This solicitation is for the design and construction of a new helipad and associated facilities for the Payson Ranger District. Key requirements include earthwork, utilities, asphalt/paving, concrete, carpentry, thermal and moisture protection, electrical, HVAC, plumbing, telecommunications, access control, and lightning protection systems. The project scope encompasses all labor, materials, equipment and supplies to deliver fully functional helipad facilities. Specifics outlined in the Agency Specific Requirements attachment include space needs, adjacencies, general building standards, site details such as multiple helipads and parking, and technical requirements for electrical, IT, security and communications systems. The Department of Agriculture Forest Service R3-Southwestern Region is the contracting agency.
View the file
Other files for this federal contract opportunity
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation No. 12837120R0008 Payson Helibase Design/Build
Agency Specific Requirements/Design Prospectus USDA Forest Service
Tonto National Forest Payson Helibase Payson, AZ
The Agency Specific Requirements (ASRs) do not reduce the minimum requirements contained within the Lease. These ASRs provide specific agency requirements, which may be complementary, more specific, or more stringent than those of the Lease minimum requirements. If conflicts exist between the Lease and ASR, the ASR’s shall take precedence.
Tonto National Forest Payson Helibase 2 | P a g e
1. ROOM SCHEDULE AND DETAILS
1.01 ROOM SCHEDULE
1.02 SPACE DETAILS
2. ADJACENCIES
2.01 DESIGN ADJACENCIES
3. GENERAL REQUIREMENTS
3.01 SECURITY
3.02 ACCESS CONTROL
3.03 INTRUSION DETECTION SYSTEM
3.04 INFORMATION TECHNOLOGY
3.05 PA SYSTEM
3.06 ACOUSTICS
3.07 WINDOWS
3.08 WINDOW TREATMENTS
3.09 ELECTRICAL
3.10 PLUMBING
3.11 HVAC SYSTEMS
4. SITE REQUIREMENTS
4.01 HELIPADS:
4.02 PARKING
4.03 OTHER SITE REQUIREMENTS
Tonto National Forest Payson Helibase 3 | P a g e
1. ROOM SCHEDULE AND DETAILS
1.01 ROOM SCHEDULE
Space # or
People Size-sf
Flooring Carpet Tiles (CT), Sealed Concrete(SC)
Addl HVAC Reqts. (See
Details)
Office-FAO 1 100 (CT)/(SC) No
Office – Helicopter Manager 1 100 (CT)/(SC) No
Office – Permanents (8s) 2 120 CT/SC No
Office – Perm Seasonals (7s) 2 100 CT/SC No
Office – Temp & PS (5s) 10 350 CT/SC No
Pilots Lounge 1 260 CT No
Operations Room 1 390 CT/SC No
Conference Room 1 450 CT Yes
Exercise Room 1 500 Rubber Exercise Flooring
Yes
Break Room 1 200 SC As needed
Laundry Area 1 80 SC As needed
Crew Ready Room 1 750 SC No
Restrooms 2 set As needed Ceramic Tile As needed
Showers 5 As needed Ceramic Tile Yes
IT Room 1 100 Anti-Static Yes
Mechanical Room 1 As needed SC As needed
Janitor Room 1 As needed SC
Mail Room 1 100 SC No
Vehicle Bay 1 set 1250 SC No
1.02 SPACE DETAILS
A. Office Space:
1. FAO/Helicopter Manager – Shall be a closed office space area so that confidential conversations and performance evaluations can be conducted in this space as needed.
2. Permanents (8’s) – This area can be a stand-alone area sufficient for system furniture for 2 workspaces. This area can also be incorporated into the Permanent Seasonal and Temporary work space areas.
3. Permanent Seasonals (7’s) - This area can be a stand-alone area sufficient for system furniture for 2 workspaces. This area can also be incorporated into the Permanents and Temporary work space areas.
4. Temporary & Permanent Seasonals (5’s) - This area can be a stand-alone area sufficient for approximately 4 shared workstations and a gathering area for 10 people. This area can also be incorporated into the Permanents and Permanent Seasonal work space areas.
B. Pilots Lounge:
1. Electrical, Data, Wireless, Voice, Fax – Provide a telecommunications/electrical outlet every 8 linear feet along the wall.
2. Space shall be equipped with a minimum of 4 linear feet of countertop with integral backsplash/base cabinets with concealed hinges and staple pulls. Include a small stainless steel sink and all associated plumbing. Include space for one small refrigerator, one microwave
Tonto National Forest Payson Helibase 4 | P a g e oven and coffee maker. Approximately 4 feet of wall cabinets shall be provided above base cabinets.
3. Provide one dedicated duplex electrical receptacle for refrigerator. Provide dedicated electrical receptacles for microwave oven above the counter. Provide an additional duplex electrical receptacles above the counter (GFI as required by code).
4. Should be located away from busy activity areas and noise.
5. This space is required to be a quiet area where pilots can get away and rest as needed to meet work/rest ratios. Provide special acoustics for noise reduction in this area.
C. Operations Room:
1. Space shall be located to provide clear, 180 degree unobstructed views of helipads and aircraft parking. Aircraft ramp viewing area window shall be a minimum of six feet high, and extend outward from the plane of the building wall approximately three feet (consider a very large bay window concept). This room will require a minimum of 15 feet of clear horizontal wall space for maps and status boards. On walls with windows, install a continuous 24 inch deep countertop at desk height and under windows with punch outs for cords to come through at the back of the desktop.
2. Electrical, Data, Wireless, Voice, Fax– Provide a telecommunications/electrical outlet every 8 linear feet along the wall and one or two floor boxes central in the room.
3. Provide space for two big screen TV’s (~52 inches) to be mounted on the walls. Provide electrical and data outlets near the TV mounting locations and provide additional wall blocking as needed for mounting.
D. Conference Room:
1. Provide a separate entry for each section of the room. Each door shall have a window lite for visibility through the door.
2. Provide separately regulated HVAC zones for the conference room. Ceiling exhaust fans capable of exchanging air as required by code and must be without objectionable noise.
3. Provide a locking storage area within the conference room for storage of tables, chairs, flip charts and other training material. Use double doors to access storage.
4. Dimmer switches shall be two or three way as required to meet operation specifications.
5. A floor grid layout of 8 ft x 8 ft max. for the telecommunications/electrical shall be required.
Provide a combination outlet box with power supply and telecommunications outlet/connector that will allow the use of 2-4 computers, or 2 phones and 2 computers from each box. Provide recessed floor power/data outlet boxes. Ensure data ports can be wired for FS systems.
Provide a minimum of 8 recessed floor boxes.
6. Provide a telecommunications/electrical outlet every 8 linear feet along the wall. Provide additional groupings of two outlets by each side of a white board or screen location on the walls.
7. Provide 2 data ports placed either high on the wall or in the ceiling. These will be used for wireless access points.
8. One magnetic white marker board shall be located at one end of the conference room.
Approximate size of the board shall be 48 inches high by 96 inches wide.
9. An extruded aluminum and cork tack strip shall run around the room at 4 foot and 6 foot above the finished floor. A chair rail shall run continuous around the room at 30 inches above the finished floor.
10. Provide a projector screen with automated operation controls in the room. Screen shall be contained above white board or tack strip when not in use. Provide support structure and
Tonto National Forest Payson Helibase 5 | P a g e video/data and power wiring to ceiling space in the center of the room section with the projection screen. Provide video projection system that includes stereo sound components, amplifiers, ceiling mounted speakers, volume controls, and wiring that connects to computers and have at least 2 zones. Provide HDMI inputs on wall jacks to feed AV projection and sound system for connection to Government laptop computers.
11. This space shall be located near the break room and rest rooms.
E. Exercise Room:
1. Locate near the toilet rooms and shower rooms.
2. Electrical: Place duplex outlets spaced every 4 linear feet along walls for electrical equipment (treadmills, ellipticals, etc).
3. HVAC – Independent HVAC zone on thermostat in this room and provide means to ensure negative pressure for this room to avoid odors from escaping the room. Exhaust directly to the outside.
4. Provide for separate outside access with sufficient space to be able to extend the workout space in good weather. Access to this area by roll –up door or double doors to allow equipment to be moved in and out. A hard (concrete), covered surface would be best to accommodate the needs of the exercise space.
5. Provide additional wall framing and blocking to accommodate wall-mounted exercise equipment.
F. Break Room:
1. Space shall be equipped with a full kitchen including cabinets, counter space, stove/range, garbage and recycle space, double basin stainless steel sink, instant hot water tap and all associated plumbing meeting ABA access standards. Include space for 2 full size refrigerators, 1 countertop microwave or one under-cabinet mounted microwave; and provide space for 1 coffee maker and 1 toaster. Ensure adequate counter space for prep, dish washing and the countertop appliances.
2. Provide floor space for 2-4 tables that seat 4 people with chairs to accommodate the space.
3. Provide a covered patio type space adjacent to the Break Room for an outdoor eating area in good weather and when the crew is fully staffed.
4. Electrical, Data, Voice, Wireless – Provide three duplex electrical receptacles and one wall combination data/voice jack near the seating area. Provide two dedicated duplex electrical receptacles for refrigerators. Provide two dedicated electrical receptacles for microwave ovens above the counter. Provide two additional duplex electrical receptacles above the counter (GFI as required by code).
5. HVAC (Only if enclosed room) – Independent HVAC zone on thermostat in this room and provide means to ensure negative pressure for this room to avoid odors from escaping this room. Provide filters to remove odors from any air being mixed back into the supply air for the remainder of the building or exhaust directly to the outside.
G. Laundry Area:
1. Space adequate to provide room for 1 Washer and 1 Dryer residential size that will be government provided.
2. Space shall include cabinets and shelving for storage of laundry supplies and over flow storage as space allows.
3. Provide power outlets as needed for the appliances and space.
4. Ventilate the dryer directly outside.
Tonto National Forest Payson Helibase 6 | P a g e
H. Crew Ready Room:
1. Room shall have a bay door opening onto the tarmac to allow for transfer of equipment and gear on and off of the helicopters. This bay door shall also be accessible by vehicles to allow for packing of equipment and gear into a vehicle and off and for supply loading and off-loading.
Three of the walls shall be left open for future installation of government-provided heavy duty shelves and storage lockers.
2. Room shall provide space for 16 lockers provided by government, each approximately 2-1/2’ D x 3’ W x 7’ H in size.
3. The idea for this room is to allow for both a crew ready room area where the crew can store their gear, change into their full gear and coordinate their individual preparation for flights as well as an area where they can have tables and be able to refurbish initial attack gear.
4. Room shall provide space for a large assembly table (min table size 5x8 with room around all sides to work) that will be used to assemble initial attack gear in preparation for assignments.
5. Provide electrical outlets as per code with additional outlets sufficient to handle a 220 air compressor.
I. Covered Outdoor Maintenance Area:
1. This space shall include room for a maintenance bench, tools, spare chains and storage of up to 20 chain saws. This area can and is best if outside of the main office building. A shed for equipment storage would be best and a covered area for the maintenance bench could be adjacent to the office building.
2. If space is enclosed it shall be equipped with a ventilation system capable of exhausting the fumes from running chain saws and storage of chain saws. Meet all applicable fire codes.
3. Provide sufficient 220 & 110 electrical outlets to accommodate electrical tools, grinders, air compressor and maintenance equipment.
4. Provide an air system that would allow compressed air to be utilized in specific areas throughout the maintenance area.
5. Room shall provide space for a tool maintenance area including a work bench and storage area for tools to be worked on.
6. This space shall be concrete and measure approximately 30 ft x 40 ft.
J. Vehicle Bay/Fire Cache
1. Room shall provide space for Cache storage of tools, supplies, clothing, safety equipment, hose & fittings, food supplies, pumps, medical supplies, sleeping gear, tarps, radios, batteries, etc.
2. Room shall include a utility sink, space for an ice machine, and a floor drain to accommodate the ice machine and in case of spills or splashes around the utility sink. The ice machine will require an electrical outlet and water supply.
3. This area needs to be accessible to pull supplies and equipment out of the Cache storage area.
4. This room shall function as a big open space with specific storage areas strategically placed around the room. The main open assembly area will be multi-functional being used as a crew assembly area prior to departure, vehicle supply area, supply off-loading area, etc.
Tonto National Forest Payson Helibase 7 | P a g e
5. Provide electrical outlets as per code with additional outlets sufficient to handle a 220 air compressor, tool grinder, saw chain grinder, and miscellaneous electrical hand tools. Provide ventilation hoods as needed for grinder areas.
6. A set of overhead bay doors measuring approximately 14 ft wide x 14 ft tall that would allow vehicles to drive straight through the vehicle bay.
7. Provide an air system that would allow compressed air to be utilized in specific areas throughout the Bay/Cache.
8. This area could include a mezzanine for additional storage space above vehicle bay as to best accommodate the space.
K. Employee Restrooms and Showers:
1. Shall have one set for each gender, and the restroom portion shall be sized for a minimum of 16 people. It is desirable to have at a minimum 3 water closets and 2 urinals in the men’s restroom space and 2 water closets in the women’s restroom space. Size and accommodate restrooms for 70% male, 30% female building user population.
2. 5 Shower stalls shall be available for the crew.
a. Configure 2 stalls as individual unisex rooms with at least one having fully accessible features. Provide lighting, exhaust fans, privacy locks on doors, towel hooks, a wall mounted bench, and floor drain outside the shower stalls. Provide space for Government furnished double-tiered lockers in each room. Individual lockers are estimated to be 12” wide x 12” deep x 36” high.
b. Configure 2 shower stalls in, or immediately adjacent to and accessible from within, the men’s restroom,
c. Configure one shower stall in, or immediately adjacent to the women’s restroom.
3. Exhaust fans for the showers shall operate on motion sensors/lights. Fan to turn on with space occupancy followed by a 30 minute delay off. Do not return air from restrooms and showers to the building air supply.
4. Provide space for Government furnished double-tiered lockers in each restroom. Individual lockers are estimated to be 12” wide x 12” deep x 36” high.
5. Provide GFI duplex receptacles throughout the restroom at code-required spacing. Provide one duplex GFI receptacle at each sink.
L. IT Room:
1. Refer to IT and Electrical Design Guidelines regarding IT requirements
2. Wall construction must be ¾” fireproof plywood on all walls and extend from structural floor to structural ceiling. Solid-core wood doors and walls must meet all required fire ratings. Flooring materials shall be static resistant and slip resistant as defined by Design Guidelines. Ceilings may be hard surfaced and painted or acoustic tile grid. Isolated Ground (IG) electrical system(s) is required for all IT spaces.
3. This space shall be secured through Access Control Credential ID/proximity card reader and a high security lockset separately keyed from all other building doors. This door lock shall not be part of the master key system
4. This room shall contain the following components:
a. IT racks, patch panels for data and phone network, and Government owned network equipment, routers, network switches, and radio equipment.
b. IT room power panel dedicated to only equipment in this room.
Tonto National Forest Payson Helibase 8 | P a g e
c. IT room UPS and bypass switch and backup batteries for 30 minutes of run time.
d. Intrusion detection panel power from IT room power panel.
e. Phone system equipment
f. Access control panel powered from IT room power panels.
g. PA system powered from IT room power panel.
h. EPO (Emergency power off shutdown panel) shut down panel to shut down UPS, room HVAC equipment, high temperature shutdowns, and cross zoned smoke detectors.
5. The IT room shall have a separate zone split system cooling system sized for the total heat load of the room equipment and UPS. This system shall be tied into the IT room EPO shut down panel. Refer to IT and Electrical Design Guidelines and EPO panel specifications for details of construction.
M. Janitor Room:
1. Provide a storage space with mop sink and shelving to hold restroom supplies such as toilet paper, paper towels, soap, cleaners, vacuum cleaner, dusters, etc.
2. This room could be incorporated with the laundry room, restrooms or shower rooms.
N. Mail/Copy/Supply Room:
1. Provide a space for copy machine/printer/scanner workcenter combination and a fax machine in this area.
2. Provide a space for a table that measure approximately 5 ft x 3 ft.
3. Supply storage for copy/printer paper, folders, pens & pencils, etc. can be located in this area
Tonto National Forest Payson Helibase 9 | P a g e
2. ADJACENCIES
2.01 DESIGN ADJACENCIES
The Operations/Mission Planning, Helicopter Manager, and Assistant Helicopter Manager (GS-8’s) shall have exterior windows that allow occupants to directly oversee the aircraft ramp area. The visitors’ entrance shall be located near the Helicopter Manager and the Assistant Helicopter Manager’s Office.
Provide an employee outside entrance near the PS and Temp office space as well as outside entrances to the Conference/Training Room.
The Ready Room needs to have direct access to the Ramp/Helipad Area.
The Vehicle Bay/Fire Cache and Ready Rooms need to be located such that large flatbed trucks can access the areas when making fire suppression supplies and equipment deliveries. The Fire Cache should be directly adjacent to the Ready Room. The Ready Room should b
The office space for the PS and Temp employees needs to be located relatively close to the Assistant Helicopter Manager Offices. The PSE (GS-7) office space may be located within the PS/Temp office space, or in an adjacent, separate space. This space does not need to have a direct view of the ramp/helipad area.
The break room and restrooms should be close to the conference room and the pilot’s lounge.
The showers should be near the restrooms and the fitness room.
Tonto National Forest Payson Helibase 10 | P a g e
3. GENERAL REQUIREMENTS
3.01 SECURITY
The following security standards are listed in addition to those listed in the Lease document and the building specific security attachment.
A. Adhere to all Federal Aviation Administration and Interagency Security Committee requirements for airport layout and access.
B. The site is a Facility Security Level II site and shall meet the requirements laid out in the Building Physical Security Requirements attached to this solicitation.
3.02 ACCESS CONTROL
A. See attached access control design guidelines, example drawings and 281300-Access Control System specification for design details.
B. Design and install a complete and functioning Access Control System consisting of card readers, door position switches, automatic door lock/release mechanisms, software, cabling, output/control relays, computer system, monitor, network components, documentation, and other associated equipment and appurtenances required for system operation.
1. Work shall include supply and installation of rigid or flexible conduit, cabling/wiring, system components, system operation testing, initial supply of 100 HID brand Corporate 1000 proximity cards, and an Operation and Maintenance Manual with full operation instructions and a listing of all system components of the system with cut sheets. System shall meet requirements of USDA Access Control System design guidelines and support Lync Pass USDA access cards.
2. Refer to Access Control System Design Guidelines and 281300 specifications for design of access control system.
3. System shall have 24 hour battery backup for operation.
4. Access control panel shall be located in IT room and power from IT room power panel.
C. Individual (stand-alone) electronic door systems that are not monitored by computer may be installed for the IT room only. A manual lock is also required.
D. Site vehicle gates shall be automated to open with access control card for entry into secured, fenced areas and open for exit from secured area by vehicle induction loop or a “press for exit” button. Any personnel gate entering into a secured fenced area shall also be part of the access control system and have a card reader activated locking mechanism.
E. Keyed Locks information for Access Control
1. A master key system shall be used for the high security locks for building entries or interior doors. The system shall include all doors with card readers.
2. Six master keys shall be supplied to the Government and 6 keysets for each group of locksets.
All supplied keys shall have an alpha-numeric code to designate building/door and be consecutively numbered (Example: MA 1 for master key 1)
3. Provide a secure key storage cabinet at the exterior of the building that emergency services can access for the purpose of obtaining building keys. Knox Box® model 3275 or approved equal.
3.03 INTRUSION DETECTION SYSTEM
1. Provide an intrusion alarm system for the building with a digital dialer for remote monitoring.
2. System shall have the following functions:
Tonto National Forest Payson Helibase 11 | P a g e
a. Remote digital alarm and monitoring panel with digital message showing system status and alarm zone area, with a keypad for arming/disarming system at entry doors.
b. Door position magnetic sensors on all exit doors
c. Motion detectors in rooms with windows.
d. Audible alarm horns
e. Provide 24 hours of battery backup.
3.04 INFORMATION TECHNOLOGY
The following IT standards are listed in addition to those listed in the Lease document.
A. See IT room requirements above for all systems to be included in this room.
B. Refer to the following for details on the IT standards:
1. IT and Electrical System Design Guidelines
2. 270000 Telecommunications systems wiring spec
3. 262417 IT Room Shutdown Panel
4. IT Room Layout sample drawing
5. 26262417 – IT Room Shutdown Panel EPO shutdown specification and sample drawing.
C. There will be 10 VoIP/Phone lines for the building
D. Analog lines will be provided for the following systems:
1. Emergency phones (min 2)
2. 2 Fax lines
3. Intrusion Detection System dialer
4. EPO panel shutdown alarm system dialer
E. Provide space for a base radio station. Provide for a radio antenna on the building roof to work in conjunction with the base radio.
F. Provide the building telecommunications wiring system from IT room patch panels to work stations using Cat 6 wire cables. See IT design guidelines and equipment load list work sheet for specific location of IT equipment and equipment power requirements.
G. Local Exchange Carrier (LEC) shall provide both analog POTS line and adequate data network capability to meet IT design guidelines. LEC equipment shall be located in IT room.
1. T1 Lines quantity of 2
3.05 PA SYSTEM
A. Provide a PA system that is tied into the phone system and base station radio, and that is capable of being heard both inside and outside of the building. Refer to IT and electrical System Design Guidelines.
B. PA system shall be located in IT room and powered from IT room power panel.
C. Provide separate volume controls for each area.
3.06 ACOUSTICS
A. Provide soundproofing materials such as mineral fiber acoustic insulation, caulking, and construction techniques specifically made for interior walls. Rooms with acoustic treatment shall extend from floor to ceiling, as well as the ceiling. The minimum Sound Transmission Class (STC) shall be 45. Room doors shall have a minimum STC of 45.
B. Provide acoustic treatments for walls and ceilings of the following areas:
Tonto National Forest Payson Helibase 12 | P a g e
1. Conference Rooms
2. Rest Rooms and Showers
3. Private Offices
4. Break Room
5. Exercise Room
6. Pilot Lounge
7. Laundry Room
8. Mechanical Room
3.07 WINDOWS
A. All windows in office or meeting space areas shall be double paned or noise reducing window types.
B. Windows in the Operations room shall be anti-glare, tinted and/or angled.
C. All windows shall either have shatter resistant film meeting performance condition ‘3b’ or laminated security glass required to meet Level II security requirements at an airport facility.
3.08 WINDOW TREATMENTS
A. All windows, except those in the bathroom, shall have window blinds..
B. Bathroom windows shall have obscure glass if glass is utilized.
3.09 ELECTRICAL
A. This section does not cover the entire design requirements. See attached IT and Electrical Design Guidelines for additional information on the following systems:
1. Service and power system design for power panels and feeders, and spare capacity
2. Lighting
3. IT room power, UPS for IT equipment, and EPO shut down systems
4. Telecommunications wiring systems
5. Grounding
B. Power panels for subpanels may be located in hallways if space for a dedicated electrical room cannot be provided.
C. Provide separate panels for the computer power needs and for normal receptacles, computer receptacles, lighting, and HVAC and IT room panel. Provide 200% neutral bus and feeders for computer needs.
D. Provide separate conduits for normal and computer feeder circuits.
E. All internal building raceways shall be steel.
F. Exterior equipment shall be corrosion resistant and enclosures shall be stainless steel.
G. Provide transient voltage surge suppression at the building service entrance panel, all isolated ground panels and any normal power control panels feeding other building equipment (i.e. HVAC equipment control panels).
H. Grounding and Bonding:
1. Grounding shall be per the NEC, local codes, and the additional requirements of IT and Electrical design guidelines. When there is a code conflict, the most stringent requirement shall be followed.
2. When compatible or more stringent than code, follow grounding instructions of the equipment manufacturer.
Tonto National Forest Payson Helibase 13 | P a g e
I. IT Room Electrical Systems
1. See IT and Electrical Systems Design Guidelines for IT room electrical design requirement.
Some of these requirements (but not all) are:
a. Network racks and cable racks for network wiring horizontal distribution.
b. Separate IT room power panel that serves this room only.
c. IT Room UPS that powers all equipment in IT room including:
i. IT racks for equipment power including servers, radio equipment, and network switches.
ii. PA System
iii. Security Control System
iv. Access Control System
v. EPO (Emergency Power Off) shut down system
vi. Two cross zoned smoke detectors to EPO panel
vii. Two high temperature shut down thermostats to EPO panel.
2. IT room shall be sized to allow for minimum NEC code clearances from front and backs of equipment racks to equipment mounted on adjacent walls.
3. Number of racks shall be a minimum of four racks, (four post racks) (Verify with equipment number of racks required). Government network equipment shall be on three racks, patch panels shall be in fourth rack.
J. IT Room UPS
1. UPS shall feed IT room power panel which shall power all IT room electrical and Electronic systems.
2. Size UPS for a 30 minute run time at full load.
3. Provide UPS size to power all network equipment, and other electronic systems in IT room from loads listed in equipment load list, plus 25% spare capacity.
4. Provide a separately mounted maintenance bypass switch next to UPS to allow for 100% bypass of UPS for maintenance or for UPS total removal for repair.
5. Provide a separate cabinet for extended run time batteries.
K. Emergency Power
1. Provide emergency power systems for life safety, egress lighting in exit corridors, emergency lighting and exit signage meeting the requirements of NFPA 101.
2. Emergency power to be provided by emergency ballasts with battery backup in emergency fluorescent lighting fixtures and/or by internal batteries in wall mounted dual head emergency lighting fixtures and by battery backup in emergency exit signs.
3. Provide an external connection for an emergency power generator on the outside of the building in a location suitable for bringing in a portable generator if needed.
L. Lighting
1. Lighting should furnish a high level of visibility and, at the same time, a low level of glare.
Consideration should be given to evenness of light, which is often more critical than the absolute level of lighting.
2. Internal lighting levels shall comply with ASHRAE maximum allowed lighting power density (LPD) for interior lighting, or the Oregon State Energy Code, whichever is lower.
3. Office spaces should use a variety of fixtures: recessed, suspended, wall or pendant mount to achieve lighting goals. Fixtures to use a combination of direct and indirect light to prevent the space from appearing ‘flat and dull’ while retaining the low glare benefits of indirect lighting.
Tonto National Forest Payson Helibase 14 | P a g e
a. Select combination indirect/direct lighting fixtures to be used with a minimal amount of at desk task lighting, to create a low-glare environment that maximally benefits occupants who work at a desk or computer screen. Hallways and egress paths to have light that maximizes depth and contrast.
4. All lighting fixtures near windows shall be equipped with ambient light photocell dimming capability.
5. Provide emergency lighting where required by the life safety code, NFPA 101.
6. Lighting control will be accomplished using occupancy sensors, photocells, and manual switching. Occupancy sensors will be provided to control lighting in all offices, restrooms, and corridors.
7. Provide full level dimmers and manual on/off switching in all conference rooms.
M. Outlets
1. See IT and Electrical Systems Design Guidelines for specific outlet and circuiting design requirements for normal and computer circuit receptacles.
2. Design for cubicle-style systems furniture that does not have electrical power included within the panels. Use strategically placed wall and floor outlets.
3. General purpose duplex outlets will be provided for cleaning and general maintenance in corridors and common areas.
4. Dedicated receptacles and junction box connections will be provided for equipment such as vending machines, refrigerators, copiers and other equipment as required.
5. All outlets shall be 20A specification grade nylon back and side wired.
6. Provide floor combination power and data outlet boxes in the conference room, pilot’s lounge, and crow’s nest (operations/mission planning room).
a. Provide 4 RJ-45 data jacks in each floor outlet box and two 20 A duplex outlets fed from computer power panels.
N. Electrical Supply Needs
Ops Room Conference Room
50" TV Electrical Projection Screen
50" TV Projector
BK Base Station Radio Audio System
VHF Base Station Radio
Desktop Computer w/Monitor Cache/Vehicle Bay/Shop
FAO Office Welder
Laptop Computer Ice Machine
Computer Monitor Air Compressor
Desk Lamp Chainsaw Grinder
Desk Lamp Electrical Tool Charging station
Pilot lounge
Chest Freezer Sewing Machine
50" TV
Refrigerator Microwave Coffee Maker Laptop
Tonto National Forest Payson Helibase 15 | P a g e
Electrical Supply Needs cont.
GS-9 office
Laptop Break Room
Monitor Microwave
Desk Lamp Refrigerator
Electric Desk Refrigerator
GS-8 office Coffee Maker
Laptop Toaster
Laptop Coffee grinder
Monitor
Monitor Exercise Room
2 -Treadmills
GS-7 office
50" TV
2-Eliptical Machines Stereo System
Laptop
Monitor Copy/Print Area
Monitor Copy/Printer/Scanner Combo
Fax Machine
GS-5 office
Laptop Laundry Area
Laptop Washing Machine
Laptop Clothes Dryer
Tonto National Forest Payson Helibase 16 | P a g e
3.10 PLUMBING
A. A drinking fountain shall be located outside the restrooms and shall include a sensor activated water bottle fill station.
B. Hose bibs (non-freeze wall hydrant, key type, with integral vacuum breakers) should be provided on the exterior as required. Provide at least one hose bib on each side of the building.
C. Trap prime all floor drains.
3.11 HVAC SYSTEMS
A. The system shall provide temperature, relative humidity, and air velocities within the comfort envelope as defined in ASHRAE Standards. Design the system to provide the temperature conditions stipulated in each space during normal operation hours. Pressurize the building interior to minimize infiltration.
B. Calculations to follow all ASHRAE recommended procedures. The emphasis of systems analysis should be placed on the occupancy profile for various areas of the building.
C. Areas requiring only part time occupancy, with conditions being maintained at the unoccupied level the remainder of the time, shall be isolated from the full time occupied area. Use either separate equipment or zones to meet the needs of these areas.
D. Areas having excessive heat gain or heat loss, seasonal imbalances, or affect by solar radiation at different time of the day shall be independently zoned or controlled.
E. For the spaces that have additional HVAC requirements:
1. Address each room, heating, cooling, and exhausting fumes in a separately zoned or dedicated HVAC system, as required.
2. Provide automatic, countdown timer, or on/off switch controlled exhaust fans as appropriate.
Fans to exhaust to the outside.
F. Fresh air intakes shall be located away from the helipads so that they do not introduce excess dust and gas fumes into the facility. For security purposes, they shall be located, extended, or secured to prevent tampering. Locate intakes on the roof or as high as practical. Locating intakes high on a wall is preferred over a roof location. Access to mechanical areas and building roofs shall be strictly controlled.
4. SITE REQUIREMENTS
4.01 HELIPADS:
A. Type 2 Helicopter: Two (2) pads in total. Pad shall be concrete. Dimensions shall be 20’ x 20’ centered in a 90’ radius circle with a minimum 150’ separation from each pad and have weight bearing capability of 11,900 pounds minimum.
B. Type 1 Helicopter: One (1) pad in total. Pad shall be concrete. Dimensions shall be 35’ x 35’ centered in a 150’ radius circle with a minimum of 300’ separation to adjacent pad(s) and have a weight bearing capability of 44,700 pounds minimum. Consideration shall be made for other aircraft parked in proximity to the Type 1 as it can kick up a lot of debris.
C. The helipads shall be constructed to meet FAA requirements and meet Airport requirements concerning rotor wash.
Tonto National Forest Payson Helibase 17 | P a g e
D. Provide anchored tiedowns per FAA and helicopter manufacturer requirements. At a minimum, the tiedowns shall securely hold the aircraft to withstand 100 year storm event.
E. All helipads shall be marked in accordance with FAA standards Advisory Circular 150/5390-2C.
F. Surface between pads should be natural, semi natural vegetation, or other permanent surface that will inhibit dust and blowing debris from rotor wash and meet FAA and Airport requirements.
G. Provide lighting in accordance with FAA Standards.
H. Provide each helipad with a frost free hose bib in a valve box that is flush with the ground.
I. Provide each helipad with two 20 Amp GFI receptacles in a valve box that is flush with the ground.
J. Depending on layout, this row of helipads should have additional distance from the building(s) – an apron area – to reduce the influence of rotor wash, noise, etc. on the building occupants.
K. The helipads shall have direct access to take off area so that each aircraft has an unobstructed path to the hover lanes and approach and departure routes.
L. The area around the helipads shall be free of obstacles.
M. Each helipad shall be accessible by large trucks with good traffic flow for fuel and mechanic trucks.
N. Parking for fuel and mechanic trucks also needs to be considered in the helipad and building layout.
The preferred location for support vehicle parking is at each individual helipad
4.02 PARKING
Type of Parking Number of Spaces Special Description (as necessary)
Secured Parking 35 spaces 6 vehicle spaces shall be for larger vehicles (i.e. Ford 350/550’s), 2 spaces for pull behind trailers that are appx 10’ wide.
Helicopter Support Vehicles 10 spaces 5 medium vehicles, 5 large (semi) vehicles
A. The preferred option for Helicopter Support Vehicles is to have the parking at each helipad. This would require (2) two, 12x30 parking areas at each Type II helipad (outside the safety circle) and (2) two, 12x50 parking areas at each Type I helipad. This would need to take into account FAA regulations associated with the hardened area around the actual concrete helipad. The electrical outlets required at each helipad will need to be located so that they can be shared between the parking areas for use by the support vehicles. If this option is selected by the offeror, the 10 spaces listed above for the “Helicopter Support Vehicles” are not required.
B. The parking lot for the office shall be designed to allow for the turning movement of a typical fuel truck/Type 3 Engine. Parking lots shall be configured such that design vehicles have free movement, meaning that they will not run over curbs nor encounter areas where vehicles will need to be relocated to allow them to pass.
C. If the preferred option of controlled access to the site with a main gate is chosen then a minimum building set back from the parking area is 20 feet. If the main gate is not controlled access then maximize distance between the parking area and the building, preferably at least 100’. If it is not feasible, e.g., existing construction of sites and roadways does not permit this distance, strive to limit parking closest to building to employees only.
D. Curb should be at least 20’ from the front of the building.
E. If the preferred option of controlled access to the main gate is not chosen - Design site entrance and circulation controls to prevent high speed approaches to buildings by vehicles. Use various types and designs of static barriers such as walls, fences, bike racks, plantings, trees, and street furniture to prevent vehicular damage to buildings and protect vulnerable areas. Offset vehicle entrances as necessary from the direction of a vehicle’s approach to force a reduction in speed.
Tonto National Forest Payson Helibase 18 | P a g e
F. If the preferred option of controlled access to the main gate is not chosen - Provide a path for delivery vehicles that does not allow access to unauthorized areas.
G. With the preferred option of controlled access to the main gate is chosen then provide a straight access alignment to the helipads from the main gate with parking for the building off to one side of this access.
H. Provide secured parking area vehicle and person access gates/entrances with electronic controls to minimize vehicle entry and removal. Gate access shall be tied into the access control system.
4.03 OTHER SITE REQUIREMENTS
A. The site building should have a buffer zone of at least 100’ 50’ from public roads and property of other ownership. Meet FAA design requirements.
B. Provide a 30’ x 30’ exterior covered courtyard area adjacent to the Break Room.
C. Provide a covered, hardened surface (concrete) out front of Exercise Room
D. Provide space for temporary Porta Potties outside in the event seasonal influxes and fire conditions require additional staffing at this location.
E. Signing and Markers:
1. Provide a USDA Forest Service Site Identification Sign along the entrance road. Sign should meet the requirements shown in chapter 8C signs for an A5 sign.
2. Provide standard road marking signs per the MUTCD.
F. Fencing is required around Government vehicle parking areas, employee parking areas, aircraft and cargo areas, and “Mission Essential Vulnerable Areas” such as ground level utility mains, transformers, natural gas lines, fuel tanks, and ground level HVAC units. The preferred option for fencing is to have controlled access to the main entrance and therefore the entire site. An electronic access gate controlled by key card access with a call button tied back to the helibase building is optimal. With this option there is no need for further fencing within the site. All parking would then be secure parking.
1. Use eight foot chain link fence with 3 strand barbed wire top guard.
G. On the eastern boundary (along the Type 1 helipads) and the western Boundary (along the future Airport aircraft parking apron) some type of vehicular barrier shall be installed to prevent vehicular access. Acceptable barriers could consist of a chain link fence, a berm with vegetative obstacles, or boulders. The most economical approach shall be chosen for this boundaries. On the North boundary of the site a chain link fence with access gate(s) shall be required. This fence shall be tied into the western and eastern boundary barriers to form a continuous vehicular access barrier.
1. If chain link is selected, use eight foot chain link fence with 3 strand barbed wire top guard.
H. Provide 5 foot wide concrete walkways between the facility and parking area(s). Slope to allow water runoff. All walkways shall meet accessibility standards.
I. Landscape with native plants to reduce maintenance. Minimize the use of irrigation systems. Where needed, use drip or other point of use irrigation systems and consider temporary systems to establish plants only. Where landscape plants must be watered, grade surface terrain to harvest runoff.
J. Harden and protect underground utilities by encasing them in metal conduit. Blast protect incoming power and water lines.
Tonto National Forest Payson Helibase 19 | P a g e
5. ATTACHMENTS FOLLOWING
2.
ASR Attachment 1 - Telecommunications Wiring Systems Example Specification 270000
ASR Attachment 2 - Access Control System Example Specification 281300
ASR Attachment 3 - Access Control Systems Design Guidelines
ASR Attachment 4 - Forest Identification Signing Document
ASR Attachment 5 - USDA Lightning Protection and Grounding Standards for Radio Systems
ASR Attachment 6 - FAA Advisory Circular for Heliport Design, 4/24/2012
ASR Attachment 7 - USDA Forest Service Telecommunication Wiring Systems Design Guidelines Draft