B08_Solicitation_attach_5_Drawing_Spec_4_of_4.pdf

PDF 5 MB Posted

Attached to
JECA HVAC Replacement Federal contract opportunity
Solicitation number
140P6324B0003
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This package of documents relates to solicitation number 140P6324B0003 for HVAC replacement services at Jewel Cave National Monument in Custer, South Dakota. The opportunity is being offered by the National Park Service Midwest Region on behalf of the Department of the Interior.

The documents include plans, specifications, schedules and diagrams detailing the scope of work. Mechanical equipment such as air handlers, condensing units, boilers and pumps will be replaced. Electrical work includes a new main panelboard, reinstallation of lighting and devices, and extension of conduit and wiring to support the new equipment. Bidders are advised to verify existing conditions and coordinate outages with the owner. The contractor will be responsible for restoration work, fire alarm integration, and compliance with all specifications.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. SEE ARCHITECTURAL SHEETS FOR EXACT AREAS AND WALLS

AFFECTED BY THE DEMOLITION AND REMODEL.

B. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT.

COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES.

PROVIDE TEMPORARY POWER AND LIGHTS AS REQUIRED TO ALLOW

THE WORK OF OTHER TRADES TO PROCEED OR AS REQUIRED TO

ALLOW THE OWNER TO OCCUPY THE SPACE.

C. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING ARE

EXISTING. THE LOCATIONS OF THE EQUIPMENT AND DEVICES WERE

OBTAINED FROM EXISTING DRAWING AND FIELD INVESTIGATION. THE

LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN

FOR THE CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE

INFORMATION SHOWN IS NOT GUARANTEED. THE CONTRACTOR IS

RESPONSIBLE FOR THE VERIFICATIONS OF ALL EXISTING CONDITIONS

PRIOR TO SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF

BIDS NEED TO BE FULLY COORDINATED WITH THE OWNER.

D. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE

VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE

INFORMATION SHOWN AND INCLUDED ON THE PANEL SCHEDULES IS

NOT GUARANTEED.

E. LUMINAIRES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE

LOCATED ON CEILINGS OR WALLS, SHALL HAVE LUMINAIRES, DEVICE

AND ALL ASSOCIATED CIRCUIT WIRING AND CONDUIT REMOVED BACK

TO NEAREST JUNCTION BOX, OR DEVICE NOT INDICATED TO BE

REMOVED. ACTUAL CIRCUITING MUST BE DETERMINED IN THE FIELD.

THE CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT,

DEVICES AND CONNECTIONS NECESSARY TO ENSURE CIRCUIT

CONTINUITY OF THE REMAINING DEVICES.

F. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.

ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE

REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY THE

CONTRACTOR. CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF

ANY PCB BALLAST OR HAZARDOUS LAMPS.

G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE

LABELING OF SPARE OR ABANDONED CIRCUITS AND/OR CIRCUIT

BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE

CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE

CIRCUITING OF THE NEW OR REMODELED AREA AS SPACE AND PANEL

LOADING WILL ALLOW.

H. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE

PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING

PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO

THE DEMOLITION WORK DONE BY THE ELECTRICAL CONTRACTOR,

UNDER THE TERMS OF THIS SPECIFICATION. CLOSE AND SEAL ALL

OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.

I. EXISTING FIRE ALARM DEVICES, EMERGENCY LIGHTS AND EXIT SIGNS

SHALL BE COMPLETE AND OPERABLE AT ALL TIMES. PROVIDE

TEMPORARY DEVICES IN AREAS BEING WORKED ON TO ALLOW FOR A

WORKABLE SYSTEM DURING CONSTRUCTION.

J. PROVIDE MINIMUM [2] DAYS ADVANCE NOTICE OF OUTAGES.

COORDINATE WITH OWNER FOR ALL ANTICIPATED OUTAGES. OWNER

HAS FINAL APPROVAL ON TIME AND EXTENT OF POWER OUTAGE.

K. PROTECT EXISTING FURNITURE, CARPET AND OTHER

APPURTENANCES FROM DAMAGE DURING THE COURSE OF

CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO THE

OWNER.

L. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR

SALVAGED ARE SHOWN AS FULL-TONE LINES ON DEMO PLANS. ALL

OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN

AS HALF-TONE.

A. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS

INDICATED OTHERWISE.

B. ALL AUXILIARY CABLE ABOVE CEILING SHALL BE PLENUM RATED

WHERE REQUIRED.

C. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE

WHERE INSTALLED IN ACOUSTICAL TILE CEILING.

D. PROVIDE 120 VOLT POWER CIRCUIT(S) FOR AUXILIARY SYSTEMS AS

REQUIRED FOR COMPLETE AND OPERATIONAL SYSTEMS.

E. FOR EXISTING CIRCUITS IN EXISTING PANELBOARDS '(EXTG)', VERIFY

ALL LOADS AND UPDATE PANEL SCHEDULE. SUBMIT FOR ENGINEER'S

REVIEW.

A. DRAWINGS DO NOT SHOW TOTAL NUMBER OF CONDUCTORS FOR

CIRCUITS REQUIRED. PROVIDE THE NUMBER OF CONDUCTORS

NEEDED TO COMPLETE INSTALLATION OF SPECIFIC EQUIPMENT

FURNISHED. A GREEN GROUND CONDUCTOR, SIZED PER NEC, SHALL

ALSO BE INCLUDED IN EACH CIRCUIT. ADJUST CONDUCTOR SIZES AS

NEEDED TO LIMIT VOLTAGE DROP TO LEVELS RECOMMENDED BY

NEC. THE CONTRACTOR SHALL ALSO COORDINATE INSPECTIONS

WITH THE AHJ.

B. SEE ARCHITECTURAL SHEETS FOR REFLECTED CEILING PLANS.

C. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRAL WIRES BUT CAN

SHARE AN INSULATED GREEN GROUND WIRE IN MINIMUM 3/4" EMT

CONDUIT.

D. NO BOXES SHALL BE MOUNTED BACK TO BACK.

E. CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE OR

FIRE/SMOKE RATED WALLS AND FLOORS.

F. ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY AND IN

ACCORDANCE WITH NEC PARAGRAPHS 230.8, 300.5(G) AND 300.7(A).

ALL RACEWAYS SHALL BE SEALED AS REQUIRED BY NEC AND NFPA.

G. CABLE AND CONDUIT SHALL NOT INTERFERE WITH EQUIPMENT

ACCESS.

H. ALL CABLING ABOVE CEILING SHALL BE PROPERLY SUPPORTED (NOT

FROM CEILING SYSTEM).

I. CONTRACTOR SHALL COORDINATE FINAL PANEL DIRECTORIES WITH

OWNER.

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E 00

ELECTRICAL INFO SHEET

07310034- 7- E 00 ELECTRICAL INFO SHEET

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,

DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR

ALL REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE

MECHANICAL DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT

TO BE REMOVED. UPDATE PANELBOARD SCHEDULES TO REFLECT

ALL CHANGES.

D2 REMOVE EXISTING CEILING LUMINAIRES AND DEVICES SHOWN,

FOR CEILING REMOVAL AND MECHANICAL WORK. CLEAN AND

STORE LUMINAIRES AND DEVICES FOR IN-PLACE

REINSTALLATION. COORDINATE TEMPORARY STORAGE LOCATION

WITH OWNER. EXISTING WIRING TO BE PROTECTED DURING

DEMOLITION/CONSTRUCTION FOR REUSE.

D3 REMOVE INDICATED CONDUCTORS AND CONDUIT FROM EMPTY

DISCONNECT ENCLOSURE BEING USED AS A JUNCTION BOX.

COVER OR PLUG EMPTY HOLES, PER NEC REQUIREMENTS.

D4 FIELD VERIFY EXISTING CONDUCTOR SIZES. REMOVE

CONDUCTORS FROM EXISTING CONDUIT FOR INSTALLATION OF

NEW CONDUCTORS. EXISTING CONDUIT TO REMAIN TO EXTENT

POSSIBLE. SEE SHEET E502 FOR ADDITIONAL INFORMATION.

1 NEW PANEL 'MDP' TO REPLACE EXISTING 'MDP'. SEE E101, E502,

AND E601 FOR COMPLETE INFORMATION.

2 REINSTALL CEILING LUMINAIRES AND DEVICES IN NEW CEILING AT

ORIGINAL LOCATIONS, UNLESS SHOWN OTHERWISE. RECONNECT

TO EXISTING WIRING, EXTEND AS REQUIRED.

3 PROVIDE NEW CONDUCTORS AND RE-ROUTE/EXTEND EXISTING

CONDUIT TO NEW 'MDP' LOCATION AS REQUIRED FOR A FULLY

FUNCTIONAL SYSTEM. NEW CONDUCTORS TO MATCH EXISTING

CONDUCTOR SIZE. EXISTING CONDUIT SHALL BE REUSED TO

EXTENT POSSIBLE, IF IN ACCEPTABLE CONDITION.

4 COORDINATE REQUIREMENTS WITH MECHANICAL CONTRACTOR

FOR BOILER SHUT OFF REQUIREMENTS.

5 PROVIDE UNISTRUT MOUNTING FOR 600A/3 'MDP' DISCONNECT AT

THIS LOCATION. FIELD COORDINATE ORIENTATION TO ENSURE

WORKING CLEARANCE REQUIREMENTS PER NEC.

E 00 ELECTRICAL INFO SHEET

E 01 ELECTRICAL SPECIFICATIONS

E 02 ELECTRICAL SPECIFICATIONS

E 03 ELECTRICAL SPECIFICATIONS

E001 SUB-GRADE PLAN - DEMOLITION

E002 FIRST FLOOR PLAN - DEMOLITION

E003 SECOND FLOOR PLAN - DEMOLITION

E004 THIRD FLOOR PLAN - DEMOLITION

E101 SUB-GRADE PLAN - ELECTRICAL

E102 FIRST FLOOR PLAN - ELECTRICAL

E103 SECOND FLOOR PLAN - ELECTRICAL

E104 THIRD FLOOR PLAN - ELECTRICAL

E401 ELECTRICAL DETAILS

E501 POWER RISER DIAGRAM - DEMOLITION

E502 POWER RISER DIAGRAM

E601 ELECTRICAL SCHEDULES

S

SYMBOL LEGEND

PC

J

J

OS

MS

IC

S

S

M

N

TV

VC

N E

N S

N

N D

N 2

G

K1

V

A

F

F

F

F

FS

D

PS

TS

R

M

M

T

DH

WALL MOUNTED STRIP LUMINAIRE

SYMBOL NOTES:

STROBE

HORN

MANUAL PULL STATION

HORN STROBE

PHOTOCELL

VOICE AND DATA

JUNCTION BOX - CEILING MOUNT

JUNCTION BOX - WALL MOUNT

VOICE OUTLET

DATA OUTLET

OCCUPANCY SENSOR

MOTION SENSOR

CEILING FAN

HEAT DETECTOR

SMOKE DETECTOR

REMOTE INDICATOR LIGHT

SPRINKLER TAMPER SWITCH

DUCT SMOKE DETECTOR

FLOW SWITCH

POST INDICATING VALVE SWITCH

POLE MOUNTED SITE LUMINAIRE

NURSE CALL

SPEAKER

BEDSIDE STATION

INTERCOM SPEAKER STATION

VOLUME CONTROL STATION

MICROPHONE JACK

TELEVISION OUTLET

CCTV CAMERA

SOUND, TELEVISION, AND SECURITY

FUSE

EMERGENCY PULL STATION

DISCONNECT SWITCH

STAFF STATION

DUTY STATION

DOME LIGHT

MASTER STATION

EMERGENCY GENERATOR

POWER DISTRIBUTION ONE LINE

CONDUIT UP

CONDUIT DOWN

INDICATES BUSHED CONDUIT

VOICE/DATA OUTLET

DOUBLE BED BEDSIDE STATION

DRAW OUT VACUUM

CIRCUIT BREAKER

LIGHTNING SURGE ARRESTOR

THERMAL OVERLOAD RELAY

PLUG-IN OR DRAWOUT

CONNECTOR

CIRCUIT BREAKER

FUSED DISCONNECT SWITCH

VOLTMETER

AMMETER

X:Y

CURRENT TRANSFORMER -

(RATIO)

KIRK KEY INTERLOCK

MAGNETIC DOOR HOLDER

"C" INDICATES CEILING MOUNTED

"F" INDICATES FLOOR MOUNTED

"S" INDICATES SURFACE MOUNTED

"G" INDICATES GROUND FAULT INTERRUPTING

"IG" INDICATES ISOLATED GROUND

"AC" INDICATES MOUNTING 6" ABOVE COUNTERTOP

OR BACKSPLASH

"WP" INDICATES WEATHERPROOF

"XP" INDICATES EXPLOSION PROOF

"U" INDICATES USB CHARGER

"R" INDICATES EXISTING DEVICE REMOVED AND

RELOCATED

LOWER CASE LETTER BY SWITCHES AND FIXTURES

INDICATE ASSOCIATED UNIT FOR SWITCHING

LIGHTING

LUMINAIRE

WALL MOUNTED LUMINAIRE

RECESSED LUMINAIRE

WALL MOUNTED LUMINAIRE

SURFACE MOUNTED LUMINAIRE

TRACK LIGHTING

DIMMER SWITCH

TIMER SWITCH

WIRING DEVICES - SWITCHES

SINGLE POLE SWITCH

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT

THERMAL ELEMENT SWITCH

FOUR-WAY SWITCH

TWO POLE SWITCH

THREE-WAY SWITCH

STRIP / INDUSTRIAL LUMINAIRE

LUMINAIRE - NIGHT LIGHTING

LUMINAIRE - EMERGENCY SYSTEM

EMERGENCY BATTERY PACK LUMINAIRE

REMOTE EMERGENCY HEAD

WALL WASH LUMINAIRE

PENDANT MOUNTED LUMINAIRE

POWER POLE

METER SOCKET

POWER EQUIPMENT

WIRING DEVICES - RECEPTACLES

COMBINATION STARTER SAFETY SWITCH

RELAY - CONTROL AS NOTED

PUSHBUTTON STATION

MOTOR CONNECTION

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

EMERGENCY RECEPTACLE

SPECIAL PURPOSE RECEPTACLE, NEMA

CONFIGURATION NOTED

PLUG-IN STRIP - LENGTH AND QUANTITY

OF OUTLETS AS SHOWN

SAFETY SWITCH

DROP CORD RECEPTACLE ASSEMBLY

FUSIBLE SWITCH (FUSETRON)

PANELS AND CABINETS

DISTRIBUTION PANEL

SWITCHBOARD, SWITCHGEAR, MCC

EQUIPMENT OR TERMINAL CABINET

DRY TYPE TRANSFORMER

BRANCH CIRCUIT PANEL

CONDUIT AND BOXES

FIRE ALARM SYSTEM

HORN (PA, PUBLIC ADDRESS)

TRANSFORMER

EXIT LIGHT - WALL MOUNT WITH

DIRECTIONAL ARROWS AS INDICATED,

FILLED-IN QUARTERS INDICATE

ILLUMINATION SIDES

EXIT LIGHT - CEILING OR PENDANT

MOUNT WITH DIRECTIONAL ARROWS AS

INDICATED, FILLED-IN QUARTERS

INDICATE ILLUMINATION SIDES

EMERGENCY EXIT LIGHT COMBO

LOW VOLTAGE MOMENTARY

CONTACT SWITCH

H

S

S

N P PILLOW SPEAKER

FB FLOOR BOX

FP FLOOR POKE-THROUGH DEVICE

N M

WIRELESS ACCESS POINT

S S2

S3

S4

SD

SK

SP

STE

ST

SFT

X

CONTROLLED RECEPTACLE

WB WALL AV BOX

F SPEAKER STROBES

F SPEAKERS

RC ROOM CONTROLLER

PP POWER PACK

ABBREVIATIONS

TEL TELEPHONE

TEMP TEMPERATURE

TVSS TRANSIENT VOLTAGE

SURGE SUPPRESSOR

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS

LABORATORIES

UPS UNINTERRUPTIBLE

POWER SYSTEM

VFD VARIABLE FREQUENCY

DRIVE

W WEST

W/ WITH

W/O WITHOUT

WHM WATTHOUR METER

WT WEIGHT

XFMR TRANSFORMER

ACSR ALUMINUM CONDUCTOR

STEEL REINFORCED

AFF ABOVE FINISH FLOOR

AIC AMPS INTERRUPTING

CAPACITY (SYM RMS)

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

APPROX APPROXIMATE

AUTO AUTOMATIC

AVG AVERAGE

L ANGLE

BKR BREAKER

C OR CL CENTER LINE

C OR CND CONDUIT (ELECTRICAL

SHEETS)

CKT CIRCUIT

CLG CEILING

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CPT CONTROL POWER

TRANSFORMER

DC DIRECT CURRENT

DEG DEGREE

DEMO DEMOLITION

DIA DIAMETER

DIM DIMENSION

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DWG DRAWING

E EAST

EA EACH

EL OR

ELEV

ELEVATION - GRADE OR

BUILDING

ELEC ELECTRIC OR

ELECTRICAL

ELEV ELEVATOR

EMD ESTIMATED MAXIMUM

DEMAND

ENCL ENCLOSURE

EQUIP EQUIPMENT

EST ESTIMATE

EWC ELECTRIC WATER

COOLER

EXIST EXISTING

EXP EXPOSED

EXT EXTERIOR

FA FIRE ALARM

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FLUOR FLUORESCENT

AWG GAUGE

HP HORSE POWER

HR HOUR

HTG HEATING

HTR HEATER

HZ HERTZ

FAAP FIRE ALARM

ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL

PANEL

FAEP FIRE ALARM EXTENDER

PANEL

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

CUH CABINET UNIT HEATER

EMI ELECTROMAGNETIC

INTERFERENCE

SOUTH

SCHED SCHEDULE

SF SQUARE FOOT (FEET)

SPEC SPECIFICATIONS

SPKR SPEAKER

SQ SQUARE

STD STANDARD

STL STEEL

SW SWITCH

SWBD SWITCH BOARD

SYM SYMMETRICAL

S

GFI GROUND FAULT CIRCUIT

INTERRUPTER

SCCR SHORT CIRCUIT

CURRENT RATING

SPD SURGE PROTECTIVE

DEVICE

SPDT SINGLE POLE, DOUBLE

THROW

VFC VARIABLE FREQUENCY

CONTROLLER

ID INSIDE DIAMETER

IES ILLUMINATING

ENGINEERING SOCIETY

IN INCH

INSUL INSULATION

INT INTERIOR

KCMIL KCM KILO CIRCULAR MIL

KV KILOVOLTS

KVA KILOVOLT AMPERES

KVAR KILOVOLT AMPERES

REACTIVE

KW KILOWATT

LBS POUNDS

LRA LOCKED ROTOR AMPS

LTG LIGHTING

QTY QUANTITY

REC RECEPTACLE

REFR REFRIGERATOR

REINF REINFORCEMENT

REQD REQUIRED

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

N NORTH

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO NUMBER

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

OH OVERHEAD

OPNG OPENING

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PSI POUNDS PER SQUARE IN.

MCCB MOLDED CASE CIRCUIT

BREAKER

OCPD OVERCURRENT

PROTECTIVE DEVICE

RFI RADIO FREQUENCY

INTERFERENCE

REF. DEMO NOTES ( )

PROJECT ELECTRICAL REFERENCED DEMOLITION NOTES

X

DX

PROJECT ELECTRICAL REFERENCED NOTES

NORTH

ARROW

MATCHLINE

AREA A

AREA B

EXISTING

COLUMN

NEW

COLUMN

X

X

X

XX-XX

SIM

X

XX-XX

XXXX

DX

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

150 SF

ROOM

NUMBER

LETTER INDICATES

NEW COLUMN LINE

LETTER INDICATES

EXISTING COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

ROOM AREA DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION

DESIGNATION

GRAPHIC AREA FOR DRAWING

TITLE

SCALE OF THE DRAWING

REF. NOTES ( )

GENERAL NOTESGENERAL DEMO NOTES

ELECTRICAL SHEET LIST

GEN. POWER & AUX SYSTEMS NOTES

TRUE

NORTH

PLAN

NORTH

NORTH

DATE INITIAL

02/24/202302/24/2023

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E 01

ELECTRICAL

SPECIFICATIONS

07310034- 7- E 01 ELECTRICAL SPECIFICATIONS

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

02/24/2023

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E 02

ELECTRICAL

SPECIFICATIONS

07310034- 7- E 02 ELECTRICAL SPECIFICATIONS

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E 03

ELECTRICAL

SPECIFICATIONS

07310034- 7- E 03 ELECTRICAL SPECIFICATIONS

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

J

J

M

M

M

H

H

PANEL 'ELEVP'

PANEL 'P'

EXTG PANEL 'MDP'

PANEL 'E'

D1

D1D1

PANEL 'N'

PANEL 'C'

D1

D1

D2

ATS

D2

D2

D2

D2

D2

MECH

STAIR

ENTRY

STORAGE

RESTROOM

OFFICE

ELEV

ELEV

XFMR

METER

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E001

SUB-GRADE PLAN -

DEMOLITION

07310034- 7- E001 SUB-GRADE PLAN - DEMOLITION

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

REF. DEMO NOTES ( ):DX

D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,

DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL

REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL

DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.

UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.

D2 REMOVE EXISTING CEILING LUMINAIRES AND DEVICES SHOWN, FOR

CEILING REMOVAL AND MECHANICAL WORK. CLEAN AND STORE

LUMINAIRES AND DEVICES FOR IN-PLACE REINSTALLATION. COORDINATE

TEMPORARY STORAGE LOCATION WITH OWNER. EXISTING WIRING TO BE

PROTECTED DURING DEMOLITION/CONSTRUCTION FOR REUSE.

KEY PLAN NORTH

SCALE: 1/4" = 1'-0"

SUB-GRADE FLOOR PLAN - ELECTRICAL DEMOLITION

S S

SS

S

S

S

S

H

S

D1

PANEL 'F'

PANEL 'A'

FAEP

FAAP

PANEL 'RR'

D2

(TYP. ALL LUMINAIRES AND

CEILING DEVICES SHOWN)

LOBBY

VESTIBULE

CORRIDOR

ELEVATOR

LOBBY

HOISTWAY

ELEVATOR

GUIDES

STAIR

COURTYARD

LOBBY EXHIBIT

PARK STORE

HALL

SECRETARY

STORAGE

OFFICE

EXHIBIT ROOM

CORRIDOR

OFFICE

OFFICE

OFFICE

WORKROOM

114 VESTIBULE

MECH

WOMENS

MENS

CORRIDOR

117A

CORRIDOR

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E002

FIRST FLOOR PLAN -

DEMOLITION

07310034- 7- E002 FIRST FLOOR PLAN - DEMOLITION

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

REF. DEMO NOTES ( ):DX

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - ELECTRICAL DEMOLITION

D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,

DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL

REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL

DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.

UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.

D2 REMOVE EXISTING CEILING LUMINAIRES AND DEVICES SHOWN, FOR

CEILING REMOVAL AND MECHANICAL WORK. CLEAN AND STORE

LUMINAIRES AND DEVICES FOR IN-PLACE REINSTALLATION. COORDINATE

TEMPORARY STORAGE LOCATION WITH OWNER. EXISTING WIRING TO BE

PROTECTED DURING DEMOLITION/CONSTRUCTION FOR REUSE.

DATE INITIAL

KEY PLAN NORTH

D1

D1

STORAGE

WORKROOM

STAIR

FAN ROOM

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E003

SECOND FLOOR PLAN -

DEMOLITION

07310034- 7- E003 SECOND FLOOR PLAN - DEMOLITION

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

REF. DEMO NOTES ( ):DX

KEY PLAN NORTH

SCALE: 1/4" = 1'-0"

SECOND FLOOR PLAN - ELECTRICAL DEMOLITION

D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,

DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL

REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL

DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.

UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.

PANEL 'M'

FACP

XFMR

XFMR

ELEVATOR

MACHINE

ROOM

STAIR

D1

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E004

THIRD FLOOR PLAN -

DEMOLITION

07310034- 7- E004 THIRD FLOOR PLAN - DEMOLITION

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

REF. DEMO NOTES ( ):DX

KEY PLAN NORTH

SCALE: 1/4" = 1'-0"

THIRD FLOOR PLAN - ELECTRICAL DEMOLITION

D1 REMOVE ELECTRICAL POWER AND CONTROL WIRING, CONDUITS,

DISCONNECTS, AND ASSOCIATED ELECTRICAL COMPONENTS FOR ALL

REMOVED MECHANICAL EQUIPMENT IN THIS AREA. SEE MECHANICAL

DEMOLITION DRAWING(S) FOR SPECIFIC EQUIPMENT TO BE REMOVED.

UPDATE PANELBOARD SCHEDULES TO REFLECT ALL CHANGES.

DATE INITIAL

02/24/2023 jlkirk Highlight jlkirk Highlight jlkirk Highlight

H

H

PANEL 'E'

PANEL 'P'

PANEL 'ELEVP'

MDP - 8

ACCU-1

N - 12

B-1

PANEL 'MDP'

PANEL 'N'

N - 1,3,5

HWP-1

N - 2,4,6

HWP-2

M - 2,4,6

CU-1

PANEL 'C'

ATS

EMERGENCY

BOILER SHUT OFF

MGB

EMERGENCY

BOILER SHUT OFF

MDP - 11

DSS-1B

STAIR

MECH

ENTRY

STORAGE

RESTROOM

OFFICE

ELEV

ELEV

XFMR

METER

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E101

SUB-GRADE PLAN -

ELECTRICAL

07310034- 7- E101 SUB-GRADE PLAN - ELECTRICAL

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

KEY PLAN NORTH

SCALE: 1/4" = 1'-0"

SUB-GRADE FLOOR PLAN - ELECTRICAL

DATE INITIAL

REF. NOTES ( ):X

1 NEW PANEL 'MDP' TO REPLACE EXISTING 'MDP'. SEE E101, E502, AND E601

FOR COMPLETE INFORMATION.

2 REINSTALL CEILING LUMINAIRES AND DEVICES IN NEW CEILING AT

ORIGINAL LOCATIONS, UNLESS SHOWN OTHERWISE. RECONNECT TO

EXISTING WIRING, EXTEND AS REQUIRED.

4 COORDINATE REQUIREMENTS WITH MECHANICAL CONTRACTOR FOR

BOILER SHUT OFF REQUIREMENTS.

5 PROVIDE UNISTRUT MOUNTING FOR 600A/3 'MDP' DISCONNECT AT THIS

LOCATION. FIELD COORDINATE ORIENTATION TO ENSURE WORKING

CLEARANCE REQUIREMENTS PER NEC.

S S

SS

S

S

S

S

H

S

PANEL 'A'

PANEL 'F'

FAAP

FAEP

(TYP. ALL LUMINAIRES AND

CEILING DEVICES SHOWN)

PANEL 'RR'

LOBBY

CORRIDOR

ELEVATOR

LOBBY

HOISTWAY

ELEVATOR

STAIR

GUIDES

COURTYARD

HALL

PARK STORE

LOBBY EXHIBIT

VESTIBULE

EXHIBIT ROOM

115 SECRETARY

STORAGE

OFFICE

OFFICE

OFFICE

OFFICE

VESTIBULE

WORKROOM

CORRIDOR

117A

CORRIDOR

CORRIDOR

MENS

WOMENS

MECH

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E102

FIRST FLOOR PLAN -

ELECTRICAL

07310034- 7- E102 FIRST FLOOR PLAN - ELECTRICAL

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

REF. NOTES ( ):X

2 REINSTALL CEILING LUMINAIRES AND DEVICES IN NEW CEILING AT

ORIGINAL LOCATIONS, UNLESS SHOWN OTHERWISE. RECONNECT TO

EXISTING WIRING, EXTEND AS REQUIRED.

KEY PLAN NORTH

DATE INITIAL

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - ELECTRICAL

S D

MDP - 9

RAF-1

MDP - 10

AHU-1

MDP - 11

DSS-1A

MDP - 12

FT-1

STORAGE

FAN ROOM

STAIR

WORKROOM

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E103

SECOND FLOOR PLAN -

ELECTRICAL

07310034- 7- E103 SECOND FLOOR PLAN - ELECTRICAL

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

KEY PLAN NORTH

SCALE: 1/4" = 1'-0"

SECOND FLOOR PLAN - ELECTRICAL

DATE INITIAL

02/24/2023 jlkirk Highlight jlkirk Highlight

PANEL 'M'

M - 1,3

BCU-1

FACP

XFMR

XFMR

ELEVATOR

MACHINE

ROOM

STAIR

MDP - 13

UH-1

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E104

THIRD FLOOR PLAN -

ELECTRICAL

07310034- 7- E104 THIRD FLOOR PLAN - ELECTRICAL

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

KEY PLAN NORTH

SCALE: 1/4" = 1'-0"

THIRD FLOOR PLAN - ELECTRICAL

DATE INITIAL

02/24/2023 jlkirk Highlight jlkirk Highlight

SYSTEM CONDUCTOR IDENTIFICATION

208Y/120V 3Φ 4W

A – PHASE – BLACK

B – PHASE – RED

C – PHASE – BLUE

NEUTRAL – WHITE

GROUND – GREEN

SYSTEM CONDUCTOR IDENTIFICATION

480Y/277V 3Φ 4W

A – PHASE – BROWN

B – PHASE – ORANGE

C – PHASE – YELLOW

NEUTRAL – GRAY

GROUND – GREEN

SYSTEM IDENTIFICATION DECAL

SYSTEM CONDUCTOR IDENTIFICATION

120/240V

A – PHASE – BLACK

B – PHASE – RED

NEUTRAL – WHITE

GROUND – GREEN

SYSTEM CONDUCTOR IDENTIFICATION

240V DELTA 3Φ 3W

A – PHASE – PINK

B – PHASE – PURPLE

C – PHASE – TAN

GROUND – GREEN

FED FROM MDP

PANEL IDENTIFICATION DECAL

PANEL TYPE PANEL

DESIGNATION

NOTES:

1. DECALS SHALL BE LAMINATED ACRYLIC WITH WHITE ENGRAVED LETTERING ON A BLACK BACKGROUND. PANELS OR EQUIPMENT CONNECTED TO AN ALTERNATE

POWER SOURCE SHALL HAVE WHITE ENGRAVED LETTERING ON A RED BACKGROUND.

2. DECALS SHALL BE SIZED TO ACCOMMODATE SPECIFIED LEGENDS BUT NO SMALLER THAN SIZES SHOWN, MINIMUM OF 1/16” THICK.

3. DECALS SHALL BE PUNCHED OR DRILLED FOR MECHANICAL FASTENERS WITH 1/4” GROMMETS IN CORNERS FOR MOUNTING.

4. COLORS FOR 240V DELTA SYSTEMS BASED ON AVAILABLE COLORS OFFERED BY SOUTHWIRE. OTHER COLORS THAT DO NOT CONFLICT WITH OTHER VOLTAGE

SYSTEMS PERMITTED.

CR = CRITICAL

EQ = EQUIPMENT

LS = LIFE SAFETY

EM = EMERGENCY

OS = OPTIONAL STANDBY

H = 480V L = 208V

H1

DISCONNECT IDENTIFICATION

DECAL TO BE PERMANENTLY

POSTED. SEE DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

PANEL IDENTIFICATION DECAL TO

BE PERMANENTLY POSTED. SEE

DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

SYSTEM IDENTIFICATION DECAL TO BE

PERMANENTLY POSTED.

SIZE: 1-1/2”H x 3”W. TEXT HEIGHT: 1/8"

BRANCH/FEEDER IDENTIFICATION

DECAL TO BE PERMANENTLY

POSTED. SEE DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

PANEL H1

BRANCH/FEEDER IDENTIFICATION DECAL

TRANSFORMER IDENTIFICATION

DECAL TO BE PERMANENTLY

POSTED. SEE DETAILS AT RIGHT.

SIZE: 1”H x 3”W. TEXT HEIGHT: 1/4"

TL1

TRANSFORMER IDENTIFICATION DECAL

FED FROM MDP

FEEDS L1

EF-1

DISCONNECT IDENTIFICATION DECAL

480V

FED FROM MDP

INSULATORS (TYP. 2)

BOLT TO WALL

ANCHOR BOLTS

COPPER GROUND BAR

WALL MOUNTING BRACKET

'MGB'

ERICO EGBA14424MMT

2'-0"

'MGB'

BUILDING

STRUCTURAL

COLUMN OR

BEAM (TYP.)

EXOTHERMIC WELD

BURNDY TYPE BCS-3 MOLD

4 AWG OR LARGER BARE COPPER

CONDUCTOR OR STEEL REINFORCING

BAR OR ROD NOT LESS THAN

1/2" DIAMETER AT LEAST 20' LONG.

(CONCRETE ENCASE ELECTRODE)

CONNECTION LISTED

FOR PURPOSE (TYP.)

NON-METALLIC

PROTECTIVE

SLEEVE

INSULATED #4/0 GROUNDING

ELECTRODE CONDUCTOR IN 1"C. (TYP.)

N G

'MDP'

CONNECTION LISTED

FOR PURPOSE (TYP.)

GROUND RODS

MAIN BONDING JUMPER

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E401

ELECTRICAL DETAILS

07310034- 7- E401 ELECTRICAL DETAILS

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

SCALE: 1/8" = 1'-0"

PANELBOARD & EQUIPMENT IDENTIFICATION DETAIL

SCALE: NOT TO SCALE

GROUND BAR DETAIL

SCALE: NOT TO SCALE

SERVICE GROUNDING DETAIL

T

T

PANEL

'ELEVP'

SUB GRADE

FIRST FLOOR

GENERATOR

UTILITY

THIRD FLOOR

PANEL

'E'

'ATS'

'A'

PANEL

'M'

PANEL

'N'

T

ELEVATOR EQUIPMENT ROOM

OFFICE

CORRIDOR

ELECTRICAL EQUIPMENT ROOM

PANEL

'C'

'RR'

THEATER KIOSK VENDING MACHINE CANOPY

PANEL

'P'

PANEL

'G'

PANEL

'P1'

PANEL

'V''F'

PANEL

'MDP'

D3

D4

D4

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E501

POWER RISER DIAGRAM -

DEMOLITION

07310034- 7- E501 POWER RISER DIAGRAM - DEMOLITION

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

DATE INITIAL

REF. DEMO NOTES ( ):DX

D3 REMOVE INDICATED CONDUCTORS AND CONDUIT FROM EMPTY

DISCONNECT ENCLOSURE BEING USED AS A JUNCTION BOX. COVER OR

PLUG EMPTY HOLES, PER NEC REQUIREMENTS.

D4 FIELD VERIFY EXISTING CONDUCTOR SIZES. REMOVE CONDUCTORS

FROM EXISTING CONDUIT FOR INSTALLATION OF NEW CONDUCTORS.

EXISTING CONDUIT TO REMAIN TO EXTENT POSSIBLE. SEE SHEET E502

FOR ADDITIONAL INFORMATION.

SCALE: NOT TO SCALE

POWER RISER DIAGRAM - DEMOLITION

PROVIDE 4"

CONCRETE PAD

PANEL

'MDP'

T

T

PANEL

'ELEVP'

SUB GRADE

FIRST FLOOR

GENERATOR

UTILITY

THIRD FLOOR

PANEL

'E'

'ATS'

'A'

PANEL

'M'

PANEL

'N'

T

ELEVATOR EQUIPMENT ROOM

OFFICE

CORRIDOR

ELECTRICAL EQUIPMENT ROOM

PANEL

'C'

'RR'

THEATER KIOSK VENDING MACHINE CANOPY

PANEL

'P'

PANEL

'G'

PANEL

'P1'

PANEL

'V''F'

MGB

E401

E401

F600A4G

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E502

POWER RISER DIAGRAM

07310034- 7- E502 POWER RISER DIAGRAM

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

REF. NOTES ( ):X

1 NEW PANEL 'MDP' TO REPLACE EXISTING 'MDP'. SEE E101, E502, AND E601

FOR COMPLETE INFORMATION.

3 PROVIDE NEW CONDUCTORS AND RE-ROUTE/EXTEND EXISTING CONDUIT

TO NEW 'MDP' LOCATION AS REQUIRED FOR A FULLY FUNCTIONAL

SYSTEM. NEW CONDUCTORS TO MATCH EXISTING CONDUCTOR SIZE.

EXISTING CONDUIT SHALL BE REUSED TO EXTENT POSSIBLE, IF IN

ACCEPTABLE CONDITION.

SCALE: NOT TO SCALE

POWER RISER DIAGRAM

DATE INITIAL

F600A4G 2 SETS OF 4#350, 1#1G - 3"C

FEEDER SCHEDULE ( ):FXXXXXXX

GENERAL EQUIPMENT SCHEDULE NOTES:

A. THIS SCHEDULE DISPLAYS SIZING INFORMATION THAT IS GENERIC IN

NATURE. SCHEDULE DOES NOT ITEMIZE ALL INSTANCES OF

EQUIPMENT. CONTRACTOR SHALL REFER TO THE PLANS FOR FINAL

QUANTITIES AND LOCATIONS.

B. MOUNT ALL DISCONNECTS AND STARTERS ON ASSOCIATED

EQUIPMENT UNLESS SHOWN OTHERWISE. MAINTAIN WORKING

CLEARANCES PER NEC; COORDINATE WITH MECHANICAL

CONTRACTOR.

C. BCU = BOX COVER UNIT (COOPER #SSY / #STY OR EQUAL) WITH FUSE.

D. NFD OR FD = NON-FUSED OR FUSED DISCONNECT SWITCH.

E. CS/NFD, FD = COMBINATION STARTER/ NON OR FUSED DISCONNECT

SWITCH.

F. INT = INTEGRAL DISCONNECT FURNISHED WITH EQUIPMENT.

G. FHPMC = FRACTIONAL HORSEPOWER MANUAL CONTROLLER.

H. IHPMC = INTEGRAL HORSEPOWER MANUAL CONTROLLER.

I. STE = THERMAL ELEMENT SWITCH. PROVIDE THERMAL UNIT.

J. EXP = DEVICE TO BE EXPLOSION-PROOF.

K. ALL SWITCHES, DISCONNECTS, ETC SHALL BE LOCKABLE.

L. ALL SWITCHES, DISCONNECTS, ETC SHALL BE NEMA 3R WHERE

REQUIRED.

M. PROVIDE FUSES AS SHOWN; REVISE SIZES PER ACTUAL NAMEPLATE

DATA.

N. STARTER ACCESSORIES:STARTER ACCESSORIES:

1. CONTROL TRANSFORMER

2. H-O-A SWITCH

3. RED RUN LIGHT

4. 2 NO CONTACTS; 2 NC CONTACTS

EQUIPMENT SCHEDULE NOTES:

1. EQUIPMENT CONTROLLED BY VFD. COORDINATE REQUIREMENTS

WITH VFD MANUFACTUROR PRIOR TO INSTALLATION. SEE

MECHANICAL SHEETS FOR ADDITIONAL INFORMATION.

2. INDOOR UNIT 'DSS-1A' POWERED BY OUTDOOR UNIT 'DSS-1B'. SEE

MECHANICAL SHEETS FOR ADDITIONAL INFORMATION.

3. CONNECT AIR HANDLER RETURN DUCT SMOKE DETECTOR TO

EXISTING FIRE ALARM SYSTEM. SMOKE DETECTION SHALL INITIATE

BUILDING FIRE ALARM AND SHUT DOWN AIR HANLDER. COORDINATE

REQUIREMENTS WITH FIRE ALARM MANUFACTURER PRIOR TO

INSTALLATION.

1044 North 115th Street | Suite 300

Omaha, NE 68154

(402) 493-4800 www.schemmer.com

REVISED TITLE OF SHEET DRAWING NO.

SHEET

PMIS / PKG. NO.

OF

SUB SHEET NO.

ARCH/ENG PROJ #

DESIGNED

DRAWN

CHECKED

PREPARED

DATE

238608 / 80005

80005

C U s e rs \d la n g h o ld t\ D o c u m e n ts

\0

-E

L E

C

R d la n g h o ld tT W

S

J .r v t

JEF

DJL

JCB

2/24/23

07310.034

E601

ELECTRICAL SCHEDULES

07310034- 7- E601 ELECTRICAL SCHEDULES

HVAC REPLACEMENT

JEWEL CAVE NATIONAL MONUMENT

CUSTER, SD

EQUIPMENT SCHEDULE

DEVICE DEVICE DESCRIPTION VOLTAGE PH KW FLA HP

STARTER / DISCONNECT

PLUG CONFIG

RECEPT

CONFIG FEEDER SIZE NOTES TYPE SIZE FUSE

ACCU-1 AIR COOLED CONDENSING UNIT 208 V 3 - 120 - NFD 200/3 - - - F150A3G 3#1/0, 1#6G - 1-1/2"C

AHU-1 AIR HANDLING UNIT 208 V 3 - 29.5 - NFD 60/3 - - - F60A3G 3#4, 1#10G - 1-1/4"C 3

B-1 GAS FIRED BOILER 120 V 1 - 1.0 - FD 30/2 15 - - F20A2G 2#12, 1#12G - 3/4"C

BCU-1 INDOOR AIR HANDLER 208 V 1 - - 1/2 FD 30/2 15 - - F20A2G 2#12, 1#12G - 3/4"C

CU-1 OUTDOOR CONDENSING UNIT 208 V 3 - 12.2 1/8 NFD 30/3 - - - F20A3G 3#12, 1#12G - 3/4"C

DSS-1A DUCTLESS SPLIT SYSTEM 208 V 1 - 0.67 - - - - - - F20A2G 2#12, 1#12G - 3/4"C 2

DSS-1B DUCTLESS SPLIT SYSTEM 208 V 1 - 10 - FD 30/2 15 - - F20A2G 2#12, 1#12G - 3/4"C 2

FT-1 FINTUBE 208 V 1 1.0 - - NFD 30/2 - - - F20A2G 2#12, 1#12G - 3/4"C

HWP-1 INLINE PUMP 208 V 3 - - 3.0 FD 30/3 25 - - F30A3G 3#10, 1#10G - 3/4"C 1

HWP-2 INLINE PUMP 208 V 3 - - 3.0 FD 30/3 25 - - F30A3G 3#10, 1#10G - 3/4"C 1

RAF-1 INLINE FAN 208 V 3 - - 5.0 NFD 60/3 - - - F40A3G 3#8, 1#10G - 1"C 1

UH-1 UNIT HEATER 208 V 1 2.5 - - NFD 30/2 - - - F20A2G 2#12, 1#12G - 3/4"C

MCB: Main Circuit Breaker

LOCK: Lockable Circuit Breaker

GFI: GFCI Circuit Breaker MLO: Main Lug Only

FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker

Legend: Notes:

Total Est. Demand Current (80% Rated): 190 A

Continuous Current @ 125%: 41 A

Non-Cont. Current @ 100%: 150 A

EQP_NON CONT 53860 VA 100.00% 53860 VA Total Est. Demand Current (100% Rated): 182 A

EQP_CONT 11737 VA 100.00% 11737 VA Total Est. Demand: 65597 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

182 A

65597 VA

13 EQP_C - UH-1 - THIRD FLOOR 2 20 A 2500 VA

12 EQP_C - FT-1 - SECOND FLOOR 2 20 A 1000 VA

11 EQP_C - DSS-1A / B - SUB GRADE / SECOND FLOOR 2 20 A 2220 VA

10 EQP_NC - AHU-1 - SECOND FLOOR 3 60 A 10628 VA

9 EQP_C - RAF-1 - SECOND FLOOR 3 40 A 6017 VA

8 EQP_C - ACCU-1 - SUB GRADE 3 150 A 43232 VA

7 (EXTG) PANEL 'A' 3 100 A 0 VA

6 (EXTG) 1 20 A 0 VA

5 (EXTG) PANEL 'G' 3 125 A 0 VA

4 (EXTG) PANEL 'E' 3 450 A 0 VA

3 (EXTG) PANEL 'P' 3 200 A 0 VA

2 (EXTG) KIOSK 2 100 A 0 VA

1 (EXTG) PANEL 'N' 3 125 A 0 VA

CKT Circuit Description # of Poles Trip Rating Load Remarks

Mounting: SURFACE Wires: 4 FCB / MCB Rating: 600 A

Supply From: Phases: 3 MLO / MCB: MLO

Location: MECH 005 Volts: 208Y/120 A.I.C. Rating:

Power Panel: MDP

MCB: Main Circuit Breaker

LOCK: Lockable Circuit Breaker

GFI: GFCI Circuit Breaker MLO: Main Lug Only

FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker

Legend: Notes:

Total Est. Demand Current (80% Rated): 18 A

Continuous Current @ 125%: 15 A

Non-Cont. Current @ 100%: 3 A

EQP_NON CONT 1124 VA 100.00% 1124 VA Total Est. Demand Current (100% Rated): 15 A

EQP_CONT 4396 VA 100.00% 4396 VA Total Est. Demand: 5520 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 18 A 18 A 12 A

Total Load: 2027 VA 2027 VA 1465 VA

23 0 -- -- -- 24

21 0 -- -- -- 22

19 0 3 30 A (EXTG) SURGE PROTECTION DEVICE 20

17 (EXTG) EMERG. LIGHT 20 A 1 0 0 1 20 A (EXTG) REC - IT WALL 18

15 (EXTG) MIKE'S OFFICE 20 A 1 0 0 -- -- -- 16

13 (EXTG) REC - AIR COMP 30 A 1 0 0 2 40 A (EXTG) REC - WELDER 14

11 (EXTG) LTG - EL-1 20 A 1 0 0 1 20 A (EXTG) SERVER RACK 12

9 (EXTG) LTG - EL-2 30 A 1 0 0 1 20 A (EXTG) FIRE ALARM CONTROL PANEL 10

7 (EXTG) SERVER RACK 20 A 1 0 0 1 20 A (EXTG) FA CHARGER 8

5 SPARE 20 A 1 0 1465 -- -- -- 6

3 -- -- -- 562 1465 -- -- -- 4

1 EQP_NC - BHU-1 - ELEV ROOM 20 A 2 562 1465 3 20 A EQP_C - CU-1 - ON GRADE 2

CKT Circuit Description Trip P A B C P Trip Circuit Description CKT

Mounting: Wires: 4 FCB / MCB Rating: 100 A

Supply From: E Phases: 3 MLO / MCB: MLO

Location: ELEVATOR MACHINE ROOM... Volts: 208Y/120 A.I.C. Rating:

Extg Branch Panel: M

MCB: Main Circuit Breaker

LOCK: Lockable Circuit Breaker

GFI: GFCI Circuit Breaker MLO: Main Lug Only

FCB: Feeder Circuit Breaker MCCB: Molded Case Circuit Breaker FOR EXISTING CIRCUITS '(E)', VERIFY ALL LOADS AND UPDATE PANEL SCHEDULE.

Legend: Notes:

Total Est. Demand Current (80% Rated): 22 A

Continuous Current @ 125%: 0 A

Non-Cont. Current @ 100%: 22 A

Total Est. Demand Current (100% Rated): 22 A

EQP_NON CONT 7758 VA 100.00% 7758 VA Total Est. Demand: 7758 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 21 A 21 A 22 A

Total Load: 2546 VA 2546 VA 2666 VA

15 16

13 14

11 (EXTG) SPARE 20 A 1 0 120 1 20 A EQP_NC - B-1 - SUB GRADE 12

9 -- -- -- 0 0 1 20 A (EXTG) WASHER 10

7 (EXTG) DRYER 30 A 2 0 0 1 20 A (EXTG) CHARGING RECEPTS 8

5 -- -- -- 1273 1273 -- -- -- 6

3 -- -- -- 1273 1273 -- -- -- 4

1 EQP_NC - HWP-1 - SUB GRADE 30 A 3 1273 1273 3 30 A EQP_NC - HWP-2 - SUB GRADE 2

CKT Circuit Description Trip P A B C P Trip Circuit Description CKT

Mounting: SURFACE Wires: 4 FCB / MCB Rating: 100 A

Supply From: Phases: 3 MLO / MCB: MLO

Location: MECH 005 Volts: 208Y/120 A.I.C. Rating:

Extg Branch Panel: N

DATE INITIAL

02/24/2023 jlkirk Highlight jlkirk Highlight

07310034-7-E 00
07310034-7-E 01
07310034-7-E 02
07310034-7-E 03
07310034-7-E001
07310034-7-E002
07310034-7-E003
07310034-7-E101
07310034-7-E102
07310034-7-E401
07310034-7-E501
07310034-7-E502

File details come from the government source that posted it. Updated .