
DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL
REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL
DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.
UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.
D2 REMOVE EXISTING CEILING LUMINAIRES AND DEVICES SHOWN, FOR
CEILING REMOVAL AND MECHANICAL WORK. CLEAN AND STORE
LUMINAIRES AND DEVICES FOR IN-PLACE REINSTALLATION. COORDINATE
TEMPORARY STORAGE LOCATION WITH OWNER. EXISTING WIRING TO BE
PROTECTED DURING DEMOLITION/CONSTRUCTION FOR REUSE.
DATE INITIAL
KEY PLAN NORTH
D1
D1
STORAGE
WORKROOM
STAIR
FAN ROOM
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E003
SECOND FLOOR PLAN -
DEMOLITION
07310034- 7- E003 SECOND FLOOR PLAN - DEMOLITION
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
REF. DEMO NOTES ( ):DX
KEY PLAN NORTH
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - ELECTRICAL DEMOLITION
D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,
DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL
REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL
DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.
UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.
PANEL 'M'
FACP
XFMR
XFMR
ELEVATOR
MACHINE
ROOM
STAIR
D1
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E004
THIRD FLOOR PLAN -
DEMOLITION
07310034- 7- E004 THIRD FLOOR PLAN - DEMOLITION
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
REF. DEMO NOTES ( ):DX
KEY PLAN NORTH
SCALE: 1/4" = 1'-0"
THIRD FLOOR PLAN - ELECTRICAL DEMOLITION
D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,
DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL
REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL
DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.
UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.
DATE INITIAL
02/24/2023 jlkirk Highlight jlkirk Highlight jlkirk Highlight
H
H
PANEL 'E'
PANEL 'P'
PANEL 'ELEVP'
MDP - 8
ACCU-1
N - 12
B-1
PANEL 'MDP'
PANEL 'N'
N - 1,3,5
HWP-1
N - 2,4,6
HWP-2
M - 2,4,6
CU-1
PANEL 'C'
ATS
EMERGENCY
BOILER SHUT OFF
MGB
EMERGENCY
BOILER SHUT OFF
MDP - 11
DSS-1B
STAIR
MECH
ENTRY
STORAGE
RESTROOM
OFFICE
ELEV
ELEV
XFMR
METER
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E101
SUB-GRADE PLAN -
ELECTRICAL
07310034- 7- E101 SUB-GRADE PLAN - ELECTRICAL
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
KEY PLAN NORTH
SCALE: 1/4" = 1'-0"
SUB-GRADE FLOOR PLAN - ELECTRICAL
DATE INITIAL
REF. NOTES ( ):X
1 NEW PANEL 'MDP' TO REPLACE EXISTING 'MDP'. SEE E101, E502, AND E601
FOR COMPLETE INFORMATION.
2 REINSTALL CEILING LUMINAIRES AND DEVICES IN NEW CEILING AT
ORIGINAL LOCATIONS, UNLESS SHOWN OTHERWISE. RECONNECT TO
EXISTING WIRING, EXTEND AS REQUIRED.
4 COORDINATE REQUIREMENTS WITH MECHANICAL CONTRACTOR FOR
BOILER SHUT OFF REQUIREMENTS.
5 PROVIDE UNISTRUT MOUNTING FOR 600A/3 'MDP' DISCONNECT AT THIS
LOCATION. FIELD COORDINATE ORIENTATION TO ENSURE WORKING
CLEARANCE REQUIREMENTS PER NEC.
S S
SS
S
S
S
S
H
S
PANEL 'A'
PANEL 'F'
FAAP
FAEP
(TYP. ALL LUMINAIRES AND
CEILING DEVICES SHOWN)
PANEL 'RR'
LOBBY
CORRIDOR
ELEVATOR
LOBBY
HOISTWAY
ELEVATOR
STAIR
GUIDES
COURTYARD
HALL
PARK STORE
LOBBY EXHIBIT
VESTIBULE
EXHIBIT ROOM
115 SECRETARY
STORAGE
OFFICE
OFFICE
OFFICE
OFFICE
VESTIBULE
WORKROOM
CORRIDOR
117A
CORRIDOR
CORRIDOR
MENS
WOMENS
MECH
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E102
FIRST FLOOR PLAN -
ELECTRICAL
07310034- 7- E102 FIRST FLOOR PLAN - ELECTRICAL
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
REF. NOTES ( ):X
2 REINSTALL CEILING LUMINAIRES AND DEVICES IN NEW CEILING AT
ORIGINAL LOCATIONS, UNLESS SHOWN OTHERWISE. RECONNECT TO
EXISTING WIRING, EXTEND AS REQUIRED.
KEY PLAN NORTH
DATE INITIAL
SCALE: 1/8" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL
S D
MDP - 9
RAF-1
MDP - 10
AHU-1
MDP - 11
DSS-1A
MDP - 12
FT-1
STORAGE
FAN ROOM
STAIR
WORKROOM
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E103
SECOND FLOOR PLAN -
ELECTRICAL
07310034- 7- E103 SECOND FLOOR PLAN - ELECTRICAL
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
KEY PLAN NORTH
SCALE: 1/4" = 1'-0"
SECOND FLOOR PLAN - ELECTRICAL
DATE INITIAL
02/24/2023 jlkirk Highlight jlkirk Highlight
PANEL 'M'
M - 1,3
BCU-1
FACP
XFMR
XFMR
ELEVATOR
MACHINE
ROOM
STAIR
MDP - 13
UH-1
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E104
THIRD FLOOR PLAN -
ELECTRICAL
07310034- 7- E104 THIRD FLOOR PLAN - ELECTRICAL
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
KEY PLAN NORTH
SCALE: 1/4" = 1'-0"
THIRD FLOOR PLAN - ELECTRICAL
DATE INITIAL
02/24/2023 jlkirk Highlight jlkirk Highlight
SYSTEM CONDUCTOR IDENTIFICATION
208Y/120V 3Φ 4W
A – PHASE – BLACK
B – PHASE – RED
C – PHASE – BLUE
NEUTRAL – WHITE
GROUND – GREEN
SYSTEM CONDUCTOR IDENTIFICATION
480Y/277V 3Φ 4W
A – PHASE – BROWN
B – PHASE – ORANGE
C – PHASE – YELLOW
NEUTRAL – GRAY
GROUND – GREEN
SYSTEM IDENTIFICATION DECAL
SYSTEM CONDUCTOR IDENTIFICATION
120/240V
A – PHASE – BLACK
B – PHASE – RED
NEUTRAL – WHITE
GROUND – GREEN
SYSTEM CONDUCTOR IDENTIFICATION
240V DELTA 3Φ 3W
A – PHASE – PINK
B – PHASE – PURPLE
C – PHASE – TAN
GROUND – GREEN
FED FROM MDP
PANEL IDENTIFICATION DECAL
PANEL TYPE PANEL
DESIGNATION
NOTES:
1. DECALS SHALL BE LAMINATED ACRYLIC WITH WHITE ENGRAVED LETTERING ON A BLACK BACKGROUND. PANELS OR EQUIPMENT CONNECTED TO AN ALTERNATE
POWER SOURCE SHALL HAVE WHITE ENGRAVED LETTERING ON A RED BACKGROUND.
2. DECALS SHALL BE SIZED TO ACCOMMODATE SPECIFIED LEGENDS BUT NO SMALLER THAN SIZES SHOWN, MINIMUM OF 1/16” THICK.
3. DECALS SHALL BE PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4” GROMMETS IN CORNERS FOR MOUNTING.
4. COLORS FOR 240V DELTA SYSTEMS BASED ON AVAILABLE COLORS OFFERED BY SOUTHWIRE. OTHER COLORS THAT DO NOT CONFLICT WITH OTHER VOLTAGE
SYSTEMS PERMITTED.
CR = CRITICAL
EQ = EQUIPMENT
LS = LIFE SAFETY
EM = EMERGENCY
OS = OPTIONAL STANDBY
H = 480V L = 208V
H1
DISCONNECT IDENTIFICATION
DECAL TO BE PERMANENTLY
POSTED. SEE DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
PANEL IDENTIFICATION DECAL TO
BE PERMANENTLY POSTED. SEE
DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
SYSTEM IDENTIFICATION DECAL TO BE
PERMANENTLY POSTED.
SIZE: 1-1/2”H x 3”W. TEXT HEIGHT: 1/8"
BRANCH/FEEDER IDENTIFICATION
DECAL TO BE PERMANENTLY
POSTED. SEE DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
PANEL H1
BRANCH/FEEDER IDENTIFICATION DECAL
TRANSFORMER IDENTIFICATION
DECAL TO BE PERMANENTLY
POSTED. SEE DETAILS AT RIGHT.
SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"
TL1
TRANSFORMER IDENTIFICATION DECAL
FED FROM MDP
FEEDS L1
EF-1
DISCONNECT IDENTIFICATION DECAL
480V
FED FROM MDP
INSULATORS (TYP. 2)
BOLT TO WALL
ANCHOR BOLTS
COPPER GROUND BAR
WALL MOUNTING BRACKET
'MGB'
ERICO EGBA14424MMT
2'-0"
'MGB'
BUILDING
STRUCTURAL
COLUMN OR
BEAM (TYP.)
EXOTHERMIC WELD
BURNDY TYPE BCS-3 MOLD
4 AWG OR LARGER BARE COPPER
CONDUCTOR OR STEEL REINFORCING
BAR OR ROD NOT LESS THAN
1/2" DIAMETER AT LEAST 20' LONG.
(CONCRETE ENCASE ELECTRODE)
CONNECTION LISTED
FOR PURPOSE (TYP.)
NON-METALLIC
PROTECTIVE
SLEEVE
INSULATED #4/0 GROUNDING
ELECTRODE CONDUCTOR IN 1"C. (TYP.)
N G
'MDP'
CONNECTION LISTED
FOR PURPOSE (TYP.)
GROUND RODS
MAIN BONDING JUMPER
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E401
ELECTRICAL DETAILS
07310034- 7- E401 ELECTRICAL DETAILS
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
SCALE: 1/8" = 1'-0"
PANELBOARD & EQUIPMENT IDENTIFICATION DETAIL
SCALE: NOT TO SCALE
GROUND BAR DETAIL
SCALE: NOT TO SCALE
SERVICE GROUNDING DETAIL
T
T
PANEL
'ELEVP'
SUB GRADE
FIRST FLOOR
GENERATOR
UTILITY
THIRD FLOOR
PANEL
'E'
'ATS'
'A'
PANEL
'M'
PANEL
'N'
T
ELEVATOR EQUIPMENT ROOM
OFFICE
CORRIDOR
ELECTRICAL EQUIPMENT ROOM
PANEL
'C'
'RR'
THEATER KIOSK VENDING MACHINE CANOPY
PANEL
'P'
PANEL
'G'
PANEL
'P1'
PANEL
'V''F'
PANEL
'MDP'
D3
D4
D4
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E501
POWER RISER DIAGRAM -
DEMOLITION
07310034- 7- E501 POWER RISER DIAGRAM - DEMOLITION
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
DATE INITIAL
REF. DEMO NOTES ( ):DX
D3 REMOVE INDICATED CONDUCTORS AND CONDUIT FROM EMPTY
DISCONNECT ENCLOSURE BEING USED AS A JUNCTION BOX. COVER OR
PLUG EMPTY HOLES, PER NEC REQUIREMENTS.
D4 FIELD VERIFY EXISTING CONDUCTOR SIZES. REMOVE CONDUCTORS
FROM EXISTING CONDUIT FOR INSTALLATION OF NEW CONDUCTORS.
EXISTING CONDUIT TO REMAIN TO EXTENT POSSIBLE. SEE SHEET E502
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE
POWER RISER DIAGRAM - DEMOLITION
PROVIDE 4"
CONCRETE PAD
PANEL
'MDP'
T
T
PANEL
'ELEVP'
SUB GRADE
FIRST FLOOR
GENERATOR
UTILITY
THIRD FLOOR
PANEL
'E'
'ATS'
'A'
PANEL
'M'
PANEL
'N'
T
ELEVATOR EQUIPMENT ROOM
OFFICE
CORRIDOR
ELECTRICAL EQUIPMENT ROOM
PANEL
'C'
'RR'
THEATER KIOSK VENDING MACHINE CANOPY
PANEL
'P'
PANEL
'G'
PANEL
'P1'
PANEL
'V''F'
MGB
E401
E401
F600A4G
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E502
POWER RISER DIAGRAM
07310034- 7- E502 POWER RISER DIAGRAM
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
REF. NOTES ( ):X
1 NEW PANEL 'MDP' TO REPLACE EXISTING 'MDP'. SEE E101, E502, AND E601
FOR COMPLETE INFORMATION.
3 PROVIDE NEW CONDUCTORS AND RE-ROUTE/EXTEND EXISTING CONDUIT
TO NEW 'MDP' LOCATION AS REQUIRED FOR A FULLY FUNCTIONAL
SYSTEM. NEW CONDUCTORS TO MATCH EXISTING CONDUCTOR SIZE.
EXISTING CONDUIT SHALL BE REUSED TO EXTENT POSSIBLE, IF IN
ACCEPTABLE CONDITION.
SCALE: NOT TO SCALE
POWER RISER DIAGRAM
DATE INITIAL
F600A4G 2 SETS OF 4#350, 1#1G - 3"C
FEEDER SCHEDULE ( ):FXXXXXXX
GENERAL EQUIPMENT SCHEDULE NOTES:
A. THIS SCHEDULE DISPLAYS SIZING INFORMATION THAT IS GENERIC IN
NATURE. SCHEDULE DOES NOT ITEMIZE ALL INSTANCES OF
EQUIPMENT. CONTRACTOR SHALL REFER TO THE PLANS FOR FINAL
QUANTITIES AND LOCATIONS.
B. MOUNT ALL DISCONNECTS AND STARTERS ON ASSOCIATED
EQUIPMENT UNLESS SHOWN OTHERWISE. MAINTAIN WORKING
CLEARANCES PER NEC; COORDINATE WITH MECHANICAL
CONTRACTOR.
C. BCU = BOX COVER UNIT (COOPER #SSY / #STY OR EQUAL) WITH FUSE.
D. NFD OR FD = NON-FUSED OR FUSED DISCONNECT SWITCH.
E. CS/NFD, FD = COMBINATION STARTER/ NON OR FUSED DISCONNECT
SWITCH.
F. INT = INTEGRAL DISCONNECT FURNISHED WITH EQUIPMENT.
G. FHPMC = FRACTIONAL HORSEPOWER MANUAL CONTROLLER.
H. IHPMC = INTEGRAL HORSEPOWER MANUAL CONTROLLER.
I. STE = THERMAL ELEMENT SWITCH. PROVIDE THERMAL UNIT.
J. EXP = DEVICE TO BE EXPLOSION-PROOF.
K. ALL SWITCHES, DISCONNECTS, ETC SHALL BE LOCKABLE.
L. ALL SWITCHES, DISCONNECTS, ETC SHALL BE NEMA 3R WHERE
REQUIRED.
M. PROVIDE FUSES AS SHOWN; REVISE SIZES PER ACTUAL NAMEPLATE
DATA.
N. STARTER ACCESSORIES:STARTER ACCESSORIES:
1. CONTROL TRANSFORMER
2. H-O-A SWITCH
3. RED RUN LIGHT
4. 2 NO CONTACTS; 2 NC CONTACTS
EQUIPMENT SCHEDULE NOTES:
1. EQUIPMENT CONTROLLED BY VFD. COORDINATE REQUIREMENTS
WITH VFD MANUFACTUROR PRIOR TO INSTALLATION. SEE
MECHANICAL SHEETS FOR ADDITIONAL INFORMATION.
2. INDOOR UNIT 'DSS-1A' POWERED BY OUTDOOR UNIT 'DSS-1B'. SEE
MECHANICAL SHEETS FOR ADDITIONAL INFORMATION.
3. CONNECT AIR HANDLER RETURN DUCT SMOKE DETECTOR TO
EXISTING FIRE ALARM SYSTEM. SMOKE DETECTION SHALL INITIATE
BUILDING FIRE ALARM AND SHUT DOWN AIR HANLDER. COORDINATE
REQUIREMENTS WITH FIRE ALARM MANUFACTURER PRIOR TO
INSTALLATION.
1044 North 115th Street | Suite 300
Omaha, NE 68154
(402) 493-4800 www.schemmer.com
REVISED TITLE OF SHEET DRAWING NO.
SHEET
PMIS / PKG. NO.
OF
SUB SHEET NO.
ARCH/ENG PROJ #
DESIGNED
DRAWN
CHECKED
PREPARED
DATE
238608 / 80005
80005
C U s e rs \d la n g h o ld t\ D o c u m e n ts
\0
-E
L E
C
R d la n g h o ld tT W
S
J .r v t
JEF
DJL
JCB
2/24/23
07310.034
E601
ELECTRICAL SCHEDULES
07310034- 7- E601 ELECTRICAL SCHEDULES
HVAC REPLACEMENT
JEWEL CAVE NATIONAL MONUMENT
CUSTER, SD
EQUIPMENT SCHEDULE
DEVICE DEVICE DESCRIPTION VOLTAGE PH KW FLA HP
STARTER / DISCONNECT
PLUG CONFIG
RECEPT
CONFIG FEEDER SIZE NOTES TYPE SIZE FUSE
ACCU-1 AIR COOLED CONDENSING UNIT 208 V 3 - 120 - NFD 200/3 - - - F150A3G 3#1/0, 1#6G - 1-1/2"C
AHU-1 AIR HANDLING UNIT 208 V 3 - 29.5 - NFD 60/3 - - - F60A3G 3#4, 1#10G - 1-1/4"C 3
B-1 GAS FIRED BOILER 120 V 1 - 1.0 - FD 30/2 15 - - F20A2G 2#12, 1#12G - 3/4"C
BCU-1 INDOOR AIR HANDLER 208 V 1 - - 1/2 FD 30/2 15 - - F20A2G 2#12, 1#12G - 3/4"C
CU-1 OUTDOOR CONDENSING UNIT 208 V 3 - 12.2 1/8 NFD 30/3 - - - F20A3G 3#12, 1#12G - 3/4"C
DSS-1A DUCTLESS SPLIT SYSTEM 208 V 1 - 0.67 - - - - - - F20A2G 2#12, 1#12G - 3/4"C 2
DSS-1B DUCTLESS SPLIT SYSTEM 208 V 1 - 10 - FD 30/2 15 - - F20A2G 2#12, 1#12G - 3/4"C 2
FT-1 FINTUBE 208 V 1 1.0 - - NFD 30/2 - - - F20A2G 2#12, 1#12G - 3/4"C
HWP-1 INLINE PUMP 208 V 3 - - 3.0 FD 30/3 25 - - F30A3G 3#10, 1#10G - 3/4"C 1
HWP-2 INLINE PUMP 208 V 3 - - 3.0 FD 30/3 25 - - F30A3G 3#10, 1#10G - 3/4"C 1
RAF-1 INLINE FAN 208 V 3 - - 5.0 NFD 60/3 - - - F40A3G 3#8, 1#10G - 1"C 1
UH-1 UNIT HEATER 208 V 1 2.5 - - NFD 30/2 - - - F20A2G 2#12, 1#12G - 3/4"C
MCB: Main Circuit Breaker
LOCK: Lockable Circuit Breaker
GFI: GFCI Circuit Breaker MLO: Main Lug Only
FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker
Legend: Notes:
Total Est. Demand Current (80% Rated): 190 A
Continuous Current @ 125%: 41 A
Non-Cont. Current @ 100%: 150 A
EQP_NON CONT 53860 VA 100.00% 53860 VA Total Est. Demand Current (100% Rated): 182 A
EQP_CONT 11737 VA 100.00% 11737 VA Total Est. Demand: 65597 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
182 A
65597 VA
13 EQP_C - UH-1 - THIRD FLOOR 2 20 A 2500 VA
12 EQP_C - FT-1 - SECOND FLOOR 2 20 A 1000 VA
11 EQP_C - DSS-1A / B - SUB GRADE / SECOND FLOOR 2 20 A 2220 VA
10 EQP_NC - AHU-1 - SECOND FLOOR 3 60 A 10628 VA
9 EQP_C - RAF-1 - SECOND FLOOR 3 40 A 6017 VA
8 EQP_C - ACCU-1 - SUB GRADE 3 150 A 43232 VA
7 (EXTG) PANEL 'A' 3 100 A 0 VA
6 (EXTG) 1 20 A 0 VA
5 (EXTG) PANEL 'G' 3 125 A 0 VA
4 (EXTG) PANEL 'E' 3 450 A 0 VA
3 (EXTG) PANEL 'P' 3 200 A 0 VA
2 (EXTG) KIOSK 2 100 A 0 VA
1 (EXTG) PANEL 'N' 3 125 A 0 VA
CKT Circuit Description # of Poles Trip Rating Load Remarks
Mounting: SURFACE Wires: 4 FCB / MCB Rating: 600 A
Supply From: Phases: 3 MLO / MCB: MLO
Location: MECH 005 Volts: 208Y/120 A.I.C. Rating:
Power Panel: MDP
MCB: Main Circuit Breaker
LOCK: Lockable Circuit Breaker
GFI: GFCI Circuit Breaker MLO: Main Lug Only
FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker
Legend: Notes:
Total Est. Demand Current (80% Rated): 18 A
Continuous Current @ 125%: 15 A
Non-Cont. Current @ 100%: 3 A
EQP_NON CONT 1124 VA 100.00% 1124 VA Total Est. Demand Current (100% Rated): 15 A
EQP_CONT 4396 VA 100.00% 4396 VA Total Est. Demand: 5520 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 18 A 18 A 12 A
Total Load: 2027 VA 2027 VA 1465 VA
23 0 -- -- -- 24
21 0 -- -- -- 22
19 0 3 30 A (EXTG) SURGE PROTECTION DEVICE 20
17 (EXTG) EMERG. LIGHT 20 A 1 0 0 1 20 A (EXTG) REC - IT WALL 18
15 (EXTG) MIKE'S OFFICE 20 A 1 0 0 -- -- -- 16
13 (EXTG) REC - AIR COMP 30 A 1 0 0 2 40 A (EXTG) REC - WELDER 14
11 (EXTG) LTG - EL-1 20 A 1 0 0 1 20 A (EXTG) SERVER RACK 12
9 (EXTG) LTG - EL-2 30 A 1 0 0 1 20 A (EXTG) FIRE ALARM CONTROL PANEL 10
7 (EXTG) SERVER RACK 20 A 1 0 0 1 20 A (EXTG) FA CHARGER 8
5 SPARE 20 A 1 0 1465 -- -- -- 6
3 -- -- -- 562 1465 -- -- -- 4
1 EQP_NC - BHU-1 - ELEV ROOM 20 A 2 562 1465 3 20 A EQP_C - CU-1 - ON GRADE 2
CKT Circuit Description Trip P A B C P Trip Circuit Description CKT
Mounting: Wires: 4 FCB / MCB Rating: 100 A
Supply From: E Phases: 3 MLO / MCB: MLO
Location: ELEVATOR MACHINE ROOM... Volts: 208Y/120 A.I.C. Rating:
Extg Branch Panel: M
MCB: Main Circuit Breaker
LOCK: Lockable Circuit Breaker
GFI: GFCI Circuit Breaker MLO: Main Lug Only
FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker FOR EXISTING CIRCUITS '(E)', VERIFY ALL LOADS AND UPDATE PANEL SCHEDULE.
Legend: Notes:
Total Est. Demand Current (80% Rated): 22 A
Continuous Current @ 125%: 0 A
Non-Cont. Current @ 100%: 22 A
Total Est. Demand Current (100% Rated): 22 A
EQP_NON CONT 7758 VA 100.00% 7758 VA Total Est. Demand: 7758 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 21 A 21 A 22 A
Total Load: 2546 VA 2546 VA 2666 VA
15 16
13 14
11 (EXTG) SPARE 20 A 1 0 120 1 20 A EQP_NC - B-1 - SUB GRADE 12
9 -- -- -- 0 0 1 20 A (EXTG) WASHER 10
7 (EXTG) DRYER 30 A 2 0 0 1 20 A (EXTG) CHARGING RECEPTS 8
5 -- -- -- 1273 1273 -- -- -- 6
3 -- -- -- 1273 1273 -- -- -- 4
1 EQP_NC - HWP-1 - SUB GRADE 30 A 3 1273 1273 3 30 A EQP_NC - HWP-2 - SUB GRADE 2
CKT Circuit Description Trip P A B C P Trip Circuit Description CKT
Mounting: SURFACE Wires: 4 FCB / MCB Rating: 100 A
Supply From: Phases: 3 MLO / MCB: MLO
Location: MECH 005 Volts: 208Y/120 A.I.C. Rating:
Extg Branch Panel: N
DATE INITIAL
02/24/2023 jlkirk Highlight jlkirk Highlight
| 07310034-7-E 00 |
| 07310034-7-E 01 |
| 07310034-7-E 02 |
| 07310034-7-E 03 |
| 07310034-7-E001 |
| 07310034-7-E002 |
| 07310034-7-E003 |
| 07310034-7-E101 |
| 07310034-7-E102 |
| 07310034-7-E401 |
| 07310034-7-E501 |
| 07310034-7-E502 |
File details come from the government source that posted it. Updated .