5Yakutat_Ranger_House_AsbestosMP.PDF

PDF 2 MB Posted

Attached to
Yakutat Ranger House Remodel
Solicitation number
12010918Q0078
Issued by

About this file

Attachment #5 - Asbestos Management Plan

View the file

Other files

File Type Posted
12010918Q0078_amend3.pdf PDF
12010918Q0078_amend2.pdf PDF
8Yakutat_Ranger_House_LBP_XRF_file.xls.csv CSV file
7Yakutat_Ranger_House_LBP.PDF PDF
12010918Q0078_amend1.pdf PDF
3Modular_Units_Sketches.pdf PDF
12010918Q0078.pdf PDF
4WageRate_AK180005.pdf PDF
1Photos.docx DOCX document
6EXPERIENCE_AND_CAPABILITY_QUESTIONNAIR1.docx DOCX document
2Floorplan_blg_1021_yakutatRD.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS MANAGEMENT PLAN

Yakutat Ranger House

USDA Forest Service

Alaska Region 10 Tongass National Forest Yakutat Ranger District

YEAR BUILT: 1964

AREA: 1,444 sf

BACKGROUND INFORMATION:

The Yakutat Ranger House is a three-bedroom, single story home with a 325 sf residential garage attached. The facility is used for housing.

INSPECTION:

The Yakutat Ranger House was inspected for asbestos in 1992 by Ray Wiggins, a USFS employee and certified asbestos inspector on a 4 week detail from the Coronado National Forest.

ASBESTOS SAMPLES – Yakutat Ranger House

Location Material Description Quantity

(lf, ft2, ea) Asbestos Type

Percentage Asbestos Friable (Y/N)

Kitchen, Dining Room

Yellow Square Pattern Linoleum Floor Tile

190 ft2 Chrysotile 40% N

Bathroom White Linoleum Floor Tile 30 ft2 Chrysotile 40% N Various Ceilings Popcorn Ceiling 1000 ft2 Chrysotile 5% N Crawl Space Under Floor

Mudded Pipe Joints and Elbows

- - - Assumed N

ND = non detect lf = linear feet

As a safety precaution, all asbestos containing linoleum was encapsulated in 1994. ¼” plywood was stapled over the linoleum and a non-asbestos type mastic and linoleum was placed on the plywood. Activities should be avoided that could puncture the new linoleum, risking damage to the asbestos containing linoleum.

The popcorn ceiling was encapsulated in 1994 as a safety precaution to accidental damage and fiber release. Certane 2000 – Overcoat, a bridging encapsulant, was used to cover the popcorn ceiling. Two continuous and unbroken coats were applied using airless spray equipment. Disturbing or damaging the encapsulated ceiling with drilled holes, chips, and break should be avoided.

The maintenance staff will discuss any construction, renovation, maintenance or repair involving the ACM with the asbestos coordinator in advance. The coordinator will ensure that recommended procedures and safety precautions are followed.

SIGNING:

The required identification sign for ACM’s remaining in buildings must be displayed.

The sign reads:

DANGER

CONTAINS ASBESTOS FIBERS

AVOID CREATING DUST

CANCER AND LUNG DISEASE HAZARD

REINSPECTION:

This facility was inspected by Kerri Willoughby, Environmental Engineer, in July, 2007. The popcorn ceiling has been disturbed in various places. Permanent replacement of the popcorn ceiling is recommended during the planned renovation for the building.

The required signs are not currently in place. Signs must be displayed in the building.

During the electrical inspection with electrician Jerry Patterson, it was observed that that the old romex insulation throughout the wiring in the house may contain asbestos. No samples were taken. It is recommended that no renovation to the wiring in the house take place unless a sample confirms that there is no threat from asbestos.

Pipe insulation in the attic, in the crawl space underneath the house, and the remains of an abandoned boiler chimney insulation in the garage are all suspect for asbestos. It is recommended that no renovation in these locations take place unless a sample confirms that there is no threat from asbestos.

EMERGENCY FIBER RELEASE:

In the event of an asbestos fiber release episode, contact the asbestos coordinator:

Kerri Willoughby

(907) 228-6267

APPENDIX A: Lab Results – Attached.

Yakutat Ranger House AMP.doc
Yakutat Ranger House Inspection .pdf