QUESTIONS & ANSWERS REGARDING:

SOLICITATION/REQUEST FOR Quotes NO. 140P3021Q0042

Amendment 0001

Replace HVAC System at Prince William Forest Park

(AMENDMENT 0001)

QUESTIONS RECEIVED AS OF 7/27/2021:

1. In the Artifact Room: Can we disconnect existing duct above ceiling (cap and seal) and patch drywall where diffusers and supply duct currently penetrate the ceiling, or do we have to remove and replace entire drywall ceiling to remove all existing duct work?

ANSWER: The existing duct above the ceiling in the artifact room can be abandoned in place as long as it is completely sealed off to prevent it from becoming a home to pests.

2. Can we reuse existing pad outside to set new outdoor unit?

ANSWER: Yes, the existing pad can be used as long as the NPS can inspect it upon removal of the existing outside unit and there are no serious damages or deficiencies found.

3. Does power have to be demoed back to panel or can it be demoed to nearest junction and made safe?

ANSWER: The power does not need to be demoed back to the panel, it can be terminated in a junction box or disconnect as long as it accessible.

4. Are there specifications for the humidifier beyond what is given in the SOW?

ANSWER: No