Audiology Sound Booth-Custom Sound Room

Closed Solicitation Posted

Solicitation number
36C25524Q0539
Agency
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Place of performance
Saint Joseph, Missouri 64506, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs, Veterans Health Administration, Veterans Integrated Service Network 15 is seeking to procure one (1) custom audiology sound booth for the St. Joseph Community-Based Outpatient Clinic in Missouri. The vendor will be responsible for designing, developing, integrating, testing, delivering, installing, and providing warranty support for the sound booth, which must meet or exceed specifications in the VA Booth Audiometric Examination Specifications and ANSI S3.1-1999 standards. Key requirements include UL-listed electrical components, static-resistant and hypoallergenic carpeting, adequate ventilation, and vibration isolation. Offers will be evaluated based on the offeror's relevant experience, past performance, and price. The delivery date is no later than November 2024, with the installation to be completed by December 2024.

This is a total set-aside for certified service-disabled veteran-owned small businesses (SDVOSBs). Offerors must be listed in the SBA certification database as an eligible SDVOSB to be considered for award. There are no known incumbents or current contractors, and the award value is not specified. The place of performance is the new St. Joseph CBOC Audiology Department.

Notice text

SECTION D - CONTRACT DOCUMENTS, EXHIBITS, OR ATTACHMENTS

D.1  STATEMENT OF WORK

Eastern Kansas VAMC

Audiology Sound Booth

  1. Purpose: Eastern Kansas has a requirement for one (1) sound booth for testing in the audiology clinic in St. Joseph for activation. Full services will be available with the new CBOC building. A sound booth is the gold standard for audiology testing.
  1. Requirements: 

One (1) Sound Booth- Custom Eckel Sound Room

Requirements and evaluation factors are as follows

STANDARD AUDIOMETRIC ROOM/BOOTH FEATURES & OPTIONS

SEE DRAWINGS ON FOLLOWING PAGES FOR OPTIONS TAKEN

1. OPTIONAL 32"W BY 73 3/4"H CLEAR OPENING DOORS "C/O", 36"W BY 73 3/4"H C/O DOORS

& 36"W BY 80"H C/O DOORS - SPECIAL SIZED DOORS UPON REQUEST.

2. OPTIONAL 20"W BY 22"H OR 20"W BY 60"H DOUBLE GLAZED ACOUSTIC WINDOWS

AVAILABLE FOR DOORS - SPECIAL SIZES UPON REQUEST.

3. STANDARD 20"W BY 30"H OR 24"W BY 30"H DOUBLE GLAZED ACOUSTIC PATIENT

VIEWING WINDOW - SPECIAL SIZES UPON REQUEST.

4. STANDARD FAN EXHAUST & FAN INLET RECESSED CEILING SILENCERS - NOTE:

SMALLER MODELS COME WITH A FAN EXHAUST CEILING SILENCER AND A STATIC INLET

RECESSED WALL SILENCER.

5. IN EITHER CASE FOR POINT 4, THE FANS CAN BE REMOVED IN FAVOR OF A 6" OR 8"

HVAC COLLAR - HVAC CONNECTIONS ARE BY OTHERS - WE RECOMMEND A BALANCED

SYSTEM ANYWHERE BETWEEN 80 TO 120 CFM.

6. STANDARD JACK PANEL C/W TWELVE 1/4" PHONE JACKS, TWO USB PORTS & ONE

1 3/4" PASS-THRU WITH GROMMET - SPECIAL CONNECTIONS CAN BE ADDED UPON

REQUEST.

7. "LP" OR LOW PROFILE ROOMS HAVE AN UNDERLAY OF TWO LAYERS OF RUBBER MAT

FOR A TOTAL RISE OF 1 9/16" FROM HOST FLOOR TO DOOR OPENING - A 3 SIDED

SLOPED 1:12 RISE TO RUN RUBBER RAMP MEASURING 18 3/4" LONG IS SUPPLIED WITH

THE ROOM FOR WHEEL CHAIR ACCESS.

8. "LP2" OR 2" ISOLATED FLOOR ROOMS HAVE A STEEL FLOOR ON ISOLATORS FOR A 2 1/2"

TOTAL RISE FROM HOST FLOOR TO THE DOOR OPENING - A 3 SIDED SLOPED 1:12 RISE

TO RUN RUBBER RAMP MEASURING 30" LONG IS SUPPLIED WITH THE ROOM FOR

WHEEL CHAIR ACCESS.

9. "FP7" OR 7" ISOLATED FLOOR ROOMS HAVE A STEEL FLOOR ON ISOLATORS FOR A 7 1/2"

TOTAL RISE FROM HOST FLOOR TO DOOR OPENING.

10. OPTIONAL 3"Ø SPRINKLER ACCESS HOLES - SPRINKLER BY OTHERS.

11. STANDARD CARPET OR CARPET TILE SUPPLIED.

12. EMPTY UTILITY BOXES WITH PULL WIRES CAN BE PROVIDED FOR UTILITIES SUCH AS

DATA, ALARMS & THERMOSTATS UPON REQUEST.

5. Specific Tasks. 

5a. Engineering Focus Objectives:

  1. Design, develop, integrate, test, deliver, install and provide warranty support for one (1) sound booth in St. Joseph, MO.
  2. Meet or exceed all specifications, testing, and criteria found in the Department of Veterans Affairs Booth Audiometric Examination Specifications document (attached).  Must also meet or exceed ANSI S3.1-1999  (or later standards):  Maximum Permissible Ambient Noise Levels for Audiometric Test Rooms.
  3. Audiology sound booth- One (1) single walled sound booth.
  4. All electrical components shall be UL (or equivalent laboratory approved) listed Hospital Grade components and shall operate on 110 V, 60 Hz, single phase power.  Each booth needs numerous electrical outlets to support standard equipment to be installed. Each audiometric booth must have a dedicated 20 amp circuit for power. If the lighting is on a separate circuit, then the lighting and power need to go to a single source ground.
  5. Before booths are delivered, the contractor will provide the power requirements to Eastern Kansas VA so that the Engineering team can assess the functionality and viability.
  6. Carpeting used must be static resistant and durable, hypoallergenic materials preferred. Carpeted or soft material used on side panels within suites is desirable, as they would increase attractiveness of environment for plane tree objectives, but not absolutely necessary as they do not effect test results. 
  7. Suites must have adequate ventilation for comfort and connect to building HVAC.  Suite shall be provided with a ventilation system designed to be connected to the facility building HVAC systems, and provide vibration isolation from the duct work of the building HVAC system, to prevent vibration/noise affecting booth sound quality.
  8. Awarded contractor must provide Project Engineering with a set of Shop Drawings within 30 days of award which show all connections to building systems.

Deliverables:  Successful delivery of Audiology Booths to the St. Joseph CBOC at the new CBOC location.

 

6. Performance Monitoring

Not applicable.  This is a contract to purchase audiology suites and booths.

7. Security Requirements

There is no security requirements for this contract. 

8.  Government-Furnished Equipment (GFE)/Government-Furnished Information (GFI).  

There is no government-furnished equipment for this contract. 

9.  Other Pertinent Information or Special Considerations.

      a.  Identification of Possible Follow-on Work.  Not applicable

      b.  Identification of Potential Conflicts of Interest (COI).   Not applicable

      c.  Identification of Non-Disclosure Requirements. Not applicable

      d.  Packaging, Packing and Shipping Instructions.  Not applicable

      e.  Inspection and Acceptance Criteria.   Safe and timely delivery of audiology suites and booths to the basement of Building 500 in the Audiology Clinics.  Equipment should be fully functional, unbroken, etc.

10. Risk Control

11.  Place of Performance. The booth will be delivered to the  St. Joseph CBOC.

12.  Period of Performance.  No later than December 2024.

  1. Delivery Date: November 2024.
  2. Delivery Location:

Eastern Kansas VAMC

St. Joseph CBOC new build

Audiology Department

Files

File Type Posted
St Joseph CBOC- Architectural Plans Page 3 Updated (1).pdf PDF
Room number is 152.docx DOCX document
36C25524Q0539.docx DOCX document
Supply eCMS Line Item Audio Sound Room FY23 .xlsx XLSX spreadsheet

Notice history

Notice Type Posted
This notice Latest solicitation Solicitation
Audiology Sound Booth-Custom Eckel Sound Room Original Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
DA10--Legacy VHA VISN 10 - AudioCare Modules and PM&S Services NAICS 513210 Veterans Integrated Service Network 10 No set-aside
Z2DA--657-24-111JC Renovate Ambassador Suite & Main Lobby B1 Saint Louis, Missouri 63108, United States · NAICS 236220 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business