Attachment 2_Specifications.pdf

PDF 559 KB Posted

Attached to
Fire Alarm Upgrade, Phoenix Rearing Facility Federal contract opportunity
Solicitation number
12639522R0015
Issued by
Department of Agriculture Animal and Plant Health Inspection Service Marketing and Regulatory Programs Business Services

View the file

Other files for this federal contract opportunity

Other files attached to Fire Alarm Upgrade, Phoenix Rearing Facility, newest first.
File Type Posted
Attendance sheet_02232022 site visit fire alarm upgrade.pdf PDF
Questions from site visit 022322.docx DOCX document
Questions and Answers 02172022.docx DOCX document
Questions and Answers 02112022.docx DOCX document
12639522R0015.pdf PDF
Attachment 3_Drawings.pdf PDF
Attachment 5_USDA Sustainable Buildings Implementation Plan.doc DOC document
Attachment 4_Designated Green Products for Federal Procurement.xls XLS spreadsheet
Attachment 1_Federal Construction Wage Rates_AZ20220031.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

09.14.2021

Phoenix Rearing Facility

Department of Agriculture

FIRE ALARM UPGRADE

Project Manual

P

R

O

J

E

C

T

M

A

N

U

A

L

Volume 1 of 1 | Divisions 26-28

OWNER

USDA – Dept of Food & Agriculture

36345 East Chipman Road

Phoenix, AZ

ARCHITECT/ENGINEER

Cushing Terrell

800 West Main Street, Suite 800

Boise, ID 83702

208.336.4900

Project Manager: Gary Glassing

PHOENIX REARING FACILITY – DEPARTMERNT OF FOOD AND AGRILCULTURE

PHOENIZ, ARIZONA USDAAPHIS_PFA

TABLE OF CONTENTS 1

TABLE OF CONTENTS

TECHNICAL SPECIFICATIONS

DIVISION 26 – ELECTRICAL

260300 – DEMOLITION/REMODEL ..................................................................................................... 1 -2

260500 - COMMON WORK RESULTS FOR ELECTRICAL .............................................................. 1 - 5

260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES ....................... 1 - 3

260529 – HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS ........................................... 1 - 5

260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS ............................................. 1 - 13

DIVISION 28 – ELECTRONIC SAFETY AND SECURITY

284621.11 – ADDRESSABLE FIRE-ALARM SYSTEMS .................................................................. 1 - 20

PHOENIX REARING FACILITY – DEPARTMENT OF FOOD AND AGRICULTURE

DEMOLITION/REMODEL 260300 - 1

SECTION 260300 - DEMOLITION/REMODEL

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section describes general requirements and methods of execution relating to the Demolition of portions of the electrical system for the Project.

1.2 DEMOLITION/REMODEL WORK

A. The Contractor shall carefully examine the Drawings and Specifications, visit the project site, and make note of all existing conditions, dimensions, and limitations prior to Bid and make allowances thereto.

B. No Change Orders shall be issued due to the Contractor's lack of knowledge of the existing conditions of the Project and of the amount and difficulty of the remodel and/or demolition work necessary for a complete installation of the systems shown.

C. The Contractor shall also notify all corporations, companies, individuals or local authorities owning, or having jurisdiction over existing utilities and services which interfere in any manner with the execution of the Work under this Contract, and shall remove, relocate or protect such utilities or equipment as required by the parties having jurisdiction over same.

D. If existing active or nonactive services (which may not be shown on Plans) are encountered that require relocation or disconnecting, the Electrical Contractor shall make written request for decision on proper handling of the services. The Electrical Contractor shall not proceed with the Work until so authorized by the Architect.

E. When areas of the existing buildings are adjacent to the area of construction in which work is going on and are occupied, then this Contractor shall arrange the Work so as to reduce to a minimum the periods of interruption or outages in the various services.

F. Not less than one week before any system is to be put out of service, the Contractor shall notify and coordinate with other trades and the Owner of such necessity including the extent of the Work to be done during the outage, possible length of time required for that phase of the Work, and the desired time at which the outage is to begin.

G. Balance additional loads to existing circuitry between phases. Furnish a revised, typed panel directory on existing panelboards where circuitry is changed.

H. Carefully lay out all work in advance to minimize cutting, channeling, or drilling. Where necessary, all cutting and patching shall be done in a manner approved by the Architect. Do not endanger the stability of the structure. Restore any damaged surfaces to original conditions.

Contractor at fault to assume all costs.

DEMOLITION/REMODEL 260300 - 2

I. Remove or relocate existing conduits, wires, equipment, devices, or fixtures indicated on Drawings and as required by remodel operations. Where the reuse of existing conduits, wires, devices, or fixture is permitted, verify that wiring is continuous. Existing outlets or junction boxes shall not be rendered inaccessible by structural changes made to the building. Where existing walls are being furred out or refinished, extend existing outlets and devices to new surface as required.

J. Existing equipment which is indicated as being removed and not indicated for re-use shall be disposed of unless stated otherwise. Remove and dispose of any material, except fluorescent lamps and ballasts. Contractor shall be responsible for disposal of all removed lamps and ballasts. Ballasts may contain PCB’s and shall be disposed of according to environmental regulations.

PART 2 - PRODUCTS (Not Used)

PART 3 - EXECUTION (Not Used)

END OF SECTION 260300

COMMON WORK RESULTS FOR ELECTRICAL 260500 - 1

SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section and all Division 26.

1.2 SUMMARY

A. Section Includes:

1. Electrical equipment coordination and installation.

2. Sleeves for raceways and cables.

3. Sleeve seals.

4. Grout.

5. Common electrical installation requirements.

1.3 QUALITY ASSURANCE

A. Comply with latest adopted IBC Codes, NFPA Codes, Elevator Codes, ANSI, UL, ADAAG, and applicable Local and State Codes. Also comply with Utility Company regulations, industry standards and Construction Documents.

B. Work shall be done by only trained, licensed and experienced workmen familiar with the requirements.

C. All microprocessor based equipment and software with equipment shall utilize 4 digits for the year part of all dates. A two digit date shall be an option for only for printing at Owner's preference.

1.4 EXTENT OF DRAWINGS / SPECIFICATION

A. Drawings indicate intent and general layout of electrical systems for the Project. Drawings are partly diagrammatic and do not indicate all fittings and accessories which may be required.

Provide such fittings and accessories as required to form a complete and operating system in general conformance with Specifications and Drawings.

1.5 PRIOR APPROVALS

A. All products submitted for prior approval shall be received by the Engineer 10 business days prior to Bid. Supply technical data, photometrics and dimensional Drawings showing that substitutes are equal to product specified. Faxed prior approvals will not be accepted.

COMMON WORK RESULTS FOR ELECTRICAL 260500 - 2

1.6 DISCREPANCIES

A. Prior to submitting Bid, Contractor shall refer any apparent discrepancies or omissions to Engineer for clarification. The more stringent provisions shall take precedence where codes, Specifications and Drawings differ with one another. The Contractor shall Bid the more expensive requirement unless discrepancy is addressed by Addendum prior to Bid.

1.7 TEMPORARY LIGHTING/POWER

A. Provide temporary electrical power and lighting for all trades that require service during the course of this Project. Provide temporary service and distribution as required. Comply with the NEC and OSHA requirements. Energy Costs by General Contractor.

1.8 SHOP DRAWING SUBMITTALS

A. General: Follow the procedures specified in Division 01 Section "Submittal Procedures."

Submit for final and official approval through the General Contractor.

B. Provide the number of electrical related Shop Drawings, product data, and samples submitted, to allow for required distribution plus one copy of each submittal required, which will be retained by the Electrical Consulting Engineer.

1. Engineer - 1 copy.

2. General Contractor - 2 copies.

3. Subcontractor - Copies as required.

C. All Shop Drawings shall be bound in PDF format. Provide title sheet for each Specification Section indicating the Specification number and name. Copies of price list sheets not acceptable.

1.9 SEQUENCING AND SCHEDULING

A. Coordinate electrical equipment installation with other building components.

B. Arrange for chases, slots, and openings in building structure during progress of construction to allow for electrical installations.

C. Coordinate installing required supporting devices and set sleeves in poured-in-place concrete and other structural components as they are constructed.

D. Sequence, coordinate, and integrate installing electrical materials and equipment for efficient flow of the Work. Coordinate installing large equipment requiring positioning prior to closing in the building.

E. Coordinate connecting electrical service to components furnished under other Sections.

COMMON WORK RESULTS FOR ELECTRICAL 260500 - 3

F. Coordinate connecting electrical systems with exterior underground and overhead utilities and services. Comply with requirements of governing regulations, franchised service companies, and controlling agencies. Coordinate requirements for access panels and doors where electrical items requiring access are concealed by finished surfaces. Access panels and doors are specified in Division 08 Section "Access Doors and Frames."

1.10 RECORD DOCUMENTS

A. Prepare Record Documents in accordance with the requirements in Division 01 Section "Closeout Procedures." In addition to the requirements specified in Division 01, indicate the following installed conditions:

1. Actual location of all electrical service gear/feeders, panel/motor/special equipment feeders, all major underground or underslab conduits, all conduit stubs for future use, any change in branch circuitry from Drawings, key junction boxes and pull boxes not indicated on Drawings, any control locations or indicator lights not shown on Drawings.

2. Addendum items, Change Order items and all changes made to Drawings from Bidding phase through to Project completion.

3. Actual equipment and materials installed. Where manufacturer and catalog number are indicated on Drawings, generally or in fixture or equipment schedules, change to reflect actual products installed.

4. Change service panel and branch panel breaker locations and schedules to reflect actual installed conditions.

1.11 MAINTENANCE MANUALS

A. Prepare maintenance manuals in accordance with Division 01 Section "Closeout Procedures." In addition to the requirements specified in Division 01. Assemble O & M Manuals as follows:

1. Compile Operating and Maintenance Manuals for the electrical systems and equipment.

The manuals shall be provided to the Architect for approval complete and at one time, prior to requesting final payment. Partial or separate data will be returned for completion.

2. Manuals shall be assembled in three-ring binders. Binders shall be 3 inch thick or less and have slip sleeve jacket on binder side and front. More than one binder shall be used for each set of data if required to prevent overfilling of one binder. All information shall be arranged in Sections and each Section shall have a blank buff colored, heavy paper divider with a protruding tab clearly labeled. Sections shall be arranged in the same order that the equipment is listed in the Specification and each Specification Section shall have a separate tab. Shop Drawings which are larger than 8-1/2-inch by 11 inch shall be individually folded so they are 8-1/2-inch by 11 inch or less and inserted behind the appropriate tab.

3. Tabs shall be labeled and arranged as follows:

a. Index: Furnish under the first tab an index of Sections listing name of Section and Specification numbers.

b. Equipment Manufacturers: Furnish under the second tab a complete typed list of equipment suppliers and manufacturers representative including type of

COMMON WORK RESULTS FOR ELECTRICAL 260500 - 4

equipment, name, address and phone number. The company listed here should be the one which could furnish replacement parts and offer technical information about the equipment.

c. Product Literature: Each tab, starting with the third shall contain the name of a Specification Section. Behind each tab shall be the previously submitted and approved Shop Drawing, factory published operation and maintenance instructions and parts lists. Also include description of function, normal operating characteristics and limitations, engineering data and tests, and complete nomenclature and commercial numbers of replacement parts. Manufacturer's printed operating procedures to include start-up, break-in, and routine and normal operating instructions; regulation, control, stopping, shutdown, and emergency instructions; and summer and winter operating instructions. Maintenance procedures for routine preventative maintenance and troubleshooting; disassembly, repair, and reassembly; aligning and adjusting instructions. Servicing instructions and lubrication charts and schedules.

4. Upon completion and approval of the booklets, one copy shall be given to the Architect, and two to the Owner. Using the booklet, the Electrical Contractor shall explain in detail and instruct the Owner's operating personnel in the correct operation and maintenance of the equipment.

1.12 COORDINATION

A. Coordinate arrangement, mounting, and support of electrical equipment:

1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.

2. To provide for ease of disconnecting the equipment with minimum interference to other installations.

3. To allow right of way for piping and conduit installed at required slope.

4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.

B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

C. Coordinate location of access panels and doors for electrical items that are behind finished surfaces or otherwise concealed. Access doors and panels are specified in Division 08 Section "Access Doors and Frames."

D. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Penetration Firestopping."

COMMON WORK RESULTS FOR ELECTRICAL 260500 - 5

PART 2 - PRODUCTS (Not Used)

PART 3 - EXECUTION

3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with NECA 1.

B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.

C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.

D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.

E. Right of Way: Give to piping systems installed at a required slope.

END OF SECTION 260500

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 1

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Building wires and cables rated 600 V and less.

2. Connectors, splices, and terminations rated 600 V and less.

3. Sleeves and sleeve seals for cables.

1.3 DEFINITIONS

A. EPDM: Ethylene-propylene-diene terpolymer rubber.

B. NBR: Acrylonitrile-butadiene rubber.

1.4 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Qualification Data: For testing agency.

C. Field quality-control test reports.

1.5 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Comply with NFPA 70.

1.6 COORDINATION

A. Set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 2

PART 2 - PRODUCTS

2.1 CONDUCTORS AND CABLES

A. Feeders: Copper THHN-THWN. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.

B. Branch Circuits: Copper THHN-THWN. Solid for No. 10 AWG and smaller; stranded for No.

8 AWG and larger.

C. Multiconductor Cable: Copper Type AC and Type MC with ground wire. (Only permitted where specifically noted on Construction Documents.)

2.2 CONNECTORS AND SPLICES

A. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.

PART 3 - EXECUTION

3.1 INSTALLATION OF CONDUCTORS AND CABLES

A. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.

B. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.

D. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible.

E. Support cables according to Division 26 Section "Hangers and Supports for Electrical Systems."

F. Identify and color-code conductors and cables according to Division 26 Section "Identification for Electrical Systems."

G. Feeders and branch circuits shall not be installed in concrete slabs, but are permitted to be routed through concrete slabs perpendicularly and under slabs.

H. Install all wire in raceway; minimum size shall be #12 AWG.

I. Shared neutral conductors are not allowed.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 3

3.2 CONNECTIONS

A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B.

B. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.

1. Use oxide inhibitor in each splice and tap conductor for aluminum conductors.

C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches of slack.

3.3 COLOR CODING FOR PHASE IDENTIFICATION

A. Color code secondary feeder and branch circuit conductors with factory applied color as follows:

120/208 Volts Phase 277/480 Volts Black A Brown Red B Purple Blue C Yellow White N Grey Green G Green

3.4 FIELD QUALITY CONTROL

A. Prior to energizing, test wires and cables for electrical continuity and for short-circuits.

END OF SECTION 260519

PHOENIX REARING FACILITY – DEPARTMERNT OF FOOD AND AGRICULTURE

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 1

SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following:

1. Hangers and supports for electrical equipment and systems.

2. Construction requirements for concrete bases.

B. Related Sections include the following:

1. Division 26 Section "Vibration and Seismic Controls for Electrical Systems" for products and installation requirements necessary for compliance with seismic criteria.

1.3 DEFINITIONS

A. EMT: Electrical metallic tubing.

B. IMC: Intermediate metal conduit.

C. RMC: Rigid metal conduit.

1.4 PERFORMANCE REQUIREMENTS

A. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents.

B. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.

C. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force.

1.5 SUBMITTALS

A. Product Data: For the following:

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 2

1. Steel slotted support systems.

2. Nonmetallic slotted support systems.

1.6 QUALITY ASSURANCE

A. Comply with NFPA 70.

1.7 COORDINATION

A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete, reinforcement, and formwork requirements are specified in Division 03.

B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These items are specified in Division 07 Section "Roof Accessories."

PART 2 - PRODUCTS

2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS

A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field assembly.

B. Nonmetallic Slotted Support Systems: Structural-grade, factory-formed, glass-fiber-resin channels and angles with 9/16-inch- diameter holes at a maximum of 8 inches o.c., in at least 1 surface.

1. Fittings and Accessories: Products of channel and angle manufacturer and designed for use with those items.

2. Fitting and Accessory Materials: Same as channels and angles, except metal items may be stainless steel.

3. Rated Strength: Selected to suit applicable load criteria.

C. Raceway and Cable Supports: As described in NECA 1 and NECA 101.

D. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.

E. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body shall be malleable iron.

F. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.

G. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 3

1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened Portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.

2. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated steel, for use in hardened Portland cement concrete with tension, shear, and pullout capacities appropriate for supported loads and building materials in which used.

3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to MSS Type 18; complying with MFMA-4 or MSS SP-58.

4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for attached structural element.

5. Through Bolts: Structural type, hex head, and high strength. Comply with

ASTM A 325.

6. Toggle Bolts: All-steel springhead type.

7. Hanger Rods: Threaded steel.

2.2 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES

A. Description: Welded or bolted, structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment.

B. Materials: Comply with requirements in Division 05 Section "Metal Fabrications" for steel shapes and plates.

PART 3 - EXECUTION

3.1 APPLICATION

A. Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical equipment and systems except if requirements in this Section are stricter.

B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for EMT, IMC, and RMC as required by NFPA 70. Minimum rod size shall be 1/4 inch in diameter.

C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted or other support system, sized so capacity can be increased by at least 25 percent in future without exceeding specified design load limits.

1. Secure raceways and cables to these supports with two-bolt conduit clamps.

D. Spring-steel clamps designed for supporting single conduits without bolts may be used for 1- 1/2-inch and smaller raceways serving branch circuits and communication systems above suspended ceilings and for fastening raceways to trapeze supports.

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 4

3.2 SUPPORT INSTALLATION

A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this Article.

B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC, and RMC may be supported by openings through structure members, as permitted in NFPA 70.

C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits.

Minimum static design load used for strength determination shall be weight of supported components plus 200 lb.

D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:

1. To Wood: Fasten with lag screws or through bolts.

2. To New Concrete: Bolt to concrete inserts.

3. To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor fasteners on solid masonry units.

4. To Existing Concrete: Expansion anchor fasteners.

5. Instead of expansion anchors, powder-actuated driven threaded studs provided with lock washers and nuts may be used in existing standard-weight concrete 4 inches thick or greater. Do not use for anchorage to lightweight-aggregate concrete or for slabs less than 4 inches thick.

6. To Steel: Welded threaded studs complying with AWS D1.1/D1.1M, with lock washers and nuts or Beam clamps (MSS Type 19, 21, 23, 25, or 27) complying with MSS SP-69.

7. To Light Steel: Sheet metal screws.

8. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that meet seismic-restraint strength and anchorage requirements.

E. Drill holes for expansion anchors in concrete at locations and to depths that avoid reinforcing bars.

3.3 INSTALLATION OF FABRICATED METAL SUPPORTS

A. Comply with installation requirements in Division 05 Section "Metal Fabrications" for site-fabricated metal supports.

B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor electrical materials and equipment.

C. Field Welding: Comply with AWS D1.1/D1.1M.

HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 5

3.4 CONCRETE BASES

A. Construct concrete bases of dimensions indicated but not less than 4 inches larger in both directions than supported unit, and so anchors will be a minimum of 10 bolt diameters from edge of the base.

B. Use 3000-psi, 28-day compressive-strength concrete. Concrete materials, reinforcement, and placement requirements are specified in Division 03 Section "Cast-in-Place Concrete."

C. Anchor equipment to concrete base.

1. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

2. Install anchor bolts to elevations required for proper attachment to supported equipment.

3. Install anchor bolts according to anchor-bolt manufacturer's written instructions.

3.5 PAINTING

A. Touchup: Comply with requirements in Division 09 painting Sections for cleaning and touchup painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous metal.

B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A 780.

END OF SECTION 260529

RACEWAYS AND BOXES FOR ELECTRICAL AND COMMUNICATIONS

SYSTEMS

260533 - 1

SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Metal conduits and fittings.

2. Nonmetallic conduits and fittings.

3. Metal wireways and auxiliary gutters.

4. Nonmetal wireways and auxiliary gutters.

5. Surface raceways.

6. Boxes, enclosures, and cabinets.

7. Handholes and boxes for exterior underground cabling.

B. Related Requirements:

1. Section 078413 "Penetration Firestopping" for firestopping at conduit and box entrances.

2. Section 260543 "Underground Ducts and Raceways for Electrical Systems" for exterior ductbanks, manholes, and underground utility construction.

1.3 DEFINITIONS

A. ARC: Aluminum rigid conduit.

B. GRC: Galvanized rigid steel conduit.

C. IMC: Intermediate metal conduit.

D. EMT: Electrical metallic conduit.

E. ENT: Electrical non-metallic conduit.

F. FMC: Flexible metal conduit.

G. LFMC: Liquid flexible metal conduit.

H. LFNC: Liquid flexible non-metallic conduit.

260533 - 2

1.4 ACTION SUBMITTALS

A. Product Data: For surface raceways, wireways and fittings, floor boxes, hinged-cover enclosures, and cabinets.

B. Shop Drawings: For custom enclosures and cabinets. Include plans, elevations, sections, and attachment details.

1.5 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of items involved:

1. Structural members in paths of conduit groups with common supports.

2. HVAC and plumbing items and architectural features in paths of conduit groups with common supports.

B. Qualification Data: For professional engineer.

C. Seismic Qualification Data: Certificates, for enclosures, cabinets, and conduit racks and their mounting provisions, including those for internal components, from manufacturer.

1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.

2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.

3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.

4. Detailed description of conduit support devices and interconnections on which the certification is based and their installation requirements.

D. Source quality-control reports.

PART 2 - PRODUCTS

2.1 METAL CONDUITS AND FITTINGS

A. Metal Conduit:

1. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. GRC: Comply with ANSI C80.1 and UL 6.

3. ARC: Not allowed.

4. IMC: Comply with ANSI C80.6 and UL 1242.

5. PVC-Coated Steel Conduit: PVC-coated rigid steel conduit.

a. Comply with NEMA RN 1.

260533 - 3

b. Coating Thickness: 0.040 inch, minimum.

6. EMT: Comply with ANSI C80.3 and UL 797.

7. FMC: Comply with UL 1; zinc-coated steel.

8. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360.

B. Metal Fittings:

1. Comply with NEMA FB 1 and UL 514B.

2. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

3. Fittings, General: Listed and labeled for type of conduit, location, and use.

4. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 1203 and

NFPA 70.

5. Fittings for EMT:

a. Material: Steel.

b. Type: Setscrew.

6. Expansion Fittings: PVC or steel to match conduit type, complying with UL 651, rated for environmental conditions where installed, and including flexible external bonding jumper.

7. Coating for Fittings for PVC-Coated Conduit: Minimum thickness of 0.040 inch, with overlapping sleeves protecting threaded joints.

C. Joint Compound for IMC, GRC, or ARC: Approved, as defined in NFPA 70, by authorities having jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect threaded conduit joints from corrosion and to enhance their conductivity.

D. Comply with TIA-569-D for communication systems applications.

2.2 NONMETALLIC CONDUITS AND FITTINGS

A. Nonmetallic Conduit:

1. Listing and Labeling: Nonmetallic conduit shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2. Fiberglass:

a. Comply with NEMA TC 14.

b. Comply with UL 2515 for aboveground raceways.

c. Comply with UL 2420 for belowground raceways.

3. ENT: Not allowed.

4. RNC: Type EPC-40-PVC with EPC-80 PVC fittings, complying with NEMA TC 2 and

UL 651 unless otherwise indicated.

5. LFNC: Comply with UL 1660.

6. Rigid HDPE: Not allowed.

260533 - 4

7. Continuous HDPE: Not allowed.

8. Coilable HDPE: Not allowed.

9. RTRC: Comply with UL 2515A and NEMA TC 14.

B. Nonmetallic Fittings:

1. Fittings, General: Listed and labeled for type of conduit, location, and use.

2. Fittings for RNC: Comply with NEMA TC 3; match to conduit or tubing type and material.

a. Fittings for LFNC: Comply with UL 514B.

3. Solvents and Adhesives: As recommended by conduit manufacturer.

2.3 METAL WIREWAYS AND AUXILIARY GUTTERS

A. Description: Sheet metal, complying with UL 870 and NEMA 250, type as indicated on Construction Documents, and sized according to NFPA 70.

1. Metal wireways installed outdoors shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.

C. Wireway Covers: Hinged type unless otherwise indicated.

D. Finish: Manufacturer's standard enamel finish.

2.4 NONMETALLIC WIREWAYS AND AUXILIARY GUTTERS

A. Listing and Labeling: Nonmetallic wireways and auxiliary gutters shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. Comply with TIA-569-D for communication systems applications.

B. Description: Fiberglass polyester, extruded and fabricated to required size and shape, without holes or knockouts. Cover shall be gasketed with oil-resistant gasket material and fastened with captive screws treated for corrosion resistance. Connections shall be flanged and have stainless-steel screws and oil-resistant gaskets.

C. Description: PVC, extruded and fabricated to required size and shape, and having snap-on cover, mechanically coupled connections, and plastic fasteners.

D. Fittings and Accessories: Couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings shall match and mate with wireways as required for complete system.

260533 - 5

E. Solvents and Adhesives: As recommended by conduit manufacturer.

2.5 SURFACE RACEWAYS

A. Listing and Labeling: Surface raceways and tele-power poles shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Surface Metal Raceways: Galvanized steel with snap-on covers complying with UL 5.

Manufacturer's standard enamel finish.

2.6 BOXES, ENCLOSURES, AND CABINETS

A. General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets installed in wet locations shall be listed for use in wet locations. Comply with TIA-569-D for communications systems.

B. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A.

C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, ferrous alloy, Type FD, with gasketed cover.

D. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1.

E. Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, galvanized, cast iron with gasketed cover.

F. Box extensions used to accommodate new building finishes shall be of same material as recessed box.

G. Hinged-Cover Enclosures: Comply with UL 50 and NEMA 250, NEMA, enclosure type as indicated on Construction Documents with continuous-hinge cover with flush latch unless otherwise indicated.

1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.

2. Nonmetallic Enclosures: Plastic.

3. Interior Panels: Steel; all sides finished with manufacturer's standard enamel.

H. Cabinets:

1. NEMA 250, NEMA enclosure type as indicated on Construction Documents, galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel.

2. Hinged door in front cover with flush latch and concealed hinge.

3. Key latch to match panelboards.

4. Metal barriers to separate wiring of different systems and voltage.

5. Accessory feet where required for freestanding equipment.

260533 - 6

6. Nonmetallic cabinets shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

2.7 HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING

A. General Requirements for Handholes and Boxes:

1. Boxes and handholes for use in underground systems shall be designed and identified as defined in NFPA 70, for intended location and application.

2. Boxes installed in wet areas shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. Polymer-Concrete Handholes and Boxes with Polymer-Concrete Cover: Molded of sand and aggregate, bound together with polymer resin, and reinforced with steel, fiberglass, or a combination of the two.

1. Standard: Comply with SCTE 77.

2. Configuration: Designed for flush burial with closed bottom unless otherwise indicated.

3. Cover: Weatherproof, secured by tamper-resistant locking devices and having structural load rating consistent with enclosure and handhole location.

4. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of 0.50.

5. Cover Legend: Molded lettering, "ELECTRIC" or "COMMUNICATIONS" or as indicated for each service type.

6. Conduit Entrance Provisions: Conduit-terminating fittings shall mate with entering ducts for secure, fixed installation in enclosure wall.

7. Handholes 12 Inches Wide by 24 Inches Long and Larger: Have inserts for cable racks and pulling-in irons installed before concrete is poured.

2.8 SOURCE QUALITY CONTROL FOR UNDERGROUND ENCLOSURES

A. Handhole and Pull-Box Prototype Test: Test prototypes of handholes and boxes for compliance with SCTE 77. Strength tests shall be for specified tier ratings of products supplied.

1. Tests of materials shall be performed by an independent testing agency.

2. Strength tests of complete boxes and covers shall be by either an independent testing agency or manufacturer. A qualified registered professional engineer shall certify tests by manufacturer.

3. Testing machine pressure gages shall have current calibration certification complying with ISO 9000 and ISO 10012 and traceable to NIST standards.

2.9 COMMUNICATION CABLING HOOKS

A. Description: Pre-fabricated sheet metal cable supports for communications cabling.

1. Listed and labeled as defined in NFPA 70, by an NRTL and marked for intended location and application.

2. Comply with TIA-569-D.

260533 - 7

3. Steel J type.

PART 3 - EXECUTION

3.1 RACEWAY APPLICATION

A. Outdoors: Apply raceway products as specified below unless otherwise indicated:

1. Exposed Conduit: GRC.

2. Concealed Conduit, Aboveground: EMT.

3. Underground Conduit: RNC, Type EPC-40-PVC with Type EPC-80-PVC fittings.

4. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC.

5. Boxes and Enclosures, Aboveground: NEMA 250, Type 3R.

B. Indoors: Apply raceway products as specified below unless otherwise indicated:

1. Exposed, Not Subject to Physical Damage: EMT.

2. Exposed, Not Subject to Severe Physical Damage: EMT.

3. Exposed and Subject to Severe Physical Damage: GRC or IMC. Raceway locations include the following:

a. Loading dock.

b. Corridors used for traffic of mechanized carts, forklifts, and pallet-handling units.

c. Mechanical rooms.

4. Concealed in Ceilings and Interior Walls and Partitions: EMT.

5. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): FMC, except use LFMC in damp or wet locations.

6. Damp or Wet Locations: GRC or IMC.

7. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250, Type 4X stainless steel in institutional and commercial kitchens and damp or wet locations.

C. Minimum Raceway Size: 1/2-inch trade size.

D. Raceway Fittings: Compatible with raceways and suitable for use and location.

1. Rigid and Intermediate Steel Conduit: Use threaded rigid steel conduit fittings unless otherwise indicated. Comply with NEMA FB 2.10.

2. PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with this type of conduit. Patch and seal all joints, nicks, and scrapes in PVC coating after installing conduits and fittings. Use sealant recommended by fitting manufacturer and apply in thickness and number of coats recommended by manufacturer.

3. EMT: Use setscrew, steel fittings. Comply with NEMA FB 2.10.

4. Flexible Conduit: Use only fittings listed for use with flexible conduit. Comply with

NEMA FB 2.20.

260533 - 8

E. Install nonferrous conduit or tubing for circuits operating above 60 Hz. Where aluminum raceways are installed for such circuits and pass through concrete, install in nonmetallic sleeve.

F. Aluminum conduits, boxes, or fittings are not allowed.

G. Install surface raceways only where indicated on Drawings.

H. Do not install nonmetallic conduit where ambient temperature exceeds 120 deg F.

3.2 INSTALLATION

A. Comply with requirements in Section 260529 "Hangers and Supports for Electrical Systems" for hangers and supports.

B. Comply with NECA 1 and NECA 101 for installation requirements except where requirements on Drawings or in this article are stricter. Comply with NFPA 70 limitations for types of raceways allowed in specific occupancies and number of floors. Comply with NECA 105, NECA III and TIA-569-D for communication systems.

C. Do not install raceways or electrical items on any "explosion-relief" walls or rotating equipment.

D. Do not fasten conduits onto the bottom side of a metal deck roof.

E. Keep raceways at least 6 inches away from parallel runs of flues and steam or hot-water pipes.

Install horizontal raceway runs above water and steam piping.

F. Complete raceway installation before starting conductor installation.

G. Arrange stub-ups so curved portions of bends are not visible above finished slab.

H. Install no more than the equivalent of three 90-degree bends in any electrical power or lighting conduit. Support within 12 inches of changes in direction.

I. Make bends in raceway using large-radius preformed ells. Field bending shall be according to NFPA 70 minimum radii requirements. Use only equipment specifically designed for material and size involved.

J. Conceal conduit within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines.

K. Support conduit within 12 inches of enclosures to which attached.

L. Raceways Embedded in Slabs: Not allowed unless specifically indicated on the Construction Documents.

M. Stub-Ups to Above Recessed Ceilings:

1. Use EMT or RMC for raceways.

260533 - 9

2. Use a conduit bushing or insulated fitting to terminate stub-ups not terminated in hubs or in an enclosure.

N. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound to threads of raceway and fittings before making up joints. Follow compound manufacturer's written instructions.

O. Coat field-cut threads on PVC-coated raceway with a corrosion-preventing conductive compound prior to assembly.

P. Raceway Terminations at Locations Subject to Moisture or Vibration: Use insulating bushings to protect conductors including conductors smaller than No. 4 AWG.

Q. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to 1-1/4-inch trade size and insulated throat metal bushings on 1-1/2-inch trade size and larger conduits terminated with locknuts. Install insulated throat metal grounding bushings on service conduits.

R. Install raceways square to the enclosure and terminate at enclosures with locknuts. Install locknuts hand tight plus 1/4 turn more.

S. Do not rely on locknuts to penetrate nonconductive coatings on enclosures. Remove coatings in the locknut area prior to assembling conduit to enclosure to assure a continuous ground path.

T. Cut conduit perpendicular to the length. For conduits 2-inch trade size and larger, use roll cutter or a guide to make cut straight and perpendicular to the length.

U. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not less than 200-lb tensile strength. Leave at least 12 inches of slack at each end of pull wire. Cap underground raceways designated as spare above grade alongside raceways in use.

V. Pathways for Optical-Fiber and Communications Cable: Install pathways, metal and nonmetallic, rigid and flexible, as follows:

1. 3/4-inch Trade Size and Smaller: Install pathways in maximum lengths of 50-inch.

2. 1-inch Trade Size and Larger: Install pathways in maximum lengths of 75-feet.

3. Install with a maximum of two 90-degree bends or equivalent for each length of pathway unless Drawings show stricter requirements. Separate lengths with pull or junction boxes or terminations at distribution frames or cabinets where necessary to comply with these requirements.

W. Surface Raceways:

1. Install surface raceway with a minimum 2-inch radius control at bend points.

2. Secure surface raceway with screws or other anchor-type devices at intervals not exceeding 48 inches and with no less than two supports per straight raceway section.

Support surface raceway according to manufacturer's written instructions. Tape and glue are not acceptable support methods.

260533 - 10

X. Install raceway sealing fittings at accessible locations according to NFPA 70 and fill them with listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a blank cover plate having a finish similar to that of adjacent plates or surfaces. Install raceway sealing fittings according to NFPA 70.

Y. Install devices to seal raceway interiors at accessible locations. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal the interior of all raceways at the following points:

1. Where conduits pass from warm to cold locations, such as boundaries of refrigerated spaces.

2. Where an underground service raceway enters a building or structure.

3. Conduit extending from interior to exterior of building.

4. Conduit extending into pressurized duct and equipment.

5. Conduit extending into pressurized zones that are automatically controlled to maintain different pressure set points.

6. Where otherwise required by NFPA 70.

Z. Comply with manufacturer's written instructions for solvent welding RNC and fittings.

AA. Expansion-Joint Fittings:

1. Install in each run of aboveground RNC that is located where environmental temperature change may exceed 30 deg F and that has straight-run length that exceeds 25 feet. Install in each run of aboveground RMC and EMT conduit that is located where environmental temperature change may exceed 100 deg F and that has straight-run length that exceeds 100 feet.

2. Install type and quantity of fittings that accommodate temperature change listed for each of the following locations:

a. Outdoor Locations Not Exposed to Direct Sunlight: 125 deg F temperature change.

b. Outdoor Locations Exposed to Direct Sunlight: 155 deg F temperature change.

c. Indoor Spaces Connected with Outdoors without Physical Separation: 125 deg F temperature change.

d. Attics: 135 deg F temperature change.

3. Install fitting(s) that provide expansion and contraction for at least 0.00041 inch per foot of length of straight run per deg F of temperature change for PVC conduits. Install fitting(s) that provide expansion and contraction for at least 0.000078 inch per foot of length of straight run per deg F of temperature change for metal conduits.

4. Install expansion fittings at all locations where conduits cross building or structure expansion joints.

5. Install each expansion-joint fitting with position, mounting, and piston setting selected according to manufacturer's written instructions for conditions at specific location at time of installation. Install conduit supports to allow for expansion movement.

BB. Communications Cabling Hooks:

1. Size to allow a minimum of 25 percent future capacity without exceeding design capacity limits.

260533 - 11

2. Shall be supported by dedicated support wires. Do not use ceiling grid support wire or support rods.

3. Hook spacing shall allow no more than 6 inches of slack. The lowest point of the cables shall be no less than 6 inches adjacent to ceilings, mechanical ductwork and fittings, luminaires, power conduits, power and telecommunications outlets, and other electrical and communications equipment.

4. Space hooks no more than 5 feet o.c.

5. Provide a hook at each change in direction.

CC. Flexible Conduit Connections: Comply with NEMA RV 3. Use a maximum of 72 inches of flexible conduit for recessed and semirecessed luminaires, equipment subject to vibration, noise transmission, or movement; and for transformers and motors.

1. Use LFMC in damp or wet locations subject to severe physical damage.

2. Use LFMC or LFNC in damp or wet locations not subject to severe physical damage.

DD. Mount boxes at heights indicated on Drawings. Install boxes with height measured to center of box unless otherwise indicated.

EE. Recessed Boxes in Masonry Walls: Saw-cut opening for box in center of…

This is the start of the file's text. The full file is on GovTribe.