Questions and Answers 02112022.docx
DOCX document 26 KB Posted
- Attached to
- Fire Alarm Upgrade, Phoenix Rearing Facility
- Solicitation number
- 12639522R0015
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attendance sheet_02232022 site visit fire alarm upgrade.pdf | ||
| Questions from site visit 022322.docx | DOCX document | |
| Questions and Answers 02172022.docx | DOCX document | |
| Attachment 3_Drawings.pdf | ||
| Attachment 5_USDA Sustainable Buildings Implementation Plan.doc | DOC document | |
| Attachment 4_Designated Green Products for Federal Procurement.xls | XLS spreadsheet | |
| Attachment 1_Federal Construction Wage Rates_AZ20220031.pdf | ||
| Attachment 2_Specifications.pdf | ||
| 12639522R0015.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation 12639522R0015, Fire Alarm Upgrade, Phoenix Rearing Facility Questions and Answers:
Q: Spec Sec 284621.11-5 2.1 New system shall be non-proprietary. Can you confirm the purpose of this requirement? Non proprietary is a loaded question in the idea that real non proprietary system do not require technicians to have training on the system, meaning anyone can install it. Edwards is proprietary in the means it requires training to install and program, but there are several companies that work on it in the Phoenix area.
A: Here is a list of nonproprietary systems. Any NICET certified installer can work on these systems. This is nothing new as we have done this for multiple federal and nonfederal clients and never had this question.
3 major Nonproprietary Manufacturers Silent Knight Kiddie Fire Lite
Spec states the following:
QUALITY ASSURANCE
Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation of units required for this Project.
Installer Qualifications: Installation shall be by personnel certified by NICET as fire-alarm Level II technician.
Q: 284621.11-8 D.1.D VESD
A HLI Connection, prints do not show a vesda system, can you confirm there is one and from my knowledge the HLI is usually monitored through a computer, the fire alarm monitors contacts directly on the Vesda panel.
A: This reference is deleted.