SPECIFICATIONS - Volume 3
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment_0005_PN80773.pdf | ||
| Amd4_PN80773_W912PM-16-R-0020.pdf | ||
| AMD0003_PN80773_PLANS_Vol1.pdf | ||
| AMD0003_PN80773_PLANS_Vol2.pdf | ||
| AMD0003_PN80773_PLANS_Vol1_CADDfiles.zip | ZIP file | |
| PN_80773_-_Amendment_0003.pdf | ||
| W912PM-16-R-0020-0002__PN80773.pdf | ||
| AMD0002_PLANS_PN80773_VOL1_Caddfiles.zip | ZIP file | |
| AMD0002_PLANS_PN80773_VOL1.pdf | ||
| AMD0002_PLANS_PN80773_VOL2.pdf | ||
| AMD0001_PLANS_PN80773_V1.pdf | ||
| Amendment_0001_-_PN_80773.pdf | ||
| AMD0001_PLANS_PN80773_V1_Caddfiles.zip | ZIP file | |
| AMD0001_PLANS_PN80773_V2.pdf | ||
| Site_Visit_Sign-In.pdf | ||
| ADV_PLANS_PN80773_Vol2.pdf | ||
| BR80773vol2.pdf | ||
| BR80773vol4-FF E.pdf | ||
| ADV_PLANS_PN80773_Vol1.pdf | ||
| BR80773vol1.pdf |
Show all 20
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFP No. W912PM-16-R-0020
SOF Battalion Operations Facility
PN: 80773
Fort Bragg, North Carolina
Specifications – Volume 3 of 4
July 2016
*IMPORTANT: THIS CONTRACT MUST COMPLY
WITH THE 2014 EDITION OF THE EM 385-1-1
SOF BATTALION OPERATIONS FACILITY PN80773
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
STANDARD FORM 1442
00 10 00 SOLICITATION, CONTRACT LINE ITEM NUMBER (CLIN) SCHEDULE
00 21 16 INSTRUCTIONS TO PROPOSERS
00 45 00 REPRESENTATIONS AND CERTIFICATIONS
00 70 00 CONDITIONS OF THE CONTRACT
00 73 00 SUPPLEMENTARY CONDITIONS
00 01 15 LIST OF DRAWINGS
DIVISION 01 - GENERAL REQUIREMENTS
01 10 00.10 38 SUPPLEMENTARY SPECIAL CONTRACT REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 00.10 10 QUALITY CONTROL SYSTEM (QCS)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 57 19.00 37 INDOOR AIR QUALITY (IAQ) MANAGEMENT
01 74 19.00 37 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 83 16.00 37 EXTERIOR ENCLOSURE PERFORMANCE REQUIREMENTS
01 91 00.00 37 COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
DIVISION 03 - CONCRETE
03 11 13.00 10 STRUCTURAL CAST-IN-PLACE CONCRETE FORMING
03 15 00.00 10 CONCRETE ACCESSORIES
03 20 00.00 10 CONCRETE REINFORCING
03 30 00.00 10 CAST-IN-PLACE CONCRETE
DIVISION 05 - METALS
05 05 23.16 STRUCTURAL WELDING
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 20 00 FINISH CARPENTRY
06 41 16.00 10 LAMINATE CLAD ARCHITECTURAL CASEWORK
06 61 16 SOLID POLYMER (SOLID SURFACING) FABRICATIONS
PROJECT TABLE OF CONTENTS Page 1
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 13 53 ELASTOMERIC SHEET WATERPROOFING
07 16 19 METALLIC OXIDE WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 27 FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR RETARDING
07 31 13 ASPHALT SHINGLES
07 54 19 POLYVINYL-CHLORIDE ROOFING
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 34 59 VAULT DOORS AND DAY GATES
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 06 90 COLOR SCHEDULE
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 24 23 STUCCO
09 29 00 GYPSUM BOARD
09 30 00 CERAMIC TILE, QUARRY TILE, AND PAVER TILE
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 68 00 CARPET
09 83 13 ACOUSTICAL WALL TREATMENT
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.20 INTERIOR SIGNAGE
10 14 01 EXTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 13 WIRE MESH PARTITIONS
10 22 39 FOLDING PANEL PARTITIONS
10 26 13 WALL AND CORNER GUARDS
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
10 51 13 METAL LOCKERS
DIVISION 11 - EQUIPMENT
11 05 40 COMMON WORK RESULTS FOR FOODSERVICE EQUIPMENT
11 47 00 ICE MACHINES
DIVISION 12 - FURNISHINGS
PROJECT TABLE OF CONTENTS Page 2
12 21 00 WINDOW BLINDS
12 48 13.13 ENTRANCE FLOOR MATS
DIVISION 13 - SPECIAL CONSTRUCTION
13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT
13 48 00.00 10 SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT
DIVISION 14 - CONVEYING EQUIPMENT
14 24 00 HYDRAULIC ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 05 15 COMMON PIPING FOR HVAC
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 23 LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER
BUILDING CONTROL SYSTEMS
23 11 25 FACILITY GAS PIPING
23 23 00 REFRIGERANT PIPING
23 25 00 CHEMICAL TREATMENT OF WATER FOR MECHANICAL SYSTEMS
23 52 00 HEATING BOILERS
23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 82 02.00 10 UNITARY HEATING AND COOLING EQUIPMENT
DIVISION 26 - ELECTRICAL
26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 41 00 LIGHTNING PROTECTION AND GROUNDING SYSTEM
26 42 14.00 10 CATHODIC PROTECTION SYSTEM (SACRIFICIAL ANODE)
26 51 00 INTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 14.00 10 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
27 05 29.00 10 PROTECTIVE DISTRIBUTION SYSTEM (PDS) FOR SIPRNET
COMMUNICATION SYSTEMS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 40 00 AUDIO VIDEO SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 16 01.00 10 SMALL INTRUSION DETECTION SYSTEM
28 20 01.00 10 ELECTRONIC SECURITY SYSTEM
PROJECT TABLE OF CONTENTS Page 3
28 23 23.00 10 CLOSED CIRCUIT TELEVISION SYSTEMS
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 11 00 CLEARING AND GRUBBING
31 31 16.13 CHEMICAL TERMITE CONTROL
31 32 11 SOIL SURFACE EROSION CONTROL
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 19 FIELD MOLDED SEALANTS FOR SEALING JOINTS IN RIGID
PAVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 16.16 BASE COURSE FOR RIGID AND SUBBASE COURSE FOR FLEXIBLE
PAVING
32 11 23 AGGREGATE AND/OR GRADED-CRUSHED AGGREGATE BASE COURSE
32 12 10 BITUMINOUS TACK AND PRIME COATS
32 12 17 HOT MIX BITUMINOUS PAVEMENT
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 16 13 CONCRETE SIDEWALKS AND CURBS AND GUTTERS
32 17 23.00 20 PAVEMENT MARKINGS
32 92 19 SEEDING
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
DIVISION 33 - UTILITIES
33 40 00 STORM DRAINAGE UTILITIES
33 51 15 NATURAL-GAS/LIQUID PETROLEUM GAS DISTRIBUTION
33 70 02.00 10 ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
APPENDICES
Appendix A TRAFFIC SIGNAL SPECIFICATIONS Appendix B AUDIOVISUAL ROOM DATA MATRIX Appendix C PERMITS AND PROCEDURES Appendix D RECORD OF ENVIRONMENTAL CONSIDERATION
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
SOF BATTALION OPERATIONS FACILITY BR80773
Ft. Bragg, NC
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 05 48.00 10
SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
10/07
PART 1 GENERAL
1.1 REFERENCES
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
1.2.2 Electrical Equipment
1.2.3 Electrical Systems
1.2.4 Contractor Designed Bracing
1.2.5 Conduits Requiring No Special Seismic Restraints
1.3 EQUIPMENT REQUIREMENTS
1.3.1 Rigidly Mounted Equipment
1.4 SUBMITTALS
PART 2 PRODUCTS
2.1 LIGHTING FIXTURE SUPPORTS
2.2 SWAY BRACING MATERIALS
PART 3 EXECUTION
3.1 SWAY BRACES FOR CONDUIT
3.2 LIGHTING FIXTURES IN BUILDINGS
3.2.1 Pendant Fixtures
3.2.2 Ceiling Attached Fixtures
3.2.2.1 Recessed Fluorescent Fixtures
3.2.2.2 Surface-Mounted Fluorescent Fixtures
3.2.3 Assembly Mounted on Outlet Box
3.2.4 Wall-Mounted Emergency Light Unit
3.2.5 Lateral Force
-- End of Section Table of Contents --
SECTION 26 05 48.00 10 Page 1
SECTION 26 05 48.00 10
SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
10/07
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 325 (2011) Steel Construction Manual
ASTM INTERNATIONAL (ASTM)
ASTM E580/E580M (2014) Application of Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels in Areas Requiring Moderate Seismic Restraint
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-310-04 (2013) Seismic Design for Buildings
UNDERWRITERS LABORATORIES (UL)
UL 1598 (2008; Reprint Oct 2012) Luminaires
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
The requirements for seismic protection measures described in this section shall be applied to the electrical equipment and systems listed below.
Structural requirements shall be in accordance with Section 13 48 00
SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT.
1.2.2 Electrical Equipment
Electrical equipment shall include the following items to the extent required on the drawings or in other sections of these specifications:
Control Panels Air Handling Units
Pumps with Motors
Light Fixtures
Motor Control Centers Transformers
SECTION 26 05 48.00 10 Page 2
Switchboards (Floor Mounted) Storage Racks
Solar Heating Units
1.2.3 Electrical Systems
The following electrical systems shall be installed as required on the drawings and other sections of these specifications and shall be seismically protected in accordance with this specification.
1.2.4 Contractor Designed Bracing
Submit copies of the Design Calculations with the Drawings. Calculations shall be approved, certified, stamped and signed by a Registered Professional Engineer. Calculations shall verify the capability of structural members to which bracing is attached for carrying the load from the brace. Design the bracing in accordance with UFC 3-310-04 and additional data furnished by the Contracting Officer. Resistance to lateral forces induced by earthquakes shall be accomplished without consideration of friction resulting from gravity loads. UFC 3-310-04 uses parameters for the building, not for the equipment in the building;
therefore, corresponding adjustments to the formulas shall be required.
Loadings determined using UFC 3-310-04 are based on strength design;
therefore, AISC 325 shall be used for the design.
1.2.5 Conduits Requiring No Special Seismic Restraints
Seismic restraints may be omitted from electrical conduit less than 2-1/2 inches trade size . All other interior conduit, shall be seismically protected as specified.
1.3 EQUIPMENT REQUIREMENTS
Submit detail drawings along with catalog cuts, templates, and erection and installation details, as appropriate, for the items listed. Submittals shall be complete in detail, indicating thickness, type, grade, class of metal, and dimensions; and shall show construction details, reinforcement, anchorage, and installation with relation to the building construction.
Submit copies of the design calculations with the detail drawings.
Calculations shall be stamped by a registered engineer and shall verify the capability of structural members to which bracing is attached for carrying the load from the brace.
1.3.1 Rigidly Mounted Equipment
The following specific items of equipment to be furnished under this contract shall be constructed and assembled to withstand the seismic forces specified in UFC 3-310-04. Each item of rigid electrical equipment shall be entirely located and rigidly attached on one side only of a building expansion joint. Piping, electrical conduit, etc., which cross the expansion joint shall be provided with flexible joints that are capable of accommodating displacements equal to the full width of the joint in both orthogonal directions.
Transformers Switch Boards and Switch Gears Free Standing Electric Motors
SECTION 26 05 48.00 10 Page 3
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Lighting Fixtures in Buildings Equipment Requirements
SD-03 Product Data
Lighting Fixtures in Buildings G, RO Equipment Requirements G, RO Contractor Designed Bracing G, RO
PART 2 PRODUCTS
2.1 LIGHTING FIXTURE SUPPORTS
Lighting fixtures and supports shall conform to UL 1598.
2.2 SWAY BRACING MATERIALS
Sway bracing materials (e.g. rods, plates, rope, angles, etc.) shall be as specified in Section 13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS
EQUIPMENT.
PART 3 EXECUTION
3.1 SWAY BRACES FOR CONDUIT
Conduit shall be braced as for an equivalent weight pipe in accordance with Section 13 48 00.00 10 SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT.
3.2 LIGHTING FIXTURES IN BUILDINGS
Lighting fixtures and supports shall conform to the following:
3.2.1 Pendant Fixtures
Pendant fixtures shall conform to the requirements of UFC 3-310-04.
3.2.2 Ceiling Attached Fixtures
3.2.2.1 Recessed Fluorescent Fixtures
Recessed fluorescent individual or continuous-row mounted fixtures shall be supported by a seismic-resistant suspended ceiling support system built in accordance with ASTM E580/E580M and Section 09 51 00 ACOUSTICAL CEILINGS.
Seismic protection for the fixtures shall conform to the requirements of UFC 3-310-04. Recessed lighting fixtures not over 56 pounds in weight may be supported by and attached directly to the ceiling system runners using screws or bolts, number and size as required by the seismic design.
Fixture accessories, including louvers, diffusers, and lenses shall have
SECTION 26 05 48.00 10 Page 4 lock or screw attachments.
3.2.2.2 Surface-Mounted Fluorescent Fixtures
Surface-mounted fluorescent individual or continuous-row fixtures shall be attached to a seismic-resistant ceiling support system built in accordance with ASTM E580/E580MSection 09 51 00 ACOUSTICAL CEILINGS. Seismic protection for the fixtures shall conform to the requirements of
UFC 3-310-04.
3.2.3 Assembly Mounted on Outlet Box
A supporting assembly, that is intended to be mounted on an outlet box, shall be designed to accommodate mounting features on 4 inch boxes, plaster rings, and fixture studs.
3.2.4 Wall-Mounted Emergency Light Unit
Attachments for wall-mounted emergency light units shall be designed and secured for the worst expected seismic disturbance at the site.
3.2.5 Lateral Force
Structural requirements for light fixture bracing shall be in accordance with Section 13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT.
-- End of Section --
SECTION 26 05 48.00 10 Page 5
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
02/14
PART 1 GENERAL
1.1 REFERENCES
1.2 DEFINITIONS
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Fuses
1.4.2 Regulatory Requirements
1.4.3 Standard Products
1.4.3.1 Alternative Qualifications
1.4.3.2 Material and Equipment Manufacturing Date
1.5 MAINTENANCE
1.5.1 Electrical Systems
1.6 WARRANTY
1.7 SUSTAINABILITY REQUIREMENTS
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.2 CONDUIT AND FITTINGS
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
2.2.1.2 Rigid Aluminum Conduit
2.2.2 Rigid Nonmetallic Conduit
2.2.3 Intermediate Metal Conduit (IMC)
2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
2.2.5 Plastic-Coated Rigid Steel and IMC Conduit
2.2.6 Flexible Metal Conduit
2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
2.2.7.1 Fittings for Rigid Metal Conduit and IMC
2.2.7.2 Fittings for EMT
2.2.8 Fittings for Rigid Nonmetallic Conduit
2.2.9 Liquid-Tight Flexible Nonmetallic Conduit
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
2.4 CABLE TRAYS
2.4.1 Basket-Type Cable Trays
2.4.2 Ladder-Type Cable Trays/Cable Runways
2.5 OUTLET BOXES AND COVERS
2.5.1 Floor Outlet Boxes
2.5.2 Outlet Boxes for Telecommunications System
2.6 CABINETS, JUNCTION BOXES, AND PULL BOXES
2.7 WIRES AND CABLES
2.7.1 Conductors
2.7.1.1 Equipment Manufacturer Requirements
SECTION 26 20 00 Page 1
2.7.1.2 Aluminum Conductors
2.7.1.3 Minimum Conductor Sizes
2.7.2 Color Coding
2.7.2.1 Ground and Neutral Conductors
2.7.2.2 Ungrounded Conductors
2.7.3 Insulation
2.7.4 Bonding Conductors
2.7.4.1 Telecommunications and Security Bonding Backbone (TBB)
2.7.4.2 Bonding Conductor for Telecommunications and Security
2.7.5 Service Entrance Cables
2.7.6 Cable Tray Cable or Power Limited Tray Cable
2.7.7 Cord Sets and Power-Supply Cords
2.8 SPLICES AND TERMINATION COMPONENTS
2.9 DEVICE PLATES
2.10 SWITCHES
2.10.1 Toggle Switches
2.10.2 Switch with Red Pilot Handle
2.10.3 Breakers Used as Switches
2.10.4 Disconnect Switches
2.11 FUSES
2.11.1 Fuseholders
2.11.2 Cartridge Fuses, Current Limiting Type (Class R)
2.11.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting
Type (Classes J, L, and CC)
2.11.4 Cartridge Fuses, Current Limiting Type (Class T)
2.12 RECEPTACLES
2.12.1 Switched Duplex Receptacles
2.12.2 Weatherproof Receptacles
2.12.3 Ground-Fault Circuit Interrupter Receptacles
2.12.4 Special Purpose Receptacles
2.12.5 Plugs
2.13 PANELBOARDS
2.13.1 Enclosure
2.13.2 Panelboard Buses
2.13.2.1 Panelboard Neutrals for Non-Linear Loads
2.13.3 Circuit Breakers
2.13.3.1 Multipole Breakers
2.13.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter
2.13.3.3 Circuit Breakers for HVAC Equipment
2.14 ENCLOSED CIRCUIT BREAKERS
2.15 MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)
2.16 TRANSFORMERS
2.16.1 Specified Transformer Efficiency
2.16.2 Transformers With Non-Linear Loads
2.17 MOTORS
2.17.1 High Efficiency Single-Phase Motors
2.17.2 Premium Efficiency Polyphase Motors
2.17.3 Motor Sizes
2.17.4 Wiring and Conduit
2.18 MOTOR CONTROLLERS
2.18.1 Control Wiring
2.18.2 Control Circuit Terminal Blocks
2.18.3 Types of Terminal Blocks
2.18.4 Control Circuits
2.18.5 Enclosures for Motor Controllers
2.18.6 Multiple-Speed Motor Controllers and Reversible Motor
Controllers
2.18.7 Pushbutton Stations
2.18.8 Pilot and Indicating Lights
SECTION 26 20 00 Page 2
2.19 MANUAL MOTOR STARTERS (MOTOR RATED SWITCHES)
2.20 LOCKOUT REQUIREMENTS
2.21 TELECOMMUNICATIONS SYSTEM
2.22 CABLE TELEVISION (CATV) SYSTEM
2.22.1 CATV Outlets
2.22.2 CATV Faceplates
2.22.3 Backboards
2.23 GROUNDING AND BONDING EQUIPMENT
2.23.1 Ground Rods
2.23.2 Ground Bus
2.23.3 Telecommunications Security and CATV Grounding Busbar
2.24 MANUFACTURER'S NAMEPLATE
2.25 FIELD FABRICATED NAMEPLATES
2.26 WARNING SIGNS
2.27 FIRESTOPPING MATERIALS
2.28 WIREWAYS
2.29 METERING
2.30 SURGE PROTECTIVE DEVICES
2.31 FACTORY APPLIED FINISH
2.32 TRANSFORMER FACTORY TESTS
2.33 COORDINATED POWER SYSTEM PROTECTION
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Underground Service
3.1.2 Service Entrance Identification
3.1.2.1 Labels
3.1.3 Wiring Methods
3.1.3.1 Pull Wire
3.1.3.2 Flat Conductor Cable
3.1.4 Conduit Installation
3.1.4.1 Restrictions Applicable to EMT
3.1.4.2 Restrictions Applicable to Nonmetallic Conduit
3.1.4.3 Restrictions Applicable to Flexible Conduit
3.1.4.4 Underground Conduit
3.1.4.5 Conduit for Circuits Rated Greater Than 600 Volts
3.1.4.6 Conduit Installed Under Floor Slabs
3.1.4.7 Conduit Through Floor Slabs
3.1.4.8 Conduit Installed in Concrete Floor Slabs
3.1.4.9 Stub-Ups
3.1.4.10 Conduit Support
3.1.4.11 Directional Changes in Conduit Runs
3.1.4.12 Locknuts and Bushings
3.1.4.13 Flexible Connections
3.1.4.14 Telecommunications and Signal System Pathway
3.1.4.15 Cable Television (CATV) System Conduits
3.1.5 Cable Tray Installation
3.1.6 Boxes, Outlets, and Supports
3.1.6.1 Boxes
3.1.6.2 Pull Boxes
3.1.6.3 Extension Rings
3.1.7 Mounting Heights
3.1.8 Conductor Identification
3.1.8.1 Marking Strips
3.1.9 Splices
3.1.9.1 Splices of Aluminum Conductors
3.1.10 Terminating Aluminum Conductors
3.1.10.1 Termination to Copper Bus
SECTION 26 20 00 Page 3
3.1.10.2 Termination to Aluminum Bus
3.1.11 Covers and Device Plates
3.1.12 Electrical Penetrations
3.1.13 Grounding and Bonding
3.1.13.1 Ground Rods
3.1.13.2 Grounding Connections
3.1.13.3 Ground Bus
3.1.13.4 Resistance
3.1.13.5 Telecommunications System
3.1.14 Equipment Connections
3.1.15 Elevator
3.1.16 Government-Furnished Equipment
3.1.17 Watthour Meters
3.1.18 Surge Protective Devices
3.2 FIELD FABRICATED NAMEPLATE MOUNTING
3.3 WARNING SIGN MOUNTING
3.4 FIELD APPLIED PAINTING
3.5 FIELD QUALITY CONTROL
3.5.1 Devices Subject to Manual Operation
3.5.2 600-Volt Wiring Test
3.5.3 Transformer Tests
3.5.4 Ground-Fault Receptacle Test
3.5.5 Grounding System Test
3.5.6 Watthour Meter
-- End of Section Table of Contents --
SECTION 26 20 00 Page 4
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
02/14
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire
ASTM B8 (2011) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D709 (2013) Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2012; Errata 1 2012; INT 1-4 2012; Errata
2 2013; INT 5-7 2013; INT 8-10 2014; INT
11 2015) National Electrical Safety Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C12.1 (2008) Electric Meters Code for Electricity Metering
ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)
ANSI C80.3 (2005) American National Standard for Electrical Metallic Tubing (EMT)
ANSI C80.5 (2005) American National Standard for Electrical Rigid Aluminum Conduit
NEMA 250 (2014) Enclosures for Electrical Equipment
SECTION 26 20 00 Page 5
(1000 Volts Maximum)
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Standard for Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 4 (2015) Terminal Blocks
NEMA ICS 6 (1993; R 2011) Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2014) Motors and Generators
NEMA MG 10 (2013) Energy Management Guide for Selection and Use of Fixed Frequency Medium AC Squirrel-Cage Polyphase Induction Motors
NEMA MG 11 (1977; R 2012) Energy Management Guide for Selection and Use of Single Phase Motors
NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (1992; R 1997) Standard for Dry-Type Transformers for General Applications
NEMA TC 2 (2013) Standard for Electrical Polyvinyl Chloride (PVC) Conduit
NEMA TC 3 (2015) Standard for Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing
NEMA TP 1 (2002) Guide for Determining Energy Efficiency for Distribution Transformers
NEMA VE 1 (2009) Standard for Metal Cable Tray Systems
NEMA VE 2 (2013) Cable Tray Installation Guidelines
NEMA WD 1 (1999; R 2005; R 2010) Standard for General Color Requirements for Wiring Devices
NEMA WD 6 (2012) Wiring Devices Dimensions Specifications
NEMA Z535.4 (2011) American National Standard for
SECTION 26 20 00 Page 6
Product Safety Signs and Labels
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code
NFPA 70E (2015; ERTA 1 2015) Standard for Electrical Safety in the Workplace
NFPA 780 (2014) Standard for the Installation of Lightning Protection Systems
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.1 (2009; Add 2 2011; Add 1 2012) Commercial Building Telecommunications Cabling Standard
TIA-569 (2015d) Commercial Building Standard for Telecommunications Pathways and Spaces
TIA-607 (2011b) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. ARMY (DA)
Bragg NEC IDC (2014) Installation Design Criteria (IDC) For Fort Bragg Specific Communications Infrastructure Requirements
U.S. ARMY INFORMATION SYSTEMS ENGINEERING COMMAND (USAISEC)
TC I3A (2012) Technical Criteria for the Installation Information Infrastructure Architecture
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.147 Control of Hazardous Energy (Lock Out/Tag Out)
UNDERWRITERS LABORATORIES (UL)
UL 1 (2005; Reprint Jul 2012) Standard for Flexible Metal Conduit
UL 1063 (2006; Reprint Jul 2012) Machine-Tool Wires and Cables
UL 1242 (2006; Reprint Mar 2014) Standard for Electrical Intermediate Metal Conduit -- Steel
UL 1283 (2015) Electromagnetic Interference Filters
SECTION 26 20 00 Page 7
UL 1449 (2014;Reprint Mar 2015) Surge Protective Devices
UL 1561 (2011; Reprint Jun 2015) Dry-Type General Purpose and Power Transformers
UL 1660 (2014) Liquid-Tight Flexible Nonmetallic Conduit
UL 198M (2003; Reprint Feb 2013) Standard for Mine-Duty Fuses
UL 20 (2010; Reprint Feb 2012) General-Use Snap Switches
UL 360 (2013; Reprint Jan 2015) Liquid-Tight Flexible Steel Conduit
UL 4248-1 (2007; Reprint Oct 2013) UL Standard for Safety Fuseholders - Part 1: General Requirements
UL 4248-12 (2007; Reprint Dec 2012) UL Standard for Safety Fuseholders - Part 12: Class R
UL 44 (2014; Reprint Feb 2015) Thermoset-Insulated Wires and Cables
UL 467 (2007) Grounding and Bonding Equipment
UL 486A-486B (2013; Reprint Feb 2014) Wire Connectors
UL 486C (2013; Reprint Feb 2014) Splicing Wire Connectors
UL 489 (2013; Reprint Mar 2014) Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures
UL 498 (2012; Reprint Oct 2014) Attachment Plugs and Receptacles
UL 5 (2011) Surface Metal Raceways and Fittings
UL 50 (2007; Reprint Apr 2012) Enclosures for Electrical Equipment, Non-environmental Considerations
UL 506 (2008; Reprint Oct 2013) Specialty Transformers
UL 508 (1999; Reprint Oct 2013) Industrial Control Equipment
UL 510 (2005; Reprint Jul 2013) Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape
UL 514A (2013) Metallic Outlet Boxes
SECTION 26 20 00 Page 8
UL 514B (2012; Reprint Nov 2014) Conduit, Tubing and Cable Fittings
UL 514C (2014; Reprint Dec 2014) Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers
UL 6 (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit-Steel
UL 651 (2011; Reprint May 2014) Standard for Schedule 40 and 80 Rigid PVC Conduit and Fittings
UL 67 (2009; Reprint Apr 2015) Standard for Panelboards
UL 6A (2008; Reprint Nov 2014) Electrical Rigid Metal Conduit - Aluminum, Red Brass, and Stainless Steel
UL 797 (2007; Reprint Dec 2012) Electrical Metallic Tubing -- Steel
UL 817 (2015) Standard for Cord Sets and Power-Supply Cords
UL 83 (2014) Thermoplastic-Insulated Wires and Cables
UL 854 (2004; Reprint Nov 2014) Standard for Service-Entrance Cables
UL 869A (2006) Reference Standard for Service Equipment
UL 870 (2008; Reprint Feb 2013) Standard for Wireways, Auxiliary Gutters, and Associated Fittings
UL 943 (2006; Reprint Jun 2012) Ground-Fault Circuit-Interrupters
UL 984 (1996; Reprint Sep 2005) Hermetic Refrigerant Motor-Compressors
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in
SECTION 26 20 00 Page 9 accordance with Section 01 33 00.
SD-02 Shop Drawings
Panelboards; G, RO
Transformers; G, RO
Cable trays; G, RO
Wireways; G, RO
Marking strips drawings; G, RO
SD-03 Product Data
Receptacles; G, RO
Circuit breakers; G, RO
Switches; G, RO
Transformers; G, RO
Enclosed circuit breakers; G, RO
Motor controllers; G, RO
Manual motor starters; G, RO
Metering; G, RO
CATV outlets; G, RO
Telecommunications Grounding Busbar; G, RO
Surge protective devices; G, RO
Include performance and characteristic curves.
LEED product data
SD-06 Test Reports
600-volt wiring test; G, RO
Grounding system test; G, RO
Transformer tests; G, RO
Ground-fault receptacle test; G, RO
SD-07 Certificates
Fuses; G, RO
SD-09 Manufacturer's Field Reports
Transformer factory tests
SECTION 26 20 00 Page 10
SD-10 Operation and Maintenance Data
Electrical Systems, Data Package 5; G, RO
Metering, Data Package 3 G, RO
1.4 QUALITY ASSURANCE
1.4.1 Fuses
Submit coordination data as specified in paragraph, FUSES of this section.
1.4.2 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" or "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.4.3 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.3.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.3.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site are not acceptable.
1.5 MAINTENANCE
1.5.1 Electrical Systems
Submit operation and maintenance manuals for electrical systems that
SECTION 26 20 00 Page 11 provide basic data relating to the design, operation, and maintenance of the electrical distribution system for the building. Include the following:
a. Single line diagram of the "as-built" building electrical system.
b. Schematic diagram of electrical control system (other than HVAC, covered elsewhere).
c. Manufacturers' operating and maintenance manuals on active electrical equipment.
1.6 WARRANTY
Provide equipment items supported by service organizations that are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.7 SUSTAINABILITY REQUIREMENTS
See Section 01 33 29 SUSTAINABILITY for equipment energy efficiency requirements and submittals. Comply for all energy using equipment specified in this section.
All composite wood products shall meet LEED low-emitting materials requirements. See Section 01 33 29 SUSTAINABILITY for detailed requirements. Submit LEED product data for all applicable and contributing materials.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
As a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70 for all materials, equipment, and devices.
2.2 CONDUIT AND FITTINGS
All conduits shall have bushings installed. All NIPR conduits shall be marked with green tape every 8 feet and all SIPR conduits shall be marked with red tape every 8 feet. Conform to the following:
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
ANSI C80.1, UL 6.
2.2.1.2 Rigid Aluminum Conduit
ANSI C80.5, UL 6A.
2.2.2 Rigid Nonmetallic Conduit
PVC Type EPC-40 in accordance with NEMA TC 2,UL 651
SECTION 26 20 00 Page 12
2.2.3 Intermediate Metal Conduit (IMC)
UL 1242, zinc-coated steel only.
2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
UL 797, ANSI C80.3.
2.2.5 Plastic-Coated Rigid Steel and IMC Conduit
NEMA RN 1, Type 40( 40 mils thick).
2.2.6 Flexible Metal Conduit
UL 1.
2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel
UL 360.
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
UL 514B. Ferrous fittings: cadmium- or zinc-coated in accordance with
UL 514B.
2.2.7.1 Fittings for Rigid Metal Conduit and IMC
Threaded-type. Split couplings unacceptable.
2.2.7.2 Fittings for EMT
Steelcompression type.
2.2.8 Fittings for Rigid Nonmetallic Conduit
NEMA TC 3 for PVC, and UL 514B.
2.2.9 Liquid-Tight Flexible Nonmetallic Conduit
UL 1660.
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
UL 5, two-piece aluminum, totally enclosed, snap-cover type.
2.4 CABLE TRAYS
NEMA VE 1. Cable trays shall form a wireway system and shall be of nominal width and depth as indicated on the drawings. Cable trays shall be constructed of steel that has been zinc-coated after fabrication. Trays shall include splice and end plates, dropouts, and miscellaneous hardware.
Edges, fittings, and hardware shall be finished free from burrs and sharp edges. Fittings shall have not less than load-carrying ability of straight tray sections and shall have manufacturer's minimum standard radius.
Radius of bends shall be 36 inches.
SECTION 26 20 00 Page 13
2.4.1 Basket-Type Cable Trays
Provide size as indicated with maximum wire mesh spacing of 2 by 4 inch.
2.4.2 Ladder-Type Cable Trays/Cable Runways
Provide size as indicated with maximum rung spacing of 12 inches.
2.5 OUTLET BOXES AND COVERS
UL 514A, cadmium- or zinc-coated, if ferrous metal. UL 514C, if nonmetallic.
2.5.1 Floor Outlet Boxes
Provide the following:
a. Boxes: fully adjustable before and after pour, concrete tight, with a series of device mounting plates that will accept both duplex power devices, as well as plates that will accept voice, data and AV connectivity outlets and modular inserts, and other open system devices.
b. Each outlet: consisting of cast-metal body with threaded openings, or sheet-steel body with knockouts for conduits, adjustable, and cover plate with threaded plug.
c. Telecommunications outlets: consisting of flush, aluminum or stainless steel housing with a receptacle as specified and 3/4 inch top opening.
d. Receptacle outlets: consisting of flush aluminum or stainless steel housing with duplex-type receptacle as specified herein.
e. Activation covers: manufactured of die-cast aluminum or die-cast zinc, in a plated brass finish, available in a flanged version for carpeted floors and a flangeless version for tile floors. Covers shall be available with options for tile or carpet inserts, flush covers.
f. Provide gaskets where necessary to ensure watertight installation.
2.5.2 Outlet Boxes for Telecommunications System
Provide the following:
a. Standard type 4 11/16 inches square by 2 1/8 inches deep.
b. Outlet boxes for wall-mounted telecommunications outlets: 4 by 2 1/8 by 2 1/8 inches deep.
c. Depth of boxes: large enough to allow manufacturers' recommended conductor bend radii.
d. Outlet boxes for fiber optic telecommunication outlets: include a minimum 3/8 inch deep single or two gang plaster ring as shown and installed using a minimum 1 inch conduit system. All conduit terminations shall include bushings.
2.6 CABINETS, JUNCTION BOXES, AND PULL BOXES
Volume greater than 100 cubic inches, UL 50, hot-dip, zinc-coated, if sheet
SECTION 26 20 00 Page 14 steel.
2.7 WIRES AND CABLES
Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 12 months prior to date of delivery to site.
2.7.1 Conductors
Provide the following:
a. Conductor sizes and capacities shown are based on copper, unless indicated otherwise.
b. Conductors No. 8 AWG and larger diameter: stranded.
c. Conductors No. 10 AWG and smaller diameter: solid.
d. Conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3: stranded unless specifically indicated otherwise.
Conductors indicated to be No. 6 AWG or smaller diameter: copper.
Conductors indicated to be No. 4 AWG and larger diameter: either copper or aluminum, unless type of conductor material is specifically indicated, or specified, or required by equipment manufacturer.
2.7.1.1 Equipment Manufacturer Requirements
When manufacturer's equipment requires copper conductors at the terminations or requires copper conductors to be provided between components of equipment, provide copper conductors or splices, splice boxes, and other work required to satisfy manufacturer's requirements.
2.7.1.2 Aluminum Conductors
Provide aluminum conductors of AA-8000 series electrical grade aluminum alloy conductors. Type EC/1350 aluminum is not acceptable. If Contractor choosees to provide aluminum for conductors No. 4 AWG and larger diameter, Contractor is responsible for increasing conductor size to have same ampacity as copper size indicated; increasing conduit and pull box sizes to accommodate larger size aluminum conductors in accordance with NFPA 70;
ensuring that pulling tension rating of aluminum conductor is sufficient;
providing panelboards that are UL listed for use with aluminum, and so labeled; relocating equipment, modifying equipment terminations, resizing equipment; and resolving problems that are direct results of providing aluminum conductors in lieu of copper.
2.7.1.3 Minimum Conductor Sizes
Provide minimum conductor size in accordance with the following:
a. Branch circuits: No. 12 AWG.
b. Class 1 remote-control and signal circuits: No. 14 AWG.
c. Class 2 low-energy, remote-control and signal circuits: No. 16 AWG.
SECTION 26 20 00 Page 15
d. Class 3 low-energy, remote-control, alarm and signal circuits: No. 22
AWG.
2.7.2 Color Coding
Provide factory color coding for service, feeder, branch, control, and signaling circuit conductors.
2.7.2.1 Ground and Neutral Conductors
Provide factory color coding of ground and neutral conductors as follows:
a. Grounding conductors: Green.
b. Neutral conductors: White.
c. Exception, where neutrals of more than one system are installed in same raceway or box, other neutrals color coding: white with a different colored (not green) stripe for each.
2.7.2.2 Ungrounded Conductors
Provide factory color coding of ungrounded conductors in different voltage systems as follows:
a. 208/120 volt, three-phase
(1) Phase A - black
(2) Phase B - red
(3) Phase C - blue
b. 480/277 volt, three-phase
(1) Phase A - brown
(2) Phase B - orange
(3) Phase C - yellow
c. 120/240 volt, single phase: Black and red
2.7.3 Insulation
Unless specified or indicated otherwise or required by NFPA 70, provide power and lighting wires rated for 600-volts, Type THWN/THHN conforming to UL 83, except that grounding wire may be type TW conforming to UL 83;
remote-control and signal circuits: Type TW or TF, conforming to UL 83.
Where lighting fixtures require 90-degree Centigrade (C) conductors, provide only conductors with 90-degree C insulation or better.
2.7.4 Bonding Conductors
ASTM B1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;
ASTM B8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter.
SECTION 26 20 00 Page 16
2.7.4.1 Telecommunications and Security Bonding Backbone (TBB)
Provide a copper conductor TBB in accordance with TIA-607 with No. 6 AWG minimum size, and sized at 2 kcmil per linear foot of conductor length up to a maximum size of 750 MCM. Provide insulated TBB with insulation as specified in the paragraph INSULATION and meeting the fire ratings of its pathway.
2.7.4.2 Bonding Conductor for Telecommunications and Security
Provide a copper conductor Bonding Conductor for Telecommunications between the telecommunications main grounding busbar (TMGB) and the electrical service ground in accordance with TIA-607. Size the bonding conductor for telecommunications the same as the TBB.
2.7.5 Service Entrance Cables
Service Entrance (SE) and Underground Service Entrance (USE) Cables, UL 854.
2.7.6 Cable Tray Cable or Power Limited Tray Cable
UL listed; type TC or PLTC.
2.7.7 Cord Sets and Power-Supply Cords
UL 817.
2.8 SPLICES AND TERMINATION COMPONENTS
UL 486A-486B for wire connectors and UL 510 for insulating tapes.
Connectors for No. 10 AWG and smaller diameter wires: insulated, pressure-type in accordance with UL 486A-486B or UL 486C (twist-on splicing connector). Provide solderless terminal lugs on stranded conductors.
2.9 DEVICE PLATES
Provide the following:
a. UL listed, one-piece device plates for outlets to suit the devices installed.
b. For metal outlet boxes, plates on unfinished walls: zinc-coated sheet steel or cast metal having round or beveled edges.
c. For nonmetallic boxes and fittings on unfinished walls, other suitable plates may be provided.
e. Plates on finished walls: satin finish stainless steel or brushed-finish aluminum, minimum 0.03 inch thick.
f. Screws: machine-type with countersunk heads in color to match finish of plate.
g. Sectional type device plates are not be permitted.
h. Plates installed in wet locations: gasketed and UL listed for "wet locations."
SECTION 26 20 00 Page 17
2.10 SWITCHES
2.10.1 Toggle Switches
NEMA WD 1, UL 20, single pole, double pole, three-way, and four-way, totally enclosed with bodies of thermoplastic or thermoset plastic and mounting strap with grounding screw. Include the following:
a. Handles: white thermoplastic.
b. Wiring terminals: screw-type, side-wired.
c. Contacts: silver-cadmium and contact arm - one-piece copper alloy.
d. Switches: rated quiet-type ac only, 120/277 volts, with current rating and number of poles indicated.
2.10.2 Switch with Red Pilot Handle
NEMA WD 1. Provide the following:
a. Pilot lights that are integrally constructed as a part of the switch's handle.
b. Pilot light color: red and illuminate whenever the switch is closed or "on".
c. Pilot lighted switch: rated 20 amps and 120 volts or 277 volts as indicated.
d. The circuit's neutral conductor to each switch with a pilot light.
2.10.3 Breakers Used as Switches
For 120- and 277-Volt fluorescent fixtures, mark breakers "SWD" in accordance with UL 489.
2.10.4 Disconnect Switches
NEMA KS 1. Provide heavy duty-type switches. Utilize Class R fuseholders and fuses for fused switches, unless indicated otherwise. Provide horsepower rated for switches serving as the motor-disconnect means.
Provide switches in NEMA 1 , enclosure or as indicated per NEMA ICS 6.
2.11 FUSES
NEMA FU 1. Provide complete set of fuses for each fusible switch.
Coordinate time-current characteristics curves of fuses serving motors or connected in series with circuit breakers or other circuit protective devices for proper operation. Submit coordination data for approval.
Provide fuses with a voltage rating not less than circuit voltage.
2.11.1 Fuseholders
Provide in accordance with UL 4248-1.
2.11.2 Cartridge Fuses, Current Limiting Type (Class R)
UL 198M, Class RK-5 time-delay type. Provide only Class R associated
SECTION 26 20 00 Page 18 fuseholders in accordance with UL 4248-12.
2.11.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting Type (Classes J, L, and CC)
UL 198M, Class J for zero to 600 amperes, Class L for 601 to 6,000 amperes, and Class CC for zero to 30 amperes.
2.11.4 Cartridge Fuses, Current Limiting Type (Class T)
UL 198M, Class T for zero to 1,200 amperes, 300 volts; and zero to 800 amperes, 600 volts.
2.12 RECEPTACLES
Provide the following:
a. UL 498, hard use (also designated heavy-duty), grounding-type.
b. Ratings and configurations: as indicated.
c. Bodies: white as per NEMA WD 1.
d. Face and body: thermoplastic supported on a metal mounting strap.
e. Dimensional requirements: per NEMA WD 6.
f. Screw-type, side-wired wiring terminals or of the solderless pressure type having suitable conductor-release arrangement.
g. Grounding pole connected to mounting strap.
h. The receptacle: containing triple-wipe power contacts and double or triple-wipe ground contacts.
2.12.1 Switched Duplex Receptacles
Provide separate terminals for each ungrounded pole. Top receptacle:
switched when installed.
2.12.2 Weatherproof Receptacles
Provide receptacles, UL listed for use in "wet locations". Include recessed cast metal box with gasketed, hinged, lockable and weatherproof while-in-use, polycarbonate, UV resistant/stabilized cover plate.
2.12.3 Ground-Fault Circuit Interrupter Receptacles
UL 943, duplex type for mounting in standard outlet box. Provide device capable of detecting current leak of 6 milliamperes or greater and tripping per requirements of UL 943 for Class A ground-fault circuit interrupter devices. Provide screw-type, side-wired wiring terminals or pre-wired (pigtail) leads.
2.12.4 Special Purpose Receptacles
Receptacles serving indicated areas are special purpose. Provide in ratings indicated.
SECTION 26 20 00 Page 19
2.12.5 Plugs
Provide heavy-duty, rubber-covered three-, four-, or five-wire cord of required size, install plugs thereon, and attach to equipment. Provide UL listed plugs with receptacles, complete with grounding blades. Where equipment is not available, turn over plugs and cord assemblies to the Government.
2.13 PANELBOARDS
Provide panelboards in accordance with the following:
a. UL 67 and UL 50 having a short-circuit current rating as indicated.
b. Panelboards for use as service disconnecting means: additionally conform to UL 869A.
c. Panelboards: circuit breaker-equipped.
d. Designed such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL.
e. "Specific breaker placement" is required in panelboards to match the breaker placement indicated in the panelboard schedule on the drawings.
f. Use of "Subfeed Breakers" is not acceptable unless specifically indicated otherwise.
g. Main breaker: "separately" mounted "above" branch breakers.
h. Where "space only" is indicated, make provisions for future installation of breakers.
i. Directories: indicate load served by each circuit in panelboard.
j. Directories: indicate source of service to panelboard (e.g., Panel PA served from Panel MDP).
l. Type directories and mount in holder behind transparent protective covering.
m. Panelboards: listed and labeled for their intended use.
n. Panelboard nameplates: provided in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
2.13.1 Enclosure
Provide panelboard enclosure in accordance with the following:
a. UL 50.
b. Cabinets mounted outdoors or flush-mounted: hot-dipped galvanized after fabrication.
c. Cabinets: painted in accordance with paragraph PAINTING.
d. Outdoor cabinets: NEMA 3R raintight with conduit hubs welded to the
SECTION 26 20 00 Page 20 cabinet.
e. Front edges of cabinets: form-flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front.
f. All cabinets: fabricated such that no part of any surface on the finished cabinet deviates from a true plane by more than 1/8 inch.
g. Holes: provided in the back of indoor surface-mounted cabinets, with outside spacers and inside stiffeners, for mounting the cabinets with a 1/2 inch clear space between the back of the cabinet and the wall surface.
h. Flush doors: mounted on hinges that expose only the hinge roll to view when the door is closed.
i. Each door: fitted with a combined catch and lock, except that doors over 24 inches long provided with a three-point latch having a knob with a T-handle, and a cylinder lock.
j. Keys: two provided with each lock, with all locks keyed alike.
k. Finished-head cap screws: provided for mounting the panelboard fronts on the cabinets.
2.13.2 Panelboard Buses
Support bus bars on bases independent of circuit breakers. Design main buses and back pans so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet
2.13.2.1 Panelboard Neutrals for Non-Linear Loads
Provide in accordance with the following:.
a. UL listed, with panelboard type specifically UL heat rise tested for use on non-linear loads.
b. Panelboard: heat rise tested in accordance with UL 67, except with the neutral assembly installed and carrying 200 percent of the phase bus current during testing.
c. Verification of the testing procedure: provided upon request.
d. Two neutral assemblies paralleled together with cable is not acceptable.
e. Nameplates for panelboard rated for use on non-linear loads: marked "SUITABLE FOR NON-LINEAR LOADS" and in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
f. Provide a neutral label with instructions for wiring the neutral of panelboards rated for use on non-linear loads.
SECTION 26 20 00 Page 21
2.13.3 Circuit Breakers
UL 489, thermal magnetic-type having a minimum short-circuit current rating equal to the short-circuit current rating of the panelboard in which the circuit breaker will be mounted. Breaker terminals: UL listed as suitable for type of conductor provided. Where indicated on the drawings, provide circuit breakers with shunt trip devices. Series rated circuit breakers and plug-in circuit breakers are unacceptable.
2.13.3.1 Multipole Breakers
Provide common trip-type with single operating handle. Design breaker such that overload in one pole automatically causes all poles to open. Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.
2.13.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter
UL 943 and NFPA 70. Provide with "push-to-test" button, visible indication of tripped condition, and ability to detect and trip on current imbalance of 6 milliamperes or greater per requirements of UL 943 for Class A ground-fault circuit interrupter.
2.13.3.3 Circuit Breakers for HVAC Equipment
Provide circuit breakers for HVAC equipment having motors (group or individual) marked for use with HACR type and UL listed as HACR type.
2.14 ENCLOSED CIRCUIT BREAKERS
UL…