Amendment 2_ESheets.FishlakeSO - Correct.pdf

PDF 5 MB Posted

Attached to
FISHLAKE SUPERVISOR’S OFFICE RENNOVATIONS Federal contract opportunity
Solicitation number
1240LT22R0035
Issued by
Department of Agriculture Forest Service

About this file

This is a solicitation for electrical renovations at the Fishlake Supervisor's Office. The solicitation is seeking proposals to update electrical, lighting, communications, and HVAC systems throughout the building. Key areas of work include replacing receptacles, luminaires, and controls; updating communications infrastructure including removing outdated data cabling; and removing existing HVAC equipment in the attic while installing new HVAC disconnects. Proposals are due by 1240LT22R0035. The selected contractor will work with the Department of Agriculture Forest Service Intermountain Region to complete the renovations.

View the file

Other files for this federal contract opportunity

Other files attached to FISHLAKE SUPERVISOR’S OFFICE RENNOVATIONS, newest first.
File Type Posted
Q and A Fishlake NF Supervisory Office 5.18.22.docx DOCX document
Amendment 2_Fishlake.NFSO.rennovations.Addendum.5.16.2022.docx DOCX document
Amendment 2.pdf PDF
Site Visit Sign In Sheet.pdf PDF
Amendment 1-Extend Closing Date.pdf PDF
ATTACHMENT 3_WAGE DETERMINATION.pdf PDF
1240LT22R0035.pdf PDF
ATTACHMENT 1_SPECS.FISHLAKESO.FINAL.3.2.2022.pdf PDF
Attach_4_Determination of Responsibility.pdf PDF
ATTACHMENT 2_DRAWINGS.FINAL.FISHLAKE.4.11.2022.pdf PDF
Attach_2_Paintrock Road FSSS.pdf PDF
Attach_3_Wage Determination.pdf PDF
Attach_1_Paintrock Road Improvements Drawings.pdf PDF
1240LT22R0029.pdf PDF
Attach_4_Determination of Responsibility.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL LEGEND

EXISTING LOAD CENTER/ PANELBOARD "X"

SAFETY DISCONNECT SWITCH, UNIT SERVED "X", "#a"

# AMPERE SIZED FUSES, GENERAL DUTY, NEMA 3R

UNDERGROUND ELECTRICAL LINE, NEW

EXISTING LIGHTING TRACK, SALVAGE OR NEW

LOCATION

12-INCH LADDER TRAY, REQUIRED APPURTENANCES

ALSO SHOWN ON DRAWINGS

EXISTING JUNCTION BOX OR OTHER BOX TO BE

REMOVED

ELECTRICAL CONNECTION TO PROJECTOR CEILING

BOX

HAND DRYER, SEE ARCHITECTURAL DRAWINGS

EXISTING CEILING EXHAUST FAN TO BE REMOVED

EXISTING THERMOSTAT, TO BE REMOVED. NEW

THERMOSTATS SHOWN ON MECHANICAL DRAWINGS

FAN FORCED WALL HEATER, TYPE "X"

BASE BOARD HEATER, TYPE "X"

FAN FORCED HEATER MOUNTED ON CEILING, TYPE

"X"

NEW SIDE OF POLE MOUNTED LUMINAIRES

REPLACING EXISTING LUMINAIRES ONLY, TYPE "P",

MOUNT ON EXISTING POLE (ONE POLE MUST BE

ROTATED ON BASE). SEE SHEET E110

LINEAR LUMINAIRE, TYPE "X", LOWER CASE LETTER

INDICATES SWITCH GROUP. MOUNTING STYLE:

SURFACE, AND RECESSED

MOVE EXISTING LINEAR LUMINAIRE LOWER CASE

LETTER INDICATES SWITCH GROUP. MOUNTING

STYLE: SURFACE, AND RECESSED

EXISTING LINEAR LUMINAIRE TO REMAIN, CIRCUITING

MAY BE AFFECTED AND LOWER CASE LETTER

INDICATES SWITCH GROUP. MOUNTING STYLE:

SURFACE, AND RECESSED

REMOVE LINEAR LUMINAIRE, TYPE "S" INDICATES

SALVAGE. MOUNTING STYLE: SURFACE, RECESSED,

AND WALL

LUMINAIRE, TYPE "X", LOWER CASE LETTER

INDICATES SWITCH GROUP. MOUNTING STYLE:

SURFACE, RECESSED, SUSPENDED, AND WALL

REMOVE LUMINAIRE, TYPE "S" INDICATES SALVAGE.

MOUNTING STYLE: SURFACE, RECESSED, AND WALL

EMERGENCY LUMINAIRE, TYPE "E". MOUNTING

STYLE: WALL

EXISTING EXIT SIGN, SALVAGE OR NEW LOCATION,

SINGLE FACE W/ DIRECTING ARROW(S). MOUNTING

STYLE: BACK, SIDE, AND CEILING

EXISTING EXIT SIGN, SALVAGE OR NEW LOCATION,

DOUBLE FACE W/ DIRECTING ARROW(S). MOUNTING

STYLE: SIDE AND CEILING

EXISTING TRACK LUMINAIRE, SALVAGE OR NEW

LOCATION LOWER CASE LETTER INDICATES SWITCH

GROUP.

REMOVE EMERGENCY LIGHT, TYPE "X", WITH

BATTERY

SWITCH, SINGLE POLE. TYPICAL: LOWER CASE

LETTERS INDICATE SWITCH CONTROL GROUP

SWITCH TYPICAL OF TYPE INDICATED TO BE

REPLACED, REMAIN, OR REMOVED

EXISTING SWITCH, TO BE MOVED OR NEW LOCATION

SWITCH, DIMMING, ENSURE COMPATIBILITY WITH

CONTROLS, LAMPS, AND BALLASTS

SWITCH, ELECTRIC COUNTDOWN TIMER

SWITCH, LOW VOLTAGE, COORDINATE WITH SPECIAL

EQUIPMENT (PROJECTOR CEILING BOX, OR SCREEN)

SWITCH, FUSED AT 15 AMP LOCKABLE (LOCKING MAY

BE PROVIDED BY A LOCKABLE COVER PLATE ON A

FUSED TOGGLE SWITCH)

OUTLET, GFCI BLANK FACE TO PROTECT

DOWNSTREAM ITEMS, SHALL BE ACCESSIBLE

SWITCH BOX MOUNTED PIR OCCUPANCY SENSOR,

LINE VOLTAGE TYPE. SET FOR MANUAL ON, AUTO

OFF.

OCCUPANCY SENSOR, LOW VOLTAGE TYPE TYPICAL

HOWEVER WHERE COMPATIBLE LINE VOLTAGE ALSO

ALLOWED. TYPE "U" INDICATES DUAL PIR AND

ULTRASONIC TYPE. LOWER CASE LETTER INDICATES

SWITCH GROUP. CEILING MOUNT

PHOTO CONTROL, BUTTON TYPE IN JUNCTION BOX

RECEPTACLE, DUPLEX. "T " INDICATES TO SERVE

COUNTER/WORK TOP COORDINATE HEIGHT WITH

ARCHITECTURAL DRAWINGS

RECEPTACLE TYPICAL OF TYPE INDICATED TO

REMAIN, OR REMOVE

RECEPTACLE, GFCI

RECEPTACLE, QUAD OR TWO DUPLEX, MAY INCLUDE

ADDITIONAL DESIGNATION

EXISTING DATA OUTLET TO BE REMOVED INCLUDING

CABLE AND CONNECTION AT PATCH PANEL

DATA OUTLET, "#" INDICATES THE NUMBER OF

PORTS

DATA OUTLET, 1-PORT, LOCAL CONNECTION ONLY,

DOES NOT GO TO PATCH PANEL. "C" INDICATES

INSTALLED IN PROJECTOR CEILING BOX

EXISTING CEILING MOUNTED WIFI ROUTER AND DATA

OUTLET TO BE MOVED TO SAME AREA AND ITS NEW

LOCATION

EXISTING CAT 5 DATA OUTLET TO REMAIN INCLUDING

CONNECTION TO PATCH PANEL

BRANCH CIRCUIT: o - INDICATES GROUND, LONG LINE

- "NEUTRAL" OR "GROUNDED CONDUCTOR" AND THE

SHORT LINE - "HOT" OR "LINE" CONDUCTORS

PANEL X

#a

X

E E

T T T T

J

C

J

D

X a

T

X

X

X

P

XX

X a

X a

X a

X a a

X

S a

S S

S

M

S

D

S

T

S

L

S

F

S

GFI

S

O

M

PC

GFI

HD

WIFI

NOTES

SEVERAL SYMBOLS SHOWN ON DEMOLITION AND ELECTRICAL PLANS

ARE THE SAME. A NEARBY LETTER INDICATES THE FOLLOWING:

"S" - DEMOLITION: SALVAGE FOR REUSE, IN SOME CASES

MAY ALSO ALLOW FOR REWORK OF CIRCUITS TO FEED

NEW EQUIPMENT NEAR THE SAME LOCATION.

NEW: INDICATES THE PROPOSED LOCATION FOR THE

SALVAGED EQUIPMENT WITH WIRING TO ALLOW FOR

PROPER OPERATION.

"M" - MOVE THE DEVICE TO A NEARBY LOCATION WITH

ADJUSTMENTS OF THE RELATED CIRCUITRY.

DEMOLITION: EXISTING LOCATION.

NEW: PROPOSED LOCATION.

"R" - EXISTING DEVICE TO REMAIN, MAY BE AFFECTED BY THE

MOVING OF OTHER INTERRELATED ITEMS.

"X" - REMOVE THE DEVICE (ONLY ON THE DEMOLITION PLANS).

FIRE ALARM SYSTEM LEGEND

EXISTING FIRE ALARM CONTROL PANEL, CIRCUIT,

AND MULTIPLE CONNECTIONS TO DEVICES. MOVE

OR NEW LOCATION

EXISTING HORN AND STROBE TO BE MOVED, OR

NEW LOCATION

HEAT OR SMOKE DETECTOR TO BE MOVED, OR NEW

LOCATION

FACP

F

H

INTERCOM SYSTEM LEGEND

EXISTING MASTER INTERCOM EQUIPMENT TO BE

MOVED, OR NEW LOCATION

EXISTING SPEAKER, CEILING MOUNT. MOVE,

SALVAGE, OR NEW LOCATION

EXISTING INTERCOM VOLUME CONTROL. MOVE,

SALVAGE, OR NEW LOCATION

MI

S

S

V

THE EXISTING FIRE ALARM SYSTEM MAY INCLUDE DUCT DETECTORS

FOR AIR HANDLING UNITS IN ATTIC. THESE SHALL BE REMOVED WITH

CIRCUITING TO THE FACP (ALL NEW UNITS UNDER 2000 CFM).

THE FACP HAS NOT BEEN TESTED FOR SOME TIME. UNLESS

OTHERWISE DIRECTED, IT IS NOT THE INTENT OF THIS CONTRACT TO

BRING THIS SYSTEM INTO COMPLIANCE OR UP TO CODE.

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

5/1 2/2

2 1 5:

S

AB

RO

W N

X:

\F

IS

HL

AK

E\

FI

SH

LA

KE

.S

UP

ER

VI

SO

RS

.O

FF

IC

E.

RE

MO

DE

L.

\D W

G\ E0

.F

IS

HL

AK

ES

O

- C

OR

RE

CT

.D

W G;

R-4

INTERMOUNTAIN REGION

S.BROWN 5/12/22

FISHLAKE

SUPERVISORS

OFFICE

RENOVATIONS

FISHLAKE NATIONAL

FOREST

INTERMOUNTAIN REGION

ELECTRICAL LEGEND

03/01/2022

S.BROWN

S.BROWN

D.JEPPSEN

E001 64 74

APPROVED ON 02/28/2022 - CORRECTED

ADDED MISSING ITEM TO LEGEND

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

AutoCAD SHX Text E

EXISTING PANEL A SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-5

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, RMS 105, 107, 109

20 20

LIGHTS, RMS 110, 113

LIGHTS, RMS 111, 114, 115, 116

20 20

LIGHTS, RM 112

OUTLETS, RMS 115, 116

20 20

LIGHTS, RM 108

OUTLETS, RMS 111, 114

20 20

OUTLETS, RMS 109, 111

OUTLETS, RMS 114,115

20 20

OUTLETS, RMS 107,109

OUTLETS, RM 108

20 20

OUTLETS, RMS 107, 109

OUTLETS, RMS 104, 105

20 20

OUTLETS, RMS 108, 110

OUTLETS, RMS 104, 108

20 20

OUTLETS, RMS 108, 110, 113

OUTLETS, RM 112

20 20

OUTLETS, RMS 110, 113

OUTLETS, RM 112

20 20

OUTLETS, RMS 112

OUTLETS, RM 112

20 20

OUTLETS, RM 112

OUTLETS, RM 119

20 20 FUTURE POWER POLES RM112 <UNUSED> 24

OUTLETS, RMS 119 120

20 20 <?> 26

OUTLETS, RM 120

20 20 <UNUSED> 28

29 <UNUSED> 20

20 <UNUSED>

31 <UNUSED> 20 32

33 <UNUSED> 20 34

<UNUSED> 40 20 <UNUSED>

37 38

39 40

41 42

EXISTING PANEL B SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-4

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, HALL

20 20

LIGHTS, RMS 130, 131

LIGHTS, RMS 121, 123

20 20

LIGHTS, RMS 122, 129

LIGHTS, RMS 119,120

20 20

OUTLETS, RMS 120

OUTLETS, RMS 122,

20 20

OUTLETS, RMS 121, 123

OUTLETS, RMS 122, 130

20 20

OUTLETS, RMS 123, 124

OUTLETS, RM 130 BREAK ROOM

20 20

OUTLETS, RMS 130, 131

OUTLETS, RMS 131

20 20

OUTLETS, RM 130

OUTLETS, RM132

20 20 SPARE <UNUSED> 16

17 FUTURE POWER POLES RM 132 20 20

OUTLETS, RMS 133, 139, 132 REST ROOM PLG

19 FUTURE POWER POLES RM 132 20 20

OUTLETS, RMS 139, 140

21 ELECTRICAL WATER COOLER WEST HALL 20 20

OUTLETS, RM 140

23 EXHAUST FANS REST ROOMS 20 20

EXHAUST FANS RMS 129, 130, 131

WATER HEATER, RM 122

20 20 <UNUSED> 26

27 <UNUSED> 20 20 <UNUSED> 28

220 VOLT OUTLET RM 122 20 20 220 VOLT OUTLET RM 122

31 32

220 VOLT OUTLET RM 122 20 20 <UNUSED>

35 36

<UNUSED> 20 20 <UNUSED>

39 40

41 42

EXISTING PANEL C SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-6

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, HALL

20 20

LIGHTS, RMS 124

LIGHTS, RM 136

20 20

LIGHTS, 125, 126

LIGHTS, RMS 137

20 20

LIGHTS, RMS 132 GIS LITES (DAVID+?)

LIGHTS, RMS 138

20 20

LIGHTSS, RMS 133, 134, 139, 140

OUTLETS, RMS 124

20 20

OUTLETS, RMS 126

OUTLETS, RMS 124

20 20

OUTLETS, RMS 125,126

OUTLETS, RMS 124

20 20

OUTLETS, RMS 124, 125 & H ALL

OUTLETS, RMS 124

20 20

OUTLETS, RMS GIS

OUTLETS, RMS 124

20 20

OUTLETS, RMS GIS (WANDAS COMP)

OUTLETS, RM 132

20 20

OUTLETS, RMS 139, 140 (FREDS RM +

OUTLETS, RM 136

20 20 SHUNT TRIP CONTROL 22

OUTLETS, RM 136,137

20 20

OUTLETS, ATTIC

OUTLETS, RMS

20 20 LIGHTS ATTIC 26

27 DAMPER MOTORS ATTIC 20 20 <UNUSED> 28

29 DAMPER MOTORS ATTIC 20 20 <UNUSED> 30

31 <UNUSED> 20

30 COMPUTER

33 <UNUSED> 20 34

35 <UNUSED> 20 36

<UNUSED> 20 20 <UNUSED>

39 40

41 42

TO BE BROKEN TO

TWO CIRCUITS 916

AND 18) IF

REMAINING

DOUBLED UP AFTER

DEMOLITION AND

CONSTRUCTION

EXISTING COMM ROOM PANEL SCHEDULE

TYPE: SQUARE D []

120/240 VAC

1 PHASE

A.I.C.: 22,000

SURFACE MOUNT

FEEDER: EXISTING FROM C-32,34,36

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD

(WATTS)

A B

MAIN (2 POLE WITH SHUNT TRIP)

?2

6 ?

NORTH INTERIOR COMMUNICATIONS ROOM PANELBOARD NOTES

1. THE SHUNT RIP CIRCUIT SHALL BE REMOVED FROM THE BACKFED SHUNT TRIP

MAIN BREAKER. SEE COMMUNICATIONS DEMOLITION PLAN FOR THE LOCATION

OF THE HIGH TEMPERATURE SHUT DOWN THERMOSTAT AND BREAKGLASS

DEVICES BEING REMOVED.

2. VERIFY AND COORDINATE REMOVAL OF SHUNT TRIP CIRCUIT 22 FROM

PANELBOARD C. BREAKER TO REMAIN MAY BE REUSED TO SERVE OTHER

LOADS.

3. CIRCUIT 4, 5 IS EXPECTED TO FEED THE TWISTLOCK RECEPTACLE. THE

CIRCUIT SHALL BE REPURPOSED WITH THE 2-POLE BREAKER BEING REPLACED

WITH TWO QO120 BREAKER: ONE TO FEED 120 VAC, 20 AMP RECEPTACLE

REPLACING THE TWISTLOCK RECEPTACLE, THE TO BE INSTALLED IN THE

NORTHWEST COMMUNICATIONS CLOSET (FOR SURGE PROTECTION). LABEL

BOTH RECEPTACLES WITH "UPS POWER ONLY," AND PANEL AND CIRCUIT

IDENTIFICATION. CIRCUIT 4, 5 MAY BE SWITCHED WITH CIRCUIT 7, 8.

4. CIRCUIT 6 IS EXPECTED TO FEED THE PLUG STRIP BY THE RACK IN THIS ROOM.

VERIFY AND LABEL CIRCUIT.

5. CIRCUIT 7, 8 IS EXPECTED TO BE THE SURGE PROTECTOR, BUT MAY BE

SWAPPED WITH CIRCUIT 4, 5. VERIFY AND LABEL.

CORRECTED/FINAL PANEL A SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-5

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, RMS *

20 20

LIGHTS, RMS *

LIGHTS, RMS *

20 20

LIGHTS, RMS *

OUTLETS, RMS *

20 20

LIGHTS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20 SPARE 24

OUTLETS, RMS *

20 20 * 26

OUTLETS, RMS *

20 20 SPARE 28

29 SPARE 20

20 SPARE

31 SPARE 20 32

33 SPARE 20 34

SPARE 40 20 SPARE

37 38

39 40

41 42

CORRECTED/FINAL PANEL B SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-4

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, HALL *

20 20

LIGHTS, RMS *

LIGHTS, RMS *

20 20

LIGHTS, RMS *

LIGHTS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS * <OR SPARE? SEE EXISTING

SCHEDULE>

17 * 20 20

OUTLETS, RMS *

19 * 20 20

OUTLETS, RMS *

21 ELECTRICAL WATER COOLER * 20 20

OUTLETS, RMS *

23 EXHAUST FANS REST ROOMS * 20 20 * 24

WATER HEATER, ATTIC *

20 20 SPARE 26

27 SPARE 20 20 SPARE 28

* 20 20 *

31 32

* 20 20 SPARE

35 36

SPARE 20 20 SPARE

39 40

41 42

CORRECTED/FINAL PANEL C SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-6

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, HALL *

20 20

LIGHTS, RMS *

LIGHTS, RMS *

20 20

LIGHTS, RMS *

LIGHTS, RMS *

20 20

LIGHTS, RMS *

LIGHTS, RMS *

20 20

LIGHTS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20 SPARE 22

OUTLETS, RMS *

20 20

OUTLETS, ATTIC

OUTLETS, RMS *

20 20 LIGHTS ATTIC 26

27 DAMPER MOTORS ATTIC * 20 20 SPARE 28

29 DAMPER MOTORS ATTIC * 20 20 SPARE 30

31 SPARE 20

PANELBOARD COMM ROOM (NORTH MIDDLE)

33 SPARE 20 34

35 SPARE 20 36

SPARE 20 20 SPARE

39 40

41 42

TO BE REMOVED,

SEE COMM ROOM

PANEL NOTES.

CORRECTED/FINAL COMM ROOM PANEL SCHEDULE

TYPE: SQUARE D [QO TYPE]

120/240 VAC

1 PHASE

A.I.C.: 22,000

SURFACE MOUNT

FEEDER: EXISTING FROM C-32,34,36

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD

(WATTS)

A B

MAIN (SHUNT UNUSED)

?2

OUTLET, FOR RACK MOUNTED UPS THIS ROOM

QO120

OR

OUTLET, FOR RACK MOUNTED UPS IN NW COMM RM

QO120 12

6 * PLUGSTRIP THIS ROOM ?

* SURGE PROTECTION ?

EXISTING PANEL E SCHEDULE

TYPE: GE [THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM *

GROUNDING: #4 CU GRD TO WATER PIPES AND GROUND ROD

OR CONCRETE ENCASED ELECTRODE, SEE SPECIFICATIONS

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

1 20 20 FIRE ALARM PRIM 2

3 SPARE 20 20 FIRE ALARM SUP 4

5 TELEPHONE COMP 20 20 SOUND SYSTEM 6

7 20

20 BASEBOARD HEATER

9 SPARE 20 10

11 INSIDE COMPUTER ROOM AIR COND. 20 20 12

OUTSIDE COMPUTER ROOM AIR COND. 30

60 MAIN

15 16

17 18

EXISTING PANEL M SCHEDULE

TYPE: GE [CCB, TYPE TEDS OR

TED4 BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: 18,000

FLUSH MOUNT

FEEDER: EXISTING SERVICE

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

1 ISOLATION TRANSFORMER 100 125 SPARE 2

3 ELECT. PANEL "D" 125 125 ELECT. PANEL "B" 4

5 ELECT. PANEL "A" 150 150 ELECT. PANEL "C" 6

MAIN 500

CORRECTED/FINAL PANEL E SCHEDULE

TYPE: GE [THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM *

GROUNDING: #4 CU GRD TO WATER PIPES AND GROUND ROD

OR CONCRETE ENCASED ELECTRODE, SEE SPECIFICATIONS

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

1 * 20 20 FIRE ALARM PRIM 2

3 SPARE * 20 20 FIRE ALARM SUP 4

5 TELEPHONE COMP * 20 20 SOUND SYSTEM 6

7 * 20

20 BASEBOARD HEATER *

9 SPARE * 20 10

11 INSIDE COMPUTER ROOM AIR COND. 20 20 * 12

OUTSIDE COMPUTER ROOM AIR COND. 30

60 MAIN

15 16

17 18

GENERAL NOTES

1. CIRCUIT DOCUMENTATION BEFORE DEMOLITION IS REQUIRED, SEE ELECTRICAL DEMOLITION

PLANS.

2. MULTIPLE CIRCUITS ARE BEING REWORKED/REUSED IN SOME MANNER. LIGHTING SHALL BE

KEPT SEPARATE FROM OTHER TYPES OF CIRCUITS.

3. MULTIPLE POWER WIRING METHODS MAY HAVE BEEN USED OVER THE LIFE OF THE BUILDING, NOTED WERE EMT AND FMC, HOWEVER TYPE AC OR MC CABLES MAY ALSO BE ENCOUNTERED.

THESE MAY REMAIN IN USE AND EXTENDED.

3.1. IF NMB OR SIMILAR WIRING IS ENCOUNTERED ABOVE DROP CEILING, IT SHALL BE NOTED

TO THE CONTRACTING OFFICER IF IT IS NOT BEING REMOVED AS PART OF THE GENERAL

CONSTRUCTION.

3.2. SHARED CONDUITS WITH 20 AMP 12 GAGE TYPES THWN-2, THHN, OR XHHW SHALL BE

LIMITED TO 9 CURRENT CARRYING CONDUCTORS, PLUS EQUIPMENT GROUND. IF

INCREASED TO 10 GAGE WHERE BUNDLED SHALL BE LIMITED TO 20 CONDUCTORS PLUS

EQUIPMENT GROUND.

4. NO ORPHANED BRANCH CIRCUITS SHALL BE LEFT AFTER COMPLETING CONSTRUCTION,

EXTEND TO THE APPROPRIATE PANELBOARD AND A BREAKER. PURPOSE/LOCATION SERVED

SHALL BE CLEARLY LABELED IN THE PANELBOARD DIRECTORY.

5. IT IS VERY LIKELY THAT BREAKERS WITH ABANDONED OR REMOVED CIRCUITS WILL BE

ENCOUNTERED. LABEL THESE AS "SPARE" AND ARE AVAILABLE FOR USE IN THIS CONTRACT.

PANELBOARD NOTES

6. ALL ITEMS MARKED WITH "*" SHALL HAVE THE ENTRIES INVESTIGATED AND UPDATED.

7. ROOM NUMBERS FROM EXISTING PANELS DO NOT CORRESPOND TO THIS CONTRACTS ROOM

LABELING.

8. CORRECTING/UPDATING THE PANELBOARD DIRECTORY SHALL BE BASED ON THE NEW ROOM

LABELS AND CONTRACTOR PROVIDED CIRCUIT DOCUMENTATION.

8.1. A FLOOR PLAN OF ROOM LABELS SHALL BE AVAILABLE FOR THE CONTRACTOR TO USE,

INCLUDING A CLEAN PLAN WHICH SHALL BE INCLUDED WITH THE NEW DIRECTORY IN EACH

PANELBOARD (ONLY ONE REQUIRED FOR THE ELECTRICAL UTILITY ROOM).

9. ALSO VERIFY WHAT CIRCUIT FEEDS PANELBOARD E AND PROPERLY LABEL THE CIRCUIT.

10. CURRENTLY, I AM UNAWARE OF ANY COPY MACHINE OR SIMILAR 240 VAC RECEPTACLES.

THOSE NOTED AS SUCH ARE LIKELY ABANDONED, BUT IF EXISTING AND UNUSED IN A WALL TO

REMAIN, THEY MAY REMAIN.

EXISTING PANEL MH SCHEDULE

TYPE: GE [CCB, TYPE TEDS OR

TED4 BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: 18,000

FLUSH MOUNT

FEEDER: EXISTING SERVICE

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

1 SPARE 100 100 SPARE 2

3 OUTSIDE COMP UNITS 125 125 OUTSIDE COMP UNITS 4

5 SPARE 125 6

ELECTRICAL PANEL H

HEATING UNITS AND W/TR

H/TR OR ELECTRICAL

HEATING PANEL # H

MAIN ?00

PANELBOARD M, CIRCUIT 1 MUST HAVE A VERY ISOLATED TRANSFORMER, IF UNUSED, MARK AS SPARE AND

INDICATE WHERE CONDUCTORS, IF ANY, TERMINATE.

EXISTING PANEL D SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-3

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, HALL

20 20

LIGHTS, RMS 145, 146, 147, 148, 149

LIGHTS, RMS 142, 143, 144

20 20

LIGHTS, 101, 104

OUTLETS, RM 137 SPARE

20 20

OUTLETS, RMS 136, 142

OUTLETS, RMS 137, 138

20 20

OUTLETS, RMS 142

OUTLETS, RMS 138

20 20

OUTLETS, RMS 143, 144

OUTLETS, RMS 144, 145

20 20

OUTLETS, RMS 146, 147

OUTLETS, RMS 144

20 20

OUTLETS, RMS 146, 147, 148

OUTLETS, RMS 145, 146

20 20

OUTLETS, RMS 148, 149

OUTLETS, RMS 149, 101

20 20

OUTLETS, HALL

OUTLETS, RMS 101, OUTSIDE

20 20

OUTLETS, 138

OUTLETS, RMS 101

20 20

OUTLETS, 138

CPU OUTLETS 20

20 PM 137 OUTLETS SHUNT TRIP 24

25 20 OUTLETS RM 137 26

27 OUTSIDE LIGHTS 20 20 28

29 OUTSIDE LIGHTS 20 20 30

OUTSIDE LIGHTS, CLOCK

20 20 32

20 20 220 V COPY MACHINE

35 36

20 20

39 40

41 42

CORRECTED/FINAL PANEL D SCHEDULE

TYPE: GE [NLAB, THQB TYPE BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

FLUSH MOUNT

FEEDER: EXISTING FROM M-3

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

LIGHTS, HALL *

20 20

LIGHTS, RMS *

LIGHTS, RMS *

20 20

LIGHTS, RMS *

5 SPARE * 20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, HALL *

OUTLETS, RMS *, OUTSIDE

20 20

OUTLETS, RMS *

OUTLETS, RMS *

20 20

OUTLETS, RMS *

SPARE * 20

20 SPARE * 24

25 20

OUTLETS, RMS *

27 OUTSIDE LIGHTS * 20 20 SPARE * 28

29 OUTSIDE LIGHTS * 20 20 SPARE * 30

OUTSIDE LIGHTS, CLOCK *

20 20 SPARE * 32

SPARE * 20 20 SPARE *

35 36

SPARE * 20 20 SPARE *

39 40

41 42

EXISTING PANEL H SCHEDULE (IN ATTIC)

TYPE: GE [CCB, TYPE TEDS OR

TED4 BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

SURFACE MOUNT

FEEDER: EXISTING FROM MH-7

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

WATER HEATER 30

20 BLOWER UNIT A 2

3 BLOWER UNIT E 20 20 BLOWER UNIT C 4

5 BLOWER UNIT G 20 20 BLOWER UNIT I 6

7 SPARE OR HEAT UNIT C? 20? 100 HEAT UNIT A 8

9 SPARE OR HEAT UNIT C? 100 100 HEAT #1 UNIT I 10

11 HEAT UNIT E 150

13 HEAT UNIT G 175

CORRECTED/FINAL PANEL H SCHEDULE (IN ATTIC)

TYPE: GE [CCB, TYPE TEDS OR

TED4 BREAKERS]

120/208 VAC

3 PHASE

A.I.C.: ?

SURFACE MOUNT

FEEDER:

CKT LOAD DESCRIPTION WATTS BREAKER AWG

LOAD (WATTS)

AWG BREAKER WATTS LOAD DESCRIPTION CKT

A B C

SPARE 30

12 20

FURNACE, WEST ZONE

AND OUTLET

FURNACE, EAST ZONE AND

OUTLET

20 12 12 20

FURNACE, NORTH ZONE

AND OUTLET

41500 1500

FURNACE, SOUTH ZONE

AND OUTLET

20 12 12 20

FURNACE, INTERIOR ZONE

AND OUTLET

1500 1500

WATER HEATER AND CIRC.

PUMP OUTLET

20 12 100 SPARE 8

9 SPARE 100 100 SPARE 10

11 SPARE 150

13 SPARE 175

IN PANELBOARD B, CIRCUIT 25 IS ALSO MISTAKENLY REFERRED TO AS CIRCUIT 26.

CIRCUIT 23,25 AND 24 ARE LIKELY SPARES. IT IS ALSO UNKNOWN IF CIRCUITS 28, 30, 32, 33,35, 37,39,41, 34,36, AND 38,40,42 HAVE WIRES CONNECTED, PLAN FOR FINDING WHAT THE CIRCUITS

FEED.

CIRCUIT 7 AND 9 SHOW SOME CONFUSION ON THE EXISTING DIRECTORY AS TO WHICH IS WHICH. HOWEVER THE FUZZY PHOTO OF THE FIRST

CIRCUITS BREAKER SIZE APPEARS TO BE 20 AMP IN SIZE AND THUS IS LIKELY THE SPARE OF THE TWO.

ASSUME 18,000 A.I.C.

NEW GATE OPENER TO BE FED FROM PANEL D. CONDUCTORS TO LEAVE BUILDING IN THE CONDUIT FOR THE OUTSIDE PARKING LOT LIGHTING CIRCUIT, INTERCEPT CIRCUIT AND REWORK

INTO A GRADE LEVEL HANDHOLE AND ROUTE TO GATE OPENER.

INSTALL AS 120 VAC CIRCUITS, USE ONLY A SINGLE POLE OF EACH BREAKER AS SHOWN. IF PANELBOARD DOES NOT INCLUDE A NEUTRAL AND

NEUTRAL BAR, SUBMIT COST PROPOSAL TO CONTRACTING OFFICER OF SUPPLYING OR ALTERNATIVE FEED LOCATION FOR THESE PIECES OF

EQUIPMENT.

IF CIRCUIT 7 IS NOT 20 AMP, THE WATER HEATER AND CIRC PUMP MAY BE INSTALLED ON CKT 3 BREAKER LINE A.

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

5/1 2/2

2 1 5:

S

AB

RO

W N

X:

\F

IS

HL

AK

E\

FI

SH

LA

KE

.S

UP

ER

VI

SO

RS

.O

FF

IC

E.

RE

MO

DE

L.

\D W

G\ E0

.F

IS

HL

AK

ES

O

- C

OR

RE

CT

.D

W G;

R-4

INTERMOUNTAIN REGION

FISHLAKE

SUPERVISORS

OFFICE

RENOVATIONS

FISHLAKE NATIONAL

FOREST

INTERMOUNTAIN REGION

ELECTRICAL

PANELBOARD

SCHEDULES

03/01/2022

S.BROWN

S.BROWN

D.JEPPSEN

E002 65 74

APPROVED ON 02/28/2022 - REPRINT TO

PDF BASED ON ADOBE MOVING TEXTS

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

NETWORK

A. 50-FOOT HDMI CABLE CONCEALED TO

PROJECTOR WITH EXCESS COILED AFTER

EXITING A BRUSH COVERPLATE ACCESS HOLE.

B. CAT 6 PATCH CABLE.

C. CAT 6 CABLING AND TERMINATIONS PER

SPECIFICATIONS. ONLY CONNECTS TO THE

RELATED PROJECTOR.

D. LOW VOLTAGE CABLE (1ma@5VDC) AND LOW

VOLTAGE DC RATED SWITCH. DOES NOT COME

WITH PROJECTOR CEILING BOX.

PROJECTOR

(SWITCHED)

SEE SHEET A4.07

HD

NETWORK

HD

SWITCHEDUNSWITCHED

BUILT-IN

ACCESS

HOLE

ACCESS

HOLE

S

L

D

C

A

MAIN CONFERENCE EQUIPMENT DETAIL

+24VDC

+24VDC

Common

Control Output

Control Output

Common

+24VDC

Control Output

Common

Neutral

Hot

R e d

Blk

Pack

B l k

B l u

Wht

Power

Ceiling/Wall

Ceiling/Wall

Any

Sensor

24VDC

Sensor

Any

Red

Ceiling/Wall

24VDC

Sensor

24VDC

Any

Red a d o

L

ONE OR MORE SENSORS DETAIL

NOTES:

A. UNLABELED SENSOR USE PASSIVE INFRARED TO

DETECT OCCUPANCY, LOW VOLTAGE.

B. "U" SENSOR LABEL USE PASSIVE INFRARED AND

ULTRASONIC TO DETECT OCCUPANCY, LOW VOLTAGE.

C. NUMBER OF SENSORS VARIES ON LOCATION.

D. POWER PACKS SHALL BE RATED 120% OR MORE OF

CONNECTED LOAD.

E. LABEL ON CEILING GRID POWER PACK LOCATIONS.

F. AREAS WITH A SINGLE SENSOR MAY BE 120 VAC

INSTEAD OF LOW VOLTAGE.

Green

Purple

Grey

Dimming

(0-10 VDC)

Ground

Black

White

Purple

Grey

Dimming

(0-10 VDC)

Black

White

Purple

Grey

To

Additional

LEDs

To

Additional

LEDs

Red From Power Pack

Neutral

MAIN CONFERENCE ROOM DIMMING CONTROLS WIRING

DETAILS

1. SINGLE POLE DIMMER, ENSURE COMPATIBILITY. DIMMER

SHALL HAVE INTEGRATED POWER PACK OR BE POWERED

THROUGH REMOTE POWER PACK.

2. POWER PACKS SHALL BE RATED 120% OR MORE OF

CONNECTED LOAD.

3. LABEL ON CEILING GRID POWER PACK LOCATIONS.

B

PROJECTOR CEILING BOX,

LEGRAND (877-295-3472)

ECB2SP-CR, COMES WITH

RECEPTACLES AND

PROJECTOR POLE MOUNT,

RECEPTACLES CIRCUIT NOTED

ON DRAWINGS

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

5/1 2/2

2 1 5:

S

AB

RO

W N

X:

\F

IS

HL

AK

E\

FI

SH

LA

KE

.S

UP

ER

VI

SO

RS

.O

FF

IC

E.

RE

MO

DE

L.

\D W

G\ E0

.F

IS

HL

AK

ES

O

- C

OR

RE

CT

.D

W G;

R-4

INTERMOUNTAIN REGION

FISHLAKE

SUPERVISORS

OFFICE

RENOVATIONS

FISHLAKE NATIONAL

FOREST

INTERMOUNTAIN REGION

ELECTRICAL -

CONFERENCE ROOM

AND CONTROLS DETAILS

03/01/2022

S.BROWN

S.BROWN

D.JEPPSEN

E003 66 74

APPROVED ON 02/28/2022

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

UP

(537 Sq Ft OF

SLAB DEMO)

N UTILITY

RECEPTION

S VEST. HALL 01

CONFERENCE ROOM

MENS

RESTROOM

WOMENS

RESTROOM

HALL 06

COMM EQUIPMENT RM

GENERAL STORAGE

& WAREHOUSE

HALL 05

HA

LL

SI 01 SI 02

N VEST

N 01

N 04E 06E 04E 03

S COPY RM

N 02

NI 02

BREAK ROOM

NI 02

E 05

SI 04

N 03

(SMALL CONFERENCE)

NI 01

S 06

S 05

S 04

S 03

S 02

S 01

S 07 E 01

W 05W 04W 03W 02W 01 W 06 W 07

E 02

HA

LL

HA

LL

SI 03

SI 05

STAFF OFFICE STAFF OFFICE

STAFF OFFICE

STAFF OFFICE

NW COMM RM

MOVE RECEPTACLE NORTH

OR SOUTH IF AFFECTED BY

NEW DOOR CUTOUT

ELECTRICAL DEMOLITION NOTES

1. CIRCUIT DESCRIPTIONS IN THE PANELBOARDS ARE VERY CRYPTIC REFERRING TO

NON-EXISTENT ROOM NUMBERS. CARE SHALL BE TAKEN TO DOCUMENT CHANGES AND

ADDITIONS FOR EACH CIRCUIT. USE NEW PROPOSED NUMBERING SYSTEM SHOWN

AND EXPLAINED ON SHEET SHOWING PANELBOARD SCHEDULES.

1.1. BEFORE ANY ELECTRICAL DEMOLITION, DETERMINE EXISTING CIRCUITS

LOCATIONS AND ALSO WITH LIGHTING FULLY LOADED AMPERAGE DRAW. PROVIDE

CORRECTED DESCRIPTIONS FOR EACH CIRCUIT USING NEW NUMBERING SYSTEM.

2. DEVICES ARE SHOWN IN THERE APPROXIMATE LOCATION. IT IS LIKELY THAT SOME

ITEMS WERE MISSED AND OTHERS HORRIBLY MISPLACED. VERIFY ON SITE.

2.1. CLOCK RECEPTACLES WHEN ENCOUNTERED IN WALLS TO BE DEMOLISHED SHALL

BE REMOVED. PROVIDE JUNCTION BOX ABOVE CEILING FOR CIRCUIT CONTINUITY.

2.1.1. IF IT IS DETERMINED THAT THE ABANDONED CLOCK CIRCUIT IS PERMANENTLY

ELECTRICALLY DEAD (BREAKER JUST NOT TURNED OFF), NO JUNCTION BOX

REQUIRED, REMOVE ALL CONDUIT AND CONDUCTORS BACK TO PREVIOUS AND

NEXT CLOCK RELATED DEVICE.

3. DEVICES DOWN FED FROM REMOVED DEVICES SHALL REMAIN OPERATIONAL.

DEMOLITION ALSO INCLUDES PREPARATION IN MULTIPLE LOCATIONS FOR NEW DOORS

OR SIMILAR THAT MAY AFFECT ELECTRICAL PATHWAYS OF DEVICES THAT SHALL

REMAIN OPERATIONAL.

3.1. BASED ON WHAT IS ENCOUNTERED, AVOID JUNCTION BOXES BELOW ATTIC LEVEL,

WHICH IN SOME CASES WILL REQUIRE PULLING NEW WIRE FROM THE LAST OR

NEXT DEVICE AND EXTENDING CONDUITS. CABLING METHODS ALLOWED IN THE

SPECIFICATIONS ARE ALSO ALLOWED.

3.1.1. PULLING CABLES THROUGH EXISTING UN-OPENED WALLS IS ALLOWED.

4. PRESERVE COMMUNICATIONS TO REMAIN.

5. EMPTY CONDUITS EXCEPT WHERE REQUIRED AS SPARES FOR FUTURE USE, AND

ABANDONED CABLES SHALL BE REMOVED.

6. MOBILE WALLS ARE BEING SANDWICHED IN SHEETROCK. GENERALLY DEVICES ARE

NOT SHOWN ON THESE WALLS NOTED AS "SEE NOTE 6, SHEET ED01." THERE ARE

LIKELY 4 RECEPTACLES AND CAT 5 OUTLETS WHICH SHALL BE EXTENDED TO THE NEW

SURFACE FACE PER NEC 314.22. THERE ARE LIKELY OTHER DEVICES, ANALOG PHONE,

AND ABANDONED DATA ON THEM, ABANDONED DEVICES MAY BE BURIED IF ALL

CABLING REMOVED.

7. REMOVAL OF CAT 5 DATA CABLING WHERE SHOWN OR INDICATED DUE TO THE

REMOVAL OF WALLS SHALL INCLUDE CABLES ALL THE WAY TO THE COMMUNICATIONS

CLOSET AND PATCH PANEL INCLUDING THE RELATED JACKS (IF MODULAR, TO

PREVENT REUSE).

8. THE ABANDONED ANCIENT DATA (IEEE 1284 TYPE) THAT IS SHOWN (SEE PHOTOS) AS

BEING REMOVED HAS EXTENSIVE CABLING IN THE ATTIC AND THE NORTH INTERIOR

COMM ROOM WHICH SHALL BE REMOVED.

8.1. THE RELATED PVC CONDUIT DATA PATHWAYS DO NOT REQUIRE REMOVAL AND

MAY BE REUSED AS PATHWAYS FOR ANY NEW DATA INSTALLED.

8.2. WHERE BOXES ARE LOCATED IN WALLS THAT REMAIN, CONDUIT AND BOXES MAY

BE ABANDONED-IN-PLACE, CABLING REMOVED. INSTALL BOX WITH BLANK COVER

PLATE. DOUBLE AND SINGLE GANG WILL BE ENCOUNTERED.

8.3. THESE ABANDONED BOXES AND CONDUIT MAY BE REUSED FOR NEW DEVICES

WHEN LOCATION IS APPROVED IN WRITING AS CLOSE ENOUGH TO REQUIRED NEW

DEVICES. WHEN USED FOR POWER, THE BOX MUST MEET CODE REQUIREMENTS.

9. ABANDONED ANALOG PHONE AND CABLES SHALL BE TREATED THE SAME AS

ABANDONED ANCIENT DATA (POTS - "PLAIN OLD" TELEPHONE SERVICE). THESE ARE

RUN THROUGH OUT THE BUILDING AND THE SYSTEM FOR THE MOST PART HAS BEEN

REPLACED WITH IP BASED PHONES.

9.1. EXCEPTION: TWO ANALOG PHONE LINES ARE RUN TO THE FIRE ALARM CONTROL

PANEL AND SHALL BE RELOCATED WITH PANEL AND REMAIN OPERATIONAL.

9.2. REMOVE ALL UNUSED 66 BLOCKS AND RELATED WIRING IN THE NORTHWEST COMM

ROOM (ENTRANCE FACILITY) , WITH EXCEPTION OF THE 66 BLOCK SERVING THE

FIRE ALARM PANEL, WIRING TO THE FIRE ALARM CONTROL PANEL, AND THIS 66

BLOCKS RELATED WIRING FROM THE SERVICE PROVIDER OWNED BUILDING

ENTRANCE PROTECTORS.

9.3. SEE PHOTOS. COORDINATE WITH THE GOVERNMENT TELECOMMUNICATIONS

REPRESENTATIVE.

10. POWER FOR LIGHTING IN THE SAME GENERAL AREA SHALL BE REUSED FOR NEW

LIGHTING. THERE MAY BE SITUATIONS WHERE LIGHTING BANKS ARE COMBINED WHICH

WERE FED FROM DIFFERENT CIRCUITS OR EXTENDED INTO AN AREA OF ANOTHER

CIRCUIT.

10.1. PLAN DEMOLITION OF LIGHTING FOR EVENTUAL USE OF THE LEAST LOADED

CIRCUIT WHERE THERE IS ABOUT A 50/50 CHOICE (REQUIRES AMPERAGE

READINGS IN PANELBOARD TO DETERMINE TAKEN WITH ALL LIGHTING ON).

10.2. INSPECT SALVAGED FOR REUSE LUMINAIRES, IF DAMAGED, SUBSTITUTE A GOOD

LUMINAIRE MARKED FOR DISPOSAL.

10.2.1. ALLOW GOVERNMENT TO USE OTHER EXCESS GOOD LUMINAIRES MARKED

FOR DISPOSAL, AT THE GOVERNMENTS DISCRETION, SALVAGE FOR

REPLACING OTHER NOT-IN-CONTRACT DAMAGED LUMINAIRES, IF ANY.

10.2.2. FLUORESCENT LAMPS THAT SHOW NO DARKENING AT THE ELECTRODES, MAY

BE SALVAGED FOR REUSE AT THE SITE.

10.2.3. LED BASED LAMPS SHALL BE SALVAGED AND GIVEN TO THE GOVERNMENT IF

NOT INSTALLED IN A FIXTURE MARKED FOR SALVAGE. DOCUMENT LINEAR

LEDS, IF SALVAGED OUTSIDE OF A LUMINAIRE, WITH INSTALLATION

INSTRUCTIONS (BALLAST REMAINS OR 120 VAC DIRECT CONNECT).

10.2.4. DISPOSE OF OLD AND DEAD LAMPS PROPERLY.

11. THERE IS LIGHTING OUTSIDE ON THE BUILDING THAT IS BEING REPLACED IN PLACE

THAT IS NOT SHOWN ON THIS DEMO PLAN.

12. SPEAKER (PAGING) SYSTEM TO REMAIN OPERATION. THERE MAY BE EXCESS DEVICES

(SPEAKERS AND VOLUME CONTROLS) WHICH MAY BE MOVED TO NEW LOCATIONS AND

CONTROL CHANGES DUE TO CHANGES IN ROOM SIZES. ANY EXCESS EQUIPMENT (NOT

WIRING) SHALL BE SALVAGED AND GIVEN TO THE GOVERNMENT.

12.1. ABANDONED WIRING SHALL BE REMOVED. TREAT SIMILAR TO ABANDONED

ANCIENT DATA.

13. REMOVE EXISTING MECHANICAL ELECTRICAL: FIVE LARGE ELECTRIC HEATERS AND AIR

HANDLING UNITS IN THE ATTIC AND RELATED CONDENSER UNITS ON THE NORTH

EXTERIOR OF THE BUILDING, ONE CONDENSER AND RELATED AIR HANDLING UNIT FOR

THE NORTH INTERIOR COMMUNICATIONS ROOM (REMOVE EVEN IF THIS INFORMATION

IS INACCURATE), ATTIC MOUNTED ELECTRIC WATER HEATER, THERMOSTATS, BAS

SYSTEM, AND VARIOUS EXHAUST FANS.

13.1. THE CONDUITS MAY BE REUSED, HOWEVER ABANDONED CONDUITS AND

CIRCUITS SHALL BE REMOVED.

13.2. NOT ALL THERMOSTATS ARE SHOWN. REPAIR WALLS AND PAINT TO MATCH

WHERE THERMOSTATS ARE REMOVED.

14. IN LOCATIONS WHERE REMOVED DEVICES LEAVE HOLES IN WALLS THAT REMAIN,

INCLUDING DATA RINGS WHICH SHALL BE REMOVED, THE WALLS SHALL BE REPAIRED

AND PAINTED TO MATCH.

14.1. IF THE HOLE INCLUDES A STANDARD DEVICE BOX A STANDARD SIZED BLANK FACE

PLATE MAY BE INSTALLED. OVERSIZED FACEPLATES ARE NOT ALLOWED AND

WALL SHALL BE REPAIRED.

15. NOT SHOWN ON THESE DEMO PLANS IS DEMOLITION RELATED SITE ELECTRICAL WORK.

SEE SHEET E110 FOR ONE POLE MOVE AND ONE POLE ROTATE ON EXISTING BASE.

P A

N E

L

A

J

R

P A

N E

L

B

EXTENSION CORD

TO WATER HEATER

J

X

J

X

J

X

J

X

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

J

P N

L

C

O M

M

S U

R G

E

SEE NOTE 6,

SHEET ED01

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

THIS WALL LIKELY HAS

POWER TO BE

REMOVED

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

DOOR CUTOUT

NEW LOBBY HAS THE

EXISTING CEILING

RAISED.

CONFERENCE ROOM

HAS THE EXISTING

CEILING RAISED.

THESE RECEPTACLES MAY BE BLANKED OFF

AS JUNCTION BOXES AND THE CIRCUITS

EXTENDED TO FEED DESK TOPS

THESE RECEPTACLES MAY BE BLANKED OFF

AS JUNCTION BOXES AND THE CIRCUITS

EXTENDED TO FEED DESK TOPS

DOOR CUTOUT

DOOR CUTOUT

PLUG STRIP

TWISTLOCK TO BE REPLACED

DOOR CUTOUT

D O

O R

C

U T

O U

T

DOOR CUTOUT

MAGLOCK AND

ACCESSORIES TO BE

REMOVED

PNL E

PNL M PNL MH

ABANDONED BAS SYSTEM TO

BE REMOVED AND REPLACED

PER MECHANICAL PLANS

P A

N E

L

C

J

VERIFY IF FEEDS ATTIC

DAMPER MOTORS, C-27,29

(TO REMAIN).

RELOCATING THE ATTIC

LIGHT SWITCH MAY BE

REQUIRED

PANEL D

P N

L

H

PANEL H IS IN ATTIC

EXISTING BLANKED OFF

RECEPTACLE DEMOLITION FLOOR

PLAN

16'8'4'2'02'

SEE NOTE 6,

SHEET ED01

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

5/1 6/2

2 0 8:

S

AB

RO

W N

X:

\F

IS

HL

AK

E\

FI

SH

LA

KE

.S

UP

ER

VI

SO

RS

.O

FF

IC

E.

RE

MO

DE

L.

\D W

G\

ED

.F

IS

HL

AK

ES

O

- C

OR

RE

CT

.D

W G;

R-4

INTERMOUNTAIN REGION

S.BROWN 5/12/22

FISHLAKE

SUPERVISORS

OFFICE

RENOVATIONS

FISHLAKE NATIONAL

FOREST

INTERMOUNTAIN REGION

ELECTRICAL

DEMOLITION-

RECEPTACLE FLOOR

PLAN

03/01/2022

S.BROWN

S.BROWN

D.JEPPSEN

ED01

67 74

DRINKING FOUNTAIN BEING REMOVED IN THIS

AREA. IF RECEPTACLE FED, RECEPTACLE

SHALL REMAIN. IF HARDWIRED, INSTALL

RECEPTACLE OR BLANK COVER AND NOTE

CIRCUIT IN COVERPLATE PER SPECIFICATIONS.

APPROVED ON 02/28/2022 - CORRECTED

MOBILE WALLS ELECTRICAL

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

SLAB DEMO)

N UTILITY

RECEPTION

S VEST. HALL 01

CONFERENCE ROOM

MENS

RESTROOM

WOMENS

RESTROOM

HALL 06

COMM EQUIPMENT RM

GENERAL STORAGE

& WAREHOUSE

HALL 05

HA

LL

SI 01 SI 02

N VEST

N 01

N 04E 06E 04E 03

S COPY RM

N 02

NI 02

BREAK ROOM

NI 02

E 05

SI 04

N 03

(SMALL CONFERENCE)

NI 01

S 06

S 05

S 04

S 03

S 02

S 01

S 07 E 01

W 05W 04W 03W 02W 01 W 06 W 07

E 02

HA

LL

HA

LL

SI 03

SI 05

STAFF OFFICE STAFF OFFICE

STAFF OFFICE

STAFF OFFICE

NW COMM RM

M

M

N E

W

C

O N

T R

O L S

TTTTTTTT

S S S

S

S

S

M

M

S

S S

M

M

S

M M

M M M M

M

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

S

R

M

M

M

REMOVE TWO LIGHTS

AND SWITCH.

LIGHTING CONTROLS TO

CHANGE TO CEILING

MOUNTED MOTION SENSORS

REUSE IN SAME

AREA (TYPICAL OF 4)

N E

W

C

O N

T R

O L S

DOOR CUTOUT

OTHER LUMINAIRES

TO REMAIN NEW

SWITCH LOCATION

NEW LIGHTING

CONTROLS

NEW LIGHTING CONTROLS

S

S

S

LOCATION REQUIRES REPAIR

SOFFETT TO MATCH EXISTING

NEW LOBBY HAS THE

EXISTING CEILING

RAISED.

CONFERENCE ROOM

HAS THE EXISTING

CEILING RAISED.

NEW CONTROLS,

MOTION

NEW LIGHTING,

CONTROLS,

DIMMING TO BE

ADDED

NEW LIGHTING,

CONTROLS,

DIMMING TO BE

ADDED

DOOR CUTOUT

DOOR CUTOUT

NEW LIGHTING

CONTROLS,3

SOUTH BANKS

NEW LIGHTING

CONTROLS, 3

NORTH BANKS

NEW LIGHTING

CONTROLS, MOTION

NEW LIGHTING

CONTROLS, MOTION

ATTIC LIGHT TIMER SWITCH

MUST BE MOVED TO

ACCOMMODATE NEW WALL.

S

S

S

DOOR CUTOUT

D O

T

O U

T

ATTIC AREA TYPICAL WIRING

NEW CONTROLS

S

SS

S

SS

S

S

S

DOOR CUTOUT

S

S

S

S

NEW CONTROLS,

MOTION

M

S

S

S

S

S

SS

S S

S

S

LIGHTS SPLIT TO

NEW CONTROL

1 AND POSSIBLY 2 HALL LUMINAIRES ARE AFFECTED

BY CHANGES, REMOVE FROM CIRCUIT. CONTROLS AND

THE REST OF THE CIRCUIT TO REMAIN OPERATIONAL.

16'8'4'2'02'

LIGHTING DEMOLITION FLOOR PLAN

S

M

INSTALL WEATHER-PROOF BLANK

COVERS AND SEAL AROUND TOP AND

SIDES WITH SILICONE CAULK

ALLOWING FOR A DRIP HOLE AT THE

BOTTOM. SEAL MOUNTING HOLES

WITH SILICONE CAULK COLORED TO

MATCH THE BUILDING BRICK.

SWITCH HANDLE PER SEE

NOTE 6, SHEET ED01

REQUIREMENT

IN CONJUNCTION WITH REPLACEMENT OF CEILING GRIDS, THE CONTRACT IS MODIFIED TO

REPLACE ALL LUMINAIRES WITH EXCEPTIONS AS NOTED:

A. THE LUMINAIRES SHOWN (TYPES S, M, AND TO REMAIN) SHALL ALL BE REPLACED.

B. OFFICES WITH LIGHTING NOT SHOWN (ALSO 2X4 TROFFERS) SHALL HAVE

LUMINAIRES REPLACED IN THE SAME LOCATIONS. THERE ARE A TOTAL OF 66 OF THESE.

C. HALLS THAT DO NOT HAVE LUMINAIRES SHOWN (2X2 TROFFERS) SHALL BE

REPLACED. THERE ARE A TOTAL OF 36 OF THESE.

D. LIGHTING CONTROLS (NOT SHOWN) SHALL ALSO BE REPLACED. COORDINATE WITH

CONTROL TYPES INDICATED ON SHEET E120 (THIS INCLUDES HALLWAYS WHICH

GENERALLY HAVE MULITWAY SWITCH CONTROLS AT ENDS). SWITCHES, (NOT SHOWN) ON

THIS SHEET AND SHEET E120, BEING REPLACED WITH CEILING MOUNTED MOTION

SENSORS, SHALL BE BLANKED OFF WITH A STAINLESS STEEL BLANK COVER.

E. REMOVE ALL ABANDONED CONDUCTORS, HOWEVER POWER MAY REMAIN ROUTED

THROUGH THE OLD SWITCH BOX.

F. SWITCHING IS NOT CHANGING FOR THE NW COMM AND THE N UTILITY ROOMS.

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

5/1 6/2

2 0 8:

S

AB

RO

W N

X:

\F

IS

HL

AK

E\

FI

SH

LA

KE

.S

UP

ER

VI

SO

RS

.O

FF

IC

E.

RE

MO

DE

L.

\D W

G\

ED

.F

IS

HL

AK

ES

O

- C

OR

RE

CT

.D

W G;

R-4

INTERMOUNTAIN REGION

S.BROWN 5/12/22

FISHLAKE

SUPERVISORS

OFFICE

RENOVATIONS

FISHLAKE NATIONAL

FOREST

INTERMOUNTAIN REGION

ELECTRICAL

DEMOLITION- LIGHTING

FLOOR PLAN

03/01/2022

S.BROWN

S.BROWN

D.JEPPSEN

ED02

68 74

APPROVED ON 02/28/2022 - REVISED TO

INCLUDE MORE LIGHTING CHANGES

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

SLAB DEMO)

N UTILITY

RECEPTION

S VEST. HALL 01

CONFERENCE ROOM

MENS

RESTROOM

WOMENS

RESTROOM

HALL 06

COMM EQUIPMENT RM

GENERAL STORAGE

& WAREHOUSE

HALL 05

HA

LL

SI 01 SI 02

N VEST

N 01

N 04E 06E 04E 03

S COPY RM

N 02

NI 02

BREAK ROOM

NI 02

E 05

SI 04

N 03

(SMALL CONFERENCE)

NI 01

S 06

S 05

S 04

S 03

S 02

S 01

S 07 E 01

W 05W 04W 03W 02W 01 W 06 W 07

E 02

HA

LL

HA

LL

SI 03

SI 05

STAFF OFFICE STAFF OFFICE

STAFF OFFICE

STAFF OFFICE

NW COMM RM

H

F A

C P

WIFI

S

S

S

S

S

S

F

M

REMOVE ANCIENT DATA OUTLETS AND

ALL RELATED CABLING EVERYWHERE IT IS

ENCOUNTERED, INCLUDING IN AREAS

NOT AFFECTED BY CONSTRUCTION.

BLANK OFF BOX WITH BLANK COVER

PLATE OR REMOVE AND REPAIR WALL.

SOME HAVE BEEN REMOVED BUT

CABLING REMNANTS REMAIN IN ATTIC

AND COMM ROOM WHICH SHALL BE FULLY

REMOVED.

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

REMOVE POTS (PLAIN OLD TELEPHONE OUTLETS

AND ALL RELATED CABLING EVERYWHERE IT IS

ENCOUNTERED, INCLUDING AREAS NOT AFFECTED

BY CONSTRUCTION WITH EXCEPTIONS. BLANK OFF

BOX WITH BLANK COVER PLATE OR REMOVE AND

REPAIR WALL. SOME HAVE BEEN REMOVED BUT

CABLING REMNANTS REMAIN IN ATTIC AND AT

ENTRANCE FACILITY WHICH SHALL BE FULLY

REMOVED WITH EXCEPTIONS.

EXCEPTION: FIRE ALARM PANEL, 2 CABLES AND

SEPARATE ANALOG PHONE NUMBERS WHICH SHALL

REMAIN OPERATIONAL.

S

S

S

S

WIFI

S

V

S

V

S

V

S

V

S

V

S

V

DATA TYPICALLY

REMAINS

S

S

V

S

S

V

S

V

S

S S

S

J

BREAK GLASS DEVICE AND

SHUT TRIP THERMOSTAT

TO BE REMOVED

SHUNT

T

S

V

S

S

DOOR CUTOUT

S

M

M S

S

M

M

M

M

M

M

R

NEW LOBBY HAS THE

EXISTING CEILING

RAISED.

CONFERENCE ROOM

HAS THE EXISTING

CEILING RAISED.

R

S

S

M

R

RR

R

R

R

R

R

REMAINS ON

OLD CONTROL

DOOR CUTOUT

DOOR CUTOUT

R

R R

R

R

VOLUME CONTROL

WILL BE IN OTHER

ROOM

SEE NOTE 6, SHEET

ED01

SEE NOTE 6,

SHEET ED01

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

THIS WALL LIKELY HAS

COMM TO BE REMOVED

SALVAGE SPEAKER AND

CONTROL

THIS WALL LIKELY HAS

COMM TO BE REMOVED

THIS WALL LIKELY HAS

COMM TO BE REMOVED

SEE NOTE 6, SHEET

ED01

SEE NOTE 6, SHEET

ED01

DOOR CUTOUT

ANCIENT DATA PANEL 1 TO BE

REMOVED

ANCIENT DATA PANEL 2 TO BE

REMOVED

ANCIENT DATA PANEL 3 TO BE

REMOVED

ANCIENT DATA TO BE REMOVED

POTS (VERIFY)

DATA (MOST TO REMAIN)

ANCIENT DATA

ANCIENT DATA

ANCIENT DATA

POTS (VERIFY)

PATHWAY TO REMAIN

PATHWAY TO REMAIN

ANCIENT DATA

DATA (MOST TO REMAIN)

ANCIENT DATA

DATA IS NOT ALLOWED

TO BE SUPPORTED BY

DROP CEILING. CABLES

NOT TO BE REMOVED

SHALL BE PROPERLY

SUPPORTED.

ANCIENT DATA OUTLET TO BE

REMOVED (TYPICAL)

POTS TO BE REMOVED (TYPICAL)

SERVICE PROVIDER EQUIPMENT TO REMAIN

REMOVE 66 BLOCKS AND RELATED

ABANDONED CABLES, FIRE ALARM

CONTROL PANEL COMMUNICATIONS

LINES AND RELATED 66 BLOCK SHALL

REMAIN

NORTH EQUIPMENT ROOM

(ENTRANCE FACILITY)

DATA RACKS, SEE ALSO

COMMUNICATIONS FLOOR PLAN

D O

T

O U

T

COMM PANELBOARD

TO REMAIN

SURGE ARRESTOR

TO REMAIN

MOSTLY ANCIENT DATA CABLES

TO BE REMOVED.

DOOR CUTOUT

COMMUNICATION PATHWAYS ABOVE

THE NEW CONFERENCE ROOM AREA

SHALL BE RAISED AS NEEDED TO

ACCOMMODATE NEW CEILING HEIGHT.

COMMUNICATION PATHWAYS ABOVE

THE NEW CONFERENCE ROOM AREA

SHALL BE RAISED AS NEEDED TO

ACCOMMODATE NEW CEILING HEIGHT.

COMMUNICATION PATHWAYS ABOVE

THE NEW LOBBY AREA SHALL BE RAISED

AS NEEDED TO ACCOMMODATE NEW

CEILING HEIGHT.

COMMUNICATION PATHWAYS ABOVE

THE NEW CONFERENCE ROOM AREA

SHALL BE RAISED AS NEEDED TO

ACCOMMODATE NEW CEILING HEIGHT.

S

R

S

R

S

V

R

RECEPTION AREA

FIRE ALARM CONTROL PANEL

HEAT DETECTOR

EXISTING INTERCOMM SYSTEM MOST

LIKELY HAS INTERFACE IN THE RECEPTION

AREA WHICH SHALL BE MOVED TO NEW

RECEPTION DESK LOCATION.

EXISTING INTERCOMM SYSTEM

INTERFACE IN THE RECEPTION AREA

AND CONNECTION TO INTERCOMM

SYSTEM WHICH SHALL BE MOVED TO

NEW RECEPTION DESK LOCATION.

SPEAKERS (3) ENCOUNTERED IN THE

RECEPTION AREA SHALL BE SALVAGED

AND GIVEN TO THE CONTRACTING

OFFICER.

16'8'4'2'02'

COMMUNICATIONS DEMOLITION

FLOOR PLAN

MAY REQUIRE ADJUSTING LOCATION FOR

NEW WALL, SPEAKER CONTROL IS TO BE

SPLIT

MI

VOLUME CONTROL HANDLE

PER SEE NOTE 6, SHEET

ED01 REQUIREMENT

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

5/1 6/2

2 0 8:

S

AB

RO

W N

X:

\F

IS

HL

AK

E\

FI

SH

LA

KE

.S

UP

ER

VI

SO

RS

.O

FF

IC

E.

RE

MO

DE

L.

\D W

G\

ED

.F

IS

HL

AK

ES

O

- C

OR

RE

CT

.D

W G;

R-4

INTERMOUNTAIN REGION

S.BROWN 5/12/22

FISHLAKE

SUPERVISORS

OFFICE

RENOVATIONS

FISHLAKE NATIONAL

FOREST

INTERMOUNTAIN REGION

ELECTRICAL

DEMOLITION-

COMMUNICATIONS

FLOOR PLAN

03/01/2022

S.BROWN

S.BROWN

D.JEPPSEN

ED03

69 74

APPROVED ON 02/28/2022 - CORRECTED

MOBILE WALLS ELECTRICAL

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

SLAB DEMO)

N UTILITY

RECEPTION

S VEST. HALL 01

CONFERENCE ROOM

MENS

RESTROOM

WOMENS

RESTROOM

HALL 06

COMM EQUIPMENT RM

GENERAL STORAGE

& WAREHOUSE

HALL 05

HA

LL

SI 01 SI 02

N VEST

N 01

N 04E 06E 04E 03

S COPY RM

N 02

NI 02

BREAK ROOM

NI 02

E 05

SI 04

N 03

(SMALL CONFERENCE)

NI 01

S 06

S 05

S 04

S 03

S 02

S 01

S 07 E 01

W 05W 04W 03W 02W 01 W 06 W 07

E 02

HA

LL

HA

LL

SI 03

SI 05

STAFF OFFICE STAFF OFFICE

STAFF OFFICE

STAFF OFFICE

NW COMM RM

T

T

T

T

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

X

T

DOOR CUTOUT

NEW LOBBY HAS THE

EXISTING CEILING

RAISED.

CONFERENCE ROOM

HAS THE EXISTING

CEILING RAISED.

ASSOCIATED EXHAUST FAN

ALSO TO BE REMOVED

FOR EXHAUST FAN

DOOR CUTOUT

DOOR CUTOUT

DOOR CUTOUT

D O

T

O U

T

ATTIC AREA HVAC TO BE

REMOVED, TYPICAL OF 5

DOOR CUTOUT

ASSOCIATED EXHAUST FAN

ALSO TO BE REMOVED

ASSOCIATED EXHAUST FAN

ALSO TO BE REMOVED

EXISTING GUTTERS AND DISCONNECTS

FOR CONDENSER UNITS. REMOVE ALL 5

DISCONNECTS AND WIRING TO THE

EXISTING UNITS BEING REMOVED. SEE

PHOTO.

16'8'4'2'02'

PANEL H (TO REMAIN)

LOCATION IN ATTIC

HVAC ELECTRICAL DEMOLITION

FLOOR PLAN

CONTROLS AND SPAGHETTI FACTORIES TYPICAL

GUTTERS TO REMAIN REMOVE DISCONNECTS AND CIRCUITS TO CONDENSER UNITS

CONDENSER UNITS ON

NORTHWEST END OF

BUILDING, TO BE REMOVED

5 CONDENSERS TO BE REMOVED

REMOVE EXISTING DISCONNECT FOR NORTH

CONDENSER UNIT WITH CIRCUIT AND ALL RELATED

INDOOR EQUIPMENT. BUILDING PENETRATION FOR

CONDUIT AND CONDENSING LINES SHALL BE

SEALED ACCORDING TO ARCHITECTURAL DEMO

PLANS. SEAL MOUNTING HOLES WITH SILICONE

CAULK COLORED TO MATCH THE BUILDING BRICK.

CONDENSER UNIT ON NORTH

END OF BUILDING TO BE

REMOVED

ATTIC AREA WATER HEATER TO

BE REMOVED (REPLACEMENT

LOCATION IS LIKELY DIFFERENT)

SEE SHEET ED01, NOTE 13 AND

PHOTOS THIS SHEET FOR ATTIC

EQUIPMENT.

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE NO.

DATE

PROJECT NO.

DRAWING SHEET NO.

DATENO.

REVISION / ISSUE

OFSHEET

United States Department of Agriculture Forest Service

5/1 2/2

2 1 5:

S

AB

RO

W N

X:

\F

IS

HL

AK

E\

FI

SH

LA

KE

.S

UP

ER

VI

SO

RS

.O

FF

IC

E.

RE

MO

DE

L.

\D W

G\

ED

.F

IS

HL

AK

ES

O

- C

OR

RE

CT

.D

W G;

R-4

INTERMOUNTAIN REGION

FISHLAKE

SUPERVISORS

OFFICE

RENOVATIONS

FISHLAKE NATIONAL

FOREST

INTERMOUNTAIN REGION

ELECTRICAL

DEMOLITION- HVAC

FLOOR PLAN

03/01/2022

S.BROWN

S.BROWN

D.JEPPSEN

ED04

70 74

APPROVED ON 02/28/2022 - REPRINT TO

MAKE INTERIOR WALLS VISIBLE.

AutoCAD SHX Text F

AutoCAD SHX Text O

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text S

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text V

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text P

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text T

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text A

AutoCAD SHX Text G

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text T

AutoCAD SHX Text U

AutoCAD SHX Text R

DN

N UTILITY

RECEPTION

S VEST. HALL 01

CONFERENCE ROOM

MENS

RESTROOM

WOMENS

RESTROOM

HALL 06

MAIN

COMM RM

GENERAL STORAGE

& WAREHOUSE

HALL 05

HA

LL

EAST

VESTIBULE

SI 01 SI 02

CHANGING/

NURSING

NORTH

VESTIBULE

SECURED LINK

PASS STATION

N 01

N 04E 06E 04E 03

S COPY RM

N 02

NI 03

SEASONAL WORKER

AREA

MAIL/ COPY

ROOM

BREAK ROOM

SECURE SALES AREA

PHONE CONF.

ROOM

NI 02

E 05

SI 04

N 03

(SMALL CONFERENCE)

NI 01

S 06

S 05

S 04

S 03

S 02

S 01

S 07 E 01

W 05W 04W 03W 02W 01 W 06 W 07

E 02

HA

LL

HA

LL

SI 03

EI 01

NW COMM RM

SECURED

STORAGE 2

CONF RM

STORAGE

SECURED

STORAGE 1

NEW

NEW

NEW WALL

T

T

T

T T

T

T

T

T T

T T

T

T

T

T T T T

T GFI

GFI

G F

I

T GFI

T

G

F I

T

G

F I

GFI

GFI

G F

I

T

GFI

PLUG STRIP

REPLACES TWISTLOCK

T GFI

GFI

INSTALL FOR

MICROWAVE SHELF

T

T

TT

T

G F

I

G F

I

S

GFI

FEED FROM PNL COMM

P A

N E

L

A

P A

N E

L

B

P N

L

C

O M

M

S U

R G

E

PNL E

PNL M PNL MH

P A

N E

L

C

PANEL D

EXISTING GUTTERS TO

FEED NEW DISCONNECTS

FOR HVAC EQUIPMENT

P N

L

H

PANEL H IS IN ATTIC

ACCESSIBLE FROM

NORTH WALKWAY

RECEPTACLE FLOOR PLAN

J

C

IN CEILING

PROJECTOR

MOUNT, SEE

CONFERENCE

EQUIPMENT

DETAIL

SHEET E003

ACCESS HOLE WITH BRUSHED

TYPE FACEPLATE, SEE SHEET E003

S

L

TO PROJECTOR BOX,

LABEL "PROJECTOR",

MAY SHARE BOX WITH

SCREEN CONTROL

J

C

ACCESS HOLE WITH BRUSHED TYPE

FACEPLATE, SEE SHEET E003

S

L

TO PROJECTOR BOX,

LABEL "PROJECTOR",

MAY SHARE BOX WITH

SCREEN CONTROL

CIRCUITING INFORMATION

1. THE ROOMS ARE TYPICALLY LABELED WITH THE COMPASS DIRECTION OF THE

LOCATION, "S" MEANING SOUTH, "E" MEANING EAST, ETC. WHEN FOLLOWED BY

THE LETTER "I" IT REFERS TO AN INTERIOR AREA.

2. KEEP THE TOTAL NUMBER OF RECEPTACLES ON A CIRCUIT 10 OR LESS, EXCEPT

WHERE OTHERWISE RESTRICTED.

3. PROPOSED RECEPTACLES IN ROOMS W01-W06, S01-S07, SI03, SI05, E01, E03-E06,

NI01-NI03, N03, AND N04 SHALL BE ON LOCAL EXISTING CIRCUITS FEEDING

EXISTING RECEPTACLES IN THAT OR THE ADJACENT ROOM.

4. OTHER PROPOSED RECEPTACLES:

4.1. ROOM SI04 SHALL EITHER BE ON ONE CIRCUIT WITH NO OTHER

RECEPTACLES FED OUTSIDE THE ROOM, OR, FED BY TWO OR MORE

CIRCUITS AS LONG AS IT IS LOGICAL, NOT ONE HERE, SKIP, THEN ONE THERE

SORT OF LAYOUT.

4.2. SOUTH COPY ROOM SHALL HAVE A DEDICATED CIRCUIT FOR JUST THAT

ROOMS RECEPTACLES.

4.3. E02 AND LINKPASS ROOM SHALL BE ON NEW (OR REUSED) SHARED CIRCUIT

NO OTHER RECEPTACLES SERVED.

4.4. CONFERENCE ROOM PROJECTORS, SCREENS, AND THE NORTH PROPOSED

RECEPTACLES SHALL BE ON NEW (OR REUSED) CIRCUIT NO OTHER

RECEPTACLES SERVED.

4.5. SEASONAL WORK AREA SHALL BE SERVED WITH A MINIMUM OF 3 CIRCUITS

WITH RECEPTACLES EVENLY SPLIT BETWEEN THEM.

4.6. THE BREAK ROOM SHALL BE FED WITH 5 CIRCUITS: 2 FOR THE MICROWAVES,

2 FOR THE NORTH COUNTER AND FRIDGE, AND ONE FOR THE EATING

COUNTER AND TABLE AREA.

4.7. THE DRINKING FOUNTAIN SHALL BE FED WITH THE EXISTING CIRCUIT

(EXTEND TO NEW LOCATION), AND/OR MAY BE ON THE BREAK AREA

COUNTER/TABLE CIRCUIT, OR ON THE CIRCUIT WITH THE RESTROOMS AND

JANITORS CLOSET.

4.8. THE RESTROOMS, JANITOR CLOSET, CHANGING, AND PHONE CONFERENCE

ROOM, MAY BE SERVED WITH EITHER ONE OR TWO CIRCUITS NEW OR

REUSED.

4.9. MAIL/COPY ROOM SHALL BE FED WITH TWO CIRCUITS: ONE FOR THE QUADS,

THE OTHER FOR THE COUNTER TOP RECEPTACLES.

5. LIGHTING SHALL BE ON THE SAME CIRCUITS AS THE EXISTING THAT IT IS

REPLACING TYPICALLY.

5.1. THE EXTERIOR ENTRY LUMINAIRES SHALL BE ON THE SAME EXTERIOR

CIRCUIT(S) AS THE REMOVED LUMINAIRES THAT SERVED THE SAME

PURPOSE WITH THE SAME GENERAL CONTROL (TIMED ACCORDING TO

PANELBOARD SCHEDULE), HOWEVER WITH LOCAL PHOTOCONTROL ALSO AS

SHOWN.

5.2. EXTERIOR EMERGENCY LUMINAIRES AT EACH ENTRY SHALL HAVE REMOTE

BATTERIES IN ATTIC AREA, BUT WITH PUSH TO TEST BUTTONS MOUNTED AT

60-INCHES A.F.F. IN VESTIBULES. POWER WITH UNSWITCHED LOCAL

LIGHTING CIRCUIT.

5.3. EXIT SIGNS SHALL BE POWERED BY WITH UNSWITCHED LOCAL CIRCUIT. IF

BATTERY DEAD, INFORM CONTRACTING OFFICER.

5.4. INTERIOR LUMINAIRES WITH "E" DESIGNATION, NEW, EXISTING, SALVAGED

SHALL HAVE 24/7 POWER FROM THE SAME LOCAL CIRCUIT AS THE

SURROUNDING LIGHTS. THESE ALSO SERVE AS AFTER HOURS LIGHTS AND

SHALL NOT BE SWITCHED.

6. THERE MAY BE ISSUES WITH LIGHTING CIRCUITS BECOMING UNEVENLY LOADED

IN THE MIDDLE AREA CONTAINING THE RESTROOMS, BREAKROOM, AND

SEASONAL WORK AREA. THIS AREA SHALL BE FED TWO LIGHTING CIRCUITS

MINIMUM: ONE FOR THE SEASONAL WORK AREA, THE OTHER FOR THE REST OF

THE AREAS.

7. THERE MAY ALSO BE ISSUES WITH HEAVILY LOADING THE RECEPTION AREA

LIGHTING. IF NOT FED BY IT'S OWN LIGHTING CIRCUIT, SPLIT THE AREA SO THAT

THE NEW SOUTH OFFICES AND THE SALES AREA ARE ONE CIRCUIT (THAT MAY

EXTEND FURTHER), WHILE THE RECEPTION AREA WOULD BE ON EITHER THE

HALL LIGHTING CIRCUIT, OR WITH THE OFFICES TO THE NORTH.

DRAWN

DESIGNER

STAMPS, LOGOS, AND SEALS

PROJECT NAME

DRAWING TITLE

CHECKED

ARCHIVE…