1-2026 01 19 - Little Creek - Structural Bid.pdf
PDF 2 MB Posted
- Attached to
- Little Creek Park Maintenance Building
- Solicitation number
- Not on record
- Issued by
- York County, Pennsylvania
About this file
This structural specifications document pertains to the Little Creek Park Maintenance Building project in Jackson Township, York County, Pennsylvania, prepared by C.S. Davidson, Inc. The project encompasses the construction of a maintenance building and is divided into four separate contracts: General Construction, Mechanical Construction, Electrical Construction, and Plumbing Construction. Sealed bids are being received online through the PennBid Program until 10:00 A.M. on Thursday, February 26, 2026, with public opening and reading of bids occurring electronically on the same date. The contract time for project completion is one hundred fifty (150) calendar days. Bidding documents are available at no cost via the PennBid Program at https://pennbid.bonfirehub.com. Jackson Township reserves the right to accept any bid or reject any or all bids, with contract awards to be made at a regularly scheduled township meeting.
The structural specifications establish design and construction requirements in accordance with the 2018 International Building Code and apply to all structural work including concrete masonry, cast-in-place concrete construction, and foundation work. Key design parameters include an allowable soil bearing pressure of 2,500 PSF, roof dead load of 25 PSF with live load of 35 PSF, ground snow load of 30 PSF, basic wind speed of 115 MPH, and seismic design category B. Concrete compressive strengths range from 3,000 to 4,500 PSI depending on application. Each bidder must provide a bid bond or certified check equal to 10 percent of the maximum bid amount payable to Jackson Township and must submit evidence of qualifications to perform the work. This project is subject to the Pennsylvania Prevailing Wage Act approved August 15, 1961 (Act No. 442, P.L. 987), as amended.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL SPECIFICATIONS AND GENERAL CONDITIONS (04-12)
GENERAL
1. Where these specifications conflict with other project specifications, these specifications shall govern.
2. C.S. Davidson, Inc. will assume no responsibility and/or liability for problems which arise from failure to follow these plans, specifications, and the design intent they convey or for problems which arise from others' failure to obtain and/or follow the Engineer's guidance.
3. All work shall be performed in accordance with local applicable codes and regulations. Appropriate safety measures satisfying local and OSHA requirements shall be provided.
4. Proper temporary bracing of all construction work in progress is the Contractor's responsibility.
5. If during demolition existing conditions do not agree with information shown on the design drawings, the Contractor shall notify the Engineer immediately.
6. The Contractor shall be responsible for the location and protection of all existing utilities during construction and the repair of any damaged facilities.
7. Sections and details shown, while drawn for specific locations, are intended to establish the general types of details to be used throughout.
8. Drawings should not be scaled. Contact the Engineer for clarification of any dimension in question.
9. Anchor bolt layout shall be performed under the direction of a professional land surveyor.
10. All dimensions shall be verified by the Contractor. Layout shall be checked and coordinated between all construction documents and specifications prior to the start of work.
11. Shop drawings prepared by the subcontractors, suppliers, etc. shall be reviewed by the Engineer for conformance with design concept only. Each shop drawing submitted shall be stamped, initialed and dated as being reviewed by the construction manager/general contractor. Work shall not begin without the review by the Engineer.
12. Any engineering design provided by others and submitted for review or record shall bear the stamp and signature of a professional structural engineer registered in the state in which the project is located.
13. Relation of Specifications and Drawings are as follows:
A. To be equal authority and priority. Should they disagree in themselves, or with each other, bids shall be based on the most expensive combination of quality and quantity of work indicated. The appropriate work, in the event of the above mentioned disagreements shall be determined by the Owner's Representative.
B. Figures take precedence over scaled measurements.
C. Large scale details take precedence over smaller scale details.
D. Architectural drawings, if applicable, shall take precedence in regard to dimensions, when in conflict with Mechanical and Structural drawings, except for the size of structural members.
E. Specifically titled drawings and sections of the specifications take precedence over indications of items in a collateral way.
14. Issued documents, other than those notated “ISSUED FOR CONSTRUCTION” and/or “100% CONSTRUCTION DOCUMENTS”, shall not be considered to be final. Budgetary exercises performed using documents other than final construction documents shall be considered preliminary.
15. Where specific products are called for (i.e. Hilti HUS anchors or DeWALT anchors), The Contractor may submit equivalent products for E.O.R. to review.
Submit data showing comparative capacities of products.
CONSTRUCTION PROCEDURES AND SAFETY REQUIREMENTS
1. The contract structural drawings and specifications represent the finished structure. Unless otherwise indicated, they do not indicate the means or methods of construction.
2. Provide all measures necessary to protect the workmen and other persons during construction. Provide all necessary measures to avoid excessive stresses and to hold the structural elements in place during construction. Such measures shall include, but not be limited to, bracing, shoring for construction equipment, shoring for earth banks, forms, scaffolding, planking, safety nets, support and bracing for cranes and hoists, guying, etc.
3. Engage properly qualified persons to determine where and how temporary precautionary measures shall be used. Observation visits to the site by structural engineer's field representative shall not include the items noted above.
4. Supervise and direct the work so as to maintain sole responsibility for all construction means, methods, techniques, sequences, and procedures. Retain the services of a professional structural engineer licensed in the state in which the project is located to design and supervise any scaffolding for workmen, and all shoring of forms and elements of the construction.
FOUNDATION CONSTRUCTION
1. Allowable soil bearing pressure (net) assumed in design is 2,500 PSF (pounds per square foot).
2. Soil bearing capacity shall be field verified by an approved soil testing agency and documented in writing to the Engineer.
3. If soil of design capacity is not encountered at footing elevations shown, excavate to a depth necessary to attain design capacity and extend foundations as required. Obtain Engineer's approval prior to lowering the foundations.
4. The bottoms of all exterior footings shall extend a minimum of 3'-0" below finished grade unless noted otherwise.
5. Excavate all foundations to reasonable exact outline and depth avoiding over-excavation and cave-in of surrounding material. Bottoms of all foundations shall be dry, soil proof-rolled, and rock surfaces leveled and cleared of loose debris prior to pouring.
6. Neatly level and trim all foundation excavations prior to setting steel.
7. Pipes extending under footings shall be placed before footing is placed and the void produced in laying the pipe shall be filled with 3,000 psi concrete.
8. Thoroughly compact all foundation and slab subgrade material prior to placement of stone bases or concrete.
9. Provide weathertight covering for all foundations after excavation; do not expose to rainwater or freezing.
10. Where foundations are formed, backfill edges immediately after form removal.
11. No fill or backfill shall be placed against retaining or foundation walls until grout or concrete has attained design strength and supporting members are in place, unless prior written approval is obtained from the Engineer.
12. All backfill shall be granular material approved by the Engineer. Backfill shall be deposited and machine compacted in 8-inch maximum layers. Compaction shall be a minimum of 95% of the maximum dry weight density at the optimum moisture content in accordance with ASTM D1557 (Modified Proctor) as verified by a testing laboratory.
13. All backfill adjacent to retaining structures shall be compacted using hand operated equipment; no heavy equipment shall be allowed within 5 feet of any wall.
14. For all foundation construction that will be exposed to freezing temperatures during construction, the bottom of all footings (interior and exterior) shall extend a minimum of 3'-0" below grade (at no additional cost to the owner). Contractor shall contact the Engineer of Record for approval to lower foundations and obtain concrete pier sizes, if necessary.
CONCRETE MASONRY CONSTRUCTION
1. All concrete masonry shall conform to the requirements of ASTM C90 unless noted otherwise. Concrete masonry construction shall conform to the requirements of ACI 530/ASCE 5/TMS 402, building code requirements for Masonry Structures, latest edition and ACI 530.1/ASCE 6/TMS 602, Specifications for Masonry Structures, latest edition, including all supplements.
2. 28 day design compressive strength of masonry (f'm) used is as follows:
A. Standard Masonry = 2,000 psi.
3. All CMU block units shall be layed up in running bond pattern, with vertical head joints located at center of units in alternate course below, unless otherwise shown on the Contract Drawings.
4. The Contractor shall be responsible for the temporary bracing of all masonry construction. Bracing shall remain in place until masonry has had sufficient time to gain design strength. Where masonry attaches to floor and/or roof systems, bracing shall remain in place until the diaphragm has been anchored in its final position.
5. Grout lifts for reinforced masonry walls shall not exceed 5' -4" in height. High lift grout procedures may be used only after written approval is provided by the Engineer.
6. All mortar shall conform to ASTM C270. Mortar shall be Type S (except Ivany Block). Mortar shall be Type M for walls below grade or walls exposed to earth.
Mortar shall be mixed to the proportions indicated in ASTM C270.
7. Grout shall conform to the requirements of ASTM C476. Fill grouted cores, bond beams, and wall reinforcement where shown on plans with 3,000 psi small aggregate concrete mix with 8"-11" slump. Grout samples shall be tested per the Cast-in-place Concrete Construction specifications.
8. All steel lintels shall be temporarily shored where a height of masonry greater than half the span of the lintel will be placed above the lintel prior to masonry gaining design strength. Shoring shall remain in place until masonry has gained design strength and all required permanent bracing is installed.
9. All steel lintels for exterior masonry shall be galvanized. Lintel sizes, unless indicated otherwise on the drawings, shall be as follows:
A. Clear opening of 3'-4" or less = (1) 5 x 3-1/2 x 5/16 angle (L.L.V.) per 4" of masonry wall thickness with 8" min. end bearing on 16" thick of solid or grouted masonry.
B. Clear opening of 6'-4" or less = (1) 6 x 3 1/2 x 3/8 angle (L.L.V.) per 4" of masonry wall thickness with 8" min. end bearing on 16" thick of solid or grouted masonry.
10. Provide vertical control joints in above grade masonry walls so that the distance between joints does not exceed the lesser of 1 1/2 times the overall wall height, or 25 feet. Control joints shall not be placed greater than 8" from a bearing plate or jamb of an opening. A control joint shall be placed at one side of an opening less than 6'-0" wide and at both sides of openings over 6'-0" wide. Provide vertical control joints at intersections of reinforced & unreinforced walls, U.N.O.
Submit a shop drawing showing control joint locations to the Engineer for approval prior to construction. Coordinate exact control joint & expansion joint locations with architectural drawings.
11. Horizontal joint reinforcement shall consist of truss type ASTM A951 cold drawn No. 9 gauge galvanized wire steel, located 16" o.c. Cross rods to be welded to side rods at 16" o.c. to form a truss. Lap splices 6" minimum. Provide horizontal reinforcing in the two courses above and below openings and at the top of walls or partitions.
12. Masonry cores below grade shall be grouted solid.
13. Head joints shall be mortared solid the full depth of the face shell. Webs shall be fully mortared at grouted cores.
14. A minimum of one course of masonry shall be grouted solid below transitions in masonry thickness.
15. Cold Weather Masonry Construction shall conform to the requirements of AC1
530.1/ASCE 6/TMS602, latest edition.
16. Masonry stair shafts and elevator shafts shall be grouted solid, unless noted otherwise.
17. Reinforcing steel shall be deformed, billet-steel conforming to ASTM A615 -
Grade 60. Welding of reinforcing steel must be approved by the Engineer and shall be performed in accordance with the requirements of the AWS Code, D1.4, Structural Welding Code - Reinforcing Steel latest edition and be performed only by qualified welders. Shop drawings for the fabrication and placement of reinforcing steel shall be submitted to and approved by the Engineer before fabrication commences.
18. Submittals required to be reviewed and approved by the Engineer prior to concrete masonry construction include, but are not limited to: Mix designs, Reinforcement Shop Drawings, Vertical Control Joint Location Plans.
19. Mortar shall be sampled and tested according to ASTM C 270, C 780, and C 1586.
20. Wet setting of reinforcing steel is prohibited unless approved by the Engineer.
DESIGN DATA
Building Code = 2018 International Building Code
Roof Load:
Dead Load = 25 PSF (includes structure weight) Live Load = 35 PSF Snow Load: (Roof Live Load May Control)
Ground Snow Load, Pg = 30 PSF Flat Roof Snow Load, Pf = 21 PSF Snow Exposure Factor, Ce = 1.0 Snow Load Importance Factor, Is = 1.0 Thermal Factor, Ct = 1.0
Wind Load:
Basic Wind Speed (3-second gust) = 115 MPH Building Category = II Exposure Category = C Internal Pressure Coefficient, GCpi = ±0.18 Wind Design Pressure (MWFRS) = 27 PSF Net Uplift Load Varies, See Load Diagram. Min. Net Uplift load = 10 PSF
Earthquake Design Data:
Building Category = II Seismic Importance Factor, Ie = I.0 Mapped Spectral Response Accelerations:
Ss = 0.152 S1 = 0.044 Site Class = D (assumed)
Spectral Response Coefficients:
SDS = 0.162
SD1 = 0.071
Seismic Design Category = B Basic Seismic Force-Resisting System = Light-Frame (Wood) Walls Sheathed with
Wood Structural Panels Rated for Shear Resistance
Design Base Shear = 2.67 kips (0.7E For ASD Load Combinations/1.0E for LRFD Load Combinations) Seismic Response Coefficient, Cs = 0.0247 Response Modification Factor, R = 6.50 Analysis Procedure = Equivalent Lateral Force Procedure
All loads indicated on the drawings are ASD loads unless otherwise noted elsewhere in the drawings.
Concrete Masonry and Concrete shall be designed per either ASD or LRFD methods; other material design methods shall be based on ASD unless otherwise indicated by the design drawings.
MIN. 28-
DAY
COMP.
STRENGTH
MAX.
W/C
RATIO
SLUMP
RANGETYPE OF CONSTRUCTION
(1) Footings, interior slabs-on-grade < 4" thk. & slabs-on-metal deck
(3) Exterior slabs, walls, beams, columns, piers & grade beams
(2) Interior slabs-on-grade > 4" thk.
3,000 PSI
4,500 PSI
4,000 PSI
0.53
0.45
0.45
3" - 6"
3" - 6"
3" - 6"
CAST-IN-PLACE CONCRETE CONSTRUCTION
1. All concrete work shall conform to the requirements of ACI 318, Building Code
Requirements for Reinforced Concrete, latest edition and ACI 301, Specifications for Structural Concrete for Buildings, latest edition, including all revisions, except as modified herein.
2. Concrete shall be supplied by a qualified ready-mixed concrete plant in accordance with the following requirements:
A. Entrained Air = 4 to 7% for all exposed concrete, footings, piers, exterior slabs, all concrete exposed to freezing temperatures, and where otherwise noted.
B. Coarse aggregate shall be:
1. Normal weight coarse aggregate - AASHTO NO. 57 stone.
Maximum aggregate size = 1.5" C. Submit mix designs to Engineer for approval. No admixtures permitted without Engineer's approval.
D. Chloride containing admixtures are not permitted.
E. Fine aggregate must be natural sand, unless approved by the Engineer.
F. Air-entraining admixtures are not permitted on trowel finished slabs.
G. For Interior Slabs-on-grade > 4" thick:
1. When specified as temperature and shrinkage reinforcement, cold-drawn steel fibers meeting ASTM A820 criteria shall be added at a minimum rate of 25 lb. / cu. yd. or macro synthetic fibers made from virgin polyolefin shall have an equivalent diameter between 0.016" and 0.05" with a minimum aspect ratio (length / equivalent diameter) of 50, and added at a minimum rate of 4 lb. / cu. yd.
2. Fibrous reinforcement shall be manufactured by SIKA, BASF, Grace, or approved equal.
3. Slabs must be laser-screened, U.N.O.
H. For Exterior Slabs <= 5" thick: 6x6 W2.9 x W2.9 welded wire reinforcement, U.N.O.
3. At Contractor's option, fly ash, ground granulated blast furnace slag, or other pozzolans may be substituted for Portland cement, up to 25% of the cementitious content. Concrete mixes using these materials must be approved by the Engineer.
4. When concrete arrives at the project with slump below that suitable for placement, as indicated by the Specifications, water may be added only if neither the maximum permissible water-cement ratio nor the maximum slump is exceeded. The water shall be incorporated by additional mixing equal to at least half of the total mixing required. Discharge of the concrete shall be completed within 1-1/2 hours, or before the truck drum has revolved 300 revolutions, whichever comes first, after the introduction of the mixing water to the cement and aggregates or the introduction of the cement to the aggregates. Truck batch slips must include time of batching, total drum revolutions upon arrival at site, and quantity of water (in gallons) per cubic yard available to be added to attain the maximum design water-cement ratio.
5. Reinforcing steel shall be deformed, billet-steel conforming to ASTM A615 - Grade
60. Welding of reinforcing steel must be approved by the Engineer and shall be performed in accordance with the requirements of the AWS Code, D1.4, Structural Welding Code - Reinforcing Steel latest edition and be performed only by qualified welders. Reinforcing steel to be welded shall conform to A706 - Grade 60.
6. When specified, welded wire fabric shall conform to ASTM A1064 and supplied in flat sheets only. Bar chairs are required at the recommended spacing for structural slabs.
7. Reinforcing steel splices shall be ACI Class B splices unless indicated otherwise.
8. Provide adequate bolsters, hi-chairs, support bars, etc., to maintain specified clearance for the entire length of all reinforcing bars. Provide accessories which are plastic tipped or galvanized with turned-up ends for reinforcement at all faces of exposed concrete, interior or exterior.
9. Shop drawings for the fabrication and placement of reinforcing steel shall be submitted to and approved by the Engineer before fabrication commences.
10. Concrete shall be placed only after approval of the reinforcement and mix designs by the acting special inspection agency or the Engineer. Contractor is responsible for coordinating inspections prior to concrete placement.
11. Schedule the pouring of foundations on the same day the excavation is completed.
12. Cure all concrete in accordance with accepted ACI Standards and conformance to
ACI 308.1, Standard Specification for Curing Concrete, latest edition, for the worst case weather conditions anticipated during the curing period. All concrete construction and procedures shall conform to the requirements of ACI 306.1, Standard Specification for Cold Weather Concreting, latest edition.
13. No aluminum of any type shall be allowed in the concrete work unless coated to prevent aluminum-concrete reaction.
14. Mechanically vibrate concrete. Slabs-on-grade need only be vibrated around floor ducts and other embedded items.
15. Do not place pipes, ducts, reglets or chases in structural concrete or composite floor systems without approval of the structural engineer.
16. Maximum free drop of any concrete = 5'-0".
17. Chamfer all exposed concrete edges a minimum of 3/4" x 3/4".
18. Provide a minimum of concrete cover for reinforcing bars as follows unless noted otherwise on drawings:
1. Footings = 3 inches earth face, 2 inches all others, U.N.O.
2. Concrete walls, beams, and piers = 2 inches earth face, 1-1/2 inches all others, U.N.O.
19. Nine (9) 4x8 test cylinders shall be prepared for every 50 cubic yards of concrete placed on any given day to represent all concrete placed on that day. Three (3) cylinders shall be tested at seven (7) days and three (3) cylinders shall be tested at 28 days for verification of concrete design strength with three (3) cylinders remaining.
20. Concrete Finishes, as defined in Chapter 5 of ACI 301, shall be as follows, U.N.O.:
1. Formed surfaces not exposed to public view: Rough-form finish
2. Formed surfaces exposed to public view: Smooth-form finish.
3. Walls as indicated: Rubbed finish
4. Typical interior commercial/industrial floor: Troweled finish
5. Floors to receive ceramic tile, portland cement, terrazzo, etc.: Scratch finish
6. Exterior slabs on grade, walkways, etc.: Non-slip broom finish
21. Provide vertical control joints in concrete walls at a maximum 30'-0" O.C. spacing.
Submit a control joint location plan to the Engineer for approval prior to construction. Control joints shall not be placed in concrete shear walls.
22. Concrete submittals required to be reviewed and approved by the Engineer prior to cast-in-place concrete construction include, but are not limited to: Mix designs, Reinforcement Shop Drawings, Control Joint Plans for Walls, and Control Joint Plans for Slabs.
23. Slabs on Grade:
A. Slabs on grade shall be placed in accordance with the requirements of ACI
302.1R.
B. Slab finishing operations shall meet ACI Class 1 (Typical), Class 5
(Warehouse) floor requirements in accordance with Chapter 8 of ACI 302.
Floors receiving a surface hardener must be finished to ACI Class 6 floor requirements.
C. A minimum floor flatness (FF) / levelness (FL) tolerance meeting ACI FF 25/ FL 20 (Typical) FF 35/ FL 25 (Warehouse) requirements shall be achieved through placing and finishing the slab per the guidelines set forth in Table 8.15 of ACI 302.1R.
D. Curing of slabs shall begin as soon as finishing operations are complete by either water curing, wet covering, or liquid membrane-forming curing compound in accordance with Chapter 9 of ACI 302.1R for a period of seven (7) days.
E. Sawcut control joints must be completed within 1 to 4 hours of finishing and to a minimum depth of 1/3 the slab thickness (1/4 for slabs with welded wire fabric). Provide joints at a maximum 15'-0" O.C. spacing Submit a sawcut joint location plan to the Engineer for approval.
F. Slab joint sealant shall be preformed electrometric sealants which meet the requirements of ASTM C920-87 (Typical), or be a two-component epoxy resin (Warehouse) epoxy resin with a minimum shore A hardness of 80 in accordance with ASTM D2240.
G. Do not allow construction equipment on newly placed slabs for a minimum of seven (7) days.
H. When strip pouring, allow seven (7) days before placing adjacent slab sections.
I. A slab on grade pre-construction conference involving the Owner, Contractor and Engineer is recommended to review installation procedures and requirements.
WOOD FRAMING
1. All work shall be performed in accordance with the National Design
Specification for Wood Construction, latest edition, as issued by the
AWC/AFPA.
2. All materials, unless noted otherwise, shall be as indicated in items 3-15.
3. All exposed wood and wood in direct permanent contact with masonry or concrete shall meet the requirements of AWPA use category UC3B. All wood exposed to ground contact shall meet the requirements of AWPA use category UC4A.
4. Studs, plates, ledgers, and bracings = Spruce pine fir No. 2 or better.
5. Joists and beams = Spruce pine fir No. 2 or better.
6. Posts and Shear Wall Chords = Southern pine No. 2 or better.
7. Moisture content of all structural lumber shall be 19% maximum as verified by stamp.
8. All hardware for pressure-treated lumber, fire-retardant-treated lumber, or other exterior lumber shall be stainless steel (grade 304 or better) or hot dipped galvanized.
A. Bolt heads and nuts bearing on wood shall be provided with standard cut washers.
B. Minimum nailed connections for wood framing members shall be in accordance with the local building code or table 2304.10.1 of the International Building Code if not noted on the project drawings.
C. All attachments to existing wood framing shall be predrilled to prevent splitting.
D. All metal wood connectors shown in the project drawings are manufactured by Simpson Strong-Tie. Installation shall be as recommended by the manufacturer. Written approval by engineer is required for substitutions.
E. All metal framing clips and fasteners shall be hot dipped galvanized after fabrication. All Simpson Strong-Tie connectors shall have ZMAX G185 galvanized coatings.
F. Lag screws shall have a minimum bending yield strength of 45,000 psi.
G. All lag bolt connections shall be predrilled with a proper size. Lead hole diameter in accordance with the AITC Timber manual.
9. Wood trusses shall comply with the following standards:
A. ANSI/TPI 1 "National Design Standard for Metal-Plate-Connected
Wood Truss Construction."
B. TPI HIB "Commentary and Recommendations for Handling, Installing and Bracing Metal Plate Connected Wood Trusses."
C. TPI DSB "Recommended Design Specification for Temporary
Bracing of Metal Plate Connected Wood Trusses."
10. Wood roof truss manufacturer shall submit to the Engineer for review, shop drawings and design calculations sealed by a professional engineer licensed in the state in which the project is located. Wood roof trusses shall be designed for the loads indicated in items 12-15.
11. For roof trusses greater than 60 feet in length, a qualified registered design professional shall provide a design for temporary construction bracing (restraint) and permanent truss bracing (restraint).
12. All wind loads and snow loads, including balanced, unbalanced, drift and sliding snow, determined using the the most recent applicable version of the International Building code (IBC), as referenced in the 'Design Data'.
13. Minimum Top chord live load = 35 psf
14. Top chord dead load = 10 psf
15. Bottom chord dead load = 15 psf
16. Sheathing:
A. Roof Sheathing = Exterior, APA rated sheathing 40/20, min. 19/32" thick, U.N.O.
B. Floor Sheathing = Interior, APA rated sheathing 48/24, min. 23/32" thick, U.N.O.
C. Structural Wall Sheathing = Interior or exterior as applicable, APA structural 1 rated sheathing Wall-16, min. 15/32" thick, U.N.O.
D. Non-structural Wall Sheathing = Interior or exterior as applicable, APA rated Sheathing Wall-24, min. 15/32" thick, U.N.O.
E. APA Rated OSB, can be substituted for structural or non- structural interior and exterior wall & roof sheathing.
17. Roof and floor sheathing shall be nailed to framing members with 8d nails according to the following patterns:
A. At supported edges of each sheathing panel, nails shall be spaced at
6" o.c. max., U.N.O.
B. At intermediate supports of each sheathing panel, nails shall be spaced at 12" o.c. max., U.N.O.
C. Sheathing panels shall be placed with long dimension of the panel spanning between framing members.
D. The short ends of the sheathing panels shall be staggered so that they are not continuous.
18. Wall sheathing shall be nailed to framing members with 8d nails according to the following patterns:
A. At supported edges of each sheathing panel, nails shall be spaced at
6" o.c. max., U.N.O.
B. At intermediate supports of each sheathing panel, nails shall be spaced at 12" o.c. max., U.N.O.
C. Sheathing panels for shear wall shall not be less than 4'x8', except at boundaries and changes in framing, and framing members or blocking shall be provided at the edges of all panels.
DELEGATED DESIGNS/SUBMITTALS
1. Unless otherwise noted in the construction documents, shop drawings and calculations shall be required on the following items:
A. Shoring and Bracing for Building Elements (calculations*) B. Concrete Reinforcement (shop drawings) C. Masonry Reinforcement (shop drawings) D. Pre-engineered Wood Trusses (shop drawings* and calculations*)
2. Contractor shall allow for Engineer's review time of 10 business days. If a submittal is needed sooner please note in submittal and the Engineer will make an effort meeting the request in a timely manner. In an effort to coordinate and meet the demands of the project schedule, the Contractor shall send the Engineer of Record a submittal schedule for review and comment.
3. Submittals (shop drawings) noted with a (*) above and all calculations shall be signed and sealed by an Engineer registered in the state in which the project is located.
4. Contractor shall submit all submittals noted above to the code official at their request.
POST INSTALLED ANCHORS
1. All adhesive anchors (unless specifically noted otherwise on plans or details) to be
Hiti HIT-HY 200 Safe Set, DeWALT AC200+, or approved equal adhesive anchoring system with either threaded rods or rebar and installed per manufacturer's written instructions.
(Refer to table below for minimum embedment depth)
2. Minimum embedment depth may vary depending on site conditions, adjacent fasteners, and edge distances. Final anchor size, location and embedment depths must be approved by a licensed professional engineer.
3. All adhesive anchors (U.N.O.) in masonry to be Hilti HIT-HY 70, DeWALT AC100+ Gold, or approved equal masonry adhesive anchoring system with threaded rods and metal screen tubes installed per manufacturer's written instructions. Anchors shall be 5/8" diameter minimum, embedment depth of 6" minimum, U.N.O.
4. All expansion anchors (unless specifically noted otherwise on plans or details) to be Hilti Kwik Bolt TZ, DeWALT Power-Stud+ SD2, or approved equal expansion anchors installed per manufacturer's written instructions.
POST INSTALLED ANCHOR MIN. EMBED. DEPTH
TABLE
INTO UNCRACKED, NORMAL WEIGHT, REINFORCED
CONCRETE, U.N.O.
REBAR - ANCHOR
SIZE
MIN. EMBED.
DEPTH
#4 - 1/2"⌀
#5 - 5/8"⌀
3"
3 1/2"
LEGEND OF ACRONYMS & ABBREVIATIONS
& USE FOR "AND" WHEN APPROPRIATE
@ USE FOR "AT" WHEN APPROPRIATE
A.C.T. ACOUSTICAL CEILING TILE
ADDL. ADDITIONAL
A.F.F. ABOVE FINISHED FLOOR
ALUM. ALUMINUM
ARCH. ARCHITECTURAL
BL BUILDING LINE
BLDG. BUILDING
BLK. BLOCK
B.O.F. BOTTOM OF FOOTING
BRG. BEARING
BTWN. BETWEEN
C. CARPET
C.I.P. CAST-IN-PLACE
CL CENTERLINE
CLG. CEILING
CLR. CLEAR
CMU CONCRETE MASONRY UNIT
COL. COLUMN
CONC. CONCRETE
CONT. CONTINUOUS
D. OR DP. DEEP
db REINFORCING BAR DIAMETER
DIA. DIAMETER
DIM. DIMENSION
DN. DOWN
DWG. DRAWING
EA. EACH
E.F. EACH FACE
ENG. ENGINEER(S) / ENGINEERING
ELEC. ELECTRIC / ELECTRICAL
ELEV. ELEVATOR
EQ. EQUAL
EQUIP. EQUIPMENT
E.W. EACH WAY
EX. EXISTING
EXT. EXTERIOR
F.E. FIRE EXTINGUISHER
F.E./C FIRE EXTINGUISHER WITH CABINET
F.F. FINISHED FLOOR
F.G. FINISHED GRADE
FIB. FIBERGLASS
FIN. FINISH(ED)
FLR. FLOOR
FTG. FOOTING
GA. GAUGE
GALV. GALVANIZED
GYP. GYPSUM
H.A.S. HEADED ANCHOR STUD
HGT. HEIGHT
H.M. HOLLOW METAL
HORIZ. HORIZONTAL
HVAC HEATING / VENTILATION / AIR CONDITIONING
I.F. INSIDE FACE
INSUL. INSULATION
INT. INTERIOR
L. LENGTH
L.L.H. LONG LEG HORIZONTAL
L.L.V. LONG LEG VERTICAL
MAX. MAXIMUM
MET. METAL
MFG. MANUFACTURER
MIN. MINIMUM
MISC. MISCELLANEOUS
N.I.C NOT IN CONTRACT
NO. NUMBER
O.C. ON CENTER
O.F. OUTSIDE FACE
PennDOT PENNSYLVANIA DEPT. OF TRANSPORTATION
PL. PLATE
PLF POUNDS PER LINEAL FOOT
PNT. PAINT
PWD. POWDER
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RAD. RADIUS
REQ. REQUIRED
REINF. REINFORCING
RET. RETURN
SC SLIP CRITICAL
SECT. SECTION
SIM. SIMILAR
SLR. SEALER
SPC. SPACE
S.S. STAINLESS STEEL
STL. STEEL
T&B TOP AND BOTTOM
THK. THICK
T.O.F. TOP OF FOOTING
T.O.S. TOP OF STEEL
T.O.W. TOP OF WALL
TYP. TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
V. VINYL
VAR. VARIES
V.C.T. VINYL COMPOSITION TILE
VERT. VERTICAL
W. WIDE / WIDTH
W/ WITH
WD. WOOD
W.W.R WELDED WIRE REINFORCING
- REINFORCED MASONRY WALL
- CONCRETE
- PROPOSED CONDITIONS
- EXISTING CONDITIONS
- SECTION MARK
GENERAL LEGEND
"TEXT"
"Text"
S1
SIM
- WOOD SHEAR WALL
CHECK EACH
THAT APPLIES
TYPE OF SPECIAL INSPECTION
OR OBSERVATION CREDENTIALS
INSPECTION OF STEEL CONSTRUCTION
SECTION 1705.2
INSPECTION OF CONCRETE CONSTRUCTION
SECTION 1705.3
INSPECTION OF MASONRY CONSTRUCTION
SECTION 1705.4
INSPECTION OF WOOD CONSTRUCTION
SECTION 1705.5
INSPECTION OF SOIL CONSTRUCTIONS
SECTION 1705.6
INSPECTION OF DRIVEN DEEP FOUNDATIONS
SECTION 1705.7
INSPECTION OF CAST-IN-PLACE DEEP FOUNDATIONS
SECTION 1705.8
INSPECTION OF HELICAL PILE FOUNDATIONS
SECTION 1705.9
INSPECTION OF FABRICATED ITEMS
SECTION 1705.10
INSPECTION FOR WIND RESISTANCE
SECTION 1704.6;1705.13
INSPECTION OF SPRAYED FIRE-RESISTANT MATERIALS
SECTION 1705.14
INSPECTION OF MASTIC AND INTUMESCENT FIRE-RESISTANT
COATINGS
SECTION 1705.15
INSPECTION OF EXTERIOR INSULATION AND FINISH SYSTEMS
(EIFS)
SECTION 1705.16
INSPECTION OF FIRE-RESISTANT PENETRATIONS AND JOINTS
SECTION 1705.17
TESTING OF SMOKE CONTROL
SECTION 1705.18
ACI AMERICAN CONCRETE INSTITUTE CERTIFIED CONCRETE
FIELD TESTING TECHNICIAN
AWS AMERICAN WELDING SOCIETY CERTIFIED WELDING INSPECTOR
ASNT AMERICAN SOCIETY OF NON-DESTRUCTIVE TESTING
AWCI ASSOCIATION OF WALL AND CEILING INDUSTRIES
MCA MODEL CODE AGENCY (ICC,BOCA,SBCCI, ICBO)
SPECIAL INSPECTION CERTIFICATION
PA PROFESSIONAL ARCHITECT (CURRENTLY LICENSED)
PE PROFESSIONAL ENGINEER (CURRENTLY LICENSED)
OTHER SPECIALIZED TRAINING COURSEWORK OR OTHER BASIS FOR
COMPETENCY DEEMED ACCEPTABLE
X
X
X
X
DRAWING LIST
SHEET
NUMBER SHEET NAME
S-001 GENERAL NOTES
S-002 DIAGRAMS & HEADER PLANS
S-101 STRUCTURAL PLANS
S-201 FOUNDATION DETAILS
S-301 WOOD FRAMING DETAILS
S-401 SECTIONS
C O
N T
A C
T I N
F O
R M
A T
IO
N
D E
S
IG
N
M U
L A
G R
O U
P
C
O T
T A
G E
H
IL
L R
O A
D
Y O
R K
P A
.8
.0
B L A
IR
L
E H
M A
N
H
A N
O V
E R
R O
A D
Y O
R K
P
A
L
IT
T L
E C
R E
E K
P A
R K
M A
IN
T
E N
A N
C E
B U
IL
D
IN
G
G E
N E
R A
L N
O T
E S
S-001
N E
W C
O N
S T
R U
C T
IO
N
F O
R
.8
.2 .0
R E
C O
R D
O F
IS
S
U E
D A
T E
IS
S
U E
R E
V
.1
.1
IS
S U
E D
F O
R P
E R
M
IT
.0
.1
IS
S U
E D
F O
R B
ID
01.19.2026
NOTE:
LOADS INDICATED ARE THE FULL UPLIFT. FOR UPLIFT ON JOIST, SUBTRACT 15 PSF
(0.6 DEAD LOAD) FROM UPLIFT PRESSURES INDICATED FOR NET UPLIFT.
WIND UPLIFT TABLE
TRIBUTARY
AREA (SQ. FT)
ZONE 1
(PSF)
ZONE 2
(PSF)
54.6 79.6 94.6
82.054.6 69.6
32.0 54.6 64.6
100 17.0 44.6 49.6
ZONE 3
(PSF)
66.9
66.9
54.5
42.0
ZONE 4
(PSF)
106.9
94.4
74.4
59.4
ZONE 5
(PSF)
WOOD WALL HEADER SCHEDULE
HEADER
DESIGNATION WALL TYPE SECTIONS
H1 2x6 STUD
WALL
(3) 2x10 W/ 2x6 TOP PL.
CLEAR OPENING
REFER TO
PLAN FOR
LOCATION
SIZE
(3) 2x6 W/ 2x6 TOP PL.
MIN. NO. OF
JACK
STUDS
(1) 2x6
(2) 2x6
MIN. NO.
OF KING
STUDS
(1) 2x6
(1) 2x6
1/2" PLYWOOD, TYP.
NOTES:
1. COORDINATE EXACT LOCATIONS, LENGTHS AND HEIGHTS WITH ARCHITECTURAL DRAWINGS.
2. ALL THREE PLY MEMBERS SHALL BE FACE FASTENED TOGETHER W/ 12d-16d NAILS @ 12" O.C. TOP & BOTTOM STAGGERED
ON OPPOSITE SIDES (E.S. STAGGERED) OR 1/4" DIA. SDS x (4" LONG FOR 4 1/2" WIDE MEMBERS OR 5" LONG FOR 5 1/4" WIDE
MEMBERS) @ 24" O.C. TOP & BOTTOM STAGGERED
3. ALL TWO PLY MEMBERS SHALL BE FACE FASTENED TOGETHER W/ 12d-16d NAILS @ 12" O.C.
(2) ROWS TOP & BOT. OR 1/4" DIA. SDS SCREWS x3 3/8" LONG TOP & BOT @ 24" O.C.
5 1/2"
2x6 STUD
WALL
2x6 STUD
WALL
(3) 1.75x11.25 2.0E LVL's W/ 2x6 TOP PL.
(2) 2x6 (2) 2x6
H2
H3
/4
1/8" PLYWOOD, TYP.
1/2" PLYWOOD, TYP.
/4
5 1/2"
(3) 1.75x14 2.0E LVL's W/ 2x6 TOP PL.
(3) 2x6 (1) 2x6 2x6 STUD
WALL
H4 1
1/8" PLYWOOD, TYP.
REFER TO
PLAN FOR
LOCATION
REFER TO
PLAN FOR
LOCATION
REFER TO
PLAN FOR
LOCATION
23 3
23 3
/8
45 5
H2
H
H
H
H3
H2
H2H2
H
WDSW1
25' - 0"
W D
S W
W D
S W
WDSW2
11' - 6"
WDSW2
8' - 0"
H4
(2) 2X6 POSTS
(3) 2X6 POSTS(2) 2X6 POSTS (2) 2X6 POSTS
(2) 2X6 POSTS
6X6 POSTS
H2
(2) 2X6
POSTS
S-002A
W A
L L
O P
E N
IN
G
S
HEADER, REFER TO WD.
WALL HEADER SCHEDULE
CRIPPLE STUD, MATCH
WALL SPACING
BOT. PLATE
NOTES:
1. PROVIDE SIMPSON A35 CLIP ON E.S., INSTALL PER MFG. SPECS.
2. ALL JACK STUDS AND KING STUDS SHALL BE NAILED AS NOTED IN THE
TYPICAL NAILING DIMENSION AT BUILT-UP WOOD COLUMNS ON SHEET S3.2.
REFER TO NOTE
1, TYP.
JACK STUD, 2x STUD TO MATCH
WALL FRAMING MIN., REPLACE
WITH COLUMN WHERE INDICATED
KING STUD,
2x STUDS TO MATCH
WALL FRAMING
HEADER, REFER TO WOOD WALL HEADER SCHEDULE
KING STUD, 2x STUDS TO
MATCH WALL FRAMING
U.N.O., REFER TO WD.
WALL HEADER
SCHEDULE
2x SILL PLATE, DOUBLE 2x SILL PLATE REQ'D. AT
OPENINGS GREATER
THAN 6'-4" IN WIDTH,
REFER TO WD. WALL
HEADER SCHEDULE
HEADER BOT. PLATE
JACK STUD, 2x STUD TO
MATCH WALL FRAMING
MIN., REFER TO WD. WALL
HEADER SCHEDULE
KING STUD, 2x STUDS TO
MATCH WALL FRAMING U.N.O.,
REFER TO WD. WALL HEADER
SCHEDULE
2x SILL PLATE, DOUBLE 2x SILL
PLATE REQ'D. AT OPENINGS
GREATER THAN 6'-4" IN WIDTH,
REFER TO WD. WALL HEADER
SCHEDULE
HEADER, REFER TO WD.
WALL HEADER SCHEDULE
JACK STUD, 2x STUD TO
MATCH WALL FRAMING
MIN., REFER TO WD.
WALL HEADER
SCHEDULE
DOUBLE
TOP PLATE
KING STUD, 2x STUDS TO
MATCH WALL FRAMING U.N.O.,
REFER TO WD. WALL HEADER
SCHEDULE
HEADER, REFER TO WD.
WALL HEADER SCHEDULE
DIAPHRAGM PANEL
(NORMALLY 4' x 8' ) LAY IN A
STAGGERED JOINT PATTERN
CONT. OVER 2 OR MORE
SPANS.
REFER TO TYP. HOLD-
DOWN ANCHOR DETAIL,
THIS SHEET
HOLD-DOWN ANCHOR,
REFER TO WOOD SHEAR
WALL SCHEDULE
CHORD STUDS, REFER
TO SHEAR WALL
SCHEDULE
PROVIDE BLOCKING (TO
MATCH WALL STUDS) AT ALL
PANEL EDGES ONLY WHERE
NOTES IN THE SHEAR WALL
SCHEDULE
EDGE NAILING
NAILING AT INTERMEDIATE SUPPORTS
2X6 WALL STUDS
NOTE:
REFER TO WOOD SHEAR WALL SCHEDULE FOR
EDGE AND FIELD NAILING REQUIREMENTS. THE
USE OF STAPLE EQUIVALENTS IS PROHIBITED.
REFER TO TYP. HOLD-
DOWN ANCHOR DETAIL
FOUNDATION
HOLD-DOWN ANCHOR,
REFER TO WOOD SHEAR
WALL SCHEDULE
CHORD STUDS, REFER
TO SHEAR WALL
SCHEDULE
PROVIDE BLOCKING (TO
MATCH WALL STUDS) AT ALL
PANEL EDGES ONLY WHERE
NOTES IN THE SHEAR WALL
SCHEDULE
DIAPHRAGM PANEL
(NORMALLY 4' X 8') LAY IN A
STAGGERED JOINT
PATTERN CONT. OVER (2)
OR MORE SPANS
EDGE NAILING
NAILING AT INTERMEDIATE SUPPORTS
2X6 WALL STUDS
AT TOP OF OPENING PROVIDE (2) 2X6 WD.
BLOCKING & SIMPSON CS20 COIL STRAP
CONT. W/ (8) 0.131" X 2 1/2" NAILS MIN.
EACH END; BETWEEN ENDS NAIL EVERY
HOLE STAGGERED SIDES
WINDOW OPENING
IN SHEAR WALL
NOTE:
REFER TO WOOD SHEAR WALL SCHEDULE FOR
EDGE AND FIELD NAILING REQUIREMENTS. THE
USE OF STAPLE EQUIVALENTS IS PROHIBITED.
C O
N T
A C
T I N
F O
R M
A T
IO
N
D E
S
IG
N
M U
L A
G R
O U
P
C
O T
T A
G E
H
IL
L R
O A
D
Y O
R K
P A
.8
.0
B L A
IR
L
E H
M A
N
H
A N
O V
E R
R O
A D
Y O
R K
P
A
L
IT
T L
E C
R E
E K
P A
R K
M A
IN
T
E N
A N
C E
B U
IL
D
IN
G
D
IA
G R
A M
S
H E
A D
E R
P L
A N
S
S-002
N E
W C
O N
S T
R U
C T
IO
N
F O
R
.8
.2 .0
NOT TO SCALE S-002
C
TYPICAL WOOD SHEAR
WALL ELEVATION
DETAIL
NOT TO SCALE S-002
B
WALL OPENINGS LESS
THAN 12'-0"
NOT TO SCALE S-002
AWALL OPENINGS - 12'-0"
WOOD SHEAR WALL SCHEDULE
SHEAR WALL PANEL HOLD DOWNS
CHORD STUDS
SILL ANCHORAGE
REMARKS
MARK LENGTH THK. (IN.) RATING
BLOCKED PANEL
EDGES REQUIRED
NUMBER OF
SIDES
EDGE
NAILING
TYPE ANCHOR DIA. (IN.) ANCHORAGE TYPE SPACING (IN.)
WDSW1
REFER TO
PLAN
7/16"
WOOD STRUCTURAL
PANELS
Yes ONE 8d @ 4" O.C. HDU2-SDS2.5 5/8" DIA.
SSTB20 ANCHOR
BOLT
(2) 2x6
1/2" DIA.
J-BOLT
24" O.C.
WDSW2
REFER TO
PLAN
7/16"
WOOD STRUCTURAL
PANELS
Yes ONE 8d @ 4" O.C. HDU8-SDS2.5 7/8" DIA.
SSTB28 ANCHOR
BOLT
(3) 2x6
1/2" DIA.
J-BOLT
24" O.C.
1/8" = 1'-0"
WIND UPLIFT DIAGRAM
1/8" = 1'-0"
HEADER AND SHEAR WALL PLAN
P L A
N N
O R
T H
P L A
N N
O R
T H
NOTES:
1. EDGES OF ALL SHEATHING PANELS SHALL BE FULLY BLOCKED, U.N.O. IN SHEAR WALL SCHEDULE ABOVE. SHEAR WALL BLOCKING CAN BE INSTALLED ON THE FLAT.
2. ANCHOR BOLTS AND HOLD DOWNS REFERENCED ABOVE ARE BY SIMPSON STRONG TIE, OR APPROVED EQUAL. INSTALL PER MANUFACTURER'S REQUIREMENTS.
3. AT ALL INTERMEDIATE SUPPORTS EACH SHEATHING PANEL NAILING SHALL BE SPACED AT 12" ON CENTER, MAXIMUM, U.N.O. ABOVE.
4. SILL PLATES AND TOP PLATES SHALL BE CONTINUOUS. CONTACT ENGINEER OF RECORD FOR SOLUTIONS IF CONDITION IS NOT MET.
5. IN LIEU OF SIMPSON TITEN ANCHORS, 1/2" DIAMETER F1554 CAST-IN ANCHORS MAY BE USED. ALL ANCHORS SHALL HAVE A STEEL PLATE WASHERS. COORDINATE WITH
TYPICAL SHEAR WALL HOLD DOWN DETAIL ON WASHER SIZE. THE EDGE OF THE PLATE WASHER SHALL EXTEND TO WITHIN 1/2" OF THE EDGE OF BOTTOM PLATE ON
SHEATHED SIDE.
R E
C O
R D
O F
IS
S
U E
D A
T E
IS
S
U E
R E
V
.1
.1
IS
S U
E D
F O
R P
E R
M
IT
.0
.1
IS
S U
E D
F O
R B
ID
NOT TO SCALE S-002
D
TYPICAL WOOD SHEAR
WALL ELEVATION W/
OPENING IN SHEAR
WALL DETAIL 01.19.2026
60' - 1 1/4"
7 5/8"
58' - 10"
7 5/8"
/4
/8
/8
WF2.5 (-2' - 8")
W F
.5
-2
W F
.5
-2
WF2.5 (-2' - 8")
B
S-201
TYP.
A
S-201
TYP.
PROVIDE POLYDRAIN PRE-
SLOPED TRENCH DRAIN, OR
APPROVED EQUAL; REFER TO
PLUMBING DWGS.
FLOOR SLOPE
FLOOR SLOPE
C
S-201
TYP.
L A
D D
E R
T R
U S
S
O .C
L A
D D
E R
T R
U S
S
O .C
WOOD ROOF TRUSSES @ 24" O.C., MAX.
S-401
RIDGE
T R
U S
S M
A N
U F
A C
T U
R E
R
C
O O
R D
W
R
O O
F
ASSUMED ATTIC SPACE AT
ROOF TRUSS BOTTOM
CHORD; REFER TO ROOF
TRUSS ELEVATION
ATTIC LADDER TO BE
COORDINATED W/ OWNER
WDSW1
WDSW1
WDSW2 WDSW2
WDSW2
A
S-301
TYP.
A
S-301
TYP.
B
S-301
TYP.
CONNECT GARAGE DOORS
TO 2X WOOD JAMBS PER
MANUFACTURER'S
SPECIFICATIONS, TYP.
HORIZONTAL TRACK SUPPORT
FOR GARAGE DOORS TO BE
SUPPORTED FROM ROOF
TRUSSES ABOVE PER
MANUFACTURER'S
SPECIFICATIONS, TYP.
MASONRY REINFORCING SPLICE
LENGTH SCHEDULE
REINF. SIZE VERT. OR HORIZ. (IN.)
#3 27
#4 36
#5 45
NOTES:
1. WHEN SPLICING BARS OF DIFFERENT SIZES
USE SPLICE LENGTH FOR LARGEST BAR.
2. MINIMUM HOOK LENGTH EQUALS 16db FOR
NO. 3-8 BARS & 17db FOR NO. 9,10&11 BARS.
3. SPLICE LENGTHS GIVEN ARE MINIMUM,
U.N.O.
12 * db
17db (FOR NO. 9-11 BAR)
16db (FOR NO. 3-8 BAR)
CONCRETE REINFORCING SPLICE LENGTH SCHEDULE
REINF. SIZE
3000 psi
#3 17
#4 23
#5 28
NOTES:
1. TOP HORIZONTAL BARS ARE DEFINED AS HORIZONTAL BARS WITH MORE THAN 12" OF
FRESH CONCRETE CAST IN THE MEMBER BELOW THE REINFORCEMENT. BOTTOM
HORIZONTAL BARS ARE ALL OTHER HORIZONTAL BARS.
2. FOR LIGHTWEIGHT AGGREGATE CONCRETE, MULTIPLY THE VALUES ABOVE BY 1.3.
3. FOR EPOXY COATED REINFORCEMENT WITH COVER LESS THAN 3db OR CLEAR SPACING
LESS THAN 6db, MULTIPLY VALUES ABOVE BY 1.5. FOR ALL OTHER EPOXY COATED
REINFORCEMENT, MULTIPLY THE VALUES ABOVE BY 1.3.
4. ALL SPLICES ASSUMED TO BE CLASS B SPLICES.
5. WHEN SPLICING BARS OF DIFFERENT SIZES, USE SPLICE LENGTH FOR LARGEST BAR.
6. MINIMUM HOOK LENGTH EQUALS 16db FOR NO. 3-8 BARS & 17db FOR NO. 9, 10, & 11 BARS.
7. SPLICE LENGTHS GIVEN ARE MINIMUM, U.N.O.
4000 psi
TOP HORIZ.
BARS (IN.)
VERTICAL (IN.)
OR BOTTOM HORIZ.
TOP HORIZ.
BARS (IN.)
VERTICAL (IN.)
OR BOTTOM HORIZ.
12 * db
17db (FOR NO. 9-11 BAR)
16db (FOR NO. 3-8 BAR)
FOUNDATION PLAN NOTES:
1. FINISHED FIRST FLOOR ELEV.= 470.50 (0'-0"), U.N.O.
2. ALL ELEVATIONS NOTED THUS (-X'-X") DESIGNATE TOP OF FOOTING OR PIER ELEVATIONS AND ARE WITH RESPECT TO THE FINISHED
FIRST FLOOR ELEVATION.
3. TOP OF INTERIOR FOOTING ELEVATION IS (-0'-8") BELOW FINISHED FIRST FLOOR ELEVATION, U.N.O.
4. TOP OF EXTERIOR FOOTING ELEVATION IS (-2'-8") BELOW FINISHED FIRST FLOOR ELEVATION, U.N.O.
5. ALL WALL FOOTINGS SHALL BE WF2.5, U.N.O. ALL INTERIOR NON-LOAD BEARING WALLS MAY BEAR ON THICKENED SLAB, U.N.O.
6. ALL WALLS TO CENTER ON WALL FOUNDATIONS, U.N.O.
7. ALL INTERIOR FLOOR SLABS SHALL BE 6" THK. NON-AIR ENTRAINED FIBER-REINFORCED CONCRETE ON 4" OF PennDOT 2A COMPACTED
STONE, U.N.O. PROVIDE SAWCUT CONTROL JOINTS AS INDICATED IN THE CAST-IN-PLACE CONCRETE CONSTRUCTION SECTION OF THE GENERAL SPECIFICATIONS. SUBMIT A CONTROL JOINT LOCATION PLAN TO THE ENGINEER FOR REVIEW AND APPROVAL.
8. ALL EXTERIOR CONCRETE SLABS SHALL BE 4" THK. AIR ENTRAINED CONCRETE W/6x6 W2.9xW2.9 W.W.R. ON 6" PennDOT 2A COMPACTED STONE, U.N.O. ALL EXTERIOR SLABS SHALL BE TURNED DOWN AROUND PERIMETER AND EXTEND TO (-3'-0") BELOW
FINISHED GRADE. SEE SLAB TURNDOWN DETAIL, SHEET S-201.
9. MASONRY WALLS SHALL BE REINFORCED W/ #5 @ 24" O.C. WHERE REINFORCING IS SHOWN, U.N.O. PROVIDE CONTROL JOINTS IN CMU WALLS AS INDICATED IN THE CONCRETE MASONRY CONSTRUCTION SECTION OF THE GENERAL SPECIFICATIONS, U.N.O. SUBMIT A
CONTROL JOINT LOCATION PLAN TO THE ENGINEER FOR REVIEW AND APPROVAL.
10. REFER TO WALL FOOTING SCHEDULE, THIS SHEET.
11. REFER TO ARCHITECTURAL DRAWINGS FOR ALL NECESSARY EMBEDDED ITEMS, RAMPS, STAIRS, LANDINGS, AND FINISH DETAILS.
12. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS AND ELEVATIONS NOT SHOWN.
13. CONTRACTOR SHALL VERIFY WALL LOCATIONS WITH ARCHITECTURAL PLANS PRIOR TO FOUNDATION LAYOUT. ANY DISCREPANCIES
SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT AND ENGINEER.
14. ALL STRUCTURAL WOOD BEARING AND SHEAR WALLS TO BE 2x6 @ 16" O.C.
C O
N T
A C
T I N
F O
R M
A T
IO
N
D E
S
IG
N
M U
L A
G R
O U
P
C
O T
T A
G E
H
IL
L R
O A
D
Y O
R K
P A
.8
.0
B L A
IR
L
E H
M A
N
H
A N
O V
E R
R O
A D
Y O
R K
P
A
L
IT
T L
E C
R E
E K
P A
R K
M A
IN
T
E N
A N
C E
B U
IL
D
IN
G
S T
R U
C T
U R
A L
P L
A N
S
S-101
N E
W C
O N
S T
R U
C T
IO
N
F O
R
.8
.2 .0
3/16" = 1'-0"
FOUNDATION PLAN
P L A
N N
O R
T H
WALL FOOTING SCHEDULE
MARK
DIMENSIONS
REINFORCINGWIDTH DEPTH
WF2.5 2' - 6" 1' - 0" (3) #4 CONTINUOUS BOTTOM WITH #4 TIES AT 4'-0" ON CENTER
3/16" = 1'-0"
ROOF FRAMING PLAN
P L A
N N
O R
T H
WOOD ROOF FRAMING PLAN NOTES:
1. ALL ELEVATIONS NOTED THUS (+X'-X") REFERENCED TO FINISHED FIRST FLOOR ELEVATION.
2. TRUSS BEARING ELEV. = (+12' - 0"), U.N.O.
3. ALL ROOF SHEATHING SHALL BE A MIN. 40/20 MIN. 19/32 THK. AND BE NAILED AS NOTED IN THE GENERAL SPECIFICATIONS.
4. DETAILS AS SHOWN INDICATE TYPICAL CONNECTIONS AND CONDITIONS.
5. ROOF TOP UNIT LOCATION AND WEIGHTS TO BE COORDINATED WITH MECHANICAL ENGINEER / CONTRACTOR. ROOF TRUSS DESIGN TO ACCOUNT FOR
ANY PROPOSED UNITS.
6. REFER TO ARCHITECTURAL PLANS FOR TOP OF NON-LOAD BEARING WALL HEIGHTS AND ROOF SLOPES.
7. REFER TO ARCHITECTURAL AND HVAC PLANS FOR EXACT LOCATIONS OF ROOF TOP UNITS, ROOF DRAINS, AND ROOF VENTS.
8. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS AND ELEVATIONS NOT SHOWN.
R E
C O
R D
O F
IS
S
U E
D A
T E
IS
S
U E
R E
V
.1
.1
IS
S U
E D
F O
R P
E R
M
IT
.0
.1
IS
S U
E D
F O
R B
M
IN
8"
#4 BAR @ 12"
O.C., TYP.
FINISH GRADE
TOOLED EDGE
OPTIONAL
CONSTRUCTION
JOINT
12" HOOK
M
IN
OPTIONAL
CONST. JOINT
#5 BAR @ 24"
O.C. GROUT
SOLID
1/2" ISOLATION
JOINT MATERIAL
NOTE:
REFER TO CIVIL AND ARCHITECTURAL
PLANS FOR SIZE AND LOCATION OF
LANDINGS.
WALL BEYOND
REFER TO ARCH.
PLANS FOR DOOR &
WINDOW SCHEDULE
OF LANDING
8" TYP.
AROUND PERIMETER
#4 @ 12" O.C.
SLOPE 1/4"/FT.
REFER TO WALL FTG.
SCHEDULE FOR SIZE
AND REINF.
TOOLED EDGE12" HOOK, TYP.
M
IN
NOTES:
1. PROVIDE CONCRETE EQUIPMENT PADS
WHERE INDICATED ON CIVIL, ARCHITECTURAL
OR MEP DRAWINGS.
2. REFER TO CIVIL, ARCHITECTURAL, OR MEP
DRAWINGS FOR EXACT SIZE OF CONCRETE
PADS.
3/4"
CHAMFER,
TYP.
COMPACTED SUBGRADE
6 x 6 - W2.9 x W2.9 W.W.R., TYP.
OPTIONAL CONSTRUCTION JOINT
PROVIDE TURNDOWN ON ALL
SIDES OF THE PAD
FINISHED GRADE
#4 BAR @ 12" O.C., TYP.
2'-0"
#4 BAR @ 12" O.C., TYP.
2'-0"
INTERIOR CONCRETE
SLAB
REFER TO PLAN FOR
WALL THICKNESS
EXTERIOR GRADE
5/8" DIA. F1554 HOOKED
ANCHOR BOLTS W/ 2" HOOK.
7" EMBEDMENT @ 48" O.C.
2x6 PRESSURE TREATED
SILL PLATE
4" COMPACTED STONE
REFER TO ARCH. DWGS.
FOR PERIMETER
INSULATION
8" CMU FOUNDATION WALL
REFER TO WALL FOOTING
SCHEDULE FOR SIZE &
REINF.
DOWELS PER
SSTB ANCHOR
BOLT DETAIL &
WHERE
INDICATED ON
PLAN
1/2" THK. ISOLATION
JOINT MATERIAL
M
IN
VERTICAL
REINFORCEMENT
AS REQUIRED
GROUT AS REQUIRED
CONCRETE MASONRY WALL
DOWEL MAY BE BENT UP TO
1IN. LATERALLY PER
6IN. VERTICALLY
CONCRETE FOUNDATION
V A
R
IE
S
1/2"CONTROL JOINT
CONTROL
JOINT FILLER
(WATERSTOP)
JOINT
SEALER, TYP.
HORIZONTAL
REINFORCING (CUT 1/2
@ CONTROL JOINT)
PROVIDE VERT. REINF. ON
EA. SIDE OF CONTROL JOINT;
SEE PLAN FOR REINF. SIZE
NOTES:
1. PROVIDE CONTROL JOINTS AS INDICATED
IN PLAN AND IN THE CONCRETE MASONRY
CONSTRUCTION SECTION OF THE
GENERAL SPECIFICATIONS
2. HORIZ. REINF. CONTINUOUS THROUGH
JOINT ONLY AT SILL OR LINTEL
NO. 9 GAUGE HORIZONTAL
JOINT REINFORCEMENT
(LADDER TYPE SHOWN,
TRUSS TYPE IS SIMILAR)
@ 16" O.C.
REFER TO PLAN FOR REBAR
SIZE & SPACING WHERE
INDICATED
2' - 0" MIN. SPLICE TYP.
2' - 8"
No. 9 GAGE HORIZONTAL LADDER
JOINT REINFORCEMENT @ 16"
O.C.
(1) FULL HEIGHT VERT. REINF. TO
MATCH TYP. WALL REINF. IN CORNER;
REFER TO PLANS FOR DETAILS
CORNER
No. 9 GAGE HORIZONTAL LADDER
JOINT REINFORCEMENT @ 16"
O.C.
WALL END OR MASONRY OPENING
(2) FULL HEIGHT VERT. REINF. TO
MATCH TYP. WALL REINF.; REFER
TO PLAN FOR DETAILS
GROUT ALL CELLS HAVING VERTICAL BARS
GROUT JAMB SOLID FULL HEIGHT
NO. 9 GAUGE HORIZONTAL
CONT. REINFORCEMENT
LADDER TYPE @ 16" O.C., TYP.
1 1/2" X 1/4" GALVANIZED Z
STRAP ANCHORS @ 48" O.C.
2" 2"24"
(1) FULL HEIGHT VERT. REINF. TO
MATCH TYP. WALL REINF.; REFER
TO PLAN FOR DETAILS; LOCATE IN
CENTER OF WALL U.N.O.
INTERSECTION
16" CMU
14" CMU
12" CMU
10" CMU
8" CMU
12 5/8"
10 5/8"
8 5/8"
6 5/8"
4 5/8" "d"
EQUAL
"d"
EQUAL
WALL SECTION - SINGLE REINFORCING
"d" = 1/2 x SPECIFIED UNIT THICKNESS
WALL SECTION - DOUBLE REINFORCING
"d" = ACTUAL UNIT THICKNESS MINUS 3.00 INCHES
ELEVATION
PLAN
SHEAR WALL, REFER TO PLANS
AND SCHEDULE THIS SHEET
TYP. SILL PL. ANCHOR
BOLT
2x6 CONT. SILL PLATE, (TREATED), TYP.
CORNER
CHORD STUDS,
REFER TO SHEARWALL
SCHEDULE
HOLD-DOWN
ANCHOR, REFER
TO SHEARWALL
SCHEDULE
HOLD-DOWN
ANCHOR BOLT,
REFER TO SHEARWALL
SCHEDULE & TYP. REINF. @
SSTB ANCHOR BOLT DETAIL
1/2" DIA. ANCHOR BOLT W/
WASHER @ 4'-0" O.C., TYP.
2x6 SPF NO.2 STUDS @ 16" O.C.
CHORD STUDS. REFER
TO SHEARWALL
SCHEDULE
SHEARWALL HOLD-DOWN -
REFER TO SHEARWALL
SCHEDULE
1/2" THK. PLATE WASHER W/
ANCHOR BOLT, REFER TO SHEAR
WALL SCH. FOR SPACING
/2
2 1/2"
#5 BAR @ 24" O.C.
GROUT SOLID
1/2" ISOLATION
JOINT MATERIAL
NOTE:
REFER TO CIVIL AND ARCHITECTURAL
PLANS FOR SIZE AND LOCATION OF
LANDINGS.
WALL BEYOND
REFER TO ARCH.
PLANS FOR DOOR &
WINDOW SCHEDULE
SLOPE PER
ARCH. DWGS.
REFER TO WALL FTG.
SCHEDULE FOR SIZE
AND REINF.
4" COMPACTED STONE
REFER TO ARCH.
DWGS. FOR PERIMETER
INSULATION
C O
N T
A C
T I N
F O
R M
A T
IO
N
D E
S
IG
N
M U
L A
G R
O U
P
C
O T
T A
G E
H
IL
L R
O A
D
Y O
R K
P A
.8
.0
B L A
IR
L
E H
M A
N
H
A N
O V
E R
R O
A D
Y O
R K
P
A
L
IT
T L
E C
R E
E K
P A
R K
M A
IN
T
E N
A N
C E
B U
IL
D
IN
G
F O
U N
D A
T
IO
N
D E
T A
IL
S
S-201
N E
W C
O N
S T
R U
C T
IO
N
F O
R
.8
.2 .0
NOT TO SCALE S-201
DSLAB TURNDOWN
NOT TO SCALE S-201
B
TYPICAL SECTION AT
EXTERIOR DOOR
LANDINGS
NOT TO SCALE S-201
E
EXTERIOR CONCRETE
EQUIPMENT PAD
NOT TO SCALE S-201
K
VERTICAL
REINFORCEMENT
LOCATION
NOT TO SCALE S-201
F
FOUNDATION DOWEL
ALIGNMENT DETAIL
NOT TO SCALE S-201
G
MASONRY WALL
CONTROL JOINT
NOT TO SCALE S-201
J
MASONRY WALL
HORIZONTAL
REINFORCEMENT
DETAIL
NOT TO SCALE S-201
H
TYPICAL MASONRY
WALL REINFORCING
DETAIL
NOT TO SCALE S-201
A
TYPICAL EXTERIOR
WALL
NOT TO SCALE S-201
L
TYPICAL SHEAR WALL
HOLDOWN DETAIL
1" = 1'-0" S-201
C
SECTION AT GARAGE
DOOR LANDINGS
R E
C O
R D
O F
IS
S
U E
D A
T E
IS
S
U E
R E
V
.1
.1
IS
S U
E D
F O
R P
E R
M
IT
.0
.1
IS
S U
E D
F O
R B
REFER TO ARCH.
DWGS.
2x TOP PL.; NOTE SOME AREAS
REQUIRE TRIPLE TOP PL. REFER
TO FRAMING PLAN FOR
LOCATIONS
H2.5A SIMPSON HURRICANE TIE, E.S.
OF TRUSS, TYP.; INSTALL TO ACHIEVE
DOUBLE CAPACITY OF TIE; REFER TO
MFR. SPECS FOR INSTALLATION &
FASTENER REQUIREMENTS
ROOF TRUSS
BEARING WALL; REFER TO
PLAN FOR LOCATION &
SHEAR WALL SCHED. FOR
DETAILS
NOTE: FRAMING NOT SHOWN FOR CLARITY
10d COMMON NAILS
MIN. OF (10)
10d COMMON NAILS
MIN. OF (10)
INSIDE CORNER DETAIL
OUTSIDE CORNER DETAIL
EDGE SHEATHING NAILING
PATTERN; REFER TO
GENERAL NOTES AND
SHEAR WALL SCHED. FOR
NAIL SIZE & SPACING
NON EDGE SHEATHING NAILING PATTERN;
REFER TO GENERAL NOTES AND SHEAR
WALL SCHED. FOR NAIL SIZE & SPACING
NON EDGE SHEATHING
NAILING PATTERN; REFER
TO GENERAL NOTES AND
SHEAR WALL SCHED. FOR
NAIL SIZE & SPACING
WOOD STRUCTURAL PANEL
PER GENERAL NOTES
WOOD STRUCTURAL
PANEL PER GENERAL
NOTES16d NAIL @ 24" O.C.
16d NAIL @ 24" O.C.
DOUBLE 2x6
TOP PLATE
SIMPSON HGA10
@ 2'-0" O.C.
GABLE END TRUSS
DRYWALL
CEILING
2x6 NAILER
PERPENDICULAR PARALLEL
PRE-
FABRICATED
ROOF TRUSSES
NON-BEARING WALL DOUBLE 2x TOP PLATE
SIMPSON STC ROOF TRUSS
CLIP @ EA. TRUSS1
/2
G A
P
NON-BEARING WALL
PRE-FABRICATED
ROOF TRUSSES
(2) 3" BOX
NAILS EA. SIDE
2x WD. BLOCKING @ 48" O.C.
/2
G
A P
DOUBLE 2x TOP PLATE
SIMPSON STC ROOF TRUSS
CLIP @ EA. TRUSS
NOTE:
AT CONTRACTORS OPTION IN LIEU OF SIMPSON CLIPS
PROVIDE SIMPSON SDPW DEFLECTON SCREWS
SDPW14312 - 1/2" L 0-3/4" GAP 2x TOP PLATE SDPW14500 - 5" L 0-1 1/2" GAP 2x + 3/4" WSP SDPW19600 - 6" L 0-1 1/2" GAP (2) 2x TOP PLATE
ROOF TRUSS BY
TRUSS SUPPLIER
SIMPSON H2.5A HURRICANE TIE @ EA.
TRUSS, MAXIMUM UPLIFT CAPACITY
OF 535#. TRUSS SUPPLIER TO
CONFIRM UPLIFT REACTION DOES NOT
EXCEED CAPACITY OF TIE
DOUBLE TOP PLATE
EXTERIOR WALL STUD;
REFER TO PLAN
2x BLOCKING
(4) 10d NAILS
(5) 10d NAILS
ROOFING MATERIAL,
REFER TO ARCH. DWGS.
PLYWOOD SHEATHING, REFER TO GENERAL NOTES;
SHEATHING SHALL BE CONTINUOUS OVER LADDER
TRUSS AND FIRST TRUSS BEYOND GABLE END
2x LADDER TRUSS, REFER TO PLAN
PREFABRICATED ROOF TRUSS,
BY SUPPLIER
SIMPSON HGA10, REFER TO
OTHER DETAILS
10d…