00017694 Plans.pdf
PDF 1 MB Posted
- Attached to
- Mosier Pre-Fab Metal Structure
- Solicitation number
- S-73000-00017694
- Issued by
- Oregon
About this file
This is an architectural and engineering plans document prepared by the Oregon Department of Transportation (ODOT) for a secondary containment structure and building cover project located in Mosier, Oregon (Wasco County, District 9). The project involves the construction of a pre-engineered metal building (PEMB) structure with an integral secondary containment system designed to house magnesium chloride tanks. The containment structure has a gross volume of 1,665.5 cubic feet (net volume of 1,394.5 cubic feet or 10,430 gallons), which exceeds regulatory requirements of 40 CFR 264.175, providing capacity for more than 10% of total primary container volume plus 100% of the largest container volume. Estimated material quantities include 29.5 cubic yards of concrete for slab and footings, 8.5 cubic yards for columns and stem walls, and 8,000 pounds of mild steel reinforcement. The structure encompasses approximately 748 square feet and is designed as Construction Type II-B (Unprotected, Non-Combustible) for Occupancy Class Group U (Utility and Miscellaneous).
The project plans specify detailed structural, material, and design requirements including a reinforced concrete slab with 8-inch minimum depth, hot-dip galvanized PEMB framing, pre-finished metal roofing and siding, and a rigid building frame system. Design parameters include a basic design wind speed of 99 mph, ground snow load of 42 psf, seismic design category D, 24-inch frost depth, and presumptive soil bearing capacity of 1,500 psf. All work must comply with the Mosier Municipal Code, Wasco County General Requirements, and the 2016 Oregon Structural Specialty Code. Materials must be sourced from ODOT-approved vendor lists where applicable, and all concrete must meet 3,300 psi specifications. Compaction testing and engineer approval are required for subbase materials, with site work grading designed to slope away from the containment system to prevent water pooling.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 00017694 ITB.docx | DOCX document | |
| 00017694 Sample Contract.docx | DOCX document | |
| 00017694 Specifications.docx | DOCX document | |
| 00017694 Q and A 1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
1'-4"
34'-0"
Gross Containment Volume 1665.5 Cu. Ft.
Net Containment Volume 1394.5 Cu. Ft. = 10430 Gallons
Net volume assumes one container is punctured near its base.
PLAN
Scale:
16"=1'-0"
Magnesium Chloride Tank
(Installed by Others)
Magnesium Chloride Tank
(Installed by Others)
Containment wall
Turned down slab
Column, typ.
and 1C-2C.
columns 1A-2A
X-brace between
16'-0"16'-0"1'-0" 1'-0"
Form low point, sloping 1" over 3'-0".
Slab is level except in area shown.
3'-0" R
8"=1'-0"
TYPICAL SECTION
CONTAINMENT WALL AND TURNED DOWN SLAB
TYPICAL SECTION
COLUMN
Granular Structure Backfill
3 ~ #4 cont.
3 ~ #4 cont.
and Footing Reinforcement
Horizontal Stemwall Terminate w/ std. 90 deg. hook each end
#5 @ 6" o.c. each way, top and bottom, Slab Reinforcement and bearing details per PEMB manufacturer.
Column base plate, threaded rod spacing, embedded plate with matching nut.
Place rod in a 4"x4" grid and secure rod to
4 ~ 3/4" dia. x 4'-0" grade 55 threaded rod
" diameter holes.8 with x 8 x 8 Embeded plate 2 roughened construction joint.
Continuous PVC waterstop across with slab reinforcement
Omit 1 hoop where conflict exists applications from the ODOT QPL.
Select grout suitable for use in bearing
Nominal 1" thick non-shrink grout pad.
3/4" chamfer (typ.)
3/4" chamfer (typ.)
8 ~ #4 c-bars each column
A B C
OF TRANSPORTATION
OREGON DEPARTMENT
Checker:Drafter:
Designer:
SHEET NO.
BUILDING NO.
BDS DWG NO.
CALC. BOOK
COUNTY Reviewer:
AVAILABLE UPON REQUEST
FINAL ELECTRONIC DOCUMENT
WASCO COUNTY
TAX LOT 2N 11E 2 D 200
OREGON DEPARTMENT OF TRANSPORTATION PROPERTIES
Secondary Containment Structure and Building Cover
District 9 - Mosier, OR
HWY:
M.P.:
DATE
F O
T N
E
MTRAPED
G
OI
ATROPS
A
Johathan S. Doughton
Paul J. Strausser
Rhonda L. Freeman
SCALE WARNING
DRAWING IS NOT TO SCALE
MEASURE ONE INCH, THEN
IF THIS SCALE LINE DOES NOT
WASCO
N/A
01/25
OREGON
RE
GI
ST
ERE
DPROFESSIONALEN
GINEER
RENEWS: 06-30-2026
P
U
L
JOSEPH STRA
S
RM
Y
23,2
82398PE
BR_PIN4650_510_D9_gen_01.dgn :: C02 1/3/2025 8:59:37 AM hwye44d
Note:
Do not construct contraction joints in concrete slab.
Estimated Quantities:
Slab and footings 29.5 CUYD**
Columns and stem walls 8.5 CUYD**
Mild Steel Reinforcement 8000 lbs
**Neat line quantities based on nominal dimensions.
**Adjust actual quantities as required.
Aisle
6'-0" max.
8" " cl.2 c o n r e te s la b m in r f r c d m l.
p a c e h p
6" min. to 2'-6" max.
Increase excavation and backfill depth as required to reach undisturbed soil.
1'-0"
1'-0"
2'-8"
2'-0"
COLUMN PLAN
"=1'-0"2 upon completion of construction.
* Building Number to be assigned
CONCRETE DETAILS
FLOOR PLAN AND REINFORCED
C02
2025-01-03T11:02:49-0800
STRAUSER Paul J
2'-6"
SW ELEVATION (FRONT) NW ELEVATION (SE OPPOSITE)
2'-6" 2'-6" 2'-6"
NE ELEVATION (REAR)
Siding closed at eave down, typical.
girts to be turned
Interior flange or zee siding, typ.
Pre-finished metal roofing, typ.
enclosed wall, as required
Knee bracing at partially
Eave trim, typ.
Top of frame at sidewalls
BR_PIN4650_510_D9_gen_01.dgn :: C03 1/3/2025 8:59:39 AM hwye44d shown for clarity
Framing not frame, typ.
Rigid building roof over purlins, typ.
3" standing seam metal
1 2
B
C
B
C03
BUILIDING ELEVATION VIEWS
2025-01-03T11:03:18-0800
STRAUSER Paul J
SITE PLAN
BR_PIN4650_510_D9_gen_01.dgn :: C01 1/6/2025 3:11:43 PM hwye43p
K
K
D
Taxlot 2N 11E 2 D 300
Taxlot 2N 11E 2 903
Slope finished grade to drain away from the containment system, approximately six inches over ten feet.
all site work and obtain approval prior to constructing footings and slabs.
compacted to 95% of maximum dry density per ASTM D1557. Provide compaction test reports to the Engineer for
Subbase material for slabs and footings shall be undisturbed natural ground or granular structure backfill
SITE WORK
Furnish exposed fastener metal roof and siding. Install siding between purlins.
Provide a well graded, 3/4" minus crushed rock or approved equal for granular structure backfill.
Hot dip galvanize plates, threaded rods, hardware, and all PEMB framing according to ASTM A123.
Furnish ASTM A36 steel for embedded plates.
Furnish heavy hex nuts according to ASTM A563 Grade A and washings according to ASTM F436.
Furnish grade 55 theaded rod according to ASTM F1554.
Furnish grade 60 reinforcing steel according to ASTM A615, ASTM A496, or ASTM A82.
Furnish structural, non-epoxy grout from the ODOT QPL suitable for bearing applications.
Furnish general structure concrete, 3300 psi for all concrete.
MATERIAL REQUIREMENTS
Obtain approval from the Engineer prior to fabrication.
Submit stamped working drawings and calculations to the Engineer for approval .
PRE-ENGINEERED METAL BUILDING (PEMB) REQUIREMENTS
container volume (2000 gallons) and 100% of the largest container volume (10000 gallons).
40 CFR264.175 - Secondary containment provides capacity exceeding 10% of total primary
OREGON OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION REQUIREMENTS
Collateral Load = 5 psf
Seismic Design Base Shear = 0.103WRoof Live Load = 20 psf
Seismic Design Category DDesign Ground Snow Load = 42 psf
Site Class DPresumptive Soil Load Bearing = 1500 psf
: 0.461 and 0.325 D1 and S
DS
Design Spectral Accelerations SExposure Category C
: 0.492 and 0.227 and S
Mapped Spec. Response Accel SBasic Design Wind Speed = 99 MPH
Risk Category IISevere Weathering Class
Seismic Importance Factor = 1.0Frost Depth: 24" all other applicable state and local regulations.
Requirements, Commercial Building Requirements of the 2016 Oregon Structural Specialty Code (OSSC 2016), and
Building Code Perform all work in strict compliance with the Mosier Municipal Code (MMC), Wasco County General, GENERAL BUILDING REQUIREMENTS
Actual Area = 748 SFBase allowable area = 8500 SF
Construction Type: II-B (Unprotected, Non-Combustible)
Occupancy Class: Group U (Utility and Misc.)
Industrial Zone (I)
CODE DATA
Salem, OR 97302Wasco County
4040 Fairview Industrial Drive, SECity of Mosier
Oregon Department of TransportationOwner:Tax Lot: 2N 11E 2 D 300Site:
Construct secondary containment system and building cover.
DESCRIPTION OF WORK
Taxlot 2N 11E 2 D 200
Taxlot 2N 11E 2 402
Taxlot 2N 11E 2 D 200
Taxlot 2N 11E 2 D 201 structure
Proposed structure
Existing
Mosier City Limits
LOCATION MAP
LAT. 45.68194, LONG. -121.40523
SEC. 02, T. 02 N., R. 11 E., W.M.
Wasco County
DEFERRED SUBMITTALS
prior to pouring foundations.
Submit building reactions to the Engineer of Record
Pre-engineered metal building plans and calculations.
Oregon Structure Specialty Code, Chapter 17.
Complete special inspections as required by the
SPECIAL INPECTIONS
C01
ODOT ENTRANCE
File details come from the government source that posted it. Updated .