Test_Balance Result Baca School (5)_0003.pdf

PDF 16 MB Posted

Attached to
FIRE/SMOKE DAMPERS & ACTUATORS REPAIR, BACA DLO'AY
Solicitation number
140A2321Q0112
Issued by

View the file

Other files

File Type Posted
Sol_140A2321Q0112_Amd_0005.pdf PDF
Sol_140A2321Q0112_Amd_0004.pdf PDF
REVISED SOW_0003.pdf PDF
Sol_140A2321Q0112_Amd_0003.pdf PDF
Sol_140A2321Q0112_Amd_0002.pdf PDF
PHOTO Baca Comm. School Actuator Replacement_0002.jpg JPG image
Sol_140A2321Q0112_Amd_0001.pdf PDF
Sol_140A2321Q0112.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1.

2.

3.

4.

5.

6.

7.

8.

9. Reference Materials Pages 84 - 89

Notes and Comments Pages 25 - 26

Recap and Index Sheet Pages 27 - 28

T&B Report Contents Pages 29 - 83

Equipment List & Calibration Certs. Pages 4 - 18

Balancing Procedures Pages 19 - 22

Abbreviations Pages 23 - 24

LOCATION: Prewitt, NM

General Information Sheet Page 1

Certification Sheets Pages 2 - 3

PROJECT#: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TABLE OF CONTENTS

PROJECT: Baca / DLO'AY AZHI Consolidated Replacement School

190683 3/18/2020

BC, RS

PHONE 202-208-6123 FAX N/A

WEBSITE

E-MAIL

PHONE 505-830-0203 FAX N/A

WEBSITE

E-MAIL

PHONE 505-883-4111 FAX N/A

WEBSITE

E-MAIL

PHONE 918-430-3475 FAX N/A

WEBSITE

E-MAIL

PHONE N/A FAX N/A

WEBSITE

E-MAIL

PHONE 505-881-7070 FAX N/A

WEBSITE

E-MAIL

CAL. DATE

6/24/2019 7/8/2019

4/17/2019 4/23/2019 7/8/2019

4/27/2018 N/A N/A N/A N/A N/A N/A

LOCATION Pillowcrest Road COMPLETION DATE Prewitt, NM 87045 BALANCING CREW

OWNER

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

GENERAL PROJECT INFORMATION

PROJECT Baca / DLO'AY AZHI Consolidated Replacement School PROJECT NUMBER

ARCHITECT

NAME Dyron Murphy Architects

ADDRESS 4505 Montbel Pl NE dyronmurphy.com

Albuquerque, NM 87107 N/A

NAME Bureau of Indian Education

ADDRESS 1849 C Street, NW bie.edu Washington, DC 20240 N/A

CONTRACTORS

GENERAL Cherokee Nation Environmental & Construction

ADDRESS 10838 East Marshall Street, Ste 220 cn-bus.com Tulsa, OK 74116 aaron.hooker@cn-bus.com

MECHANICAL ENGINEER

NAME Bridgers & Paxton Consulting Engineers

ADDRESS 4700-C Montgomery Blvd. NE bpce.com Albuquerque, NM 87109 N/A

CONTROLS Automated Control Systems Inc.

ADDRESS 5801 McLeod NE #B acsionline.com Albuquerque, NM 87109 Info@acsionline.com

MECHANICAL N/A

ADDRESS N/A N/A

N/A N/A

Differential Pressure/Hydrodata Alnor HM675 Tachometer Extech 461920

INSTRUMENTS USED

DESCRIPTION MANUFACTURER MODEL

Velometer/Micromanometer Alnor EBT731

Rotating Vane Anemometer Alnor RVD Balometer Alnor CFM-83

Volt & Amp Meter Extech MA640 Thermometer Alnor HM675

Magnehelic Gauges (in. H20) Dwyer 2000 Series Sound Level Meter Simpson Model 886-2

Pitot Tube Dwyer 18", 24", 36" Inclined Manometer Dwyer 400,200,100

MISCELANEOUS INFORMATION

1. Project altitude to the nearest hundred feet: 6,800 A.S.L.

2. Static Pressure correction factor: 1.29

3. Recorded pressure readings are measured.

Octave Band Filter Simpson Model 898

Extech Instruments Tachometer Range: 0 to 99,999 RPM

Extech Instruments 200A AC Clamp Meter Range: 0 - 200 Amps

0 - 600 Volts AC/DC 0 - 1350 Deg. F

Extech Instruments Thermocouple Range: 32 - 158 Deg. F

Alnor Instruments Thermometer Range: -100 - 250 Deg. F.

Taylor Calibration date: N/A Sling Psychrometer Range: 10% - 100% R.H.

Alnor Instruments Electronic Manometer Range: 50 - 8000 FPM *2

50 - 2500 FPM *3

25 - 2500 CFM *4

0 - 50 " W.C.

32 - 158 Deg. F

Alnor Instruments Electronic Manometer Range: 0.1 - 250 PSI

-100 - 250 Deg. F.

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

Equipment List Used on Project Rotation measurement

Model # 461920 Calibration date: 4/17/2019

Serial # 71922018

Serial # Z373016 Electrical Measurement

Model # EX655 Calibration date: 4/23/2019 Serial # Z373536

Temperature Measurement Model # EX655 Calibration date: 4/23/2019

Serial # Z373536

Model # HM-675 Calibration date: 7/8/2019

Humidity Measurement Model #1330 Serial # N/A

Airflow Measurement Model # EBT731 Calibration date: 6/24/2019

*3 - When used with the Alnor Instruments "VelGrid"

Serial # EBT731925027

Water flow and Differential Pressure Measurement Model # HM675 Calibration date: 7/8/2019

Serial # 71922018

NOTES

*1 - The equipment listed above is for one individual technician's use. When a need for additional technicians is required their equipment is compared to the above referenced equipment and a comparison factor is then applied to it's readings regardless of it's calibration certificate values. These corrected readings are used in the final report for consistency of the information contained with-in the report.

*2 - When used with a pitot tube.

*4 - When Used with the Alnor Instruments "Model EBT731 Flow Hood"

1. Testing, Adjusting and Balancing of Air Handling Unit Systems:

The following procedure, as applicable, is used to verify the proper performance in packaged rooftop unit systems.

A. Preliminary Packaged AHU Check Before Balancing.

Fresh air and return air dampers are checked for travel and closed-off position. If found to be loose and leakage is excessive then they are adjusted for maximum efficiency.

Coils and filters are checked, where possible, to be sure they are not plugged with foreign material and free from excessive dirt build-up.

Sheave alignment and belt tension is checked and they are adjusted as necessary to provide minimum sheave and belt wear. Rotation of fan is also checked for proper rotation and binding of fan blades.

Controls that serve the AHU are verified to operate properly in the manipulation of the unit.

B. Packaged AHU Total Airflow Testing, Adjusting and Balancing

A pitot traverse on the supply air duct is performed to determine the overall total airflow being delivered by the unit and is compared to the total designed airflow. (See below exception)

The fan speed is then set to the airflow level that comes closest to the design airflow and flow is recorded along with voltage and amperage measurements.

The unit is forced into cooling mode at this airflow and the entering air temperature and leaving air temperature and is taken and recorded. Amperage readings are taken and recorded on each compressor and condenser fan at this time also.

The unit is forced into heating mode at this airflow and the entering air temperature and leaving air temperature and is taken and recorded.

A static profile is created by measuring external static pressure before and after each individual component in the unit and is recorded.

Exception: In the case where a pitot duct traverse is not possible the use of an anemometer or Shortridge velgrid is used on either the intake or discharge of the unit itself. When this procedure is not possible then the associated duct system outlet balance sheet is used for total flow.

Note: If a return air fan is present the above steps are repeated for that part of the equipment.

(1)

AIR BALANCING PROCEDURES TO BE USED ON THIS PROJECT

(1)

(2)

(3)

(4)

(2)

(3)

(4)

(5)

2. Testing, Adjusting and Balancing of Exhaust Fans:

A. Preliminary Exhaust Fan Check Before Balancing

Sheave alignment and belt tension is checked and they are adjusted as necessary to provide minimum sheave and belt wear. Rotation of fan is also checked for proper rotation and binding of fan blades.

B. Exhaust Fan Total Airflow Testing, Adjusting and Balancing

Using a pitot traverse on the unit a total air flow reading is taken and compared to design flows. (See exception)

Exhaust fan speeds are adjusted accordingly to bring the actual total airflow within tolerance of design airflows.

The EAP and LAP on the fan are measured and recorded to create a static profile of the unit at this time.

Exception: In the case where a pitot duct traverse is not possible the use of an anemometer or Shortridge velgrid is used on either the intake or discharge of the unit itself. When this procedure is not possible then the associated duct system outlet balance sheet is used for total flow.

3. Proportional Balancing of Ductwork Distribution Systems:

A. Preliminary Ductwork System Check Before Balancing

All ductwork is visually inspected, from the unit to the diffuser/register/grille, for obvious restrictions, leakage or integrity due to poor installation or construction practices.

All balancing and fire/smoke dampers serving the diffusers, registers, grilles and/or branch ducts in the ductwork system are inspected and/or adjusted to their full open position. Any visible obstructions, such as plastic covering, are also removed at this time. This also includes any motorized control dampers such as economizer dampers found in the units serving these ductwork distribution systems.

B. Proportional Balancing of Ductwork Distribution System

Outlets are separated out on a spreadsheet by the equipment and/or terminal device they are being served by such as rooftop units, air handlers, VAV boxes, fan powered boxes and fan coils.

Airflow measurements of all outlets (diffusers, registers, grilles and/or open ended ducts) are taken using a balometer utilizing its direct CFM readings. When the use of a balometer is not possible an anemometer or Shortridge Velgrid is used to obtain the face velocity and airflow is then calculated multiplying the velocity by the area of the outlet to obtain airflow. The deflection blades on grilles and registers are set to be perpendicular to the face of the outlet to ensure even flow for instrument. These readings are then recorded for every outlet.

Outlets are then determined to be either on one main ductline or on a separate branch ductlines with each branch duct line balanced separately from the other branch lines.

(1)

(2)

(3)

AIR BALANCING PROCEDURES TO BE USED ON THIS PROJECT (cont'd)

(1)

(1)

(2)

(1)

(2)

3. Proportional Balancing of Ductwork Distribution Systems (cont'd):

The outlet with the lowest percentage of flow compared to design becomes the "KEY" outlet in which all other outlets are balanced to it. Starting with the next lowest outlet we close off the balancing damper to match the percentage of flow of the "KEY" outlet.

After all outlets are balanced on each branch line the branches are then proportionately balanced with each other on the main duct line. The duct lines (or zones) are then proportionately balanced with each other. The unit is then set as close as possible to obtain the design conditions. Then the outlets on the system are read again and the deflection blades are set to ensure maximum comfort conditions.

The airflow readings of the balanced outlets are then added up to find the total airflow at the outlets which is then recorded.

4. Minimum Outside Air Setting:

Minimum fresh air will be determined by taking the difference of the outside air temperature and return air temper-ature when the differential is 15 degrees or more. This is accomplished by using the following example: If the OA is 50 deg. & the RA is 75 deg. the difference is 25 deg. If the fresh air (FA) required is 3 % then 30% of 25 deg.

is 7.5 deg. Therefore the RA temp. of 75 deg. minus 7.5 deg. = 67.5 deg. of mixed air (MA) temp. for the required 30% of FA. The dampers are then adjusted until the desired MA temp. is achieved. This is expressed in the following equation:

If the temperature difference between the OA & RA is less than 15 deg F then an attempt to measure the fresh air intake in relation to total unit output using conventional means such as a rotating vane anemometer or Shortridge Velgrid.

(1)

AIR BALANCING PROCEDURES TO BE USED ON THIS PROJECT (cont'd)

(4)

(5)

(6)

%OA = (RAT - MAT) X 100 OR MAT = (%OA x OAT) + (%RA x RAT)

(RAT - OAT) 100

3. Proportional Balancing of Heating and Chilled Water Distribution Systems:

A. Preliminary System Check Before Balancing

All piping is visually inspected, from the pump to the element for obvious issues concerning the pipe integrity due to poor installation or construction practices.

All valves and balancing devices serving the elements and/or branch piping in the system are inspected and/or adjusted to their full open position.

B. Proportional Balancing of Water Distribution System

The elements are separated out on a spreadsheet by the equipment and/or device they are being served by such as rooftop units, air handlers, VAV boxes, fan powered boxes and fan coils.

Water flow measurements of all elements are taken using a differential pressure meter and the readings are recorded. This pressure drop is then compared on the factory flow data of the element flow device to determine flow in GPM. When a flow device is not present the use of temperature differential is used on the entering and leaving sides of the airflow and water flow and GPM is calculated by use of BTUH.

Elements are then determined to be either on one main pipe line or on a separate branch pipe line with each branch pipe line balanced separately from the other branch lines.

The element with the lowest percentage of flow compared to design becomes the "KEY" outlet in which all other elements are balanced to it. Starting with the next lowest element we close off the balancing device to match the percentage of flow of the "KEY" element.

After all elements are balanced on each branch line the branches are then proportionately balanced with each other on the main pipe line. The pipe lines (or zones) are then proportionately balanced with each other. The pump is then set as close as possible to obtain the design conditions.

The water flow readings of the balanced elements are then added up to find the total water flow at the outlets which is then recorded.

(4)

(5)

(6)

WATER BALANCING PROCEDURES TO BE USED ON THIS PROJECT

(1)

(2)

(1)

(2)

(3)

ABS- Absolute DENS- Density KWH- Kilowatt per Hour AC- Alternating Current DEWPT- Dew Point Temperature LAT- Leaving Air Temperature ACCU- Air Cooled Condensing Unit DIA- Diameter LB- Pounds AP- Access Panel DIFF- Difference LDBT- Leaving Dry Bulb Temperature ACU- Air Conditioning Unit DIV- Division LF- Linear Feet AD- Access Door, Area Drain DP- Differential Pressure LH- Latent Heat AF- Air Filter DM- Damper Motor LSD- Linear Slot Diffuser AFF- Above Finished Floor DV- Diverting Valve LT- Leaving Temperature AHU- Air Handling Unit E/P- Electric Pneumatic LWBT- Leaving Wet Bulb Temperature ALT- Altitude EA- Exhaust Air LWT- Leaving Water Temperature AMB- Ambient EAT- Entering Air Temperature MAU- Make Up Air Unit AMD- Air Measuring Device ECON- Economizer MAX- Maximum AMP- Ampere ECU- Evaporative Cooling Unit MIN- Minimum ANSI- American Standards National Institute EDBT- Entering Dry Bulb Temperature MPH- Miles per Hour APD- Air Pressure Drop EER- Energy Efficiency Ratio MU- Make Up Water APPROX- Approximate EF- Exhaust Fan MA- Mixed Air AS- Air Separator EFF- Efficiency MBH- 1,000 BTUH ASC- Above Suspended Ceiling EG- Exhaust Grille MD- Motorized Damper ATC- Automatic Temperature Control EL- Elevation MV- Mixing Valve ATM- Atmosphere ENT- Entering MZ- Multizone AVG- Average EQV- Equivalent NA- Not Applicable, No Access BAL- Balance ER- Exhaust Register NC- Noise Criteria, Normally Closed

Barometric Pressure ESP- External Static Pressure NO- Normally Open BFW- Boiler Feed Water ET- Expansion Tank, Entering Temp. NF- No Flow BFV- Butterfly Valve EVAP- Evaporator NG- Not Given BD- Balance Damper EWBT- Entering Wet Bulb Temperature NI- Not Installed BLDG- Building EWT- Entering Water Temperature NL- Not Legible BHP- Brake Horsepower EXCH- Exchanger NP- Not Possible BTU- British Thermal Unit EXH- Exhaust NPSHA- Net Positive Suction Head Avail.

BTUH- British Thermal Units per Hour EXP- Expansion NPSRR- Net Positive Suction Head Req.

BV- Ball Valve FA- Face Area, Free Area NV- No Volume Control Installed BW- Both Ways FCU- Fan Coil Unit OA- Outside Air BYP- Bypass FD- Fire Damper, Floor Drain OBD- Opposed Blade Damper C- Celsius F/SD Fire/Smoke Damper OAF- Outside Air Fan C/C- Cooling Coil F- Fahrenheit OAI- Outside Air Intake CACU- Computer Air Conditioning Unit FLA- Full Load Amps OD- Outside Diameter CAP- Capacity FM- Flow Meter OV- Oval CCW- Counter Clockwise FMD- Flow Measuring Device OZ- Ounce CD- Condensate Drain FLTR- Filter P- Pump CFM- Cubic Feet Per Minute FPM- Feet Per Minute P/E- Pneumatic Electric CH- Chiller FPS- Feet Per Second %- Percent CHW- Chilled Water FT- Feet PCC- Pre-Cool Coil CHWP- Chilled Water Pump GA- Gauge PD- Pressure Drop, Pressure DIFF.

CHWR- Chilled Water Return GAL- Gallon PHC- Preheat Coil CHWS- Chilled Water Supply GPD- Gallons per Day PF- Pre-filter CKT- Circuit GPH- Gallons per Hour Ph- Phase CL- Centerline GPM- Gallons per Minute PSI- Pound Per Square Inch CLG- Cooling HC- Heating Coil, Hose Cabinet PSIA- Pound Per Square Inch Absolute COMPR- Compressor HD- Head PSIG- Pound Per Square Inch Gauge COND- Condenser HEX- Heat Exchanger PTAC- Package Terminal Air Conditioner CT- Cooling Tower HG- Mercury, Heat Gun QTY- Quantity CUH- Cabinet Unit Heater HR- Hour RA- Return Air CW- Clockwise, Condenser Water HVAC- Heating Ventilating Air Conditioning REFR- Refrigeration CWP- Condenser Water Pump HVU- Heating Ventilating Unit RET- Return CWR- Condenser Water Return HP- Horsepower REV- Revolutions CWS- Condenser Water Supply HWC- Heating Water Coil REF- Reference CV- Constant Volume HWCP- Heating Water Circulating Pump RFGT- Refrigerant CVVT- Constant Volume Variable Temp. HWP- Heating Water Pump RH- Relative Humidity DB- Dry Bulb HWR- Heating Water Return RHC- Reheat Coil DBT- Dry Bulb Temperature HWS- Heating Water Supply RPM- Revolutions per Minute dB- Decibel HZ- Hertz RTU- Rooftop Unit DC- Direct Current ID- Inside Diameter RD- Round DCW- Domestic Cold Water IN WC- Inches Water Column RF- Return Fan DDC- Direct Digital Control INSTR- Instrument RG- Return Grille DEG- Degree (Celsius or Fahrenheit) KW- Kilowatt RO- Return Opening

ABBREVIATIONS

RR- Return Register SA- Supply Air SD- Supply Diffuser SF- Safety Factor, Square Feet SL- Sea Level SG- Supply Grille SLD- Slide Damper SP- Static Pressure SPLY- Supply SPEC- Specification SPLD- Splitter Damper SQ- Square SQ.Ft.- Square Feet SR- Supply Register STD- Standard SUP- Supply T & P- Temperature and Pressure TA- Throwaway TD- Temperature Differential TDH- Total Dynamic Head TEMP- Temperature TSP- Total Static Pressure

Total Pressure TSTAT Thermostat U- Heat Transfer Coefficient UH- Unit Heater V- Vent, Volts VAC- Volts Alternating Current VAR- Variable, Variation VAV- Variable Air Volume VD- Volume Damper VEL- Velocity VENT- Vent, Ventilation VERT- Vertical VP- Velocity Pressure VFD- Variable Frequency Drive W- Watt WB- Wet Bulb WBT- Wet Bulb Temperature WC- Water Column WG- Water Gauge WPD- Water Pressure Drop WT- Weight YR- Year Z- Zone

ABBREVIATIONS (cont'd)

PROJECT:

PROJECT#:

LOCATION:

this system. No testing could be done at this time.

This unit has a fire/smoke damper that is closed and not operational which does not allow for any airflow to reach the outlets on

Prewitt, NM

FCU-1 & FCU-3:

These units are not operational and appear to have bad fan motors. No testing could be done at this time.

FCU-2:

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

NOTES AND COMMENTS

Baca / DLO'AY AZHI Consolidated Replacement School 190683

EF-10:

The following systems have fire/smoke dampers that are closed and not operational. This does not allow for a complete balancing of their air distribution systems:

EF-1, 2, 3, 4, 5, 6, 7 & 8

TU-48, 45, 40, 36, 37, 43, 4, 3, 2, 42, 49, 8, 9, 10, 21, 12, 22, 13, 19,

EF-7:

This fan has a cracked and fraying belt which needs to be replaced as soon as possible.

AHU-2:

The fan belts on this unit are cracking and loose. And should eb replaced as soon as possible.

HWP-1, 2 and CHWP-1, 2:

This fan was not installed and no data was possible at time of testing.

This fan has a bad motor which is very hot to the touch and is near failure. Motor should be replaced as soon as possible.

TU-16:

1. This terminal unit has a blank thermostat which needs to be looked at. Unable to verify if it is actually reading room temperature.

EF-3:

FIRE/SMOKE DAMPERS:

The pressure manifild on these pumps was piped incorrectly and does not produce the right pressure drop across the pumps for testing total water flow. Unable to get readings at the time of testing.

TRANSFER AIR DUCT:

There are several transfer air ducts in the ceiling space which have fire/smoke dampers in them that are closed and not operational. This affects room and building pressure along with room temrperatures and indoor air quality.

2. Heating water control valve is not wired or connected to controller and is not operational.

HWP-2:

The 1/2" piping on the pressure manifold is leaking on the heel of one of the elbows, unable to use pressure manifold for testing.

LOCATION:

the minimum flow position could be done at the time of testing.

AHU-1:

The outside air dampers on this unit were not operational at time of testing. It looks like the damper motor and shaft has been modifyied and is no longer able to turn damper.

CH-1:

Due to low ambient conditions at time of testing this unit was not operational. Unable to test at this time.

VAV Terminal Units General Note:

The Allerton DDC controls program has only one point of calibration for airflow which is done at the maximum cooling flow damper position. There is no calbration point for the minimum flow damper position available therefore some minimum flows may show their actual flows at this position more than the plus or minus 10% requirement. No further increase or decrease in flows at

Prewitt, NM

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

NOTES AND COMMENTS

Baca / DLO'AY AZHI Consolidated Replacement School

PROJECT #:

LOCATION:

ROOM EQUIPMENT DESIGN ACTUAL UNITS % PAGE COMMENTS

AHU-1 Equipment 49,000 44,116 CFM 90 29

Air Balance 46,795 44,116 CFM 94 30 - 41 AHU-2 Equipment 23,500 18,670 CFM 79 43

Air Balance 19,600 18,670 CFM 95 44 - 49 FCU-1 Equipment 600 N/A CFM N/A 50 See N&C Page

Air Balance 600 N/A CFM N/A 51 See N&C Page FCU-2 Equipment 900 N/A CFM N/A 52 See N&C Page

Air Balance 900 N/A CFM N/A 53 See N&C Page FCU-3 Equipment 900 N/A CFM N/A 54 See N&C Page

Air Balance 900 N/A CFM N/A 55 See N&C Page MAU-1 Equipment 3,240 3,316 CFM 102 56

Traverse 3,240 3,316 CFM 102 57 ACU-1 Equipment 800 1,389 CFM 174 58 UH-1 Equipment 1,130 N/A CFM N/A 59 See N&C Page EF-1 Equipment 2,040 N/A CFM N/A 60 See N&C Page

Air Balance 2,040 N/A CFM N/A 61 See N&C Page EF-2 Equipment 1,250 N/A CFM N/A 60 See N&C Page

Air Balance 1,220 N/A CFM N/A 61 See N&C Page EF-3 Equipment 1,740 1,471 CFM 85 62

Air Balance 1,480 1,471 CFM 99 63 EF-4 Equipment 790 955 CFM 121 62

Air Balance 990 955 CFM 96 63 EF-5 Equipment 2,580 620 CFM 24 64 See N&C Page

Air Balance 2,700 620 CFM 23 66 See N&C Page EF-6 Equipment 1,050 995 CFM 95 64

Air Balance 1,050 995 CFM 95 67 EF-7 Equipment 1,050 1,127 CFM 107 65

Air Balance 1,050 1,127 CFM 107 68 EF-8 Equipment 1,600 1,584 CFM 99 69

Air Balance 1,600 1,584 CFM 99 70 EF-9 Equipment 1,600 1,630 CFM 102 69

Air Balance 1,600 1,630 CFM 102 71 EF-10 Equipment 1,000 N/A CFM N/A 72 See N&C Page

Air Balance 1,000 N/A CFM N/A N/A See N&C Page KEF-1 Equipment 4,042 3,973 CFM 98 72

Traverse 4,042 3,973 CFM 98 73 KEF-2 Equipment 720 780 CFM 108 74

Traverse 720 780 CFM 108 75 KEF-3 Equipment 500 530 CFM 105 74

Traverse 500 530 CFM 105 76 B-1 Equipment 1,800 2,000 MBH 111 77 B-2 Equipment 1,800 2,000 MBH 111 77

HWP-1 Equipment N/A N/A GPM N/A 78 See N&C Page HWP-2 Equipment N/A N/A GPM N/A 78 See N&C Page

Heating Water Balance 127.57 127.80 GPM 100 79 - 80

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

RECAP AND INDEX SHEETS

Baca / DLO'AY AZHI Consolidated Replacement School

Prewitt, NM

PROJECT #:

LOCATION:

ROOM EQUIPMENT DESIGN ACTUAL UNITS % PAGE COMMENTS

CH-1 Equipment 225 225.0 TON 100 81

CHWP-2 Equipment 340 N/A GPM N/A 82 See N&C Page CHWP-2 Equipment 340 N/A GPM N/A 82 See N&C Page

Chilled Water Balance 327.9 312.9 GPM 95 83

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

RECAP AND INDEX SHEETS

Baca / DLO'AY AZHI Consolidated Replacement School

Prewitt, NM

PROJECT: DATE:

SYSTEM:

DISCONNECTS:

OVERLOAD PROT:

MFG.: HP: 60 VOLTS:

FRAME: 364 - T Ph: 3 S.F.: 1.15 AMPS:

RPM: 1785 PF: 84.9 EFF.: 94.5 TYPE:

MOTOR:

FAN:

BELT: QTY: 5 QTY: 5

MOTOR

VOLTS

MFG.: HP: N/A VOLTS:

FRAME: N/A Ph: N/A S.F.: N/A AMPS:

RPM: N/A PF: N/A EFF.: N/A TYPE:

MOTOR:

FAN:

BELT: QTY: N/A QTY: N/A

MOTOR

N/A

VOLTS

N/A

IN OUT DIFF

-0.193 -0.960 0.77 -0.960 -1.496 0.536 -1.496 1.140 2.636

190683 AREA SERVED: CLR / ADMIN

NAMEPLATE

DATA:

Trane Model #: MCCA100GA1AABC Serial #: K02M97129A

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

AIR HANDLING UNIT DATA SHEET

Baca / DLO'AY AZHI Consolidated Replacement School N/A

DRIVE DATA

Switch on VFD

VFD

AHU-1 LOCATION: Prewitt, NM

SPECIFIED

DATA:

49,000 CFM, 45,800 CFM Actual, 12,000 CFM MIN OSA

1168.2 MBH Total Cool

1168.2 MBH Cool Sens.

SUPPLY FAN MOTOR(S)

AO Smith 230 / 460

140 / 70

SCF

FAN

1080 1805 1080

INITIAL FINAL

5TB94 X Q2 2 3/8 5TB94 X Q2 2 3/8

5B154R X R1 2 15/16 5B154R X R1 2 15/16 B116 B116

MSRD. RPM:

FAN MOTOR

DRIVE DATA

MSRD. ELEC.:

AMPS VOLTS AMPS

55 457 55

RETURN FAN MOTOR(S)

N/A N/A N/A N/A

FAN

N/A N/A N/A

INITIAL FINAL

N/A N/A N/A N/A

N/A N/A

MSRD. RPM:

FAN MOTOR

CHW Coil " W.C.

MSRD. ELEC.:

AMPS VOLTS AMPS

N/A N/A N/A

MEASURED PRESSURES

DESCRIPTION NOTES

Filters " W.C.

FAN: " W.C.

COMMENTS:

Outlet Room Area No. No. Req'd Actual Sq. Ft. CFM FPM FPM % FPM % FPM CFM %

TU-30 (1.45 K-Factor) 1 262 10" rnd. Same 1.00 250 250 502 201 276 110 265 265 106 2 262 10" rnd. Same 1.00 250 250 535 214 270 108 272 272 109 3 262 10" rnd. Same 1.00 250 250 502 201 227 91 255 255 102 4 262 10" rnd. Same 1.00 250 250 471 188 278 111 260 260 104

Max.: 1000 1052 105 Min.: 500 522 104

TU-31 (2.04 K-Factor) 1 267 18 x 8 15 x 5.5 1.00 325 325 468 144 327 101 320 320 98 2 267 18 x 8 15 x 5.5 1.00 325 325 474 146 311 96 311 96 3 267 18 x 8 15 x 5.5 1.00 325 325 463 142 312 96 315 315 97 4 267 18 x 8 15 x 5.5 1.00 325 325 469 144 303 93 315 315 97 5 267 18 x 8 15 x 5.5 1.00 325 325 501 154 365 112 350 350 108 6 267 18 x 8 15 x 5.5 1.00 325 325 453 139 317 98 318 318 98 7 267 18 x 8 15 x 5.5 1.00 325 325 457 141 318 98 322 322 99 8 267 18 x 8 15 x 5.5 1.00 325 325 459 141 317 98 316 316 97

Max.: 2600 2567 99 Min.: 780 895 115 *2

TU-29 (1.18 K-Factor) 1 263 10" rnd. Same 1.00 270 270 454 168 334 124 340 340 126 2 264 6" rnd. Same 1.00 120 120 0 0 0 0 0 0 0 *1 3 265 10" rnd. Same 1.00 220 220 384 175 294 134 285 285 130

Max.: 610 625 102 Min.: 180 202 112 *2

TU-34 (1.45 K-Factor) 1 136 10" rnd. Same 1.00 320 320 502 157 338 107 338 338 107 2 135 10" rnd. Same 1.00 250 250 371 148 252 101 252 252 101 3 134 10" rnd. Same 1.00 290 290 408 141 318 110 318 318 110

Max.: 860 908 106 Min.: 260 311 120 *(2)

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

AIR BALANCE SHEET

Project: Baca / DLO'AY AZHI Consolidated Replacement School

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

TU-39 (1.95 K-Factor) 1 132 10" rnd. Same 1.00 300 300 542 181 286 95 286 286 95 2 132 10" rnd. Same 1.00 300 300 505 168 360 100 300 300 100 3 121 10" rnd. Same 1.00 200 200 371 186 208 104 208 208 104

Max.: 800 794 99 Min.: 240 195 81 *3

TU-40 (1.10 K-Factor) 1 131 8" rnd. Same 1.00 150 150 382 255 382 255 389 389 259 2 122 10" rnd. Same 1.00 275 275 0 0 0 0 0 0 0 *1

Max.: 425 389 92 Min.: 130 137 105

TU-35 (1.80 K-Factor) 1 138 N.G. 10" rnd. 1.00 310 310 477 154 325 105 325 325 105 2 137 N.G. 10" rnd. 1.00 320 320 487 152 324 101 324 324 101 3 Corrid. N.G. 10" rnd. 1.00 275 275 376 137 279 101 279 279 103

Max.: 905 928 103 Min.: 270 260 96

TU-38 (2.25 K-Factor) 1 124 10" rnd. Same 1.00 220 220 330 150 229 104 229 229 104

Max.: 225 229 104 Min.: 70 127 181 *2

TU-36 (1.40 K-Factor) 1 127 10" rnd. Same 1.00 300 300 446 149 293 98 311 311 104 2 127 10" rnd. Same 1.00 300 300 475 158 313 104 317 317 106 3 127 10" rnd. Same 1.00 300 300 491 164 368 123 305 305 102 4 127 10" rnd. Same 1.00 300 300 456 152 327 109 313 313 104 5 126 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1

Max.: 1260 1246 99 Min.: 630 574 93

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

AIR BALANCE SHEET

Project: Baca / DLO'AY AZHI Consolidated Replacement School

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

*3 - No calibration point available for minimum flow in DDC controls program, no further increase possible at time of testing.

TU-28 (1.47 K-Factor) 1 251 10" rnd. Same 1.00 300 300 456 152 342 114 330 330 110 2 251 10" rnd. Same 1.00 300 300 448 149 333 111 325 325 108 3 251 10" rnd. Same 1.00 300 300 424 141 298 99 315 315 105 4 251 10" rnd. Same 1.00 300 300 441 147 314 105 320 320 107 5 251 10" rnd. Same 1.00 300 300 456 152 314 105 328 328 109 6 251 10" rnd. Same 1.00 300 300 461 154 317 106 319 319 106

Max.: 1800 1937 108 Min.: 900 956 106

TU-27 (2.21 K-Factor) 1 253 N.G. 10" rnd. 1.00 270 270 634 235 267 99 267 267 99

Max.: 270 267 99 Min.: 80 110 138 *2

TU-42 (1.09 K-Factor) 1 116 10" rnd. Same 1.00 220 220 0 0 0 0 0 0 0 *1 2 117 6" rnd. Same 1.00 120 120 233 194 176 147 170 170 142 3 118 6" rnd. Same 1.00 80 80 177 221 121 151 119 119 149 4 119 6" rnd. Same 1.00 80 80 163 204 123 154 120 120 150 5 120 8" rnd. Same 1.00 120 120 218 182 166 138 182 182 152 6 115 6" rnd. Same 1.00 140 140 283 202 212 151 200 200 143

Max.: 760 792 104 Min.: 230 265 115 *2

TU-33 (1.32 K-Factor) 1 105 6" rnd. 10" rnd. 1.00 80 80 116 145 92 119 92 92 119 2 100 6" rnd. 10" rnd. 1.00 120 120 0 0 0 0 0 0 0 *1 3 103 10" rnd. 12" rnd. 1.00 325 325 558 172 362 111 362 362 111 4 103 10" rnd. 12" rnd. 1.00 325 325 477 147 372 114 372 372 114

Max.: 850 826 97 Min.: 260 287 110

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

AIR BALANCE SHEET

Project: Baca / DLO'AY AZHI Consolidated Replacement School

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

TU-32 (1.66 K-Factor) 1 104 12" rnd. Same 1.00 330 330 479 145 340 103 340 340 103

Max.: 330 340 103 Min.: 100 119 119 *2

TU-43 (1.21 K-Factor) 1 107 12" rnd. Same 1.00 420 420 465 111 465 111 465 465 111 2 108 6" rnd. Same 1.00 30 30 0 0 0 0 0 0 0 *1

Max.: 450 465 111 Min.: 140 110 79 *3

TU-37 (1.65 K-Factor) 1 123 10" rnd. Same 1.00 300 300 418 139 338 113 330 330 110 2 123 10" rnd. Same 1.00 300 300 399 133 316 105 323 323 108 3 123 10" rnd. Same 1.00 300 300 397 132 314 105 327 327 109 4 123 10" rnd. Same 1.00 300 300 430 143 345 115 336 336 112 5 125 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1

Max.: 1260 1316 104 Min.: 630 732 116 *2

TU-41 (1.82 K-Factor) 1 111 10" rnd. Same 1.00 230 230 343 149 251 109 251 251 109 2 110 10" rnd. Same 1.00 230 230 363 158 262 114 262 262 114 3 109 12" rnd. 10" rnd. 1.00 325 325 547 168 346 106 346 346 106

Max.: 785 859 109 Min.: 240 386 161 *2

TU-12 (1.53 K-Factor) 1 208 8" rnd. Same 1.00 180 180 412 229 314 174 314 314 174 2 208 8" rnd. Same 1.00 180 180 347 193 312 173 312 312 173 3 209 10" rnd. Same 1.00 250 250 0 0 0 0 0 0 0 *1

Max.: 610 626 103 Min.: 310 323 104

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

*3 - No calibration point available for minimum flow in DDC controls program, no further increase possible at time of testing.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

AIR BALANCE SHEET

Project: Baca / DLO'AY AZHI Consolidated Replacement School

TU-26 (1.17 K-Factor) 1 258 12" rnd. Same 1.00 330 330 265 80 318 96 318 318 96 2 258 12" rnd. Same 1.00 330 330 288 87 320 97 320 320 97 3 257 10" rnd. Same 1.00 260 260 239 92 262 101 262 262 101 4 257 10" rnd. Same 1.00 260 260 241 93 271 104 271 271 104

Max.: 1180 1171 99 Min.: 590 543 92

TU-13 (1.73 K-Factor) 1 205 10" rnd. Same 1.00 300 300 411 137 306 102 306 306 102 2 205 10" rnd. Same 1.00 300 300 387 129 305 102 305 102 3 205 10" rnd. Same 1.00 300 300 394 131 313 104 313 313 104 4 205 10" rnd. Same 1.00 300 300 414 138 314 105 314 314 105 5 207 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1

Max.: 1260 1238 98 Min.: 630 655 104

TU-18 (1.64 K-Factor) 1 196 10" rnd. Same 1.00 275 275 318 106 323 108 302 302 110 2 196 10" rnd. Same 1.00 275 275 379 126 289 96 282 282 94 3 196 10" rnd. Same 1.00 275 275 411 137 297 99 286 286 95 4 196 10" rnd. Same 1.00 275 275 387 129 289 96 284 284 95

Max.: 1100 1154 105 Min.: 550 681 124 *2

TU-14 (1.43 K-Factor) 1 204 10" rnd. Same 1.00 300 300 412 137 302 101 302 302 101 2 204 10" rnd. Same 1.00 300 300 429 143 298 99 298 298 99 3 204 10" rnd. Same 1.00 300 300 425 142 305 102 305 305 102 4 204 10" rnd. Same 1.00 300 300 416 139 300 100 300 300 100

Max.: 1200 1205 101 Min.: 600 510 85 *3

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

*3 - No calibration point available for minimum flow in DDC controls program, no further increase possible at time of testing.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-17 (1.47 K-Factor) 1 197 10" rnd. Same 1.00 300 300 389 130 299 100 299 299 100 2 197 10" rnd. Same 1.00 300 300 377 126 305 102 305 305 102 3 197 10" rnd. Same 1.00 300 300 398 133 290 97 290 290 97 4 197 10" rnd. Same 1.00 300 300 370 123 310 103 310 310 103

Max.: 1200 1204 100 Min.: 600 581 97

TU-15 (1.21 K-Factor) 1 201 10" rnd. Same 1.00 300 300 373 124 325 108 325 325 108 2 201 10" rnd. Same 1.00 300 300 319 106 320 107 320 107 3 201 10" rnd. Same 1.00 300 300 276 92 311 104 311 311 104 4 201 10" rnd. Same 1.00 300 300 343 114 326 109 326 326 109 5 203 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1

Max.: 1260 1282 102 Min.: 630 680 108

TU-16 (1.39 K-Factor) 1 200 10" rnd. Same 1.00 300 300 360 120 339 113 339 339 113 2 200 10" rnd. Same 1.00 300 300 303 101 344 115 344 344 115 3 200 10" rnd. Same 1.00 300 300 308 103 320 107 320 320 107 4 200 10" rnd. Same 1.00 300 300 417 139 330 110 330 330 110 5 198 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1 6 Vest. 6" rnd. Same 1.00 110 110 0 0 0 0 0 0 0 *1

Max.: 1370 1333 97 Min.: 690 664 96

TU-25 (1.64 K-Factor) 1 174 10" rnd. Same 1.00 300 300 485 162 329 110 315 315 105 2 174 10" rnd. Same 1.00 300 300 440 147 298 99 309 309 103

Max.: 600 624 104 Min.: 180 265 147 *2

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-24 (1.07 K-Factor) 1 176 8" rnd. Same 1.00 200 200 124 62 198 99 198 198 99 2 176 8" rnd. Same 1.00 200 200 140 70 215 108 215 215 108 3 176 8" rnd. Same 1.00 200 200 158 79 217 109 217 217 109 4 176 8" rnd. Same 1.00 200 200 161 81 220 110 220 220 110

Max.: 800 850 106 Min.: 400 437 109

TU-19 (1.66 K-Factor) 1 191 10" rnd. Same 1.00 215 215 316 147 293 136 285 285 133 2 191 10" rnd. Same 1.00 215 215 355 165 265 123 272 272 127 3 191 10" rnd. Same 1.00 215 215 340 158 280 130 282 131 4 191 10" rnd. Same 1.00 215 215 332 154 269 125 284 284 132 5 191 10" rnd. Same 1.00 215 215 333 154 287 133 286 286 133 6 191 10" rnd. Same 1.00 215 215 348 162 272 127 274 274 127 7 188 6" rnd. Same 1.00 120 120 0 0 0 0 0 0 0 *1 8 190 10" rnd. Same 1.00 240 240 0 0 0 0 0 0 0 *1

Max.: 1650 1683 102 Min.: 830 778 94

TU-23 (1.07 K-Factor) 1 179 8" rnd. Same 1.00 200 200 154 77 239 120 215 215 108 2 179 8" rnd. Same 1.00 200 200 176 84 210 105 212 212 106 3 179 8" rnd. Same 1.00 200 200 154 77 200 100 201 201 101 4 179 8" rnd. Same 1.00 200 200 145 73 191 96 196 196 98 5 177 8" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1 6 181 8" rnd. Same 1.00 180 180 141 78 193 107 190 190 106 7 180 8" rnd. Same 1.00 180 180 134 74 187 104 189 189 105

Max.: 1220 1203 99 Min.: 610 656 108

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-5 (1.54 K-Factor) 1 234 10" rnd. Same 1.00 215 215 303 141 225 105 225 225 105 2 234 10" rnd. Same 1.00 215 215 296 138 221 103 221 221 103 3 234 10" rnd. Same 1.00 215 215 294 138 230 107 230 230 107 4 234 10" rnd. Same 1.00 215 215 300 140 222 103 222 222 103 5 234 10" rnd. Same 1.00 215 215 295 137 229 107 229 229 107 6 234 10" rnd. Same 1.00 215 215 304 141 234 109 234 234 109

Max.: 1290 1361 106 Min.: 650 727 112 *2

TU-1 (1.46 K-Factor) 1 250 10" rnd. Same 1.00 210 210 332 221 221 105 221 221 105 2 250 10" rnd. Same 1.00 210 210 305 210 210 100 210 210 100 3 250 10" rnd. Same 1.00 210 210 304 222 222 106 222 222 106 4 250 10" rnd. Same 1.00 210 210 312 215 215 102 215 215 102

Max.: 840 868 103 Min.: 420 445 106

TU-4 (1.46 K-Factor) 1 239 10" rnd. Same 1.00 250 250 466 186 280 112 280 280 112 2 239 10" rnd. Same 1.00 250 250 399 160 279 112 279 279 112 3 239 10" rnd. Same 1.00 250 250 399 160 282 113 282 282 113 4 239 10" rnd. Same 1.00 250 250 382 153 278 111 278 278 111 5 239 10" rnd. Same 1.00 250 250 415 166 275 110 275 275 110 6 239 10" rnd. Same 1.00 250 250 379 166 270 108 270 270 108 7 235 6" rnd. Same 1.00 120 120 0 0 0 0 0 0 0 *1

Max.: 1620 1664 103 Min.: 810 795 98

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-3 (1.42 K-Factor) 1 241 10" rnd. Same 1.00 250 250 393 157 304 122 304 304 122 2 241 10" rnd. Same 1.00 250 250 305 122 312 125 312 312 125 3 241 10" rnd. Same 1.00 250 250 411 165 319 128 319 319 128 4 241 10" rnd. Same 1.00 250 250 401 160 300 120 300 300 120 5 242 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1 6 Vest. 6" rnd. Same 1.00 10 10 0 0 0 0 0 0 0 *1

Max.: 1170 1235 106 Min.: 590 630 107

TU-2 (1.55 K-Factor) 1 245 10" rnd. Same 1.00 210 210 395 188 305 145 305 305 145 2 245 10" rnd. Same 1.00 210 210 393 187 301 143 301 301 143 3 245 10" rnd. Same 1.00 210 210 341 162 289 138 289 289 138 4 245 10" rnd. Same 1.00 210 210 349 161 290 138 290 290 138 5 Corrid. 10" rnd. Same 1.00 250 250 0 0 0 0 0 0 0 *1 6 246 6" rnd. Same 1.00 60 60 114 190 87 145 87 87 145

Max.: 1150 1272 110 Min.: 580 595 103

TU-6 (1.51 K-Factor) 1 229 10" rnd. Same 1.00 215 215 357 166 277 129 260 260 121 2 229 10" rnd. Same 1.00 215 215 363 169 270 126 268 268 125 3 229 10" rnd. Same 1.00 215 215 375 174 286 133 275 275 128 4 229 10" rnd. Same 1.00 215 215 383 178 287 133 281 281 131 5 229 10" rnd. Same 1.00 215 215 359 167 256 119 264 264 123 6 229 10" rnd. Same 1.00 215 215 359 167 255 119 261 261 121 7 330 10" rnd. Same 1.00 250 250 0 0 0 0 0 0 0 *1

Max.: 1540 1609 106 Min.: 770 845 110

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-7 (1.32 K-Factor) 1 225 10" rnd. Same 1.00 300 300 426 142 313 104 298 298 99 2 225 10" rnd. Same 1.00 300 300 447 149 333 111 295 295 98 3 225 10" rnd. Same 1.00 300 300 362 121 284 95 311 311 104 4 225 10" rnd. Same 1.00 300 300 437 146 301 100 301 301 100 5 226 8" rnd. Same 1.00 180 180 251 139 171 95 180 180 100 6 227 8" rnd. Same 1.00 180 180 248 138 177 98 179 179 98

Max.: 1560 1566 101 Min.: 780 745 96

TU-8 (1.75 K-Factor) 1 222 10" rnd. Same 1.00 300 300 353 118 374 125 336 336 112 2 222 10" rnd. Same 1.00 300 300 349 116 369 123 335 335 112 3 222 10" rnd. Same 1.00 300 300 387 129 367 122 321 321 107 4 222 10" rnd. Same 1.00 300 300 354 118 362 121 331 331 110 5 224 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1

Max.: 1260 1323 105 Min.: 630 645 102

TU-9 (1.58 K-Factor) 1 221 10" rnd. Same 1.00 300 300 349 116 370 123 345 345 115 2 221 10" rnd. Same 1.00 300 300 382 127 341 114 330 330 110 3 221 10" rnd. Same 1.00 300 300 358 119 328 109 335 335 112 4 221 10" rnd. Same 1.00 300 300 375 125 328 109 340 340 113 5 Vest. 6" rnd. Same 1.00 110 110 0 0 0 0 0 0 0 *1

Max.: 1310 1350 103 Min.: 660 726 110

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-10 (1.68 K-Factor) 1 218 10" rnd. Same 1.00 250 250 370 148 359 144 280 280 112 2 218 10" rnd. Same 1.00 250 250 400 160 379 152 290 290 116 3 218 10" rnd. Same 1.00 250 250 318 127 340 136 265 265 106 4 218 10" rnd. Same 1.00 250 250 430 172 390 156 270 270 108 5 270 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1

Max.: 1060 1105 104 Min.: 530 625 118 *2

TU-11 (1.38 K-Factor) 1 215 10" rnd. Same 1.00 275 275 416 151 310 113 270 98 2 215 10" rnd. Same 1.00 275 275 443 161 241 88 250 250 91 3 215 10" rnd. Same 1.00 275 275 447 163 285 104 265 265 96 4 215 10" rnd. Same 1.00 275 275 441 160 286 104 268 268 97 5 216 10" rnd. Same 1.00 230 230 346 126 232 84 260 260 95 6 211 6" rnd. Same 1.00 120 120 167 139 101 84 109 109 91

Max.: 1450 1422 98 Min.: 730 690 95

TU-20 (1.35 K-Factor) 1 187 10" rnd. Same 1.00 300 300 414 138 387 129 387 387 129 2 187 10" rnd. Same 1.00 300 300 396 132 373 124 373 373 124 3 187 10" rnd. Same 1.00 300 300 365 122 374 125 374 374 125 4 187 10" rnd. Same 1.00 300 300 383 128 360 120 360 360 120 5 Corrid. 10" rnd. Same 1.00 250 250 0 0 0 0 0 0 0 *1

Max.: 1450 1495 103 Min.: 730 795 109

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-21 (1.56 K-Factor) 1 184 10" rnd. Same 1.00 300 300 420 140 324 108 324 324 108 2 184 10" rnd. Same 1.00 300 300 391 130 305 102 305 305 102 3 184 10" rnd. Same 1.00 300 300 365 122 310 103 310 310 103 4 184 10" rnd. Same 1.00 300 300 372 124 315 105 315 315 105 5 186 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1

Max.: 1260 1254 98 Min.: 630 630 100

TU-22 (1.71 K-Factor) 1 183 10" rnd. Same 1.00 225 225 425 189 337 150 289 128 2 183 10" rnd. Same 1.00 225 225 399 177 321 143 282 282 125 3 183 10" rnd. Same 1.00 225 225 394 175 330 147 284 284 126 4 183 10" rnd. Same 1.00 225 225 423 188 319 142 291 291 129 5 270 6" rnd. Same 1.00 60 60 0 0 0 0 0 0 0 *1 6 Vest. 6" rnd. Same 1.00 110 110 0 0 0 0 0 0 0 *1

Max.: 1070 1146 107 Min.: 620 725 112 *2

AHU-1 Totals: 46,795 44,116 99

System: AHU - 1 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Fire / Smoke Damper closed.

*2 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

Date Time ASL

29 X 98

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 246 299 267 309 437 552 571 554 518 467

2 270 393 437 309 445 497 445 420 293 462

3 484 502 472 350 376 499 520 529 444 577

FPM @ S.P.: "W.C.

FPM @ S.P.: "W.C.

CFM or 57 CFM or 102

Project # 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

DUCT TRAVERSE PITOT SHEET (Square Ductwork)

Project Baca / DLO'AY AZHI Consolidated Replacement School

System AHU-2 OSA

Station # N/A N/A N/A Altitude Ft. 6,827

Horizontal Spacing N/A N/A

Duct Size Duct Area: 19.70 Sq. Ft. Required CFM 8,400

Test reading spacing From edge of duct Between readings Required Velocity 427

°F

Vertical Spacing N/A N/A

Readings

AVERAGE MEASURED VELOCITY

INITIAL: 242 N/A TEMPERATURE: 55.0

FINAL: 8628 % OF DESIGN @ 59.9 Hz

FINAL: 438 N/A TEMPERATURE: 55.0 °F

MEASURED VOLUME

INITIAL: 4767 % OF DESIGN

COMMENTS

SYSTEM:

DISCONNECTS:

OVERLOAD PROT:

MFG.: HP: 25 VOLTS:

FRAME: 284 T Ph: 3 S.F.: 1.15 AMPS:

RPM: 1740 PF: 84.1 EFF.: 91.7 TYPE:

MOTOR:

FAN:

BELT: QTY: 3 QTY: 3

MOTOR

VOLTS

MFG.: HP: N/A VOLTS:

FRAME: N/A Ph: N/A S.F.: N/A AMPS:

RPM: N/A PF: N/A EFF.: N/A TYPE:

MOTOR:

FAN:

BELT: QTY: N/A QTY: N/A

MOTOR

N/A

VOLTS

N/A

IN OUT DIFF

-0.167 -1.056 0.940 -1.056 -1.088 0.032 -1.088 -1.340 0.252 -1.340 1.440 2.780

190683 AREA SERVED: GYM / Café

NAMEPLATE

DATA:

Trane Model #: MCCBO5OUAOCOUA Serial #: K02M98849A

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

AIR HANDLING UNIT DATA SHEET

Baca / DLO'AY AZHI Consolidated Replacement School N/A

DRIVE DATA

Switch on VFD

VFD

AHU-2 LOCATION: Prewitt, NM

SPECIFIED

DATA:

23,500 CFM, 19,600 CFM Actual, 8,400 CFM MIN OSA 396MBH Total Heat 280 MBH Cool Total, 580 MBH Cool Sens.

SUPPLY FAN MOTOR(S)

AO Smith 230 / 460

60.6 / 30.3

MOGB

FAN

1057 1761 1057

INITIAL FINAL

3B5V66 X B 1 7/8 3B5V66 X B 1 7/8

3B5V86 X B 2 7/16 3B5V86 X B 2 7/16

BX73 BX73

MSRD. RPM:

FAN MOTOR

DRIVE DATA

MSRD. ELEC.:

AMPS VOLTS AMPS

17.1 402 17.1

RETURN FAN MOTOR(S)

N/A N/A N/A N/A

FAN

N/A N/A N/A

INITIAL FINAL

N/A N/A N/A N/A

N/A N/A

MSRD. RPM:

FAN MOTOR

HW Coil " W.C.

MSRD. ELEC.:

AMPS VOLTS AMPS

N/A N/A N/A

MEASURED PRESSURES

DESCRIPTION NOTES

Filters " W.C.

CHW Coil " W.C.

Fan " W.C.

TU-48 (1.50 K-Factor) 1 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1 2 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1 3 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1 4 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1 5 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1 6 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1 7 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1 8 149 16 x14 Same 1.56 690 442 415 94 415 94 415 648 94 *1

Max.: 5520 5184 94 Min.: 3310 3210 92

TU-50 (1.75 K-Factor) 1 155 10" rnd. Same 1.00 250 250 309 124 252 101 252 252 101 2 154 10" rnd. Same 1.00 220 220 187 85 227 103 227 227 103 3 153 10" rnd. Same 1.00 220 220 280 127 219 100 219 219 100 4 152 8" rnd. Same 1.00 160 160 223 139 159 99 159 159 99

Max.: 850 857 101 Min.: 260 255 98

TU-52 (1.85 K-Factor) 1 163 8" rnd. Same 1.00 210 210 237 113 222 106 222 222 106 2 163 8" rnd. Same 1.00 210 210 235 112 213 101 213 213 101 3 163 8" rnd. Same 1.00 210 210 262 125 227 108 227 227 108 4 163 8" rnd. Same 1.00 210 210 267 127 221 105 221 221 105 5 169 12" rnd. Same 1.00 400 400 503 126 416 104 416 416 104

Max.: 1240 1302 105 Min.: 370 362 98

System: AHU - 2 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Was unable to get manlift on finished gymnasium floor. Unit was measured for total flow and this flow was divided equally among the outlets serving this unit for reference only. Outlets were verified to have their OBD's in the full open position.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-51 (1.95 K-Factor) 1 161 6 x 6 Same 1.00 100 100 30 30 101 100 101 101 100 2 160 8" rnd. Same 1.00 200 200 90 45 205 103 205 205 103 3 159 12" rnd. Same 1.00 400 400 214 54 417 104 417 417 104 4 159 12" rnd. Same 1.00 400 400 214 54 412 103 412 412 103

Max.: 1100 1135 103 Min.: 330 303 92

TU-53 (1.65 K-Factor) 1 162 12" rnd. Same 1.00 360 360 286 79 341 95 341 341 95 2 162 12" rnd. Same 1.00 360 360 275 76 342 95 342 95 3 162 12" rnd. Same 1.00 360 360 297 83 362 101 362 362 101 4 162 12" rnd. Same 1.00 360 360 289 80 335 93 335 335 93 5 162 12" rnd. Same 1.00 360 360 289 80 333 93 333 333 93 6 162 12" rnd. Same 1.00 360 360 291 81 325 90 325 325 90 7 162 12" rnd. Same 1.00 360 360 285 79 358 99 358 358 99 8 162 12" rnd. Same 1.00 360 360 280 78 347 93 347 347 93

Max.: 2880 2743 95 Min.: 1740 1602 92

TU-46 (1.25 K-Factor) 1 167 10" rnd. Same 1.00 300 300 183 61 194 65 297 297 99

Max.: 300 297 99 Min.: 90 117 130 *1

TU-44 (3.75 K-Factor) 1 147 10 x 6 Same 1.00 200 200 361 181 215 108 215 215 108 2 147 10 x 6 Same 1.00 200 200 371 186 220 110 220 220 110

Max.: 400 435 109 Min.: 120 103 86 *2

System: AHU - 2 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - No calibration point available for minimum flow in DDC controls program, no further decrease possible at time of testing.

*2 - No calibration point available for minimum flow in DDC controls program, no further increase possible at time of testing.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

TU-49 (2.50 K-Factor) 1 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1 2 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1 3 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1 4 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1 5 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1 6 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1 7 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1 8 148 14 x 12 Same 1.17 690 590 558 95 558 95 558 653 95 *1

Max.: 5520 5224 95 Min.: 3310 3385 102

TU-45 (1.70 K-Factor) 1 145 8" rnd. Same 1.00 200 200 233 117 214 107 214 214 107 2 145 8" rnd. Same 1.00 200 200 228 114 220 110 220 220 110 3 145 8" rnd. Same 1.00 200 200 208 104 212 106 212 212 106 4 145 8" rnd. Same 1.00 200 200 209 105 210 105 210 210 105 5 146 6" rnd. Same 1.00 120 120 127 106 130 108 130 130 108 6 143 6" rnd. Same 1.00 80 80 106 118 90 113 90 90 113 7 142 6" rnd. Same 1.00 90 90 0 0 0 0 0 0 0 *2 8 144 8" rnd. Same 1.00 145 145 178 123 155 107 155 155 107 9 140 6" rnd. Same 1.00 80 80 97 121 88 110 88 88 110

10 141 10" rnd. Same 1.00 240 240 245 102 255 104 255 255 104

Max.: 1555 1574 101 Min.: 780 822 105

TU-47 (2.10 K-Factor) 1 165 8" rnd. Same 1.00 200 200 154 77 201 101 201 201 101

Max.: 200 201 101 Min.: 60 65 108

AHU-2 Totals: 19,565 18,670 95

System: AHU - 2 Terminal Size Required Initial Balanced Final Cmnts.

Comments:

*1 - Was unable to get manlift on finished gymnasium floor. Unit was measured for total flow and this flow was divided equally among the outlets serving this unit for reference only. Outlets were verified to have their OBD's in the full open position.

*2 - Fire / Smoke Damper closed.

Project #: 190683

NN--DDeemmaanndd TTeesstt aanndd BBaallaannccee,, LLLLCC

22 X 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 1795 1675 1700 1745 1758

2 1722 1705 1692 1776 1585

3 1905 1002 1731 1821 1674

4 2022 1972 1932 1948 1760

5 2076 2087 2020 1984 1698

6 2118 2119 2077 1997 1785

7 2108 2117 2070 1987 1954

8 1705 1705 2170 2065 1958

FPM @ S.P.: "W.C.

FPM @ S.P.: "W.C.

CFM or 20 CFM or 94

COMMENTS

FINAL: 5184 % OF DESIGN

FINAL: 1885 N/A TEMPERATURE: 70.0 °F

MEASURED VOLUME

INITIAL: 1111 % OF DESIGN

°F

Vertical Spacing 1.375 2.75

Readings

AVERAGE MEASURED VELOCITY

INITIAL: 404 N/A TEMPERATURE: 70.0

Horizontal Spacing 1.8 3.6

Duct Size Duct Area: 2.75 Sq. Ft. Required CFM 5,520

Test reading spacing From edge of duct Between readings Required Velocity…