Substation #2 Power Upgrade Supplies
Award Notice Posted
- Solicitation number
- W912EF14Q0095
- Agency
-
ENDIST Walla Walla
US Army Corps of Engineers, Department of Defense
- Awarded
- to Electrical Service Products, Inc.
- Set-aside
- No set-aside
Opportunity facts
- Contract number
- W912EF-14-P-0065 Federal contract award
- NAICS code
- 335311 Power, Distribution, and Specialty Transformer Manufacturing
- PSC
- Not on record
Notice details come from SAM.gov. Updated .
Notice text
2 versions
Update #2 · Latest ·
The purchase of a new transformer and sectionalizing cabinet for distribution system for use at McNary Lock & Dam.
Update #1 ·
The synopsis is not a Request for Quotes (RFQ) or proposals (RFP). This announcement is for information and planning purposes only and is not a commitment by the Government, implied or otherwise, to issue a solicitation or award a contract. Summary of Work: The salient characteristics of the products must meet specifications.
McNary Lock & Dam (MNA) relies on potable water to operate its main unit generators. A 400,000 gallon tank is located on the hill above McNary Dam. Well house pumps are used to maintain the water level and pressure to supply the project. The town site Pump House is currently being used for chlorinating the potable water supplied to the McNary machine shop, warehouses and powerhouse. This water is used for gland systems in addition to potable water. The town site has a dedicated transformer bank to supply power. The construction of the new McNary Dam Potable Water System, adding a 60A breaker for the future load, could impact the existing design load of the town site house. It's recommended to increase the capacity of the transformer bank.
It's the intent of the USACE to procure a new system for sectionalizing, tapping or terminating underground cable and a new 225KVA transformer for the substation to feed the town site house load and the existing 208V /120V, three phase load from well house #2.
THREE PHASE PAD MOUNTED TRANSFORMER
The transformer high-voltage compartment shall contain the incoming line, transformer high-voltage bushings, load-break switch handle(s), and access to oil-immersed bayonet fuses; tap changer handle, insulated phase barriers, and ground pad.
The transformer shall be radial-feed oil-immersed type rated at 15 kv, 95 kv BIL, with a continuous current rating and load-break rating of 200 Amperes, and a make-and-latch rating of 12,000 rms amperes symmetrical. The switch handle shall be located in the high-voltage compartment. Audible sounds level shall not exceed a maxim of 55 decibels, and transformer efficiency 99.17percent.
Transformer Test Reports
Routine and other tests shall be performed in accordance with IEEE C57.12.90 by the manufacturer on the actual transformer to be supplied. Contractor shall submit test reports containing results of the below required tests and receive Government approval prior to delivering equipment to the project site.
THREE PHASE SECTIONALIZING CABINET SPECIFICATIONS
The contractor shall supply a three phase sectionalizing cabinet.
PORCELAIN FUSE CUTOUT, 100A, 15KV CLASS
The contractor shall supply a three (3) cutout fuse, 15KV, 100A, BIL 110kv.