AMENDMENT 0002 - The purpose of amendment 0002 is to address a contractor's questions as follows:

QUESTION:  Does the customer need any of the following:

1.  Standard Rigid Factory Curb to sit on?

RESPONSE:  No factory curb is required, as long as the unit has horizontal discharge.

 2.  We are only hitting 60F Leaving Air Temperature.  Do they need to get lower to dehumidify?

 RESPONSE:  They do not need to get lower than 60F Leaving Air Temperature.

 3.  What type of BACnet interface do they need?

RESPONSE:  The fresh air unit needs a BACnet unit controller that is supported by Tracer SC.

4.  What is the entering air temperature for heating?

RESPONSE:  No defined entering air temperature for heating. Just the 32kW heating capacity.

 5.  I see that this project is in AR, are there any other special conditions we need to know?  Does this job have a Military Priority Rating?

RSEPONSE:  This requirement is rated DO-A6.

===========================================================================

AMENDMENT 0001 - REVISION:

PINE BLUFF ARSENAL PROVIDED CLARIFICATION ON THE REQUIREMENT AND THE FOLLOWING IS ACCEPTABLE:

100% OSA Unit requirements: 95F ambient condensing temperature, 3000 CFM airflow, 78.8F entering wet bulb, and 90.1F entering dry bulb

Due to formatting issues, the combined synopsis/solicitation for the HVAC and Humidifer requirement to support Pine Bluff Arsenal, is provided as an attachment.  Also attached is Addendum information that is applicable to this procurement.  For questions/issues, please contract Sheila Peters, email address sheila.k.peters2.civ@mail.mil.

Update #2 ·

AMENDMENT 0001 - REVISION:

PINE BLUFF ARSENAL PROVIDED CLARIFICATION ON THE REQUIREMENT AND THE FOLLOWING IS ACCEPTABLE:

100% OSA Unit requirements: 95F ambient condensing temperature, 3000 CFM airflow, 78.8F entering wet bulb, and 90.1F entering dry bulb

Due to formatting issues, the combined synopsis/solicitation for the HVAC and Humidifer requirement to support Pine Bluff Arsenal, is provided as an attachment.  Also attached is Addendum information that is applicable to this procurement.  For questions/issues, please contract Sheila Peters, email address sheila.k.peters2.civ@mail.mil.

Update #1 ·

Due to formatting issues, the combined synopsis/solicitation for the HVAC and Humidifer requirement to support Pine Bluff Arsenal, is provided as an attachment.  Also attached is Addendum information that is applicable to this procurement.  For questions/issues, please contract Sheila Peters, email address sheila.k.peters2.civ@mail.mil.

Files

Notice history

Notice Type Posted
Heating, Ventilation and Air Conditioning (HVAC) & Humidifier Award Award Notice
This notice Latest solicitation Solicitation

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity