The Dalles Generator Step-Up Transformer Replacement

Award Notice Posted

Solicitation number
W9127N-15-R-0060
Agency
Awarded
to Gardner Zemke Co
Set-aside
No set-aside

Opportunity facts

Contract number
W9127N-16-C-0006 Federal contract award
NAICS code
335311 Power, Distribution, and Specialty Transformer Manufacturing
PSC
Not on record

Notice details come from SAM.gov. Updated .

Notice text

Added: Feb 09, 2016 5:41 pm Description of Requirement: Generator Step-up Transformer at the Dalles Dam, Dalles OR, 97058-0564. The Dalles Dam is undergoing an upgrade to the existing Step-Up Transformers and will be replacing the existing systems. The project will eventually replace a total of nineteen transformers of various specifications over the course of the next several years.

Class II Three-phase GSU Power Transformer:
Design, manufacture, and factory test of one three-phase generator step-up (GSU) power transformer rated 175,000/233,333 kVA, 230 kV high-voltage, 13.2 kV low-voltage, Class ODAF/ODAF cooling, for delivery f.o.b. to The Dalles power plant including transformer shipment, hauling, site movement, reassembly and field testing.


Class II Single-phase GSU Power Transformers:
Design, manufacture, and factory testing of three single-phase generator step-up (GSU) power transformers rated 9,000/12,000 kVA, 115 GrdY/66.395 kV high-voltage, 13.2 kV low-voltage, Class ONAN/ONAF cooling, for delivery f.o.b. to The Dalles power plant including transformer shipment, hauling, site movement, reassembly and field testing.


Design, manufacture, and factory testing of three single-phase generator step-up (GSU) power transformers rated 37,800/50,400/63,000 kVA, 115 GrdY/66.395 kV high-voltage, 13.2 kV low-voltage, Class ONAN/ONAF/ONAF cooling, for delivery f.o.b. to The Dalles power plant including transformer shipment, hauling,site movement, reassembly and field testing.


Design, manufacture, and factory testing of twelve single-phase generator step-up (GSU) power transformers rated 37,800/50,400/63,000 kVA, 230 GrdY/132.790 kV high-voltage, 13.2 kV low-voltage, Class ONAN/ONAF/ONAF cooling, for delivery f.o.b. to The Dalles power plant including transformer shipment, hauling, site movement, reassembly and field testing.  